KSB Cervomatic EDP.2 Operating Manual

Page 1
Automatic Control Unit
Cervomatic EDP.2
Installation/Operating Manual
Page 2
Legal information/Copyright
Installation/Operating Manual Cervomatic EDP.2
Original operating manual
Subject to technical modification without prior notice.
© KSB SE & Co. KGaA, Frankenthal 09/01/2018
Page 3
Contents
3 of 28
Cervomatic EDP.2
Contents
1 General.................................................................................................................................................... 4
1.1 Principles ...........................................................................................................................................................4
1.2 Target group.....................................................................................................................................................4
1.3 Other applicable documents............................................................................................................................4
1.4 Symbols .............................................................................................................................................................4
2 Safety...................................................................................................................................................... 5
2.1 Key to safety symbols/markings.......................................................................................................................5
2.2 General..............................................................................................................................................................5
2.3 Intended use .....................................................................................................................................................5
2.4 Personnel qualification and personnel training.............................................................................................6
2.5 Consequences and risks caused by non-compliance with this manual .........................................................6
2.6 Safety awareness ..............................................................................................................................................6
3 Transport/Temporary Storage/Disposal............................................................................................... 7
3.1 Checking the condition upon delivery............................................................................................................7
3.2 Transport...........................................................................................................................................................7
3.3 Storage..............................................................................................................................................................7
3.4 Disposal .............................................................................................................................................................8
4 Description.............................................................................................................................................. 9
4.1 General description ..........................................................................................................................................9
4.2 Designation.......................................................................................................................................................9
4.3 Name plate........................................................................................................................................................9
4.4 Design details..................................................................................................................................................10
4.5 Configuration and function...........................................................................................................................10
4.6 Technical data.................................................................................................................................................10
4.7 Displays and indicator lamps .........................................................................................................................11
4.8 Fluids handled.................................................................................................................................................11
5 Installation at Site................................................................................................................................ 12
5.1 Safety regulations...........................................................................................................................................12
5.2 Checks to be carried out prior to installation...............................................................................................12
5.3 Connecting the automatic control unit ........................................................................................................12
5.4 Connecting the piping ...................................................................................................................................13
5.4.1 Connecting the piping (dry installation) ..........................................................................................13
5.4.2 Connecting the piping (wet installation) .........................................................................................13
5.5 Electrical connection ......................................................................................................................................14
6 Commissioning/Start-up/Shutdown................................................................................................... 16
6.1 Prerequisites for commissioning/start-up......................................................................................................16
6.2 Commissioning/Start-up.................................................................................................................................16
6.2.1 Commissioning ...................................................................................................................................16
6.2.2 Configuration..................................................................................................................................... 16
6.2.3 Pre-charging of accumulator.............................................................................................................18
6.3 Shutdown/storage/preservation ....................................................................................................................18
6.4 Returning to service .......................................................................................................................................18
7 Maintenance......................................................................................................................................... 19
8 Trouble-shooting.................................................................................................................................. 20
9 Related Documents.............................................................................................................................. 22
9.1 Wiring diagrams .............................................................................................................................................22
9.2 Additional electrical connections ..................................................................................................................23
10 EU Declaration of Conformity............................................................................................................. 24
Index ..................................................................................................................................................... 25
Page 4
1 General
4 of 28
Cervomatic EDP.2
1 General
1.1 Principles
This operating manual is supplied as an integral part of the type series and variants indicated on the front cover. The manual describes the proper and safe use of this equipment in all phases of operation.
The name plate indicates the type series, the main operating data and the serial number. The serial number uniquely describes the system and is used as identification in all further business processes.
In the event of damage, immediately contact your nearest KSB service centre to maintain the right to claim under warranty.
1.2 Target group
This operating manual is aimed at the target group of trained and qualified specialist technical personnel.
