Kronoterm WPG 7, WPG 30 Owner's Manual

Page 1
Owner’s Manual
for heat pumps water-water, brine-water and
air-water
The instructions for use have to be handed over to the end user.
ENG
Id.: 17-16-19-2972-04 | 6.2018
Page 2
Owner’s manual for heat pumps water-water, brine-water and air-water Id.: 17-16-19-2972-04 | 6.2018 Printed in Slovenia, copyright: Kronoterm d.o.o. This document is copyrighted. Any use outside the provisions of the copyright law without the permission of Kronoterm d.o.o. is illegal and punishable by law. All previous versions of this document are void. We reserve the right to make changes and mistakes in print.
Page 3
6.2018
3
Content
Content ............................................................................................................................................. 3
1 Instructions for the use of the documentation .......................................................................... 5
1.1 To the buyer ...................................................................................................................... 5
1.2 Important information ........................................................................................................ 5
1.3 Symbols ............................................................................................................................ 5
1.4 Attached documentation ................................................................................................... 5
1.5 Glossary of used terms and conceptions ......................................................................... 6
2 General facts about the heat pump .......................................................................................... 7
2.1 What is a heat pump ......................................................................................................... 7
3 TERMOTRONIC controllers ..................................................................................................... 8
3.1 General ............................................................................................................................. 8
3.2 Controlling the device and heating system ..................................................................... 10
3.3 Activating the electrical power supply of the device ....................................................... 11
3.4 Activating the device ....................................................................................................... 11
3.5 Operation of the device .................................................................................................. 11
3.6 Standby ........................................................................................................................... 12
3.7 Operation HP STOP ....................................................................................................... 12
3.8 Device HP STOP ............................................................................................................ 12
3.9 Power outage .................................................................................................................. 12
3.10 Display of the state of the device .................................................................................... 13
3.11 Setting parameters ......................................................................................................... 13
3.12 Setting the language ....................................................................................................... 14
4 Quick settings ......................................................................................................................... 15
4.1.1
Setting room temperature with the spatial corrector KT-2 ...................................... 15
4.1.2
Setting room temperature with the spatial corrector KT-1 ...................................... 16
4.1.3
Setting the room temperature with a room thermostat ........................................... 17
4.2 Setting the temperature of heating water ....................................................................... 17
4.3 Setting the temperature of DHW .................................................................................... 19
4.4 Changing the operational mode - winter/summer mode ................................................ 20
4.4.1
Changing the operating mode ................................................................................ 20
4.5 Setting the cooling temperature ...................................................................................... 21
4.6 Switching on the additional heat source ......................................................................... 22
4.7 Manual activation of the additional heat source ............................................................. 23
5 Advanced settings .................................................................................................................. 25
5.1 Heating settings .............................................................................................................. 26
5.1.1
Heating water control mode .................................................................................... 26
5.1.2
Weather controlled heating – heating curve ........................................................... 27
5.1.3
Heating based on constant temperature ................................................................ 30
5.2 Operating mode .............................................................................................................. 32
5.3 Setting the cooling system .............................................................................................. 32
5.3.1
Active cooling (only in reversible models) .............................................................. 32
5.3.2
Passive cooling ....................................................................................................... 33
5.4 Schedules ....................................................................................................................... 34
5.4.1
Operating mode ...................................................................................................... 34
5.4.2
Setting operation schedules ................................................................................... 34
5.5 Alternative source: .......................................................................................................... 36
5.6 Set the temperature for the heating water for heating the pool ...................................... 38
5.7 Programme for drying screeds ....................................................................................... 39
5.7.1
Standard programme .............................................................................................. 39
5.8 Meters for operating hours ............................................................................................. 40
5.9 Setting the date, hour and day of the week .................................................................... 41
5.10 Remote turn on/off .......................................................................................................... 41
5.11 PV signal ......................................................................................................................... 41
5.12 Silent operation mode ..................................................................................................... 42
6 User menus and parameters .................................................................................................. 43
6.1 Menu structure ................................................................................................................ 43
7 Registration of the heat pump into the cloud (WEB) .............................................................. 49
8 Information display of operation ............................................................................................. 50
Page 4
4
6.2018
8.1 Diagnostic displays ........................................................................................................ 53
9 Disruptions in operation, alarms and troubleshooting ............................................................ 54
9.1 Errors and alarms in normal operation mode ................................................................. 54
9.2 Troubleshooting ............................................................................................................. 56
9.2.1
Air-water device type .............................................................................................. 56
10 Device maintenance ............................................................................................................... 60
11 Settings of your heating system at start-up ............................................................................ 61
Page 5
6.2018
5
1 Instructions for the use of the documentation
Before first use, read the instructions for use thoroughly and learn its content. You will learn the purpose, functions and the handling procedures for the device.
In case of malfunctions of the heating system first consult section 9 and consult your installer who will find the reason for the malfunction and resolve it. In case the malfunction cannot be resolved, he will contact the customer service of the manufacturer who will resolve the malfunction.
1.1 To the buyer
We thank you for the trust you have shown by buying our heat pump. With the purchase of the heat pump KRONOTERM you have become the owner of a modern, high-quality and highly efficient device for heating and cooling which saves energy, uses renewable sources and thus maintains the environment clean. Future generations will be grateful for your decision.
1.2 Important information
The instructions are written to give you information on all the needed activities before the first and further use. The manual describes the process of setting up and use of the device.
NOTE
In case the product shall be given to a third person for use, the manual has to be handed over to them as well.
Incorrectly set parameters of the control unit can lead to stoppage or incorrect operation of the device. To reduce risk the manual points out important information with the use of symbols. Follow all general safety instructions and warnings connected with the operation.
1.3 Symbols
This symbol marks important information for the user.
A NOTE is a notification which holds important information regarding requirements of
the manufacturer and the device.
1.4 Attached documentation
Attached to the device you can find the following documentation which you are required to read before the first use of the device:
Owner’s manual intended to familiarise the user how to operate the device. The Installation manual intended to familiarise the installer end user with the guidelines,
requirements and warnings for correct installation and maintenance of the device.
Instructions for installing the control unit intended to familiarise the electrician and user
with the correct electrical connection, requirements and warnings as well as maintenance of the device.
Warranty is intended for the user to prove eligibility for free repair of the device in the
warranty period in case of malfunction.
Page 6
6
6.2018
1.5 Glossary of used terms and conceptions
In case of unfamiliar terms in the document, you can find the explanation here.
ALTERNATIVE SOURCE: The heat source is used for systems with solar collectors,
fireplaces and wood stoves when we either do not have a heat source on hand at any moment or an automatic switch through the signal from the controller of the device (i.e. in a wood stove) is not possible.
ADDITIONAL SOURCE: The external heat source found alongside the device (i.e.
oil/gas/pellet/external heater furnace) or internal heat source (electrical flow heater) which is factory integrated in certain types of devices. The spare or additional source can be used as “assistance” to the device under the so-called bivalent point when the capacity of the device does not suffice for maintaining the desired temperature. It can be used alongside the device alternatively (the either-or system) – the switch is automatic.
BACKUP SOURCE: A function, which turns on the selected additional source in the event
of an error or a remote shutdown. The device operates in antifreeze mode. The device will turn off following the confirmation of an error or interrupt signal from the remote off.
The flow heater which is installed in the device and turns on in the case of device
malfunction (in the so-called antifreeze programme). This ensures temporary operation for bridging the time until an authorised person from the service company arrives and corrects the error.
HEATING WATER: The liquid which flows inside the heating system (pipelines, floor, wall
and radiator heating). DHW: The water intended for sanitary use (cleaning, showering, washing ...). HEAT PUMP (HP): The device which takes energy from the environment, uses electric
energy to drive the device and releases heat from space heating and DHW. In the text
below the term ‘device’ will be used for the heat pump. HW: The device takes heat from the earth. AW: The device takes heat from the air. WW: The device takes heat from groundwater. Parameter NORMAL: The desired temperature of heating in the Normal mode of
operation. Parameter ECO: Lowering the desired temperature in the Eco mode of operation. Parameter COMFORT: Raising the desired temperature in the Comfort mode of operation. Operator: Is a natural or legal person who has real control over the technical operation of
the products and equipment covered in the directive (EU) No. 517/2014; a member state
can impose operator obligations on the owner in clearly defined and specific cases.
Page 7
6.2018
7
2 General facts about the heat pump
2.1 What is a heat pump
A heat pump is a device which uses renewable energy sources (air, earth and water) and enables us economical and ecologically friendly heating and cooling of the building as well as heating DHW. Whether it is intended for internal or external installation depends on the device itself. Heat pump operation:
HEAT SOURCE
HEAT PUMP
HEATING SYSTEM
The device takes heat from the environment or source (groundwater, earth, air) and transfers it to the water in the heating system. This is achieved with the process of evaporating the coolant in the evaporator which is a heat exchanger especially designed for this task. This coolant is compressed in the compressor in the next circuit to a higher pressure which makes the temperature of the coolant rise to a temperature higher than the temperature of the heated water. This coolant then condenses in the water-cooled condenser where the heat taken from ground water/earth/air and electrical energy needed for the operation of the compressor are transmitted to the heating water. The heating water can be heated up to 65 degrees Celsius and more through this process (depending on the operating conditions of the device); this makes the devices suitable for renovating older heating systems.
Evaporator
Condenser
Expansion
Compressor
Energy of the surrounding s
Drive power
Heat of the air
Heat of the earth
Heat of the water
Page 8
8
6.2018
3 TERMOTRONIC controllers
3.1 General
TERMOTRONIC is a self-adapting controller for controlling the heat pump (hereinafter the DEVICE) and the heating system. It controls the operation of the device so as to ensure the most efficient way to produce the desired temperature of the building based on the needs of the heating system and outside temperature.
The TERMOTRONIC controller offers controlling of the device and the heating system of the building (no more than 4 heating circuits) as well as controlling the heating with an alternative heat source, passive cooling (in the case of using the earth-water or water-water device), active cooling with the device, heating of pools, heating DHW with the device and/or alternative heat source and/or backup source.
Possibility of controlling the elements of the heating system with the controller TERMOTRONIC:
EXPANSION I/O MODULE
BASIC I/O MODULE
Page 9
6.2018
9
MARK DESCRIPTION CLOUD/WEB
Remote control of heating system via computers and smart mobile devices.
KT-1(2)
Room collectors KT-1(2) – control unit of the heating circuit.
A, B, C, D
Heating circuit (heating/cooling).
1
DHW heating.
2
Room heating.
3
Room cooling.
4
Weather controlled room heating.
5
Passive room cooling.
6
Heat pump control.
7
Control of additional source (DHW, electrical heater ...).
8
Control of auxiliary electrical heater for DHW.
9
Control of alternative heating source (SER - solar energy receivers or solid
fuel DHW).
10
Control of alternative heating source for DHW (SER or solid fuel DHW).
11
SER cooling.
12
Warm DHW circulation
13
Swimming pool heating.
MD1
Basic input-output module MD1.
MD2
Expansion input-output module MD2.
Modbus
Communication with the control system of the building (BMS) or smart
installation.
For performing the connection to the TERMOTRONIC controller see chapter “Connection of the internal unit” in the installation manual.
In addition to the listed control options the TERMOTRONIC controller also has a number of safety mechanisms built in which protect the device and the heating system from malfunction and defects.
Page 10
10
6.2018
3.2 Controlling the device and heating system
The device and heating system can be controlled with the use of 4 buttons on the controller interface TERMOTRONIC. The controller interface has a 4-line LCD screen which displays the current state of the device or controller and a LCD light indicator of malfunctions in the operation of the device
(ALARM).
The controller interface TERMOTRONIC in devices:
WPL in WPG 7 – 21 kW WPLV, WPL + HM, in WPG 30 – 110 kW
BUTTON BUTTON FUNCTION
MENU: Scrolling through the main menu and sub-menus.
ENTER: On, off, accessing the menu, accessing the settings and
confirming selected values.
»+«: Selecting the values, scrolling up the menus and sub-menus.
»-«: Selecting the values, scrolling down the menus and sub-menus.
ALARM: Indicator of device malfunction.
NOTE
Below only the following symbols are used in grey colour: (MENU),
(ENTER), (+), (-) and (ALARM).
Page 11
6.2018
11
3.3 Activating the electrical power supply of the device
The device’s electrical supply is turned on by switching:
The main switch into position “1” and Circuit breakers of the electric power supply of the device (1-ON).
The main switch of the device earth-water, Water-water (WPG).
Circuit breakers for the power supply of the air­water device (WPL, WPLV).
By switching on the main switch or circuit breaker of the electrical supply the device is live but still not working. After the startup delay time the device turns on.
3.4 Activating the device
After switching on the main switch or circuit breaker the interface screen displays the current state of the device - standby for the short delay time. The device is not operational yet.
NOTE
The temperature values can differ from the ones displayed on the picture. This also applies for all following pictures.
NOTE
If before shut down the device was in a state of HP STOP (HP STOP), it returns to the HP STOP mode after switching on the circuit breakers. The display displays HP STOP.
The device is turned on by holding the (ENTER) key for 3 seconds - see below for more information.
3.5 Operation of the device
After the start-up delay time the device starts operating in the selected mode (heating, cooling or heating DHW) according to present needs. The display displays the status:
In the case the set temperature parameters (Heating, Return, DHW ...) is reached, the device displays Standby.
