Please read through these instructions
carefully before installing or operating. Following the
installation, pass the instructions on to the operator. This unit must be installed and commissioned
in accordance with the regulations and standards
in force. These instructions can also be found at
www.docuthek.com.
Explanation of symbols
• , , , ... = Action
▷ = Instruction
Liability
We will not be held liable for damage resulting from
non-observance of the instructions and non-compliant use.
Safety instructions
Information that is relevant for safety is indicated in
the instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified
gas technicians. Electrical interventions may only be
carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM
spare parts.
Changes to edition 0.5
The following chapters have been changed:
– Installation
– Connection diagram
– Commissioning
– Assistance in the event of malfunction
– Certification
GB-1
GB
F
NL
I
E
Checking the usage
Burner control unit BCU570 is designed to monitor and control modulating forced draught burners
of unlimited capacity in intermittent or continuous
operation.
The fail-safe outputs for controlling the burners, e.g.
for fan, actuator and valves, are activated via a replaceable power module. All the parameters required
for operation are saved on the integrated parameter
chip card.
Type code
CodeDescription
BCUBurner control unit
570Series 570
Q
W
C0
C1
F1
F2
RBW interface or frequency converter
U0
K0
K1
K2
Part designations
No valve proving system
With valve proving system
Modulating capacity control:
three-point step, IC 20 and IC 40
in case of operation with gas
Mains voltage:
120 V AC, 50/60 Hz
230 V AC, 50/60 Hz
Ionization or UV control
Connection terminals:
none
screw terminals
spring force terminals
Input voltage– see type label.
BCU
1
2
3
4
5
6
7
LED display for program status and fault
messages
Reset/Information button
On/Off button
4 Type label
5 Connection for opto-adapter
6 Power module, replaceable
7 Power module type label
8 Parameter chip card, replaceable
8
GB-2
GB
F
NL
I
E
Installation
1
45
CAUTION
Please observe the following to ensure that the
burner control unit is not damaged:
– Dropping the device can cause permanent dam-
age. In this event, replace the entire device and
associated modules before use.
▷
Installation position: vertically upright, horizontal
or tilted to the left or right.
▷ The BCU mounting is designed for horizontally
aligned 35×7.5mm DINrails.
▷
If the DINrail is aligned vertically, end clamps are
required (e.g. Clipfix35 by Phoenix Contact) to
prevent the BCU from slipping.
Replacing the power module/
parameter chip card
Disconnect the system from the electrical power
supply.
2
Disengage the BCU from the DINrail.
▷
Install in a clean environment (e.g. a control
cabinet) with an enclosure ≥IP54, whereby no
condensation is permitted.
6 Remove the old parameter chip card from the
BCU and insert the new one.
▷ All the parameter settings of the BCU are saved
on the parameter chip card.
7 Slide the power module back on.
8 Reconnect the connection terminals.
9 Mount the BCU on the DINrail again.
GB-3
GB
F
NL
I
E
Cable selection
▷ Signal and control line for screw terminals max.
2.5mm2 (min.AWG24, max.AWG12), for spring
force terminals max. 1.5mm2 (min.AWG24,
max.AWG12).
▷
Do not route BCU cables in the same cable
duct as frequency converter cables or cables
emitting strong fields.
▷
The control lines must be selected in accordance
with local/national regulations.
▷ Avoid external electrical interference.
Ionization cable, UVcable
▷ Cable lengths of 100m are acceptable if there
is no electromagnetic interference.
▷
The flame signal is adversely affected by EMCin-
fluences.
▷
Lay cables individually (with low capacitance)
and, if possible, not in a metal conduit.
Wiring
▷
Do not reverse phaseL1 and neutral conductorN.
▷
Do not connect different phases of a three-phase
current system to the inputs.
▷ Do not supply voltage to the outputs.▷
A short-circuit on the outputs causes one of the
replaceable fuses to trip.
▷ Do not set the remote reset so that it operates
(automatically) in cycles.
▷ Wire the safety circuit inputs via contacts (relay
contacts) only.
▷ The unit features an output for fan control (termi-
nal58). This single-pole contact can be loaded
with a max. of 3A. The max. start-up current of
the fan motor must not exceed a value of max.
6A for 1s– use an external motor protection
or coupling contactor if required.
▷
The limiters in the safety interlock (linking of all the
relevant safety control and switching equipment
for the use of the application, for example, safety
temperature limiter) must isolate terminal46 from
the voltage supply. If the safety interlock is interrupted, the display shows a blinking
a warning signal and all of the BCU’s control
outputs are disconnected from the electrical
power supply.
▷
Connected control elements must be equipped
with protective circuits in accordance with the
manufacturer’s instructions. The protective circuit
prevents high voltage peaks which can cause
malfunctioning of the BCU.
▷
Observe the maximum duty cycle for the ignition
transformer (see manufacturer’s instructions).
Adjust the minimum pause time tBP (parameter62) correspondingly, if required.
▷
Functions of terminals 51, 65, 66, 67 and 68 are
dependent on parameter values:
TerminalDependent on parameter
5169
6570
6671
6772
6873
See page19 (Parameters and values).
Disconnect the system from the electrical power
supply.
Before wiring the BCU, ensure that the yellow
parameter chip card has been inserted in the
BCU – see page 3 (Replacing the power
module/parameter chip card).
▷
Screw terminals or spring force terminals are
available for the BCU– see page23 (Accessories).