1.3 Other applicable documents
Table1: Overview of other applicable documents
Document Contents
Operating manual Description of the proper and safe use of the
pump in all phases of operation Wiring diagram Description of the electrical connections Supplementary operating
manual
1)
Description of the proper and safe use of
supplementary product components
For accessories and/or integrated machinery components, observe the relevant manufacturer's product literature.
1.4 Symbols
Table2: Symbols used in this manual
Symbol Description
Conditions which need to be fulfilled before proceeding with the
step-by-step instructions
Safety instructions Result of an action Cross-references
1.
2.
Step-by-step instructions
Note Recommendations and important information on how to handle the product
1) Optional
Page 5
2 Safety
5 of 28
Cervomatic EDP.2
2 Safety
!
DANGER
All the information contained in this section refers to hazardous situations.
2.1 Key to safety symbols/markings
Table3: Definition of safety symbols/markings
Symbol Description
!
DANGER
DANGER
This signal word indicates a high-risk hazard which, if not avoided, will result in death or serious injury.
!
WARNING
WARNING
This signal word indicates a medium-risk hazard which, if not avoided, could result in death or serious injury.
CAUTION
CAUTION
This signal word indicates a hazard which, if not avoided, could result in damage to the machine and its functions.
Explosion protection
This symbol identifies information about avoiding explosions in potentially explosive atmospheres in accordance with Directive 2014/34/EU (ATEX).
General hazard
In conjunction with one of the signal words this symbol indicates a hazard which will or could result in death or serious injury.
Electrical hazard
In conjunction with one of the signal words this symbol indicates a hazard involving electrical voltage and identifies information about protection against electrical voltage.
Machine damage In conjunction with the signal word CAUTION this symbol indicates a hazard for the machine and its functions.
2.2 General
This operating manual contains general installation, operating and maintenance instructions that must be observed to ensure safe operation of the system and prevent personal injury and damage to property.
The safety information in all sections of this manual must be complied with. The operating manual must be read and understood by the responsible specialist
personnel/operators prior to installation and commissioning. The contents of this operating manual must be available to the specialist personnel
at the site at all times. Instructions/information attached directly to the automatic control unit must be
observed at all times and kept in a perfectly legible condition. This applies to, for example:
Markings for connectionsName plate
The operator is responsible for ensuring compliance with all local regulations not taken into account in this operating manual.
2.3 Intended use
The values specified in the technical product literature for the mains voltage, mains frequency, ambient temperature, and motor current must not be exceeded. The automatic control unit must only be operated in accordance with the instructions provided in the operating manual and other applicable documents (ðSection1.3,Page4) .
Page 6
2 Safety
6 of 28
Cervomatic EDP.2
2.4 Personnel qualification and personnel training
All personnel involved must be fully qualified to install, operate, maintain and inspect the equipment this manual refers to. The responsibilities, competence and supervision of all personnel involved in transport, installation, operation, maintenance and inspection must be clearly defined by the operator.
Deficits in knowledge must be rectified by means of training and instruction provided by sufficiently trained specialist personnel. If required, the operator can commission the manufacturer/supplier to train the personnel.
Training on the automatic control unit must always be supervised by specialist technical personnel.
2.5 Consequences and risks caused by non-compliance with this manual
Non-compliance with this operating manual will lead to forfeiture of warranty
cover and of any and all rights to claims for damages.
Non-compliance can, for example, have the following consequences:
– Hazards to persons due to electrical, thermal, mechanical and chemical
effects and explosions
Failure of important product functionsFailure of prescribed maintenance and servicing practicesHazard to the environment due to leakage of hazardous substances
2.6 Safety awareness
In addition to the safety information contained in this manual and the intended use, the following safety regulations shall be complied with:
Accident prevention, health and safety regulationsExplosion protection regulationsSafety regulations for handling hazardous substancesApplicable standards, directives and laws
Page 7
3 Transport/Temporary Storage/Disposal
7 of 28
Cervomatic EDP.2
3 Transport/Temporary Storage/Disposal
3.1 Checking the condition upon delivery
1. On transfer of goods, check each packaging unit for damage.
2. In the event of in-transit damage, assess the exact damage, document it and
notify KSB or the supplying dealer (as applicable) and the insurer about the damage in writing immediately.
