KSB Delta Solo SVP, Delta Eco SVP Operating Manual

Page 1
Pressure Booster System
KSBDeltaSolo / KSBDeltaEco
KSB Delta Solo SVP KSB Delta Eco SVP
Installation/Operating Manual
Page 2
Installation/Operating Manual KSBDeltaSolo / KSBDeltaEco
Original operating manual
All rights reserved. The contents provided herein must neither be distributed, copied, reproduced, edited or processed for any other purpose, nor otherwise transmitted, published or made available to a third party without the manufacturer's express written consent.
Subject to technical modification without prior notice.
© KSB B.V., Alphen aan den Rijn, Nederland 13/09/2018
Page 3
Contents
3 of 68
KSBDeltaSolo / KSBDeltaEco
Contents
Glossary .................................................................................................................................................. 5
1 General.................................................................................................................................................... 6
1.1 Principles ...........................................................................................................................................................6
1.2 Installation of partly completed machinery....................................................................................................6
1.3 Target group.....................................................................................................................................................6
1.4 Other applicable documents............................................................................................................................6
1.5 Symbols .............................................................................................................................................................6
1.6 Key to safety symbols/markings.......................................................................................................................7
2 Safety...................................................................................................................................................... 8
2.1 General..............................................................................................................................................................8
2.2 Intended use .....................................................................................................................................................8
2.2.1 Prevention of foreseeable misuse.......................................................................................................8
2.3 Personnel qualification and personnel training.............................................................................................8
2.4 Consequences and risks caused by non-compliance with this manual .........................................................9
2.5 Safety awareness ..............................................................................................................................................9
2.6 Safety information for the operator/user.......................................................................................................9
2.7 Safety information for maintenance, inspection and installation ................................................................9
2.8 Unauthorised modes of operation................................................................................................................10
2.9 Electromagnetic compatibility (EMC)............................................................................................................10
2.9.1 Interference emission requirements .................................................................................................10
2.9.2 Line harmonics requirements............................................................................................................11
2.9.3 Interference immunity requirements ...............................................................................................11
3 Software Changes................................................................................................................................ 12
4 Transport/Temporary Storage/Disposal............................................................................................. 13
4.1 Checking the condition upon delivery..........................................................................................................13
4.2 Transport.........................................................................................................................................................13
4.3 Storage/preservation......................................................................................................................................13
4.4 Return to supplier ..........................................................................................................................................14
4.5 Disposal ...........................................................................................................................................................14
5 Description............................................................................................................................................ 15
5.1 General description ........................................................................................................................................15
5.2 Designation.....................................................................................................................................................15
5.3 Name plate......................................................................................................................................................15
5.4 Design details..................................................................................................................................................15
5.5 Configuration and function...........................................................................................................................16
5.6 Noise characteristics .......................................................................................................................................17
5.7 Scope of supply...............................................................................................................................................17
5.8 Dimensions......................................................................................................................................................18
5.9 Terminal wiring diagram ...............................................................................................................................18
5.10 Potential equalisation ....................................................................................................................................18
6 Installation at Site................................................................................................................................ 19
6.1 Installation ......................................................................................................................................................19
6.2 Checks to be carried out prior to installation...............................................................................................19
6.3 Installing the pressure booster system..........................................................................................................19
6.4 Installing the piping .......................................................................................................................................20
6.4.1 Fitting an expansion joint .................................................................................................................20
6.4.2 Installing a pressure reducer .............................................................................................................21
6.5 Installing unpressurised inlet tanks...............................................................................................................21
6.6 Fitting the dry running protection device ....................................................................................................22
6.7 Connection to power supply..........................................................................................................................23
6.7.1 Sizing the power cable ......................................................................................................................23
Page 4
Contents
4 of 68
KSBDeltaSolo / KSBDeltaEco
6.7.2 Connecting the pressure booster system..........................................................................................23
6.7.3 Removing the housing cover.............................................................................................................24
6.7.4 Overview of terminal strips...............................................................................................................25
6.7.5 Connection to mains power supply and motor ...............................................................................26
6.7.6 Establishing an earth connection......................................................................................................31
7 Commissioning/Start-up/Shutdown................................................................................................... 32
7.1 Commissioning/Start-up.................................................................................................................................32
7.1.1 Prerequisites for commissioning/start-up .........................................................................................32
7.1.2 Dry running protection......................................................................................................................32
7.1.3 Commissioning/start-up of pressure booster system .......................................................................32
7.2 Switching on the pressure booster system....................................................................................................34
7.3 Checklist for commissioning/start-up ............................................................................................................34
7.4 Shutdown........................................................................................................................................................34
8 Operation.............................................................................................................................................. 35
8.1 Standard control panel ..................................................................................................................................35
8.1.1 Display ................................................................................................................................................35
8.1.2 Main screen ........................................................................................................................................38
8.1.3 Settings menu ....................................................................................................................................39
8.1.4 Service interface and LED traffic light function...............................................................................42
9 Servicing/Maintenance........................................................................................................................ 43
9.1 General information/Safety regulations .......................................................................................................43
9.1.1 Inspection contract ...........................................................................................................................44
9.2 Servicing/Inspection........................................................................................................................................44
9.2.1 Supervision of operation...................................................................................................................44
9.2.2 Checklist for inspection .....................................................................................................................45
9.2.3 Setting the pre-charge pressure........................................................................................................45
9.2.4 Replacing the non-return valve ........................................................................................................46
9.2.5 Mounting the manifold in a mirrored position ...............................................................................48
10 Trouble-shooting.................................................................................................................................. 52
10.1 Faults/malfunctions: Trouble-shooting .........................................................................................................52
10.2 Alerts ...............................................................................................................................................................53
10.3 Warnings.........................................................................................................................................................56
10.4 Information messages ....................................................................................................................................59
11 Related Documents.............................................................................................................................. 60
11.1 General assembly drawings/exploded views with list of components........................................................60
11.1.1 KSB Delta Solo SVP.............................................................................................................................60
11.1.2 KSB Delta Eco SVP..............................................................................................................................61
12 EU Declaration of Conformity............................................................................................................. 62
13 Certificate of Decontamination........................................................................................................... 63
14 Commissioning Report......................................................................................................................... 64
Index ..................................................................................................................................................... 65
Page 5
Glossary
5 of 68
KSBDeltaSolo / KSBDeltaEco
Glossary
Accumulator
The accumulator serves to compensate for pressure losses in the piping system downstream of the pressure booster system which may be caused by the consumption of small quantities of water. As a result, the frequency of starts of the pressure booster system is minimised.
Braking resistor
Takes up the braking power produced during generator operation.
Certificate of decontamination
A certificate of decontamination is enclosed by the customer when returning the product to the manufacturer to certify that the product has been properly drained to eliminate any environmental and health hazards arising from components in contact with the fluid handled.
Dry running protection
Dry running protection devices prevent the pump from being operated without the fluid to be handled, which would result in pump damage.
Page 6
1 General
6 of 68
KSBDeltaSolo / KSBDeltaEco
1 General
1.1 Principles
This operating manual is valid for the type series and variants indicated on the front cover.
The manual describes the proper and safe use of this equipment in all phases of operation.
The name plate indicates the type series, the main operating data and the serial number. The serial number uniquely describes the product and is used as identification in all further business processes.
In the event of damage, immediately contact your nearest KSB Service centre to maintain the right to claim under warranty.
1.2 Installation of partly completed machinery
To install partly completed machinery supplied by KSB refer to the sub-sections under Servicing/Maintenance.
1.3 Target group
This operating manual is aimed at the target group of trained and qualified specialist technical personnel. (ðSection2.3,Page8)
1.4 Other applicable documents
Table1: Overview of other applicable documents
Document Contents
Sub-supplier product literature Operating manuals, logic diagram and other
product literature of accessories and integrated machinery components
1.5 Symbols
Table2: Symbols used in this manual
Symbol Description
Conditions which need to be fulfilled before proceeding with the
step-by-step instructions
Safety instructions
Result of an action
Cross-references
1.
2.
Step-by-step instructions
Note Recommendations and important information on how to handle the product
Page 7
1 General
7 of 68
KSBDeltaSolo / KSBDeltaEco
1.6 Key to safety symbols/markings
Table3: Definition of safety symbols/markings
Symbol Description
!
DANGER
DANGER This signal word indicates a high-risk hazard which, if not avoided, will result in death or serious injury.
!
WARNING
WARNING This signal word indicates a medium-risk hazard which, if not avoided, could result in death or serious injury.
CAUTION
CAUTION This signal word indicates a hazard which, if not avoided, could result in damage to the machine and its functions.
General hazard In conjunction with one of the signal words this symbol indicates a hazard which will or could result in death or serious injury.
Electrical hazard In conjunction with one of the signal words this symbol indicates a hazard involving electrical voltage and identifies information about protection against electrical voltage.
Machine damage In conjunction with the signal word CAUTION this symbol indicates a hazard for the machine and its functions.
Page 8
2 Safety
8 of 68
KSBDeltaSolo / KSBDeltaEco
2 Safety
!
DANGER
All the information contained in this section refers to hazardous situations. In addition to the present general safety information the action-related safety
information given in the other sections must be observed.
2.1 General
This operating manual contains general installation, operating and maintenance instructions that must be observed to ensure safe operation of the system and prevent personal injury and damage to property.
The safety information in all sections of this manual must be complied with. The operating manual must be read and understood by the responsible specialist
personnel/operators prior to installation and commissioning. The contents of this operating manual must be available to the specialist personnel
at the site at all times. Information attached directly to the product must always be complied with and kept
in a perfectly legible condition at all times. This applies to, for example:
Arrow indicating the direction of rotationMarkings for connectionsName plate
The operator is responsible for ensuring compliance with all local regulations not taken into account in this operating manual.
2.2 Intended use
The pressure booster system must only be operated within the operating limits
described in the other applicable documents.
Only operate pressure booster systems which are in perfect technical condition.Do not operate partially assembled pressure booster systems.The pressure booster system must only handle the fluids described in the product
literature of the respective design variant.
Never operate the pressure booster system without the fluid to be handled.Observe the information on minimum flow rates specified in the product
literature (to prevent overheating, bearing damage, etc).
Observe the maximum flow rates indicated in the data sheet or product
literature (to prevent overheating, cavitation damage, bearing damage, etc).
Do not throttle the flow rate on the suction side of the pressure booster system
(to prevent cavitation damage).
Consult the manufacturer about any other modes of operation not described in
the product literature.
2.2.1 Prevention of foreseeable misuse
Never exceed the permissible application and operating limits specified in the
product literature regarding pressure, temperature, etc.
Observe all safety information and instructions in this manual.
2.3 Personnel qualification and personnel training
All personnel involved must be fully qualified to install, operate, maintain and inspect the machinery this manual refers to.
The responsibilities, competence and supervision of all personnel involved in installation, operation, maintenance and inspection must be clearly defined by the operator.
Page 9
2 Safety
9 of 68
KSBDeltaSolo / KSBDeltaEco
Deficits in knowledge must be rectified by means of training and instruction provided by sufficiently trained specialist personnel. If required, the operator can commission the manufacturer/supplier to train the personnel.
Training on the pressure booster system must always be supervised by technical specialist personnel.
2.4 Consequences and risks caused by non-compliance with this manual
Non-compliance with these operating instructions will lead to forfeiture of
warranty cover and of any and all rights to claims for damages.
Non-compliance can, for example, have the following consequences:
– Hazards to persons due to electrical, thermal, mechanical and chemical
effects and explosions – Failure of important product functions – Failure of prescribed maintenance and servicing practices – Hazard to the environment due to leakage of hazardous substances
2.5 Safety awareness
In addition to the safety information contained in this manual and the intended use, the following safety regulations shall be complied with:
Accident prevention, health regulations and safety regulationsExplosion protection regulationsSafety regulations for handling hazardous substancesApplicable standards, directives and laws
2.6 Safety information for the operator/user
Fit protective equipment (e.g. contact guards) supplied by the operator for hot,
cold or moving parts, and check that the equipment functions properly.
