Kutai electronics EA05A-B Operation Manual

Page 1
EA05A-B
Generator Automatic Voltage Regulator
Operation Manual
Self Excited Automatic Voltage Regulator
5 Amp AC110V AVR For General Generators
Headquarters : No.3, Lane 201, Chien Fu ST., Chyan Jenn Dist., Kaohsiung, TAIWAN Tel : + 886-7-8121771 Fax : + 886-7-8121775 URL : http://www.kutai.com.tw
Page 2
______________________________________________________________________________________ 2 EA05A-B
1. SPECIFICATION
Sensing Input
Voltage 95~130 VAC, 1 phase2 wire Frequency 50 / 60 Hz, DIP switch selectable
Power Input
Voltage 50 ~ 150 VAC, 1 phase 2 wire
Output
Voltage Max. 45 VDC @ 120 VAC input Current Continuous 5A Intermittent 7A for 10 sec Resistance Min. 15 ohm Max. 100 ohm
Voltage Regulation
< ± 0.5% ( with 4% engine governing )
Voltage Build-up
Residual voltage at AVR terminal > 5 VAC
Thermal Drift
0.03% per °C change in AVR ambient
External Volts Adjustment
7% with 1K ohm 1 watt trimmer
EMI Suppression
Internal electromagnetic interference filtering
Unit Power Dissipation
Max. 8 watt
Under Frequency Protection (Factory Setting)
60 Hz system presets knee point at 55 Hz 50 Hz system presets knee point at 45 Hz
Soft Start Ramp Time
3 sec.
Dimensions
101mm L * 69mm W * 47.5mm H
Weight 183g ± 2%
2. WIRING
When generator supply is over load, N phase will be different with the sharing load by 3 phases (load imbalance). Hence, the voltage from N phase to 3 phases (R.S.T.) will be altered. When the rated voltage of the traditional single input’s AVR is above 110V, it will increase the voltage drift rate by using N phase as the detective input. It will also cause the voltage imbalance.
EA05A-B can improve the above situation, and increase the generator’s rated voltage usage space, such as 110V. We can all detect by the “phase voltage”.
1. When the rated phase voltage of the generator is 110VAC, the input terminals B, C and sensing terminals A, C can join together (as show as figure3. It’s the original setting).or connect independent.(as show as Figure3).
2. When the rated phase voltage of the generator is 110V, the input terminals B, C and sensing terminals A, C must separate connect the wiring (as show as Figure 3). The voltage between B and C must not be over 300 VAC.
3. F+ F- terminals connect to the generator field. ( J and K )
FEXT.VR is the potentiometer (1K 1W). These two terminals must be by-pass when external potentiometer is needless.
P.S. : A, B, C, F+ F- the usage of wire gauge are
AWG16 or 1.25mm2 85°C above 600V.
The EXT.VR connection wires must be made of isolated wiring.
3. ADJUSTMENTS
The voltage setting for 110V and the frequency setting for 50/60HZ is show in Figure3. Please check the voltage/frequency selector setting is correct before start the generator.
CAUTION :
The generator or AVR may be damaged if the voltage / frequency selector setting is incorrect.
UFRO DIP: Close - please refer to solid curve in Figure5. Open - please refer to dotted curve in Figure5.
1. Before you turn on the generator, please turn the
Page 3
______________________________________________________________________________________ EA05A-B 3
voltage adjustment and stability adjustment full anti-clockwise. After the generator is on and run stably, turn the voltage adjustment clockwise to reach the required out voltage. (If there is an external potentiometer, turn the external potentiometer to the middle position before adjust internal voltage potentiometer.)
2. Adjust “Stability Adjustment” clockwise slowly to change the feedback time between AVR and the generator. If the adjustment is too big, it might cause the voltage instable. If too small, the load voltage will change too much at heavy load. Our suggestion is to trace by the multi-meter DCV. To adjust “stability adjustment”, you just need to make the multi-meter waving smaller. It can also improve the full load’s voltage drift rate.