Standby……………………………. Heating 35.5°C Return 35.3°C DHW 49.0°C
Heating……………………………… Heating► 35.5°C Return 32.3°C DHW 49.0°C
Page 12
12
6.2018
NOTE
Depending on the type of device the delay lasts from 30 to 300 seconds.
3.6 Standby
The device enters standby state when the values of the selected parameters Heating, Cooling, DHW , device protection ... are reached. The display of the interface displays the status:
NOTE
The device enters the standby mode also when any operation protection is active (compressor start-up delay, insufficient water flow); see chapter 9.
3.7 Operation HP STOP
In case you want to shut down the device, press the (ENTER) key and hold it for 3 seconds. The operation of the device is interrupted but the device is still live.
The device can be turned on again by pressing the (ENTER) key and holding it for 3 seconds.
3.8 Device HP STOP
The device can be disconnected from the power supply by switching the main switch to position “0” or disconnecting the circuit breaker (the electrical power supply fuses).
NOTE
WPL devices must not be disconnected from the power supply for a longer time (via the main switch or circuit breakers) because by doing so you disable the devices protection against water freezing in the system which leads to complete device malfunction. Here the requirements from the installation manual have to be considered.
3.9 Power outage
In case of a power outage the device ceases to operate. After power is restored the device undergoes 300 seconds of protection mode and then automatically returns to the mode before the power outage. In the case of a power outage the controller retains all settings set before the outage.
NOTE
In case of a power outage longer than 2 hours air-water models with a water connection, water has to be drained from the connecting pipes between the external and internal device. Operate in accordance with the requirements in the installation manual.
Standby……………………………. Heating 35.5°C Return 35.3°C DHW 49.0°C
HP STOP……………………………. Heating 35.5°C Return 32.3°C DHW 49.0°C
Page 13
6.2018
13
3.10 Display of the state of the device
After activating the power supply the device displays the current state of the device on the display according to the operating mode and values of basic parameters of the heating/cooling system of the building; see chapter 8.2.
Keys and allow moving up and
down the basic display.
READING ON THE DISPLAY DESCRIPTION
Standby Current state of operation.
Heating 2
35.5 °C Set or calculated temperature of heating (only in winter mode).
Return 32.3 °C Current temperature of the return. DHW 49.0 °C Current temperature of DHW. TD outside 88 7 °C Current outside temperature. TD60 in 12 days Time left until the start of DHW thermal desinfection
(i.e. next thermal desinfection will begin in 12 days). Setting of DHW thermal desinfection is controlled by changing parameters TD and HT every described in section 6 located in the main menu DHW.
2016/02/10 12:24 TUESDAY Current time and day of the week. Setting the time
and day of the week is described in section 5.9.
NOTE
No. 2 means the number of days until automatic mode switch. No. 88 represents the activation delay time of the additional source in minutes. The symbol displays the activation of the electric heater.
3.11 Setting parameters
All parameter settings of the device’s operation and heating/cooling system of the building are set as described below.
1.
For entering the user menu press the key
(MENU) on the basic display.
2.
The currently chosen menu is marked by the symbols > < (CHOOSE).
Keys or select the desired menu. To enter the selected menu, press the
(ENTER) key.
For exiting the menus to the basic display press the (MENU) key.
The display shows only those menus which were actually activated during the start-up of the device!
Standby…………………………….. Heating
2
35.5°C Return 32.3°C DHW 49.0°C
Standby……………………………… Heating 35.5°C Return 32.3°C DHW 49.0°C
> Heating <
1. Circuit
2. Circuit
3. Circuit
Page 14
14
6.2018
3.
After entering the selected menu the initial parameter is marked with the symbols > < (CHOOSE).
The key selects the parameter you want to change. When you select the parameter, press
key (ENTER).
4.
The signs * * along the chosen parameter indicate the “mode setting” (SET). The value of the chosen parameter can be changed to the
desired value by using keys or . To confirm the settings press key (ENTER).
5.
After confirming the settings by pressing key
(ENTER), the signs * * (SET) change
back into signs > < (CHOOSE). For changing the value of other parameters, repeat the process. After completing the settings you can return to the main menu by pressing the key (MENU).
NOTE
MARK
DESCRIPTION
> <
The arrows on the sides indicate the presently selected
parameter/menu (CHOOSE).
* *
The stars on the sides indicate the mode of setting the chosen
parameter (SET).
A full arrow with the name of the parameter (i.e.: DHW 50°C) indicates the current operation of the circulation pump or the position of the switching valve (i.e. DHW). In the case of more circulation pumps of the heating system being in operation, more full arrows are displayed.
3.12 Setting the language
The TERMOTRONIC controller enables setting different display languages. To set a language of your choice, follow the steps below or set the language thought the Home Cloud application.
Press key (MENU) in the basic menu.
Use the key to choose the Mode (Mode, Regime, Betriebsart, Nacin). menu.
To confirm the settings press key (ENTER).
C/W I Schedule >Normal 35.5°C < Eco -2.0°C
C/W I Schedule *Normal 35.5°C * Eco -2.0°C
C/W I Schedule >Normal 39.1°C < Eco -2.0°C
Standby………………… Heating 35.5°C Return 32.3°C DHW 49.0°C
> Mode <
Temperatures
Page 15
6.2018
15
Use the button to choose the parameter
Langugage EN (Jezik SI, Lingua IT, Sprache DE, Jezik CRO).
Press to go it to SET mode and use the button to select the desired language.
To confirm the settings press key (ENTER).
4 Quick settings
NOTE
The parameters of the TERMOTRONIC controller were set according to project documentation of the heating/cooling system, recommendations of the manufacturer of the device and your requests by the authorised contractor for commissions at commission. At handover, the contractor for commissions is obliged to thoroughly present you with the possible ways of the device’s operation and explain the setting modes of the parameters important for the user.
The basic function of the device is space heating and heating the DHW . The controller of the device calculates the optimal needed temperature of the heating water to achieve the desired air temperature of the room in dependence on the outside temperature.
Setting the temperature of heating/cooling The temperature in the heated/cooled room is controlled in two stages, by setting the temperature:
1. of the room with the spatial corrector or thermostat and
2. the heating/cooling water in the accumulator and heating/cooling circuits on the controller TERMOTRONIC.
NOTE
In case despite the change in the setting of the temperature with the spatial corrector or thermostat after a longer period of operation of the heating/cooling circuit (in floor heating this could last up to 4 days) the desired room temperature was not achieved, check the heating water temperature settings. For settings see chapter 4.2.
4.1.1 Setting room temperature with the spatial corrector KT-2
The spatial corrector KT-2 enables an advanced and very easy settings of room temperature and basic functions of the device.
By pressing the key or the display displays the currently set room temperature. The temperature is marked by an orange border. By pressing the key or again you adjust the desired room temperature. You confirm the change by pressing the OK button, although, the change auto-saves in 8 seconds.
C/W ALL I D8-PV Cooling Silent mode >Language EN <
Page 16
16
6.2018
NOTE
The space corrector influences the whole heating circuit and not the temperature of the individual room. The desired room temperature where the spatial corrector is located in the reference temperature for all other rooms of the heating circuit controlled by this spatial corrector. Before raising the temperature of heated water or the desired room temperature on the spatial corrector make sure the valves on the heat sources in the room where it is too cold for you, are completely or sufficiently opened. If the temperature of other rooms is too high or too low open or close the valves for floor heating or radiators where the deviations from the desired temperature take place.
NOTE
For maintaining the correct operation of the heating system you have to choose a suitable operating mode - winter (heating and DHW) or summer (DHW and cooling ­only in certain models). For choosing the mode see chapter4.3.
NOTE
A detailed description of the settings and additional functions (weather report, DHW, operating mode, information about the state of the device ...) see the manual for the spatial corrector KT-2.
4.1.2 Setting room temperature with the spatial corrector KT-1
The spatial corrector KT-1 enables basic settings of room temperature.
By pressing the key or the LED display displays the currently set desired room temperature. By pressing the key or again you adjust the desired room temperature. By pressing the keys you adjust the values by 0.5 °C. The change is confirmed automatically.
Quick setting: By pressing and holding the key the temperature setting changes in steps of 1 °C.
NOTE
The space corrector influences the whole heating circuit and not the temperature of the individual room. The desired room temperature where the spatial corrector is located in the reference temperature for all other rooms of the heating circuit controlled by this spatial corrector. Before raising the temperature of heated water or the desired room temperature on the spatial corrector make sure the valves on the heat sources in the room where it is too cold for you, are completely or sufficiently opened. If the temperature of other rooms is too high or too low open or close the valves for floor heating or radiators in the rooms where the deviations from the desired temperature take place.
NOTE
For maintaining the correct operation of the heating system you have to choose a suitable operating mode - winter (heating and DHW) or summer (DHW and cooling ­only in certain models). For choosing the mode see chapter4.3.
NOTE
You can find a detailed description of settings and additional functions in the manual for the spatial corrector KT-1.
Page 17
6.2018
17
4.1.3 Setting the room temperature with a room thermostat
For setting the room temperature with a room thermostat consult the manual which come with the thermostat or consult the installer.
NOTE
In case the thermostat is turned on all this time and the heating system does not heat/cool the space to the desired temperature, check the settings of temperatures of the heating system on the device.
NOTE
For choosing the function of heating or cooling an appropriate thermostat has to be installed which allows both functions.
NOTE
For maintaining the correct operation of the heating system you have to choose a suitable operating mode - winter (heating and DHW) or summer (DHW and cooling ­only in certain models). For choosing the mode see chapter 4.4.
4.2 Setting the temperature of heating water
Upon start-up the control of the heating water temperature of your heating system was set to Heating curve mode which ensures the most energy efficient operation of the device. In case the automatically calculated temperature of the heating water (in accordance with the external temperature) is insufficient for ensuring the comfort of living in the rooms, the temperature of the heated water can quickly be raised or lowered by changing the parameter of cooler/hotter (C/W). The values of the parameter C/W are adjusted in the menus 1. Circuit 2. Circuit 3. Circuit or
4. Circuit depending on which temperature you want to change. If you want to change (raise/lower) the temperature of the heated water for the whole building or heating system, change the parameter C/W in the menu Heating.
NOTE
Upon start-up the heating water temperature control was set to Heating curve mode. The authorised contractor for commissioning noted your heating water settings of the heating circuits into chapter 11.
By setting the parameter C/W you set the number of temperature steps (one temperature step equals 1 °C) for which you want to raise or lower the temperature of heated water. You perform the settings in the following steps:
1.
Press key (MENU) in the basic menu.
2.
In the user interface, use the key and choose menu 1. Circuit and press the key
(ENTER).
Standby……………………………… Heating 35.5°C Return 32.3°C DHW 49.0°C
Heating
> 1. Circuit <
2. Circuit
3. Circuit
Page 18
18
6.2018
3.
The first line has the parameter C/W
selected.
To set the parameter press key (ENTER).
6.
* * appear along the chosen parameter. The keys and change the value of the
parameter C/W. This raises or lowers the temperature of heated water.
7.
Each pressing of the key raises/ lowers the temperature of the heating circle for one temperature step (<, >). To confirm the settings press key
(ENTER).
7.
After conformation the controller calculates the new temperature setting for the heating circuit or heated water according to the external temperature (in case of weather control). For returning to the basic view press the key
(MENU) twice.
For advanced changing the temperature of the heated water control mode of the heating system see chapter 5.1.
NOTE
The temperature of heated water can be raised or lowered for no more than
four temperature steps.
The heating and individual circuits settings are separated from the cooling, this
is why all settings for heating remain unchanged with the change of the mode into cooling. The same is true for parameter settings in the menu Cooling,
1. Circuit, 2. Circuit, 3. Circuit, 4. Circuit and Heating, which are separated so as to maintain all settings when changing the heating Mode (winter/summer).
For heating curve you can choose various temperature modes of operation
with setting daily and weekly schedules. See chapter5.4.
NOTE In case of radiator heating for a significant change, change the parameter C/W for 2 or 3 temperature steps at once but only for 1 temperature step in case of floor heating. Please note that the responsiveness of the heating system in the case of radiator heating is quicker than in the case of floor heating. By changing the parameter C/W several hours can pass (in the case of floor heating) before the heating system responds properly and you can feel the change of the adjustment.
>C/W I < Schedule Normal 35.5°C Eco
-2.0°C
*C/W I * Schedule Normal 35.5°C Eco
-2.0°C
*C/W I>> * Schedule Normal 35.5°C Eco
-2.0°C
>C/W I>> < SCHEDULE Normal 35.5°C Eco
-2.0°C
Page 19
6.2018
19
4.3 Setting the temperature of DHW
Once the temperature of the DHW falls below the set temperature minus the parameter Hysteresis (example: DHW setting is 50,0 °C, Hysteresis setting is 5,0 °C DHW heating will start at 44,9 °C), the controller switches the device from space heating to heating DHW. Heating DHW has priority over other modes of operation. Setting the temperature of DHW is performed in the following steps:
1.
Press key (MENU) in the basic menu.
2.
In the user menu choose the menu DHW with the key and press the key (ENTER).
3.
In the menu DHW in the first line the parameter DHW is chosen. To set the parameter press key
(ENTER).