Do not remove any protective equipment (e.g. contact guards) during operation.Eliminate all electrical hazards. (In this respect refer to the applicable national
safety regulations and/or regulations issued by the local energy supply companies.)
If shutting down the pump does not increase potential risk, fit an emergency-
stop control device in the immediate vicinity of the pump (set) during pump set installation.
2.7 Safety information for maintenance, inspection and installation
Modifications or alterations of the pressure booster system are only permitted
with the manufacturer's prior consent.
Use only original spare parts or parts authorised by the manufacturer. The use of
other parts can invalidate any liability of the manufacturer for resulting damage.
The operator ensures that maintenance, inspection and installation is performed
by authorised, qualified specialist personnel who are thoroughly familiar with the manual.
Carry out work on the pressure booster system during standstill only.The pump casing must have cooled down to ambient temperature.Pump pressure must have been released and the pump must have been drained.When taking the pressure booster system out of service always adhere to the
procedure described in the manual.
Decontaminate pressure booster systems which handle fluids posing a health
hazard.
Page 10
2 Safety
10 of 68
KSBDeltaSolo / KSBDeltaEco
As soon as the work has been completed, re-install and/or re-activate any safety-
relevant and protective devices. Before returning the product to service, observe all instructions on commissioning.
Make sure the pressure booster system cannot be accessed by unauthorised
persons (e.g. children).
Prior to opening the device, pull the mains plug and wait for at least 10minutes.
2.8 Unauthorised modes of operation
Always observe the limits stated in the product literature. The warranty relating to the operating reliability and safety of the pressure booster
system supplied is only valid if the equipment is used in accordance with its intended use. (ðSection2.2,Page8)
2.9 Electromagnetic compatibility (EMC)
2.9.1 Interference emission requirements
The EN61800-3 EMC product standard is relevant for electric variable speed drives/ control systems. It specifies all pertinent requirements and refers to the relevant generic standards for complying with the EMC Directive.
Frequency inverters are commonly used by operators as a part of a system, plant or machine assembly. It should be noted that the operator bears all responsibility for the final EMC properties of the equipment, plant or installation.
A prerequisite or requirement for complying with the relevant standards or the limit values and inspection/test levels referenced by them is that all information and descriptions regarding EMC-compliant installation be observed and followed.
In accordance with the EMC product standard, the EMC requirements to be met depend on the purpose or intended use of the frequency inverter. Four categories are defined in the EMC product standard:
Table4: Categories of intended use
Category Definition Limits to EN55011
C1 Frequency inverters with a supply voltage under 1000V installed in the
first environment (residential and office areas).
Class B
C2 Frequency inverters with a supply voltage under 1000V installed in the
first environment (residential and office areas) that are neither ready to be plugged in/connected nor are mobile and must be installed and commissioned by specialist personnel.
Class A, Group 1
C3 Frequency inverters with a supply voltage under 1000V installed in the
second environment (industrial environments).
Class A, Group 2
C4 Frequency inverters with a supply voltage over 1000V and a nominal
current over 400A installed in the second environment (industrial environments) or that are envisaged for use in complex systems.
No borderline/
boundary
1)
The following limit values and inspection/test levels must be complied with if the generic standard on interference emissions applies:
Table5: Classification of installation environment
Environment Generic standard Limits to EN55011
First environment (residential and office areas) EN/IEC61000-6-3
for private, business and commercial environments
Class B
Second environment (industrial environments) EN/IEC61000-6-4
for industrial environments
Class A, Group 1
The frequency inverter meets the following requirements:
1) An EMC plan must be devised.
Page 11
2 Safety
11 of 68
KSBDeltaSolo / KSBDeltaEco
Table6: EMC properties of the frequency inverter
Power
[kW]
Cable length
[m]
Category to EN 61800-3 Limits to EN55011
≤ 11 ≤5 C1 Class B
The EN61800-3 standard requires that the following warning be provided for drive systems that do not comply with category C1 specifications: This product can produce high-frequency interference emissions that may necessitate targeted interference suppression measures in a residential or office environment.
2.9.2 Line harmonics requirements
The product is a device for professional applications as defined by EN 61000-3-2. The following generic standards apply when establishing a connection to the public power grid:
EN 61000-3-2
for symmetric, three-phase devices (professional devices with a total power of up to 1kW)
EN 61000-3-12
for devices with a phase current of between 16A and 75A and professional devices from 1kW up to a phase current of 16 A.
2.9.3 Interference immunity requirements
In general, the interference immunity requirements for a frequency inverter hinge on the specific environment in which the inverter is installed.
The requirements for industrial environments are therefore higher than those for residential and office environments.
The frequency inverter is designed such that the immunity requirements for industrial environments and, thus, the lower-level requirements for residential and office environments, are met and fulfilled.
The following relevant generic standards are used for the interference immunity test:
EN 61000-4-2: Electromagnetic compatibility (EMC)
– Part 4-2: Testing and measurement techniques – Electrostatic discharge
immunity test
EN 61000-4-3: Electromagnetic compatibility (EMC)
– Part 4-3: Testing and measurement techniques – Radiated, radio-frequency,
electromagnetic field immunity test
EN 61000-4-4: Electromagnetic compatibility (EMC)
– Part 4-4: Testing and measurement techniques – Electrical fast transient/burst
immunity test
EN 61000-4-5: Electromagnetic compatibility (EMC)
– Part 4-5: Testing and measurement techniques – Surge immunity test
EN 61000-4-6: Electromagnetic compatibility (EMC)
– Part 4-6: Testing and measurement techniques – Immunity to conducted
disturbances, induced by radio-frequency fields
Page 12
3 Software Changes
12 of 68
KSBDeltaSolo / KSBDeltaEco
3 Software Changes
The software has been specially created for this product and thoroughly tested. Making changes or additions to the software or parts of the software is prohibited. This does not, however, apply to software updates supplied by KSB.
Page 13
4 Transport/Temporary Storage/Disposal
13 of 68
KSBDeltaSolo / KSBDeltaEco
4 Transport/Temporary Storage/Disposal
4.1 Checking the condition upon delivery
1. On transfer of goods, check each packaging unit for damage.
2. In the event of in-transit damage, assess the exact damage, document it and notify KSB or the supplying dealer and the insurer about the damage in writing immediately.
4.2 Transport
NOTE
The pressure booster system is bolted to a pallet and wrapped in plastic film for shipping and temporary storage. All connecting points are capped.
DANGER
Pressure booster system tipping over
Danger to life from falling pressure booster system!
Never suspend the pressure booster system by its power cable.Do not lift the pressure booster system by its manifold.Observe the applicable local accident prevention regulations.Observe the information on weights, centre of gravity and fastening points.Use suitable and permitted transport equipment, e.g. crane, forklift or pallet
jack.
ü The pressure booster system has been checked for in-transit damage.
1. Make sure the transport equipment is suitable for safely carrying the indicated load.
2. Transport the pressure booster system to the place of installation.
3. Attach the pressure booster system to the lifting tackle. Lift it off the pallet. Dispose of the pallet.
4. Use suitable lifting equipment to lift the pressure booster system and carefully place it down at the place of installation.
4.3 Storage/preservation
If commissioning is to take place some time after delivery, the following measures are recommended when storing the pressure booster system:
CAUTION
Damage during storage due to frost, moisture, dirt, UV radiation or vermin
Corrosion/contamination of pressure booster system!
Store the pressure booster system in a frost-proof room. Do not store outdoors.
CAUTION
Wet, contaminated or damaged openings and connections
Leakage or damage of the pressure booster system!
Only open the openings of the pressure booster system at the time of
installation.
Page 14
4 Transport/Temporary Storage/Disposal
14 of 68
KSBDeltaSolo / KSBDeltaEco
NOTE
Rotate the shaft by hand every three months, e.g. via the motor fan.
Store the pressure booster system in a dry, protected room where the atmospheric humidity is as constant as possible.
4.4 Return to supplier
1. Drain the pressure booster system as per operating instructions.
2. Always flush and clean the pressure booster system, particularly if it has been used for handling noxious, explosive, hot or other hazardous fluids.
3. If the pressure booster system has handled fluids whose residues could lead to corrosion damage in the presence of atmospheric humidity or could ignite upon contact with oxygen, the pressure booster system must also be neutralised and treated with anhydrous inert gas to ensure drying.
4. Always complete and enclose a certificate of decontamination when returning the pressure booster system. (ðSection13,Page63) Always indicate any safety and decontamination measures taken.
NOTE
If required, a blank certificate of decontamination can be downloaded from the following web site: www.ksb.com/certificate_of_decontamination
4.5 Disposal
WARNING
Fluids handled, consumables and supplies which are hot and/or pose a health hazard
Hazard to persons and the environment!
Collect and properly dispose of flushing fluid and any fluid residues.Wear safety clothing and a protective mask if required.Observe all legal regulations on the disposal of fluids posing a health hazard.
1. Dismantle the pressure booster system. Collect greases and other lubricants during dismantling.
2. Separate and sort the pump materials, e.g. by:
- Metals
- Plastics
- Electronic waste
- Greases and other lubricants
3. Dispose of materials in accordance with local regulations or in another controlled manner.
Page 15
5 Description
15 of 68
KSBDeltaSolo / KSBDeltaEco
5 Description
5.1 General description
Pressure booster system
5.2 Designation
Example: KSB Delta Eco 3/1508 SVP
Table7: Designation key
Code Description
KSB Delta Eco Type series 3 Number of pumps 15 Size 08 Number of stages SVP Design
SVP Pressure booster system with variable speed system and KSB
SuPremE motor
5.3 Name plate
ID PN Prod. IP RDP PO U Kalkovenweg 13 F Alphen a/d Rijn, NL Imax www.ksb.com
KSB B. V.
Made in NL
KSB Delta Eco 3/1508
SVP
48278598
56.1A
50 Hz
3x400V
PT
01/2018 1234567-01
123456789
54
16
1
14
13
12
6
11
10
9
8
7
2
5
43
Fig.1: Name plate (example)
1 Type series 8 Dry running protection 2 Design 9 Power supply voltage 3 Number of pumps 10 Power supply frequency 4 Size 11 Maximum current input 5 Number of pump stages 12 Max. operating pressure 6 Serial number 13 Enclosure 7 Month of production/ year of
production, consecutive number
14 Order number
5.4 Design details
Design
Fully automatic pressure booster package systemVariable speed operationBaseplate-mountedHydraulic components made of stainless steel/ brass for high operating reliabilityLift check valve for each pumpShut-off valve for each pump
Page 16
5 Description
16 of 68
KSBDeltaSolo / KSBDeltaEco
Membrane-type accumulator on the discharge side, approved for drinking waterPressure gauge for pressure indicationElectronic dry running protectionPressure transmitter on the discharge sideAnti-vibration pads per pump
Installation
Stationary dry installation
Drive
Electric motorEfficiency class IE4/IE5 to IEC TS 60034-30-2:2016IP54 enclosure
Automation
One frequency inverter per pumpService interface for connection to a PCMotor protection switch per pumpControl cabinet IP54Fault message signalling contact per pumpOperation signalling contact per pump
5.5 Configuration and function
1
2
3
6
4
5
2
3
6
4
Fig.2: Configuration
1 Terminal box 2 Pump 3 Control unit 4 Membrane-type accumulator 5 Manifold 6 Baseplate
Design The fully automatic pressure booster system is equipped with vertical high-pressure
pumps (2) (all of which are speed-controlled) for pumping the fluid handled to the consumer installations in the set pressure range.
Function Either two or three pumps (2) are controlled and monitored by motor-mounted
frequency inverters. As the demand increases or decreases, pumps are started and stopped automatically. As soon as the demand increases again after one pump has been stopped, another
Page 17
5 Description
17 of 68
KSBDeltaSolo / KSBDeltaEco
pump which has not been in operation before is started up. The stand-by pump is also included in the alternating cycle. The standard setting is for the pressure booster system to start automatically as a function of pressure; the actual pressure is measured by an analog pressure measuring device (pressure transmitter). As long as the pressure booster system is in operation, the pumps are started and stopped as a function of demand (standard setting). In this way it is ensured that the individual pumps operate only in line with actual demand. The use of variable speed pumps reduces wear as well as the frequency of pump starts in parallel operation. If a duty pump fails, the next pump is started up immediately. A fault is output, which can be reported via volt-free contacts (e.g. to the control station). If the demand drops towards 0, the pressure booster system slowly runs down to the stop point.
