Kutai electronics GCU-3000 Operator's Manual

Page 1
KUTAI ELECTRONICS INDUSTRY CO., LTD.
TEL : +886-7-8121771 FAX : +886-7-8121775 Website : www.kutai.com.tw Headquarters : No.3, Lane 201, Chien Fu St., Chyan Jenn Dist., Kaohsiung 80664, TAIWAN
GCU-3000 Ver1.0
Automatic Engine Control and
Protection Module Operators Manual
Page 2
___________________________________________________________________________________________
2 GCU-3000
TABLE OF CONTENTS
Section Page
SECTOIN 1 : INTRODUCTION
1.1 Panel Layout ............................................................................................................................................... 4
1.2 Front Panel Layout...................................................................................................................................... 4
1.3 Unit Dimensions (Measurement : mm) ....................................................................................................... 5
1.4 Panel Cut-Out (Measurement : mm)........................................................................................................... 5
SECTOIN 2 : OPERATOR
2.1 Summary ..................................................................................................................................................... 6
2.2 AUTO .......................................................................................................................................................... 6
2.3 Manual ........................................................................................................................................................ 6
2.4 Off & Reset ................................................................................................................................................. 6
SECTION 3 : SYSTEM SETTING & OPERATION
3.1 DC Input Power ........................................................................................................................................... 7
3.2 System Setting (Programming) ................................................................................................................... 7
3.3 The Hour Meter ........................................................................................................................................... 7
3.4 AC Voltage & Current Setting ..................................................................................................................... 7
3.5 Over-Load Protection Setting ..................................................................................................................... 8
3.6 Shutdown Override ..................................................................................................................................... 8
3.7 Magnetic Pick-up (MPU) Setting ................................................................................................................. 8
3.8 The Additional Inputs Alarm1 & Alarm2 ...................................................................................................... 9
3.9 Setting the Service Reminder ..................................................................................................................... 9
3.10 Screen Viewing ........................................................................................................................................... 9
3.11 Engine Idle Operation Function .................................................................................................................. 9
3.12 Digital Temperature Sensor (Optional) ....................................................................................................... 9
3.13 Ceramic Capacitive Oil Pressure Sensor (Optional) .................................................................................. 9
3.14 The Event Log ............................................................................................................................................. 9
3.15 Communication With PC (KCU-XX) .......................................................................................................... 10
3.16 CANBus J1939 Transducer KCU-04 (Optional) ....................................................................................... 12
3.17 System Setting Line-by-Line Programming Table .................................................................................... 12
SECTOIN 4 : FAILURE WARNING DESCRIPTION
4.1 Failure Signal Reference Table ................................................................................................................ 15
4.2 Warning ..................................................................................................................................................... 15
4.3 Shutdown .................................................................................................................................................. 15
SECTOIN 5 : SPECIFICATION
SECTION 6 : TERMINAL & WIRING DESCRIPTION
6.1 Connection Detail...................................................................................................................................... 16
6.2 Wiring Diagram ......................................................................................................................................... 17
SECTION 7 : TROUBLESHOOTING
Page 3
___________________________________________________________________________________________
GCU-3000 3
SECTION 1 : INTRODUCTION
The GCU-3000 is an integrated modular Automatic Generator Control & Protection unit with the largest LCD screen in the market. It is suitable for use on all conventional generator applications. The module uses easy to recognize icons and powerful software to protect the generators. The GCU-3000 makes the complicated simple by providing an easy to install and easy to Program Generator Controller.
To simplify installation you can program the GCU directly from the front panel without complicated computer setup. After programming, all the new settings are recorded into the internal (EEPROM) and protected from erasure.
The main advantages of using the GCU-3000 are
Integrated design including an emergency stop button, AVR control, fuses, and positive outputs
Large easy to see LCD screen
Programmable start cycles
Programmable idle speed timer
Programmable cool down timer
Maintenance notifications
Engine block heater control
Digital temperature sensor included
High precision oil pressure sensor included
Full monitoring and protection
LCD information includes the following
Full phase AC voltage monitoring
Full phase AC line voltage monitoring
Full phase load current monitoring
KVA output
Frequency
Hour Meter
Battery voltage Indicator
Oil pressure readings in Psi or Bar
Temperature in C or F
Universal Failure Warning icons
The module includes a front panel emergency stop button and a built in potentiometer (VR) to adjust the Automatic Voltage Regulators (AVR) directly from the front panel. It also comes with all AC and DC fuses and relays for quick installation and operation.
When a generator failure occurs, the built in warning buzzer and LCD graphic display, gives you the reasons for the warnings instantly. In addition, it provides a remote failure-warning signal to the control room; to also notify the maintenance personnel. It also incorporates a Failure Event Log program, which records the previous 15 failures; then you can read the log directly from the front panel screen.
The Engine Block Heater control is also integrated into the GCU using its build in digital temperature sensor. The generator is then able to maintain smooth and good starts in the coldest weather.
Maintenance personnel can obtain; Engine Temperature, Battery voltage and hours of operation at any time by pressing the Mute Button. Even with the engine off.
GCU Monitoring and Protects
High engine temperature protection
Low oil pressure protection
Over & Under speed protection
Full phase AC over & Under voltage and loss of
phase monitoring
Full phase load current monitoring
Battery over & under voltage monitoring
Low Fuel Level Monitoring
Temperature & Pressure Sensor Failure
Magnetic Pick-up (MPU) Failure
The GCU also reserves two extra inputs for future expansion.
