All rights reserved. The contents provided herein must neither be distributed, copied, reproduced,
edited or processed for any other purpose, nor otherwise transmitted, published or made available to a
third party without the manufacturer's express written consent.
Subject to technical modification without prior notice.
2.1Key to safety symbols/markings.......................................................................................................................7
4.4Return to supplier ..........................................................................................................................................10
5.5Configuration and function...........................................................................................................................12
5.7Scope of supply...............................................................................................................................................13
5.8Dimensions and weights ................................................................................................................................13
6Installation at Site................................................................................................................................ 14
6.1Installation to DIN 1988 .................................................................................................................................14
6.2Checks to be carried out prior to installation...............................................................................................14
6.3Installing the pressure booster system..........................................................................................................14
6.4Installing the piping .......................................................................................................................................15
6.4.1Fitting an expansion joint .................................................................................................................15
6.4.2Installing a pressure reducer .............................................................................................................16
6.6Fitting the dry running protection device ....................................................................................................17
6.7Connection to power supply..........................................................................................................................17
6.7.1Sizing the power cable ......................................................................................................................17
6.7.2Connecting the pressure booster system..........................................................................................17
7.1.3Commissioning/start-up of pressure booster system .......................................................................19
7.2Switching on the pressure booster system....................................................................................................20
7.3Checklist for commissioning/start-up ............................................................................................................21
8Operating the Pressure Booster System............................................................................................. 22
8.1Graphical control panel..................................................................................................................................22
8.2Service interface and LED traffic light function ...........................................................................................29
8.3Adjusting the settings ....................................................................................................................................30
8.3.1Setting the setpoint ...........................................................................................................................30
8.3.2Changing the controller settings ......................................................................................................30
10.2 Trouble-shooting: frequency inverter...........................................................................................................35
11.1 List of components .........................................................................................................................................37
11.1.1 Hya-Solo DSV with Movitec 2, 4, 6, 10, 15........................................................................................37
11.1.2 Hya-SoloDSV with Movitec 25, 40, 60, 90........................................................................................38
12EU Declaration of Conformity............................................................................................................. 39
13Certificate of Decontamination........................................................................................................... 40
Index ..................................................................................................................................................... 42
4 of 44
Hya-Solo DSV
Page 5
Glossary
Glossary
Accumulator
The accumulator serves to compensate for
pressure losses in the piping system downstream
of the pressure booster system which may be
caused by the consumption of small quantities of
water. As a result, the frequency of starts of the
pressure booster system is minimised.
Automatic mode
The pump is started as a function of pressure and
stopped as a function of flow.
Certificate of decontamination
A certificate of decontamination is enclosed by the
customer when returning the product to the
manufacturer to certify that the product has been
properly drained to eliminate any environmental
and health hazards arising from components in
contact with the fluid handled.
Dry running protection
Dry running protection devices prevent the pump
from being operated without the fluid to be
handled, which would result in pump damage.
Manual mode
In manual mode, the pressure booster system is
operated directly on mains power, independently
of the control unit.
Hya-Solo DSV
5 of 44
Page 6
1 General
1 General
1.1 Principles
This operating manual is supplied as an integral part of the type series and variants
indicated on the front cover. The manual describes the proper and safe use of this
equipment in all phases of operation.
The name plate indicates the type series/size, the main operating data and the order
number. The series/serial number uniquely identifies the pressure booster system and
serves as identification for all further business processes.
In the event of damage, immediately contact your nearest KSB service centre to
maintain the right to claim under warranty.
Noise characteristics see (ðSection5.6,Page13)
1.2 Installation of partly completed machinery
To install partly completed machinery supplied by KSB refer to the sub-sections under
Servicing/Maintenance.
1.3 Target group
This operating manual is aimed at the target group of trained and qualified specialist
technical personnel.
1.4 Other applicable documents
Table1: Overview of other applicable documents
DocumentContents
Sub-supplier product literatureOperating manuals, logic diagram and other
product literature of accessories and integrated
machinery components
1.5 Symbols
Table2: Symbols used in this manual
SymbolDescription
✓Conditions which need to be fulfilled before proceeding with the
step-by-step instructions
⊳Safety instructions
⇨Result of an action
⇨Cross-references
1.
2.
Step-by-step instructions
Note
Recommendations and important information on how to handle
the product
6 of 44
Hya-Solo DSV
Page 7
2 Safety
!
DANGER
!
DANGER
!
WARNING
CAUTION
2 Safety
All the information contained in this section refers to hazardous situations.
2.1 Key to safety symbols/markings
Table3: Definition of safety symbols/markings
SymbolDescription
DANGER
This signal word indicates a high-risk hazard which, if not avoided,
will result in death or serious injury.
WARNING
This signal word indicates a medium-risk hazard which, if not
avoided, could result in death or serious injury.
CAUTION
This signal word indicates a hazard which, if not avoided, could
result in damage to the machine and its functions.
General hazard
In conjunction with one of the signal words this symbol indicates a
hazard which will or could result in death or serious injury.
Electrical hazard
In conjunction with one of the signal words this symbol indicates a
hazard involving electrical voltage and identifies information about
protection against electrical voltage.
Machine damage
In conjunction with the signal word CAUTION this symbol indicates
a hazard for the machine and its functions.
Hya-Solo DSV
7 of 44
Page 8
3 Software Changes
3 Software Changes
The software has been specially created for this product and thoroughly tested.
It is not allowed to make any changes or additions to the software or parts of the
software. Software updates supplied by KSB are excluded from this rule.
8 of 44
Hya-Solo DSV
Page 9
4 Transport/Temporary Storage/Disposal
4 Transport/Temporary Storage/Disposal
4.1 Checking the condition upon delivery
1. On transfer of goods, check each packaging unit for damage.
2. In the event of in-transit damage, assess the exact damage, document it and
notify KSB or the supplying dealer and the insurer about the damage in writing
immediately.
4.2 Transport
NOTE
The pressure booster system is bolted to a pallet and wrapped in plastic foil for
shipping and temporary storage. All connecting points are capped.
DANGER
Pressure booster system tipping over
Risk of injury by falling pressure booster system!
▷ Never suspend the pressure booster system by its power cable.
▷ Observe the applicable local accident prevention regulations.
▷ Pay attention to the weight data and the centre of gravity.
▷ Use suitable and permitted transporting equipment, e.g. crane, forklift or
elevating platform truck.
▷ Attach the pressure booster system to crane lifting tackle as shown, or use a
forklift or pallet truck to move the pallet.
Fig.1: Transporting the pressure booster system
ü The pressure booster system has been checked for in-transit damage.
1. Make sure the transport equipment is suitable for safely carrying the indicated
load.
2. Transport the pressure booster system to the place of installation.
3. Attach the pressure booster system to the lifting tackle as shown, lift it off the
pallet and dispose of the pallet.