As standard, one of the pumps is on stand-by. The control system defines each of the pumps as stand-by pump in alternation. This prevents stagnation of water in any of the pumps. Via a parameter in the control system the stand-by pump function can be disabled in order to operate the system without stand-by function.
The pressure booster system is designed with integrated electronic dry running protection. A digital lack-of-water indicator can be connected to the corresponding contacts.
During commissioning and after every power failure, the pressure booster system fills the piping system slowly, to prevent any damage to the piping by surge pressure.
5.6 Noise characteristics
Pressure booster systems are available with different numbers and sizes of pumps. Therefore, the expected total sound pressure level in dB(A) needs to be calculated. Refer to the pump's operating manual for the noise characteristics of the individual pumps.
Calculation example:
Number of pumps Expected total sound pressure level
in dB(A)
Single pump . . . . . dB(A)
2 pumps, total +3 dB(A) 3 pumps, total +4,5 dB(A) 4 pumps, total +6 dB(A) 5 pumps, total +7 dB(A) 6 pumps, total +7,5 dB(A)
Example Single pump 48 dB(A) 4 pumps, total +6 dB(A)
54 dB(A)
The expected total sound pressure level of 54dB(A) for this configuration may develop when all four pumps are running under full-load conditions. Refer to the pumps' operating manual for the noise characteristics of the individual pumps.
5.7 Scope of supply
Depending on the model, the following items are included in the scope of supply:
Up to three vertical high-pressure centrifugal pumps with oval flangePowder-coated / epoxy resin-coated steel baseplateIntegrated check valve per pumpDischarge-side gate valve per pumpSuction-side gate valve per pump
Page 18
5 Description
18 of 68
KSBDeltaSolo / KSBDeltaEco
Suction-side manifold and discharge-side manifold made of stainless steelPressure transmitter on the discharge sidePressure gaugeDry running protection switch on the inlet pressure sideMembrane-type accumulator on the discharge side, approved for drinking waterControl cabinet IP54
– Sheet steel housing: colour RAL7035 – Parameterisable BoosterControl Advanced control unit – Graphical display with operating panel – Three LEDs signalling the operating status – Lockable master switch (repair switch) – Motor protection switch per pump – One frequency inverter per pump – Service interface for KSB ServiceTool
5.8 Dimensions
For dimensions refer to the outline drawings of the pressure booster system.
5.9 Terminal wiring diagram
For the terminal assignment refer to the circuit diagram.
5.10 Potential equalisation
Fig.3: Earth symbol
A terminal marked with the earth symbol is provided on the baseplate for connecting a PE conductor.
1
2
Fig.4: PE terminal
1 Earthing terminal 2 Baseplate
Page 19
6 Installation at Site
19 of 68
KSBDeltaSolo / KSBDeltaEco
6 Installation at Site
6.1 Installation
Install pressure booster systems either in the technical equipment room or in a well­ventilated, frost-free, lockable room used for no other purpose. No harmful gases are allowed to enter the place of installation. An adequately sized floor drain (leading to a sewer or equivalent) must be provided.
The pressure booster system is designed for a maximum ambient temperature of 0°C to +40°C at a relative humidity of 50%.
NOTE
Do not install pressure booster systems next to sleeping or living quarters.
The anti-vibration mounting of the pressure booster system provides adequate insulation against solid-borne noise. If expansion joints (KSB accessory) are used for damping vibrations, their fatigue strength (endurance limit) must be given due consideration. Expansion joints must be easily replaceable.
6.2 Checks to be carried out prior to installation
Place of installation
WARNING
Installation on mounting surfaces which are unsecured and cannot support the load
Personal injury and damage to property!
Use a concrete of compressive strength class C12/15 which meets the
requirements of exposure class X0 to EN206-1.
The mounting surface must have set and must be completely horizontal and
even.
Observe the weights indicated.
NOTE
The anti-vibration mounts of the pressure booster system provide adequate insulation against solid-borne noise. Thanks to level-adjustable feet (KSB accessory) the pressure booster system can also be installed in a horizontal position on uneven floors.
For pressure booster systems with Movitec 2, 4, 6, 10 and 15, level-adjustable feet are available as accessories.
Check the structural requirements. All structural work required must have been prepared in accordance with the dimensions stated in the outline drawings.
6.3 Installing the pressure booster system
WARNING
Top-heavy pressure booster system
Risk of personal injury by pressure booster system tipping over!
Pressure booster systems awaiting final installation must be secured against
tipping over.
Firmly anchor the pressure booster system.
Page 20
6 Installation at Site
20 of 68
KSBDeltaSolo / KSBDeltaEco
Remove all packaging before installing the pressure booster system. Connect the pressure booster system's inlet line and discharge line to the corresponding site distribution lines.
NOTE
In order to avoid transmission of piping forces onto the pressure booster system and transmission of solid-borne noise, we recommend installing length-limited expansion joints.
Allow sufficient space for maintenance and repair work.
ü All structural work required has been checked. ü The dimensions of the concrete foundation are correct, and the concrete has set
firmly.
1. Mark out the anchoring holes on the floor as shown in the outline drawing.
2. Drill the holes (max. diameter: 12mm).
3. Insert plug fixings of appropriate size.
4. Set the pressure booster system down in its correct installation position.
5. Use suitable bolts to firmly anchor the pressure booster system.
6.4 Installing the piping
Make sure that piping is installed without transmitting any stresses or strains. The use of length-limited expansion joints (see accessories) is recommended.
CAUTION
Air pockets in suction line
Pressure booster system cannot prime!
Lay piping with a continuously rising slope (as shown).
Suction lift operation
Incorrect Correct
NOTE
For suction lift operation install suitable swing check valves at the suction line ends which are submerged in the fluid handled. Take into account the head losses caused by these swing check valves. Do not exceed the maximum suction lift of the pumps.
6.4.1 Fitting an expansion joint
DANGER
Sparks and radiant heat
Fire hazard!
Take suitable precautions to protect the expansion joint if any welding work is
carried out nearby.
Page 21
6 Installation at Site
21 of 68
KSBDeltaSolo / KSBDeltaEco
CAUTION
Leaking expansion joint
Flooding of installation room!
Regularly check for cracks or blisters, exposed fabric or other defects.
ü The expansion joint has a length limiter with solid-borne sound insulation so as
to be able to absorb reaction forces.
1. Install the expansion joint in the piping free of twist or distortion. Never use the expansion joint to compensate for misalignment or mismatch of the piping.
2. Tighten the bolts evenly and crosswise during assembly. The ends of the bolts must not protrude from the flange.
3. Do not apply paint to the expansion joint. Protect it from any contact with oil.
4. The position of the expansion joint within the pressure booster system must allow easy access and inspection and it must, therefore, not be insulated along with the piping.
5. Expansion joints are subject to wear.
6.4.2 Installing a pressure reducer
NOTE
A pipe length of approximately 600 mm must be provided on the inlet side to accommodate a pressure reducer, if necessary.
NOTE
A pressure reducer must be installed
- if the inlet pressure fluctuation is too high for the pressure booster system to operate as intended or
- if the total pressure (inlet pressure plus shut-off head) of the pressure booster system exceeds the design pressure. The maximum pump discharge pressure at zero flow point is reached in manual mode.
A minimum pressure gradient of 5 metres is required for the pressure reducer to fulfill its function. The pressure downstream of the pressure reducer (downstream pressure) is the basic parameter for determining the pump head.
For example:
The inlet pressure fluctuates between 4 and 8 bar. A pressure reducer is needed upstream of the pressure booster system on the inlet side. Min. inlet pressure (p
inl
)=4bar Min. pressure gradient=0.5bar Downstream pressure=3.5bar.
6.5 Installing unpressurised inlet tanks
Installation and location of an unpressurised inlet tank together with the pressure booster system are governed by the same rules applicable to the pressure booster system.
Install the closed PE inlet tank (under atmospheric pressure) available as a KSB accessory as described in the installation instructions supplied with the tank.
CAUTION
Contamination in the pressure booster system
Damage to the pumps!
Clean the tank before filling it.
Page 22
6 Installation at Site
22 of 68
KSBDeltaSolo / KSBDeltaEco
The tank must be connected mechanically and electrically to the pressure booster system prior to commissioning of the system.
6.6 Fitting the dry running protection device
Install the dry running protection device supplied together with the pressure booster system as a separate, non-fitted accessory, or supplied at a later date for retrofitting, in accordance with its operating instructions and connect it to the switchgear and controlgear assembly. The switchgear and controlgear assembly is provided with the requisite inputs.
For a multiple pump system:
1. For information on connecting the external dry running protection device, refer to the circuit diagram.
For a single-pump system:
1. Remove the front cover to access the terminal strip.
NOTE
The new frequency inverter generation is equipped with a second relay.
400V/ 3~ variant with
1relay
DI­E
N
+ 2 4 V
G ND
DI 3
DI2D
I
1
+ 2 4 V
DIC
OM
AO
­G
N D
AO
A I
N 2
N O
+ 24
V
GN
D
COM+24V
B1B2B3B
4B5B6
B7
B8B
9
B1 0
A 1
A2A3A4A
5
A 6
A 7
A8
A 9
A 1 0
GNDG
N D
AI N1
+2 4
V
L1 L2 L3
LINE
PE U V W
MOTOR
PTC
MOTOR
PE
-
1
2
3
4
BR
+
6
1
2
Fig.5: Overview of terminal strips for 400V/ 3~ variant with 1relay
1 Connection to power supply
network and motor
2 Control cables
In the case of direct connection (direct connection of the pump system to the drinking water supply line of the public water supply system):
1. Use a wire jumper to connect DI1 (B4) and +24V (B3). ð When this connection type is used, monitoring by the suction-side pressure
sensor protects the pump system against lack of water.
In the case of indirect connection (connection to an unpressurised drinking water reservoir (water tank)):
1. Remove the wire jumper between DI1 (B4) and +24V (B3). Connect an external dry running protection device (e.g. a float switch) in its place.
ð When this connection type is used, the lack-of-water function must be
adjusted.
Page 23
6 Installation at Site
23 of 68
KSBDeltaSolo / KSBDeltaEco
Adjusting the lack-of-water function:
1. Log in at the frequency inverter using the customer login (standard: 0000). Open parameter 3 "Settings".
2. Open parameter 3-9-11 "Lack-of-water function". Adjust parameters 3-9-11-5 and 3-9-11-6.
3. If a single-pump pressure booster system is operated with an indirect connection (e.g. water tank), set parameter 3-9-11-4 to "OFF".
6.7 Connection to power supply
DANGER
Electrical connection work by unqualified personnel
Danger of death from electric shock!
Always have the electrical connections installed by a trained and qualified
electrician.
Observe regulations IEC60364.
WARNING
Incorrect connection to the mains
Damage to the mains network, short circuit!
Observe the technical specifications of the local energy supply companies.
NOTE
A motor protection device is recommended.
NOTE
If a residual current device is installed, observe the operating manual for the frequency inverter.
The circuit diagrams for the pressure booster system are included in the control cabinet, where they must remain when not in use. The product literature of the switchgear and controlgear assembly supplied with the pressure booster system includes a list of the electrical components installed. When ordering spare parts for electrical components, please always indicate the circuit diagram number.
6.7.1 Sizing the power cable
The cross-section of the power cable must be sized for the total rated power requirement.
6.7.2 Connecting the pressure booster system
Single-pump system
Plug the mains plug into a suitable socket. Observe the data on the name plate.
Multiple pump system:
Connect the pressure booster system to the power supply via terminals L1, L2, L3 and PE as shown in the enclosed circuit diagram. Observe the data on the name plate.