Page 4
___________________________________________________________________________________________
4 GCU-3000
1.1 Panel Layout
Icon
Function
Down Arrow
UP Arrow
Auto
Off
Manual
Pen
Mute
1.2 Front Panel Layout
Page 5
___________________________________________________________________________________________
GCU-3000 5
1.3 Unit Dimensions (Measurement : mm)
1.4 Panel Cut-out (Measurement : mm)
GCU-2000
GCU-3000
Page 6
___________________________________________________________________________________________
6 GCU-3000
SECTION 2 : OPERATION
2.1 Summary
The GCU has 3 main control buttons :
1. Auto
2. Manual
3. Off
In addition, we have the (UP Arrow), (Down Arrow), (Pen Button) and the (Mute Button). Everything you need to operate the generator is on the front panel.
2.2 AUTO
In AUTO, the generator starts & stops automatically under the control of the remote start signal. (Usually from an ATS)
Press the AUTO key and notice the screen flashes (AUTO). When the control receives a remote start signal the flashing stops and the start sequence begins.
First the Pre-Heat timer is activated and (Pr.Ht) shows up on the screen. (However, if the Pre-Heat timer is set to 0 (See setting Line 41) then the system omits the pre-heat countdown and proceeds to crank start. If it fails to start the first time, it tries to (restart) three times after a 5 seconds rest.
The starter cranking time is factory pre-set for 6 seconds (See settings Line. 43). When cranking (Strt) shows on the screen. If the engine fails to start, the system goes back to Pre-Heat and tries again. If it fails to start within the preset number of tries, then the system declares a start failure with a flashing FAIL signal comes up on the screen together with the sound alarm. The GCU also sends out the warning output.
The starter motor stops cranking when any of the condition below is established, in order to prevent damage to the starter and flywheel ring gear.
Oil pressure builds up and oil pressure sensor is activated
Oil pressure sensor sees more than 25Psi
AC voltage
The AC Frequency reaches 20% of the rated
Frequency
MPU sensing 20% of rated speed (needs to be pre-set).
The GCU can also provide idle speed. Once started the system enters into idle speed operation and the word (Idle) appears on the screen. The idle speed can be cancelled if the genset does not need it. See setting reference Line 50 and set countdown timer to 00 to cancel.
After starting, the GCU implements a 30 sec grace period to confirm that speed, oil pressure, voltage and all other parameter are normal. If the generator fails to reach normal operational parameters, the GCU sends a shutdown signal and FAIL appears on the screen. But if all parameter are reached and stabilized, the GCU proceeds to Warm Up, and once the countdown ends, the genset connects the load, and activates all protections.
(If the generator has no load contactor then this step is omitted.)
If the remote start signal disappears during operation, the load contactor disconnects. The no load Cool-down is initiated and on the screen the word COOL appears and the Cool-down times out. If the remote signal returns during Cool-down, The GCU once again connects to load contactor and goes back to normal operations.
Once the Cool-down ends, the GCU executes a stop
countdown and stops the generator on either “energize to start” or “energize to stop”. In addition, the word
Stop appears on the screen.
NOTICE
When the generator is on Cool-down the protection system remains in effect and if any failure occurs, the module bypasses the countdown and shutdown the generator immediately.
2.3 Manual
In MANU (manual), the start command is initiated by pushing the MANU button on the front panel. After the generator starts the, GCU automatically, connect the load. To stop press OFF or AUTO and the generator executes the normally pre-programmed shut-down.
In manual, the procedure is the same as in AUTO.
2.4 Off & Reset
Pushing the OFF button represents a shutdown command or a RESET. If OFF is selected during normal genset operation, the generator proceeds to shut-down disconnecting the load contactor, executes a Cool-down without load, and stops.
If the system senses a major failure during normal operation, it immediately stops the genset; and after it comes to a complete stop, the failure is showed on the screen. The service personnel can use this information to conduct service and repair accordingly. If there are more than two failures, all of the failures are shown on the screen. And by pressing OFF again, the failure notices are erased and the GCU is RESET.
Page 7
___________________________________________________________________________________________
GCU-3000 7
SECTION 3 : SYSTEM SETTING & OPERATION
NOTICE
Before proceeding to system setting, you must install correctly all the wirings connection and connect the Battery.
3.1 DC Input Power
GCU works with a wide range of battery power inputs from 9 to 36VDC, and the GCU is protected from any incorrect DC voltage input and connections.
3.2 System Setting (Programming)
There are 68 lines of programming. You must adjust each line according to the generator type and protection requirements.
You can preprogram the GCU-3000 away from the generator just by using a small power supply.
To enter Line-by-Line programming, first press (OFF) and then press the (UP Arrow)(Down Arrow) (Pen) and (MUTE) buttons together for 4 seconds.
The software version appears for 2 seconds, followed by the word (Prog) for 4 seconds, and then the screen shows the Line number and value entered for that line (See illustration below).
(Ln.01) indicates Line.1, and (00) representing the entered value. You press (UP Arrow) or (Down Arrow) to change the value. Each time you press the Pen Button we move to the next Line. If the setting is left unattended for 30 seconds or if the last Line 68 is reached the word END indicates that you finished and all modified values are saved.
To end programming at any time press the (OFF) and (Pen) Buttons together for 4 seconds until the END appears.
To restore factory setting at any time press (AUTO) and (Pen) Buttons together for 4 seconds until the word (Au.PO) appears.
3.3 The Hour Meter
The (Hour-Meter) is the total accumulation of the generator operating hours stored in memory. The GCU never erases or resets the hour meter to zero.
However, to set a new value on the hour-meter memory, enter programming mode and before the word (Prog) disappears from the screen (about 4 seconds), press the (OFF) button for 4 seconds, the panel should now read (Ch.Hr), see the illustration below. The (0567Hr) displays the current accumulated operation hour stored in memory.
Now press (UP Arrow) or (Down Arrow) button to change the hour reading. By holding down the button you increase the scrolling speed.
To END at any time press the (OFF) and (Pen) Buttons together for 4 seconds or until the word END appears on the screen or just leave all keys alone for 10 seconds.
