Kromschroder ZIO, ZIO 165, ZIO 200 Operating Instructions Manual

F
NL
I
E
03250473
D GB F NL I E
TR CZ PL RUS H
DK S N P GR
www.docuthek.com
Operating instructions
Burners for gas ZIO 65, ZIO 00
© 2014 Elster GmbH · Edition 05.14
Translation from the German

Contents

Burners for gas ZIO 65, ZIO 00 ..........
Contents ..............................
Safety.................................
Checking the usage .....................
Installation ............................
Installation in a burner quarl ................3
Burner with attachment tube ...............3
Installation on the furnace .................4
Air connection, gas connection .............4
Installing the burner insert .................5
Wiring ................................5
Preparing commissioning ................6
Determining the flow rates . . . . . . . . . . . . . . . . . 6
Notes on the flow rate curve ...............6
Restrictors .............................7
Hot-air compensation .................... 7
Commissioning.........................8
Igniting and adjusting the burner ............8
Tightness test...........................9
Cooling air .............................9
Blocking and recording the settings ..........9
Maintenance ..........................0
Assistance in the event of malfunction ....
Accessories ..........................
Technical data ........................
Logistics .............................
Declaration of Incorporation.............
Certification ..........................4
Contact ..............................4

Safety

Please read and keep in a safe place
Please read through these instructions carefully before installing or operating. Following the installation, pass the instructions on to the opera­tor. This unit must be installed and commissioned in accordance with the regulations and standards in force. These instructions can also be found at www.docuthek.com.
Explanation of symbols
,  ,  ,  ... = Action
= Instruction
Liability
We will not be held liable for damage resulting from non-observance of the instructions and non-com­pliant use.
Safety instructions
Information that is relevant for safety is indicated in the instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified gas technicians. Electrical interventions may only be carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM spare parts.
Changes to edition .
The following chapters have been changed: – Checking the usage – Installation – Preparing commissioning – Technical data – Logistics – Declaration of Incorporation
GB
GB-1
F
NL
I
E

Checking the usage

Burner for heating industrial thermoprocessing equip­ment. For installation in a burner quarl or for use with an extended, heat-resistant burner tube. For natural gas, town gas and LPG. Other types of gas on request.
This function is only guaranteed when used within
the specified limits – see also page 12 (Technical data). Any other use is considered as non-compliant. Construction stage, rated capacity Q see type label.
D-49018 Osnabrück Germany
GB
ZIO 165HB-100/35/18/D
BR 84246114
Qmax
BR 74970471 BK 18
Gas N SN
630 kW
Type code
Code Description
ZIO ZIOW
Burner for gas with internal
65 – 00 Burner size R H K B D G M
Coke oven gas, town gas Propane, propane/butane, butane Propane, propane/butane, butane
L Ignition lance
-50
-00
-50
Burner tube length [mm]
-00 ... /5­/5­/5-
Position of burner head [mm]
...
-() to -(99)
-(E) to
Burner head identifier
High temperature version
-(99E) A to Z Construction stage Z Special version
, gas type–
max
D
1114
Burner for gas
insulation
Normal flame
Long, soft flame
Flat flame
Natural gas
Part designations
5
4
2
3
1
6
8
7
Burner insert Gas housing gasket Air housing 4 Burner tube gasket 5 Burner tube with mounting flange 6 Mounting gasket 7 Type label 8 Enclosed documentation (flow rate curves,
operating characteristic diagrams, dimension sheet, spare parts list, spare parts drawing and Declaration of Incorporation)
Check letter marking and identification marks on
the burner head using the information provided on the type label.
GB-2
F
NL
I
E

Installation

Installation in a burner quarl

Conical burner quarl
For industrial furnaces and kilns and for burning in an open combustion chamber.
Control: High/Low, continuous. Type of burner head: R. Max. capacity: 100%.
We recommend the cold-air operating mode, otherwise the nitric oxide values will be too high.
Cylindrical burner quarl
For industrial furnaces and kilns and for burning in an open combustion chamber.
Control: High/Low, High/Low/Off, continuous. Type of burner head: R, H. Max. capacity: 100%. Normal to medium flow velocity.
Tapered burner quarl
Flat flame burner quarl
For industrial furnaces and kilns and for burning in an open combustion chamber.
Control: High/Low, High/Low/Off, continuous (limited control range).
Type of burner head: K. Capacity range: 40 – 100%.

