Wiring check function confirms connection and displays ideal vector (at the
lower left corner) according to the selected wiring system, and shows con-
nection errors.
Wiring check
www.GlobalTestSupply.com
Demand change
Ideal vector
Power Quality
Event
Measures voltage swells / dips /
interruptions / transients and inrush
currents that may indicate a weak
power distribution system. Such
phenomena may damage or reset
devices. KEW 6315 can catch swells
/ dips / interruptions and inrush currents based on half cycle (10 ms @
50Hz or 8.3ms @ 60Hz) TRMS.
All necessary data is displayed by
●
Swell
Swell is a instantaneous voltage increase, most of the
time originated by upstream power line failure or switching OFF large
load or switching ON large capaci-tor.
pressing one key.
Windows software for data
KEW 6315
POWER QUALITY ANALYZER
analysis and setting via USB port
●
Automatic creation of graph and list from recorded data.
●
Uniform management of setting and recorded data acquired from multiple devices.
●
Data can be expressed in crude oil and
equivalent values in the report.
CO
2
〈System requirements〉
●
OS:WindowsⓇ 7/8/10
●
Display:XGA(Resolution 1024×768 dots) or more
●
Hard-disk: Space required 1Gbyteor more
●
Other:With CD-ROM drive and USB port,
NET Framework (3.5 or more)
®
※Windows
is registered trademark of Microsoft in the United States.
axis and time axis are selectable, and also full-scale
unction for automatic scal-
f
ing is available.
Real time and Remote
measurements
Measurements can be
●
graphically displayed on
Android devices or PC in
real-time via Bluetooth
communication.
Bluetooth is a registered trademark of the
※
Bluetooth SIG, Inc.
Android
is a registered trademark of the
Google Inc.
USB Terminal
Digital Output Terminal
●
Harmonics Analysis
Open Collector Output (1ch)
Analogue Input Terminal
●
2ch DC100mV / 1000mV, 10V. To
record additional parameters (i.e.
Lux, Temperature, Humidity,etc.)
Graph
Graphic display of harmonic components up to 50th
●
order for voltage, current and power in total and for
each phase.
List display of harmonic content, rms value and phase
●
angle of each order.
Can analyze harmonic currents that may contribute
●
to damage capacitor banks for PF correction, overheating transformers / neutral conductors / cables,
unwanted tripping of br
●
Dip
Dip, as the opposite of a swell, is a instantaneous voltage
decrease, most of the time caused by switching ON large
load e.g. motors or by downstream power line failure.
●
Interruption
Interruption is a power line cut-off from any source of
supply. It can be caused by a fault in a power line, which
causes switch gear to open.
●
Transients/Over Voltage (Impulse)
Transient is a very fast and momentary voltage increase
that can seriously damage devices connected to a power line. It may be caused by electrical switching events
such as instable contacts of r
but also by lightening. KEW 6315 can catch Transients
from 2.4 μs.
●
Inrush Current
Inrush current is a surge current that happens when
motors, large or low-impedance loads are switched ON.
Then the current will stabilize as soon as the load hasreached normal working conditions.
eakers.
elays, tripping of breakers
List
www.GlobalTestSupply.com
Flicker
Designed to meet IEC61000-4-15
Flicker is a phenomenon giving an impression of unsteadiness of visual sensation induced by periodic voltage changes caused by fluctuating loads when using:
ar
c furnace, spot welder, crane, excavator, etc..
●
Displays Pst (1min) on a trend graph.
SD card Interface
●
SD cards up to 2GB can be used
Possible recording time
When the 2GB of SD is used:
Interval
1sec13da ys3days
1min
30min
Data of power quality events are not considered to
estimate the possible recording time. The max possible time will be shortened by recording such events.
List
REC item
Power
1-year or more
10-year or m ore 7-year or more
Trend graph
+
Harmonics
3mounths
Optional
Load current clamp sensors
MODEL 8128
MODEL 8127
MODEL 8126
Load current flexible clamp sensors
MODEL 8125MODEL 8124KEW 8130
MAX
φ24φ24φ40φ40φ68
50A
Leakage &Load current clamp
KEW 8146
MAX
φ24φ40φ68
30A
※
8146/8147/8148 can measure up to 10A
MAX
100A
KEW 8147
MAX
70A
MAX
200A
KEW 8148
MAX
100A
MAX
500A
Power supply
adaptor
MODEL 8312MODEL 9132
Can you close your distribution board door during
surveys?
The KEW6315 facilitates safe testing by being extremely
compact and with two clever option extras: a magnetic
case(9132) for attaching it to the sides of metal enclosures
and a power supply adaptor(8312) which takes the power
for the instrument from the supply being measured.
Specifications
Wiring connections1P2W, 1P3W, 3P3W, 3P4W
Measurements and
parameters
Voltage (RMS)
Range600.0/1000V
Accuracy0.08% of nominal voltage (sine wave, 40 - 70Hz)
Allowable input1 - 120% of each range (rms). 200% of each range (peak)
Display range 0.15 - 130% of each range
Crest factor3 or less
Sampling speed of
Voltage transient
Current (RMS)
Range8128 (50A type) 5000mA/50.00A/AUTO
Accuracy
Allowable input1 - 110% of each range (rms). 200% of each range (peak)
Display range 0.15 - 130% of each range
Crest factor3 or less
Active power
Accuracy
Influence of power
factor
Voltage, Current, Frequency, Active power, Reactive power,
Apparent power, Active energy, Reactive energy,
Apparent energy, Power factor (cos
Demand, Harmonics, Quality (Swell/Dip/Interruption,
Transients/Over voltage, Inrush current, Unbalance rate),
Capacitance calculation for PF correction unit, Flicker