3.2 Transport
The automatic control unit must be shut down for transport.
Table4: Ambient conditions for transport
Ambient condition Value
Relative humidity Max. 80% (no condensation) Ambient temperature -10°C to + 70°C
CAUTION
Improper transport
Damage to the automatic control unit!
The automatic control unit must always be transported properly and in its
original packaging.
For transport, observe the transport instructions on the original packaging.Do not throw the automatic control unit.
1. Unpack the automatic control unit upon receipt and check for in-transit damage.
2. Report any in-transit damage to the manufacturer immediately.
3. Dispose of packaging material in accordance with local regulations.
3.3 Storage
If the ambient conditions for storage are met, the automatic control unit will give reliable service even after a prolonged period of storage.
CAUTION
Damage during storage by humidity, dirt or vermin
Corrosion/contamination of automatic control unit!
For outdoor storage, cover the (packed or unpacked) automatic control unit
and accessories with waterproof material.
Table5: Ambient conditions for storage
Ambient condition Value
Relative humidity Max. 80% (no condensation) Ambient temperature -10°C to + 70°C
Store the automatic control unit under dry and vibration-free conditions, if
possible in its original packaging.
Store the automatic control unit in a dry room where the level of atmospheric
humidity is as constant as possible.
Prevent excessive fluctuations in atmospheric humidity (see table on ambient
conditions for storage).
If properly stored indoors, the equipment is protected for a maximum of 12months.
Page 8
3 Transport/Temporary Storage/Disposal
8 of 28
Cervomatic EDP.2
3.4 Disposal
NOTE
Due to certain components it contains, the device is classified as special waste and meets RoHs 2011/65/EC requirements.
Once decommissioned, the device must be properly disposed of in accordance with local regulations.
Page 9
4 Description
9 of 28
Cervomatic EDP.2
4 Description
4.1 General description
Automatic control unit for automatically starting and stopping a pump
4.2 Designation
Example: Cervomatic EDP.2
Table6: Designation key
Code Description
Cervomatic Type series E Single-phase AC D Three-phase current P Electrical protection 2 Product version
4.3 Name plate
Product: U471031 Serial nº: V1.11-05-1015
P max: 1000 kPa- 10 bar T50 Ip55
Freq. 50/60 Hz Imax 16(10) A V: 1~230 Pump: 1~230 V: 3~230 Pump: 3~230 V: 3~400 Pump: 3~400
1
2
3
4
5
6
7
8
Johann-Klein-Straße 9
Deutschland
67227 Frankenthal
KSB SE & Co. KGaA
Fig.1: Name plate (example)
1 Product code 2 Serial number, firmware version
V1.11, 05 not relevant, month of manufacture 10, year of
construction 15 3 Max. operating pressure 4 Max. ambient temperature 5 Enclosure 6 Frequency 7 Max. rated pump current
10A continuous load 16A brief load
8 Control voltage
Page 10
4 Description
10 of 28
Cervomatic EDP.2
4.4 Design details
Design
Automatic control unitPressure-dependent starting and either pressure-dependent or flow-dependent
stopping of pump
IP55 enclosure1~230/3~230/3~400 V AC, 50/60Hz1.5m power cable with shockproof plugIntegrated check valve
4.5 Configuration and function
Function
Pressure-dependent pump startPressure-dependent or flow-dependent stop of the pumpIntegrated dry running protectionIntegrated overload protection
Operating modes
On/off mode:
The pump set is started when the pressure in the pipe drops.The pump set is stopped when flow is interrupted.
Pressure control
The pump set is started when the pressure in the pipe drops.The pump set is stopped when the stop pressure in the pipe is exceeded.