Burner with attachment tube

▷ Position of the burner head near the interior fur-
nace wall (L
= LO ± 50 mm).
L
O
1
L2 = LO ± 50 mm
Do not fit the attachment tube directly in the furnace wall.
▷ Furnace temperature ≤ 600°C.
Radiant tube heating:
▷ Reduce the outlet diameter of the radiant tube
using an orifice
to the point where a pressure loss of approx. 10 mbar occurs at the burner’s rated capacity.
2
GB
For industrial furnaces and kilns and for burning in an open combustion chamber.
Control: High/Low, High/Low/Off, continuous. Type of burner head: H. Max. capacity: approx. 80%, depending on the
outlet diameter of the burner quarl.
▷ Medium to high flow velocity.
GB-3
F
NL
I
E
Hot-air generation:
GB
At flow velocities of > 15 m/s, the protective flame tube FPT is used to protect the flame from being cooled.

Installation on the furnace

When installing, always ensure that when the burner is mounted, it is sealed tightly on the furnace wall.
1
2
▷ Install flexible tubes or bellows units to prevent
mechanical stress or transmission of vibration.
▷ Ensure that the seals are undamaged.
DANGER
Risk of explosion! Ensure the connection is gas­tight.
For connecting to ANSI/NPT connections:
An adapter set is required for connection to ANSI/
NPT, see page 12 (Accessories).
Type
ZIO 165 1½ – 11.5 NPT 4.57" ZIO 200 2 – 11.5 NPT 6.72"
* Flange hole diameter.
Weld flange H to air pipe P. Use NPT thread adapter G for gas connection GA.
Gas connection GAAir connection
GA
G
LA*
LA
H
P
Ignition lance connections on the ZIO..L:
Air connection la. Gas connection ga. Ignition lance capacity: 1.5 kW.
3

Air connection, gas connection

4
GA
LA
Type
ZIO 165 Rp 1½ DN 100 ZIO 200 Rp 2 DN 150
Threaded connection to DIN 2999, flange dimen-
sions to DIN 2633, PN 16.
Gas connection GAAir connection
LA
la
ga
Type
ZIO..L Rp ¼ Rp ½ ZIO..L with
adapter set
GB-4
Ignition lance
gas connection
ga
¼" NPT ½" NPT
Ignition lance
air connection
la
F
NL
I
E

Installing the burner insert

▷ The burner insert can be rotated to the required
position in increments of 90°.
Insert the gas housing gasket between the burner insert and the air housing.
On ZIOW, avoid the formation of dust and do not damage the surface of the internal insulation.
1 2
▷ Tighten the burner insert in a crosswise fashion
with max. 37 Nm (27.3 lbfft).

Wiring

DANGER
Electric shocks can be fatal! Before working on possible live components, ensure the unit is discon­nected from the power supply.
For the ignition and ionization cables, use (un-
screened) high-voltage cable:
FZLSi 1/6 up to 180°C (356°F), Order No. 04250410, or FZLK 1/7 up to 80°C (176°F), Order No. 04250409.
Ionization electrode I
Install the ionization cable well away from mains cables and interference from electro-magnetic sources and avoid external electrical interference. Max. length of ionization cable – see automatic burner control unit operating instructions.
Connect the ionization electrode to the automatic burner control unit via the ionization cable.
Ignition electrode Z
Length of ignition cable: max. 5 m (15 ft), recom­mended < 1 m (40").
For permanent ignition, max. ignition cable length
1 m (40").
Lay the ignition cable individually and not in a metal conduit.
Install the ignition cable separately from ionization and UV cables.
▷ A ≥ 7.5kV, 12mA ignition transformer is rec-
ommended; 5kV for ignition lance.
Ionization and ignition electrodes
1
3
4
2
5
GB
6 Connect the PE wire for burner ground to the
burner insert. In the case of single-electrode op­eration, route the PE wire from the burner insert directly to the terminal on the automatic burner control unit.
I
Z
WARNING
High-voltage risk! It is essential that a high-voltage warning label is attached to the ignition cable.
7 For more detailed information on how to wire
the ionization and ignition cables, refer to the operating instructions and connection diagrams of the automatic burner control unit and ignition transformer.
GB-5
F
NL
I
E