3.4 AC Voltage & Current Setting
The voltage and current reading are set at the factory. However, when the generator operates in heavy inductive or capacitive loads, the waveform distortion causes minor voltage differences.
If you need to correct the voltage or amperage readings, on the GCU enter System Setting lines (3), (4), (10), and (11) and increase or decrease the values. Remember that the high/low voltage and load current protections utilize these new values for shutdown, and overload protection, etc.
Page 8
___________________________________________________________________________________________
8 GCU-3000
3.5 Over-load Protection Setting
GCU provides Over-load Protection from the amperages calculated in the GCU.
To set the overload protection each unit value is equal to 50 Amps, for example: If you enter 20 then the Over current protection value equals to 20 times 50A or 1000A.
When the GCU senses a temporary generator over-load, it starts the timer and waits for the over load to disappear within the time allocated. If the generator over-load is longer than the time allocated, the GCU executes the Protection shutdown, showing Over-load failure on the screen.
The GCU has two types of over-load protections.
Stop : For immediate shutdown.
Warning : Does not stop the generator but, Shows
the failure message on the screen and sends out the trip signal output. It is up to the operator to then stop the generator.
For Over-load Protection related settings refer to chapter 3.15 system setting lines (12), (13), (14), (15).
ATTENTION
The GCU uses the internal current reading to calculate over-load protection, you need to pay special attention to these settings they cannot exceed the CT rated value, otherwise field saturation on the CT causes the system to compute incorrect values and loose Over-load Protection.
For example, If the CT ratio is 1000/5, then the over load current setting cannot exceed 1000Amps.
3.6 Shutdown Override
Override Start & Stop We use this feature to manually
start and stop a newly assembled genset, without annoying shutdowns. Giving you time to set and adjust the AC voltage speed, oil pressure shutdowns, etc.
Before entering shutdown override, you should complete all wiring connections and perform a Line-by-Line check, confirming that all systems are working. Then, enter Line (67) and select shutdown override. Also define the type of engine shutdown system you are using on Line 48 before activating Shutdown Override.
In override, the manual icon appears on the screen.
To crank and start the engine press and hold the
(MANU) button, to stop the engine, press and hold the (AUTO) button. (The starter is activated only when you
hold the button down and the same is true to stop the engine).
Once all adjustment and setting are completed, you need to set the system back to normal. To return to normal presses the (OFF) button, the GCU stops the generator and automatically resets back to normal operation.
For manual override, go to System Setting Line (67).
ATTENTION
Under manual override, the GCU cancels all protections, and if a failure occurs while in override operation, the system does not shutdown the engine. Therefore, it is strongly recommended that manual override be used only for adjustment and servicing the generator.
3.7 Magnetic Pick-up (MPU) Setting
The MPU (Magnetic Pick-up) is the sensing device installed on the flywheel bell housing, which detects the engine RPM according to the frequency generated by the flywheel ring gear. Most generators with electronic speed controllers use a MPU.
MPU operational frequency range100 Hz 10K Hz To program the MPU, Manually start the engine and
run at rated speed (50 Hz or 60 Hz) by holding the governor actuator by hand, Then quickly press the Pen Button, and read the MPU frequency, and when (Au.Po) appears on the screen the MPU programming is complete.
If the system detects that the MPU frequency is below 100 Hz, this is considered a MPU failure and the (FAIL) message appears up on the screen, and the MPU signal failure icon appears on the screen, confirming procedure failure. At this point, you should check for incorrect wiring or bad contacts. Repeat the setup procedure after the cause of the failure has be identified and corrected.
If the system detects the MPU frequency above 10 K Hz, then it considers it as MPU failure and the (FAIL) message appears on the screen, and at the same time the Over speed failure icon appears on the screen, confirming a programming failure. At this point, you should first check the MPU for, incorrect wiring or a bad installation. Repeat the setup procedure after the correcting the problem.
Page 9
___________________________________________________________________________________________
GCU-3000 9
Note : 10 to 15 Vac open circuit is about the right output voltage for a MPU measured directly into a digital voltmeter with the engine running at rated speed 50 or 60 Hz.
Some Electronics Speed Controllers or Governors do not allow sharing the MPU with other devices. If a MPU is required for over-speed protection we recommend an extra independent Magnetic Pick-up or a dual coil (MPU) If the GCU is programmed to use an MPU, and the MPU is defective or open or its, unable to read the MPU, the system shutdown the engine and the MPU signal failure icon appears on the screen.
For MPU related settings refer to chapter 3.15 System Setting lines (1), (16), (17), (18), (19), (20), (44).
3.8 The Additional Inputs Alarm1 & Alarm2
The GCU is equipped with 2 spare inputs to add two extra protections.
To set Alarm1 & Alarm2 go to chapter 3.15 System Setting Lines (56), (57), (58), (59), (60), (61).
3.9 Setting the Service Reminder
The maintenance icon on the screen is a reminder to the service personal that it is time to carry out maintenance on the generator. When setting the service timer, each unit entered is equal to 10hrs, for example if entering 20 is equal to 20 x 10Hrs = 200 Hrs.
After completing maintenance, you need to clear the record and set a future maintenance point. See System Setting Line (68).
For Service & Maintenance related settings refer to System Setting Lines (62), (68).
3.10 Screen Viewing
You can freeze the screen parameter or leave them to cycling one by one. When cycling, each parameter paused for 2 seconds, but pressing the (UP Arrow) button, you can select either AC Voltage or AC Current readings, also pressing the (Down Arrow) key permits you to cycle though the phases, The Hour meter, Battery Voltage, Hz, engine temperature measurement in C or F and oil press measurement in Psi or Bar.
When using the (UP Arrow) and (Down Arrow) keys to select specific parameters, the selected value freezes for 30 seconds and if the system is left unattended it automatically return to cycling.