Further functions
Integrated dry running protection of the pumpIntegrated overload protection
4.6 Technical data
Table7: Performance data
Characteristic Value
Maximum operating pressure 10bar Maximum rated pump current 10A Fluid temperature 0 - +40°C Ambient temperature 0 - +50°C Maximum flow rate 15m3/h Minimum flow rate 0.09m3/h Maximum start pressure
(pressure-dependent mode)
6.5 bar
Maximum stop pressure (pressure-dependent mode)
7 bar
Range of start pressure (on/off mode)
1 - 5bar
Page 11
4 Description
11 of 28
Cervomatic EDP.2
4.7 Displays and indicator lamps
MENU
LINE
FAILURE
AUTOPUMP
Cervomatic EDP.2
1
2 3
4
5
6
7 8
9
10
Fig.2: Indicator lamps
1 Display of various parameters during configuration.
In operation, the current pressure, configured start-up pressure and alerts are
displayed. 2 AUTO On/Off button: For selecting between manual and automatic mode. 3 LINE LED (green): Illuminates when the automatic control unit is connected to
the power supply. 4 FAILURE LED (red): Illuminates or flashes, depending on the type of fault. 5 AUTO LED (green): Illuminates in automatic mode; does not illuminate in
manual mode. 6 PUMP LED (yellow): Illuminates when the pump is operating. 7 PUMP start/stop button: Can only be pressed when automatic mode is
deactivated (AUTO LED does not illuminate). 8 MENU button: Opens and closes the configuration menu. 9 ENTER button: Saves configured values. A new field appears in the
configuration menu every time the button is pressed. Press MENU to exit the
configuration display. 10 and button: Adapts the configuration parameters up and down.
4.8 Fluids handled
Drinking waterService waterStormwaterFire-fighting waterCooling water
Page 12
5 Installation at Site
12 of 28
Cervomatic EDP.2
5 Installation at Site
5.1 Safety regulations
DANGER
Incorrect installation
Danger to life!
Install the automatic control unit in a flood-proof location.Never install the automatic control unit in potentially explosive atmospheres.The automatic control unit is not suitable for controlling pumps in potentially
explosive atmospheres.
5.2 Checks to be carried out prior to installation
The place of installation must meet the following requirements:
DryFrost-proofWell ventilatedLockable; unauthorised access must be prevented.Flood-proofInstallation in potentially explosive atmospheres is not permitted.
Ambient conditions
The ambient conditions specified in the following table must be observed:
Table8: Ambient conditions
Characteristic Value
Temperature during operation 0 °C to +50 °C Relative humidity Non-condensing Installation altitude Max. 1,000m above MSL
5.3 Connecting the automatic control unit
CAUTION
Automatic control unit lifted by the cable
Damage to the automatic control unit!
Do not lift the automatic control unit by the cable.
Remove the automatic control unit from its original packaging.Mount the automatic control unit in the vertical position directly on the pump.For wet-installed pumps, mount the automatic control unit to the rigid discharge
pipe in a flood-proof location.
Always install the automatic control unit with the discharge side pointing
upwards.
Screw the accompanying accumulator into the rear of the housing using suitable
sealing material (Teflon tape).
NOTE
The automatic control unit has an integrated accumulator. An external accumulator is not required. For frequent water extraction, it is recommended that the system be used in dedicated pressure-dependent mode and an external accumulator be installed.
Page 13
5 Installation at Site
13 of 28
Cervomatic EDP.2
5.4 Connecting the piping
Connect all piping without transmitting any stresses or strains.
5.4.1 Connecting the piping (dry installation)
The automatic control unit can be connected directly to the pump discharge
nozzle.
Always mount the automatic control unit in the vertical position.
CAUTION
Plastic threaded connections sealed with hemp
Stresses/strains and leaks in the plastic piping!
Use Teflon tape for sealing.