4. Use suitable lifting equipment to lift the pressure booster system and carefully
put it down at the place of installation.
4.3 Storage/preservation
If commissioning is to take place some time after delivery, we recommend that the
following measures be taken when storing the pressure booster system:
Hya-Solo DSV
9 of 44
Page 10
4 Transport/Temporary Storage/Disposal
CAUTION
Damage during storage due to frost, moisture, dirt, UV radiation or vermin
Corrosion/contamination of pressure booster system!
▷ Store the pressure booster system in a frost-proof room. Do not store outdoors.
CAUTION
Wet, contaminated or damaged openings and connections
Leakage or damage of the pressure booster system!
▷ Only open the openings of the pressure booster system at the time of
installation.
Store the pressure booster system in a dry, protected room where the atmospheric
humidity is as constant as possible.
4.4 Return to supplier
1. Drain the pressure booster system as per operating instructions.
2. Always flush and clean the pressure booster system, particularly if it has been
used for handling noxious, explosive, hot or other hazardous fluids.
3. If the pressure booster system has handled fluids whose residues could lead to
corrosion damage in the presence of atmospheric humidity or could ignite upon
contact with oxygen, the pressure booster system must also be neutralised and
treated with anhydrous inert gas to ensure drying.
4. Always complete and enclose a certificate of decontamination when returning
the pressure booster system. (ðSection13,Page40)
Always indicate any safety and decontamination measures taken.
NOTE
If required, a blank certificate of decontamination can be downloaded from the
following web site: www.ksb.com/certificate_of_decontamination
4.5 Disposal
WARNING
Fluids, consumables and supplies which are hot and/or pose a health hazard
Hazard to persons and the environment!
▷ Collect and properly dispose of flushing fluid and any residues of the fluid
handled.
▷ Wear safety clothing and a protective mask if required.
▷ Observe all legal regulations on the disposal of fluids posing a health hazard.
1. Dismantle the pressure booster system.
Collect greases and other lubricants during dismantling.
2. Separate and sort the pump materials, e.g. by:
- Metals
- Plastics
- Electronic waste
- Greases and other lubricants
3. Dispose of materials in accordance with local regulations or in another
controlled manner.
! nethcaeb gnutielnasbeirteB emhanbeirtebnI roVynamreG ni edaMZNI 1448J
9972904032
100
1 23
4
5
6
7
8
9
101112
18
17
16
13
14
15
Johann-Klein-Straße 9
Deutschland
67227 Frankenthal
KSB SE & Co. KGaA
5 Description
5.1 General description
▪ Pressure booster system
5.2 Designation
Example: Hya-Solo DSV / 04 05 / 2 - 4
Table4: Designation key
CodeDescription
Hya-SoloPressure booster system with one pump
DSVModel with three-phase motor, speed-controlled, pressure-
dependent starting and flow-dependent stopping
04Pump size
05Number of stages per pump
2 - 4Inlet pressure in bar
5.3 Name plate
Fig.2: Name plate (example) of a Hya-Solo DSV
1Type series, size2Order item number
3Order number4Series code
5Motor power P26Operating voltage/frequency
7Control voltage/frequency8Nominal motor current
9Circuit diagram10Gross vol. content
11Pre-charge pressure12Accumulator
13Maximum operating pressure14Inlet pressure
15Head at Q=016Head
17System setpoint pressure18Flow rate
5.4 Design details
Design
The pressure booster system consists of a non-self-priming multistage high-pressure
centrifugal pump with suction and discharge side shut-off valves. The shut-off valves
enable dismantling of the pump or check valve without draining the piping system.
The check valve on the discharge side prevents backflow through the pump when the
pump is not running and reduces the load on the mechanical seal.
An accumulator, a pressure transmitter and a pressure gauge are fitted on the
discharge side of the pressure booster system.
The PumpDrive speed control system is mounted on and ready-wired to the pump
set.
The system comes with separate rubber anti-vibration pads.
Hya-Solo DSV
11 of 44
Page 12
1
5
2
3
6
4
Design
Function
Automatic mode
Function
Manual mode
5 Description
5.5 Configuration and function
Fig.3: Illustration of a Hya-Solo DSV
1Master switch2Accumulator
3Pump4Pressure sensor
5PumpDrive6Valves
The fully automatic pressure booster system is equipped with a non-self-priming
vertical high-pressure pump (3) for pumping the fluid handled to the consumer
installations at a constant pressure.
The pump is started as a function of pressure and stopped as a function of flow by a
fully automatic control unit. If the pressure drops below the pre-set pressure, the
pump starts up and the frequency inverter controls the pressure booster system to
maintain the set pressure, so that the pressure is kept constant.
If the demand decreases, the pump stops as soon as the flow rate has fallen below a
set minimum value.
A key for manual operation is provided on the control panel. In manual mode the
pump operates at the pre-set minimum speed, independently of the automatic
system (pressure transmitter) or an External ON/OFF signal.
NOTE
Continuous manual mode is reserved exclusively for emergencies!
Continuous operation of the pressure booster system in manual mode may result in
waste of energy and water.
In manual mode, a minimum flow (see table below) is essential to prevent the fluid
handled and the pump from overheating when no water is consumed at the
consumer installations.
Minimum flow for pump in manual mode
Table5: Minimum flow per pump in manual mode
PumpMinimum flow per pump in manual mode
[l/h]
Movitec 2B200
Movitec 4B400
Movitec 6B600
Movitec 10B1100
Movitec 15B1600
Example
Movitec 25B2800
Movitec 40B4600
Movitec 60B6100
Movitec 90B8500
An open 1/2-inch tap equals a water consumption of approx. 800 to 1,200l/h.
12 of 44
Hya-Solo DSV
Page 13
5 Description
Function
Dry running protection
The dry running protection function is active in automatic mode and manual mode.
A digital input is provided for connecting the dry running protection device. When
the input is open, the control unit detects dry running and stops the pressure booster
system after approx. 10seconds (factory setting).
5.6 Noise characteristics
For the noise level of the individual pumps please refer to the pump's operating
instructions.
5.7 Scope of supply
Depending on the model, the following items are included in the scope of supply:
▪ Pressure booster system
▪ One Movitec vertical high-pressure centrifugal pump
▪ Check valve
▪ Shut-off valves
▪ Membrane-type direct-flow accumulator on the discharge side
▪ Pressure transmitter on the discharge side
▪ Vibration damping
▪ Pressure gauge for pressure indication
PumpDrive
▪ Self-cooling motor-mounted frequency inverter (PumpDrive) for pressure-
▪ Two freely parameterisable relay outputs (operation/fault, alert, etc.)
▪ Two NO contacts 250V AC/1A
▪ Analog input for external setpoint adjustment
▪ Analog output for transmitting the actual value, motor speed, etc.