4.
* * appear along the chosen parameter. The keys and change the value of the parameter DHW. This raises or lowers the
temperature of DHW.
To confirm the settings press key (ENTER).
5.
Next to the set parameter you can again find the symbols > <.
For returning to the basic view press the key
(MENU) twice.
NOTE
The actual reached temperature of heated water in the DHW depends on the adequacy of the DHW, pipelines, flow and ventilation of the system.
NOTE
For controlling the temperature settings of DHW in the tank you can set different modes of operation (ECO, Comfort), daily and weekly schedules. See chapter 5.4.
Standby………………… Heating.. 35.5°C Return 32.3°C DHW 49.0°C
> DHW <
Additional source
Mode
Temperatures
> DHW 50.0°C < Hysteresis 5.0°C Schedule Circulation Sched.
* DHW
50.0°C * Hysteresis 5.0°C Schedule Circulation Sched.
> DHW
50.0°C <
Hysteresis
5.0°C Schedule Circulation Sched.
Page 20
20
6.2018
4.4 Changing the operational mode - winter/summer mode
The mode of operation - winter or summer, is chosen according to season. In the time when you do not need heating or want to cool the rooms, switch to summer operating mode. In case heating is needed, switch to winter mode. The choice can be automatic or manual.
NOTE
If you do not switch into the summer mode operation in the summer, this can result in higher energy consumption. The operational costs will be increased for two reasons:
The main circulation pump will switch on from time to time to check whether
the need for heating has arisen.
The additional source could also be turned on (for the protection of the heating
system) if the temperature falls below a certain point, i.e. 12 °C – this depends on the start-up settings.
NOTE
The cooling function is only provided by reversible and WPG + passive models of the devices.
The function of the device according to the chosen mode of operation: Mode
OPERATION
Heating DHW Cooling
Winter YES YES NO Summer NO YES YES
NOTE
In the winter mode (heating and DHW) the heating system works only for heating the heating water of activated circles and DHW. By using the built-in external switch we can launch manual switch on/off of the cooling mode of the device.
4.4.1 Changing the operating mode
Changing the operation from winter to summer mode is performed in the following steps:
1.
Press key (MENU) in the basic menu.
2.
In the user interface, use the key and choose menu Mode.
3.
To choose the menu Mode press key (ENTER).
Standby……………………………. Heating 35.5°C Return 32.3°C DHW 49.0°C
> Heating <
1. Circuit
2. Circuit
3. Circuit
>
Mode
<
Temperatures
Page 21
6.2018
21
4.
The first line has the parameter Mode Winter selected. To set the parameter press key (ENTER).
5.
* * appear along the chosen parameter. The key or changes the value of the parameter into:
Mode summer for cooling and preparation of DHW or Mode winter for heating and preparation of DHW or Mode AUTO for automatic switch between winter and summer mode of operation.
To confirm the settings press key (ENTER).
6.
For returning to the basic view press the key
(MENU) twice.
NOTE
Setting the AUTO mode allows an automatic switch of the operating mode after the external temperature at 9 PM is higher or lower than the temperature of the switch (12 °C) for 3 days. This setting can be changed with the parameter Temp. mode in the menu Mode.
4.5 Setting the cooling temperature
In the operating mode (Summer, AUTO) which enables cooling you can adjust the temperature of cold water for the cooling circuits. The controller only enables the mode of controlling the temperature of cold water with maintaining constant temperature.
NOTE For setting the cooling of the building the Summer or AUTO Mode must be chosen.
NOTE
If the installer set the parameter (371) in chapter 11 Buff. to constant, always make sure the Cooling menu in 1. Circuit, 2. Circuit, 3. Circuit or 4. Circuit has the parameter Normal set to a value at least equal to or lower than the value of the circuit with the lowest setting.
Setting the temperature of cold water is performed in the following steps:
1.
Press key (MENU) in the basic menu.
> Mode
Winter <
Screed drying
NO
Initial Maximum
* Mode
Winter *
Screed drying
NE
Initial Maximum
> Mode
Summer <
Screed drying
NO
Initial Maximum
Standby………………… Cooling 13.5°C Return 14.3°C DHW 49.0°C
Page 22
22
6.2018
2.
Choose the menu Cooling or use the key to choose the desired Circuit in the first menu. To set the parameter press key (ENTER).
3.
In the menu Cooling (or Circuit) use the key
to choose the parameter Normal and
press the key (ENTER).
4.
* * appear along the chosen parameter. Use the key or to change the value of the
parameter Normal; by doing so you raise or lower the temperature of the accumulator (or circuit).
To confirm the settings press key (ENTER).
5.
For returning to the basic view press the key
(MENU) twice.
NOTE
The cooling and individual circuits settings are separated from the heating, this
is why all settings for cooling remain unchanged with the change of the mode into heating.
In the case of floor, ceiling or wall cooling appropriate settings and protection
have to be ensured in order not to cause surface condensation.
For controlling the temperature settings of cooling water you can set different
temperature modes, daily and weekly schedules. See chapter 5.4.
The response of the cooling system in convector cooling is faster than in floor,
ceiling or wall cooling.
4.6 Switching on the additional heat source
In case the heating capacity of the device is not sufficient for covering thermal losses of the building under given weather conditions, you can increase the capacity by switching on the Additional source. The device has a Backup source, a flow electric water heater fitted as standard which can function as an additional heat source by activating the parameter Additional source. Basically, the controller is set to activate the additional source which operates parallel to the device if the external air temperature falls below -7 °C. This setting is set according to the building at commissioning and can be changed later. Before setting the parameter we advise consulting the contractor for commissioning.
NOTE
In case you would like to use an oil/gas/pellet furnace or external electric heater as auxiliary heat source, you have to ask the contractor for commissioning to perform the setting.
Activating the additional source manually is performed in the following steps:
> Cooling
<
1. Circuit
2. Circuit
3. Circuit
Schedule >Normal
13.0°C <
Eco
-2.0°C
Comfort 0.0°C
Schedule *Normal 12.5°C * Eco -2.0°C Comfort 0.0°C
Schedule >Normal
12.5°C <
Eco
-2.0°C
Comfort 0.0°C
Page 23
6.2018
23
1.
Press key (MENU) in the basic menu.
2.
In the user menu choose the menu Additional source with the key and press the key
(ENTER).
3.
In the first line choose the parameter Switch o and press the key (ENTER).
4.
* * appear along the chosen parameter. The keys and change the value of the
parameter Switch o constant. The auxiliary source will operate together with the heat pump.
To confirm the settings press key ENTER.
5.
For returning to the basic view press the key
(MENU) twice.
6.
In the first row, after switching on the Backup source, the main display will display the information about the status of the device Heating+AdHeater.
NOTE
From an economic standpoint we advise using the additional source only if necessary because using it means higher heating costs. This is why we recommend to switch the auxiliary heat source from constant back to Need when there is no more need for additional heating capacity.
4.7 Manual activation of the additional heat source
In case the device has a malfunction or heating with the device is not possible for whatever reason, we recommend activating the additional source- the flow electrical water heater which will take over the heating of the heating and DHW.
Activating the backup source manually is performed in the following steps:
1.
Press key (MENU) in the basic menu.
Standby………………… Heating 35.5°C Return 32.3°C DHW 49.0°C
>
Additional source
<
Mode
Temperatures
>Switch o
Need< Bi-point -5.0°C Delay
30 min Mode
PARALLEL
*Switch o
constant* Bi-point -5.0°C Delay
30 min
Mode
PARALLEL
> Switch o
constant < Bi-point -5.0°C Delay
30 min
Mode
PARALLEL
Heating + add. source Heating 40°C Return 32.3°C DHW 49.0°C
Standby………………… Heating 35.5°C Return 32.3°C DHW 49.0°C
Page 24
24
6.2018
2.
In the user menu choose the menu Additional source with the key and press the key
(ENTER).
3.
In the menu Additional source choose AddSourceOnly NO with the key and press the key (ENTER).
4.
* * appear along the chosen parameter. Use the key to change the value of the
parameter to Only add. source YES. Only the source will run.
To confirm the settings press key (ENTER).
5.
For returning to the basic view press the key
(MENU) twice.
6.
In the first row, after switching on the Backup source, the main display will display the information about the status of the device
Heating - AddSourceOnly -.
NOTE
The device in this mode can heat the heating and DHW.
The heating water will heat to the temperature set in the basic menu Heating,
1. Circuit, 2. Circuit, 3. Circuit, and 4. Circuit. In the case of a Frost Protection program (FP prog) error the temperature of heating water will heat up to the set temperature with the parameter AntiFreeze in the menu AddSourceOnly.
The DHW will heat up to the temperature set with the parameter DHW in the
menu Additional source.. As soon as heating with the device will be made possible again, set the parameter to AddSourceOnly NO.
> Additional source
<
Mode
Temperatures
Delay
OFF
Mode
PARALLEL
Rise for
5.0°C
>AddSourceOnly
NO<
Delay
OFF
Mode
PARALLEL
Rise for
5.0°C
* AddSourceOnly
NO*
Delay
OFF
Mode
PARALLEL
Rise for
5.0°C
> AddSourceOnly
YES<
Heating - AddSourceOnly ­ Heating 40 °C Return 32.3°C DHW 49.0°C
Page 25
6.2018
25
5 Advanced settings
In this chapter you will find:
How to set the parameters of the device in case the system has no spatial corrector or
thermostat built in or the settings for the temperature of heating water do not suffice the
heating needs. How to set the control mode of the heating water. How to set the mode of operation for heating water/cooling water, heating/cooling circuits
and heating of DHW. How to set schedules.
For easier understanding of the chapter, you can find a general scheme of the heating (cooling) system below.
M3
M5 M7 M10
M6
M9
M11
M4
B
C
M12
D
E
A
F
ELEMENTS
MARK
CHARACTERISTICS
A Space and DHW heating device B Heating circuits C Heating water (buffer tank) D DHW (DHW tank) E Heat consumers (floor heating / radiators) F Heat pump
M3
Main circulation pump
M4
Circulating pump for DHW
M5
Circulation pump of direct heating circle 1
M6
Circulation pump of mixing-heating circle 2
M7
Mixing valve of mixing-heating circle 2
M9
Circulation pump of mixing-heating circle 3
M10
Mixing valve of mixing-heating circle 3
M11
Circulation pump of mixing-heating circle 4
M12
Mixing valve of mixing-heating circle 4
NOTE
Heating circle 1 (M5) can only be a direct heating circle (without mixing valve). For this circuit we always choose the heating circle which requires the highest temperature (i.e. radiators).
Page 26
26
6.2018
5.1 Heating settings
NOTE
When setting or changing the desired heating water temperature, check whether parameter 371 is set to constant, chapter 11. In this case the following values have to be set: Normal and Correction in the menus Heating and 1. Circuit have to be equal and higher than the setting of desired values in the mixing circuits (2. Circuit, 3. Circuit and 4. Circuit), if they are active. In case one of the circuits (2. Circuit, 3. Circuit or 4. Circuit) is direct, it can have the same setting as 1. Circuit.
NOTE
In mixing heating cycles, the controller uses the highest set or calculated temperature of heating cycles for calculating the needed temperature.
The heating temperature thus consists of the set or calculated temperature of heating cycles and factory parameter settings Avt. Corr.
In weather controlled heating you can set three parameters:
Normal: With this parameter, you set the desired return heating water temperature at an
outside air temperature of -18 °C.
Standby: With this parameter you set the desired temperature difference between the
current desired temperature of the Return and the temperature of the return when the heating of the heating circuit or device turns on again.
Correction: With this parameter you set the incline of the weather controlled heating curve
outside temperature 15 °C. It is mainly important for transitional periods because the weather controlled heating curve can be too low at this time, depending on the building and desired comfort.
The parameters Normal, Standby and Correction can be changed to the desired values with keys
or
5.1.1 Heating water control mode
The controller of the device enables two ways of controlling the temperature of heating water at the exit of the device or the entry into individual heating circuits:
a) Heating Curve: Setting the desired temperature of heating water according to external
temperature.
b) Constant: The temperature of heating water is kept constant regardless of the external
temperature. The control mode of the heating water suitable for individual buildings depends on various factors such as the type of building, its size, make of heating system ...; this is why the control mode for heating water temperature is set by a qualified person at commission (the authorised contractor for commissions) nevertheless, you can change the setting later. The recommendation of the device’s manufacturer is, if acceptable from the standpoint of comfort, etc., to set the heating water control mode to heating curve; this is why the present document regards this setting as the default setting - the setting set at commission. Heating curve means a more efficient operation of the heating system because by with higher external temperature the desired temperature of heated water is lowered, which means a more efficient operation of the device; for more information, see section 5.1.2.
Control modes for heating water have to be set separately by type in menus:
Page 27
6.2018
27
Heating…………………
1. Circuit,
2. Circuit,
3. Circuit,
4. Circuit,
Here it is necessary to take account the NOTE (chapter 5.1)! The method of adjustment is the same in all cases and is described on the example of heating curve in section 5.1.2 and for the example of control at constant temperature in section 5.1.3.
5.1.1.1 The change in heating control heating curve - constant temperature
You can switch the heating control from heating curve to control by maintaining constant temperature in the following manner:
1.