For Panel related settings refer to chapter 3.15 Setting Lines (63), (64), (65).
3.11 Engine Idle Operation Function
You can idle the generator automatically before working at full load.
For Idle Operation related settings refer to chapter 3.15 System Setting Line (50).
3.12 Digital Temperature Sensor (Optional)
You can install the most accurate temperature sensor available on the market. It greatly improves accuracy from traditional thermal sensors.
Digital Temperature Sensor accuracy-55 to +125 ˚C +/- 2 ˚C
Temperature Display Unit˚C or ˚F
3.13 Ceramic Capacitive Oil Pressure Sensor (Optional)
The Ceramic Capacitive Oil Pressure Sensor is most the most accurate oil pressure sensor available on the market. It greatly improves the accuracy from traditional oil pressure sensors.
Ceramic Capacitive Oil Pressure Sensor accuracy:0 to 120 Psi +/- 2.5%
Oil Pressure measurements in Psi or Bar
ATTENTION
The GCU uses a special Digital Temperature Sensor and a Ceramic Capacitive Oil Pressure Sensor. Do not replace with any others. If you have, any questions concerning the sensors contact our technical staff.
3.14 The Event Log
Use the Failure Event Log to assist the service personnel identify and determine the cause of a problem. To retrieve the event log from memory go to Line 66 and set (YES) The GCU retains the last 15-recorded failures in memory. Pressing the (UP Arrow) our (Down Arrow) recalls the events and the time of the event. To end the program press the (OFF) key, or leave the system unattended for 10 seconds and the system automatically closes the program and the word END pops up on the screen.
The diagram below is an example of the Failure Event Log :
Page 10
___________________________________________________________________________________________
10 GCU-3000
The (FAIL) and (01) represent the event log screen (is the memory lines 1 to 15), the (567 Hr) represents the hour when the failure occurred and the Overheat icon represents the cause of the failure.
For Failure Event Log related settings refer to chapter
3.15 system setting Line (66).
3.15 Communication With PC (KCU-XX)
The GCU with the optional USB / RS485 and Ethernet remote communications modules, can easily read all the real time information and remote control the local device via communication interface modules. There are 3 different purpose interface modules show as below :
WARNING
You can remotely control the gcu and the attention the generator can start at anytime.
Place a visible sign “DANGER!” “This generator can start up at any time!” next to the generator
and install a warning buzzer or flash warning light. Unwarned or unscheduled remote start scan result in serious injury or death. When performing service and maintenance, always disconnect the remote signal input to the generator.
Free App developed by Kutai Electronics to enables you to remotely monitor and operate generator via portable mobile device. Software currently available with Apple iOS5.1 and Android Ver.2.3.3 system and above. Other operating system software will be available at a later time.
Free software can be downloaded from App Store or Google Play by simply key in “ Kutai ” and hit search.
KCU-01 – USB interface module KCU-02 – RS-485 interface module KCU-03 – Ethernet interface module
For remote communication settings, See setting Line (69), (70), (71).
When the item (69) set to 00, then user can read all the real time information from the controller only. But when it set to 01, it allow remote control from PC also.
The items (70), (71) are for when KCU-02 RS485 interface module is used only, others do not apply.
For information that is, more detailed refer to the KCU-XX manual.
NOTE
When using the KCU-02 to make a closed LAN connection A different controller address setting must be programmed and the Baud rate setting must be the same.
Page 11
___________________________________________________________________________________________
GCU-3000 11
Page 12
___________________________________________________________________________________________
12 GCU-3000
3.16 CANBus J1939 Transducer KCU-04 (Optional)
The KCU-04 module is used with CPU equipped engines using the J1939 CAN Bus protocol. It is connected to any one of the four slots on the back of the GCU-3000 controller.
For J1939 related settings refer to Setting Line (21). Installing the KCU-04 provides the GCU with the
following information.
Temperature reading in ˚C or ˚F
Oil Pressure reading in Psi or Bar
High temperature warning and shut-down alarm
Low oil Pressure warning and shut-down alarm
Over-speed warning and shut-down alarm
Under-speed warning and shut-down alarm
Low fuel level warning and shut-down alarm
When you connect the KCU-04 module the GCU disables the High Temperature, Low Oil Pressure and Low Fuel Level protections automatically and all related programming lines are automatically eliminated. You
don’t need to install any of sensors, this information
now comes from the CAN Bus, and protections
relegated to the engine CPU. The GCU’s job is to show
warning, alarm and shutdown messages using the universal icons on the front panel.
The GCU does not disable its own over speed and under speed protection, Both of GCU and the engine CPU will shut-down the generator for over speed.
3.17 System Setting Line-by-Line Programming Table
NO.
DESCRIPTION
SETTING
FACTORY
PRE-SET
1
Frequency (60 or 50 Hz)
00  60 Hz 01  50 Hz
00
2
How is the generator wired? (3Ø 4W, 3Ø 3W, 1Ø 3W or 1Ø )
00  3Ø 4W 01  3Ø 3W 02  1Ø 3W 03  1Ø
00
3
Correct the Voltage reading on the display (If needed) Add or subtract the amount on line 4 to your reading
00 Do not correct 01 Add volts from line 4 02 Deduct volts from line 4
00
4
Volts reading display correction (If needed)
01 99 V
05 V
5
(Faulty voltage) protection time delay
00 99 sec (0 Do not Protect)
15
6
Set Under-Voltage protection
08  47 (80  470V)
18(180V)
7
Under voltage protection Warning or Shutdown
00  Warning 01 Shutdown
01
8
Set Over-Voltage protection
11 50 (110 500V)
25(250V)
9
Over-voltage protection Warning or Shutdown
00  Warning 01 Shutdown
01
10
Correct Amps reading on the display (If needed) Add or subtract the amount on line 11 to your reading
00 Do not correct 01 Add amps from line 11 02 Deduct amps from line 11
00
11
Amps reading display correction (If needed)
01 99 A
05 A
12
Set the (CT) Example : 5 if you use a 100/5 CT for current reading
(Choosing the wrong CT will give you a erroneous current reading)
01  25/5 02  50/5 03  60/5
04  75/5 05  100/5 06  150/5 07  200/5 08  250/5 09  300/5 10  400/5 11  500/5 12  600/5 13  750/5 14  800/5 15  1000/5 16  1200/5 17  1500/5 18  1600/5
19  2000/5 20  3000/5
05
13
Over-load protection activation time delay
00 99 sec (00 Option Cancelled)
00
Page 13
___________________________________________________________________________________________
GCU-3000 13
NO.