Wire as shown on the connection diagram– see
page5 (Connection diagram).
▷ Ensure a good PE (ground) wire connection to
the BCU and burners.
GB-4
50
as
GB
F
NL
I
E
Connection diagram
BCU 570
▷ Legend– see page21 (Legend).
3837
V4
V3
V2
V1
131415171811129312
5AT
90°0°
0°90°
M
53545556575849505152
3,15AT
P69
max.
PZH
Gas
min.
PZL
68
67
Gas
Air
PDZ
P72
4748
STL
Z
I
STM/
66
57
46
P71P73
Air
min.
PZL
65
45
P70
u
2
p
PZ
A
ϑ
L1
BCU 570
N
0,6 x I
N
GB-5
GB
F
NL
I
E
Flame control
V1
V2
V3
1314151718
3837
▷
In the case of UV control, use Elster UV sensors
for intermittent operation (UVS 1, 5, 6, 10) or
flame detectors for continuous operation (UVC 1).
Ionization/single-electrode operation:
▷ Parameter 04 = 0.
Z
57
UV control:
UVS 1, 5, 6, 10
▷ Parameter 01 ≥ 5 µA.▷ Parameter 04 = 1.
1
2
UVS
3
765
UVC 1
▷ Parameter 04 = 2.
L
N
PE
4
3
2
1
765
11129
Z
912
UVC 1
Z
9
GB-6
V1
V2
V3
GB
F
NL
I
E
IC 0 connected to BCU570..F
▷ Parameter 40 = 1.▷
Continuous control via three-point step controller.
7
3837
131415171811129
66
BCU 570
4748
67
0°
68
90°
S1
MinMax
5AT
3,15AT
3.15AT
S11
S1S2
0°➔90°
53545556575849505152
90°➔0°
0°➔90°
32116674812 111513
S3S4
M
90°➔0°
L1
N
PE
IC 20
PE
S10
GB-7
GB
F
NL
I
E
IC 0..E connected to BCU570..F
V1
V2
V3
▷ Parameter 40 = 1.▷
Continuous control via an analogue signal (directly connected to the control actuator).
7
3837
131415171811129
4748
66
BCU 570
67
mA
68
OUT
IN
20 19 18321674812 11
A
D
A
D
ON
123456
µC
0°
90°
++
R
131516
5AT
3,15AT
3.15AT
S2
S1
MinMax
90°➔0°
0°➔90°
53545556575849505152
L1
N
IC 20..E
R
S4
PE
0°
90°
➔
➔
OK
517
S1
0°
90°
PE
S10
R
S3
M
GB-8
V1
V2
V3
GB
F
NL
I
E
IC 40 connected to BCU570..F
▷ Parameter 40 = 2.▷ Set IC 40 to operating mode27, see operating
instructions Actuators IC 20, IC 40, IC 40S.
7
3837
131415171811129
66
BCU 570
4748
67
22 21 20
R..
5AT
3,15AT
3.15AT
90°➔0°
0°➔90°
53545556575849505152
68
mA
19 1816 15 1412 11 10875421
A
D
AC
DC
IC 40
M
PE
L
N
GB-9
GB
F
NL
I
E
RBW valve connected to BCU570..F
V1
V2
V3
V1
V2
V3
▷ Parameter 40 = 3.
Continuous control via three-point step
controller
57
3837
131415171811129
BCU 570
46
Continuous control via PLC
57
66
4748
67
68
BCU 570
0°➔90°
RBW
5AT
3,15AT
3.15AT
90°➔0°
5AT
COM
HI
AUTO
LO
53545556575849505152
R B W
M
L1
N
3837
131415171811129
46
4748
66
3,15AT
COM
HI
53545556575849505152
67
68
AUTO
LO
OUT
mA
+
A
D
PLC
+ F -
0°90°
RBW
M
L1
N
GB-10
GB
F
NL
I
E
Frequency converter connected to BCU570..F
V1
V2
V3
▷ Parameter 40 = 4.
57
BCU 570
5AT
3.15AT
3,15AT
3837
131415171811129
46
66
4748
67
68
PLC
mA
0–100%
Target = actual
M
COM
HI
AUTO
LO
53545556575849505152
P
DI 3DI 2DI 1
FC
PDZPZL
L1
GB-11
GB
F
NL
I
E
Adjustment
In certain cases, it may be necessary to change the
parameters set at the factory. Using the separate
software package BCSoft and a PC opto-adapter, it
is possible to modify parameters on the BCU, such
as the pre-purge time or the behaviour in the event
of a flame failure.
▷
The software package and the opto-adapter
are available as accessories– see page 23
(Accessories).
▷
Changed parameters are saved on the integrated
parameter chip card.
▷
The factory settings are secured with a program-
mable password.
If the password has been changed, the end cus-
▷
tomer can look up the changed password in the
plant documentation or ask the system supplier.
Commissioning
▷
During operation, the 7-segment display shows
the program status:
Start-up position/standby
00
Delay
H0
A Approaching minimum capacity
Fan OFF check
0
Fan run-up time
01
Approaching maximum capacity
A
Post-purge time air monitoring
1
Pre-purge
P1
Approaching ignition capacity
A
Valve check
Pre-ignition time tVZ
03
Safety time 1 t
04
Flame proving period 1t
05
Safety time 2 t
06
Flame proving period 2 t
07
Delay
H8
Operation/controller enable
08
Over-run tN with air actuator in position for
09
SA1
FS1
SA2
FS2
maximum capacity
Post-purge
P9
Controlled air flow
C1
Device Off
––
Remote control (with OCU)
U I
Data transfer (programming mode)
(blinking dots) Manual mode
0.0.