Preparing commissioning

δ
Safety instructions
▷ Arrange the adjustment and commissioning of
the burner with the system operator or manu­facturer. Check the entire system, upstream devices and
electrical connections.
Note the operating instructions for individual controls.
DANGER
The burner must only be commissioned by author-
ized trained personnel.
GB
Risk of explosion! Please observe the appropriate precautions when igniting the burner. Risk of poisoning! Open the gas and air supply so that the burner is always operated with excess air – otherwise CO will form in the furnace chamber. CO is odourless and poisonous! Conduct a flue gas analysis.
Pre-purge the furnace chamber with air (5 x furnace chamber volume) before every ignition attempt.
▷ If the burner does not ignite although the auto-
matic burner control unit has been switched on and off several times: check the entire system.
▷ After ignition, monitor the flame and the gas and
air pressure measured on the burner. Measure the ionization current. Switch-off threshold – see automatic burner control unit operating instructions.
Z
+ µA –
I
The burner must only be ignited at low fire
(between 10 and 30% of the rated capacity Q
) – see type label).
max
DANGER
Risk of explosion! Fill the gas line to the burner carefully and correctly with gas and vent it safely into the open air – do not discharge the test volume into the furnace chamber.
Determining the flow rates
Q
= PB/H
Gas
Q
Luft
Q
: Gas flow rate in m3/h (ft3/h)
Gas
▷ P
: Burner capacity in kW (BTU/h)
B
: Gas calorific value in kWh/m3 (BTU/ft3)
▷ H
u
▷ Q
: Air flow rate in m
Luft
λ: Lambda, air index
= Q
Gas
u
. λ . L
3
/h (SCFH)
(n)
min
L
: Minimum air requirement in m
min
(SCF/SCF)
• Use the lower calorific value H
▷ Information on the gas quality supplied can be
obtained from the competent gas supply com­pany.
Common gas qualities
H
u
Gas type
kWh/m
3
(n)
(BTU/SCF)
Natural gas H
Natural gas L
Propane
Town gas
Butane
* Data in kWh/m³
value Hu and data in BTU/SCF refer to the upper
11
(1114)
8.9
(901)
25.9
(2568)
4.09 (425)
34.4
(3406)
refer to the lower calorific
(n)
calorific value Ho.
For safety reasons, a minimum air excess of 5%
(lambda = 1.05) should be ensured.
Notes on the flow rate curve
If the gas density in the operating state differs from that reflected in the flow rate curve, convert the pressures according to the local operating state.
pB = p
δ
: Gas density reflected in the flow rate curve
M
[kg/m3 (lb/ft3)]
δ
: Gas density in operating state
B
[kg/m3 (lb/ft3)]
pM: Gas pressure reflected in the flow rate
M
δ
M
B
.
curve
pB: Gas pressure in operating state
Read off the gas pressure p p
from the enclosed flow rate curve for cold
air
air on the basis of the calculated flow rates.
[mbar ("WC)]
p
air
p
gas
p
gas
Q
gas
p
gas
air
[m
3
/h (ft3/h)]
▷ Note possible capacity changes due to positive
or negative pressures in the furnace/combustion chamber. Add positive pressures or subtract negative pressures.
GB-6
3
3
/m
(n)
(n)
u.
L
min
3
3
m
/m
(n)
(n)
(SCF/SCF)
10.6
8.6
24.4
3.67
32.3
and air pressure
Q
air
F
NL
I
E
As not all the effects caused by the equipment
3
2
4
L
are known, setting the burner using the pressure values is only approximate. It is possible to set the burner precisely by measuring the flow rates
5
p
atm.
p
0
air
p
=
atm
atmospheric pressure.
or flue gas.

Restrictors

▷ The air volume required for the low-fire rate at a
given air pressure is determined by the ignition position of a butterfly valve, a bypass hole in the air valve or an external bypass with restrictor.

