Electricity is dangerous and can cause injury and death. Always treat it with the
greatest of respect and care. If you are not quite sure how to proceed, stop and
take advice from a qualified person.
1 This instrument must only be used by a competent and trained person and operated
in strict accordance with the instructions. KYORITSU will not accept liability for any
damage or injury caused by misuse or non-compliance with the instructions or with
the safety procedures.
2 It is essential to read and to understand the safety rules contained in these
instructions. They must always be observed when using the instrument.
3 This instrument is designed to work in distribution systems where the line to earth
has a maximum voltage of 300V 50/60Hz and for some ranges where line to line
has a maximum voltage of 500V 50/60Hz.
Be sure to use it within this rated voltage.
For use in the continuity testing and insulation testing modes this instrument must
be used ONLY on circuits which are de-energized.
4 When conducting tests do not touch any exposed metalwork associated with the
installation. Such metalwork may become live for the duration of the test.
5 Never open the instrument case (except for fuse and battery replacement and in
this case disconnect all leads first) because dangerous voltages are present. Only
fully trained and competent electrical engineers should open the case. If a fault
develops, return the instrument to your distributor for inspection and repair.
6 If the overheat symbol appears in the display disconnect the instrument from the
mains supply and allow to cool down.
7 If abnormal conditions of any sort are noted (such as a faulty display, unexpected
readings, broken case, cracked test leads, etc) do not use the tester and return it to
your distributor for repair.
8 For safety reasons only use accessories (test leads, probes, fuses, cases, etc)
designed to be used with this instrument and recommended by KYORITSU. The
use of other accessories is prohibited as they are unlikely to have the correct safety
features.
9 When testing, always be sure to keep your fingers behind the finger guards on the
test leads.
10 During testing it is possible that there may be a momentary degradation of the
reading due to the presence of excessive transients or discharges on the electrical
system under test. Should this be observed, the test must be repeated to obtain a
correct reading. If in doubt, contact your distributor.
Depending on the accuracy at each function.
Measurement sequence:
X1/2 0°→X1/2 180°→X1 0°→X1 180°→X5 0°→X5 180°
Measurements with x5 are not carried out for RCDs with nominal
current of 100mA or more.
Possible number of tests with fresh batteries.
Continuity :Approx. 2000 times min. at load 1Ω
Insulation Resistance :Approx. 1000 times min. at load 1MΩ (1000V)
LOOP/PFC/PSC :Approx. 1000 times min. (ATT)
RCD :Approx. 2000 times min. (G-AC X1 30mA)
EARTH :Approx. 1000 times min. at load 10Ω
VOLT/PHASE ROTATION :Approx. 50H
Reference Conditions
Ambient temperature23±5℃
Relative humidity45% to 75%
Nominal system voltage and frequency230V, 50Hz
AltitudeLess than 2000m
5.2 Operating error
Continuity (EN61557-4)
Operating range compliant with
EN61557-4 operating error
0.20~1999MΩ±30%
The influencing variations used for calculating the operating error are denoted as
follows;
Temperature : 0 ℃ and 35 ℃
Supply voltage : 8V to 13.8V
Maximum percentage
operating error
Insulation Resistance(EN61557-2)
Volt
250V0.25~199.9MΩ
1000V1.00~1999MΩ
The influencing variations used for calculating the operating error are denoted as
4 Operate the Continuity Null (F1) button, this will null out the lead resistance and the
indicated reading should go to zero.
5 Release the test button. Press the test button and ensure the display reads zero
before proceeding. While using the Continuity null function, NULL
is displayed
on the LCD as indicated in Fig.13. The null value will be stored even if the instrument
is powered off. This memorized null value can be cancelled by disconnecting the
test leads and pushing the Continuity Null button (F1) with the test button pressed or
locked. When this is cancelled you will know because NULL OFF is displayed on the
LCD.
CAUTION - before taking any measurements always check the leads have been
zeroed.
6 Connect the test leads to the circuit whose resistance is required (see Fig.14 for a
typical connection arrangement), having first made sure that the circuit is not live.
Note that Live Circuit warning will be displayed on the LCD if the circuit is live - but
check first anyway!
7 Press the test button and read the circuit resistance from the display. The reading
will have the test lead resistance already subtracted if the Continuity null function has
been used.
8 Note that if the circuit resistance is greater than 20Ω the instrument will autorange to
the 200Ω, if it is greater than 200Ω it will autorange to the 2000Ω range.
Note: If the reading is greater than 2000Ω the overange symbol > will remain
displayed.