WARNING
Risk of explosion! Check the system for tightness
before commissioning.
Do not start the BCU until you are certain that the
wiring is correct, the parameters have been set
correctly and all input and output signals are being processed perfectly by means of conducting
a function check and reading the parameters on
the device.
Switch on the system.
▷ The display indicates
––
.
Switch on the BCU by pressing the On/Off but-
ton.
▷ The display indicates ▷
If the display blinks (fault), reset the BCU by
.
00
pressing the Reset/Information button.
Apply the start-up signal to terminal1.
▷
The display indicates A. The air control valve
moves to the position for minimum capacity.
▷
The display indicates
. The switch-on delay
H0
time (parameterP63) is active.
▷
The display indicates
. The fan run-up time
01
(parameterP30) is active.
▷ The display indicates
. The air control valve
A
moves to the position for maximum capacity.
The display indicates
▷
. The pre-purge time
P1
(parameterP34) is active.
▷
BCU..C1: the valve check runs in parallel to
pre-purge. If the valve check lasts longer than
pre-purge, the display indicates
▷
The display indicates
. The air control valve
A
moves to the position for ignition capacity.
▷ The display indicates 03,
ing a pilot and main burner,
and 05. When us-
04
and 07 are also
06
shown. Pre-ignition time, safety time and flame
proving period are running.
▷ The display indicates
. The controller enable
H8
signal delay time is running.
▷ The display indicates
. The burner is in opera-
08
tion and the controller enable signal has been
issued.
Manual mode
▷ For adjustment of the burner control unit or for
fault-finding.
▷
In Manual mode, the BCU operates independently of the status of the inputs for start-up
signal (terminal1), controlled air flow (terminal2)
and remote reset (terminal3). The function of the
controller enable/emergency stop input (terminal46) is retained.
▷ Manual mode is terminated by switching off the
BCU or in the event of a power failure.
▷
Parameter 67 = 0: Manual mode unlimited in
time. The burner control unit may continue to
be operated manually in the event of failure of
the control system or the bus.
▷ Parameter 67 = 1: The BCU will terminate Man-
ual mode 5minutes after the last time the Reset/
Information button is pressed. It switches to the
start-up position/standby (display
Switch on the BCU while holding the Reset/
Information button. Hold the Reset/Information
button until the two dots in the display start to
blink.
GB-12
.
).
00
GB
F
NL
I
E
▷ If the Reset/Information button is pressed, the
current step in Manual mode is shown. After
the button has been held for 1 second, the next
step will be shown. The BCU now executes its
program sequence until the display indicates
BCU 570..F with IC0
▷
Following controller enable (display
IC20 can be opened and closed as required.
Press the Reset/Information button.
▷
If the button continues to be held down, the
actuator opens further until it reaches the position for maximum capacity.
▷ The display indicates▷
Once the button has been released, the butterfly
valve stops in the relevant position.
Press the Reset/Information button again.
▷
If the button continues to be held down, the
actuator closes further until it reaches the position for minimum capacity.
▷ The display indicates▷ A change of direction takes place each time the
button is released and pressed again. When the
butterfly valve has reached its final position, the
dots disappear.
BCU 570..F with IC40, BCU570..F with
RBW or frequency converter
▷
Following controller enable (status display
it is possible to move between the positions for
maximum and minimum capacity on a binary
basis.
with blinking dots.
A.1.
with blinking dots.
A.0.
0.8.
08
), actuator
0.8.
Assistance in the event of
malfunction
DANGER
Electric shocks can be fatal! Before working on
possible live components, ensure the unit is disconnected from the power supply.
Fault-clearance must only be undertaken by authorized trained personnel.
▷ Faults may be cleared only using the measures
described below.
▷
If the BCU does not respond even though all
faults have been remedied: remove the unit and
return it to the manufacturer for inspection.
? Faults
! Cause
• Remedy
? The 7-segment display does not light up.
! Mains voltage is not applied.
• Check the wiring, apply mains voltage (see type
label).
0 1
? The display blinks and indicates
.
! The BCU has detected an incorrect flame signal
without the burner having been ignited (extraneous signal).
• Direct the UV sensor exactly at the burner to be
monitored.
! The UV tube in the UV sensor is defective (service
life ended) and issues a continuous flame signal.
• Exchange UV tube, OrderNo.: 04065304 – note
the Operating instructions for the UV sensor.
! Flame signal through conductive ceramic insula-
tion.
• Increase value of parameter01 in order to adapt
the switch-off threshold of the flame amplifier.
0 4
? Start-up without flame– no ignition spark–
the display blinks and indicates
! The ignition cable is too long.
• Shorten it to 1m (max.5m).
),
! Gap between spark electrode and burner head
is too great.
• Adjust gap to max. 2mm.
! Ignition cable has no contact in the terminal boot.
• Screw the cable on firmly.
! Ignition cable has no contact in the ignition trans-
former.
• Check the connection.
! Ignition cable has short-circuited to ground.
• Check installation, clean the spark electrode.
• If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer
for inspection.
? Start-up without flame– no gas supply – the
display blinks and indicates
! A gas valve does not open.
• Check the gas pressure.
• Check voltage supply to the gas valve.
! There is still air in the pipe, e.g. after installation
work has been carried out or if the system has
not been in operation for a long period.
