Please read through these instructions
carefully before installing or operating. Following the
installation, pass the instructions on to the operator. This unit must be installed and commissioned
in accordance with the regulations and standards
in force. These instructions can also be found at
www.docuthek.com.
Explanation of symbols
• , , 2 , 3 ... = Action
▷ = Instruction
Liability
We will not be held liable for damage resulting from
non-observance of the instructions and non-compliant use.
Safety instructions
Information that is relevant for safety is indicated in
the instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified
gas technicians. Electrical interventions may only be
carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM
spare parts.
Changes to edition 05.
The following chapters have been changed:
– Installation
– Certification
GB-1
GB
F
NL
I
E
Checking the usage
1
Intended use
VGP
Gas solenoid valve for safeguarding gas or air on
various appliances.
This function is only guaranteed when used within
the specified limits – see page7 (Technical data).
Any other use is considered as non-compliant.
Rated voltage, electrical power consumption, installation position, max. inlet pressure p
temperature, enclosure and medium: see type label.
D-49018 Osnabrück, Germany
emax.
, ambient
VGP
▷
The housing must not be in contact with masonry.
Minimum clearance 20mm.
> 20 mm
▷
Sealing material and dirt, e.g. thread cuttings,
must not be allowed to get into the valve housing.
▷ Install a filter upstream of every system.▷ Use approved sealing material only.▷ Use a suitable spanner.
231
4
GB-2
GB
F
NL
I
E
Wiring
Tightness test
WARNING
Electric shocks can be fatal! Before working on
possible live components, ensure the unit is disconnected from the power supply.
▷
The solenoid actuator heats up during operation
depending on ambient temperature and voltage.
> +80 °C
▷ The rectifier adapter must be installed.▷ Use temperature-resistant cable (>80°C).
Disconnect the system from the electrical power
supply.
2 Shut off the gas supply.
▷ Wiring to EN 60204-1.▷ The actuator can be rotated.
453
678
1 = N
2 = L
3
1
2
CAUTION
Please observe the following to ensure that the VGP
is not damaged during the tightness test:
– Check max. inlet pressure– see type label.
– Test pressure ≤1.5x max. inlet pressure.
Close the solenoid valve.
2 To be able to check the tightness, shut off the
downstream pipeline as close as possible to the
valve.
3
0
≤ 1,5 x p
N
2
0
4 Open the solenoid valve.
5
N
2
≤ 1,5 x p
6 Tightness OK: the unit is ready for operation.
7 Open the pipeline again and release the gas
supply.
▷ VGP leaking: dismantle the unit and return it to
the manufacturer.
e max
0
e max
▷ Plug insert can be rotated in 90° steps.
109
11
12
GB-3
GB
F
NL
I
E
Replacing the actuator
A
6
87
A
A
▷
We recommend replacing the entire actuator set
when replacing the actuator.
▷
Actuator set VGP10-15 comprises the actuator,
1xO-ring, 1x seal and 1x quick fastener.
▷
Actuator set VGP20-25 comprises the actuator
and 2xO-rings.
▷
The actuator set is available separately as a
spare part.
VGP
Disconnect the system from the electrical power
supply.
2 Shut off the gas supply.
345
VGP 0-5
6
▷ Do not remove the grounding springA.
910
87
11
4 The unit is ready for operation.
5 Release the gas supply.
Maintenance
▷ In order to ensure smooth operation: check the
tightness and function of the VGP every year, or
every six months if operated with biogas.
Checking tightness and function
▷ In order to determine whether the VGP is tight
and closes securely, check the internal and external tightness, see page3 (Tightness test).
▷
Check electrical installations in line with local regulations; pay particular attention to the PEwire,
see page3 (Wiring).
▷
We recommend replacing the entire seal set
when servicing the solenoid valve.
▷
Seal set VGP10-15 comprises the valve seal, 2x
O-rings, 1x seal and 1x quick fastener.
▷
Seal set VGP20-25 comprises the valve seal
and 3x O-rings.
▷
The seal set is available separately as a spare part.
VGP
Disconnect the system from the electrical power
supply.
2 Shut off the gas supply.
VGP 0-5
3
4
5
VGP 20-25
6
9
VGP
12
▷ Do not remove the grounding springA.
6
7
8
78
▷ Check closing spring for damage.▷
Closing spring damaged: dismantle the unit and
return it to the manufacturer.
10
11
9
10
11
13
14
12
13
14
GB-4
GB
F
NL
I
E
15
121113
14
16
15
16
17
17
1819
2123
22
VGP 20-25
3
6
4
7
109
20
CAUTION
Please observe the following to ensure that the
VGP is not damaged during subsequent operation:
– Install the closing spring in the correct position.
Ensure that the catch of the closing spring is
positioned in the opening of the valve disc.
5
18
21
8
23a
19
22
20
23
▷ Check closing spring for damage.
Closing spring damaged: dismantle the unit and
▷
return it to the manufacturer.
121113
VGP
24 Close the solenoid valve.
25 To be able to check the tightness, shut off the
downstream pipeline as close as possible to the
valve.
26
0
14
15
≤ 1,5 x p
N
2
e max
16
0
GB-5
GB
F
NL
I
E
27 Tightness OK: the unit is ready for operation.
28 Open the pipeline again and release the gas
supply.
Assistance in the event of
malfunction
! Guiding elements bent. Incorrect handling when
installing the unit.
WARNING
Electric shocks can be fatal! Before working on
possible live components, ensure the unit is disconnected from the power supply.