WARNING
The results of measurements can be adversely affected by impedances of
additional operating circuits connected in parallel or by transient currents.
Fig.14 Example of continuity test for main equipotential bonding.
PE
MAIN EQUIPOTENTIAL BONDING
Ω
NULL
ON
GAS
7.2 2Ω Buzzer () function
Use F2 Button to enable / disable the 2Ω Buzzer. The buzzer sounds when measured
resistance is 2Ω or less while this function is enabled. The buzzer does not sound if it is
Disconnect the instrument from the circuit under test before operating the
function switch.
To select the insulation resistance range select INSULATION.
8.1.1 The nature of insulation resistance
Live conductors are separated from each other and from earth metal by insulation,
which has a resistance which is high enough to ensure that the current between
conductors and to earth is kept at an acceptably low level. Ideally insulation resistance
is infinite and no current should be able to flow through it. In practice, there will normally
be a current between live conductors and to earth, and this is known as leakage current.
This current is made up of three components, which are:-
1. capacitive current
2. conduction current, and
3. surface leakage current.
8.1.2 Capacitive Current
The insulation between conductors which have a potential difference between them
behaves as the dielectric of a capacitor, the conductors acting as the capacitor plates.
When a direct voltage is applied to the conductors, a charging current will flow to the
system which will die away to zero (usually in less than a second) when the effective
capacitor becomes charged. This charge must be removed from the system at the
end of the test, a function which is automatically performed by the KEW6016. If
an alternating voltage is applied between the conductors, the system continuously
charges and discharges as the applied voltage alternates, so that there is a continuous
alternating leakage current flowing to the system.
If the circuit has alternating voltage applied, the capacitive current (8.1.2) will always be
present and can never be eliminated. This is why a direct voltage is used for insulation
resistance measurement, the leakage current in this case quickly falling to zero so that it
has no effect on the measurement. A high voltage is used because this will often break
down poor insulation and cause flashover due to surface leakage (see 8.1.4), thus
showing up potential faults which would not be present at lower levels.
The insulation tester measures the applied voltage level and the leakage current
through the insulation. These values are internally calculated to give the insulation
resistance using the expression:-
As the capacitance of the system charges up, so the charging current falls to zero and a
steady insulation resistance reading indicates that the capacitance of the system is fully
charged. The system is charged to the full test voltage, and will be dangerous if left with
this charge. The KEW6016 provides an automatic path for discharging current as soon
as the test button is released to ensure that the circuit under test is safely discharged.
If the wiring system is wet and/or dirty, the surface leakage component of the leakage
current will be high, resulting in low insulation resistance reading. In the case of a very
large electrical installation, all the individual circuit insulation resistances are effectively
in parallel and the overall resistance reading will be low. The greater the number of
circuits connected in parallel the lower will be the overall insulation resistance.
8.2 Damage to Voltage-Sensitive Equipment
An increasing number of electronic-based items of equipment are being connected
to electrical installations. The solid state circuits in such equipment are likely to be
damaged by the application of the levels of voltage used to test insulation resistance. To
prevent such damage, it is important that voltage-sensitive equipment is disconnected
from the installation before the test is carried out and reconnected again immediately
afterwards. The devices which may need to be disconnected before the test include:-
4 Attach the test leads to the circuit or the appliance under test (see Figs 20 & 21)
Fig.20 Example of Insulation resistance test on 4 wire-3 phase system.
Fig.21
MΩ
1000V
5 If the Live Circuit warning is displayed on the LCD and/or the buzzer sounds, do
not press the test button but disconnect the instrument from the circuit. Make the
circuit dead before proceeding.
MΩ
1000V
6 Press the test button, the display will show the insulation resistance of the circuit or
the appliance to which the instrument is connected.
7 Note that if the circuit resistance is greater than 20MΩ, the instrument will autorange
to the 200MΩ range. If it is greater than 200MΩ at the 500V or 1000V range, it will
autorange to the 2000MΩ range.
8 When testing is complete release the test button before disconnecting the test leads
from the circuit or from the appliance. This will ensure that the charge built up by the
circuit or the appliance during insulation test is dissipated in the discharge circuit. In
the discharging process, Live Circuit warning will be displayed on the LCD and the
According to the International Standard IEC 60364, for TT systems the characteristics of
the protective device and the circuit resistance shall fulfill the following requirements:
Ra x Ia ≤ 50V Where:
Ra is the sum of the resistances in Ω of the local earth system and the protective
conductor for the exposed conductive parts.