Automatic control unit connection between pump and consumer installation
Route connecting line between pump and automatic control unit.The diameter of the connecting line must at least equal the diameter of the
pump discharge line.
Observe the direction of fluid flow (see arrow on automatic control unit).
5.4.2 Connecting the piping (wet installation)
DANGER
Automatic control unit submerged
Danger to life!
Never submerge the automatic control unit.
Use suitable connecting elements to connect the pump's discharge line directly to
the pump discharge nozzle.
The diameter of the connecting line must at least equal the diameter of the
pump discharge line.
Observe the direction of fluid flow (see arrow on automatic control unit).Always mount the automatic control unit in the vertical position.The pump has an integrated vent valve.
For submersible borehole pumps, the automatic venting function facilitates priming under back pressure.
CAUTION
Plastic threaded connections sealed with hemp
Stresses/strains and leaks in the plastic piping!
Use Teflon tape for sealing.
Page 14
5 Installation at Site
14 of 28
Cervomatic EDP.2
5.5 Electrical connection
DANGER
Electrical connection work by unqualified personnel
Risk of fatal injury due to electric shock!
Always have any work on the connection to the power supply performed by a
trained electrician.
Remove the cover of the control electronics and make all connections as per
specifications on the terminal strip.
Check power supply.
Set the selector switch to define the voltage:
To A for 220 - 240V To B for 380 - 415V
Pumps with three-phase motors
NOTE
An upstream motor protection switch is recommended.
Power supply of automatic control unit: Connect L1, L2 and L3 via a 3-pole motor
protection switch (recommended) in de-energised state and connect the PE conductor to ensure correct earthing.
Motor power supply: Connect motor to U, V, W and PE (earth).
(ðSection9.1,Page22)
Pumps with AC motors
NOTE
An upstream motor protection switch is recommended.
Power supply of automatic control unit: Connect L1 and L2 via a motor
protection switch (recommended) in de-energised state and connect the PE conductor to ensure correct earthing.
Motor power supply: Connect motor to U, V and PE (earth).
(ðSection9.1,Page22)
NOTE
The earth conductor must always be longer than all other conductors. The earth conductor is the first to be connected during installation and the last to be removed when dismantling.
Connecting additional equipment
Alarm monitoring:
The automatic control unit has a volt-free contact with a maximum amperage of 1A for transmitting signals to various alarm devices (visual, acoustic, etc.). Connection procedure (ðSection9.2,Page23)
Level switch of inlet tank:
(e.g. via float switch in inlet tank) Input for stopping pump as soon as the external switch for detecting the minimum fill level trips. Connection procedure (ðSection9.2,Page23)
Page 15
5 Installation at Site
15 of 28
Cervomatic EDP.2
When closing the housing after establishing the electrical connection, ensure that the housing gasket is correctly seated. Ensure that the internally routed wires do not get trapped. Check the pump's direction of rotation during commissioning.
Page 16
6 Commissioning/Start-up/Shutdown
16 of 28
Cervomatic EDP.2
6 Commissioning/Start-up/Shutdown
6.1 Prerequisites for commissioning/start-up
Before commissioning/start-up of the system make sure that the following requirements are met:
The system has been properly connected to the electric power supply and is
equipped with all protection devices.
All relevant VDE standards and/or regulations applicable in the country of use are
complied with.
6.2 Commissioning/Start-up
6.2.1 Commissioning
NOTE
An upstream motor protection switch is recommended.
Energise the system. (ðSection9.1,Page22) Wait 5 seconds while the automatic control unit performs the autotest.
The configuration menu automatically opens when the automatic control unit is commissioned for the first time. A message on selecting the user interface language appears on the LCD display. Select the appropriate language and start the configuration routine.
(ðSection6.2.2,Page16)
As soon as the device is configured, press the AUTO On/Off button (green LED does not illuminate) to toggle to manual mode. Check the direction of rotation and correct pump suction by pressing the Start/Stop button. Press AUTO On/Off. The automatic control unit is ready for operation.