Press key (MENU) in the basic menu.
2.
Choose the menu Heating or use the key to choose the desired Circuit. To set the parameter press key (ENTER).
3.
Choose the Heating curve parameter by pressing and press the (ENTER) key.
4.
* * appear along the chosen parameter. By pressing the key adjust the value of the
Heating curve parameter into Const. temperature and confirm the settings by
pressing the key (ENTER).
5.
For returning to the basic view press the key
(MENU) twice.
5.1.2 Weather controlled heating – heating curve
Weather controlled heating means water temperature in the heating system is adjusted to the current air temperature. The lower the outside temperature, the higher the heat of the buildingand as a result a higher temperature of heating water is needed in the heating bodies (floor, wall or radiator heating ...) to compensate for the losses.
The opposite is true in case of higher outside temperatures. In this case the heat losses are lower and a lower heating water temperature is needed in the heating bodies to compensate for the losses.
Standby………………… Heating 35.5°C Return 32.3°C DHW 49.0°C
> Heating
<
1. Circuit
2. Circuit
3. Circuit
Normal 35.5°C Eco -2.0°C Standby 3.0°C
>Heating curve ....................<
Normal 35.5°C
Eco -2.0°C Standby 3.0°C
*Const. temperature ............*
Normal 35.5°C
Eco -2.0°C Standby 3.0°C
*Const. temperature ....... . <
Page 28
28
6.2018
The weather controlled heating curve shows that the temperature of the return (heating water returning to the heat pump from heating bodies) depends on the temperature of air outside the building. The lower the external air temperature, the higher the calculated needed temperature of the return.
The weather controlled heating curve
The appropriate heating temperature setting is essential for ensuring the desired comfort. It depends on the characteristics of the house and heating bodies as well as the project temperature. The table below lists the recommended settings which can help you decide on the appropriate parameters of the weather controlled heating.
TYPE OF
HOUSE
PARAMETER HEATING (weather controlled)
Heating, 1. Circuit, 2. Circuit, 3. Circuit, and 4. Circuit
Floor, wall [°C]
Convector
heating [°C]
Radiation heating 55 °C
Radiation heating 65 °C
Non­insulated house
Normal - 55 65
70
Standby -3 5 5
7
Correction - Correction of breaking point (+15 °C)
- 10 13
15
Insulated house
Normal
35 50 55 65
Standby
2 5 5 6
Correction - Correction of breaking point (+15 °C)
5 5 10 12
Well­insulated house
Normal 30 40 55 55 Standby, Hysteresis 2 5 5 5 Correction - Correction of breaking point (+15 °C)
3 3 5 10
NOTE
In mixing heating circuits we adjust the adjustable temperature of the supply pipe; in direct heating circuits and on the device we adjust the temperature of the return.
20
25
30
35
40
45
50
55
-18 -13 -8 -3 2 7 12 17 22
Temperature of heating water [°C]
Temperature of external air [°C]
Setting of weather controlled heating
Normal
Setting of breaking point for
the weather guided heating
- transitional period
Correction
The calculated temperature of the
return setting at current temperature
of external air.
15
Page 29
6.2018
29
5.1.2.1 Setting the temperature correction of heated water
By changing the value of the parameter Correction you can adjust the calculated temperature of heating water in transitional (autumn and spring) periods and thus adjust the desired comfort in the heated building. You perform the settings in the following steps:
1.
Press key (MENU) in the basic menu.
2.
The first line has the parameter Heating selected. To set the parameter press key (ENTER).
3.
Choose the Correction parameter by pressing
and press the (ENTER) key.
4.
* * appear along the chosen parameter. The keys and change the value of the parameter Correction. The temperature can be
raised for no more than 15 K (°C). For returning to the basic view press the key
(MENU) twice.
5.1.2.2 Setting the heating curve temperature - Normal
By setting the parameter Normal you set the maximum heating water temperature at an outside air temperature of -18 °C.
NOTE
After start-up of the device there is usually no need to change the parameter Normal in the menu Heating, except in cases of constructional changes in the heating system.
You perform the settings in the following steps:
1.
Press key (MENU) in the basic menu.
2.
The first line has the parameter Heating selected. To set the parameter press key
(ENTER).
3.
Choose the parameter Normal by pressing
and press the (ENTER) key.
Standby………………… Heating 35.5°C Return 32.3°C DHW 49.0°C
> Heating
<
1. Circuit
2. Circuit
3. Circuit
Comfort 2.0°C Hysteresis 3.0°C Heating Curve >Correction 5.0°C<
Comfort 2.0°C Hysteresis 3.0°C Heating Curve *Correction 5.0°C*
Standby………………… Heating 35.5°C Return 32.3°C DHW 49.0°C
> Heating
<
1. Circuit
2. Circuit
3. Circuit
C/W I Schedule >Normal
35.5°C <
Eco
-2.0°C
Page 30
30
6.2018
4.
* * appear along the chosen parameter. The keys and change the value of the parameter Normal. This way you raise or lower
the maximum temperature of heating water at outside temperature of -18 °C. To confirm the
settings press key (ENTER). The recommended values of the maximum temperature for individual types of heating are given in chapter 5.1.
5.
After confirming the settings the controller calculates the new temperature setting of the heating water according to outside temperature (heating curve); if the outside temperature is higher than
-18 °C, this calculated temperature lower than the set temperature. For returning to the basic view press the key
(MENU) twice.
Repeat the process for each circuit.
NOTE
For economical and comfortable use of heating we recommend the use of
heating curve heating.
For heating curve heating, you can choose various temperature modes of
operation with setting daily and weekly schedules. See chapter 5.4.
5.1.3 Heating based on constant temperature
For ensuring economical operation of the whole system we recommend choosing heating curve of heating. Nevertheless, if you want to heat the rooms with constant water temperature in the system, we recommend the following settings:
TYPE OF
HOUSE
PARAMETER HEATING (with constant temperature)
Heating, 1. Circuit, 2. Circuit, 3.
Circuit, and 4. Circuit
Floor, wall [°C]
Convector heating [°C]
Radiation heating 55 °C
Radiation
heating 65 °C
Non-insulated house
Normal 38 50 50
55
Standby 3 5 5
7
Insulated house
Normal
35 45 47 50
Standby
2 5 5 6
Well-insulated house
Normal 30 40 45 47 Standby 2 5 5 5
NOTE
In mixing heating circuits we adjust the adjustable temperature of the supply pipe; in direct heating circuits and on the device we adjust the temperature of the return.
C/W I
Schedule *Normal 45.0°C * Eco -2.0°C
C/W I Schedule >Normal
45°C <
Eco
-2.0°C
Page 31
6.2018
31
5.1.3.1 Setting the temperature of heating water
By choosing the parameter Normal you set the temperature of heating water which is maintained regardless the outside temperature.
NOTE
After start-up of the device there is usually no need to change the parameter Normal in the menu Heating, except in cases of constructional changes in the heating system.
You perform the settings in the following steps:
1.
Press key (MENU) in the basic menu.
2.
The first line has the parameter Heating selected. To set the parameter press key
(ENTER).
3.
Choose the parameter Normal by pressing
and press the (ENTER) key.
4.
* * appear along the chosen parameter. The keys and change the value of the
parameter Normal. This way you raise or lower the maximum temperature of heating water at outside temperature of -18 °C. To confirm the settings press key (ENTER). The recommended values of the maximum temperature for individual types of heating are given in chapter 5.1.
5.
After confirming the settings the device will heat the water to the set temperature regardless of the outside air temperature. For returning to the
basic view press the key (MENU) twice.
NOTE
For economical use of heating we recommend the use of heating curve
heating.
For heating curve you can choose various temperature modes of operation with
setting daily and weekly schedules. See chapter 5.4.
Standby………………… Heating 35.5°C Return 32.3°C DHW 49.0°C
Heating
> 1. Circuit <
2. Circuit
3. Circuit
C/W I Schedule >Normal
35.5°C <
Eco
-2.0°C
C/W I
Schedule *Normal 45.0°C * Eco -2.0°C
C/W I Schedule >Normal
45°C <
Eco
-2.0°C
Page 32
32
6.2018
5.2 Operating mode
The controller of the device enables heating of the heating water/ cooling of the cooling water, heating/cooling of the circuits and DHW in four different operational modes:
Normal applies to heating/cooling. DHW applies to the heating of DHW. ECO. COMFORT.
These different ways of operation can later be used with setting timetables.
The parameter ECO is used for more economical operation. During hating the temperature of the heating water is reduced, during cooling the temperature of cooling water is increased. In this operating mode you will save on costs but at the expense of comfort. The parameter COMFORT is used for the operation which means greater comfort - a raising of heating water temperature for the set value in the heating mode; in the cooling mode it means the opposite - a lowering of cooling water temperature.
In case you want to change the entire system to ECO or COMFORT operation, you can perform the adjustment in the menu mode where you change the parameter Operation AUTO to Operation
ECO or Operation COMFORT.
5.3 Setting the cooling system
You turn on the cooling mode by entering the menu mode and changing the parameter mode Winter to mode Summer (see chapter 4.4).
To turn on the cooling according to schedule you have to set the operating schedule for
cooling in the menu Cooling. The display and settings of the Cooling menu are enabled
only if the conditions of the mode’s operation listed in the section 4.4 are met (chosen mode
+ reversible heat pump or passive cooling).
For setting the parameter Schedule see chapter 5.4.
5.3.1 Active cooling (only in reversible models)
Cooling can be set for every parameter described in the table below separately.
In case of active cooling we recommend the following cooling settings:
PARAMETER COOLING
Cooling, 1. Circuit, 2. Circuit, 3. Circuit, and 4. Circuit
Floor, wall, ceiling [°C] Convector heating [°C]
Normal
19,0–20,0 12,0–15,0
Standby
2,0 3,0–4,0
NOTE
In mixing heating circuits we adjust the adjustable temperature of the supply pipe; in direct heating circuits and on the device we adjust the temperature of the return.
NOTE
Active cooling works in the area set in the menu Cooling with the parameters T.out.max. - external temperature above which the active cooling can operate actively
and the parameter Min - external temperature until which the active cooling can operate.
1.
Parameters T.out.min and max. For setting active cooling.
To set the parameter press key (ENTER).
T.out.min 20.0°C max 40.0°C
Min.Diff. 2.0°C Checking TP 2400
Page 33
6.2018
33
5.3.2 Passive cooling
NOTE
Passive cooling is only possible with devices of the WPG type.
Passive cooling uses the coolness of the groundwater or earth this is why we cannot set
the desired temperature of cooling water. Cooling is activated when at least one of the heating circuits is active.
Passive cooling will work if the difference between the supply and return temperature of the
source is higher than the parameter Min.diff. which is set in the Cooling menu. In case the temperature difference is smaller the pump turns on periodically for the time set in the parameter Checking TP and will operate for the set time in the parameter for for the period until the difference between the supply and return temperature of the source is higher than the one set with the parameter Min.diff. The submersible pump turns on periodically so that the controller can acquire information about the actual temperature of ground water from the sensors built into the device (source). Based on this information it checks whether passive cooling is possible or not.
The operating indicator of the circulation pump for passive cooling is the sign on the
display of the regulation.
NOTE
Passive cooling works in the area set in the menu Cooling with the parameters T.out. min - external temperature above which the passive cooling can operate actively and
the parameter Max - external temperature until which the passive cooling can operate.
1.
Parameters T.out.min and max for setting active cooling.
To set the parameter press key (ENTER).
2.
NOTE
Parameters for passive cooling must be set lower as the setting for active cooling!
Min.Diff. 2.0 Checking TP 2400 for 300 T.out.min 20.0°C
max
40.0°C
Page 34
34
6.2018
5.4 Schedules
5.4.1 Operating mode
Every function (heating, cooling, 1. Circuit, 2. Circuit, 3. Circuit, 4. Circuit, DHW, pool, silent operation and circulation) can operate in several ways. Setting the operation mode for individual functions are performed in the schedule for this function. In heating, cooling, mixing circuits, heating of DHW and swimming pool heating there can be 4 different types of operation:
OFF: Heating/cooling is disabled. ► HEA of COL: Operation in the heating or cooling mode (parameter Normal). ► ECO: In this mode the controller maintains the temperature which is lower by the value of
the ECO parameter than the set temperature in the parameter Normal. In case of cooling
the temperature set in this mode is higher by the value of the ECO parameter than the set
temperature in the parameter Normal. In this mode operation is more economical.
COM: In this mode the controller maintains the temperature which is higher by the value of
the COM parameter than the set temperature in the parameter Normal. In case of cooling
the temperature set in this mode is lower by the value of the COM parameter than the set
temperature in the parameter Normal. In this mode operation is less economical,
depending on the setting it can also be more comfortable.
In circulation of DHW two operation settings are possible:
OFF: Circulation pump is disabled. ► CIR: Circulation pump is truned on.
Devices of the WPLV type enable two additional operation modes set in the menu Mode with the parameter Silent mode:
NRM: Normal operation in the heating or cooling mode. ► LOW: Lowered operation mode in the heating or cooling mode. Lower noise level but also
lower heating or cooling capacity.
5.4.2 Setting operation schedules
NOTE
The easiest way to set the timetable is via the web application for remote control Cloud (cloud.KRONOTERM.com). For the use of the web interface see Instructions for use
Web interface. The schedule enables daily settings of 6 operation mode switches. Below is a description of heating with an example of a daily schedule.