• “Purge” the pipeline and reset the BCU.
• If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer
for inspection.
04
01
.
.
04
.
GB-13
GB
F
NL
I
E
0 40 5
0 60 7
?
Start-up– flame burning – nevertheless, the
display blinks and indicates
burner/burner or
! Flame failure on start-up.
• Read off the flame signal.
If the flame signal is lower than the switch-off
▷
threshold (parameter01), this may be attributable
to the following causes:
! The set value for the cut-off sensitivity is too high.
! Short-circuit on the flame rod as the result of
soot, dirt or moisture on the insulator.
06
! Flame rod not correctly positioned at the flame
edge.
! Gas/air ratio incorrect.
! Flame not contacting burner ground as the result
of excessively high gas or air pressure.
! Burner or BCU not (adequately) grounded.! Short-circuit or discontinuity on the flame signal
cable.
! Soiled UV sensor.! UV sensor wiring is defective.
• Remedy fault.
or
04
or
on the main burner.
07
on the pilot
05
1 0
? The display blinks and indicates
! Actuation of the remote reset input is faulty.
! Too many remote resets. More than 5resets
have been conducted within the last 15minutes,
either automatically or manually.
! Consecutive fault caused by a previous fault
whose actual cause has not been remedied.
• Pay attention to previous fault messages.
• Remedy cause.
▷ The cause will not be remedied by performing a
reset every time a fault lock-out occurs.
• Check whether remote reset complies with
standards (EN746 allows resetting only under
supervision) and correct if necessary.
▷ The BCU may only be reset manually under su-
pervision.
• Press the Reset/Information button on theBCU.
.
10
1 1
? The display blinks and indicates
! Too many restarts. More than 5restarts initiated
within the last 15minutes.
• Check burner setting.
• Press the Reset/Information button on theBCU.
11
.
0 8
? Operation– flame burning– burner inter-
rupted– the display blinks and indicates
! Flame failure during operation or during delayed
controller enable.
• Read off the flame signal, see page19 (Read-
ing off the flame signal, fault messages and the
parameters).
▷
If the flame signal is lower than the switch-off
threshold for the flame signal from burner 1
(parameter 01), this may be attributable to the
following causes:
! The set value for the cut-off sensitivity is too high.
! Short-circuit on the flame rod as the result of
soot, dirt or moisture on the insulator.
! Flame rod not correctly positioned at the flame
edge.
! Gas/air ratio incorrect.
! Flame not contacting burner ground as the result
of excessively high gas or air pressure.
! Burner or BCU not (adequately) grounded.! Short-circuit or discontinuity on the flame signal
cable.
! Soiled UV sensor.
• Remedy fault.
08
2 0
? The display blinks and indicates
! Voltage is applied to the output at terminal 56.
.
• Check the wiring and ensure that the voltage
outputs and inputs have the same polarity and
are not reversed.
! The unit has suffered an internal fault in the power
module.
• Replace the power module.
2 1
? The display blinks and indicates
! Inputs 51 and 52 are activated simultaneously.
• Check input 51.
▷
Input 51 may only be activated if the valve is
open.
• Check input 52.
▷ Input 52 may only be activated if the valve is in
the position for ignition capacity.
GB-14
20
21
.
.
GB
F
NL
I
E
• Establish the cause of the fault to avoid repeat
2 2
? The display blinks and indicates
! Actuator IC 20 has been wired incorrectly.
• Check the wiring. Wire the outputs and inputs
of connection terminals 52–55 as shown in the
connection diagram– see page8 (IC 20..E
connected to BCU570..F1).
! The unit has suffered an internal fault in the power
module.
• Replace the power module.
22
.
2 3
? The display blinks and indicates
! The butterfly valve position is not constantly sig-
nalled back to the BCU.
• Check the wiring and ensure that the position
of the butterfly valve for max. capacity/ignition
capacity/Closed is constantly signalled back via
terminal 52.
23
.
2 4
? The display blinks and indicates
! Faulty activation via the bus. Requirements for
“Open” and “Close” set simultaneously.
• Ensure that “Open” and “Close” are not activated
simultaneously.
24
.
3 0
? The display blinks and indicates
! Abnormal data change in the parameters set for
theBCU.
• Reset the parameters to their original values using
the BCSoft software.
• Establish the cause of the fault to avoid repeat
faults.
• Ensure that the cables have been installed prop-
erly– see page4 (Cable selection).
• If the measures described above do not help,
remove the unit and return it to the manufacturer
for inspection.
30
.
3 1
? The display blinks and indicates
! Abnormal data change in the parameters set for
theBCU.
the BCSoft software.
• Reset the parameters to their original values using
31
.
GB-15
faults.
• Ensure that the cables have been installed prop-
erly– see page4 (Cable selection).
• If the measures described above do not help,
remove the unit and return it to the manufacturer
for inspection.
3 2
? The display blinks and indicates
! Supply voltage too low or too high.
• Operate the BCU in the specified mains voltage
range (mains voltage +10/-15%, 50/60Hz).
! An internal device error occurred.
• Remove the unit and return it to the manufacturer
for inspection.
32
.
3 3
? The display blinks and indicates
! Faulty parameterization.
• Check parameter settings using BCSoft.
! An internal device error occurred.
• Remove the unit and return it to the manufacturer
for inspection.
33
.
3 6
? The display blinks and indicates
! An internal device error occurred.
• Replace the power module.