DESCRIPTION
SETTING
FACTORY
PRE-SET
14
Setting the over-load protection (One unit is equal 50 amps) Example : 20 units is equal to 1000A overload protection 20 * 50A = 1000A
01  60 (50  3000A)
02(100A)
15
Over-load protection Warning or Shutdown
00  Warning 01  Shutdown
00
16
Over-speed / Under-speed protection activation time delay
00  99 sec (0 Option Cancelled)
05
17
Magnetic Pick-up (MPU) used with the GCU-3000?
00  NO 01  Yes
00
18
RPM info taken from the generator or MPU
00  AC Hz 01  MPU
00
19
Over-speed protection setting
51 75 Hz
65 Hz
20
Under-speed protection setting
40 59 Hz
55 Hz
21
Use the Oil (PS-01) pressure sensor or get info from J1939 (KCU-04) transducer
00  (None) 01  PS-01 Sensor 02 J-1939 + KCU-04
01
22
Oil pressure reading in Psi or Bar
00  Psi 01  Bar
00
23
If the (PS-01) Oil pressure sensor fails do I want a Warning or a Shutdown
00  Warning 01  Shutdown
00
24
Low oil pressure protection activation time delay
02  99 sec
10
25
Use the (PS-01) sensor to detect low oil pressure
00  NO 01  Yes
00
26
Low oil pressure warning setting
Psi00 99 45 Psi = 3 Bar
45 Psi
27
Low oil pressure Shutdown setting
Psi00 99 14.5 Psi = 1 Bar
15 Psi
28
Backup oil pressure switch sender installed? NO (Normal Open) or NC (Normal Close)
00  Installed but Not Used 01  NO 02 NC
02
29
Is the (TS-01) temperature sensor installed?
00  No 01  Yes
01
30
Temperature display (You can change from C to F under operation)
00  Centigrade 01  Fahrenheit
00
31
If the temperature sensor (TS-01) fails do I want a Warning or a Shutdown
00  Warning 01  Shutdown
00
32
High temperature protection activation time delay
02  99 sec
05
33
Use the temp sensor to detect high water temperature
00  NO 01  Yes
00
34
High temperature warning setting (Every unit is equal to 5 Degree Centigrade)
10  20 units 18 = 194 F
18
(90 ˚C)
35
High temperature shutdown setting (HIGH / HIGH) (Every unit is equal to 5 degree C)
10  24 units 21 = 221 F
21
(105 ˚C)
36
Is the (PS-01) temp sensor used to control the block heater
00  NO 01  Yes
00
37
Block heater max temp OFF setting
00 50 ˚C
25 ˚C
38
Additional Temp switch type sensor installed NO (Normal Open) or NC (Normal Close)
00 Not installed 01 NO 02 NC
01
39
Battery under voltage protection setting
08  23 Vdc
08 Vdc
40
Battery over voltage protection setting
13  35 Vdc
32 Vdc
41
Pre-heat timer setting
00  99 sec
06
42
Start attempt
01 09 Start Attempts
03
43
Cranking timer setting
2  30 sec
06
44
Magnetic Pick-up (MPU) used for verify engine start
00  No 01  Yes
00
45
Oil pressure sensor disengages starter (At 25 Psi)
00  No 01  Yes
00
Page 14
___________________________________________________________________________________________
14 GCU-3000
NO.
DESCRIPTION
SETTING
FACTORY
PRE-SET
46
Additional oil pressure switch sensor to confirming engine start
00  No 01  Yes
01
47
Set activation timer for the energize stop solenoid (Time needed to pull the energize to stop Solenoid)
02  99 sec
10
48
Method used to stop the engine (Energize to Stop or Energize to Start)
00  Energize to stop 01 Energize to start
00
49
Cool-down timer
00  60 min
00
50
Idle timer (Used only if governor capable)
00  60 min
00
51
Time in Warm up before connecting load contactors
00  99 sec
10
52
Activate the warning buzzer
00  NO 01  Yes
01
53
Fuel level indicator switch sender type NO (Normal Open) or NC (Normal Close)
00 Not used 01 NO 02 NC
00
54
Low fuel level activation time delay
02  99 sec
10
55
Low fuel level Warning or Shutdown
00  Warning 01 Shutdown
00
56
Defined Alarm1 (switch type) NO (Normal Open) or NC (Normal Close)
00 Do Not use Alarm1 01 NO 02 NC
00
57
Alarm1 activation time delay
02  99 sec
10
58
Alarm1 Warning or Shutdown
00  Warning 01  Shutdown
00
59
Defined Alarm2 (switch type) NO (Normal Open) or NC (Normal Close)
00 Do Not use Alarm2 01 NO 02 NC
00
60
Alarm2 activation time delay
02  99 sec
10
61
Alarm2 Warning or Shutdown
00  Warning 01  Shutdown
00
62
Service and maintenance reminder (Every unit is equal to 10 hrs) 20 x 10hr is a 200 hr reminder
00 99 (00 No Service reminder)
00
63
Voltage and Amps display setting
00 Fixed Display 01  Cycle Display
01
64
Also display each phase to Neutral (L1-N, L2-N, L3-N) In 4W 3Ø (Phase systems)
00  NO 01  Yes
01
65
Display only Hour Meter, Battery Volts, or Hertz at one time or cycle though all readings
00  Hour meter 01  Battery voltage 02  Hertz 03  Display all values
02
66
To retrieve the last 15 Failure event from memory program this line to Yes and press the Pen button
00  NO 01  Yes
00
67
Override shutdowns & start and stop the engine manually Useful when servicing the generator
00  Normal 01  Manual
00
68
Erase service log and maintenance warning signal and reset service timer
00  NO 01  Yes
00
69
Enable R486 remote control by KCU-XX module
00  NO 01  Yes
00
70
KCU-02 module address setting
00  None 01 99
00
71
KCU-02 baud rate setting
01  115200 02  57600 03  38400 04  19200 05  14400 06  9600 07  4800 08  2400 09  1200
03
Page 15
___________________________________________________________________________________________
GCU-3000 15
SECTION 4 : FAILURE WARNING DESCRIPTION
4.1 Failure Signal Reference Table
GCU-3000 is equipped with a large highly illuminating LCD screen were all of the failure notices are graphically and audible indicated with the built in failure warning alarm.