Hot-air compensation

The combustion air pressure p
creased in hot-air operating mode (lambda =
must be in-
Air
constant).
250
[%]
200
Air
p
150
100
0 100 200 300 400
T
[°C]
Air
The gas pressure is increased by 5–10mbar.
The total burner capacity PB rises as the air tem-
perature T
[%]
B
120
P
increases.
Air
Low fire:
▷ The burner must only be ignited at low fire (be-
tween 10 and 30% of the rated capacity Q see type label).
max
Reduce the air supply on the air control valve and set the desired low-fire rate, e.g. using a limit switch or mechanical stop.
On air control valves with bypass, the bypass orifice should be determined on the basis of the required flow rate and the existing supply pres­sure if required.
High fire:
Set the required air pressure p tor upstream of the burner.
on the air restric-
air
When using air restricting orifices: check the air pressure p
.
air
Preparing the gas pressure measurement for low fire and high fire
Connect all measuring devices for subsequent fine adjustment of the burner.
▷ Leave the gas supply closed.
–
GB
Gas measuring nipple G, external dia. = 9 mm
110
100
0 100 200 300 400
T
[°C]
Air
Setting the air pressure for low fire and high fire  Shut off the gas and air supply.
Air measuring nipple L, external dia. = 9 mm (0.35").
(0.35").
Read off the gas pressure p flow rate from the enclosed flow rate curve for
for the required
gas
cold air.
[mbar ("WC)]
p
air
p
gas
p
gas
p
air
2
L
3
Loosen the screw 2 turns.
4
Fully open
Q
gas
[m
3
/h (ft3/h)]
Q
air
the air supply.
GB-7
F
NL
I
E
1
Loosen the screw 2 turns.
G
2
G
GB
Integrated ignition lance on the ZIO..L:
▷ Air pressure test nipple l, external dia. = 9mm
(0.35"). Gas pressure test nipple g, external dia. = 9mm
(0.35").
1
l
g
▷ Ignition lance:
p
= 30 – 50 mbar,
gas
p
= 30 – 50 mbar.
air
Check flame stability and ionization current.
The gas and air pressure of the ignition lance
must be higher than the gas and air pressure of the main burner.
Loosen the screws 2 turns.
2
g

Commissioning

Igniting and adjusting the burner

WARNING
Ensure adequate ventilation of the furnace chamber before each burner start!
▷ The burner housing will become hot during op-
eration with preheated combustion air. Provide protection against accidental contact as required.
All valves of the installation must be checked for tightness before ignition.
Setting the low-fire rate:
Set the valves to ignition position.
Limit the maximum gas volume.
▷ Should an adjustable gas restrictor be installed
upstream of the burner, open the restrictor by approx. a quarter.
Open the gas supply.
Ignite the burner.
▷ The safety time of the automatic burner control
unit starts to elapse.
If no flame forms, check and adjust the gas and air pressures of the start gas adjustment.
In the case of operation with bypass (e.g. when using an air/gas ratio control): check the bypass nozzle and adjust if required.
In the case of operation without bypass (e.g.
l
when using an air/gas ratio control without by­pass):increase the low-fire rate setting.
Check the basic setting or bypass of the air con­trol valve.
Check the position of the restrictor in the air line.
Check the fan.
Reset the automatic burner control unit and re-
ignite the burner.
▷ The burner ignites and proceeds to normal op-
eration.
Check flame stability and ionization current at low fire. Switch-off threshold – see automatic burner control unit operating instructions.
Z
+ μA
I
Monitor flame formation.
Adjust the low-fire rate settings if required.
If no flame forms – see page 11 (Assistance
in the event of malfunction).
GB-8
F
NL
I
E
Setting the high-fire rate:
p
0
p
2
p
1
Set the air and gas circuit of the burner to high fire while continuously monitoring the flame.
Avoid CO formation – always operate the burner with excess air when starting up!
▷ When the desired maximum valve positions are
reached, set the gas pressure p restrictor upstream of the burner.
p
atm.
p
gas
0
using the
gas
Re-adjusting the air flow rate:
Check the air pressure p adjust using the air restrictor if required.
on the burner and
air
When using air restricting orifices: check the air pressure p
and rework the orifice if required.
air
DANGER
Risk of explosion and poisoning during burner adjustment with an air deficiency! Adjust the
gas and air supply so that the burner is always oper­ated with excess air – otherwise CO will form in the furnace chamber. CO is odourless and poisonous! Conduct a flue gas analysis.
Measure the gas and air flow rates if possible. Determine the lambda value and re-adjust the settings if required.