50 is the maximum safety touch voltage limit (it can be 25V in particular cases like
construction sites, agricultural premises, etc.).
Ia is the current causing the automatic disconnection of the protective device within the
maximum disconnecting times required by IEC 60364-41:
- 200 ms for final circuits not exceeding 32A (at 230 / 400V AC)
- 1000 ms for distribution circuits and circuits over 32A (at 230 / 400V AC)
The compliance with the above rules shall be verified by:
1) Measurement of the resistance Ra of the local earth system by Loop tester or Earth
tester.
2) Verification of the characteristics and/or the effectiveness of the RCD associated
protective device.
Generally in TT systems, RCDs shall be used as protective device and in this case, Ia
is the rated residual operating current I△n. For instance in a TT system protected by a
RCD the max Ra values are:
Rated residual operating current I△n301003005001000(mA)
RA (with touch voltage of 50V)166750016710050(Ω)
RA (with touch voltage of 25V)833250835025(Ω)
Shown below is a practical example of verification of the protection by RCD in a TT
system according to the international Standard IEC 60364.
For this example the max permissible value is 1667 Ω (RCD =30mA and contact
voltage limit of 50 V). The instruments reads 12.74 Ω, thus the condition RA ≤ 50/Ia
is respected. However, considering that the RCD is essential for protection, it must be
tested (Please refer to RCD TESTS section).
TN System
For TN systems the earth fault loop impedance is the sum of the following impedances.
● Impedance of the power transformer secondary winding.
● Impedance of the phase conductor from the power transformer to the location of the
fault.
● Impedance of the protective conductor from the fault location to the power
transformer.
The figure below shows (dotted line) the Fault loop impedance for TN systems.
● Measurement in ATT mode requires longer time than that is required for the other
Fig.31 Connection for using Outlet
measurements (approx. 7 sec). When measuring a circuit with a large electrical
noise, the 'Noise' Message is displayed on the LCD and the measurement time
will be extended to 20 sec. If the 'NOISE' symbol is displayed on the LCD, it is
recommended to disable the ATT mode and take a measurement (RCDs may trip).
● If an impedance of 20Ω or more is measured between L-N during measurements
with ATT enabled, L-N>20Ωis displayed on the LCD and no measurement can be
made. In this case, disable the ATT function and make measurement. When a large
contact voltage exists in the circuit under test,N-PE HiVis displayed on the LCD
and no measurement can be made. In this case, disable the ATT function and make
measurement. Be aware that if the ATT mode is disabled, RCDs may trip.
● Measured result may be influenced depending on the phase angle of the distribution
system when making measurement near a transformer and the result may lower than
the actual impedance value. Errors in measured result are as follows.
System Phase
Difference
Error
(approx.)
10°-1.5%
20°-6%
30°-13%
● ATT mode is automatically enabled after one measurement when making a
The RCD tester is connected between phase and protective conductor on the load side
of the RCD after disconnecting the load.
A precisely measured current for a carefully timed period is drawn from the phase and
returns via the earth, thus tripping the device. The instrument measures and displays
the exact time taken for the circuit to be opened.
An RCD is a switching device designed for breaking currents when the residual current
attains a specific value. It works on the basis of the current difference between phase
currents flowing to different loads and returning current flowing through the neutral
conductor (for a single-phase installation). In the case where the current difference is higher
than the RCD tripping current, the device will trip and disconnect the supply from the load.
There are two parameters for RCDs; the first due to the shape of the residual current wave
form (types AC and A) and the second due to the tripping time (types G and S).
●
RCD type AC will trip when presented with residual sinusoidal alternating currents
whether applied suddenly or slowly rising. This type is the most frequently used on
electrical installations.
●
RCD type A will trip when presented with residual sinusoidal alternating currents
(similar to type AC) and residual pulsating direct currents (DC) whether suddenly
applied or slowly rising. This type of RCD is not commonly used at present, however,
it is increasing in popularity and is required by the local regulations in some countries.
Making measurement with setting uses pulsating direct currents for test.
● RCD type G. In this case G stands for general type (without tripping time delay) and
is for general use and applications.
●
RCD type S where S stands for selective type (with tripping time delay).This type of RCD
is specifically designed for installations where the time delay characteristic is required.