▪ Lockable master switch (repair switch)
5.8 Dimensions and weights
For dimensions and weights refer to the outline drawings of the pressure booster
system.
Hya-Solo DSV
13 of 44
Page 14
6 Installation at Site
6 Installation at Site
6.1 Installation to DIN 1988
Install pressure booster systems either in the technical equipment room or in a wellventilated, frost-free, lockable room used for no other purpose. No harmful gases are
allowed to enter the place of installation. An adequately sized floor drain (leading to
a sewer or equivalent) must be provided.
The system is designed for a maximum ambient temperature of 0°C to +40°C at a
relative humidity of 50%.
NOTE
Do not install pressure booster systems next to sleeping or living quarters.
If expansion joints (KSB accessory) are used for damping vibrations, their fatigue
strength (endurance limit) must be given due consideration. Expansion joints must be
installed to allow quick and easy replacement.
6.2 Checks to be carried out prior to installation
Place of installation
WARNING
Installation on mounting surfaces which are unsecured and cannot support the
load
Personal injury and damage to property!
▷ Use a concrete of compressive strength class C12/15 which meets the
requirements of exposure class X0 to EN206-1.
▷ The mounting surface must have set and must be completely horizontal and
even.
▷ Observe the weights indicated.
NOTE
The anti-vibration mounts of the pressure booster system provide adequate
insulation against solid-borne noise.
1. Check the structural requirements.
All structural work required must have been prepared in accordance with the
dimensions stated in the outline drawing.
6.3 Installing the pressure booster system
WARNING
Top-heavy pressure booster system
Risk of personal injury by pressure booster system tilting!
▷ Pressure booster systems awaiting final installation must be secured against
tipping over.
▷ Firmly anchor the pressure booster system.
14 of 44
Remove all packaging before installing the pressure booster system. Connect the
pressure booster system's inlet line and discharge line to the corresponding site
distribution lines.
Hya-Solo DSV
Page 15
6 Installation at Site
NOTE
In order to avoid transmission of piping forces onto the pressure booster system
and transmission of solid-borne noise, we recommend installing length-limited
expansion joints.
Allow sufficient space for maintenance and repair work.
ü All structural work required has been checked.
ü The dimensions of the concrete foundation are correct, and the concrete has set
firmly.
1. Mark out the anchoring holes on the floor as shown in the outline drawing.
2. Drill the holes (max. diameter: 12mm).
3. Insert plug fixings of appropriate size.
4. Set the pressure booster system down in its correct installation position.
5. Use suitable bolts to firmly anchor the pressure booster system.
6.4 Installing the piping
Make sure that piping is installed without transmitting any stresses or strains. The use
of length-limited expansion joints (see accessories) is recommended.
CAUTION
Air pockets in suction line
Pressure booster system cannot prime!
▷ Lay piping with a continuously rising slope (as shown).
Suction lift operation
IncorrectCorrect
NOTE
For suction lift operation install suitable swing check valves at the suction line ends
which are submerged in the fluid handled. Take into account the head losses
caused by these swing check valves.
Do not exceed the maximum suction lift of the pumps.
6.4.1 Fitting an expansion joint
DANGER
Sparks and radiant heat
Fire hazard!
▷ Take suitable precautions to protect the expansion joint if any welding work is
carried out nearby.
Hya-Solo DSV
15 of 44
Page 16
6 Installation at Site
CAUTION
Leaking expansion joint
Flooding of installation room!
▷ Regularly check for cracks or blisters, exposed fabric or other defects.
ü The expansion joint has a length limiter with solid-borne sound insulation so as
to be able to absorb reaction forces.
1. Install the expansion joint in the piping free of twist or distortion. Never use the
expansion joint to compensate for misalignment or mismatch of the piping.
2. Tighten the bolts evenly and crosswise during assembly. The ends of the bolts
must not protrude from the flange.
3. Do not apply paint to the expansion joint. Protect it from any contact with oil.
4. The position of the expansion joint within the pressure booster system must
allow easy access and inspection and it must, therefore, not be insulated along
with the piping.
5. Expansion joints are subject to wear.
6.4.2 Installing a pressure reducer
NOTE
A pipe length of approximately 600 mm must be provided on the inlet side to
accommodate a pressure reducer, if necessary.
NOTE
A pressure reducer must be installed
- if the inlet pressure fluctuation is too high for the pressure booster system to
operate as intended or
- if the total pressure (inlet pressure plus shut-off head) of the pressure booster
system exceeds the design pressure.
The maximum pump discharge pressure at zero flow point is reached in manual
mode.
A minimum pressure gradient of 5 metres is required for the pressure reducer to
fulfill its function. The pressure downstream of the pressure reducer (downstream
pressure) is the basic parameter for determining the pump head.
For example:
The inlet pressure fluctuates between 4 and 8 bar. A pressure reducer is needed
upstream of the pressure booster system on the inlet side.
Min. inlet pressure (p
Min. pressure gradient=0.5bar
Downstream pressure=3.5bar.
)=4bar
inl
16 of 44
6.5 Installing unpressurised inlet tanks
Installation and location of an unpressurised inlet tank together with the pressure
booster system are governed by the same rules applicable to the pressure booster
system.
Install the closed PE inlet tank (under atmospheric pressure) available as a KSB
accessory as described in the installation instructions supplied with the tank.
CAUTION
Contamination in the pressure booster system
Damage to the pumps!
▷ Clean the tank before filling it.
Hya-Solo DSV
Page 17
6 Installation at Site
The tank must be connected mechanically and electrically to the pressure booster
system prior to commissioning of the system.
6.6 Fitting the dry running protection device
Install the dry running protection device supplied together with the pressure booster
system as a separate, non-fitted accessory, or supplied at a later date for retrofitting,
in accordance with its operating instructions and connect it to digital input1
(terminals C1 and C2 on terminal stripC) of the PumpDrive.
This digital input is assigned exclusively to the Start/Stop function and is bridged if
the system is supplied without a dry running protection device. Only dry running
protection devices can be used which open a contact when dry running occurs.
No cut-out delay can be set.
6.7 Connection to power supply
DANGER
Electrical connection work by unqualified personnel
Danger of death from electric shock!
▷ Always have the electrical connections installed by a trained and qualified
electrician.
▷ Observe regulations IEC60364.
WARNING
Incorrect connection to the mains
Damage to the mains network, short circuit!
▷ Observe the technical specifications of the local energy supply companies.
NOTE
If a residual current device is installed, observe the operating manual for the
frequency inverter.
The circuit diagrams are included in the control cabinet of the pressure booster
system, where they must remain when not in use.
The product literature of the switchgear and controlgear assembly supplied with the
pressure booster system includes a list of the electrical components installed. When
ordering spare parts for electrical components, please always indicate the circuit
diagram number.