• Remove the unit and return it to the manufacturer
for inspection.
4 0
? The display blinks and indicates
! The gas solenoid valve V1 is leaking.
• Check the gas solenoid valve V1.
! The gas pressure switch DGpu/2 for the valve
check has been set incorrectly.
• Check the inlet pressure.
• Set DGpu/2 to the correct inlet pressure.
• Check the wiring.
! The test pressure between V1 andV2 has not
decreased.
• Check the installation.
! The test period is too long.
• Change parameter56 (Measurement time Vp1)
using BCSoft.
• If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer
for inspection.
36
40
.
.
GB
F
NL
I
E
4 1
5 3
? The display blinks and indicates
! One of the burner-side gas solenoid valves is
leaking.
• Check the burner-side solenoid valves.
! The gas pressure switch DGpu/2 for the valve
check has been set incorrectly.
• Check the inlet pressure.
• Set DGpu/2 to the correct inlet pressure.
• Check the wiring.
! The test period is too long.
• Change parameter56 (Measurement time V
using BCSoft.
• If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer
for inspection.
41
.
p1)
5 0
? The display blinks and indicates
! Interruption of signal at the “Enable/Emergency
stop” input (terminal46).
• Check voltage supply to terminal46.
• Check the setting of parameter10.
50
.
5 1
? The display blinks and indicates
! Short-circuit on one of the outputs of the safety
• Then check the faultless processing of all input
and output signals.
! The unit has suffered an internal fault in the power
module.
• Replace the power module.
51
.
5 2
? The display blinks and indicates
! The time between two starts is less than the
min.time (timingcycle).
• Comply with the min. timing cycletz
tz
[s] = (tVZ + 0.6 × t
min
Example:
Pre-ignition time t
Safety time 1 t
tz
= (2 + 0.6 × 3) + 9 = 12.8 s
min
8 0
SA1
= 2 s
VZ
= 3s
8 38 1
8 68 78 5
85
9 4
9 9
,
,
,
86
87
88
8 9
9 8
? The display blinks and indicates
,
84
! System fault – the BCU has performed a safety
shut-down. The cause may be a unit defect or
abnormal EMC influence.
• Ensure that the ignition cable has been installed
properly– see page4 (Cable selection).
• Ensure that the EMC regulations for the sys-
tem are satisfied– particularly for systems with
frequency converters – see page 4 (Cable
selection).
• Reset the unit by pressing the Reset/Information
button.
• Disconnect the burner control unit from the mains
supply and then switch it on again.
• Check mains voltage and frequency.
• If the measures described above do not help, the
unit has probably suffered a hardware defect–
remove the unit and return it to the manufacturer
for inspection.
9 5
,
,
,
89
94
53
.
:
min
) + 9
SA1
8 4
8 8
9 6
,
,
80
81
83
,
95
96
,
98
99
or
,
.
? The display blinks and indicates
! The BCU is permanently reset by remote reset.
• Check voltage supply to terminal3.
• Apply voltage to terminal3 only for reset, approx.
1second.
52
.
9 7
? The display blinks and indicates
! No PCC.
• Insert compatible PCC.
! Contact problems on the power module.
• Remedy contact problems.
! Power module is defective.
• Replace power module.
GB-16
.
97
GB
F
NL
I
E
• If the measures described above do not help, the
unit has probably suffered a hardware defect –
remove the unit and return it to the manufacturer
for inspection.
0
? The display blinks and indicates
! The “no flow” state check of the air or differential
pressure switch has failed.
• Check the function of the air pressure switch.
Before the fan is switched on, there must be no
high signal at the input for air monitoring (terminal47) when air monitoring is activated.
• Check the function of the differential pressure
switch. When the fan is switched off, the “no
flow” state (default position) of the differential
pressure switch (terminal 48) is also monitored
if air flow monitoring has been activated.
0
.
1
? The display blinks and indicates
! The operating check of the air pressure switch
has failed. The air monitor, depending on the
parameter setting for input 47 or 48 (P15 and
P35), has not switched after fan start-up.
• Check the air monitor wiring.
• Check the air pressure switch setpoint.
• Check the function of the fan.
1
.
P
? The display blinks and indicates
! The input signal (terminal48) for the air pressure
switch has dropped out during pre-purge.
• Check the air supply during the purging process.
• Check the electrical wiring of the air pressure
switch.
• Check voltage supply to terminal48.
• Check the air pressure switch setpoint.
23
6
7
4
8
P
.
5
9
• Check the air supply.
• Check the air pressure switch setpoint.
23
6
? The display blinks and indicates
,
,
5
6
! The signal for monitoring the max. gas pressure
(terminal50) has dropped out at program stepX
(02to09).
• Check the wiring.
• Check the gas pressure.
7
,
7
8
9
or
4
8
.
5
9
,
,
2
3
4
0
? The display blinks and indicates
! BCU waiting for connection to PLC.
• Check whether the PLC is switched on.
• Check the network wiring.
• Check the PLC programming.
• Check whether the correct device name and
IPaddress for the BCU have been entered in
the PLCprogram.
0
.
1
? The display blinks and indicates
! An invalid address has been set on the bus mod-
ule.
• Adapt the bus module’s address with the code
switches to the address allocated in the PLCprogram.
• Check whether the bus module’s address is in
the permitted address range (001toFEF).
1
.
2
? The display blinks and indicates
! The bus module has received an incorrect con-
figuration from thePLC.
• Check whether the correct GSD file was imported
into the PLC.