Heating is turned off (OFF) from 00:00 to 02:00.
0 2 4 6 8 10 12 14 16 18 20 22 24
Time of day [h]
COMFORT
Normal
OFF
ECO
Page 35
6.2018
35
The heating is turned on at 02:00 in the COMFORT mode (in this mode the temperature is higher than the temperature set in the parameter Normal by the COM parameter). The heating is turned on at 07:00 in the ECO mode (in this mode the temperature is lower than the temperature set in the parameter Normal by the ECO parameter). At 1:00 PM the operating mode switches to COMFORT. AT 5:00 MP the operating mode switches to Normal (the temperature set or calculated in the parameter Normal). At 9:00 PM the heating turns off (OFF).
You perform the settings in the following steps:
In the menus Heating, Cooling, Circuits, choose the parameter Schedule with the key . When
the symbols > < appear next to the parameter Schedule, press the key (ENTER).
The day blinks which the schedule refers to. Choose the day you would like to set the schedule by using
keys or . When you choose the day press the key (ENTER).
The time when the switch-over will be performed blinks. By pressing the key (ENTER) confirm you want to set the time. Symbols XXXXX start
blinking over the time. Set the desired time with the key of the switch-over (in 15 min). To confirm the set time press key (ENTER). The symbols
XXXXX stop blinking over the time.
By pressing you can access the field for choosing the mode of operation. This field starts
blinking. By pressing the key (ENTER) confirm you want to set the mode of operation. Symbols XXX start blinking over the operating mode. Use
keys or to choose the suitable mode of operation along the set time. To confirm the
operating mode press key (ENTER). Symbols XXX no longer blink over the operating mode.
NOTE
Once you have set the operating mode it continues to be used until a new one is set. I.e. if you set the heating to OFF on Monday and you do not set anything for the following days, the heating will be OFF for all the following days as well because there was no change of operation mode.
Use the key to navigate to the time set for the next switch-over of the operating mode. Perform the settings the same as for the first switch-over.
C/W I >Schedule
<
Normal 35.5°C
Eco -2.0°C
MO N
Co py
DE LE TE
00 :0 0
HE A - -: -- HE A
- -: --
HE A - -: -- HE A
-- :- -
HE A - -: -- HE A
MO N
Co py
DE LE TE
00 :0 0
HE A - -: --
HE A
-- :- -
HE A - -: --
HE A
-- :- -
HE A - -: --
HE A
MO N Co py D EL ET E 00:00 OFF --:-- OFF
-- :- - O FF - - : - - O FF
-- :- - O F F - - : -- O FF
MON Copy DELETE 00:00 HEA --:-- HEA
--:-- HEA --:-- HEA
--:-- HEA --:-- HEA
Page 36
36
6.2018
To switch the heating to the COMFORT mode, choose COM. To switch the heating to the ECO mode, choose ECO. To switch to the Normal mode, choose HEA or COL. To switch off the heating, choose OFF.
When you set the schedule you can use the key (MENU) to return to the menu.
The set schedule can be copied to the following day by using the following steps:
Use the key to navigate to Copy which starts blinking. Press the key (ENTER).
The controller displays the question whether you would like to copy the currently chosen schedule to the following day. To confirm, press key (ENTER). If you do not want to confirm, press key
(MENU).
Use this method to copy the schedule for all days of the week.
If you made a mistake, you can delete the schedule for the chosen day using the following steps:
Use the key to navigate to delete, which starts blinking. Press the key (ENTER).
The controller displays the question whether you would like to delete the currently chosen schedule.
To confirm, press key (ENTER). If you do not want to confirm, press key
(MENU).
You have deleted all the settings for the chosen day. The chosen day uses the last settings of the previous day.
After performing the setting you can use the key (MENU) to return to the menu.
5.5 Alternative source:
NOTE
For this function and to display the menu Alternative source on the TERMOTRONIC
controller you need the extension regulation with the input-output module TT3003.
MON Copy DELETE 00:00 HEA --:-- COM 02:00 COM --:-- COM
--:-- COM --:-- COM
MON Copy DELETE 00:00 OFF 13:00 COM 02:00 COM 17:00 HEA 07:00 ECO 21:00 OFF
****************************** * ? COPY ? * * TUESDAY * ******************************
TU E
Co py
DE LE TE
00 :0 0 O FF 13 :0 0 C OM 02 :0 0 C OM 1 7 :0 0 HE A 07 :0 0 E CO 2 1 : 0 0 O FF
TU E
Co py
DE LE TE
00 :0 0
HE A -- :- - HE A
-- :- -
HE A -- :- - HE A
-- :- -
HE A -- :- - HE A
** ** ** ** ** * * * ** ** ** ** ** * * * ** ** ** *
* ? D E LE TE ? *
** ** ** ** ** * * * ** ** ** ** ** * * * ** ** ** *
TU E
Co py
DE LE TE
-- :- -
HE A -- :- - HE A
-- :- -
HE A
-- :- - HE A
-- :- -
HE A
-- :- - HE A
Page 37
6.2018
37
The alternative source function is used for using the heat from the solar collectors (SSE) or for using heat from the biomass DHW s. All settings for the alternative source can be found in the menu Alternative source. Heating the storage buffer tank or DHW begins when the temperature of the alternative source reaches the set temperature difference (parameter Dif.Min.) between the alternative source and the buffer tank or DHW. Heating the buffer tank is performed until the set temperature in the menu Alternative source. The DHW has heating priority (parameter Prior. DHW.). When the temperature in the DHW is reached (parameter Set.Temp.) it is followed by the heating of the buffer tank. After the temperature of the buffer tank is reached the heating of the DHW is turned on again until the temperature set in the parameter Max.Temp in the menu Alternative source is reached. If the temperature of the alternative source is still higher than the temperature in the buffer tank, heating of the buffer tank continues until the parameter Max. Temp. (The maximum temperature of the buffer tank), set in the menu Alternative source. When the buffer tank and DHW reach the maximum temperature, heating with the alternative source stops. In case the temperature of the alternative source reaches the temperature of protection (parameter protection), a signal turns on which can control the users to lower the temperature of the alternative source.
NOTE
We recommend keeping the settings set by the authorised contractor for commissions.
1.
Press key (MENU) in the basic menu. In the user menu choose the menu Alternative source with the key and
press the key (ENTER).
> Alternative source <
Backup source
Mode
Temperatures
Page 38
38
6.2018
5.6 Set the temperature for the heating water for heating the pool
NOTE
For this function and to display the menu Pool on the TERMOTRONIC controller you
need the extension regulation with the input-output module TT3003.
The temperature of heating water for Swimming Pool Heating can be performed in the following steps:
1.
Press key (MENU) in the basic menu.
2.
In the user menu choose the menu Pool with the key and press the key (ENTER).
3.
In the menu Pool choose the parameter Normal by pressing and press the
(ENTER) key.
4.
* * appear along the chosen parameter. The keys and change the value of the parameter Normal. This raises or lowers the
maximum temperature of swimming pool heating. To confirm the settings press key
(ENTER).
5.
For returning to the basic view press the key
(MENU) twice.
NOTE
Swimming pool heating has the lowest priority. The highest priority is reserved for
heating DHW, followed by heating or cooling of the building, followed by swimming pool
heating.
Standby……………………………… Cooling 13.5°C Return 14.3°C DHW 49.0°C
DHW
>
Pool
<
Additional source
Mode
Schedule >Normal OFF < Eco -2.0°C Comfort 2.0°C
Schedule *Normal 30.0°C * Eco -2.0°C Comfort 2.0°C
Schedule >Normal 30.0°C < Eco -2.0°C Comfort 2.0°C
Page 39
6.2018
39
5.7 Programme for drying screeds
The controller has a built in function of gradual drying of screeds which is especially important for new buildings and before installing flooring. Before using the programme for drying screeds you have to consult the contractor for screeds. According to his requirements you can use the standard programme or adjust it. The programme for drying screeds is located in the menu mode.
5.7.1 Standard programme
This programme consists of 8 steps and is normally adjusted for all systems of floor heating. Before activating this programme you have to set the maximum allowed temperature of the return water, i.e. 30 °C.
Steps 1-4: Heating Step 5: Maintaining the reached temperature Steps 6-8: Cooling
Steps 1 to 4 mean the heating phases which last 24 hours each (parameter Step). The needed maximum temperature of return water (parameter Maximum) is reached in four equal steps which start with 20,0 °C (parameter Initial). For finishing each step the time limit of 24 hours must be met. If the temperature of individual steps is reached sooner, the device maintains this temperature for the remaining time. In step 5 we maintain the maximum reached temperature at this level for additional 264 hours (parameter Duration). After this time the following step is possible. Steps 6 to 8 are cooling phases performed in equal steps as the heating, only in reverse order. Each step lasts 24 hours - which is a total of 72 hours, in this time the temperature of the return water falls from maximum temperature to 20,0 °C (parameter Final). When this programme finishes completely, the device returns to normal operation.
Example:
The maximum temperature of return water is 300 °C.
Steps 1 to 4: 20,0/23,3/26,6/30,0 °C – in 96 hours Step 5: 30,0 °C – constant temperature for 264 hours Steps 6 to 8: 26,6/23,3/20,0 °C – in 96 hours
1.
In the user menu choose the menu Mode with the key and press the key
(ENTER).
2.
Choose the Screed drying parameter by pressing and press the (ENTER)
key.
> Mode
<
Temperatures
Mode AUTO
>Screed drying
NO <
Initial
20.0°C
Maximum..……………… 30.0°C
Page 40
40
6.2018
2.
* * appear along the chosen parameter. Choose the parameter Yes by pressing
and confirming by pressing the
(ENTER) key. You have thus turned on the operation of the mode Screed drying.
3.
Other parameters of the programme for Screed drying can be changed with the same procedure.
For returning to the basic view press the key (MENU) twice.
5.8 Meters for operating hours
If you want to see, the operating hours for individual components go to the main menu and press the key under consecutive no.1 in the table below. If you would like to examine other parameters listed in the table below use the key to move to them.
Cons. No.
Parameters of operating hours view Parameter description
1. Operating hours for compressor in heating. Operating hours for compressor in cooling. Operating hours for compressor in heating DHW. D: Operating minutes of the current day. D-1: Operating minutes of the previous day.
2. Operating hours of the heat source (ventilator, submersible pump). Operating hours of the auxiliary source 1 (flow electric heater). Operating hours of the auxiliary source 2 (external backup source). Operating hours of the main circulation pump.
3. Operating hours of passive cooling. Operating hours of backup source. Number of daily power-on of the compressor in heating. Number of daily power-on of the compressor in cooling.
4. Number of daily turn-on for compressor in heating DHW. Number of daily power-on of the compressor in defrost.
Mode AUTO *Screed drying
YES *
Initial
20.0°C
Maximum..………………30.0°C
Maximum…………………30.0°C Step…………………………..24 h Maintaining 264 h
>Final 20.0°C
Comp.HEAT.[h]: 0 Comp.COOL.[h]: 0 Comp.DHW [h]: 0 D: 0 D-1: 0
HeatSource [h]: 0 AdHeater 1[h]: 0 AdHeater 2[h]: 0 MainPump.[h]: 0
Passive [h]: 0 Alt.Sourc [h]: 0 Comp.Heata.[s/d]: 0 Comp.CooL. [s/d]: 0
Comp.DHW [s/d]: 0
Defrost [s/d]: 0
Page 41
6.2018
41
5.9 Setting the date, hour and day of the week
In case of incorrect time and date on the TERMOTRONIC controller, follow the steps below:
1.
Press key in the basic menu.
2.
Press key until the display shows the following:
To change the year press key (ENTER).
3.
The selected value 2017 starts blinking. Now use key or to choose the proper value and press key (ENTER). Now you can
adjust the month 03, day 01, name of the day using the same procedure as you did by setting the year. For returning to the basic view press the key
(MENU) twice.
5.10 Remote turn on/off
The basic regulation enables remote turn off via an external signal. Once the signal is gone the device operates in the state before shut down.
NOTE
External turn off can be performed only in case the device was fitted with an externally controlled switch upon installation.
5.11 PV signal
The PV signal can be turned on in the menu mode with the parameter D8-PV. It allows factory and user settings:
The factory control setting enables the control of the temperature operating mode. This
means that in the case of the winter mode (heating) you can turn on cooling. The parameter is set to D8-PV Cooling. It is most often used in combination with photovoltaic systems.
The user control setting with parameters D8-PV Increase 1, 2, 3 ... enables the parameters
listed below to raise various operating modes and with it to change the temperature of the mode:
a) Increase 1: Comfort mode for the buffer tank. b) Increase 2: Comfort mode for the DHW. c) Increase 3: Comfort mode for the circuits. d) Increase 4: Comfort mode for the buffer tank and circuits. e) Increase 5: Comfort mode for the DHW and circuits. f) Increase 6: Comfort mode for the buffer tank and DHW. g) Increase 7: Comfort mode for the buffer tank, DHW and circuits.
