Analog / Digital AVR, Single-phase / Three-phase Voltage detection, 8 Amp,
Voltage Regulator for use with Auxiliary Winding, PMG, and self-excited
(SHUNT) brushless generators.
Can be used together with KUTAI Auxiliary Excitation Booster module to
increase motor starting capacity of shunt generators.
ADVR-083
Universal Hybrid Analog-Digital
Voltage Regulator Operation Manual

Sensing Input (E1, E2, E3) Average Reading
Voltage and Frequency DIP switch settings
1 phase (E1, E2) / 3 phase (E1, E2, E3)
Less than +/- 0.5% (with 4% engine governing)
Less than 20 milliseconds
Voltage 60 300 Vac, 1 phase / 3 phase
1 phase ( X1, X2 ) / 3 phase ( X1, X2, Z2 )
Built-in Harmonic suppression
Voltage 60 300 Vac, 1 phase 2 wire
Under Frequency Protection (Factory Preset)
50 Hz system preset knee point at 45 Hz
Excitation Output (F+, F-)
60 Hz system preset knee point at 55 Hz
110V 1 phase Continuous 63 Vdc 8A
Max. 90 Vdc 10A for 10 secs.
Over Excitation Protection
220V 1 phase Continuous 125 Vdc 8A
25 105% of Input Power (adjust with EXC pot.)
Max. 180 Vdc 10A for 10 secs.
O/E acts after 10 sec. delay. The OE function can be
220V 3 phase Continuous 150 Vdc 8A
turned OFF by adjusting EXC. clockwise to max.
Max. 215 Vdc 10A for 10 secs.
Resistance Min.15 ohms, Max.100 ohms @ 220V
Fuse Spec. Slow blow 5 x 20 mm 10A
Less than 3% from -40 to +70 ˚C
External Voltage Adjustment (VR1, VR2)
Under-Frequency Knee Point Thermal Drift
Max. +/- 10% @ 1K ohm 1 watt potentiometer
Less than +/- 0.1 Hz from -40 to +70 ˚C
Quadrature Droop Input (S1, S2)
CT N:5A or N:1A (DIP switch setting)
Operation Temperature -40 to +60 ˚C
Burden : greater than 5VA
Storage Temperature -40 to +85 ˚C
Sensitivity +/- 7% @ PF +/- 0.5
Relative Humidity Max. 95%
(Can be adjusted through Droop setting)
Analogue Voltage Input (A1, A2)
Input resistance greater than 2K ohms
150.0 (L) x 135.0 (W) x 61.0 (H) mm
Input Range +/- 5 Vdc or 0 10 Vdc
5.91 (L) x 5.31 (W) x 2.40 (H) inch
Sensitivity Max.1 Vdc = 5% change in output voltage
(Can be adjusted through Trim setting)
Greater than 5 Vac, 25 Hz residual volts input power
ATTENTION
In order to avoid permanent damage to the AVR confirm that the voltage sensing input setting matches
the generator before use (DIP switches SW5 and SW6)
SECTION 1 : SPECIFICATION
___________________________________________________________________________________________
2 ADVR-083

130.0 [5.12"]
150.0 [5.91"]
21.5 [0.85"]
61.0 [2.40"]
135.0 [5.31"]
115.0 [4.53"]
5.5 [0.22"]
SECTION 2 : OUTLINE / SIZE / INSTALLATION REFERENCE
___________________________________________________________________________________________
ADVR-083 3