6.7.1 Sizing the power cable
The cross-section of the power cable must be sized for the total rated power
requirement.
6.7.2 Connecting the pressure booster system
Connect the pressure booster system to the power supply via terminals L1, L2, L3 and
PE of the terminal strip or the master switch in the connection space of the frequency
inverter. To do so, proceed as described in the operating manual of the PumpDrive.
Observe the data on the name plate.
6.7.3 Digital inputs
Terminal strip C, terminals C1 to C10
PumpDrive is equipped with six digital inputs.
Digital inputs 1 and 6 are factory-defaulted.
Digital inputDI-EN is the digital enable input. In as-delivered condition it is linked
with terminal C9. If the pressure booster system is equipped with a dry running
Hya-Solo DSV
17 of 44
Page 18
6 Installation at Site
protection device, this device is connected to digital input 1 (C1 and C2).
The functions of digital inputs 2 to 5 can be parameterised by the user at the control
panel. To connect the inputs use terminal C1 (+24VDC).
For setting the parameters see the PumpDrive2 operating manual.
6.7.4 Relay outputs
Terminal strip A, terminals A1 to A10
In as-delivered condition the relay outputs are parameterised as volt-free contacts for
"Alarm" (relay1) and "RUN operating status" (relay2). Different messages can be
assigned to these relay outputs via the control panel.
For setting the parameters see the PumpDrive2 operating manual.
6.7.5 Analog inputs
Terminal strip B, terminals B1 to B8
Analog input1 can be connected to an external setpoint adjustment.
Analog input2 is assigned to the pressure transmitter (feedback value transmitter) as
standard and connected to the mains-motor-PTC terminal strip.
For setting the parameters see the PumpDrive2 operating manual.
6.7.6 Analog output
Terminal strip B, terminals B9 and B10
PumpDrive features an analog output whose output value can be parameterised via
the control panel depending on the digital inputs.
For setting the parameters see the PumpDrive2 operating manual.
18 of 44
Hya-Solo DSV
Page 19
7 Commissioning/Start-up/Shutdown
7 Commissioning/Start-up/Shutdown
7.1 Commissioning/Start-up
7.1.1 Prerequisites for commissioning/start-up
Before commissioning/start-up of the pressure booster system make sure that the
following requirements are met:
▪ The pressure booster system has been properly connected to the electric power
supply and is equipped with all protection devices.
▪ All relevant VDE standards and/or regulations applicable in the country of use are
complied with.
▪ The dry running protection device has been installed.
CAUTION
Dry running of pump
Damage to the pump/pressure booster system!
▷ If no dry running protection device is connected when commissioning takes
place, the pressure booster system will start neither in manual nor in test run
mode. If the dry running protection terminal is disabled by means of a bridge,
the operator shall assume responsibility for any dry running that might occur.
NOTE
The competent authorities must be informed in due time prior to commissioning/
test running the system.
7.1.2 Dry running protection
Pressure booster systems can be factory-equipped with pressure switches as dry
running protection devices. Such dry running protection devices will be factory-set to
the inlet pressure values specified in the purchase order.
If the factory settings should not match the site data, set the start and stop pressure
as described in the operating manual of the pressure switch.
Table6: Recommended settings
Stop pressureStart-up pressure
Pressure switch0.5barbelow p
7.1.3 Commissioning/start-up of pressure booster system
inl
0.2barbelow p
inl
NOTE
The pressure booster systems undergo hydraulic testing with water at the factory
and are drained carefully before shipment. However, for technical reasons the
presence of some residual water is unavoidable.
The hydraulic connections are closed in as-supplied condition. They must only be
opened immediately before installation.
Refer to EN806 before commissioning/starting up the pressure booster system.
After an extended pre-installation period, in particular, flushing or even
professional disinfection is recommended. For extensive or branched piping systems
the pressure booster system should preferably be flushed either before installation,
or flushing should be restricted to a limited area.
Commissioning should be carried out by specialist KSB staff.
Hya-Solo DSV
19 of 44
Page 20
7 Commissioning/Start-up/Shutdown
CAUTION
Foreign matter in the piping
Damage to the pump/pressure booster system!
▷ Before commissioning/starting (or even test running) the pressure booster
system, make sure that there is no foreign matter in the pressure booster
system or piping.
NOTE
Commissioning of the pressure booster system - even test running - shall only be
carried out in full compliance with all pertinent VDE (German Association of
Electrical Engineers) regulations.
ü The pipe unions between the pump and the piping have been re-tightened.
ü The flange bolting has been checked for firm seating.
ü The cooling air inlet and outlet openings on the motor are unobstructed.
ü All shut-off valves of the pressure booster system are open.
ü The pre-charge pressure of the membrane-type accumulator has been checked.
(ðSection9.2.3,Page33)
1. Set the master switch to "0".
2. Provide connection to power supply.
3. Open/loosen the vent plugs on the pump (refer to the pump's installation and
operating instructions).
4. Slowly open the inlet-side shut-off element and prime the pressure booster
system until the fluid to be handled escapes through all vent holes.
5. Close and slightly tighten the pump vent plugs.
6. Switch on the master switch.
7. Open the discharge-side shut-off element.
8. Loosen the vent plug again to let any remaining air escape.
9. Then re-tighten the vent plugs firmly.
10. Verify that the pump is running smoothly.
11. Close the discharge-side shut-off element for a short period in order to verify
that the pump reaches the shut-off head.
12. Close the discharge-side shut-off element, causing the pump to stop.
20 of 44
NOTE
Minor leakage of the mechanical seals during commissioning is normal and will
cease after a short period of operation.
7.2 Switching on the pressure booster system
Switch on the master switch to energise the pressure booster system. The green LED
on the control panel lights up, indicating the system's readiness for operation.
NOTE
The pressure booster system is factory-set to the operating data indicated on the
name plate.
Hya-Solo DSV
Page 21
7 Commissioning/Start-up/Shutdown
7.3 Checklist for commissioning/start-up
Table7: Checklist
OperationsDone
1Read the operating instructions.
2Check power supply and compare against the name plate data.
3Check the earthing system (by measuring).
4Check the mechanical connection to the water mains.
Re-tighten the flange bolting and pipe unions.
5Prime and vent the pressure booster system from the inlet side.
6Check inlet pressure.
7Check whether all cables are still firmly connected to the terminals inside the control unit.
8Check the setpoint, re-adjust if necessary.
9Test the proper function of the lack-of-water and dry running protection equipment. If not
fitted, make a relevant note in the commissioning report.
10Vent the pump for a second time after it has been running for 5 to 10 minutes.
11Check the pre-charge pressure.