For accessories and/or integrated machinery components, observe the relevant manufacturer's product literature.
Page 24
6 Installation at Site
24 of 68
KSBDeltaSolo / KSBDeltaEco
6.7.3 Removing the housing cover
DANGER
Contact with live components
Risk of fatal injury due to electric shock!
Any work on the product shall only be performed when it has been
disconnected from the power supply (de-energised).
Never remove the centre housing part from the heat sink.Mind the capacitor discharge time.
After switching off the frequency inverter, wait 10minutes until dangerous voltages have discharged.
The terminal wiring compartment is covered by a screwed-on housing cover. The terminals of the power and motor connection cables are additionally guarded by a protective cover to prevent them from being touched.
Housing cover
Fig.6: Housing cover
1. Remove the cross recessed head screws on the cover.
2. Remove the cover.
Protective cover
Fig.7: Prying open the protective cover
1. The protective cover for connecting the power and motor connection cables is push fit. Before connecting the power and motor connection cables, carefully pry open the protective cover using a wide screwdriver.
Fig.8: Removing the protective cover
2. Remove the protective cover.
Page 25
6 Installation at Site
25 of 68
KSBDeltaSolo / KSBDeltaEco
6.7.4 Overview of terminal strips
400V/ 3~ variant with
1relay
DI­E
N
+ 2 4 V
G ND
DI 3
DI2D
I
1
+ 2 4 V
DIC
OM
AO
­G
N D
AO
A I
N 2
N O
+ 24
V
GN
D
COM+24V
B1B2B3B
4B5B6
B7
B8B
9
B1 0
A 1
A2A3A4A
5
A 6
A 7
A8
A 9
A 1 0
GNDG
N D
AI N1
+2 4
V
L1 L2 L3
LINE
PE U V W
MOTOR
PTC
MOTOR
PE
-
1
2
3
4
BR
+
6
1
2
Fig.9: Overview of terminal strips for 400V/ 3~ variant with 1relay
1 Mains power supply and motor
connection
2 Control cables
NOTE
The new frequency inverter generation is equipped with a second relay.
400V/ 3~ variant with
2relays
L1 L2 L3
LINE
PE U V W
MOTOR
PTC
MOTOR
PE
-
1
2
3
4
BR
+
6
1
2
DI-EN
+24V
GND
DI3
DI2
DI1
+24V
DICOM
AO-GND
AO
AIN2
NO1
+24V
GND
COM1
+24V
B7
B 8
B9
B10
GND
GND
AIN1
+24V
NO
2
2
+24V
C1
C2
C 3
GND
B1
B2B3B4
B 5
B6
A1A2A3
A4
A5A6A7
A8
A9
A 10
C 4
Fig.10: Overview of terminal strips for 400V/ 3~ variant with 2relays
1 Mains power supply and motor
connection
2 Control cables
230V/ 1~ variant
L N
LINE
PE U V W
MOTOR
PTC
MOTOR
PE
-
1
2
3
4
BR
+
6
1
2
DI-EN
+24V
GND
DI 3
DI2
DI 1
+ 24
V
DICOM
AO-GND
A O
AIN2
NO1
+24
V
GND
COM
1
+ 24
V
B 7
B8
B9
B10
GND
GND
AIN1+
24 V
NO2
COM
2
+24V
C1
C2C
3
GND
B1
B 2
B3
B 4
B5B
6
A1
A2
A 3
A4A5
A6A7A
8
A9
A10
C4
Fig.11: Overview of terminal strips for 230V/ 1~ variant
1 Mains power supply and motor
connection
2 Control cables
Page 26
6 Installation at Site
26 of 68
KSBDeltaSolo / KSBDeltaEco
6.7.5 Connection to mains power supply and motor
DANGER
Touching or removing the terminals and connectors of the braking resistor
Risk of fatal injury due to electric shock!
Never open or touch the terminals and connectors of the braking resistor as
long as the frequency inverter is energised.
CAUTION
Incorrect electrical installation
Damage to the frequency inverter!
Never fit a contactor (in the motor connection cable) between the motor and
the frequency inverter.
1. Route the power cable for the mains power supply and/or the motor connection cable through the cable glands and connect the cable(s) to the specified terminals.
2.
Connect the line for a PTC connection/PTC thermistor to the PTC terminal strip (3).
Connecting motor
monitoring devices (PTC
thermistor)
If no PTC connection is available on the motor side, parameter 3-2-3-1 (PTC Analysis) must be deactivated.
NOTE
IP55 enclosure protection as specified in the technical data is only provided if the cover has been fitted properly.
Size A
L1 L2 L3
LINE
P E U V W
MOTOR
P TC
MOTOR
P E
-
L1 L2 L3
N
P E
1
2
3
4
5
M
3~
BR
+
6
6
Fig.12: Establishing the mains power supply and motor connections, sizeA, 400V/3~ variant
Mains connection Motor connectionPTC connection Braking resistorMotor PTC Jumper for IT mains
Page 27
6 Installation at Site
27 of 68
KSBDeltaSolo / KSBDeltaEco
L N
PE
5
M
3~
L N
LINE
PE U V W
MOTOR
PTC
MOTOR
PE
-
1
2
3
4
BR
+
6
Fig.13: Establishing the mains power supply and motor connections, sizeA, 230V/1~ variant
Mains connection Motor connectionPTC connection Braking resistorMotor PTC Jumper for IT mains
Size B
L1 L2 L3
LINE
P E U V W
MOTOR
P TC
MOTOR
P E
-
L1 L2 L3
N
P E
1
2
3
4
5
M
3~
BR
+
6
6
Fig.14: Establishing the mains power supply and motor connections, sizeB
Mains connection Motor connectionPTC connection Braking resistorMotor PTC Jumper for IT mains
Page 28
6 Installation at Site
28 of 68
KSBDeltaSolo / KSBDeltaEco
Size C
L1 L2 L3
LINE
PE U V W
MOTOR
PTC
MOTOR
PE
-
L1 L2 L3
N
PE
1
2
3
4
5
M
3~
BR
+
6
Fig.15: Establishing the mains power supply and motor connections, sizeC
Mains connection Motor connectionPTC connection Braking resistorMotor PTC Jumper for IT mains
IT mains
DANGER
Contact with live components
Risk of fatal injury due to electric shock!
Any work on the product shall only be performed when it has been
disconnected from the power supply (de-energised).
Never remove the centre housing part from the heat sink.Mind the capacitor discharge time.
After switching off the frequency inverter, wait 10minutes until dangerous voltages have discharged.
Jumper in IT mains If the frequency inverter is to be used in an IT mains, the relevant IT mains jumpers
must be removed.
6.7.5.1 Directly connecting the motor cable without motor connector (for sizes A and B only)
DANGER
Improper electrical connection
Risk of fatal injury due to electric shock!
Never simultaneously use the motor connector with a motor cable that is
directly connected to the motor terminals.
Never touch terminals and plug-type connections of the motor connector.
When directly connecting a motor cable to the designated motor terminals (U, V, W), the motor connector fitted at the factory must first be removed.
Page 29
6 Installation at Site
29 of 68
KSBDeltaSolo / KSBDeltaEco
Fig.16: Disconnecting the cores of the motor connector
1. Disconnect the cores of the motor connector at terminals U, V and W.
Fig.17: Removing the motor connector
2. Remove the motor connector from the heat sink.
Fig.18: Inserting and fastening cover
3. Close the opening in the heat sink using the kit accompanying the frequency inverter (comprising a cover, gasket and bolts/screws).
NOTE
IP55 enclosure protection as specified in the technical data is only provided if the cover has been fitted properly.
Page 30
6 Installation at Site
30 of 68
KSBDeltaSolo / KSBDeltaEco
6.7.5.2 Retrofitting a frequency inverter for a KSB SuPremE B2 motor (for sizes C only)
Fig.19: Plug
The heat sink is closed with a plug. The following steps must be carried out to retrofit for a KSB SuPremE B2 motor.
1. Remove screwed-in plug.
Fig.20: Removing the plug
2. Remove the nut from the plug inside the frequency inverter.
NOTE
IP55 enclosure protection as specified in the technical data is only provided if the O­ring has been fitted properly.
Fig.21: Inserting the O-ring
3. Place O-ring onto adapter.
DANGER
Pinching of power cable and motor power cable
Risk of fatal injury due to electric shock!
Never damage the insulation of the power cable and motor power cable when
inserting into the opening of the frequency inverter.
Page 31
6 Installation at Site
31 of 68
KSBDeltaSolo / KSBDeltaEco
Fig.22: Inserting motor
cables
4. Place the frequency inverter onto the motor adapter of the KSB SuPremE B2 motor and insert the motor cables of the KSB SuPremE B2 motor into the opening of the frequency inverter.
5. Connect the motor cables as described.
Fig.23: Connecting the motor cables
6. Connect the PTC cables that are supplied as standard with the KSB SuPremE B2 motor.
7. Close the frequency inverter with the protective cover and the housing cover.
6.7.6 Establishing an earth connection
The frequency inverter must be earthed. Observe the following when establishing the earth connection:
Ensure that the cable lengths are as short as possible.Use different earth bus bars for the control and power/motor connection cables.The earth bus bar of the control cable must not be affected by currents from the
power/motor connection cables since this could be a source of interference.
Connect the following to the earth bus bar of the power/motor connection cable:
Motor earthing connectionsHousing of the frequency inverterShielding of the power/motor connection cable
Connect the following to the earth bus bar of the control cable:
Shielding of the analog control connectionsShielding of the sensor cablesShielding of the field bus connection cable
Installing multiple
frequency inverters
Fig.24: Establishing an earth connection
If you are installing more than one frequency inverter, the star configuration is recommended.
Page 32
7 Commissioning/Start-up/Shutdown
32 of 68
KSBDeltaSolo / KSBDeltaEco
7 Commissioning/Start-up/Shutdown
7.1 Commissioning/Start-up
7.1.1 Prerequisites for commissioning/start-up
Before commissioning/start-up of the pressure booster system make sure that the following requirements are met:
The pressure booster system has been properly connected to the electric power
supply and is equipped with all protection devices.
All relevant VDE standards and/or regulations applicable in the country of use are
complied with.
The dry running protection device has been installed.
CAUTION
Dry running of pump
Damage to the pump/pressure booster system!
If no dry running protection device is connected when commissioning takes
place, pressure booster systems in manual or test run mode will be stopped automatically after approx. 10 seconds. If the dry running protection terminal is disabled by means of a bridge, the operator shall assume responsibility for any dry running that might occur.
NOTE
The competent authorities must be informed in due time prior to commissioning/ test running the system.
7.1.2 Dry running protection
Pressure booster systems are fitted with a dry running protection device. A float switch whose volt-free contact closes the circuit in upper float position can be
connected to the control system as dry running protection. Follow the float switch manufacturer's instructions on how to set the float switch levels.
7.1.3 Commissioning/start-up of pressure booster system
NOTE
The pressure booster systems undergo hydraulic testing with water at the factory and are drained carefully before shipment. However, for technical reasons the presence of some residual water is unavoidable. The hydraulic connections are closed in as-supplied condition. They must only be opened immediately before installation. Refer to EN806 before commissioning/starting up the pressure booster system. After an extended pre-installation period, in particular, flushing or even professional disinfection is recommended. For extensive or branched piping systems the pressure booster system should preferably be flushed either before installation, or flushing should be restricted to a limited area.
Commissioning should be carried out by specialist KSB staff.
Page 33
7 Commissioning/Start-up/Shutdown
33 of 68
KSBDeltaSolo / KSBDeltaEco
CAUTION
Foreign matter in the piping
Damage to the pumps/pressure booster system!
Before commissioning/starting (or even test running) the pressure booster
system, make sure that there is no foreign matter in the pressure booster system or piping.
NOTE
Commissioning of the pressure booster system - even test running - shall only be carried out in full compliance with all pertinent VDE (German Association of Electrical Engineers) regulations.
CAUTION
Operation without the fluid to be handled
Damage to the pump!