Universal Failure Icons Reference Table
WARNING
SIGNAL
DESCRIPTION
EXECUTION
Start failure
Stop
Under speed
Stop
Over speed
Stop
Emergency stop
Stop
Coolant overheat
Stop or Warning
Lubricant under
Pressure
Stop or Warning
Overload
Stop or Warning
Ac under voltage
Stop or Warning
Ac over voltage
Stop or Warning
Dc under voltage
Warning
Sensor failure
Stop or Warning
MPU signal failure
Stop
Low fuel level
Stop or Warning
Block Heater
In manual
Service
maintenance
Warning
You Defined 1
Stop or Warning
You Defined 2
Stop or Warning
4.2 Warning
When the GCU detects a problem during operation, but the situation do not pose immediate danger to the genset or the operating personnel, the GCU gives you a warning not a shutdown
With a Warning, the genset continues normal operation and provides power to the load. The warning message(s) continue to flash on the screen and the failure Signal / Alarm output is activated. The warning is automatically reset once the failure is corrected.
4.3 Shutdown
When a major failure is detects and it poses immediate danger to the genset and its personnel, the system shut-down immediately, the failure is noted on the screen activating the alarm. After the failure(s) are cleared, press the (OFF) button to confirm and reset the failure warning notice(s).
SECTION 5 : SPECIFICATION
ITEM
SPECIFICATION
DC input
9 36 Vdc
AC input
15 500 Vac (Ph-Ph)
AC frequency
50 60 Hz
MPU Signal Strength
+/- 2 to 70V Peak
MPU Input Frequency
100 10,000 Hz
Start signal
10 Amp @ 12/24 Vdc
Stop signal
10 Amp @ 12/24 Vdc
pre-heat signal
2.5 Amp @ 12/24 Vdc
Accessory “ON”
Output
2.5 Amp @ 12/24 Vdc
System Operating Signal
2.5 Amp @ 12/24 Vdc Failure Warning signal
2.5 Amp @ 12/24 Vdc
Preheat Signal
2.5 Amp @ 12/24 Vdc
Block Heater Signal
2.5 Amp @ 12/24 Vdc
Overload Signal
2.5 Amp @ 12/24 Vdc
Idle Control Conductor Capacity
1.0 Amp @ 12/24 Vdc DC Fuse
15 Amps (F4)
AC Fuse
1.0 Amps (F1 F3)
AC Voltage Potentiometer
1000 ohms
System Inactive Power Consumption
Below 7W
Operating Temperature
-20 to 70 ˚C
Relative Humidity
Below 95%
CT capacity
Above 2.5VA
Secondary Rated Current
5A Weight
1341 g +/- 2%
Page 16
___________________________________________________________________________________________
16 GCU-3000
SECTION 6 : TERMINAL & WIRING DESCRIPTION
6.1 Connection Detail
PIN No.
DESCRIPTION
ATTENTION
1
AC Input (L1)
Connect to AC Input Phase R
3
AC Input (L2)
Connect to AC Input Phase S
5
AC Input (L3)
Connect to AC Input Phase T
7
AC Neutral Input (N)
Connect to AC Input Phase N
8
Battery Positive ( V )
Connect to battery positive (12/24V)
9
Battery Negative ( V )
Connect to battery negative
10
CT Secondary for (L3)
Connect to Secondary Phase T (L3) Monitoring CT
11
CT Secondary for (L2)
Connect to Secondary Phase S (L2) Monitoring CT
12
CT Secondary for (L1)
Connect to Secondary Phase R (L1) Monitoring CT
13
CT (COMM) Terminal Input
Connect to External CTs Common Position
14
Starter Motor Signal Output
Connect to Starter Motor. Supply (+V) (Max. rated output 10 Amp)
15
Fuel Solenoid Signal Output
Connect to Fuel Solenoid or Fuel Valve Control. Supply (+V) (Max. rated output 10 Amp)
16
Overload Alarm Signal Output
Used to Trip the AC Output Breaker. Supply (+V) (Max. rated output 2.5 Amp)
17
Panel Illumination Output
Connect to the Panel Lamp (Max. rated output 2.5 Amp)
18
Normal Operation Auxiliary Output
Connect to the Operation Indication Lamp (Max. rated output 2.5 Amp)
19
Failure Signal Output
Used to Control External Alarm Buzzer. Supply (+V) (Max. rated output 2.5 Amp)
20
Preheat Signal Output
Used to Control the Internal Heater. Supply (+V) (Max. rated output 2.5 Amp)
21
Warm up Contactor Control Output
Connect to Warm up Contactor (Max. rated output 2.5 Amp)
22
You defined signal Input 2
Negative Input When Action
23
You defined signal Input 1
Negative Input When Action
24
Low Fuel signal Input
Connect to Fuel Level Switch
25
High Water Temperature Signal Input
Connect to water temperature switch
26
Low Oil Pressure Signal Input
Connect to oil pressure switch
27
Remote Start Signal Input
Connect to A.T.S or remote start terminal
28
Remote Start Signal Input
Connect to A.T.S or remote start terminal
29
Magnetic Pick-up Input
Connect to Magnetic Pick-up to monitor speed
30
Magnetic Pick-up Input
Connect to Magnetic Pick-up to monitor speed
31
Idle Speed Control Signal Output (CO.)