Tightness test

DANGER
To ensure that there is no danger resulting from a
leak, check the gas connections on the burner for leaks immediately after the burner has been put into operation.
1

Cooling air

▷ While the burner is switched off and depending
on the furnace temperature, there must be a cer­tain air flow for cooling the burner components.
ZIO
6
5
4
Cooling air at 20°C,
3
2
air volume at rated capacity [%]
1
0
700 800 900 1000 1100 1200 1300 1400
Diagram: the relative air volume in percentage
ZIO..K
ZIO..KB..E
Furnace temperature [°C]
12
10
8
Cooling air at 450°C,
6
4
2
0
values, based on the air volume for the rated ca­pacity of the relevant size, is given in the diagram. For hot air (450°C), the values on the right-hand axis are based on the standard air volume for the relevant rated capacity.
▷ Leave the air fan switched on until the furnace
has cooled down completely.
Blocking and recording the settings  Produce a measurement report. Set the burner to low fire and check the settings.
 Set the burner to low and high fire several times
while monitoring the pressure settings, flue gas values and flame patterns.
4 Remove the measuring devices and close off
the test nipples – tighten the grub screws.
5 Block and seal the adjusting elements. 6 Induce a flame failure, e.g. by pulling the plug off
the ionization electrode. The flame detector must close the gas safety valve and signal a fault.
7 Switch the system on and off several times while
monitoring the automatic burner control unit.
8 Produce an acceptance report.
]
air volume at rated capacity [%
GB
Avoid condensation due to the furnace atmos­phere entering the burner housing. While the burner is switched off, at furnace temperatures above 500°C (932°F), it must be cooled with a low air volume – see page 9 (Cooling air).
DANGER
An incorrect change of the burner settings may change the gas/air ratio and lead to unsafe oper­ating conditions. Risk of explosion in case of CO being formed in the furnace chamber! CO is odour­less and poisonous!
GB-9
F
NL
I
E

Maintenance

6 5
11 12
14
We recommend that a function check is carried out every six months.
WARNING
Risk of burning! Outflowing flue gases and burner components are hot.
Check the ionization and ignition cables. Measure the ionization current.
▷ The ionization current must be at least 5 µA and
must not vary.
Checking the burner
13
15
GB
Z
+ μA
I
Disconnect the system from the electrical power
supply.
4 Shut off the gas and air supply – do not change
the restrictor settings.
Checking the ignition and ionization electrodes
Ensure that the electrode length does not change.
7 Remove dirt from electrodes or insulators.
3
2
1
8 If the star 4 or insulator is damaged, replace
the electrode. Before changing the electrode, measure the
total length L.
9 Connect the new electrode with the spark plug
using the dowel pin .
0 Adjust spark plug and electrode to the measured
total length L.
L
16
If the burner insert is dismantled, the gas housing gasket will have to be renewed.
7 Place the burner insert in a safe place.
Depending on the amount of dirt or wear: replace the ignition/ionization electrode rod and dowel pin during servicing – see page 10 (Checking the ignition and ionization electrodes).
8 Check burner head for dirt and thermal cracks.
WARNING
Risk of injury! Burner heads have sharp edges.
4
When replacing any burner components: ap­ply ceramic paste to the screw connections in order to avoid cold-setting – see page 12 (Accessories).
9 Check the electrode positions.
▷ The insulator must be flush with the front edge
of the burner air disc.
Distance of ignition electrode from ground pin or gas nozzle: 2 ± 0.5 mm (0.08 ± 0.02").
)
Turning the spark plug makes it easier to feed
the electrode into the burner insert.
GB-10
mm
0,5
2 ±
0.02"
(0.08 ±
F
NL
I
E
0 When the furnace chamber has cooled down,
21
27
check the burner tube and burner quarl through the furnace flange.
New gas housing gasket.
22