12Record all system conditions that do not correspond to our specifications or to the purchase
order in the commissioning report (i.e. no dry running protection or inlet pressure + max.
pressure of pressure booster system higher than 16 bar).
13Complete the commissioning report together with the operator/user and instruct the operator/
user as to the function of the system.
7.4 Shutdown
NOTE
As long as the pressure booster system is out of operation, water is supplied directly
at p
through the pressure booster system.
inl
Set the master switch to "0".
NOTE
Drain the pressure booster system for prolonged shutdown.
Hya-Solo DSV
21 of 44
Page 22
8 Operating the Pressure Booster System
OK
MAN
ESC
?
AUTO FUNC
OFF
3
1
2
3
4
8 Operating the Pressure Booster System
CAUTION
Incorrect operation
Water supply is not assured!
▷ Make sure to comply with all local regulations, particularly the EC Machinery
Directive and the EC Directive on Low-Voltage Equipment.
The pressure booster system is factory-set to the operating data indicated on the
name plate.
The settings can be modified via the control panel, if necessary.
8.1 Graphical control panel
Fig.4: Graphical control panel
Table8: Description of graphical control panel
PositionDescriptionFunction
1Graphical displayDisplays information on frequency inverter operation
2Menu keysAccessing the elements of the first menu level (Operation,
Diagnosis, Settings and Information)
3Navigation keysNavigation and parameter setting
4Operating keysToggling operating modes
8.1.1 Graphical display
The main screen breaks down into 6areas.
22 of 44
Hya-Solo DSV
Page 23
8 Operating the Pressure Booster System
C M
H
1-2-1-1
2893
rpm
17.48 m³/h
4.62 bar642.9 V
RUN
AUTO
Speed
8
1
4
5
7
6
3
2
ESC
OK
Fig.5: Main screen (example)
1Motor standstill heater is switched on
2The wireless icon illuminates when the Bluetooth module is inserted. The
wireless icon flashes when communication takes place.
3Display of the master and login level
4Display of up to four (4)operating values: One operating value is displayed in
large format. Three (3) operating values are displayed in small format. The
operating values scroll through cyclically.
5Display of operating status
6Display of the current operating mode
7Parameter number of the operating value displayed in the centre
8Name of the operating value displayed in the centre
Table9: Assignment of keys
KeyFunction
Operation menu key
Diagnosis menu key
Settings menu key
Information menu key
Arrow keys:
▪ Move up/down in the menu options.
▪ Increase/decrease the value displayed when you are entering numerals. (When an arrow
key is pressed and held down, the response repeats in ever shorter intervals.)
Escape key:
▪ Delete/reset entry
(the entry is not saved).
▪ Move up one menu level.
OK key:
▪ Confirm settings.
▪ Confirm menu selection.
▪ Move to the next digit when entering numerals.
▪ Message display: Acknowledge alert.
▪ Measured value display: Go to Favourites menu.
Hya-Solo DSV
23 of 44
Page 24
KeyFunction
?
MAN
OFF
AUTO
FUNC
MAN
ESC
OK
Help key:
▪ Displays a help text for each selected menu option.
MAN operating key:
▪ Starts the frequency inverter in manual operating mode.
OFF operating key:
▪ Stops the frequency inverter.
AUTO operating key:
▪ Switches to automatic operating mode.
FUNC operating key:
▪ Parameterisable function key
8 Operating the Pressure Booster System
Manual mode via control panel
NOTE
After a power failure, the frequency inverter reverts to the OFF operating mode.
Manual mode must be restarted.
Table10: Assignment of keys for manual mode
KeyFunction
MAN operating key:
▪ When switching the operating mode from AUTO to MAN, the current operating speed is
used as control value (Manual) 1-3-4 and is displayed accordingly. The control point 3-6-2
must be set to Local.
▪ When switching the operating mode from OFF to MAN, the frequency inverter operates
at minimum speed. The control point 3-6-2 must be set to Local.
▪ If the control value (Manual) 1-3-4 is defined via an analog input, the analog input speed
is accepted.
Arrow keys:
▪ Pressing the arrow keys changes and immediately accepts the control value (Manual)
1-3-4. Making a change using the arrow key has a direct effect even when not confirmed
with OK. The speed can only be changed between the set minimum speed and the
maximum speed.
ESC/OK key:
▪ Press the OK or ESC key to go from digit to digit. Press the ESC key to go back. Changes
are rejected. Pressing the OK key for the right-hand digit takes you back to the main
screen.
8.1.2 Menu keys
The menu keys allow you to directly access the first menu level (Operation 1-x-x-x,
Diagnosis 2-x-x-x, Settings 3-x-x-x, and Information 4-x-x-x).
The parameter numbers contain the navigation path, which helps you find a
particular parameter quickly and easily. The first digit of the parameter number
indicates the first menu level, which is called up directly via the four menu keys.
24 of 44
Hya-Solo DSV
Page 25
8 Operating the Pressure Booster System
C M
STOP
3-6-1
AUTO
OFF (Open-loop Control)
Discharge Pressure
Suction Pressure
Differential Pressure
Flow Rate
Temperature (Cooling)
Type of Control
1
2
3
4
5
6
Fig.6: Menu display
1Name of current menu/parameter
2Parameter number of parameter selected in selection list
3Display of the current operating mode
4Display of the master and login level
5Parameter/submenu selection list
6Display of operating status
8.1.2.1 Menu: Operation
The Operation section contains all information required for operating the machine
and the process. This includes:
▪ Login to device with password
▪ Operating and measured values for motor, frequency inverter, pump and system
▪ Setpoints and control values
▪ Energy meter and operating hours
8.1.2.1.1 Access levels
Three access levels have been defined to prevent accidental or unauthorised access to
frequency inverter parameters:
Table11: Access levels
Access levelDescription
Standard (No Login)Access without password entry.
CustomerAccess level for the expert user with access to all parameters required for
commissioning
Customer serviceAccess level for service personnel.
If a parameter's access level is not explicitly specified, the parameter is always
assigned the customer access level.
8.1.2.1.2 Operating values for input and output signals
The status of the digital inputs/relay outputs is displayed via the Digital Inputs
(1-2-4-6) and Digital Outputs (1-2-4-7) parameters.
Table14: Example of status of digital inputs (1-2-4-6). 24V is applied to digital input 1: System Start
Optional IO cardStandard
Digital inputDI8DI7DI6DI5DI4DI3DI2DI1
Bit pattern on display0000000I
Table15: Example of status of digital outputs (1-2-4-7). The following is reported via relay output 1: General fault
message (configurable)
Optional IO cardStandard
Digital outputR8R7R6R5R4R3DO2D01R2R1
Bit pattern on
display
000000000I
0000...9999-
0000...9999-
8.1.2.2 Menu: Diagnosis
In the Diagnosis section, the user is provided with information about faults and
warning messages that pertain to the pump set or process. The frequency inverter
can be in fault (standstill) or warning (operational) status. The user can also find
previous messages in the history.