Connect to Electronic Governor for idle speed control
32
Idle Speed Control Signal Output (NC.)
Connect to Electronic Governor for idle speed control
33
Idle Speed Control Signal Output (NO.)
Connect to Electronic Governor for idle speed control
34
Block Heater Output
Connect to Block Heater (Max. rated output 2.5 Amp)
35
Voltage Potentiometer Output
Connect to Automatic Voltage Regulator (GAVR)
36
Voltage Potentiometer Output
Connect to Automatic Voltage Regulator (GAVR)
Page 17
___________________________________________________________________________________________
GCU-3000 17
6.2 Wiring Diagram
6.2.1 3 Phase 4 Wires System Wiring Diagram
AUXILIARY
BLOCK HEATER
STOP
START
OVER LOAD
RUNNING
PRE-HEAT
ALARM
AUX.2
AUX.1
LOW FUEL SW
BATTERY
+
GOVERNOR
OIL PRESSURE SW
REMOTE START
REMOTE START
TEMPERATURE SW
Pick-up
Meganetic
OIL PRESSURE SENDER(4C)
TEMPERATURE SENDER(5C)
IDLE CONTROL
IDLE CONTROL
IDLE CONTROL
1A
GCU3000 CONTROLLER
CONTACTOR
10A
34
15
14
10A
16
L3
LOAD
N
L1
L2
10A
17
18
19
20
21
10
13
22
8
9
23
24
11
7
12
30
26
25
27
28
29
1
3
5
1A
1A
VOLTAGE
J2
J1
33
31
35
36
G
L3
AVR
N
L1
L2
32
CT
CT
CT
Page 18
___________________________________________________________________________________________
18 GCU-3000
6.2.2 3 Phase 3 Wires System Wiring Diagram
VOLTAGE
L1
LOW FUEL SW
OIL PRESSURE SENDER(4C)
TEMPERATURE SENDER(5C)
IDLE CONTROL
IDLE CONTROL
IDLE CONTROL
Meganetic
Pick-up
REMOTE START
TEMPERATURE SW
REMOTE START
OIL PRESSURE SW
33
32
31
J1
J2
G
27
29
30
28
3
1
5
26
25
24
7
12
ALARM
RUNNING
PRE-HEAT
+
BATTERY
AUX.2
AUX.1
START
STOP
BLOCK HEATER
AUXILIARY
OVER LOAD
13
23
22
9
8
11
10
19
20
10A
18
21
15
17
16
34
10A
10A
14
LOAD
L3
L2
L1
36
35
AVR
1A
1A
1A
GCU3000 CONTROLLER
L3
L2
GOVERNOR
CONTACTOR
CT
CT
CT
Page 19
___________________________________________________________________________________________
GCU-3000 19
6.2.3 1 Phase 3 Wires System Wiring Diagram
AUXILIARY
BLOCK HEATER
STOP
START
OVER LOAD
RUNNING
PRE-HEAT
ALARM
AUX.2
AUX.1
LOW FUEL SW
BATTERY
+
OIL PRESSURE SW
REMOTE START
REMOTE START
TEMPERATURE SW
Pick-up
Meganetic
OIL PRESSURE SENDER(4C)
TEMPERATURE SENDER(5C)
IDLE CONTROL
IDLE CONTROL
IDLE CONTROL
1A
GCU3000 CONTROLLER
10A
34
15
14
10A
16
LOAD
L2
N
L1
10A
17
18
19
20
21
10
13
22
8
9
23
24
11
7
12
30
26
25
27
28
29
1
3
5
1A
1A
VOLTAGE
J2
J1
33
31
35
36
G
AVR
L2
N
L1
32
GOVERNOR
CONTACTOR
CT
CT
Page 20
___________________________________________________________________________________________
20 GCU-3000
6.2.4 Single Phase System Wiring Diagram
BLOCK HEATER
START
STOP
OVER LOAD
AUXILIARY
ALARM
RUNNING
AUX.2
+
BATTERY
PRE-HEAT
TEMPERATURE SW
REMOTE START
OIL PRESSURE SW
LOW FUEL SW
AUX.1
TEMPERATURE SENDER(5C)
OIL PRESSURE SENDER(4C)
REMOTE START
Meganetic
Pick-up
IDLE CONTROL
IDLE CONTROL
IDLE CONTROL
19
10A
14
10A
15
34
16
17
18
21
LOAD
L1
L2
28
GCU3000 CONTROLLER
8
20
10A
9
22
11
10
12
24
23
25
27
26
1A
5
7
1A
3
1
1A
VOLTAGE
J2
29
30
J1
36
35
31
33
32
L2
G
AVR
L1
13
CT
GOVERNOR
CONTACTOR
Page 21
___________________________________________________________________________________________
GCU-3000 21
SECTION 7 : TROUBLESHOOTING
SYMPTOM
SYMPTOM CONFIRMATION
EXECUTION
Connected to battery, but GCU does not respond
Check battery, If voltage is < 9 Vdc
Check the battery positive and negative
connection for reversed connection
Test DC connection terminal for bad contact
Check DC input protection fuse (F4)
None of the above
Change battery
Correct error
Correct error
Change fuse
Change another GCU-3000
GCU responds normally, but the starter motor does not respond
Check battery, If voltage is < 9 Vdc
Check the starter motor circuit for incorrect
connection
Test start output terminal for bad contact
Check if the starter motor assisting relay
comply with the battery requirement
Check starter motor assisting relay
Change battery
Correct error
Correct error
Change starter motor assisting
relay
Start motor responds normally, but fails to start, panel appears start failure
Check fuel level
Check stop settings
Check governor and actuator
Check if fuel solenoid for jamming
Add fuel
Reset to correct stop settings
Change governor or actuator
Change fuel solenoid
Starter motor disengages immediately during cranking, can not start successfully
Check battery, If voltage is < 9 Vdc
Check Starter motor circuit
Check for poor contact from the start signal
terminal
Check oil pressure sensor
Change battery
Correct error
Correct error
Change suitable oil pressure
switch or cancel oil pressure switch to confirm start
starts successfully, but starter motor does not disengage
Check AC voltage (5 500 Vac)
Check AC input protection fuse (F1, F2, F3)
Check for AC open circuit
Check oil pressure switch operation
Check starter motor operation
Change AVR
Change fuse
Correct error
Change to suitable oil
pressure switch
Change starter motor
When starter does not respond, GCU executes stop
Check oil pressure switch for NO, NC setting