Prime the pressure booster system with the fluid to be handled.
ü The pipe unions between the pump and the piping have been re-tightened. ü The flange bolting has been checked for firm seating. ü The cooling air inlet and outlet openings on the motor are unobstructed. ü All shut-off valves of the pressure booster system are open. ü The pre-charge pressure of the membrane-type accumulator has been checked.
(ðSection9.2.3,Page45)
1. Set the master switch to "0"; unlock all motor protection switches (if applicable).
2. Provide connection to power supply.
3. Open/loosen the vent plugs on the pumps (refer to the pump's installation/ operating manual).
4. Slowly open the inlet-side shut-off element and prime the pressure booster system until the fluid to be handled escapes through all vent holes.
5. Close and slightly tighten the pump vent plugs.
6. Switch on all motor protection switches.
7. Set manual-0-automatic selector switches (if any) to Automatic.
8. Switch on the master switch.
9. Open the discharge-side shut-off element.
10. When all pumps are running, loosen the vent plugs again to let any remaining air escape.
11. Then re-tighten the vent plug firmly.
12. Check that the pumps are running smoothly.
13. Close the discharge-side shut-off element for a short period and verify that the pumps reach the shut-off head.
14. Close the discharge-side shut-off element, causing all pumps to stop.
NOTE
Minor leakage of the mechanical seals during commissioning is normal and will cease after a short period of operation.
Page 34
7 Commissioning/Start-up/Shutdown
34 of 68
KSBDeltaSolo / KSBDeltaEco
7.2 Switching on the pressure booster system
Switch on the master switch to energise the pressure booster system. The traffic light display provides information on the operating status of PumpDrive.
NOTE
The pressure booster system is factory-set to the operating data indicated on the name plate.
7.3 Checklist for commissioning/start-up
Table8: Checklist
Operations Done
1 Read the operating instructions. 2 Check power supply and compare against the name plate data. 3 Check the earthing system (by measuring). 4 Check the mechanical connection to the water mains.
Re-tighten the flange bolting and pipe unions. 5 Prime and vent the pressure booster system from the inlet side. 6 Check inlet pressure. 7 Check whether all cables are still firmly connected to the terminals inside the control unit. 8 Compare the settings of the motor protection switches with the name plate data; re-adjust, if
necessary. 9 Check the start and stop pressure; re-adjust, if necessary. 10 Test the proper function of the lack-of-water and dry running protection equipment. If not
fitted, make a relevant note in the commissioning report. 11 Vent the pumps for a second time after they have been running for 5 to 10 minutes. 12 Set all switches to "automatic". 13 Check the pre-charge pressure. 14 Record all system conditions that do not correspond to our specifications or to the purchase
order in the commissioning report (i.e. no dry running protection or inlet pressure + max.
pressure of pressure booster system higher than 16 bar). 15 Complete the commissioning report together with the operator/user and instruct the operator/
user as to the function of the system.
7.4 Shutdown
NOTE
As long as the pressure booster system is out of operation, water is supplied directly at p
inl
through the pressure booster system.
Set the master switch to "0".
NOTE
Drain the pressure booster system for prolonged shutdown.
Page 35
8 Operation
35 of 68
KSBDeltaSolo / KSBDeltaEco
8 Operation
8.1 Standard control panel
1
3
4
5
2
AUTO
1/min
Fig.25: Standard control panel
Table9: Description of standard control panel
Item Description Function
1 Service interface Optical interface 2 LED traffic light function The traffic light function provides information about the system's
operating status. 3 Display Displays information on frequency inverter operation 4 Operating keys Toggling operating modes 5 Navigation keys Navigation and parameter setting
8.1.1 Display
OFFOFF
MAN
AUTO
1/min
m h kW
A V Hz
% °C bar
1 2
3
4
5
6
7
8
9
Fig.26: Main screen (example)
1 Operating point display 2 Type of control 3 Display of the current operating mode
Page 36
8 Operation
36 of 68
KSBDeltaSolo / KSBDeltaEco
4 Units 5 Menu, parameter number, parameter values 6 Log in as customer 7 Active wireless connection
The wireless icon illuminates when the Bluetooth module is inserted. The
wireless icon flashes when communication takes place. 8 Single/dual pump 9 Rotational speed 0-100%
Table10: Menu, parameter number, parameter values, messages
Display Function
AUTO
Menu example: Open-loop Control
Menu example: Open-loop Control (1-3):
The letter S is used as the first character to identify a menu.The second character identifies the first menu level, i.e. Operation S1-x-x-x,
Diagnosis S2-x-x-x, Settings S3-x-x-x and Information S4-x-x-x.
The wrench icon shows that you have logged in as a customer.
AUTO
bar
Parameter number example: Setpoint (Closed-loop Control)
Parameter number example: Setpoint (Closed-loop Control) (1-3-2):
The letter P is used as the first character to identify a parameter number.The following characters show the parameter number.The wrench icon shows that you have logged in as a customer.
AUTO
bar
Parameter value example: Setpoint (Closed-loop Control)
Parameter value example: Setpoint (Closed-loop Control) (1-3-2) set to 4 bar:
If a parameter value can be edited, the digit flashes.The wrench icon shows that you have logged in as a customer.
AUTO
1/min
Message example: Dry running
Message example: Dry running (E13):
A message is identified by the letter E (Error) and a unique number.
Page 37
8 Operation
37 of 68
KSBDeltaSolo / KSBDeltaEco
Table11: Assignment of keys
Key Function
Arrow keys:
Move up/down in the menu options.Increase/decrease a numerical value. (When an arrow key is pressed and held down, the
response repeats in ever shorter intervals.)
ESC
Escape key:
Delete/reset entry
(the entry is not saved).
Move up one menu level.
OK
OK key:
Confirm settings.Confirm menu selection.Move to the next digit when entering numerals.Message display: Acknowledge alert.Measured value display: Go to Favourites menu.
MAN
MAN operating key:
Starts the frequency inverter in manual operating mode.
OFF
OFF operating key:
Stops the frequency inverter.
AUTO
AUTO operating key:
Switches to automatic operating mode.
Manual mode via control panel
NOTE
After a power failure, the frequency inverter reverts to the OFF operating mode. Manual mode must be restarted.
Table12: Assignment of keys for manual mode
Key Function
MAN
MAN operating key:
When switching the operating mode from AUTO to MAN, the current operating speed is
used as control value (Manual) 1-3-4 and is displayed accordingly. The control point 1-3-10 must be set to Local.
When switching the operating mode from OFF to MAN, the frequency inverter operates
at minimum speed. The control point 1-3-10 must be set to Local.
If the control value (Manual) 1-3-4 is defined via an analog input, the analog input speed
is accepted.
Arrow keys:
Pressing the arrow keys changes and immediately accepts the control value (Manual)
1-3-5. Making a change using the arrow key has a direct effect even when not confirmed with OK. The speed can only be changed between the set minimum speed and the maximum speed.
ESC
OK
ESC/OK key:
Press the OK or ESC key to go from digit to digit. Press the ESC key to go back. Changes
are rejected. Pressing the OK key for the right-hand digit takes you back to the main screen.
Page 38
8 Operation
38 of 68
KSBDeltaSolo / KSBDeltaEco
8.1.2 Main screen
The main screen shows factory default operating values.
AUTO
Hz
AUTO
1/min
AUTO
kW
AUTO
A
AUTO
Hz
AUTO
1/min
AUTO
kW
AUTO
A Hz
ESC
OK
ESC
OK
ESC
OK
ESC
OK
1 2
43
5
87
6
Fig.27: Selecting and displaying operating values on the main screen
1 Parameter number for speed (1-2-1-1) 2 Current speed [rpm] 3 Parameter number for motor input power (1-2-1-2) 4 Current power input of motor in kW 5 Parameter number for motor current (1-2-1-5) 6 Current motor current in A
Page 39
8 Operation
39 of 68
KSBDeltaSolo / KSBDeltaEco
7 Parameter number for output frequency (1-2-1-7) 8 Current output frequency in Hz
If a message (alert, warning or information) is currently active, it will be displayed on the main screen.
AUTO
1/min
Fig.28: Message display A message is identified by the letter E (Error) and a unique number (see list of all
messages in the Annex). The traffic light function shows whether the message is an alert (red LED), a warning (amber LED) or just information (green LED).
Messages are acknowledged by pressing OK. Acknowledged and gone messages are listed in the message history in Menu 2 – Diagnosis.
NOTE
If the motor standstill heater has been switched on, the display alternates between the measured value and the letter H.
8.1.3 Settings menu
NOTE
The standard control panel is designed to be used for simple settings only (e.g. setting the setpoint). We recommend using the KSB ServiceTool for more extensive configuration tasks.
Opening the Settings menu: Press and hold the ESC key and press OK.
AUTO
ESC
OKESC
+
AUTO
1/min
1 2
Fig.29: Switching to the settings menu
1 Main screen 2 Settings menu
The wrench symbol indicates that the settings menu has been opened and a value can be changed.
The parameter numbers identify the navigation path, which helps you find a particular parameter quickly and easily. The first digit of the parameter number indicates the first menu level, which is called up directly via the four menu keys.
Page 40
8 Operation
40 of 68
KSBDeltaSolo / KSBDeltaEco
8.1.3.1 Menu: Operation
The Operation section contains all information required for operating the machine and the process. This includes:
Login to device with passwordOperating and measured values for motor, frequency inverter, pump and systemSetpoints and control valuesEnergy meter and operating hours
8.1.3.1.1 Access levels
Three access levels have been defined to prevent unintentional or unauthorised access to frequency inverter parameters:
Table13: Access levels
Access level Description
Standard (No Login) Access without password entry. Customer Access level for the expert user with access to all parameters required for
commissioning
Customer service Access level for service personnel.
If a parameter's access level is not explicitly specified, the parameter is always assigned the Customer access level.
Table14: Access level parameters
Parameter Description Possible settings Factory setting
1-1-1 Customer Login
Log in as customer
0000...9999 0000
Customer service parameters can only be accessed using the KSBServiceTool and the appropriate dongle.
NOTE
If no keys are pressed for five minutes, the system will automatically return to the Standard access level..
The password can be changed after entering the factory default password.
Table15: Parameter for changing the password (requires use of the KSBServiceTool)
Parameter Description Possible settings Factory setting
1-1-5 Customer Access ID
Changing the customer access ID
0000...9999 -
8.1.3.2 Menu: Diagnosis
In the Diagnosis section, the user is provided with information about faults and warning messages that pertain to the pump set or process. The frequency inverter can be in fault (standstill) or warning (operational) status. The user can also find previous messages in the history.
Messages
All monitoring and protective functions trigger warnings or alerts. These are signalled via the amber or red LED of the LED traffic light function.
A corresponding message is output on the control panel display. If more than one message is output, the last one is displayed. Alerts have priority over warnings.
Pending messages If a message has occurred and been acknowledged but has not gone, this message
will be listed in the Pending Messages menu. All current messages can be displayed in the Diagnosis menu under Pending Messages (2-1). Active warnings and alerts can also be connected to the relay outputs.
Page 41
8 Operation
41 of 68
KSBDeltaSolo / KSBDeltaEco
Message history Only messages that have come, been acknowledged, and gone are listed in the
message history. The message history can be viewed by selecting the Message History parameter 2-2. The last 100 messages are listed here. You can use the arrow keys and the OK key to select an entry from the list.
Acknowledging and resetting messages
NOTE
Depending on the combination of settings, the frequency inverter could conceivably restart automatically after acknowledgement/reset or when the cause of the malfunction or fault has been eliminated.
Acknowledgement You can acknowledge the message once the cause has been rectified. Messages can
be acknowledged separately in the Diagnosis menu. A message can also be acknowledged via a digital input. Digital input 2 is defaulted for this purpose.
Overview of warnings and alerts (ðSection10,Page52) Messages can be acknowledged as follows:
Table16: Acknowledgement types for messages
Property of message Type of acknowledgement
Self-acknowledging Message self-acknowledges if condition for message has gone. Self-acknowledging
(configurable)
Users can choose between self-acknowledging and acknowledging manually.