6.2.2 Configuration
NOTE
PON must be at least 0.2bar higher than the static system pressure. Example: Static system pressure of 2bar (20m water column), PON 2.2bar. PON must always be selected 0.5 bar lower than the pump nominal pressure.
NOTE
P
OFF
must always be selected 0.5 bar lower than the pump nominal pressure in
dedicated pressure-dependent mode.
NOTE
Press the buttons to change the values and ENTER to save them. Press MENU to exit the configuration procedure. Every time the ENTER button is pressed, the different displays are shown with the individual configuration steps.
Page 17
6 Commissioning/Start-up/Shutdown
17 of 28
Cervomatic EDP.2
Table9: Displays and configuration
Display Button
0
PLINE PON 03,0 bar 02,0 bar
Press the MENU button for 3 seconds to start the configuration.
MENU
MENU
3”
1
Cervomatic EDP.2 V 0.0
The message that is briefly displayed provides information on the software version.
ENTER
3”
2
LANGUAGE ENGLISH
Use the buttons to select the respective language: "SPRACHE DEUTSCH", "LANGUAGE ENGLISH", "LANGUE FRANÇAISE", "LINGUA ITALIANA" and "IDIOMA ESPAÑOL".
MENU
ENTER
3
INT. MAX. OFF
To protect the motor from overheating, specify the rated current from 0 to 10A using the buttons. The corresponding value is specified on the name plate of the motor. Press ENTER to confirm.
MENU
ENTER
4
LEVEL PROBE NO
If no external device is available to detect the minimum water level in the inlet tank, press ENTER to confirm. Otherwise, use the buttons to change/set from NO to YES.
MENU
ENTER
5
OPERATING MODE ON-OFF
OPERATING MODE PRESSOSTATIC
The operating mode can be selected with the buttons in this step. There are 2 options available:
On/Off mode:
Only the start-up pressure is configured here. When this pressure is reached, the pump is started with the delay configured in the next step and is stopped when it is no longer required.
Pressure-dependent mode:
The start-up pressure value and stop pressure value of the pump are configured here.
MENU
ENTER
6
P ON 05,0 bar
P ON 05,0 bar
Indicates the start-up pressure for the pump. The required pressure values can be set within the respective range using the buttons:
On/Off mode: 1 to 5 bar.Pressure-dependent mode: 0 to 6.5 bar.
MENU
ENTER
7
P OFF 06,0 bar
Indicates the stop pressure of the pump for dedicated pressure­dependent mode. The stop pressure must be between 1 and 7bar or be 1bar higher than the start-up pressure. The values can be changed by pressing the buttons.
MENU
ENTER
8
START DELAY 00 sec.
Indicates the delay when the pump is started after the start-up pressure was reached. Select the time required using the buttons.
MENU
ENTER
9
STOP DELAY 00 sec.
Indicates the stop delay of the pump after the stop pressure was reached. Select the time required using the buttons.
MENU
ENTER
10
PLINE PON 05,0 03,0
PLINE PON POFF 05,0 02,0 06,0
PLINE INT F 05,0 9,0 1
The automatic control unit is ready for operation. Press the AUTOMATIC On/Off button; the green LED illuminates. Shown on the LCD display:
On/Off mode: current pressure (PLINE) and start-up pressure (PON). ▪ Pressure-dependent mode: current pressure (P
LINE
), start-up pressure
(PON) and stop pressure (P
OFF
).
An expert view mode can be selected with the following parameters in automatic mode:
P
line
: current pressure.
INT: present current consumption.F: position of the flow sensor (0: no flow, 1: with flow)
MENU
On Off
Page 18
6 Commissioning/Start-up/Shutdown
18 of 28
Cervomatic EDP.2
6.2.3 Pre-charging of accumulator
The accumulator is pre-charged to a pressure of 3.5 bar at the factory. The accumulator should be pre-charged to a pressure of 0.2bar below the pump start-up pressure configured for dedicated pressure-dependent mode. If pressure is insufficient:
In manual mode, open a consumer installation and pre-charge the accumulator
via the valve using a bicycle pump and adapter.