Given that when the protective device is an RCD, Ia is typically 5 times the rated
residual operating current I△n, then the RCD must be tested recommending the
tripping time, measured by RCD testers or Multifunction testers, shall be lower than the
maximum disconnecting times required in IEC 60364-41 (see also LOOP/PSC/PFC
section) that are:
TT system
(at 230V / 400V AC)
TN system
(at 230V / 400V AC)
200 ms for final circuits not exceeding 32A
1000 ms for distribution circuits and circuits over 32A
400 ms for final circuits not exceeding 32A
5 s for distribution circuits and circuits over 32A
However it is also good practice to consider even more stringent trip time limits, by following
Fig.35
Fig.36
the standard values of trip times at I△n defined by IEC 61009 (EN 61009) and IEC 61008
(EN 61008). These trip time limits are listed in the table below for IΔn and 5I△n:
Type of RCDIΔn5IΔn
General(G)
Selective(S)
300ms
max allowed value
500ms
max allowed value
130ms
min allowed value
40ms
max allowed value
150ms
max allowed value
50ms
min allowed value
Examples of instrument connections
Practical example of 3-phase + neutral RCD test in a TT system.
ms
L-PE
×1
230V
50.0Hz
30 mA
V
UL50
L-PE
L-N
!
PHASE : 0
°
Practical example of single phase RCD test in a TN system.
Practical example of RCD test with distribution leads.
Fig.37
Fig.38
PE
ms
L-PE
×1
230V
50.0Hz
30 mA
V
UL50
L-PE
L-N
!
PHASE : 0
°
10.2 Principles of Uc Measurement
Ground being imperfect in the Fig35, when R exists, when a fault current flows to R,
electric potential occurs. There is a possibility the person contacting in this imperfect
ground, it calls the voltage, which it occurs in the human body of this time, called Uc.
When with the Uc Test letting flow IΔN to the RCD, the Uc is calculated.
Uc voltage is calculated based on the Rated Residual Current (I△N) with the
impedance measured.
10.3 Operating Instructions for RCD
10.3.1 Initial Checks: to be carried out before any testing;
1. Preparation
Always inspect your test instrument and lead accessories for abnormality or damage:
If abnormal conditions exist DO NOT PROCEED WITH TESTING. Have the instrument
This Earth function is to test power distribution lines, in-house wiring system, electrical
appliances etc.
This instrument makes earth resistance measurement with fall-of-potential method,
which is a method to obtain earth resistance
value Rx by applying AC constant current I
between the measurement object E (earth
electrode) and H(C) (current electrode),
and finding out the potential difference V
between E and S(P) (potential electrode).
Rx = V / I
11.2 Earth resistance Measurement
WARNING
● The instrument will produce a maximum voltage of about 50V between
terminals E-H(C) in earth resistance function. Take enough caution to avoid
electric shock hazard.
CAUTION
● When measuring earth resistance, do not apply voltage between measuring
terminals.
● Do not use MODEL7228A for measuring electrical potentials that exceed 33V
rms, 46V peak or DC 70V.
1.Select Earth function with the Rotary Switch
2.Insert the Test Leads (MODEL7228A) into the instrument. (Fig.41)
d Green
3.Test Lead connection
Stick the auxiliary earth spikes S(P) and H(C) into the ground deeply. They should be
aligned at an interval of 5-10m from the earthed equipment under test. Connect the
green wire to the earthed equipment under test, the yellow wire to the auxiliary earth
spike S(P) and the red wire to the auxiliary earth spike H(C) from terminals E, S(P) and
H(C) of the instrument in order.
1. Operate the Power button and turn on the instrument. Turn the rotary switch and
select the VOLTS function.
2. Insert the Test Leads into the instrument. (Fig.47)
3. Voltage value and frequency will be displayed on the LCD when applying AC voltage.
Note : A message DC V may be displayed when measuring AC voltages with
frequencies out of the range 45Hz - 65Hz.
14. TOUCH PAD
1. The touch pad measures the potential between the operator and the tester's PE
terminal.
A message PE HiV is displayed on the LCD with the audible buzzer if a potential
difference of 100V or more is present between the operator and the PE terminal at
touching the Touch pad.
2. Touch Pad function can be enabled and disabled (ON / OFF); refer to 6.
Configuration in this manual and select ON or OFF. In case that OFF is selected, a
warning for PE HiV does not appear and the buzzer does not sound.
* Initial value: ON
Note :
A message PE HI V may be displayed when testing inverters or measuring
voltages containing high frequencies even if a user isn't touching with the Touch Pad.
15. BACK LIGHT
Pressing the Back Light Button selects Backlight ON / OFF. Backlight automatically
turns off in 60 sec after it turns on. Backlight at powering on the instrument can be set
either ON or OFF. Refer to 6. Configuration in this manual how to select ON / OFF.