Kutai electronics EA16 Operation Manual

Page 1
EA16
Generator Automatic Voltage Regulator
Operation Manual
Universal 16Amp Self Excited Automatic Voltage Regulator
for use in 220 / 380 / 440 / 480 VAC brushless generators
with paralleling compatibility
Headquarters : No.3, Lane 201, Chien Fu ST., Chyan Jenn Dist., Kaohsiung, TAIWAN Tel : + 886-7-8121771 Fax : + 886-7-8121775 URL : http://www.kutai.com.tw
Page 2
______________________________________________________________________________________ 2 EA16
1. SPECIFICATION
Sensing Input
Voltage 170 ~ 510 VAC, Single Phase 2 wires Voltage is DIP Switch selectable Frequency 50/60 Hz, DIP Switch selectable
Power Input
Voltage 60 ~ 300 VAC, Single Phase 2 wires
Output
Voltage Max. 90 VDC @ 240 VAC input Current Continuous 16A Intermittent 20A for 10 sec Resistance Min. 5 ohm
Voltage Regulation
< ± 0.5% ( with 4% engine governing )
Voltage Build-up
Residual voltage at AVR terminal > 5 VAC
Thermal Drift
0.03% per °C change in AVR ambient
Load Current Compensation 1A or 5A Max. 7% @ PF0.5 DIP Switch Selectable
Analogue Voltage Input
Max. ±5VDC. ±10% @ ±3VDC
Over Excitation Protection
Max Output DCV 95% 20sec
External Volts Adjustment
± 5% with 2K ohm 1 watt trimmer
Unit Power Dissipation
Max. 10 watt
Under Frequency Protection ( Factory Setting )
50/60 Hz DIP SW selectable
Soft Start Ramp Time
2 sec.
Dimensions
156mm L * 106mm W * 43mm H
Weight
450g ± 2%
The EA16 AVR is an update of the EA15A AVR. It is similar to the original EA15A in power and voltage sensing capabilities but with new enhanced paralleling functions; the user can now select the CT inputs either 1 & 5 Amp or use new A1 & A2 analogue signal inputs terminals for use with PLC paralleling controls. It has new over-voltage excitation safety circuits to prevent damage caused by the accidental detachment of the sensing wires or irregularities on the generator’s excitation circuits.
High Temperature
ATTENTION
1. AVR can be mounted directly on the engine, genset, switchgear, control panel, or any position that will not affects operation. For dimension reference, please see Figure 1.
2. All voltage readings are to be taken with an average-reading voltmeter Meggers and high-potential test equipment must not be used. Use of such equipment could damage the AVR.
3. Secure all wiring connection. Do not install AVR at a place with high vibrations to prevent loose connections. For safety do not touch the heat sink while in operation.
4. Fuse specification : 16A / 250V slow blow type.
5. Terminal"Fast-On" terminals 6.35mm (1/4 inch) & With 4mm crimping terminal.
Figure 1 Outline Drawing
UNIT :
mm
Page 3
______________________________________________________________________________________ EA16 3
2. CONNECTION TERMINAL
1. P1, P2Power Input Terminals from 60 to 300VAC 50/60Hz -16A rated.
2. F+, FMaximum Output current 16A.
3. VS1, VS2:Voltage sensing input terminals, Volts selected using DIP SW1 for 220V or 400V.
4. K, LLoad Current Compensation (Droop), CT secondary current input selected by using DIP SW 1A or 5A (If droop not used leave terminals open).
5. VR1, VR2:External Voltage trim use, 2K Ohms 1 watt trimmer for ±5% voltage adjustment. Keep terminals shorted when not in use.
6. A1, A2Analogue Voltage Input terminals used for Power Factor correction from a external PLC­The PLC controls provides a DC voltage signal to adjust the generator voltage. Max. Adjustment range is ±5VDC. Keep terminals open when not used.
7. DIP Switch
SW1OFF 220VAC (170 to 260VAC) ON 400VAC (340 to 510VAC)
SW2OFF CT Secondary Input 1A ON CT Secondary Input 5A
SW3OFF Generator Frequency 60Hz, 52 ~ 61Hz Adjustment
ON Generator Frequency 50Hz, 42 ~ 51Hz Adjustment
SW4OFF Over excitation protection enabled ON Over excitation protection disabled
8. LED Indicator
U/FUnder Frequency Indicator O/EOver Excitation Indicator
3. ADJUSTMENT AND SETTING
1. TRIM works together with a bias voltage applied to terminals A1 and A2. This signal is supplies by an external Power Factor Paralleling PLC. Use the TRIM potentiometer to adjust the DC voltage input that controls the level of the generator’s output voltage. When set counter-clockwise the control level is zero, and if moved clockwise the maximum control range is 10%. The signal connected to A1 and A2 can be unipolar (0,+) or bipolar (+,). Check with the manufacture of the Paralleling control PLC.
2. DROOPSelect switch K or L pending on the secondary current of the CT that you are using. Voltage droop works when the CT and the AVR senses that the output of the generator voltage and current waveforms are out of synch and the AVR droops the output voltage of the generator to correct it.
3. STABIf the generator output voltage oscillate, adjusting the STAB potentiometer will stabilize the output voltage, over adjustment will result in high voltage variation when load is applied. Use an analog type multimeter when making this adjustment. Connect the meter to terminals F+ and F and slowly adjust STAB potentiometer to the point when the pointer stops moving.