Screw the valve cap back onto the valve. Press AUTO On/Off.
6.3 Shutdown/storage/preservation
Pull the pump plug.Remove the automatic control unit from the piping.Rinse off with clean water.Press in the check valve at the automatic control unit and shake water out of the
automatic control unit.
Leave the automatic control unit to dry and store in a dry, dark and frost-proof
room.
Special preservation measures are not required.
6.4 Returning to service
For returning the equipment to service, observe the items on commissioning/start-up.
Page 19
7 Maintenance
19 of 28
Cervomatic EDP.2
7 Maintenance
Check the proper functioning of the automatic control unit once per year.
Page 20
8 Trouble-shooting
20 of 28
Cervomatic EDP.2
8 Trouble-shooting
WARNING
Improper work to remedy faults
Risk of injury!
For any work performed to remedy faults, observe the relevant information
given in this operating manual and/or in the product literature provided by the accessories manufacturer.
If problems occur that are not described in the following table, consultation with the KSB customer service is required.
A1
Lack of water
A2
Fill level sensor
A3
Pressure sensor damaged
A4
Overcurrent
A5
Pump fuse
A6
Accumulator
None
No display
Table10: Trouble-shooting
Display Fault message Description
System behaviour Remedy
A1
A1 LACK OF WATER
Fault message: LED "FAILURE" FLASHES (FAULT). Fault message after acknowledgement: LED "FAILURE" ILLUMINATED (FAULT).
If the automatic control unit detects a lack of water at the automatic control unit inlet for more than 10 seconds, the pump is stopped and the ART logic is triggered.
The ART logic restarts the pump after 5minutes and 30seconds have lapsed to reinstate the function. If there is still a lack of water, the automatic control unit restarts the function every 30minutes over a period of 24hours. If the system still detects a lack of water after several repeat attempts, the pump is stopped permanently until the fault has been rectified.
No water is present at the inlet and the safety system was triggered as a result: Check the water supply inlet. The pump can be filled with water by pressing the START/STOP button (the AUTO On/Off LED should not illuminate; if this is the case, deactivate the LED by pressing the button).
A2
A2 LEVEL
Fault message after acknowledgement: LED "FAILURE" ILLUMINATED (FAULT).
If a float is installed in the inlet tank, the float switch immediately stops the pump as soon as a lack of water is detected. The system then outputs a lack-of-water message (A1).
The pump remains stopped until the fill level sensor detects water in the tank again.
Check tank.
A3
A3 TRANSDUCER
Fault message after acknowledgement: LED "FAILURE" ILLUMINATED (FAULT).
Damage to the pressure sensor is shown on the LCD display of the automatic control unit. Call in customer service.
Operation of the automatic control unit is interrupted.
Call in customer service.
Page 21
8 Trouble-shooting
21 of 28
Cervomatic EDP.2
Display Fault message Description
System behaviour Remedy
A4
A4 OVERCURRENT
Fault message: LED "FAILURE" FLASHES (FAULT). Fault message after acknowledgement: LED "FAILURE" ILLUMINATED (FAULT).
The pump has an overcurrent protective device that responds in accordance with the value defined in the configuration menu. These overcurrents generally pertain to pump malfunctions or power supply faults.
If this fault is detected, the system attempts to restart the pump four times. If the pump still does not start after the fourth attempt, it remains stopped until the fault has been rectified.
Check the status of the pump. Impeller is blocked. Verify the amperage entered in the configuration menu (it is recommended that you always set the amperage to 15 % above the rated pump current). Check the fuses for damage. The pump is put back into operation as soon as the problems have been resolved. The INSTALLATION menu is then displayed for entering the appropriate amperage.
