
GCU-20 
Automatic Engine Control Unit 
WARNING 
Disconnect all electric power to the machine before 
installation. 
Protection Functions 
Engine fail to start  
Engine tries 3 times to start 
Engine Low Oil Pressure Protection 
Shutdown activated after 3 seconds 
Oil Pressure Switch Type NO or NC 
Auxiliary Shutdown 
Shutdown activated after 3 seconds delay by NO contact 
Engine High Water temperature Protection 
Shutdown activated after 3 seconds delay by NO contact 
Engine Over-speed Protection 
Shutdown activated after 3 seconds 
50 Hz activated at 55 Hz – 60 Hz activated at 66 Hz 
Engine Under-Speed Protection 
Shutdown activated after 5 seconds 
50 Hz activated at 45 Hz – 60 Hz activated at 54 Hz 
No Speed Signal Present Protection 
Shutdown activated after 5 seconds (MPU use only) 
Icon Reference Table 
Low Oil Pressure Alarm 
Auxiliary Alarm (Flashing) 
High Water Temperature Alarm 
Wrong speed Alarm 
No Speed Signal Alarm (Flashing) 
Engine Running Indicator 
Engine IDLE Indicator (Flashing) 
Engine Pre-Heat Indicator 
Physical Dimensions 
Mounting Pattern 
Installing Panel 

Auxiliary Alarm (Flash)
Pre-Heat
Wrong Speed
Engine IDLE (Flash)
Engine Running
No Speed Signal (Flash)
Over Cranking
High Temp.
Low Oil Pressure
Model GCU-20
A
B
D
C
E
MPU Indicator
Speed Sensor
Connector
Potentiometers & DIP Switches Detail 
Adjustments 
On the back of the GCU-20 we have five adjustment pots that 
modify time delay functions. 
● 
A Engine Pre-Heat  
Adjustable from 2 to 30 sec 
●
 B Energized to STOP
  Adjustable from 1 to 15 sec 
● 
C Engine Cool-down 
Adjustable from 0 to 300 sec 
● 
D Starter Cranking time
  Adjustable from 1 to 15 sec 
● 
E Engine Idle (Governor) 
Adjustable from 0 to 300 sec 
Function Setting 
Also In the back, the GCU-20 we have six dip / switches that 
set specific working parameters. 
SW 1 Oil Pressure Switch Used for Crank Disconnect 
ON - Disable  OFF - Enable 
SW 2 Oil Pressure Switch Type 
ON - Normal Open  OFF - Normally Close 
SW 3 Engine Stop Setting 
ON - Energize to Start OFF - Energize to STOP 
SW 4 Generator Frequency (Ignore if it is a Water Pump) 
ON – 50 Hz  OFF – 60 Hz 
SW 5 MPU Setting 
ON - Enable (used to Program Speed)  
OFF - Disable 
SW 6 Speed Signal Type 
ON - Use MPU for speed sensing  
OFF - Use AC generator frequency for speed sensing 
Lamp Test Function 
Applying battery (+) signal to terminal 1 (Lamp Test Terminal) 
the GCU-20 turns on all the front panel LEDs and 
annunciator lamps. 
+
Battery
10A
Model GCU-20
No Speed Signal (Flash)
Engine Running 
Engine IDLE (Flash)
Pre-Heat
Wrong Speed
J1 J2 J4J3
Lamp Test 
Low Oil Pressure
High Temp.
Over Cranking
Auxiliary Alarm (Flash)
Remote Annunciator
J7J6J5
Using with MPU 
If you use the MPU for speed sensing instead of the 
generator frequency you must set (Switch 6 to ON), and 
depending on flywheel size (different generators has a 
different MPU frequencies). This nominal frequency MUST 
be set FIRST. 
It is easy, if you follow the procedure below. 
Step 1:Move Switches 5 & 6 to “ON” before starting engine. 
Step 2:Start engine, by moving 
panel switch to “TEST” 
(Manual Start) 
Step 3 : Run the engine 
normally at its rated 
speed. (60 or 50 Hz) 
or pump rated RPM 
Step 4:Now quickly move 
Switch 5 to “OFF” 
Step 5:When MPU LED turns 
GREEN  setup  is 
complete. 
MPU Setup failure 
If setup fails, the control module 
shuts down the engine and 
immediately flashes ON all the 
LEDs on the front panel. 
Check MPU and wiring before  
repeating this setup again. 
WARNING 
If the MPU signal is used for speed sensing (Switch 6 
ON), but MPU frequency set up has not yet been 
completed the MPU indicator will flash RED and the 
engine will not run under any condition. 
However, if the user tries to start the engine a “No 
Speed Signal” warning LED will continue to flash 
indicating that the user should repeat the set up of the 
MPU frequency setting or switch to generator 
frequency sensing. 
Select Switch
Start
Remote
OFF
Auto
Test
Batt(-)
Select Switch
Remote
Batt(-)
Start
OFF
Test
Auto