4. FIELD FLASHING
When the regulator is operated with the generator for the first time, the polarity of residual magnetism may be reversed or too small to achieve the necessary build-up voltage for the regulator. If reversing the field connections does not induce build-up, and the residual voltage is less than the specified value of 5 VAC, shut down the Prime-mover and proceed with the following steps :
1. With the Prime-mover at rest and the regulator’s
field output wires disconnected, apply a DC source ( NOT grounded ) of not more than 3~12 VDC with Positive to F+ and Negative to F-, in series with a current-limiting resistor of 3~5 ohms 20 watt. (The set battery is a suitable source.)
2. Allow approximately 3 seconds before removing the DC source.
3. With the voltage regulator disconnected ( wires 3 and 4 ), start the prime mover and measure the “ residual ” voltage available at the auxiliary winding. If this voltage is greater than 5 VAC, reconnect voltage regulator, and voltage build-up should be successful. If less than 5 VAC is measured, repeat field flashing procedure.
4. If repeating steps a. and b. does not result in generator voltage build-up, and residual is greater than 5 VAC, replace voltage regulator.
WARNING
This Automatic Voltage Regulator is not equipped with loss-Sensing Protection function / Over Excitation Protection. An additional Over-Voltage Protection device for load may be required to avoid possible damage to the equipment or severe personal injury or death.
5. TROUBLE SHOOTING
SYMPTOM
CAUSE CORRECTION
Engine speed is too low.
Please refer to the Generator Manual.
Residual voltage is too low.
Please refer to the section introduction of excite.
B,C,F+,F- wires are not connected well. Please refer to Figure 3.
Voltage does not
build up
Defective Generator. Please refer to the Generator Manual. The input wiring of A,B,C are not correct. Please refer to Figure 3. Check the external potentiometer. Check wiring and potentiometer. Under frequency. Please refer to the Generator Manual. The exciter does not match the AVR. Please refer to the Generator Manual.
Out voltage low
The voltage / frequency selector setting is not correct.
Please refer to Figure 3.
Fuse blown
The exciter flash is too large or wiring doesn’t connect well.
Please refer to the Generator Manual. Please refer to Figure 3.
A,C terminals are not connect or wiring incorrect.
Please refer to Figure 3.
Out voltage high
The voltage / frequency selector setting is not correct.
Please refer to Figure 3.
Out voltage instable
Stability Adjustment doesn’t adjust well.
Please refer to the section introduction of Adjustment.
Use only original supplied spare protection fuse for fuse replacement.
Page 4
______________________________________________________________________________________ 4 EA05A-B
6. FIGURE AND SIZE
Please accept our sincere apology if any modification in performance, specification or appearance is
made without prior notice.
Flash with Battery
Figure 3
20
40
60
80
100
120
(% OF NOMINAL)
GENERATOR OUTPUT VOLTAGE
(% OF NOMINAL)
GENERATOR OUTPUT VOLTAGE
FREQUENCY (HZ)
0
40
20
60
10
20
30
40 6050
80
100
120
50HZ
60HZ
SOFT START (V/S)
0
1
2
STABILITY
VOLTS
U/F
UFOR DIP
ON
1 2 3
3ON1 2
220V/60HZ
220V/50HZ
N R S
T
G
~
Field
C
B A F+
F-
1 32
ON
U/F
STAB
VOLT UFRO
DIP
1000 OHM
EXT. VR
Frequency Selector
Volt /
Figure 1 Figure 2
ON
Field
STAB
U/F
VOLT
C
A F+
F-
B
1000 OHM
321
DIODE
3~5 OHM
SWITCH
BATT.
UFRO
DIP
EXT. VR
Frequency Selector
Volt /
110V / 50HZ
110V / 60HZ
2 31
ON
220V/60HZ
21 3
220V/50HZ
ON
110V / 50HZ 110V / 60HZ
Volt/Frequency Selector
Figure 4
Frequency Compensation Curves
Figure 5
Soft Start Curve
Figure 6
Loading...