2
.
,
? The display blinks and indicates
5, 6, 7, 8
! The input signal for the air pressure switch has
dropped out during start-up/operation at program stepX (02to09).
Failure of the air supply at program stepX
!
9
or
.
,
3, 4
.
,
? The display blinks and indicates
! The device name for the BCU is invalid in the
PLC program.
GB-17
3
3
.
2
GB
F
NL
I
E
▷ Device name on delivery:
not-assigned-bcu-570-xxx
(xxx = code switch setting on the BCU).
▷
The device name must at least consist of the
expression bcu-570-xxx.
• Check whether the code switch setting is identi-
cal to the entry(xxx) in the PLCprogram.
• Delete the expression “not-assigned-” in the
PLC program or replace it with an individual name
part (e.g. Furnacezone1-).
4
? The display blinks and indicates
! The PLC is set to Stop.
• Start the PLC.
4
.
0
4
8
? The display blinks and indicates
,
,
3
4
! The signal for monitoring the min. gas pressure
(terminal49) has dropped out at program stepX
(00to09).
• Check the wiring.
• Check the gas pressure.
5
1
2
6
3
7
9
,
0, 1
2
,
,
5
,
6
7
8
9
or
.
,
Replacing the fuse
▷
The device fuses F1 and F2 can be removed
for inspection.
Disconnect the system/BCU from the electrical
power supply.
Disconnect the connection terminals from the
BCU.
▷ The connection cables may remain screwed to
the connection terminals.
Disconnect the power module, see page3
(Replacing the power module/parameter chip
card).
4 Remove the fuse holder (with fine-wire fuse F1
orF2).
F1:T3,15A H
F2:T5A H
5 Check fine-wire fuse F1 or F2 for correct func-
tioning.
6 Replace the fine-wire fuse if defective.
▷
When replacing the fuse, use only the approved
fuse type (F1:3.15A, slow-acting, H, F2: 5A,
slow-acting,H; pursuant to ICE60127-2/5).
• First reconnect the power module, then recon-
nect the connection terminals and restart the
system/BCU, see also page 12 (Commissioning).
A
? The display blinks and indicates
! No “Position for minimum capacity reached”
signal from actuator.
• Check the butterfly valve and the function of the
limit switches in the actuator.
• Check the wiring.
• Check the actuator.
• If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer
for inspection.
A
.
A
? The display blinks and indicates
! No “Position for maximum capacity reached”
signal from actuator.
• Check the butterfly valve and the function of the
limit switches in the actuator.
• Check the wiring.
• Check the actuator.
• If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer
for inspection.
A
.
A
? The display blinks and indicates
! No “Position for ignition capacity reached” signal
from actuator.
• Check the butterfly valve and the function of the
limit switches in the actuator.
• Check the wiring.
• Check the actuator.
A
.
GB-18
GB
F
NL
I
E
• If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer
for inspection.
Reading off the flame signal, fault
messages and the parameters
▷
During operation (display
), information about
08
the flame signal intensity, the last 10fault mes-
E
? The display blinks and indicates
! Internal communication with bus module has
suffered a fault.
• Connected control elements must be equipped
with protective circuits in accordance with the
manufacturer’s instructions.
▷
This prevents high voltage peaks which can
cause malfunctioning of the BCU.
• Use suppressed terminal boots (1 kΩ).
• If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer
for inspection.
! The bus module is defective.
• Replace the bus module.
E
.
sages and the parameter values can be read
off by repeatedly pressing the Reset/Informa-
tion button.
DisplayInformation
F1
E0
to
E9
01
to
99
Flame signal intensity:
burner 1
Last fault message
to
tenth to last fault message
Parameter 01
to
parameter 99
• Press the Reset/Information button for approx.
F1
2s until the display indicates
.
• Release the button. The display indicates the
flame signal intensity inµA.
• Press the Reset/Information button again for
2s to go to the next item of information (fault
message, parameter value).
▷
Each time the button is released, the correspond-
? The display blinks and indicates
.
! Incorrect or defective parameter chip card (PCC).
• Only the intended parameter chip card is to be
used.
• Replace defective parameter chip card.
ing fault code or parameter value is displayed.
▷ To go to one of the last fault messages or to a
parameter more quickly, hold the Reset/Infor
mation button pressed down for longer (≥2s).
▷ If the button is pressed only briefly, the display
indicates what parameter is currently being dis-
-
played.
▷
The normal program status is displayed again
1
? The display blinks and indicates
! No input signal for the valve proof of closure
switch (POC) during standby.
• Check the wiring.
▷ Mains voltage must be supplied to the BCU (ter-
minal45) if the valve is closed and no voltage is
to be applied if the valve is open.
• Check that the proof of closure switch and valve
function perfectly, replace defective valves.
1
.
approx. 60seconds after the last time the but-
ton is pressed.
Parameters and values
Pa-
Name
ram-
Values
eter
Burner 1 flame signal switch-off threshold
01
2 – 20 = µA
Flame control
0 = Ionization
04
1 = UVS
2 = UVD
Burner 1 start-up attempts
1 = 1 start-up attempt
07
8
? The display blinks and indicates
! The BCU is receiving no information as to wheth-
er the POC switch contact is still open.
• Check the wiring.
• During start-up, mains voltage must be supplied
to the BCU (terminal45) if the valve is closed and
no voltage is to be applied if the valve is open.