Messages
All monitoring and protective functions trigger warnings or alerts. These are
signalled via the amber or red LED of the LED traffic light function.
A corresponding message is output on the control panel display. If more than one
message is output, the last one is displayed. Alerts have priority over warnings.
Fig.7: Message display
1Name of the message displayed in the centre
2Display of the master and login level
3Display of the message: The most recently received message is displayed in
4Display of operating status
5Displays the current operating mode
large format on the main screen. Three operating values are displayed in small
format.
26 of 44
Hya-Solo DSV
Page 27
8 Operating the Pressure Booster System
Pending messages
Message history
If a message has occurred and been acknowledged but has not gone, this message
will be listed in the Pending Messages menu. All current messages can be displayed in
the Diagnosis menu under Pending Messages (2-1). Active warnings and alerts can
also be connected to the relay outputs.
Only messages that have come, been acknowledged, and gone are listed in the
message history. The message history can be viewed by selecting the Message History
parameter 2-2. The last 100 messages are listed here. You can use the arrow keys and
the OK key to select an entry from the list.
Acknowledging and resetting messages
NOTE
Depending on the combination of settings, the frequency inverter could
conceivably restart automatically after acknowledgement/reset or when the cause
of the malfunction or fault has been eliminated.
Acknowledgement
Table16: Acknowledgement types for messages
Property of messageType of acknowledgement
Self-acknowledgingMessage self-acknowledges if condition for message has gone.
Self-acknowledging
(configurable)
Partially selfacknowledging
Non-self-acknowledgingMust be acknowledged manually.
Time stamp
You can acknowledge the message once the cause has been rectified. Messages can
be acknowledged separately in the Diagnosis menu. A message can also be
acknowledged via a digital input. Digital input 2 is defaulted for this purpose.
Overview of warnings and alerts
Messages can be acknowledged as follows:
Users can choose between self-acknowledging and acknowledging manually.
Alerts that are partially self-acknowledging carry out self-acknowledgement in
increasingly large intervals after the alarm condition has gone. If the alert occurs
repeatedly within a specific time window, no additional self-acknowledgement is
carried out.
As soon as the alarm condition of a pending alert no longer exists, the time interval is
started. When this interval expires, automatic acknowledgement takes place.
If the alert occurs again within 30seconds after the time interval has started, the
interval is extended by one increment. Should this not be the case, the previous
(shorter) time interval is reverted to and corresponding action is taken again in
30seconds. The time intervals are 1second, 5seconds, 20seconds, and endless (i.e.
manual acknowledgement is required). When the 20-second interval is extended, selfacknowledgement no longer takes place.
If a message is not acknowledged and its condition comes and goes several times in
this time window, the first occurrence of the message is always used for the Message
Come time stamp. The Message Condition Gone time stamp, however, always shows
the last time the message condition was no longer active.
8.1.2.3 Menu: Settings
General settings can be made or the settings for the process optimised in the Settings
section.
8.1.2.3.1 Setting the display language
The display ships from the factory with support for 4languages (language package).
A language package can be changed using the KSB Service Tool:
Display of current operating values on the main
screen
3-1-2-2Control Keys Require Login
Direct access to the MAN, OFF, AUTO and FUNC
operating keys can be disabled via this parameter.
3-1-2-3Function Key Assignment
Assigning a freely selectable function to the FUNC
key
3-1-2-4Display Contrast
Configurable contrast for the display
3-1-2-5Display Backlight
Configuring the display backlight
3-1-2-6Display Backlight Duration
Duration of display backlight on period in
automatic mode
Operating Values on Main
Screen
Up to 4operating values are simultaneously displayed on the main screen. An
operating value is displayed in large format with the associated parameter name,
parameter number and unit. Three (3) operating values are displayed in smaller
format with the associated unit. The arrow keys can be used to cycle through the
operating values. Each operating value passes through all display areas. Up to
Depending on the language package:
▪ English, German, French, Italian
▪ English, French, Dutch, Danish
▪ English, Spanish, Portuguese, Turkish
▪ English, Norwegian, Swedish, Finnish
▪ English, Estonian, Latvian, Lithuanian
▪ English, Polish, Hungarian, Czech
▪ English, Slovenian, Slovakian, Croatian
▪ English, Russian, Romanian, Serbian
Main screen selection list-
▪ OFF
▪ ON
▪ No Function
▪ System Start / Stop
▪ Setpoint (Closed-loop
Control)
▪ Control Value (Open-loop
Control)
▪ Alternative Setpoint (Closed-
loop Control)
▪ Alternative Control Value
(Open-loop Control)
▪ Immediate Pump
Changeover
▪ Immediate Functional Check
Run
▪ Language
▪ Fixed Speed 1
▪ PumpMeter Upload
▪ Remote/Local Control Point
0...10050
▪ OFF
▪ ON
▪ Automatic
0...60030
English, German,
French, Italian
OFF
Language
Automatic
28 of 44
Hya-Solo DSV
Page 29
8 Operating the Pressure Booster System
C M
RUN
AUTO
3-1-2-1
Speed
Motor Input Power
Motor Current
Output Frequency
Pump Suction Pressure
Pump Discharge Pressure
Operating Values on Main Scr...
2
1
10operating values can be selected from the predefined list for the display. The
sequence of the selection list determines the sequence of the operating values on the
main screen. If more than 4parameters are selected, the hidden parameters are also
cycled through in the background.
Selecting operating values for the main screen
1. Open parameter 3-1-2-1 in the Settings menu.
2. Using the arrow keys, select the operating value to be displayed from the list.
3. Press OK key.
4. Select additional, required operating values from the list and confirm by
pressing the OK key.
Locking operating keys
Function key assignment
Favourites menu
Fig.8: Selecting multiple parameters from the selection list
The operating keys of the control panel can be locked via the 3-1-2-2 parameter to
prevent unauthorised operation or unauthorised acknowledgement of alerts.
The FUNC operating key can be preassigned a function from a selection list.
NOTE
When the FUNC operating key is used in the System Start / Stop role, the system
must be restarted via the FUNC operating key every time the voltage is reset.
Press the OK key on the main screen to call up the favourites menu, where you can
select various parameters and quickly adapt their configuration settings.
8.1.2.4 Menu: Information
All direct information about the frequency inverter is provided in the Information
section. Important details regarding the firmware version are listed here.
8.2 Service interface and LED traffic light function
ItemDescriptionFunction
1Service interfaceOptical interface
2LED traffic light functionThe traffic light function provides information about the
Fig.9: Service interface and traffic light LEDs
system's operating status.
Hya-Solo DSV
29 of 44
Page 30
8 Operating the Pressure Booster System
Service interface
LED traffic light function
The service interface allows a PC/notebook to be connected via a special cable (USB –
optical).