(ðSection6.2.2,Page16)
A5
A5 PUMP OFF
Fault message after acknowledgement: LED "FAILURE" ILLUMINATED (FAULT).
The automatic control unit does not detect any throughflow and stops the pump to prevent greater damage from occurring. There are 3 fuses, each of which has a 10A rating. Use suitable fuses if pumps with different current input are operated.
The system remains stopped until the problem has been resolved by implementing appropriate measures.
Check the status of the fuses and replace the fuses if necessary. The motor winding and current input of the pump should also be checked. The pump is put back into operation as soon as the problems have been resolved. The INSTALLATION menu is then displayed for entering the appropriate amperage.
(ðSection6.2.2,Page16)
A6
A6 ACCUMULATION
Fault message after acknowledgement: LED "FAILURE" ILLUMINATED (FAULT).
The system checks the status of the accumulator at regular intervals. This occurs only in pressure-dependent mode.
2)
The system continues to operate even if the pressure in the accumulator is insufficient. It is highly recommended that you check the accumulator immediately.
The system has detected that the accumulator is damaged. Check the pre-charge pressure of the accumulator, the status of the membrane and the spherical accumulator and replace the membrane if necessary.
(ðSection6.2.3,Page18)
None No display
-
-
- Check the electrical connection and power supply. Call in customer service.
2) No longer available from 2014 production date
Page 22
9 Related Documents
22 of 28
Cervomatic EDP.2
9 Related Documents
9.1 Wiring diagrams
W
L3
V
L2
U
L1
400 V 230 V
A
B
C
D
Fig.3: Connections at automatic control unit
A Transformer fuse 250mA B Pump connection C Power supply connection D Pump fuse 10A
Pump connection
W
U
V
M
W
U
V
M
3~400 V 3~230 V
1~230 V
Fig.4: Wiring diagram of automatic control unit to pump
Connection to power supply
3~400 V 3~230 V
1~230 V
L3
L3
L1
L1
L2
L2
Fig.5: Wiring diagram of automatic control unit to power supply
Page 23
9 Related Documents
23 of 28
Cervomatic EDP.2
9.2 Additional electrical connections
NO
NC
C
MAX.
MIN.
A B
Fig.6: Additional electrical connections
A General fault message relay B Input for inlet tank monitoring
Cable entry
1
2
3
Fig.7: Cable entry in housing
1 Pump 2 Power supply 3 Inlet tank monitoring (optional)
Page 24
10 EU Declaration of Conformity
24 of 28
Cervomatic EDP.2
10 EU Declaration of Conformity
Manufacturer: KSB SE & Co. KGaA
Johann-Klein-Straße 9
67227 Frankenthal (Germany)
The manufacturer herewith declares that the product:
Cervomatic EDP.2
Series code range: 2016w16 to 2018w52
is in conformity with the provisions of the following Directives as amended from time to time:
Electromagnetic Compatibility Directive 2014/30/EULow-voltage Directive 2014/35/EU
The manufacturer also declares that:
The following harmonised international standards have been applied:
EN 60730-1, EN 60730-1-6, EN 60730-2-6EN 61000-6-2, EN 61000-6-3
The EU Declaration of Conformity was issued in/on:
Frankenthal, 1 February 2018
Joachim Schullerer
Head of Product Development Pump Systems and Drives
KSB SE & Co. KGaA
Johann-Klein-Straße 9
67227 Frankenthal
Page 25
Index
25 of 28
Cervomatic EDP.2
Index
C
Commissioning/start-up16
D
Design10 Designation9 Disposal8
F
Faults
Causes and remedies20
N
Name plate9
O
Other applicable documents4
S
Safety5 Safety awareness6 Storage7
T
Transport7
Page 26
Page 27
Page 28
KSB SE & Co. KGaA
Johann-Klein-Straße 9 • 67227 Frankenthal (Germany) Tel. +49 6233 86-0 www.ksb.com
5125.86/05-EN
Loading...