Operating instructions Ionization pilot burners
ZAI, ZMI, ZKIH
Translation from the German © 2011 Elster GmbH
Contents
Checking the usage . . . . . . . . . . . . . . . . . . . . . 2
Setting the gas type . . . . . . . . . . . . . . . . . . . . . 3
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Tightness test. . . . . . . . . . . . . . . . . . . . . . . . . . 6
Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . 7
Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Replacing the electrodes . . . . . . . . . . . . . . . . . . 8
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Technical data. . . . . . . . . . . . . . . . . . . . . . . . . 11
Declaration of Incorporation. . . . . . . . . . . . . 12
Safety
Please read through these instructions carefully before installing or operating. Following the installation, pass the instructions on to the opera­tor. This unit must be installed and commissioned in accordance with the regulations in force. These instructions can also be found at www.docuthek.com.
Explanation of symbols
• , 1 , 2 , 3 ... = Action
= Instruction
Liability
We will not be held liable for damages resulting from non-observance of the instructions and non­compliant use.
Safety instructions
Information that is relevant for safety is indicated in the instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified gas technicians. Electrical interventions may only be carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM spare parts.
Transport
On receipt of the product, check that the delivery is complete (see Part designations). Report any trans­port damage immediately.
Storage
Store the product in a dry place. Ambient tempera­ture: see Technical data.
GB
GB-1
F
NL
I
E
Checking the usage
Intended use
Ionization-controlled pilot burners for safely igniting gas burners. The capacity of the pilot burner should be 2 to 5% of that of the main burner. Can also be used as independently operated burners. For natural gas, town gas, coke oven gas and LPG. Other types of gas on request.
This function is only guaranteed when used within the
specified limits – see also page11 (Technical data). Any other use is considered as non-compliant.
ZMI
Type code
ZMI
Ionization pilot burner with forced air
supply and one electrode 16 – 25 Burner size T T-product
B D G
For natural gas
For town gas, coke oven gas
For LPG 150 – 1000 Flame tube length
R Rp internal thread N NPT internal thread
ZAI
GB
Type code
ZAI
Thermo ionization pilot burner with two
electrodes K Double-cone olive for 8mm tube TN 1/4" NPT internal thread
Part designations
3
2
10
4
1
6
5
7
8
9
1 Interference-suppressed adapter for ignition
electrode
2 Adapter for ionization electrode 3 Ionization electrode 4 Ignition electrode 5 Air slide valve 6 Gas connection 7 0.7 mm gas nozzle for LPG 8 Cone olive (only for ZAI K) 9 Cap screw (only for ZAI K)
10
Enclosed documentation: operating instructions
Gas connection– see type label.
D-Osnabrück Germany
ZAI K
Part designations
3
1
2
4
7
5
1 Burner housing 2 Interference-suppressed electrode adapter 3 Air nozzle 4 Gas nozzle 5 Mounting device 6 Flame tube 7 Enclosed documentation: operating
instructions and flow rate curves
Burner size, gas type, rated capacity P tube length, connection– see type label.
D-49018 Osnabrück Germany
ZMI Gas
Pmax.
max.
6
, flame
GB-2
F
NL
I
E
ZKIH
2 3
1
0.7
2
2 3
1
Gasdüse 0,7 mm (0,028") für Flüssiggas.
Gasdüse für Stadtgas 1,8 mm (0,07") separat bestellen (Best.-Nr. 74472880).
Gas nozzle Ø 0.7 mm (0.028") for LPG.
Order gas nozzle for town gas Ø
1.8 mm (0.07") separately (Order No. 74472880).
Type code
ZKIH Ionization pilot burner with forced air
supply
150 – 1000
Burner tube length
/100 Flame tube length
R Rp internal thread
Part designations
Setting the gas type
ZAI
 Pilot burners ZAI are set for natural gas on de-
livery.
 If the pilot burner is to be used with a different
type of gas, retrofit the burner for its use.
1
2
4
1 Burner housing
3
a
5
b
6
0.7
Gas nozzle Ø 0.7 mm (0.028") for LPG.
GB
Order gas nozzle for town gas Ø
2
4
1.8 mm (0.07") separately (Order No. 74472880).
5
6
2 Burner housing cover 3 Burner tube set, comprising protective tubea
and flame tubeb
4 Retaining screw for nozzle insert (in burner
housing)
5 Nozzle insert (in burner housing) 6 Enclosed documentation: operating
instructions and flow rate curves
Rated capacity P
D-49018 Osnabrück Germany
ZKIH
Gas Pmax.
, gas type– see type label.
max.
ZMI 1 Check if the nozzle diameter is suitable for the
2
required gas type.
 When changing the nozzle, remove the residue
of sealant from the burner housing.
 Suitable nozzles– see page10 (Accessories).
1
Nozzle dia.
Gas type
[mm (inch)]
ZMI 16 ZMI 25
B 0.94 (0.037) 1.40 (0.055) G 0.76 (0.029) 1.05 (0.041) D 1.30 (0.051) 1.78 (0.070)
ZKIH

Pilot burners ZKIH are set for natural gas on delivery.
 If the pilot burner is to be used with a different
type of gas, retrofit the burner for its use.
GB-3
F
NL
I
E
1
1
2
I
Z
3
1
burner using the
Installation
DANGER
Risk of explosion! Ensure the connection is gas-
tight.
 Install the pilot burner so that reliable ignition of
2
GB
I
3
Z
4
=
+
+
Natural gas
=
LPG
=
Town gas
5
6
the main burner is guaranteed.
 Attach the pilot burner securely. 
We recommend that a filter be installed in the gas and air supply line respectively.
ZAI
 Inlet pressure:
natural gas: max. 35 mbar (14"WC),
town gas: max. 30 mbar (12"WC), LPG: max. 60 mbar (23 "WC).

In the case of higher inlet pressures, insert a gas restrictor orifice.
 Ensure air intake is not obstructed.  The ZAI has bare electrodes and no protective
flame tube. Protective tube, see page10 (Acces­sories).
WARNING
Risk of injury! Observe the projecting ionization
electrode.
Attach the
two holes on the fastening lug.
7
For operation with town gas, screw the retaining

8
screw back in without the nozzle insert– do not store the nozzle insert in the connection box: danger of short-circuits.
9 After conversion to another type of gas, adjust
the air volume– see page7 (Commissioning).
8
2 mm
9

When tightening the cap screw 9, ensure that the cone olive 8 is correctly positioned– lubricate the cone olive.
 ZAI flow rate curve– see www.docuthek.com
ZMI
 Recommended inlet pressures:
gas: 50 – 60 mbar (19.7 – 23.6 "WC), air: 50 – 60 mbar (19.7 – 23.6 "WC).
 Install pressure regulators and adjusting cocks
in the air and gas supply lines upstream of the burner so that the air and gas pressures can be adjusted.
CAUTION
Burner fault! If used as pilot burner, the gas and
air pressures must be higher that the connection pressures of the main burner.
GB-4
2
Connect the pilot gas line with 8 mm tube.