Standby…………………………….. Heating……………………..35.5°C Return 32.3°C DHW 49.0°C
DHW OFF T outside 10 °C HT60 OFF
2017/03/03 13:45 Mon
DHW OFF T outside 10 °C HT60 OFF 2017/03/03 13:45 Mon
Page 42
42
6.2018
5.12 Silent operation mode
Devices of the WPLV type enable two additional operation modes set in the menu Mode with the parameter Silent mode: The setting NRM switches the mode of operation into normal heating or cooling mode. The setting LOW lowers the parameters of power and noise of the device in the heating or cooling mode. The time and day of operation for these two parameters can be adjusted in a similar manner as the schedule. The lowered frequency of operation of the device means that the compressor and ventilators will operate with a lower power and consequently the operation of the device will be less noisy and its heating capacity will be correspondingly lower.
1.
In the menu Mode use the key to choose the parameter Silent mode. When the symbols > < appear next to the parameter
Silent mode, press the key (ENTER).
2.
The day blinks which the schedule refers to. Choose the day you would like to set the
schedule by using keys or . When you choose the day press the key (ENTER).
For a similar editing mode with steps see chapter
5.4.
Temp. mode 12°C H/T all 0°C DI8 >Silent mode
<
MO N
Co py
DE LE TE
00 :0 0 NR M -- : - - N RM
-- :- - NR M - - :- - N RM
-- :- - NR M - - :- - N RM
Page 43
6.2018
43
6 User menus and parameters
NOTE
The display of the TERMOTRONIC controller interface shows only those menus dependent on the type of device and were actually activated during the start-up of the device.
6.1 Menu structure
Main
menu
Parameter name
Adjustable
value
Scope [°C]
Parameter description
HEATING
C/W I
I
By setting this parameter, we can raise/lower
the temperature for up to 4 temperature steps. Example: I>> means that the currently set temperature of the circuit (the setting in the parameter Normal) is raised for 2
temperature steps. Schedule For settings, see chapter 5.4. Normal
19.9
19.9…max. The desired temperature of heating in the Normal mode of operation.
Eco
-
2.0
-10.0…0.0 Lowering the desired temperature in the Eco mode of operation.
Comfort
2.0
0.0…10.0 Raising the desired temperature in the Comfort mode of operation.
Standby
3.0
0.0… 10.0 By setting this parameter, we change the desired temperature of the restarted device with the parameter Standby from 0,0 °C to 10,0 °C. Example: The parameter Normal is 50,0 °C. The device will be in standby from 47,0 °C to 50,0 °C.
Const. temperature
Heating with constant temperature “Const.
Temperature or optimised heating according to external temperature “Heating Curve” OG. MK.
Correction
5.0
0.0…15.0 The correction of the breaking point of the weather curve at outdoor temperature +15,0 °C.
COOLING
Parameter name
Adjustable
value
Scope [°C]
Parameter description
Schedule
For settings see chapter 5.4.
Normal
19.9
10.0…19.9 The desired temperature of cooling in the Normal mode of operation.
Eco
2.0
0.0…10.0 Raising the desired temperature in the Eco mode of operation.
Comfort
2.0
–10.0… 0.0 Lowering the desired temperature in the
Comfort mode of operation.
Standby
3.0
3.0… 10.0 By setting this parameter we change the desired temperature of the restarted device with the parameter Standby from 0,0 °C to 10,0 °C. Example: The parameter Cooling is set to 23,0 °C. The device will be in standby from 23,0 °C to 26,0 °C.
Page 44
44
6.2018
The parameters are adjusted only in case of active cooling.
T.out. min
30
0.0…55.0 Setting the external temperature above which the cooling will activate.
max
35
0.0…55.0 Setting the external temperature at which the cooling will deactivate.
The parameters are adjusted only in case of passive cooling.
Min.Diff.
2
0.0…10.0 The minimal difference between passive temperature and output temp. of source. The additional temperature sensor is installed on the primary side of the passive on the exit.
Checking TP
2400
With this parameter you optimise the
operation of the submersible pump because if the temperature difference of the input and output temp. of the groundwater are lower than Min.Dif, the submersible pump does not operate. The electronics will turn off the submersible pump for the time of Checking TP (10...3600 s) turn it on and check if there is a need for cooling.
for
300
T.out.min.
20
0.0…55.0 Setting the external temperature above which the passive cooling will activate.
max
30
0.0…55.0 Setting the external temperature at which the passive cooling will deactivate.
1. CIRCUIT/
2. CIRCUIT/
3. CIRCUIT/
4. CIRCUIT
Parameter name
Adjustable
value
Scope [°C]
Parameter description
Displayed menus in the heating mode
C/W
I
By setting this parameter we lower the
temperature for up to 4 °C or raise it for up to 4 °C. Example: I>> means that the currently set temperature of the circuit (the setting in the parameter Normal) is raised for 2 °C.
Schedule For settings see chapter 5.4. Normal
19.9
19.9…max. By setting this parameter we change the desired temperature in the Normal operating mode of the HP.
Eco
2.0
–10.0… 0.0 By setting this parameter we change the
desired temperature in the ECO operating mode of the HP.
Comfort
2.0
0.0…10.0 By setting this parameter we change the desired temperature in the Comfort operating mode of the HP.
Hysteresis
2.0
1.0… 10.0 By setting this parameter we change the Hysteresis parameter of the mixing valve from 1,0 °C to 10,0 °C. Example: The parameter Hysteresis is 30,0 °C. The mixing valve will be in standby from 28,0 °C to 32,0 °C.
Const.
temperature
Heating with constant temperature Const.
Temperature or optimised heating according to external temperature Heating Curve.
Correction
5.0
0.0…15.0 The correction of the breaking point of the weather curve at outdoor temperature +15,0 °C.
In space
22.0
17.0… 27.0 Desired room temperature which can be set from 17,0 to 27,0 °C.
Stan.space
0.5
0.0…2.0 Standby with regulation of the room temperature.
Displayed menus in the cooling mode
Schedule
For settings see chapter 5.4.
Page 45
6.2018
45
Normal
19.9
19.9…max. By setting this parameter we change the desired temperature in the Normal operating mode of the HP.
Eco
2.0
–10.0… 0.0 By setting this parameter we change the
desired temperature in the ECO operating mode of the HP.
Comfort
2.0
0.0…10.0 By setting this parameter we change the desired temperature in the Comfort operating mode of the HP.
Hysteresis
2.0
1.0… 10.0 By setting this parameter we change the Hysteresis parameter of the mixing valve from 1,0 °C to 10,0 °C. Example: The parameter HNormal is 30,0 °C. The mixing valve will be in standby from 18,0 °C to 22,0 °C.
In space
22.0
17.0… 27.0
Desired room temperature which can be set from 17 to 27 °C.
Stan.space
0.5
0.0…2.0
Standby with regulation of the room temperature.
DHW
Parameter name
Adjustable
value
Scope [°C]
Parameter description
DHW
OFF
25.0…55.0 By changing the parameter OFF to the selected temperature i.e. of 40,0 °C you turn on the DHW.
Hysteresis
7.0
3.0…10.0 By setting this parameter we change the desired temperature Hysteresis of the device which means again turning on the heating of DHW in the DHW. Example: The parameter Hysteresis is 7,0 °C. The water temperature in the DHW falls from 40,0 °C to 33,0 °C and heating of the DHW turns on again.
Schedule For settings see chapter 5.4. Circulation Sched. By setting this parameter we enable the
circulation of the water. See chapter 5.4 for settings, the settings are similar to the ones for the schedule.
TD
60
The heating temperature for preventing the
development of legionella.
TD every
OFF
By changing the parameter OFF to 1...99
days we turn on the thermal disinfection of water performed every 1...99 days.
Start at
0:00
Setting the start of thermal disinfection (from
00:00 to 21:59). If the electrical heater is integrated we recommend the use of this function during the night so as not to interfere with the heating.
Maximum
2
Maximal allowed time of DHW heating [1…4
hours]. In case of an internal flow electric heater the max. time is 12 h, in case of a heater installed in the DHW, the heating can continue simultaneously.
Eco
-
2.0
-10.0…0.0 By setting this parameter we change the desired temperature in the ECO operating mode of the HP.
Comfort
2.0
0.0…10.0 By setting this parameter we change the desired temperature in the Comfort operating mode of the HP.
Alarm under
30,0
25,0… 50,0 Set an alarm for minimum temperature of
water in DHW. The controller reports failure if the temperature od DHW does not reach the
Page 46
46
6.2018
set temperature under
Alarm under
three
times in a row.
Max ope.
600
0… 999 The maximum heating time of DHW
Time sta.
30
0… 999 The standby of DHW heating
POOL
Setting the parameters of swimming pool heating. Display and configuration options if swimming pool heating is active (an expansion module is necessary).
Parameter name
Adjustable
value
Scope [°C]
Parameter description
Schedule For settings see chapter 5.4. Normal
OFF
19.9…max. By setting this parameter we change the
desired temperature in the Normal operating mode of the HP.
Eco
2.0
–10.0… 0.0 By setting this parameter we change the
desired temperature in the ECO operating mode of the HP.
Comfort
2.0
0.0…10.0 By setting this parameter we change the desired temperature in the Comfort operating mode of the HP.
Hysteresis
3.0
0.1… 1000 By setting this parameter you change the desired temperature Hysteresis of the device. Example: The parameter Normal is 50,0 °C. The device will be in standby from 47,0 °C to 50,0 °C.
Minimum
30
30… 1999 In case a need arises for heating the DHW
which has always priority to Pool Heating,it will begin after the elapsed time of the delay set in the parameter Minimum In our case this is after 30 minutes.
HP SET
45.0
20.0…60.0 Setting the maximum temperature of the return by heating with device.
Hysteresis
4.0
1.0… -10.0 Temperature difference of standby.
ALTERNATIVE
SOURCE
Setting heating and DHW support with the alternative source (solar collectors, solid fuel DHW ...). Display and configuration options if the alternative source is active (an expansion module is necessary).
Parameter name
Adjustable
value
Scope [°C]
Parameter description
---
Heating
---
Setting heating support. Additional sensor in
the buffer tank.
Set. Temp.
60.0
20.0…80.0 Setting the desired temperature in the buffer tank.
Dif. Temp.
15.0
7.0…20.0 Min. difference between the temp. of the buffer tank and temp. of the alternative source to turn on the HP-AOG of the alternative source.
Max. Temp.
80.0
60.0…90.0 Max. allowed temperature in the buffer tank up to which heating will be performed if the alternative source will have a high enough temperature.
Min. temp.
40.0
20.0…70.0 The minimal temperature alternative source up to which the alternative source will heat the buffer tank.
---
Water heater
---
Settings for heating support for DHW. The
DHW sensor is used (basic module).
Set. Temp.
60.0
20.0…80.0 Setting the desired temperature in the DHW.
Dif. Temp.
15.0
7.0…20.0 Min. difference between the temp. of the DHW and temp. of the alternative source to turn on the HP-AOG of the alternative source.
Max. Temp.
70.0
60.0…90.0 Max. allowed temperature in the buffer tank up to which heating will be performed if the alternative source will have a high enough temperature.
Page 47
6.2018
47
Min. Temp.
40.0
20.0…70.0 The minimal temperature up to which the alternative source will heat the DHW.
---
Common
---
Prior. DWH
YES
By choosing the parameter YES heating of
the DHW will begin first, followed by heating.
Cooling
100.0
100.0…120.0 Temp. of the alternative source above which cooling is performed.
Cooled for
5.0
1.0…5.0 By how many °C to cool the backup source.
Dif. Min.
5.0
0.0…15.0 The min. difference between the temperature of the alternative source and the temp. of the buffer tank or temp. of the DHW for heating to continue.
Protection
100.0
100.0…130.0 Setting the temperature for activating the signal which the users lowering the temperature of the alternative source can be connected to.
DHW from alternat.
ALT
Heating the DHW directly from the alternative
source or the buffer tank [ALT,CON].
ADDITIONAL
SOURCE
Parameter name
Adjustable
value
Scope
Parameter description
Switch to
Need
Mode of turning on the alternative source
[Never, Need or constant].
Bi-point
7.0
-30.0…40.0 Bivalent point. Set outside temperature at which the additional source is activated.
Delay
30
0… 300 [0…180] Start-up delay for the additional
source despite reached bivalent point.
Mode
PARALLEL
[PARALLEL, ALTERNATIVE] Mode of
additional source operation.
Raise for
5.0
0.0…20.0 Raising the heating temperature with auxiliary operation.
AddSourceOnly
NO
By changing the parameter from NO to YES
you can turn on the operation of the backup source (flow el. Heater) in case of a malfunction of the cooling part of the device.
DHW
45.0
10.0…50 Turn on/off and temperature settings of DHW heating with the backup source.
AntiFreeze
25
10.0…60.0 The antifreeze programme maintains the temperature in the system using the backup source in case of a malfunction of the device. This is not true for the TZ malfunction (this temperature is adjustable).
Remote switch
OFF
Turning on the additional source with remote
turn-off.
-Prot.w.AddSource- Protection the heating system with a backup source.
AS-on under
18.0
10.0…50.0 Turning on the additional source under x °C of the return.
AS-off abov
20.0
10.0…50.0 Turning off the additional source above x °C of the return.
Delay
300
0… 999 Delay of the turning on of the supply pipe.
Immt. under
10.0
25.0… 60.0 Direct turn on of additional source under this temperature.