Partially self­acknowledging
Alerts that are partially self-acknowledging carry out self-acknowledgement in increasingly large intervals after the alarm condition has gone. If the alert occurs repeatedly within a specific time window, no additional self-acknowledgement is carried out.
As soon as the alarm condition of a pending alert no longer exists, the time interval is started. When this interval expires, automatic acknowledgement takes place.
If the alert occurs again within 30seconds after the time interval has started, the interval is extended by one increment. Should this not be the case, the previous (shorter) time interval is reverted to and corresponding action is taken again in 30seconds. The time intervals are 1second, 5seconds, 20seconds, and endless (i.e. manual acknowledgement is required). When the 20-second interval is extended, self­acknowledgement no longer takes place.
Non-self-acknowledging Must be acknowledged manually.
Time stamp If a message is not acknowledged and its condition comes and goes several times in
this time window, the first occurrence of the message is always used for the Message Come time stamp. The Message Condition Gone time stamp, however, always shows the last time the message condition was no longer active.
8.1.3.3 Menu: Settings
General settings can be made or the settings for the process optimised in the Settings section.
Locking operating keys
Table17: Parameters for setting the control panel
Parameter Description Possible settings Factory setting
3-1-2-2 Control Keys Require Login
The MAN, OFF, AUTO and FUNC keys are locked without a valid login (customer).
0 = OFF1 = ON
0 = OFF
Locking operating keys The operating keys of the control panel can be locked via the 3-1-2-2 parameter to
prevent unauthorised operation or unauthorised acknowledgement of alerts.
Page 42
8 Operation
42 of 68
KSBDeltaSolo / KSBDeltaEco
8.1.3.4 Menu: Information
All direct information about the frequency inverter is provided in the Information section. Important details regarding the firmware version are listed here.
8.1.4 Service interface and LED traffic light function
Service interface The service interface allows a PC/notebook to be connected via a special cable (USB –
optical). The following action can be taken:
Configuring and parameterising the frequency inverter with the service softwareSoftware updateSaving and documenting set parameters
LED traffic light function The LED traffic light function provides information about the current operating
status of the frequency inverter.
Table18: LED description
LED Description
Red
One or more than one alert is active
Amber
One or more than one warning is active
Green
Steady light: Trouble-free operation
Page 43
9 Servicing/Maintenance
43 of 68
KSBDeltaSolo / KSBDeltaEco
9 Servicing/Maintenance
9.1 General information/Safety regulations
The operator ensures that maintenance, inspection and installation is performed by authorised, qualified specialist personnel who are thoroughly familiar with the manual.
DANGER
Unintentional start-up of pressure booster system
Danger to life!
The pressure booster system must be de-energised before repair or
maintenance work is carried out.
DANGER
Voltage at the pressure booster system
Danger to life!
Prior to opening the device, wait at least 10minutes for any residual voltage to
dissipate.
WARNING
Improper lifting/moving of heavy assemblies or components
Personal injury and damage to property!
Use suitable transport devices, lifting equipment and lifting tackle to move
heavy assemblies or components.
WARNING
Unintentional start-up of pressure booster system
Risk of injury by moving parts!
Make sure the pressure booster system has been de-energised before
commencing work on the pressure booster system.
Make sure that the pressure booster system cannot be started up
unintentionally.
WARNING
Unqualified personnel performing work on the pressure booster system
Risk of personal injury!
Always have repair and maintenance work performed by specially trained,
qualified personnel.
CAUTION
Incorrectly serviced pressure booster system
Function of pressure booster system not guaranteed!
Regularly service the pressure booster system.Prepare a maintenance schedule for the pressure booster system, with special
emphasis on lubricants, shaft seals and pump couplings.
Always observe the safety instructions and information. Observe the operating manual of the pump when performing work on the pumps. In case of damage you can always contact our service staff.
Page 44
9 Servicing/Maintenance
44 of 68
KSBDeltaSolo / KSBDeltaEco
A regular maintenance schedule will help avoid expensive repairs and contribute to trouble-free, reliable operation of the pressure booster system with a minimum of maintenance expenditure and work.
Never use force when dismantling and re-assembling the pressure booster system.
9.1.1 Inspection contract
For all inspection and servicing work to be carried out at regular intervals we recommend taking out the inspection contract offered by KSB. Contact your Service Partner for details.
Checklist for commissioning/start-up, checklist for inspection
9.2 Servicing/Inspection
9.2.1 Supervision of operation
CAUTION
Increased wear due to dry running
Damage to the pump set!
Never operate the pump set without liquid fill.Never close the shut-off element in the suction line and/or supply line during
pump operation.
CAUTION
Impermissibly high temperature of fluid handled
Damage to the pump!
Prolonged operation against a closed shut-off element is not permitted
(heating up of the fluid).
Observe the temperature limits in the data sheet and in the section on
operating limits.
While the system is in operation, observe and check the following:
Check the test run (if activated).Compare the start and stop pressures of the pumps with the data on the name
plate (using the pressure gauge).
Compare the pre-charge pressure of the accumulator with the recommended
data. (ðSection9.2.3,Page45) Close the shut-off elements under the accumulator and drain the accumulator via the drain valve. Remove the protective cap of the accumulator valve and check the pre-charge pressure with the aid of a tyre pressure gauge. Add nitrogen as necessary.
WARNING
Wrong gas
Danger of poisoning!
Use only nitrogen to charge the accumulator.
Check the rolling element bearings for running noises.
Vibrations, noise and an increase in current input occurring during unchanged operating conditions indicate wear.
Monitor the correct functioning of any auxiliary connections.
Page 45
9 Servicing/Maintenance
45 of 68
KSBDeltaSolo / KSBDeltaEco
9.2.2 Checklist for inspection
In the event that you decide to conduct your own inspections, proceed according to the following checklist at least once a year:
1. Check the pump and drive for smooth running and the mechanical seal for integrity.
2. Check the shut-off, drain and check valves for proper functioning and tightness.
3. Clean the strainer in the pressure reducer (if applicable).
4. Check expansion joints for wear (if applicable).
5. Verify the pre-charge pressure level and check the accumulator for integrity if required. (ðSection9.2.3,Page45)
6. Check the automatic switching functionality.
7. Check the start and stop points of the pressure booster system.
8. Check the water inflow, inlet pressure, lack-of-water monitoring, flow monitoring and pressure reducer.
9. Check the inlet tank and the float valve (if applicable). Check the overflow for integrity and cleanliness.
9.2.3 Setting the pre-charge pressure
WARNING
Wrong gas
Danger of poisoning!
Use only nitrogen to charge the accumulator.
The pre-charge pressure in the accumulator should be set to a value below the set start-up pressure. The setting can be effected via a valve located under the cover at the top of the accumulator.
Example: Pre-charge pressure 10% lower than start-up pressure
Pre-charge pressure of accumulator p=0.9xp
start
p
start
= start-up pressure of pressure booster system
Recommendation
The stated values are average values. Tests on accumulators have shown that the best storage volumes are achieved with the following factors: pressures >3bar: factor0.9 and pressures <3bar: factor0.8
Example:
p
start
= 5 bar: pre-charge pressure 5x0.9=4.5bar
p
start
=2bar: pre-charge pressure 2x0.8=1.6bar
CAUTION
Pre-charge pressure too high
Damage to accumulator!
Observe data provided by accumulator manufacturer (see name plate or
operating manual of accumulator).
Page 46
9 Servicing/Maintenance
46 of 68
KSBDeltaSolo / KSBDeltaEco
9.2.4 Replacing the non-return valve
DANGER
Voltage at the pressure booster system
Danger to life!
Prior to opening the device, wait at least 10minutes for any residual voltage to
dissipate.
1. De-energise the pump set and secure it against unintentional start-up. Comply with the local regulations.
2. Close the shut-off valve of the pump.
3. Place a suitable container under the drain connection.
4. Open the drain connections. To do so, observe the pump's operating manual.
Fig.30: Removing the screw
5. Remove the screw.
Fig.31: Screwing the valve's body parts into each other
6. Use a suitable tool to screw the body parts of the non-return valve into each other to shorten the length of the body.
Fig.32: Removing the body
7. Remove the body of the non-return valve.
Page 47
9 Servicing/Maintenance
47 of 68
KSBDeltaSolo / KSBDeltaEco
8. Remove the insert check valve including O-rings.
9. Remove excessive contamination or deposits with a clean cloth.
10. Re-insert the insert check valve into the body. Apply a sealant to new O-rings. See table below.
Fig.33: Mounting the body
11. Mount the body of the non-return valve.
Fig.34: Loosening the screwed connection of the body parts
12. Use a suitable tool to loosen the screwed connection of the body parts of the non-return valve to extend the body length.
Fig.35: Verifying the alignment
13. Verify the correct alignment.
Fig.36: Fitting the screw
Page 48
9 Servicing/Maintenance
48 of 68
KSBDeltaSolo / KSBDeltaEco
14. Fit and tighten the screw.
15. Close the drain plugs of the pump. Properly dispose of the fluid collected.
16. Slowly open the shut-off valve and check for any leakage.
Table19: Spare parts for servicing non-return valves, per pump
Material number
Description Non-return
valve
O-rings Sealant for O-
rings (not water­soluble)
71630405 ER non-return
valve DN32
Watts industries IN 032 DN 32
1xEriks 12711456
Molykote® G-5511
2)
2xEriks 12711457
71630410 ER non-return
valve DN50
Watts industries IN 050 DN 50
1xEriks 12192264
2xEriks 12711459
9.2.5 Mounting the manifold in a mirrored position
DANGER
Voltage at the pressure booster system
Danger to life!
Prior to opening the device, wait at least 10minutes for any residual voltage to
dissipate.
1. De-energise the pump set and secure it against unintentional start-up. Comply with the local regulations.
2. Close the shut-off valves in the discharge line and suction line of the pressure booster system.
3. Place a suitable container under the drain connections.
4. Open the drain connections. To do so, observe the pump's operating manual.
Fig.37: Removing the bolts
5. Remove the bolts connecting the two oval flanges to the pumps.
2) Sealant for taps
Page 49
9 Servicing/Maintenance
49 of 68
KSBDeltaSolo / KSBDeltaEco
Fig.38: Removing the manifold
6. Remove the complete manifold including valves
A
A
Fig.39: Loosening the EF locknuts
A EF locknut
7. Loosen the EF locknuts at the shut-off valves by half a turn, exposing the O-ring.
B
B
A
Fig.40: Turning the pressure measuring set
A Pressure measuring set B Lever of the shut-off valve
Page 50
9 Servicing/Maintenance
50 of 68
KSBDeltaSolo / KSBDeltaEco
8. Close the lever of the shut-off valve about half way to enable the 180° turn required in the next step.
9. Turn the pressure measuring set by 90°.
NOTE
For some variants, the pressure gauge or a pressure sensor need to be removed to be able to turn the pressure measuring set.
A
A
Fig.41: Turning the shut-off valves
A Shut-off valve
10. Turn the shut-off valves by 180°. Now, turn the complete manifold including valves by 180°.
A
Fig.42: Turning the pressure measuring set
A Pressure measuring set
Page 51
9 Servicing/Maintenance
51 of 68
KSBDeltaSolo / KSBDeltaEco
11. Turn the pressure measuring set by a last 90°.
12. If the pressure gauge and/or pressure sensors have been removed, connect them again.
ð The manifold is now fitted in a mirrored position.
Page 52
10 Trouble-shooting
52 of 68
KSBDeltaSolo / KSBDeltaEco
10 Trouble-shooting
DANGER
Unintentional start-up
Risk of fatal injury due to electric shock!
Disconnect the frequency inverter from the mains before carrying out any
maintenance and installation work.
Prevent the frequency inverter from being re-started unintentionally when
carrying out any maintenance and installation work.
DANGER
Contact with live components
Risk of fatal injury due to electric shock!
Any work on the product shall only be performed when it has been
disconnected from the power supply (de-energised).