Fault-clearance must only be undertaken by authorized trained personnel.
Unauthorized repairs or incorrect electrical connections can cause the solenoid valve to become
defective. In this case, our warranty will be rendered void.
? Fault
! Cause
• Remedy
Possible faults and suggested solutions
? The solenoid valve does not open, there is
no flow downstream of the solenoid valve.
! There is no power supply.
• Check wiring, see page3 (Wiring).
! Rectifier adapter defective.
• Remove socket and rectifier adapter, see
page 4 (Replacing the actuator), steps
to 5 . Check the ohmic resistance of the rectifier
adapter between contacts and2. Note the
inscription on the rectifier adapter.
1
2
• Dismantle the unit and return it to the manufac-
turer.
? The solenoid valve does not close securely,
the flow downstream of the solenoid valve
does not stop.
! Valve seat is dirty.
• Clean the valve seat, see page 4 (Mainte-
nance).
• Install a filter upstream of the solenoid valve.
! Valve seat is damaged.
• Dismantle the unit and return it to the manufac-
turer.
! Valve seal is damaged or hardened.
• Replace the valve seal, see page4 (Mainte-
nance).
! Guiding elements bent. Incorrect handling when
installing the unit.
• Dismantle the unit and return it to the manufac-
turer.
• No resistance, replace adapter.
• The rectifier adapter is available separately as a
spare part.
! Actuator defective.
• Remove socket and rectifier adapter, see
page 4 (Replacing the actuator), steps
to 5 . Check the ohmic resistance of the actuator
between contacts (N) and 2(L). Read off the
contact assignment from the rectifier adapter.
1
2
• No resistance, change actuator, see page4
(Replacing the actuator).
• The actuator set is available separately as a spare
part.
GB-6
GB
F
NL
I
E
Technical data
Gas types: natural gas, town gas, LPG (gaseous),
biogas (max.0.1%-by-vol. H2S) or clean air;
other gases on request. The gas must be dry in
all temperature conditions and must not contain
condensate.
Opening time: 0.5s.
Closing time: <1s.
Ambient temperature: -20to+60°C.
Long-term use in the upper ambient temperature
range accelerates the ageing of the elastomer materials and reduces the service life (please contact
manufacturer).
Storage temperature: -20to+40°C.
Safety valve:
Class A, Group 2 pursuant to EN161.
Mains voltage:
230 V AC, +10/-15%, 50/60 Hz,
120 V AC, +10/-15%, 50/60 Hz.
Electrical connection:
plug with socket to EN175301-803.
Power consumption:
120/
230 V
AC
Type
VGP 1026
VGP 1526
VGP 2035
VGP 2535
Enclosure: IP 54.
Duty cycle: 100%.
Power factor of the solenoid coil: cosϕ=1.
Solenoid coil insulation: class F insulating material.
Switching frequency: any.
Valve housing: aluminium,
valve disc: Perbunan.
Internal thread: Rp to ISO7-1.
[W]
Designed lifetime
This information on the designed lifetime is based on
using the product in accordance with these operating
instructions. Once the designed lifetime has been
reached, safety-relevant products must be replaced.
Designed lifetime (based on date of manufacture) in
accordance with EN 161 for VGP:
Designed lifetime
Type
Switching
cycles
Time
[years]
VGP 10 to 15200,00010
VGP 20 to 25500,00010
You can find further explanations in the applicable
rules and regulations and on the afecor website
(www.afecor.org).
This procedure applies to heating systems. For
thermoprocessing equipment, observe local regulations.
Logistics
Transport
Protect the unit from external forces (blows, shocks,
vibration). On receipt of the product, check that the
delivery is complete, see page2 (Part designations). Report any transport damage immediately.
Storage
Store the product in a dry and clean place.
Storage temperature: see page7 (Technical data).
Storage time: 6months in the original packaging
before using for the first time. If stored for longer
than this, the overall service life will be reduced by
the corresponding amount of extra storage time.
Packaging
The packaging material is to be disposed of in ac-
cordance with local regulations.
Disposal
Components are to be disposed
GB-7
GB
F
NL
I
E
Certification
AGA
Declaration of conformity
We, the manufacturer, hereby declare that the product
VGP, marked with product ID No. CE-0063BL1554,
complies with the requirements of the listed Directives and Standards.
Directives:
– 2009/142/EC – GAD (valid until 20 April 2018)
– 2014/30/EU
– 2014/35/EU
Regulation:
– (EU) 2016/426 – GAR (valid from 21 April 2018)
The relevant product corresponds to the tested type
sample.
The production is subject to the surveillance proce-
dure pursuant to Directive 2009/142/EC AnnexII
paragraph 3 (valid until 20 April 2018) and to Regula-
tion (EU) 2016/426 Annex III paragraph 3 (valid from
21 April 2018).
Elster GmbH
Scan of the Declaration of conformity (D, GB) – see
www.docuthek.com
Approval for Australia
Australian Gas Association, Approval No.:5567
www.aga.asn.au/product_directory
Eurasian Customs Union
The product VGP meets the technical specifications
of the Eurasian Customs Union.
Contact
If you have any technical questions, please contact
your local branch office/agent. The addresses are
available on the Internet or from ElsterGmbH.
We reserve the right to make technical modifications
in the interests of progress.
hts.lotte@honeywell.com, www.kromschroeder.com
GB-8
Strotheweg 1, D-49504 Lotte (Büren)
Fax +49 541 1214-370
Elster GmbH
Tel. +49 541 1214-0