Hys.DHW2
5.0
1.0… 10.0 Temperature difference of standby.
Immt. under
10.0
-20.0… 0.0 Direct activation of additional source under this temperature.
AS at DHW NO Outside the compressor operating range, a
flow electric heater is activated to achieve higher DHW temperatures.
MODE
Parameter name
Adjustable
value
Scope
Parameter description
Mode
Winter
Changing the operating mode [Summer,
AUTO, Winter]. For a detailed explanation see chapter 4.4.
Page 48
48
6.2018
Screed drying
NO
Turning on the programme for Screed drying
[YES, NO].
Initial
20.0
10.0…50.0 Changing the initial temperature.
Maximum
30.0
10.0…50.0 Setting the highest temperature up to which the screeds can be heated.
Step
24
10.0… 100.0 Setting the operating hours for the step [10…24] h
Duration
264
10.0… 10000 Maintaining the maximum temperature reached [100…264..1000h].
Final
20.0
10.0…50.0 End temperature.
1. Circ.
Thermostat
Choosing the regulation for 1. Circuit, turned on via the set value of the thermostat [Thermostat], the spatial corrector [KT-1/KT- 2] or constantly on [ON] or off [OFF].
2. Circ.
Thermostat
Choosing the regulation for 2. Circuit, turned
on via the set value of the thermostat [Thermostat], the spatial corrector [KT-1/KT- 2] or constantly on [ON] or off [OFF].
3. Circ.
Thermostat
Choosing the regulation for 3. Circuit, turned
on via the set value of the thermostat [Thermostat], the spatial corrector [KT-1/KT- 2] or constantly on [ON] or off [OFF].
4. Circ.
Thermostat
Choosing the regulation for 4. Circuit, turned
on via the set value of the thermostat [Thermostat], the spatial corrector [KT-1/KT- 2] or constantly on [ON] or off [OFF].
Reduced
NO
I case the change of the parameter to YES
the device will operate in a lowered ECO mode during heating/cooling.
Operation
AUTO
The change of the mode for the whole system
[AUTO, ECO, COMFORT].
Mode HP
ON
Turn on [ON], off [OFF] and [AUTO] modes
of setting the parameters. Only when choosing AUTO operation mode you can set the schedule for individual parameters. In case the parameters are set to ON the parameter will be turned on but you will be unable to change the schedule.
Mode DHW
AUTO
Mode 1. Circ.
AUTO
Mode 2. Circ.
AUTO
Mode 3. Circ.
AUTO
Mode 4. Circ.
AUTO
Mode Temp.
12
0.0… 30.0 The temperature at which the mode changes 3x in a row in case of the AUTO mode at 21:00
C/W ALL
I
The correction of the current desired
temperature of the device and all circuits in the step towards + or -.
D8-PV
Rise 1
The buffer tank will switch to the Comfort
mode upon the signal from outside. You can find the descriptions of the set value in chapter 5.11.
Silent mode
Applies only for type of WPLV device. For
settings, see chapter 5.4..
Language
EN
This parameter sets the desired controller
language.
Model:
It affects the correct display on the web interface Home Cloud. In case of installing the external unit WPLV 09, set the parameter Model to 124. In case of installing the external unit WPLV 14, set the parameter Model to 125. In other devices, the model does not have to
be changed.
Temperatures
Parameter name
Adjustable
value
Scope
Parameter description
Return
28.0°C
The current temperatures of individual sensors are shown. The number of sensors depends on your heating system.
Flow
36.1°C
DHW
48.0°C
Page 49
6.2018
49
Compressor/ T outlet
11.5°C
Evaporator / T inlet
16.5°C
T outside
5.0°C
2. Circuit
27.0°C
3. Circuit
29.0°C
4. Circuit
27.0°C
Pool
33.0°C
Passive
18.5°C
Alt. Buff t.
45.2°C
Alt. Source
16.7°C
Buff.tank2
28,0°C
7 Registration of the heat pump into the cloud (WEB)
See Instructions for Connecting the Web Module. See Instructions for Using the Web Interface.
NOTE
The service of remote control of the heat pump and heating system Cloud.KRONOTERM.com is in its test phase and is completely free. The information are of exclusively informative nature and the company Kronoterm d.o.o. does not guarantee their accuracy. Kronoterm d.o.o. is also not liable for malfunctions of the system as well as the potential damage to the customer making decisions based on this information.
NOTE
Kronoterm d.o.o. is also not liable for inability of use, disruptions or malfunctions of the web service Cloud.KRONOTERM.com. The service will be available for all until the company Kronoterm d.o.o. provides it.
NOTE
In the case where Kronoterm d.o.o. for any reason temporarily or permanently can no longer provide the service, the users cannot file any claims arising from this service in relationship with the company Kronoterm d.o.o. for setting up another equivalent service. The supplier of the service reserves the right to upgrade the software or make certain adjustments and settings key for correct and effective operation of the device through the service Home Cloud without prior notice of the user.
Page 50
50
6.2018
8 Information display of operation
The controller interface TERMOTRONIC displays information about the device on its main display at any time. The information needed by the user is described in Line 1 and Line 2. The information needed by the installer is displayed in the DIAGNOSTICS DISPLAY described in chapter 8.1.
NOTE
Depending on the type of installed device, the TERMOTRONIC controller display shows various conditions of the device.
The following information is displayed in Line 1:
Line 1 Description
HP STOP.............
The operation of the device is shut down (including circuit control).
ERROR **NO WATER*
There was a switch of the heat source pump or shortage of water for the heat source
HpDHW
Alarm; the pressure in the cooling system was too high during heating DHW.
HpHeat
Alarm; the pressure in the cooling system was too high during heating.
.
HpCool
Alarm; the pressure in the cooling system was too high during cooling.
LpDHW
Alarm; the pressure in the cooling system was too low during heating DHW.
LpHea
Alarm; the pressure in the cooling system was too low during heating.
LpCol
Alarm; the pressure in the cooling system was too low during cooling.
Tz
Alarm; there was overvoltage, under voltage or inverted phase sequence in the electrical grid.
DHW.................
The device heats DHW.
Screed drying.......
The programme for drying screeds is activated.
Heating.............
The device operates in the heating mode (only in winter mode).
Cooling.............
The device operates in the cooling mode (only in summer mode).
DHW + Add.source
The device (HP – compressor) operates simultaneously with additional heat source (the compressor and additional source simultaneously). Switching on the additional source is described in the section 4.6.
ScreedDry+Add.source
Heating + DHW
The device operates in the heating mode parallel to the electric heater which is installed into the DHW for heating DHW.
Heating + Add.source
The device (HP – compressor) operates simultaneously with additional heat source (the compressor and additional source simultaneously). Switching on the additional source is described in the section 4.6.
Cooling + DHW
The device operates in the cooling mode parallel to heating of DHW.
SwimmingPoolHeating
The device operates in the swimming pool heating mode.
Heating
-
Res.source..
Line 1 Line 2 Return 32.3°C DHW 49.0°C
Page 51
6.2018
51
DHW-Res.source......
Heating is performed only by selected (internal or external) additional heat source, compressor is not working. Additional heat source is switched on manually.
Standby.............
The device is in standby mode because there is no need for heating/cooling or it is in protection mode.
--REMOTE--SHUT­OFF--
Remote deactivation (external signal) of the device is active.
Heating
- Biv.Alt.
Selected (internal or external) additional heat source is working in bivalent alternative mode. Additional heat source is active and compressor is idle because ambient temperature is below bivalent point. Switching on the additional source is described in the section 4.6.
DHW - Biv.Alt.
----Overheating-----
The device operates in the thermal disinfection mode.
DEFROST
The device is in the evaporator defrost mode (only WPL/WPLV).
-Comp.temp too high-
Too high compressor temperature.
---
? Efficiency ?
---
The device does not heat (does not generate enough heat).
Defrost T.Flow ALARM
Alarm; the water temperature of the return during defrost was too low.
------
Max dT
------
The temperature difference between the supply and return is too high.
ERROR
HeatSourceTemp
Source temperature is outside the operating range.
--MODULE 3
- ALARM
-
-
Malfunction of one of the modules. The device will restart automatically after the error is resolved.
--MODULE 4
- ALARM
-
-
--MODULE 2
- ALARM
-
-
--MODULE 1
- ALARM
-
-
-- RESET MODUL 1
---
One of the modules is in the self-reset process.
-- RESET MODUL 2
---
-- RESET MODUL 3
---
-- RESET MODUL 4
---
Caution flow :
The flow switch is not closed – there is no or not enough water flow through the device. If there is no or not enough water flow through device in 120 s, the device goes into compressor protection mode (Standby). When protection mode elapses, it tries to start again.
ERROR ..
Sensor...... 1
Alarm; one of the sensors is not connected or is damaged.
ERROR ..Sensor...... 2
ERROR ..Sensor...... 3
ERROR ..Sensor...... 4
ERROR ..Sensor...... 5
ERROR ..Sensor...... 6
ERROR ..Sensor...... 7
ERROR ..Sensor...... 8
ERROR ..Sensor...... 9
ERROR ..Sensor...... 10
ERROR ..Sensor...... 11
ERROR ..Sensor...... 12
ERROR ..Sensor...... 13
ERROR ..Sensor...... 15
Page 52
52
6.2018
--- ALARM DHW ----
The device was unable to heat the water higher than the min. set value for 3 times.
ERROR Cascade:
The warning is shown if an individual device does not respond 3 x during cascade regulation verification.
-> Checking :
The device is verifying the temperature of return.
ERROR..Thermostat...
1
One of the room correctors is not connected properly or is malfunctioning.
ERROR..Thermostat...
2
ERROR..Thermostat...
3
ERROR..Thermostat...
4
-- ALARM RTC-FAIL --
There is an error on the PLC frequency oscillator.
-- Max. ODT. / h --
The maximal limit of defrosting per hour is reached.
--
MODULE 5
- ALARM
--
Malfunction of one of the modules. The device will restart automatically after the error is resolved.
--MODULE 6 - ALARM--
ERROR ..Sensor...... 14
One of the sensors is not connected or is damaged.
Carel EEV error
The Carel controller is malfunctioning.
Carel probe 1 error
One of the probes is not connected or is damaged.
Carel probe 2 error
Carel probe 3 error
Carel probe 4 error
--MODULE INV ALARM-
No connection with the external device
INV Error xx
Number of external device error.
-- Low Comp.temp --
The compressor temperature is too low. After three indications, the PZ PROG is activated.
-- Low Cond.temp -
The plate heat exchanger temperature is too low. After three indications, the PZ PROG is activated.
The following information is displayed in Line 2:
Line 2 Description
Cooling [OFF / 22.0°C] The device is operating in the cooling mode; set point of cooling
water is written right.
Heating [OFF / 45,0°C] The device is operating in the heating mode; set point of heating
water is written right.
Heating FP PROG The device is operating in the anti-freeze programme (back-up
operation) which is activated in case of alarm on the device. The device maintains the temperature set with the parameter
Antifreeze.
Passive Cooling The device operates in the passive cooling mode.
Page 53
6.2018
53
8.1 Diagnostic displays
Other important information about the device for the installer and are not shown in Line 1 and Line 2 are shown in INFORMATION LINE 1 and INFORMATION LINE 2 in DIAGNOSTIC DISPLAY.
To see the current status or malfunction of the device, follow these steps:
1.
For accessing diagnostics on the basic display press key until the display on the left is displayed. Press the key (ENTER) to enter the menu SERVICE DISPLAY.
Depending on the current operation upon entry the display shows you various parameters.
2.
Com: Delayed start-up of compressor. BDV: Blockage of the supply pipe. AT: Timer after alarm. In the case of an alarm it
is not possible to reset the system 2x in this time.
AI5: Timer after detected too low or too high
external temperature. In this case the HP operates in the FP_PROG mode (max. Operation time of the programme is 60 min9 until the external temperature is within acceptable limits. Info. line 1: Display of blockages (here all possible blockages are displayed for protection the HP listed in the table below). Info. line 2: Display of warnings (here light alarms of the HP listed in the table below).
INFORMATION LINE1 Description
CompProtection
Compressor start delay.
Comp. start in
Blockage of the compressor - protection against too frequent turns on.
INFORMATION LINE 2 Description
Estrih timer :
The screed drying mode is activated, the timer shows the time of the program’s operation.
CAUTION.....Min Flow
The supply pipe has fallen below the minimal value set with the parameter Min Supp. Line. The device will turn on when the sum of the parameters set in the parameter Min Supp. Line and the parameter Standby elapse.
WARNING source inlet
Warning/protection of minimal inlet water temperature.
DHW C.Pump
After heating DHW the device switches to forced heating for the set time.
Temp.check Ret
The main circulation pump is activated, it checks the temperature of the return.
Caution ! Flow!....
The flow switch is not connected, there is no flow, depending on the set time in various types of device (DHW or WW) the submersible pump turns off and switches to compressor protection.
Start DEF.in
Countdown of the delay until the start of defrosting; 300 s adjustable.
--? HEAT.Cascade ?--
Cascade in the heating mode did not get conformation of the external/internal device.
--? DHW Cascade ?--
Cascade in the DHW heating mode did not get conformation of the external/internal device.