4. VOLTMove to set the generator output voltage. Set DIP Switch 1 to the generator working voltage.
Set SW1 to OFF (220V) for use from 170 to 260V Set SW1 to ON (400V) for use from 340 to 510V
When using and external VR set it to the central
position and adjust the AVR VOLT trim to the rated voltage.
NOTE
If the external VR is not used, short terminal VR1 and VR2.
5. U/FUnder Frequency protection setting.
At 60Hz U/F factory set at 55Hz At 50Hz U/F factory set at 45Hz
To adjust the U/F setting, select the correct
system frequency, start engine and adjust engine speed to the required U/F frequency (for example 55Hz or 45Hz), slow adjust U/F potentiometer until the U/F red LED turn ON, returning the engine speed to normal turn the LED off.
Function of the Under Frequency trim pot
During start up or shutdown, the engine speed
changes going over or under its rated RPM (Hz). This AVR has an Under Frequency circuit to protect the AVR and exciter; you do not need to disconnect the AVR when idling the engine.
If load is higher than the generator’s capacity, the
Under Frequency activates, reducing the generator’s voltage preventing generator overload.
Page 4
______________________________________________________________________________________ 4 EA16
6. Over Excitation Protection
This AVR has over Excitation Protection preventing the generator from working under unusually high excitation. Excitation Protection includes generator overload, accident removal of sensing wires, and incorrect voltage setting. When problems occur, the AVR will gradually shutdown the excitation voltage to the minimum residual voltage. If the O/E LED turn ON and stays ON, you need to reset the AVR by shutting the engine for 10 seconds. When working the generator in parallel this protection is not required, the user can disable this function by switching DIP switch SW4 to ON position, vice versa.
4. NOTICE OF USE
1. Installation Notice(Refer to Figure 2 and 4).
Only, a trained professional can Installation, calibrate and inspections this AVR.
Install this AVR inside the generator enclosure away from moisture, corrosion and from any easy to reach area.
2. Generator Operation Notice
During operation, the temperature on the surface of the AVR can reach higher the 60 °C / 140°F.
“DANGER” When the AVR is working never touch or ground the heat sink on the AVR. The AVR heat sink is an electrically live terminal.
A warning sticker is in place on top of the heat
sink.
5. FIELD FLASHING
When operating this AVR for the first time, the polarity of the residual magnetism may be reversed or too weak to achieve the necessary build-up on the regulator. If reversing the field connections does not induce build-up, and the residual voltage is less than 5 VAC, shut down the Prime-mover and proceed with the following steps
1. Stop the generator and disconnect the field wires
(F+ and F), apply a DC Voltage using a batteries positive terminal to F+ and the negative terminal to F, using a current-limiting resistor of 3~5 ohms 20 watt.
2. Allow approximately 3 seconds before removing
the battery.
3. Disconnect the AVR AC power input terminals and restart the generator, re-measure the residual voltage. If this voltage is greater than 5VAC, reconnect voltage regulator, and voltage build-up should be successful. If measured less than 5VAC, repeat steps 5.1 and 5.2.
4. If repeating steps 5.1 and 5.2 does not result in generator voltage build-up, and residual is greater than 5VAC, replace with a new voltage regulator.
CAUTION
Over excite may damage the AVR or the exciter.
Page 5
______________________________________________________________________________________ EA16 5
EA16A
EXT. VR
K
A1
VR1 VR2
Field
P2P1 VS1F- VS2F+
A2
L
GEN
T
R S
N
Figure 3 220V Connection
P1
VR1
EXT. VR
Field
GEN
VR2
A1
A2
VS1F+P2 F- KVS2 L
R
T N
S
Field
EXT. VR
VR1P1VR2
A2
A1
VS1F-P2 F+ LVS2 K
GEN
T N
S
R
EA16A
EA16A
GEN
EXT. VR
K
VR1 VR2
A1
F+P2P1 VS1F- VS2A2L
T N
R S
EA16A
Field
Figure 2 Paralleling Connection Figure 4 380 / 480V Connection
Field
EXT. VR
EA16
VR2VR1
A2
A1
F- VS1P1 P2 F+ LVS2 K
GEN
T N
S
R
Aux.
Winding 60~300v
Figure 5 Auxiliary Winding
Page 6
______________________________________________________________________________________ 6 EA16
6. TROUBLE SHOOTING
SYMPTOM CAUSE CORRECTION
Residual voltage below 5VAC Reference from 5. Field Flashing F+, F polarity reversed F+ and F reverse the connection F+, F, P1, P2, VS1, VS2 not
connected
Reference from Figure 3 and 4 connection
Burnt fuse Change fuse 16A 250V Ext. Switch (Breaker) not turned on Switch on (ON)
Voltage does not
build up
Engine RPM under speed Increase engine speed / frequency above25HZ Poor adjustment is made Read start procedure carefully and adjust again U/F protection activated Increase generator speed
Out voltage low
U/F activated / Incorrect voltage selection
Read user’s manual to select correct voltage
Poor adjustment is made Read start procedure carefully and adjust again
Out voltage high
Incorrect voltage selection Read user’s manual to select correct voltage Poor adjustment is made Read start procedure carefully and adjust again
Out voltage instable
Field voltage requirement lower the rang of regulator
Inquire our distributor to solve
Use only original supplied spare protection fuse for fuse replacement.
Please accept our sincere apology if any modification in performance, specification or appearance is made without prior notice.
Loading...