Never remove the centre housing part from the heat sink.Mind the capacitor discharge time.
After switching off the frequency inverter, wait 10minutes until dangerous voltages have discharged.
NOTE
Depending on the combination of settings, the frequency inverter could conceivably restart automatically after acknowledgement/reset or when the cause of the malfunction or fault has been eliminated.
The operator ensures that trouble-shooting is performed by authorised, qualified specialist personnel who are thoroughly familiar with the operating manual.
Reset the frequency inverter to the default factory settings before engaging in any fault rectification measures.
10.1 Faults/malfunctions: Trouble-shooting
WARNING
Improper work to remedy faults
Risk of injury!
For any work performed to remedy faults, observe the relevant information
given in this operating manual and/or in the product literature provided by the accessories manufacturer.
If problems occur that are not described in the following table, consultation with the KSB customer service is required.
A Mains fuse rating too small for the nominal mains current.
B Motor does not start. C Motor running unevenly.
D Max. speed not reached.
E Motor running at maximum speed only.
F Motor running at minimum speed only. G No/faulty 24V supply. H Wrong direction of rotation of the motor.
I Fault message/protective tripping.
Page 53
10 Trouble-shooting
53 of 68
KSBDeltaSolo / KSBDeltaEco
Table20: Trouble-shooting
A B C D E F G H I Possible cause Remedy
- - - - - - - No voltage applied Check the mains voltage. Check the mains fuses.
- - - - - - - - No enable Check enable via DIGIN-EN and system start.
✘ - - - - - - - - Mains fuse rating too low for
frequency inverter input current
Check configuration/selection of mains fuse.
- - - - - - - - No setpoint signal or setpoint set too low / drive overloaded and in i²t control mode
Check setpoint signal and operating point.
- - - - - - - - Process-related persistent control deviation (actual value smaller than setpoint) / no actual value (e.g. due to broken wire)
Check setpoint/actual value signal; check operating point; check controller setting.
- --- - - - - Permissible voltage range undershot/exceeded
Check mains voltage; supply frequency inverter with required voltage.
- - - - - - - - Wrong direction of rotation setting.
Change the direction of rotation.
- - ✘ ✘ - - - - Frequency inverter overloaded Reduce the power input by lowering the speed;
check the motor/pump for blockages.
- - - - - - - Short circuit in control cable/ pump blocked
Check/replace control cable connections. Remove the pump blockage manually.
- - ✘ ✘ - - - - Temperature of power electronics or motor winding too high
Reduce the ambient temperature by improving
ventilation.
Improve cooling by cleaning the cooling fins.Ensure that the intake opening for the fans is
not blocked.
Ensure that the fans are working properly.Reduce the power input by changing the
operating point (system-specific).
Check the permissible load and, if necessary, use
external cooling.
- - - - - - - 24 V voltage supply overloaded
Disconnect frequency inverter from the power supply and eliminate the cause of the overload.
- - - - - - - - Dry running of pump Check the hydraulic system and rectify the fault on
the frequency inverter.
- - - - - - Sensor signal error (e.g. broken wire)
Check sensor and sensor cable.
- ✘ ✘ - - - - - Phase failure (drive) Check motor connection and motor winding.
10.2 Alerts
Table21: Alerts
Message code
Message Description Behaviour
E1 Thermal motor protection PTC has tripped Self-acknowledging
(configurable)
E2 Overvoltage Impermissible overvoltage (mains) Partially self-
acknowledging
E3 Undervoltage Impermissible undervoltage (mains) Partially self-
acknowledging
E4 Phase failure (motor) Phase failure (motor) Non-self-
acknowledging
Page 54
10 Trouble-shooting
54 of 68
KSBDeltaSolo / KSBDeltaEco
Message code
Message Description Behaviour
E5 Short circuit Motor short-circuited (defective motor winding) Partially self-
acknowledging
E6 Hardware error Hardware defective Non-self-
acknowledging
E7 Heat sink temperature high Power electronics overtemperature Non-self-
acknowledging
E8 PCB temperature high Control electronics overtemperature Non-self-
acknowledging
E9 Overcurrent Impermissible overcurrent Partially self-
acknowledging
E10 Braking resistor Internal overcurrent (for example, if the ramp is
too steep)
Non-self­acknowledging
E11 Dynamic overload protection Impermissible overcurrent Partially self-
acknowledging
E12 Firmware update required Firmware update required Non-self-
acknowledging
E13 Dry running Dry running of pump Non-self-
acknowledging
E14 Dry running (external) Dry running of pump Self-acknowledging
(configurable)
E15 Hydraulic blockage Pumping against closed piping Non-self-
acknowledging
E16 No master control Failure of actual value sensor/ Broken wire/ Local/
No redundancy
Self-acknowledging
E18 No matching motor data
available
The extended KSB SuPremE motor data could not be determined.
Self-acknowledging
E19 No motor data available The motor data is not set Self-acknowledging E20 AMA fault The extended motor data could not be
determined.
Self-acknowledging
E76 24V overload Internal 24V power supply unit overloaded Self-acknowledging E77 PumpMeter communication Incorrect PumpMeter communication Self-acknowledging E83 Overflow - Non-self-
acknowledging E84 Setpoint/control value failure - Self-acknowledging E98 HMI hardware test not
passed.
Control panel is defective. Non-self-
acknowledging E99 IO hardware test not passed. Control electronics or M12 module defective. Non-self-
acknowledging
Table22: Alerts
Alert Possible causes Remedy
3)4)
Short circuit Motor short-circuited (defective motor
winding)
Check motor winding, perform dielectric test. Check motor for blockage.
Power supply connected incorrectly Check the cabling; connect the mains power
supply to L1, L2, L3, PE. Parallel operation of motors Impermissible operating range Motor terminal board wired incorrectly (delta/
star)
Wire motor terminal board correctly.
Motor power cable short circuit Check motor power cable.
3) Disconnect the frequency inverter from the power supply to rectify faults on current-carrying components. Observe the safety information!
4) Restore the frequency inverter’s default settings.
Page 55
10 Trouble-shooting
55 of 68
KSBDeltaSolo / KSBDeltaEco
Alert Possible causes Remedy
3)4)
Short circuit Sensor cable shielding connected incorrectly Connect sensor cable shielding to PE on one
end only.
24 V DC cabling short circuit Check cabling.
Thermal motor protection
PTC thermistor connected incorrectly Check PTC sensor connection. Incorrect motor data set Match motor data settings to motor used. Wrong direction of rotation of the pump Adjust the direction of rotation of the motor
via the phase sequence. Hydraulic overload Reduce the hydraulic load. Pump blocked mechanically/runs sluggishly Check pump. Motor terminal board wired incorrectly (delta/
star)
Wire motor terminal board correctly.
Frequency inverter power < motor power and/ or output current < motor current
Wrong device ordered, mount larger frequency
inverter.
Carrier frequency of frequency inverter set too high
Set carrier frequency to permissible range.
Fluctuating DC link voltage when pump is not running
Check mains voltage quality.
Fluctuating DC link voltage when pump operates at nominal values
Check mains voltage quality.
Incorrect motor current measurement Measure current using suitable snap-on
ammeter and compare with the information
displayed on the control panel.
NOTE!Approx. 10% tolerance is permissible. Pump runs in reverse when motor is not
supplied with current.
Check swing check valve.
Motor voltage output is too low at nominal load, <380V at nominal load
Check line input voltage; enter motor current
at 380V mains voltage; fit larger-sized motor.
Heat sink temperature high/ PCB temperature high
Ambient temperature of frequency inverter >50°C
Impermissible operating range; mind power
derating. Dirt in external fans Clean fans. Heat sink/cooling fins dirty Clean heat sink/cooling fins. Carrier frequency of frequency inverter set
too high
Set carrier frequency to permissible range.
Frequency inverter power < motor power and/ or output current < motor current
Wrong device ordered, mount larger frequency
inverter.
Frequency inverter mounted incorrectly External fans must point upwards; on the wall-
mounted model, the back of the heat sink must
be closed.
Undervoltage Line input voltage too low Check the mains voltage.
Fluctuating DC link voltage when pump is not running
Check mains voltage quality.
Mains fuse has tripped Fit new mains fuse. Brief interruption of mains voltage Check the mains voltage.
Overvoltage Line input voltage too high Check the mains voltage.
Fluctuating DC link voltage when pump is not running
Check mains voltage quality.
Ramp times too short Select longer ramp times. Pump runs in reverse when motor is not
supplied with current.
Check swing check valve.
Overcurrent/ dynamic overload protection
Mains power supply connected incorrectly Connect mains power supply to L1, L2, L3, PE. Motor terminal board wired incorrectly (delta/
star)
Wire motor terminal board correctly.
Page 56
10 Trouble-shooting
56 of 68
KSBDeltaSolo / KSBDeltaEco
Alert Possible causes Remedy
3)4)
Overcurrent/ dynamic overload protection
Incorrect motor data set (3-3-2) Match motor data settings to motor used. Parallel operation of motors This mode of operation is not permissible. Sensor cable shielding connected incorrectly Connect sensor cable shielding to PE on one
end only. Frequency inverter power < motor power and/
or output current < motor current
Wrong device ordered, mount larger frequency
inverter.
Ramp times too short Select longer ramp times. Wrong direction of rotation of the pump Adjust the direction of rotation of the motor
via the phase sequence. Pump blocked mechanically/runs sluggishly Check pump. Carrier frequency of frequency inverter set
too high
Set carrier frequency to permissible range.
Incorrect motor current measurement Measure current using suitable snap-on
ammeter and compare with the information
displayed on the control panel.
Please note: Approx. 10% tolerance is
permissible. Pump runs in reverse when motor is not
supplied with current.
Check swing check valve.
No master control KSB device bus wired incorrectly (interruption,
short circuit)
Re-wire properly.
Sensor connected incorrectly (actual value failure)
Connect sensor correctly.
No main pump recognised in system Define role in multiple pump system.
Braking resistor Stop ramp time too short Increase ramp time.
Pump runs in reverse when motor is not supplied with current.
Check swing check valve.
Generator operation of pump Impermissible operating range
Dry running/ dry running (external)
Dry running of pump Check piping.
Check the pump valves.
Hydraulic blockage Piping clogged Check piping.
Check the pump valves.
10.3 Warnings
Table23: Warnings
Message code
Message Description Behaviour
E30 External message External message present. Self-acknowledging
(configurable)
E50 Dynamic overload
protection
Impermissible overcurrent Self-acknowledging
E51 Overvoltage Overvoltage Self-acknowledging E52 Undervoltage Undervoltage Self-acknowledging E53 Resonance range Resonance range Self-acknowledging E54 Broken wire Broken wire Self-acknowledging E55 Actual value failure Failure of actual value Self-acknowledging E56 Hydraulic blockage Pumping against closed piping Self-acknowledging E56 Hydraulic blockage Pumping against closed piping Self-acknowledging E57 Low flow Low flow Self-acknowledging E58 Hydraulic overload Hydraulic overload Self-acknowledging
Page 57
10 Trouble-shooting
57 of 68
KSBDeltaSolo / KSBDeltaEco
Message code
Message Description Behaviour
E59 Heat sink temperature
high
Power electronics overtemperature Self-acknowledging
E60 PCB temperature high Control electronics overtemperature Self-acknowledging E61 Current high Motor current high Self-acknowledging E62 Current low Motor current low Self-acknowledging E63 Speed monitoring Limit value violation, speed Self-acknowledging E64 Setpoint monitoring Limit value violation, setpoint Self-acknowledging E65 Actual value monitoring Limit value violation, actual value Self-acknowledging E66 Flow rate monitoring Limit value violation, flow rate Self-acknowledging E67 Suction pressure
monitoring
Limit value violation, suction pressure Self-acknowledging
E68 Discharge pressure
monitoring
Limit value violation, discharge pressure Self-acknowledging
E69 Differential pressure
monitoring
Limit value violation, differential pressure Self-acknowledging
E70 Temperature monitoring Limit value violation, temperature Self-acknowledging E71 Frequency high Frequency high Self-acknowledging E72 Frequency low Frequency low Self-acknowledging E73 Power high Power high Self-acknowledging E74 Power low Power low Self-acknowledging E75 Limited stop ramp Set stop ramp time exceeded Self-acknowledging E76 24V overload Internal 24V power supply unit overloaded Self-acknowledging E77 PumpMeter
communication
Incorrect PumpMeter communication Self-acknowledging
E78 Firmware update for field
bus required
Module incompatible with main module Self-acknowledging
E79 Firmware update for HMI
required
Module incompatible with main module Self-acknowledging
E83 Overflow - Non-self-acknowledging E84 Setpoint/control value
failure
- Self-acknowledging
E99 General settings loaded General settings loaded Self-acknowledging
Table24: Warnings
Warning Possible causes Remedy
Dynamic overload protection
Incorrect motor data set Match motor data to motor used. Wrong direction of rotation of the pump Adjust the direction of rotation of the motor via
the phase sequence Hydraulic overload Reduce the hydraulic load. Pump blocked mechanically/runs sluggishly Check pump. Motor terminal board wired incorrectly
(delta/star)
Wire motor terminal board correctly.