Alternator Input Frequency 
Remote start signal input 
Fuel / Stop signal output 
Annunciator signal output 
Annunciator common used only 
Don’t use as main ground connection 
Accessory ON signal output 
TEST Operation 
To initiate a start sequence moves the external toggle switch 
to the on TEST (Manual Start) position. 
First, the pre-heat timer begins by energizing terminal 12. If 
Pre-Heat is not uses, simple no not use this terminal. 
Second, the Engine Fuel Solenoid energizes terminal 11, 
and idle terminals 22. 
Third, after a 1 sec. delay, the starter motor energizes, and 
the engine cranks for the duration of the crank timer. 
Fourth, after the engine (start / fires), the starter motor 
disengaged and locked out by using the 18-Hertz signal from 
the generator or the signal from the MPU. Alternatively, the 
oil pressure switch can serve as an additional back up crank 
disconnect. 
Fifth, after the engine fires and if the Engine Idle option is 
used, the ENGINE RUNNING LED will continuous flashing in 
idle indicating the status is IDLE. (If engine idle is not used set adjustment, “E” full counterclockwise). 
Sixth, if the engine does not start the first time the module 
will try again to start the engine 2 more times and stop after 
the third try. 
If the generator fail to start, move the select 
switch to the OFF (Reset) position, Find out 
why the engine failed to start before making 
any more start attempts. 
Seven, after the generator starts, the module allows Oil 
Pressure, Engine Temperature and engine speed to stabilize 
without triggering any faults for 20 seconds. 
Moving the toggle switch to the OFF position, Stops the 
engine immediately. 
Automatic (Remote Start) Operation 
In the “AUTO” mode, the GCU-20 control module monitors 
input terminals 8 & 9 for a “REMOTE START” signal. Should  
a “REMOTE START” signal be detected a start sequence 
similar to previous manual start cycle is initiated. 
Removing the Remote Start signal automatic activates the 
Cool Down Timer and after the Cool Down ends, the Fuel 
Solenoid is (de-energized or energized as the case may be) 
bringing the generator or engine to a complete stop. 
Should the Remote start signal be re-activated during the 
cooling down period, the set will immediately return to normal 
operation. 
NOTE 
Even if the generator is executing Engine Cool down 
Timer, The Module protection system remain in operation 
and if any failure occurs, the module bypasses the Engine 
Cooling Timer shutting down the generator immediately. 
OFF Operation 
The OFF position places the module into its Stop or Reset 
mode. 
In RESET mode the operator must clear any fault conditions. 
Selecting OFF when the engine is running automatically 
STOPS the generator. The fuel supply will be removed and 
engine will be brought to a standstill. Should a remote start 
signal be present while operating in this mode, a remote start 
will not occur. 

Wiring Diagram Using Generator AC Frequency Sensing 
Wiring Diagram Using MPU Frequency Sensing 
Please link to http://www.kutai.com.tw for detailed manual 
17
L1
L2
L3
N
20
18 
19
23
Relay
Start
2 
3 
4
21
1
22
15 
16
14
13
Relay
Stop
65 987
L2
L3
LOAD
N
L1
RW
G
Pre-Heat Relay
RS
RF
Start Relay
Batt(-)
Select Switch
Fuel / Stop Relay
Auto
Test
OFF
Remote
Start
RP
Common(-)
Warm-up Relay
Alarm Lamp
Engine Run Lamp
Wrong Speed Lamp
Over Crank Lamp
High Temp. Lamp
Low Oil Lamp
J3
RW
J1 J2
Remote Annunciator RA-20
J4 J5 J6 J7
Battery
+
10A
RA
RI
Batt(+)
Lamp Test SW
Low Oil SW
High Temp. SW
Auxiliary SW
Acc. ON Relay
Idle Relay
Model GCU-20
Wrong Speed Lamp
High Temp. Lamp 
Over Crank Lamp
Engine Run Lamp
Common(-)
Alarm Lamp 
Warm-up Relay
1
Auxiliary SW 
High Temp. SW
Lamp Test SW
Low Oil SW
2
4
3
Acc. ON Relay
Batt(+)
23
21
22
Start 
Relay
Stop 
Relay
Low Oil Lamp
Model GCU-20
Batt(-)
Remote
J5 J7J6J2 J4J3J1
19 
20
17 
18
16
15
13 
14
Idle Relay
Start
Battery
+
10A
Start Relay
Fuel / Stop Relay
Pre-Heat Relay
Test
Auto
OFF
Select Switch
Magnetic Pick-Up
5 6 7 8 9
RA
RI
RS
RF
RP
RW
L3
L1
L2
N
L3
L2
L1
N
RW
Remote Annunciator RA-20
LOAD
G