Assistance in the event of malfunction

DANGER
Electric shocks can be fatal! Before working on possible live components, ensure the unit is discon­nected from the power supply. Risk of injury! Burner heads have sharp edges. Fault-clearance must only be undertaken by author­ized trained personnel.
▷ If no fault is detected when checking the burner,
proceed to the automatic burner control unit and check for faults in accordance with the relevant operating instructions.
GB
23
Tighten the burner insert with max. 37 Nm
24
(27.3lbft).
5 Connect the system to the electrical power sup-
ply.
6 Open the gas and air supply.
8 Set the burner to low fire and compare the pres-
sure settings to those stated in the acceptance report.
9 Set the burner to low and high fire several times
while monitoring the pressure settings, flue gas values and flame patterns.
? Faults ! Cause
Remedy
? Burner does not function? ! Valves do not open.
Check the voltage supply and wiring.
! Tightness control signals a fault.
Check the valves for tightness.
Note the tightness control operating instructions.
! Control valves do not move to low-fire position.
Check the impulse lines.
! Gas inlet pressure is too low.
Check the filter for dirt.
! Gas and air pressures on the burner are too low.
Check the restrictors.
! Automatic burner control unit signals a fault.
Check the ionization cables and ionization cur­rent.
Check whether the burner is adequately ground­ed.
Note the automatic burner control unit operating instructions.
DANGER
Risk of explosion and poisoning during burner adjustment with an air deficiency! Adjust the
gas and air supply so that the burner is always oper­ated with excess air – otherwise CO will form in the furnace chamber. CO is odourless and poisonous! Conduct a flue gas analysis.
0 Produce a maintenance report.
GB-11
F
NL
I
E
? Burner performs a fault lock-out after burn-
ing faultlessly in normal operation?
! Incorrect gas and air flow rate settings.
Check the gas and air pressures.
! No ignition spark is created.
Check the ignition cable.
Check the voltage supply and wiring.
Check whether the burner is adequately ground-
ed.
Check the electrodes – see page 10 (Checking the ignition and ionization electrodes).
! Automatic burner control unit signals a fault.
GB
Check the ionization cable.
Measure the ionization current by connecting a
micro-ammeter into the ionization cable: min. 5µA ionization current – stable signal.
Z
+ μA
I
! Burner head dirty.
Clean gas and air bore holes and air slots.
Remove deposits on the burner head.
WARNING
Risk of injury! Burner heads have sharp edges.
! Excessive pressure fluctuations in the furnace
chamber.
Ask Elster Kromschröder for control concepts.

Accessories

Ceramic paste
Apply ceramic paste to the relevant screw connec­tions after replacing any burner components in order to avoid cold-setting. Order number: 05012009.
Adapter set
For connecting ZIO to NPT/ANSI connections.
Burner Adapter set Order No. ZIO 165 ZIO 200
BR 165 NPT BR 200 NPT
Nozzle set
Available on request for connecting integrated ignition lances to NPT threads.

Technical data

Gas supply pressure: approx. 20 to 50 mbar, air supply pressure: approx. 25 to 40 mbar, each depending on flame shape, gas type and air temperature (gas and air pressures – see operating characteristic diagrams at www.docuthek.com). Burner length increments: 100 mm. Gas types: natural gas, LPG (gaseous) and coke oven gas; other gases on request. Heating: direct using a burner quarl or an attachment tube, indirect using a burner attachment tube inside the radiant tube. Control type: staged: On/Off, High/Low/Off, continuous: constant λ value. Most of the burner components are made of corro­sion-resistant stainless steel. Housing:
ZIO: St.
Flame control: with ionization electrode (UV sensor as an option). Ignition: direct spark ignition; ignition lance as an option. Maximum furnace temperature: in the burner quarl: up to 1450°C (higher tempera­tures on request),
with burner attachment tube: up to 600°C.
Maximum air temperature: ZIO: 450°C, ZIOW: 500°C.
GB-12
74922636 74922637
F
NL
I
E
Storage temperature: -20°C to +40°C.
Sandra Runde
Die speziellen technischen Unterlagen gemäß Anhang VII B wurden erstellt und werden der zuständigen nationalen Behörde auf
Burner Weight* [kg] ZIO 165 26 ZIO 200 37
* Shortest overall length.
WARNING
applies to ZIOW only Information pursuant to REACH Regulation No.
1907/2006, Article 33. Insulation contains refrac-
tory ceramic fibres (RCF)/aluminium silicate wool (ASW). RCF/ASW are listed in the Candidate List of the European REACH Regulation No. 1907/2006.

Logistics

Transport
Protect the unit from external forces (blows, shocks, vibration). On receipt of the product, check that the delivery is complete, see page 2 (Part designa­tions). Report any transport damage immediately.
Storage
Store the product in a dry and clean place. Storage temperature: see page 12 (Technical data) Storage time: 2 years before using for the first time. If stored for longer than this, the overall service life will be reduced accordingly (by the corresponding amount of extra storage time).
Packaging
The packaging material is to be disposed of in ac-
cordance with local regulations.
Disposal
Components are to be disposed of separately in accordance with local regulations.