The following action can be taken:
▪ Configuring and parameterising the frequency inverter with the service software
▪ Software update
▪ Saving and documenting set parameters
The LED traffic light function provides information about the current PumpDrive
operating status.
Table19: LED description
LEDDescription
Red
Amber
Green
One or more than one alert is active
One or more than one warning is active
Steady light: Trouble-free operation
8.3 Adjusting the settings
8.3.1 Setting the setpoint
The pressure booster system is factory-set to the setpoint indicated on the rating
plate.
If the setpoint needs to be adjusted to site conditions, parameter 1-3-2 has to be
changed as required.
First, enter the customer password.
Then change the setpoint.
8.3.2 Changing the controller settings
The PI controller of the frequency inverter is optimised when leaving the factory,
therefore no changes are required.
Should a process-related adjustment of the PI controller be necessary, check/change
the factory settings in accordance with the PumpDrive operating manual.
30 of 44
Hya-Solo DSV
Page 31
9 Servicing/Maintenance
9 Servicing/Maintenance
9.1 General information/Safety regulations
The operator ensures that maintenance, inspection and installation is performed by
authorised, qualified specialist personnel who are thoroughly familiar with the
manual.
DANGER
Unintentional start-up of pressure booster system
Danger to life!
▷ The pressure booster system must be de-energised before repair or
maintenance work is carried out.
Switching off the motor protection switch will not de-energise the motor
power cables reliably.
WARNING
Improper lifting/moving of heavy assemblies or components
Personal injury and damage to property!
▷ Use suitable transport devices, lifting equipment and lifting tackle to move
heavy assemblies or components.
WARNING
Unintentional start-up of pressure booster system
Risk of injury by moving parts!
▷ Make sure the pressure booster system has been de-energised before
commencing work on the pressure booster system.
▷ Make sure that the pressure booster system cannot be started up
unintentionally.
WARNING
Unqualified personnel performing work on the pressure booster system
Risk of personal injury!
▷ Always have repair and maintenance work performed by specially trained,
qualified personnel.
CAUTION
Incorrectly serviced pressure booster system
Function of pressure booster system not guaranteed!
▷ Regularly service the pressure booster system.
▷ Prepare a maintenance schedule for the pressure booster system, with special
emphasis on lubricants, shaft seals and pump couplings.
Observe the general safety instructions and information.
Observe the operating manual of the pump when performing work on the pumps.
In the event of damage you can always contact our service staff.
A regular maintenance schedule will help avoid expensive repairs and contribute to
trouble-free, reliable operation of the pressure booster system with a minimum of
maintenance expenditure and work.
Never use force when dismantling and re-assembling the pressure booster system.
Hya-Solo DSV
31 of 44
Page 32
9 Servicing/Maintenance
9.1.1 Inspection contract
For all inspection and servicing work to be carried out at regular intervals we
recommend taking out the inspection contract offered by KSB. Contact your Service
Partner for details.
9.2 Servicing/inspection
9.2.1 Supervision of operation
CAUTION
Increased wear due to dry running
Damage to the pump set!
▷ Never operate the pump set without liquid fill.
▷ Never close the shut-off element in the suction line and/or supply line during
pump operation.
CAUTION
Impermissibly high temperature of fluid handled
Damage to the pump!
▷ Prolonged operation against a closed shut-off element is not permitted
(heating up of the fluid).
▷ Observe the temperature limits in the data sheet and in the section on
operating limits.
While the system is in operation, observe and check the following:
▪ Check the test run (if activated).
▪ Compare the start and stop pressures of the pumps with the data on the name
plate (using the pressure gauge).
▪ Compare the pre-charge pressure of the accumulator with the recommended
data. (ðSection9.2.3,Page33)
Close the shut-off elements under the accumulator and drain the accumulator via
the drain valve.
Remove the protective cap of the accumulator valve and check the pre-charge
pressure with the aid of a tyre pressure gauge.
Add nitrogen as necessary.
WARNING
Wrong gas
Danger of poisoning!
▷ Use only nitrogen to charge the accumulator.
▪ Check the rolling element bearings for running noises.
Vibrations, noise and an increase in current input occurring during unchanged
operating conditions indicate wear.
▪ Monitor the correct functioning of any auxiliary connections.
9.2.2 Checklist for inspection
In the event that you decide to conduct your own inspections, proceed according to
the following checklist at least once a year:
1.Check the pump and drive for smooth running and the mechanical seal for
integrity.
2.Check the shut-off, drain and check valves for proper functioning and tightness.
3.Clean the strainer in the pressure reducer (if applicable).
32 of 44
Hya-Solo DSV
Page 33
9 Servicing/Maintenance
4.Check expansion joints for wear (if applicable).
5.Verify the pre-charge pressure level and check the accumulator for integrity ifrequired. (ðSection9.2.3,Page33)
6.Check the automatic switching functionality.
7.Check the start and stop points of the pressure booster system.
8.Check the water inflow, inlet pressure, lack-of-water monitoring, flow
monitoring and pressure reducer.
9.Check the inlet tank and the float valve (if applicable). Check the overflow for
integrity and cleanliness.
9.2.3 Setting the pre-charge pressure
WARNING
Wrong gas
Danger of poisoning!
▷ Use only nitrogen to charge the accumulator.
The pre-charge pressure in the accumulator should be set to a value below the set
start-up pressure.
The setting can be effected via a valve located under the cover at the top of the
accumulator.
Example: Pre-charge pressure 10% lower than start-up pressure
Pre-charge pressure of accumulator p=0.9xp
p
= start-up pressure of pressure booster system
start
start
Recommendation
The stated values are average values. Tests on accumulators have shown that the best
storage volumes are achieved with the following factors:
pressures >3bar: factor0.9 and
pressures <3bar: factor0.8
Example:
p
= 5 bar: pre-charge pressure 5x0.9=4.5bar
start
p
=2bar: pre-charge pressure 2x0.8=1.6bar
start
CAUTION
Pre-charge pressure too high
Damage to accumulator!
▷ Observe data provided by accumulator manufacturer (see name plate or
operating manual of accumulator).
Hya-Solo DSV
33 of 44
Page 34
10 Trouble-shooting
10 Trouble-shooting
10.1 Trouble-shooting: pressure booster system
WARNING
Improper work to remedy faults
Risk of injury!
▷ For any work performed to remedy faults, observe the relevant information
given in this operating manual and/or in the product literature provided by the
accessories manufacturer.
NOTE
Before performing any work on the pump's internal parts during the warranty
period please always consult the manufacturer. Our after-sales service will be at
your disposal. Non-compliance will lead to forfeiture of any and all rights to claims
for damages.
If problems occur that are not described in the following table, consultation with the
KSB customer service is required.