VOLT:Voltage Adjustment
Sensing input voltage range set by DIP
switches SW5 and SW6
X1, X2:Single Phase Power Input
Z1, Z2:Auxiliary Power Input
X1, X2, Z2:Three Phase Power Input
Remark : X1 and Z1 are the same point
(internally shorted)
S1, S2:Quadrature Droop Input
Sensitivity +/- 7% @ PF +/- 0.5
CT N : 5A or N : 1A set by DIP
switches SW3
VR1, VR2:External VR Input
Must be shorted when not in use
A1, A2:Analog Voltage Input
Max. Input +/- 5 Vdc or 0 – 10 Vdc
DROOP:DROOP Adjustment
(Parallel operation)
Droop Adjustment
Used only during parallel operation
F+, F-:Excitation Output
Connects to generator excitation field
E1, E2:Single Phase Sensing Input
E1, E2, E3:Three Phase Sensing Input
Single Phase / Three Phase sensing set by DIP
switch SW7
EXC.:Over Excitation Protection Adjustment
25 105% of Rated Excitation (Adjustable)
Adjust EXC. potentiometer clockwise to
Max. to turn OFF O/E protection
STAB:Stability Adjustment
Stability range set by DIP
switches SW1 and SW2
U/F:Under-Frequency LED
Under-Frequency Protection status
(ON = Activated)
DIP:U/F Protection Voltage Slope
Adjustment
When U/F protection is activated the voltage
drop ratio can be adjusted by DIP switch.
Adjustment range 3 to 6 V/Hz
UF:Under Frequency Adjustment
Under frequency knee point setting
50 Hz system:40 to 50 Hz adjustable
60 Hz system:50 to 60 Hz adjustable
O/E:Over Excitation LED
Over Excitation Protection status
(ON = Activated) Excitation Output
will be reduced after a 10 sec delay
TRIM:Analogue Voltage Input Adjustment
Max. Input +/- 5 Vdc or + 10 Vdc
Sensitivity 1 Vdc for 5% (adjustable)
ADVR-083
ON
OFF
SW
3
CT 5A CT 1A
4
50 Hz 60 Hz
7
1Φ SENSING 3Φ SENSING
1. OFF 2. OFF <90KW
1. OFF 2. ON 90-500KW
1. ON 2. ON >500KW
5. OFF 6. OFF 110V
5. ON 6. OFF 220V
5. OFF 6. ON 440V
SECTION 3 : DIP SWITCH PROGRAMMING & VR ADJUSTMENTS
___________________________________________________________________________________________
4 ADVR-083

ADVR-083
~
G
R
S
N
T
Field
potentiometer
1k /1W
External
ADVR-083
~
G
R
S
N
T
Field
potentiometer
1k /1W
External
Figure 3 Self-Excited (SHUNT) 110/220 Vac
Single phase / Three phase
Figure 4 Self-Excited (SHUNT) 440 Vac
Single phase / Three phase
ADVR-083
~
G
R
S
N
T
Field
AUX. wires
potentiometer
1k /1W
External
ADVR-083
~
G
R
S
N
T
Field
potentiometer
1k /1W
External
Figure 5 Auxiliary Winding 110/220/440 Vac
Single phase / Three phase
Figure 6 PMG 110/220/440 Vac
Single phase / Three phase
SECTION 4 : WIRING CONNECTIONS
Dotted lines represent a three-phase input. Do not connect if installed in single-phase system
___________________________________________________________________________________________
ADVR-083 5

ADVR-083
~
G
R
S
N
T
Field
+
OUT1
OUT2
+
B B
IVT
S2
S1
Fuse
Time
Test
Output
Ready
Test
Batt-Volt
OVLD
ON
Droop
%
1260
2460
potentiometer
1k /1W
External
Figure 7 ADVR-083 & IVT-1260 / IVT-2460 Wiring Connection
Self-Excited (SHUNT) 110/220 Vac Single phase / Three phase
ADVR-083
potentiometer
1k /1W
External
~
G
R
S
N
T
Field
+
OUT-
OUT+
B B
S2
S1
Fuse
Test
Output
Ready
Test
Batt-Volt
OVLD
Droop
%
Gain
+
IVT
1270
2470
F+ F-
Figure 8 ADVR-083 & IVT-1270 / IVT-2470 Wiring Connection
Self-Excited (SHUNT) 110/220 Vac Single phase / Three phase
ATTENTION
1. Before using a Megger or a Withstand Voltage Tester remove the wires connecting to the AVR to
prevent high voltage damage to the regulator.
2. Improper setting of under-frequency protection could cause the output voltage of the unit to drop or
become unstable under with changes in load. Avoid making any changes to the U/F setting unless
necessary.
3. Turn off O/E in AVR when paralleling.
※
Use only the replacement fuses specified in this user manual.
※
___________________________________________________________________________________________
Appearance and specifications of products are subject to change for improvement without prior notice.