0 = Off
8 = AND with emergency stop (trm.46)
9 = AND with air min. (trm.47)
10 =
69
AND with air flow monitoring (trm.48)
11 = AND with gas max. (trm.50)
12 = AND with gas min. (trm.49)
13 = Max. capacity position feedback (IC40/
RBW)
Function of terminal 65
0 = Off
8 = AND with emergency stop (trm.46)
9 = AND with air min. (trm.47)
70
10 =
AND with air flow monitoring (trm.48)
11 = AND with gas max. (trm.50)
12 = AND with gas min. (trm.49)
Function of terminal 66
0 = Off
8 = AND with emergency stop (trm.46)
9 = AND with air min. (trm.47)
71
10
AND with air flow monitoring (trm.48)
=
11 = AND with gas max. (trm.50)
12 = AND with gas min. (trm.49)
Function of terminal 67
0 = Off
8 = AND with emergency stop (trm.46)
9 = AND with air min. (trm.47)
72
10 =
AND with air flow monitoring (trm.48)
11 = AND with gas max. (trm.50)
12 = AND with gas min. (trm.49)
Function of terminal 68
0 = Off
8 = AND with emergency stop (trm.46)
9 = AND with air min. (trm.47)
73
10
AND with air flow monitoring (trm.48)
=
11 = AND with gas max. (trm.50)
12 = AND with gas min. (trm.49)
Capacity control (bus)
0 =
Off
1 =
MIN. to MAX. capacity; standby in position for
MIN. capacity
2 =
MIN. to MAX. capacity; standby in CLOSED
position
75
3 =
IGNITION to MAX. capacity; standby in
CLOSED position
4 =
MIN. to MAX. capacity; standby in position for
MIN. capacity; burner quick start
5 =
IGNITION to MAX. capacity; standby in position for MIN. capacity; burner quick start
Password
77
0000 – 9999
Burner application
0 = Burner 1
1 = Burner 1 with pilot gas
78
2 = Burner 1 and burner 2
3 = Burner 1 and burner 2
with pilot gas
GB-20
GB
F
NL
I
E
Pa-
P
ϑ
PZ
PZH
PZL
PDZ
P
xx
M
Name
ram-
Values
eter
Pilot burner operation
0 = With shut-down
79
1 = Continuous operation
Fieldbus communication
0 = Off
80
1 = With address check
2 = No address check
Pre-ignition time
93
0
–
5 = Time in seconds
Safety time 1 t
94
2, 3, 5, 10 = Time in seconds
Flame proving period 1 t
95
0
–
20 = Time in seconds
Safety time 2 t
96
2, 3, 5, 10 = Time in seconds
Flame proving period 2 t
97
0
–
20 = Time in seconds
SA1
SA2
FS1
FS2
▷ Additional parameters for BCU570..F2
Pa-
Name
ram-
Values
eter
Running time selection
0 = Off; checking the positions for min./max.
capacity
1 = On; for approaching the positions for min./
max. capacity
41
2 = On; for approaching the position for maximum
capacity
3 = On; for approaching the position for minimum
capacity
Running time
0 – 250 =Running time in seconds, if
42
parameter41= 1, 2 or3
▷ Additional parameters for BCU570..C1
Pa-
Name
ram-
Values
eter
Valve proving system
0 = Off
1 = Tightness test before start-up
2 = Tightness test after shut-down
51
3 =
Tightness test before start-up and after shut-
down
4 = Proof of closure function
Relief valve
2 = V2
52
3 = V3
4 = V4
Measurement time Vp1
3 = Time in seconds
56
5 – 25 = (in 5 s steps)
30 – 3600 = (in 10 s steps)
Valve opening time 1 tL1
59
2 – 25 = Time in seconds
Legend
HT
TC
pu/2
p
d
GZL
Ready for operation
Safety interlocks (limits)
High temperature operation
Gas valve
Air valve
Air/gas ratio control valve
Burner
Purge
Controlled air flow
Burner operating signal
Start-up signal (BCU)
Emergency stop
Pressure switch for valve check (TC)
Pressure switch for maximum pressure
Pressure switch for minimum pressure
Differential pressure switch
Input signal
depending on parameter xx
Control element with butterfly valve
Valve check (tightness test)
Half of the inlet pressure
Outlet pressure
Valve with proof of closure switch
Input/Output, safety circuit
GB-21
GB
F
NL
I
E
Technical data
Electrical data
Mains voltage:
BCU 570Q: 120 V AC, -15/+10%, 50/60 Hz, ±5%,
BCU 570W: 230 V AC, -15/+10%, 50/60 Hz,
±5%,
for grounded or ungrounded mains.
Flame control:
with UV sensor or ionization sensor.
For intermittent or continuous operation.
Flame signal current:
ionization control: 1 – 25 μA,
UV control: 1 – 35 μA.
Ionization cable, UV cable:
max. 100m (164ft).
Contact rating:
valve outputs V1, V2, V3 and V4 (terminals 13, 14,
15,57) as well as actuator (terminals 53, 54
and55):
max. 1A each, cosφ≥0.6,
total current for the simultaneous activation of the
valve outputs (terminals 13, 14, 15,57) and of the
actuator (terminals 53, 54,55):
max. 2.5A,
fan (terminal58):
max. 3 A (start-up current: 6A<1s),
signalling contact for operating and fault signals:
max. 1 A (external fuse required).
Number of operating cycles:
The fail-safe outputs (valve outputs V1, V2, V3
andV4) are monitored for correct functioning and
are thus not subject to a max. number of operating
cycles.