Check oil pressure switch operation
Check oil pressure sensor operation
Correct internal setting
Change oil pressure switch
Change GCU exclusive oil
pressure sensor
preheat does not respond
• Check Preheat timer if equal to “0 Zero”
Check for preheat wiring open circuit
Correct internal setting
Correct error
MPU does not respond
Check MPU operation
Check open circuit in wiring
Check MPU signal strength if below +/- 2V
Change MPU
Correct error
Change MPU
Remote start signal initiated under AUTO, but does not start
Check if energize to start and energize to stop setting
Check remote start input signal
Check for starter motor open circuit
Check start signal output
Correct internal setting
Correct error
Correct error
Correct error
Page 22
___________________________________________________________________________________________
22 GCU-3000
SYMPTOM
SYMPTOM CONFIRMATION
EXECUTION
Emergency signal does not erase, can not be started
Check emergency stop button operation
Check for wiring open circuit
Change emergency stop
button
Correct error
Temperature can not be read under operation
Check temperature sensor type
Check for temperature sensor open circuit
Check if temperature sensor setting turned
off
None of the above
Change GCU exclusive
temperature sensor
Correct error
Correct internal setting
Change GCU exclusive
temperature sensor
Oil pressure can not be read under operation
Check oil pressure sensor
Check for open circuit
Check system setting if oil pressure sensor
deselected
Non of the above
Change GCU exclusive oil
pressure sensor
Correct error
Correct internal setting
Change GCU exclusive oil
pressure sensor
Frequency can not be read under operation
Check AC voltage (5 500 Vac)
Check AC input protection fuse (F1, F2, F3)
Change AVR
Change fuse
Under normal operation. The GCU load current value differs to the actual measured current value
Check internal CT if comply with the external CT ratio
Check external CT secondary if ratio equals to 5A
Check external CT circuit
Check system setting internal current reading
and adjustment setting if correct
Correct CT ratio setting
Change secondary CT to
value : 5A ratio CT
Correct error
Correct internal setting
Module appears overload failure during operation
Check system setting if overload failure setting is reasonable
Check internal CT if comply with the external CT ratio
Check external CT secondary if ratio equals to 5A
Check system setting if overload failure confirmation time is too short
Correct internal setting
Correct CT ratio setting
Correct internal setting
Correct internal setting
Module appears low oil pressure warning during operation
Check lubricant level
Check oil pressure switch operation
Check NO or NC setting
Check oil pressure sensor operation
Check for wiring open circuit
Add lubricant to correct level
Change oil pressure switch
Correct internal setting
Change GCU exclusive oil
pressure sensor
Correct error
Module appears high water temperature warning during operation
Check temperature
Check water temperature switch operation
Check temperature sensor operation
Check for wiring open circuit
Correct error
Change water temperature
switch
Change GCU exclusive temperature sensor
Correct error
Page 23
___________________________________________________________________________________________
GCU-3000 23
SYMPTOM
SYMPTOM CONFIRMATION
EXECUTION
Module appears over voltage or under voltage warning during operation
Check AC voltage
Check over voltage and under voltage setting
Check for AC open circuit
Check AC power input protection fuse (F1,
F2, F3)
Change AVR
Correct internal setting
Correct error
Change fuse
Module appears over speed or under speed warning during operation
Check governor and actuator operation
Check MPU operation
Check AC power input protection fuse (F1,
F2, F3)
Check 50/60 Hz RPM setting
Check over speed or under speed setting
Change governor or actuator
Change MPU
Change fuse
Correct internal setting
Correct internal setting
can not shut off successfully when switching to OFF during operation
Check cool down setting if over delayed
Check stop timer setting if too short
Check if energize to start and energize to
stop setting
Check for stop open circuit
Check governor and fuel solenoid operation
Correct internal setting
Correct internal setting
Correct internal setting
Correct internal setting
Change governor or fuel
solenoid
Single phase system Voltage valued normal, but module appears under voltage failure warning
Check system phase setting (1 Phase or 3 Phase)
Check under voltage setting
Check AC power input protection fuse (F1,
F2, F3)
Correct internal setting
Correct internal setting
Change fuse
Contactor can not execute, under normal operation
Check idle speed timer setting for over delay
Check load contactor
Check wiring for open circuit
Correct internal setting
Change load contactor
Correct error
Loading...