Declaration of Incorporation

according to 2006/42/EC, Annex II, No. 1B
The product ZIO is a partly completed machine pur-
suant to Article 2g and is designed exclusively for installation in or assembly with another machine or other equipment.
The following essential health and safety requirements
in accordance with Annex I of this Directive are ap-
plicable and have been fulfilled: Annex I, Articles 1.1.3, 1.1.5, 1.3.2, 1.3.4, 1.5.2, 1.7.4 The relevant technical documentation has been com-
piled in accordance with part B of Annex VII and will
be sent to the relevant national authorities on request
as a digital file. The following (harmonized) standards have been
applied:
– EN 746-2 (2010) – Industrial thermoprocessing
equipment; Safety requirements for combustion and fuel handling systems
– EN ISO 12100 (2010) – Safety of machinery –
General principles for design – Risk assessment and risk reduction (ISO 12100:2010)
The partly completed machine may only be commis-
sioned once it has been established that the machine
into which the product mentioned above is to be
incorporated complies with the provisions of the
Machinery Directive 2006/42/EC.
Elster GmbH
Einbauerklärung / Declaration of Incorporation
nach 2006/42/EG, Anhang II, Nr. 1B / according to 2006/42/EC, Annex II No. 1B
Folgendes Produkt / The following product:
Bezeichnung: Brenner für Gas
Description Burner for gas
Typenbezeichnung / Type: BIO, BIOA, ZIO, BIC, BICA, ZIC
ist eine unvollständige Maschine nach Artikel 2g und ausschließlich zum Einbau in oder zum Zusammenbau mit einer anderen Maschine oder Ausrüstung vorgesehen.
is a partly completed machine pursuant to Article 2g and is designed exclusively for installation in or assembly with another machine or other equipment.
Folgende grundlegende Sicherheits- und Gesundheitsschutzanforderungen gemäß Anhang I dieser Richtlinie kommen zur Anwendung und wurden eingehalten:
The following essential health and safety requirements in accordance with Annex I of this Directive are applicable and have been fulfilled:
Anhang I, Artikel / Annex I, Article
1.1.3, 1.1.5, 1.3.2, 1.3.4, 1.5.2, 1.7.4
Verlangen in elektronischer Form übermittelt.
The relevant technical documentation has been compiled in accordance with part B of Annex VII and will be sent to the relevant national authorities on request as a digital file.
Folgende (harmonisierte) Normen wurden angewandt: / The following (harmonized) standards have been applied:
EN 746-2:2010 – Industrielle Thermoprozessanlagen; Sicherheitsanforderungen an Feuerungen und Brennstoffführungssysteme
– Industrial thermoprocessing equipment; Safety requirements for combustion and fuel handling systems
EN ISO 12100:2010 – Sicherheit von Maschinen – Allgemeine Gestaltungsleitsätze – Risikobeurteilung
und Risikominderung (ISO 12100:2010)
– Safety of machinery – General principles for design – Risk assessment
and risk reduction (ISO 12100:2010)
BIOW, ZIOW, BICW, ZICW
GB
Die unvollständige Maschine darf erst dann in Betrieb genommen werden, wenn festgestellt wurde, dass die Maschine, in der das oben bezeichnete Produkt eingebaut werden soll, den Bestimmungen der Richtlinie für Maschinen (2006/42/EG) entspricht.
The partly completed machine may only be commissioned once it has been established that the machine into which the product mentioned above should be incorporated complies with the provisions of the Machinery Directive 2006/42/EC.
Lotte (Büren)
24.03.2014
Datum / Date
Sandra Runde ist bevollmächtigt, die speziellen technischen Unterlagen gemäß Anhang VII B zusammenzustellen.
Sandra Runde is authorized to compile the relevant technical documentation according to Annex VII B.
GB-13
Konstrukteurin / Designer
Elster GmbH
Postfach 28 09 D-49018 Osnabrück Strotheweg 1 D-49504 Lotte (Büren)
Tel. +49 (0)541 12 14-0 Fax +49 (0)541 12 14-3 70 info@kromschroeder.com www.kromschroeder.com
F
NL
I
E
Certification
Approval for Russia
Certified by Gosstandart under Technical Regulations. Approved by Rostekhnadzor (RTN).
GB

Contact

If you have any technical questions, please contact your local branch office/agent. The addresses are available on the Internet or from ElsterGmbH.
We reserve the right to make technical modifications in the interests of progress. info@kromschroeder.com, www.kromschroeder.com
Elster GmbH Postfach 28 09, D-49018 Osnabrück Strotheweg 1, D-49504 Lotte (Büren)
T +49 541 1214-0
F +49 541 1214-370
GB-14
Loading...