Control actuator (terminals 53, 54 and 55):
max. 250,000,
signalling contact for operating signals:
max. 250,000,
signalling contact for fault signals:
max. 10,000,
On/Off button:
max. 10,000,
Reset/Information button:
max. 10,000.
Input voltage of signal inputs:
Rated value120 V AC230 V AC
Signal “1”80 – 132 V160 – 253 V
Signal “0”0 – 20 V0 – 40 V
Signal input current:
Signal “1”max. 5 mA
Fuses, replaceable, F1: T 3.15A H,
F2: T 5A H, pursuant to IEC 60127-2/5.
Mechanical data
Weight: 0.7 kg.
Dimensions (W × H × D): 102 × 115 × 112 mm.
Storage temperature: -20 to +60°C (-4 to +140°F).
Ambient temperature:
-20 to +60°C (-4 to +140°F),
no condensation permitted.
Enclosure: IP 20 pursuant to IEC 529.
Installation location: min. IP 54 (for installation in a
control cabinet).
Designed lifetime
This information on the designed lifetime is based on
using the product in accordance with these operating
instructions. Once the designed lifetime has been
reached, safety-relevant products must be replaced.
Designed lifetime (based on date of manufacture):
20 years.
You can find further explanations in the applicable
rules and regulations and on the afecor website
(www.afecor.org).
This procedure applies to heating systems. For
thermoprocessing equipment, observe local regulations.
Logistics
Transport
Protect the unit from external forces (blows, shocks,
vibration). On receipt of the product, check that the
delivery is complete, see page 2 (Part designations). Report any transport damage immediately.
Storage
Store the product in a dry and clean place.
Storage temperature: see page22 (Technical data).
Storage time: 6months before using for the first
time. If stored for longer than this, the overall service
life will be reduced by the corresponding amount of
extra storage time.
Packaging
The packaging material is to be disposed of in ac-
cordance with local regulations.
Disposal
Components are to be disposed of separately in
accordance with local regulations.
GB-22
GB
F
NL
I
E
Accessories
BCSoft
The current software can be downloaded from our
Internet site at http://www.docuthek.com. To do so,
you need to register in the DOCUTHEK.
Opto-adapter PCO 00
Including BCSoft CD-ROM,
Order No.: 74960625.
Bluetooth adapter PCO 00
Including BCSoft CD-ROM,
Order No.: 74960617.
Stickers for labelling
OCU
For installation in the control cabinet door. The program status or fault messages can be read on the
OCU. In Manual mode, the OCU can be used to
proceed through the sequence of operating steps.
OK
TypeLanguagesOrder No.
OCU 500-1 D, GB, F, NL, E, I84327030
OCU 500-2 GB, DK, S, N, TR, P84327031
OCU 500-3 GB, USA, E, P(BR), F84327032
OCU 500-4 GB, RUS, PL, H, RO, CZ 84327033
BCU 570
Brenner 1
For printing with laser printers, plotters or engraving
machines, 27 × 18mm or 28 × 17.5mm.
Colour: silver.
Connection terminal set
For wiring the BCU.
7492399774923999
Plug-in, with screw terminal,
Order No.: 74923997.
Plug-in, with spring force terminal, 2connection
options per terminal,
Order No.: 74923999.
Certification
Declaration of conformity
We, the manufacturer, hereby declare that the product
BCU 570 complies with the requirements of the listed
Directives and Standards.
Directives:
– 2009/142/EC – GAD (valid until 20 April 2018)
– 2014/30/EU
– 2014/35/EU
Regulation:
– (EU) 2016/426 – GAR (valid from 21 April 2018)
Standards:
– EN 298:2012
– EN1643:2014
– EN 61508:2010, suitable for SIL 3
The relevant product corresponds to the tested type
sample.
The production is subject to the surveillance proce-
dure pursuant to Directive 2009/142/EC AnnexII
paragraph3 (valid until 20 April 2018) and to Regu
lation (EU) 2016/426 Annex III paragraph 3 (valid from
21April 2018).
Elster GmbH
Scan of the Declaration of conformity (D,GB)– see
www.docuthek.com
-
GB-23
GB
F
NL
I
E
SIL, PL
For systems up to SIL 3 pursuant to EN 61508.
Pursuant to EN ISO 13849-1, Table 4, the BCU can
be used up to PL e.
FM approved
Factory Mutual (FM) Research Class:
7610 “Combustion Safeguards and Flame Sensing
Systems”
Suitable for applications pursuant to NFPA 86.
ANSI/CSA approved
Canadian Standards Association –
ANSI Z21.20 and CSA 22.2
UL listed
Underwriters Laboratories – UL 372
Standard for Limit Controls
Eurasian Customs Union
The product BCU 570 meets the technical specifica-
tions of the Eurasian Customs Union.
Registered design
U.S. Patent No. D682,794
Directive on the restriction of the use of
hazardous substances (RoHS) in China
Scan of the Disclosure Table China RoHS2 – see
certificates at www.docuthek.com
Contact
Contact
If you have any technical questions, please contact
your local branch office/agent. The addresses are
available on the Internet or from ElsterGmbH.
We reserve the right to make technical modifications
in the interests of progress.
Strotheweg 1, D-49504 Lotte (Büren)
Elster GmbH
Tel. +49 541 1214-0
Fax +49 541 1214-370
hts.lotte@honeywell.com, www.kromschroeder.com
GB-24
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.