Pressure booster system cuts out.
A
Pressure fluctuations on the discharge side.
B
Pressure booster system does not start up.
C
Pump running but not delivering water.
D
Insufficient delivery of pressure booster system.
E
Discharge-side pressure too low.
F
Discharge-side pressure too high.
G
Leakage at mechanical seal.
H
Motor/pump overheated.
I
Motor protection switch triggered.
J
Pressure booster system does not stop.
K
Excessive starting/stopping of pressure booster system.
L
Motor overheated.
M
Table20: Trouble-shooting
A B C D E F G H IJ K L M Possible causeRemedy
✘ -✘ ---------- Dry-running protection device not
connected.
✘ -✘ ---------- Mains supply interruptedCheck and remedy defect.
Check/correct the value set at the
pressure switch.
key.
Check; fit new valve if required.
Interchange two phases of the
power cable.
Connect inlet tank, contact KSB.
Contact KSB.
1)
10.2 Trouble-shooting: frequency inverter
WARNING
Improper work to remedy faults
Risk of injury!
▷ For any work performed to remedy faults, observe the relevant information
given in this operating manual and/or in the product literature provided by the
accessories manufacturer.
If problems occur that are not described in the following table, consultation with the
KSB customer service is required.
Mains fuse rating too small for the nominal mains current.
A
Motor does not start.
B
Motor running unevenly.
C
Max. speed not reached.
D
Motor running at maximum speed only.
E
Motor running at minimum speed only.
F
No/faulty 24V supply.
G
Wrong direction of rotation of the motor.
H
Fault message/protective tripping.
I
Hya-Solo DSV
35 of 44
Page 36
10 Trouble-shooting
Table21: Trouble-shooting
A B C D E F G H I Possible causeRemedy
- ✘---- ✘ -- No voltageCheck the mains voltage; check the mains fuses.
- ✘------- No enableCheck enable via DIGIN-EN and system start.
✘ -------- Mains fuse rating too small for
frequency inverter input
current
--- ✘----- No setpoint signal or setpoint
set too low / drive overloaded
and in i²t control mode
---- ✘---- Process-related persistent
control deviation (actual value
smaller than setpoint) / no
actual value (e.g. due to
broken wire)
- ✘------- ✘ Permissible voltage range
undershot/exceeded
Check design configuration of mains fuse.
Check setpoint signal and operating point.
Check setpoint/actual value signal; check operating
point; check controller setting.
Check mains voltage; supply frequency inverter with
required voltage.
------- ✘- Wrong direction of rotation
setting
-- ✘ ✘ ---- ✘ Frequency inverter overloaded Reduce the power input by lowering the speed;
- ✘------ ✘ Short circuit in control cable/
pump blocked
-- ✘ ✘ ---- ✘ Temperature of power
electronics or motor winding
too high
------ ✘- ✘ 24 V supply overloadedDisconnect PumpDrive from the power supply and
-------- ✘ Dry running of pumpCheck the hydraulic system and rectify the fault on
--- ✘- ✘ --✘ Sensor signal error (e.g.
broken wire)
- ✘ ✘ ----- ✘ Phase failure, drive sideCheck motor connection and motor winding.
Change the direction of rotation.
check the motor/pump for blockages.
Check/replace control cable connections. Remove the
blockage manually.
Reduce the ambient temperature by improving
ventilation.
Improve cooling by cleaning the cooling fins.
Ensure the intake opening for the motor fans is not
blocked.
Ensure that the motor fans are working properly.
Reduce the power input by changing the operating
point (system-specific).
Check the permissible load and, if necessary, use
external cooling.
eliminate the cause of the overload.
PumpDrive.
Check sensor and sensor cable.
36 of 44
Hya-Solo DSV
Page 37
11 Related Documents
82-1655
591
79-2
743.02
691743.01742743.01
11 Related Documents
11.1 List of components
11.1.1 Hya-Solo DSV with Movitec 2, 4, 6, 10, 15
Fig.10: General assembly drawing of Hya-Solo DSV with Movitec 2, 4, 6, 10, 15
Table22: Spare parts for Hya-Solo DSV with Movitec 2, 4, 6, 10, 15
Part No.DescriptionIdent. No.
591Accumulator01 079 764
655Pump
691Pressure gauge, discharge side00 401 413
742Lift check valve1 (Movitec 2, 4)01 149 253
742Lift check valve11/4 (Movitec 6)01 149 254
742Lift check valve11/2 (Movitec 10)01 149 255
742Lift check valve2 (Movitec 15)01 149 256
743.01Ball valve1 (Movitec 2, 4)01 057 427
743.01Ball valve11/4 (Movitec 6)01 057 428
743.01Ball valve11/2 (Movitec 10)01 057 429
743.01Ball valve2 (Movitec 15)01 057 430
743.02Ball valve (make Reflex)01 079 765
79-2Measuring transducer 0-16bar01 112 649
82-1PumpDriveOn request
For electric parts refer to the circuit diagram in the Annex.
NOTE
Pump spare parts correspond to Movitec in standard design (with oval flange).
Hya-Solo DSV
37 of 44
Page 38
11 Related Documents
82-1
655
591
743
746
79-2
691747
746
11.1.2 Hya-SoloDSV with Movitec 25, 40, 60, 90
Fig.11: General assembly drawing of Hya-Solo DSV with Movitec 25, 40, 60, 90
Table23: Spare parts for Hya-SoloDSV with Movitec 25, 40, 60, 90
The product/accessories have been carefully drained, cleaned and decontaminated inside and outside prior to dispatch/
placing at your disposal.
We herewith declare that this product is free from hazardous chemicals, biological and radioactive substances.
For mag-drive pumps, the inner rotor unit (impeller, casing cover, bearing ring carrier, plain bearing, inner rotor) has been
removed from the pump and cleaned. In cases of containment shroud leakage, the outer rotor, bearing bracket lantern,
leakage barrier and bearing bracket or intermediate piece have also been cleaned.
For canned motor pumps, the rotor and plain bearing have been removed from the pump for cleaning. In cases of leakage at
the stator can, the stator space has been examined for fluid leakage; if fluid handled has penetrated the stator space, it has
been removed.
No special safety precautions are required for further handling.
The following safety precautions are required for flushing fluids, fluid residues and disposal:
We confirm that the above data and information are correct and complete and that dispatch is effected in accordance with the
relevant legal provisions.
The KSB pressure booster system specified below was today commissioned by the undersigned authorised KSB
customer service engineer who created this report.
Pressure booster system details
Type series........................................................................................................................................
The system operator/operator's representative herewith confirms to have received instructions on how to operate
and service the pressure booster system. The relevant circuit diagrams and operating instructions have been
handed over.
Non-conformities found during commissioningDeadline for remedial action