- DIAGNOSTIC - DISPLAY -
I IN I
I IN I
-------------------- IN -------------------
Com: 0s
AT:0s
BDV: 0s
AI5:0'
Information line 1 Information line 2
Page 54
54
6.2018
-
Shut
-
off Cascade
-
Cascade turn off sequence.
Fault Flow Switch
After the elapsed time of checking the operation of the circulation switch the device displays an error.
..Shutdown at.
Minimal time of compressor operation. After this time in case the conditions for the shut down are met, it is enabled.
9 Disruptions in operation, alarms and troubleshooting
After instalment and successful commissioning the device is ready for regular operation. The operation of the device is protected by multiple protection mechanisms:
High pressure switch: in case operating pressure is too high. Low pressure switch: in case of too-low operating pressure. Flow switch: for protection flow loss. Temperature sensors: for protection the temperature of the return, supply pipe, compressor
and evaporator.
Safety thermostat: for protection the built-in electric heater. Phase controller and under- and over-voltage protection: for protection the correct
sequence of electric phases and appropriate electric voltage.
In case of disruptions in the operation first check whether the display displays an error message. Find the description of the malfunction in the table below and try to resolve it in accordance with the instructions in chapter 9.2. In case you cannot resolve the malfunction alone or you are prohibited from doing so, act in accordance with the instructions 1., 2., and 3., to resolve the malfunction listed in the warranty. Contact the installer who installed your device to resolve the malfunction. In case the malfunction cannot be resolved, he will contact the customer service of the manufacturer who will resolve the malfunction.
NOTE
In case of a malfunction the display displays a red alarm light (ALARM).
9.1 Errors and alarms in normal operation mode
Prikaz alarmov ERROR **NO WATER* HpDHW HpHeat HpCool LpDHW LpHea LpCol Tz
-Comp.temp too high-
---? Efficiency ?--­ Defrost T.Flow ALARM
------ Max dT -----­ ERROR HeatSourceTemp
--MODULE - ALARM--
-- RESET MODUL ---
ERROR ..Sensor...... 4
--- ALARM DHW ---­ERROR Cascade: ERROR..Thermostat...
Page 55
6.2018
55
-- ALARM RTC-FAIL --
-- Max. ODT. / h -­ Carel EEV error Carel probe error INV Error
DHW-Res.source......
Heating-Res.source.. FP PROG (2. line)
------ Max dT ------
-- Low Comp.temp --
-- Low Cond.temp -
After fixing the cause for the error you have to restart the device with the key (ENTER)
- hold it for 3 seconds. After the startup sequence elapses the device will start operating.
Page 56
56
6.2018
9.2 Troubleshooting
Resolve the errors using the procedure for resolving errors. The column Check, resolve the error prescribes how to resolve the error.
NOTE
In case you cannot resolve the malfunction alone or you are prohibited from doing so, act in accordance with the instructions 1., 2., and 3., to resolve the malfunction listed in the warranty.
9.2.1 Air-water device type
Error
Description of error
Reason for the error
Procedure to resolve the error
Check,
resolve the error
HpHeat
Exceeded pressure in the cooling system in heating mode.
Insufficient water flow
through the condenser.
1. Check the heating system if the circulation pump is working or if all valves and flaps are correctly opened/closed,
2. cleans the strainer if it is blocked
3. fill out the system (min.
1.5–2 bar),
4. vent the system.
The user
HpDHW.
Exceeded pressure in the cooling system in heating DHW.
Insufficient water flow
through the condenser.
1. Check the heating system if the circulation pump is working or if all valves and flaps are correctly opened/closed,
The user
2. cleans the strainer if it is blocked
3. fill out the system (min.
1.5–2 bar),
4. vent the system.
HpCool.
Exceeded pressure in the cooling system in cooling mode.
Insufficient air flow
through the condenser.
1. Check the operation of the fan on the heat pump,
2. enable unobstructed flow through the condenser,
The user
3. clean the blades of the condenser.
Installer
Insufficient water flow
through the condenser.
1. Check the heating system if the circulation pump is working or if all valves and flaps are correctly opened/closed,
The user
2. enable unobstructed flow through the condenser,
3. clean the blades of the condenser.
Installer
Page 57
6.2018
57
Error
Description of error
Reason for the error
Procedure to resolve the error
Check,
resolve the error
LpHeat.
Low pressure in the cooling system in heating mode.
Insufficient air flow
through the evaporator.
Frozen blades of the
evaporator and basin.
1. Check the operation of the
fan on the heat pump,
The user
2. enable unobstructed air
flow through the evaporator.
3. check the condenser drain
4. Activate manual defrost
but no more than two times.
Installer
5. check the heating cable
operation.
Insufficient water flow
through the evaporator.
Water-water:
1. Check the heat source
whether the heat pump is operational, whether all valves or flaps are correctly opened/closed, whether there is enough ground water,
The user
2. clean the strainer. Earth-water:
1. Check the heat source whether the circulation pump is operational, whether all valves or flaps are correctly opened/closed, whether there is enough antifreeze in the heat source,
The user
2. clean the strainer.
LpDHW
Low pressure in the cooling system in heating DHW.
Insufficient air flow
through the evaporator.
Frozen blades of the
evaporator and basin.
1. check the condenser drain The user
2. Activate manual defrost
but no more than two times.
3. check the heating cable operation.
Installer
Insufficient water flow
through the evaporator.
Water-water:
1. Check the heat source whether the heat pump is operational, whether all valves or flaps are correctly opened/closed, whether there is enough ground water,
The user
2. clean the strainer.
Earth-water:
1. Check the heat source whether the circulation pump is operational, whether all valves or flaps are correctly opened/closed, whether there is enough antifreeze in the heat source,
The user
2. clean the strainer.
LpCol.
Low pressure in the cooling system in cooling mode.
Insufficient water flow
through the evaporator.
1. Check the heating/cooling system if the circulation pump is working or if all valves and flaps are correctly opened/closed,
The user
2. cleans the strainer if it is blocked
Page 58
58
6.2018
3. fill out the system (min.
1.5–2 bar),
4. vent the system.
Tz
There was an error in the electrical supply.
Phase failure.
1. Check the presence of all phases and adequacy of voltage,
Installer
2. Change the phase
sequence - change the order of the phases.
Authorised maintenance worker
*NO WATER*
There is insufficient flow of medium (water) between HP and the heating system.
Insufficient water flow
through the condenser/evaporator.
1. Check the heating system
if the circulation pump is working or if all valves and flaps are correctly opened/closed,
The user
2. clean the strainer, The user
3. fill out the system (1.5–2
bar),
The user
4. vent the system. The user
SENSORS.
Error on one of the sensors.
Error in data acquisition.
1. Disconnect the device from the power source and reconnect it in 10 minutes.
The user
Max. dT
The temperature between the return and supply line is too high.
There was a disturbance
in the flow.
1. Check the heating system
if the circulation pump is working or if all valves and flaps are correctly opened/closed,
The user
2. clean the strainer, The user
3. fill out the system (1.5–2
bar)
The user
4. vent the system. The user
Defrost T.Flow ALARM
The HP does not have enough energy to defrost.
The water temperature
of the return during defrost was too low.
1. Heat the buffer tank with the backup source (at least to 20 °C),
The user
2. turn on the buffer tank heating together with the heat pump and backup source,
The user
3. gradually turns on the heat extractors from the buffer tank (1 circuit at a time).
The user
ALARM DHW
The HP could not heat the DHW above the minimal value.
Insufficient water flow
through the condenser.
The sensor is not in its
right place.
1. Check the heating system
if the circulation pump is working or if all valves and flaps are correctly opened/closed,
The user
2. clean the strainer, The user
3. fill out the system (1.5–2
bar),
The user
4. vent the system, The user
5. check if the sensor is in its designated place.
Installer
Page 59
6.2018
59
Error
Description of error
Reason for the error
Procedure to resolve the error
Check,
resolve the error
?Efficiency?
The HP does not function efficiently enough.
The device does not
reach a high enough temperature of the return.
Contact the authorised service.
Authorised maintenance worker
ALARM RTC­FAIL
There is an error on the frequency oscillator on the PLC.
The frequency oscillator
on the HP electronics is damaged.
1. A reset of the error is possible by pressing and holding ENTER for 3 seconds.
The user
2. In case the reset does not correct the error an authorised service must be contacted.
Authorised maintenance worker
--
-Comp.temp too high-
Too high compressor temperature.
Allowed max. compressor
temperature reached.
1. Reset the error.
2. Contact the authorised service.
Authorised maintenance worker
ERROR HeatSourceTe mp
Source temperature is outside the operating range.
Source temperature is
outside the operating range.
1. Check the heating system if the circulation pump is working or if all valves and flaps are correctly opened/closed,
2. clean the strainer.
The user
3. Contact the authorised service.
Authorised maintenance worker
---MODUL ­ALARM--
Malfunction of one of the modules.
Communication error. Module malfunction.
1. Contact the authorised service.
Authorised maintenance worker
- RESET MODUL -
The module is in the self­reset process.
Electromagnetic
interference.
Voltage fluctuation.
1. Contact the authorised service.
Authorised maintenance worker
ERROR Cascade:
The module MD1 did not respond 3 x to module MD4.
Communication error. The device does not have
a guaranteed constant power.
1. Contact the authorised service.
Authorised maintenance worker
ERROR Thermostat
Faulty connection or malfunction of the room corrector.
Error in data acquisition. Thermostat malfunction.
1. Check whether the thermostat is working.
2. Check the regulator settings.
The user
Installer
-- Max. ODT. / h --
The maximal limit of defrosting per hour is reached.
1. Contact the authorised service.
Authorised maintenance worker
Carel EEV error
The Carel controller is malfunctioning.
Error in data acquisition. Controller malfunction.
1. Contact the authorised service.
Authorised maintenance worker
Carel probe error
Faulty connection or malfunction of the probe.
Error in data acquisition. Probe error.
1. Contact the authorised service.
Authorised maintenance worker
INV Error
External device error.
Error in data acquisition. External device error.
1. Reset the device. The user
2. Contact the authorised
service.
Authorised maintenance worker
-- Low Comp.temp --
Allowed min. compressor
temperature reached.
1. Reset the device. The user
2. Contact the authorised
service.
Authorised maintenance worker
-- Low Cond.temp -
The plate heat exchanger temperature is too low.
The plate heat exchanger
temperature reached min. allowed temperature.
1. Contact the authorised service.
Authorised maintenance worker
Page 60
60
6.2018
After successfully establishing the cause of the safety element shut down and resolving the error you can manually turn on the device again by holding the key (ENTER) for approx. 3 seconds. After the startup sequence elapses the device will start operating.
10 Device maintenance
For a long, reliable and economical device operation regular maintenance is essential. Instructions for maintenance of individual elements of the heating system and the device can be found in the installation manual.
NOTE
The Republic of Slovenia in accordance with regulations on the use of substances harmful to the ozone and fluorinated greenhouse gasses (Ur.l.RS, št.60/16) obliges the manager of the real estate (4th article) which contains > 3kg of gas to report the device to the environmental agency Agencija Republike Slovenije za okolje – ARSO (web page: http://okolje.arso.gov.si/REMIS_TGP/OLESVZ/R_Default.aspx) in three months after commissioning. The registration is free.
NOTE Devices in EU which contain fluorinated greenhouse gasses are regulated by the directive (EU) 517/2014, which among others also defines the rules for maintenance,
use, collecting and destroying fluorinated greenhouse gasses and similar accompanying measures which you must consider!
Page 61
6.2018
61
11 Settings of your heating system at start-up
In case you need help from the installer who performed the installation or an authorised service, record in the tables below:
Your designations of rooms you control with the parameters of the control interface
TERMOTRONIC.
The values of the parameters Normal and Correction which you have set for your heating
system.
The setting for the parameter (371) Buff.tank
The parameter in the heating mode
Type of circuit (circle it)
The set heating mode (circle it)
Conception of the circuits of the control interface TERMOTRONIC
Recommended set temperature
Your designations of rooms
Normal Correction Hysteresis
Weather control/ maintaining constant temperature
Heating
direct 1. Circuit
direct/mixing 2. Circuit
direct/mixing 3. Circuit
direct/mixing 4. Circuit
The parameter in the cooling mode:
Type of circuit (circle it)
Conception of the circuits of the control interface TERMOTRONIC
Recommended set temperature Your designations of
rooms
Normal Hysteresis
Cooling
direct 1. Circuit
direct/mixing 2. Circuit
direct/mixing 3. Circuit
direct/mixing 4. Circuit
Parameters for DHW:
Conception of the parameters of the control interface TERMOTRONIC
Recommended set temperature
Your designations of rooms
Normal Standby
DHW
Filled out by the authorised contractor for commissions:
Setting the parameter (371) Buff.tank at start-up (circle it)
Buff.const Buff.if needed
Designation of hydraulic wiring diagram (Catalogue of hydraulic wiring diagrams of the device manufacturer) according to which the wiring of the DHW room is implemented
Page 62
62
6.2018
Page 63
6.2018
63
Page 64
The headquarters of the company and place of production
Kronoterm d.o.o. Trnava 5e 3303 Gomilsko
Tel.: (00386) 3 703 16 20 | Fax: (00386) 3 703 16 33 | Web-page: www.kronoterm.com | E-mail: info@kronoterm.com
Loading...