Frequency inverter power < motor power and/or output current < motor current
Wrong device ordered, mount larger frequency
inverter.
Frequency inverter carrier frequency set too high
Set carrier frequency to permissible range.
Ambient temperature of frequency inverter > 50 °C
Impermissible operating range; mind power
derating. Fluctuating DC link voltage when pump is
not running
Check mains voltage quality.
Page 58
10 Trouble-shooting
58 of 68
KSBDeltaSolo / KSBDeltaEco
Warning Possible causes Remedy
Dynamic overload protection
Incorrect motor current measurement Measure current using suitable snap-on ammeter
and compare with the information displayed on
the control panel.
NOTE!Approx. 10% tolerance is permissible. Pump runs in reverse when motor is not
supplied with current
Check swing check valve.
Motor voltage output is too low at nominal load, < 380V at nominal load
Check line input voltage; enter motor current at
380V mains voltage; fit larger-sized motor.
Broken wire Cable integrity monitoring Replace defective sensor with new one. Low flow/overload The driven pump is operated under low
flow/overload conditions.
Impermissible operating range; operate the
pump within the permissible range.
24V overload 24 V DC voltage supply overload Reduce current input to 24 V DC; compare the
number of electrical connections with the
maximum permissible current load of the 24 V DC
supply . Short circuit of consumers connected to
24VDC voltage supply
Disconnect defective 24VDC consumers.
Control terminal wiring errors (DigIn, AnIn) Re-wire properly.
Dynamic overload protection Incorrect motor data set Match motor data to motor used.
Wrong direction of rotation of the pump
Adjust the direction of rotation of
the motor via the phase sequence Hydraulic overload Reduce the hydraulic load. Pump blocked mechanically/runs
sluggishly
Check pump.
Motor terminal board wired incorrectly (delta/star)
Wire motor terminal board
correctly. Frequency inverter power < motor
power and/or output current < motor current
Wrong device ordered, mount
larger frequency inverter.
Frequency inverter carrier frequency set too high
Set carrier frequency to permissible
range. Ambient temperature of frequency
inverter > 50 °C
Impermissible operating range;
mind power derating. Fluctuating DC link voltage when
pump is not running
Check mains voltage quality.
Incorrect motor current measurement
Measure current using suitable
snap-on ammeter and compare
with the information displayed on
the control panel.
NOTE!Approx. 10% tolerance is
permissible. Pump runs in reverse when motor
is not supplied with current
Check swing check valve.
Motor voltage output is too low at nominal load, < 380V at nominal load
Check line input voltage; enter
motor current at 380V mains
voltage; fit larger-sized motor.
Page 59
10 Trouble-shooting
59 of 68
KSBDeltaSolo / KSBDeltaEco
10.4 Information messages
Table25: Information messages
Message code
Message Description Behaviour
E100 Pump maintenance/
service interval
Service interval set for pump expired. Self-acknowledging
E101 Drive disabled The motor is disabled while AMA is being
carried out.
If the Overcurrent alert is output that
causes the drive to be stopped, the drive remains disabled as long as this event is active.
In the event of a stop via the DI-EN digital
input, the motor is not stopped by the stop ramp, but coasts to a standstill. The amount of time this process takes depends on the mass moment of inertia of the system. The drive remains disabled during coasting.
Self-acknowledging
E102 Pipe flushing mode active Performing the pipe flushing function Self-acknowledging E103 Pipe filling mode active Performing the pipe filling function Self-acknowledging E104 Maintenance interval,
motor bearings
Maintenance interval set for motor expired. Self-acknowledging
E105 Factory-set defaults
loaded
Factory-set defaults are being loaded. Self-acknowledging
E106 User settings 1 loaded User settings 1 were loaded. Non-self-acknowledging E107 User settings 2 loaded User settings 2 were loaded. Non-self-acknowledging
Page 60
11 Related Documents
60 of 68
KSBDeltaSolo / KSBDeltaEco
11 Related Documents
11.1 General assembly drawings/exploded views with list of components
11.1.1 KSB Delta Solo SVP
595
655
742.01
742.02
591
79-2
743.90
691
79-2
Fig.43: KSB Delta Solo SVP
Table26: List of components
Part No. Description Part No. Description
79-2 Measuring transducer 691 Pressure gauge 591 Accumulator 742.01/.02 Check valve 595 Anti-vibration pad 743.90 Ball/plug valve 655 Pump
The individual parts of the pump set are shown in the product literature of the pump set.
Page 61
11 Related Documents
61 of 68
KSBDeltaSolo / KSBDeltaEco
11.1.2 KSB Delta Eco SVP
591
655
595
743.90
743.90
79-2
691
742.02
742.01
743
412
Fig.44: KSB Delta Eco SVP
Table27: List of components
Part No. Description Part No. Description
79-2 Measuring transducer 655 Pump 412 O-ring 691 Pressure gauge 591 Accumulator 742.01/.02 Check valve 595 Anti-vibration pad 743/.90 Ball/plug valve
The individual parts of the pump set are shown in the product literature of the pump set.
Page 62
12 EU Declaration of Conformity
62 of 68
KSBDeltaSolo / KSBDeltaEco
12 EU Declaration of Conformity
Manufacturer: KSB B.V.
Kalkovenweg 13
2401 LJ Alphen aan den Rijn (The Netherlands)
The manufacturer herewith declares that the product:
KSB Delta Solo SVP, Delta Eco SVP
Serial number: 06/2018 0000000-0001 - 52/2020 9999999-9999
is in conformity with the provisions of the following Directives as amended from time to time:
– Pump set: EC Machinery Directive 2006/42/EC – Pump set: Electromagnetic Compatibility Directive 2014/30/EU
The manufacturer also declares that
the following harmonised international standards have been applied:
– ISO 12100 – EN 809 – EN 60204-1 – EN 806-2
Person authorised to compile the technical file:
Menno Schaap Manager Product Development KSB B.V. (Subsidiary D.P. Industries B.V.) Kalkovenweg 13 2401 LJ Alphen aan den Rijn (The Netherlands)
The EU Declaration of Conformity was issued in/on:
Alphen aan den Rijn, 1 June 2018
Menno Schaap
Manager Product Development
KSB B.V.
Kalkovenweg 13
2401 LJ Alphen aan den Rijn
Page 63
13 Certificate of Decontamination
63 of 68
KSBDeltaSolo / KSBDeltaEco
13 Certificate of Decontamination
Type: ................................................................................................................................
Order number/
Order item number5): ................................................................................................................................
Delivery date: ................................................................................................................................
Field of application: ................................................................................................................................
Fluid handled5): ................................................................................................................................
Please tick where applicable5):
Radioactive Explosive Corrosive Toxic
Harmful Bio-hazardous Highly flammable Safe
Reason for return5): ................................................................................................................................
Comments: ................................................................................................................................
................................................................................................................................
The product/accessories have been carefully drained, cleaned and decontaminated inside and outside prior to dispatch/ placing at your disposal.
We herewith declare that this product is free from hazardous chemicals, biological and radioactive substances.
For mag-drive pumps, the inner rotor unit (impeller, casing cover, bearing ring carrier, plain bearing, inner rotor) has been removed from the pump and cleaned. In cases of containment shroud leakage, the outer rotor, bearing bracket lantern, leakage barrier and bearing bracket or adapter have also been cleaned.
For canned motor pumps, the rotor and plain bearing have been removed from the pump for cleaning. In cases of leakage at the stator can, the stator space has been examined for fluid leakage; if fluid handled has penetrated the stator space, it has been removed.
No special safety precautions are required for further handling. The following safety precautions are required for flushing fluids, fluid residues and disposal:
...............................................................................................................................................................
...............................................................................................................................................................
We confirm that the above data and information are correct and complete and that dispatch is effected in accordance with the relevant legal provisions.
.................................................................... ....................................................... .......................................................
Place, date and signature Address Company stamp
5) Required fields
Page 64
14 Commissioning Report
64 of 68
KSBDeltaSolo / KSBDeltaEco
14 Commissioning Report
The KSB pressure booster system specified below was today commissioned by the undersigned, authorised KSB customer service engineer who created this report.
Pressure booster system details
Type series ........................................................................................................................................
Size ........................................................................................................................................
Serial number ........................................................................................................................................
Order No. ........................................................................................................................................
Purchaser/place of installation
Purchaser Place of installation
Name .................................................... ..........................................................................
Address .................................................... ..........................................................................
.................................................... ..........................................................................
Operating data For further details please refer to the circuit diagram. Start-up pressure p
start
bar ....................................................
Inlet pressure monitoring p
inl
- x
(setting of inlet pressure switch)
....................................................
Stop pressure p
stop
bar ....................................................
Inlet pressure p
inl
bar ....................................................
Pre-charge pressure of accumulator
p
pre-charge
bar
....................................................
The system operator/operator's representative herewith confirms to have received instructions on how to operate and service the pressure booster system. The relevant circuit diagrams and operating instructions have been handed over.
Non-conformities found during commissioning Deadline for remedial action
Non-conformity
1 ............................................................................................
..........................................................................
............................................................................................................. ..........................................................................
............................................................................................................. ..........................................................................
............................................................................................................. ..........................................................................
Name of KSB representative Name of purchaser or representative
............................................................................................................. ..........................................................................
Place Date
............................................................................................................. ..........................................................................
Page 65
Index
65 of 68
KSBDeltaSolo / KSBDeltaEco
Index
A
Access levels40 Alerts53 Analog input22, 25 Arrow keys37 Automation16
C
Certificate of decontamination63 Commissioning32 Connection to mains power supply26
Control cable
Connect24 Earthing31
Cover
C-shaped24 Protective cover24
D
Design15 Designation15 Disposal14 Drive16 Dry running protection22, 32
E
Earthing
Connect31 EMC Directive10 Escape key37 Event of damage6
F
Faults
Causes and remedies53
I
Installation16 Intended use8 Interference emissions10 IT mains28
J
Jumper28
K
Key to safety symbols/markings7
L
LED display42
M
Main screen35 Mains and motor connection
Size A26 Size B27 Size C28
Motor connection26 Motor connection cable
Connect24
O
OK key37 Operating limits8 Other applicable documents6
P
Partly completed machinery6 Power/connection cables
Control cable24, 31 Routing cables26
PTC
Size A26 Size B27 Size C28
PTC thermistor26
R
Return to supplier14
S
Safety8 Safety awareness9 Scope of supply17
Sensor
Size A
26 Size B27 Size C28
Service interface42 Shielding31 Standard control panel35
T
Terminal strip22, 25 Thermal motor protection
Size A26, 27 Size C28
Traffic light42
W
Warnings7, 56
Graphical control panel42
Warranty claims6
Page 66
Page 67
Page 68
KSB B.V.
Kalkovenweg 13 2401 LJ Alphen aan den Rijn (Netherlands)
1983.821/01-EN
Loading...