Please read through these instructions
carefully before installing or operating. Following the
installation, pass the instructions on to the operator. This unit must be installed and commissioned
in accordance with the regulations and standards
in force. These instructions can also be found at
www.docuthek.com.
Explanation of symbols
• , , , ... = Action
▷ = Instruction
Liability
We will not be held liable for damage resulting from
non-observance of the instructions and non-compliant use.
Safety instructions
Information that is relevant for safety is indicated in
the instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified
gas technicians. Electrical interventions may only be
carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM
spare parts.
Changes to edition 0.4
The following chapters have been changed:
– Checking the usage
– Installation
– Tightness test
– Maintenance
– Certification
GB-1
GB
F
NL
I
E
Checking the usage
Vor dem Öffnen Feder entspannen!
Release springbefore opening!
Avant d’ouvrir le dôme, détendre le ressort!
423
Intended use
The gas pressure regulator VGBF serves to maintain
a constant outlet pressure pd despite changing gas
flow rates and inlet pressures pu in gas pipelines.
This function is only guaranteed when used within
the specified fields of application – see page 5
(Technical data).
Any other use is considered as non-compliant.
Type code
CodeDescription
VGBFGas pressure regulator
5 – 50Nominal size
R
F
05
0
40
-
-
Screw plug at the inlet and outlet
V
Medium: air and aggressive gases
(check compatibility with Viton)
Part designations
1
9
8
2
4
10
7
3
Cover cap and adjusting screw
Breather screw
Impulse line connection (not on VGBF..05)
4 Outlet
5 Outlet (pd) measuring connection
6 Arrow of direction of flow
7 Inlet (pu) measuring connection
8 Inlet
9 Type label
0
Damping valve for VGBF 40 – 100..40
Inlet pressure pu, outlet pressure pd and ambient
temperature: see type label.
VGBF
CE: 0085AQ0973
Rp internal thread
Flange to ISO 7005
p
500 mbar
u max.
p
1 bar
u max.
p
4 bar
Screw plug at the inlet
u max.
Material for wetted parts:
Viton (without approval)
VGBF..FVGBF..R
1
9
8
2
3
4
566
7
Installation
CAUTION
Please observe the following to ensure that the
gas pressure regulator is not damaged during the
installation:
– Install the unit free of mechanical stress.
– Do not clamp the unit in a vice or use it as a
lever. Risk of external leakage.
– Sealing material, cuttings and other impurities
must not be allowed to get into the regulator
housing.
– The installation location must be dry. Do not
store or install the unit in the open air.
– Dropping the device can cause permanent dam-
age. In this event, replace the entire device and
associated modules before use.
– Installation in the horizontal position, never up-
side down. VGBF 15 – 50 can also be installed
in the vertical position.
▷ The outlet pressure pd is set at the factory with
the spring dome pointing vertically upwards.
VGBF 15 – 50: if installed with the spring dome
in the horizontal position, check and adjust the
outlet pressure pd, see page 4 (Changing
the outlet pressure pd).
▷
The housing must not touch any surrounding walls.
Minimum clearance 20 mm. Ensure that there is
sufficient space for installation and adjustment.
Install a filter upstream of the unit, in order to
protect it against impurities in the pipeline.
VGBF..F
VGBF..R
423
5
GB-2
GB
F
NL
I
E
Installing the impulse line
312
VGBF 40 – 50..05 for 500 mbar
▷ No external impulse line required. VGBF..05 fea-
tures an internal feedback function.
VGBF 40 – 00..40 for 4 bar
▷ In order to avoid possible oscillations, a damp-
ing valve should be fitted. The damping valve is
secured to the spring dome with an adhesive
strip on delivery.
▷ Impulse line: 12 × 1.5 mm.
VGBF 40 – 00
CAUTION
– First apply the inlet pressure pu – then the outlet
pressure pd.
– The inlet pressure pu must always be equal to
or higher than the outlet pressure pd.
– In the event of non-compliance with the se-
quence, the inlet pressure compensation dia
phragm will reverse.
2.
p
1.
d
p
u
54
-
Push union
nut and
compression
fitting onto
the impulse
line.
54
76
VGBF 5 – 00..0 for bar and
VGBF 5 – 00..40 for 4 bar
6 Install the impulse line and seal with an approved
sealing material.
VGBF 5 – 5R
Rp 1/
4
5xDN
98
1110
VGBF 40 – 50
Rp 3/
8
5xDN
1.
2.
p
d
p
Tightness test
u
Relieve the outlet pressure pd.
WARNING
Relieve the inlet pressure pu.
If gas-filled spaces have been opened, check them
for tightness.
Block the pipeline at the inlet and outlet.
Slowly apply inlet pressure p
(pu ≤ 1.5 × p
Slowly apply outlet pressure p
(p
≤ 1.5 × pd, see type table)
d
u max.
, see type label)
.
u
.
d
GB-3
GB
F
NL
I
E
Changing the outlet pressure pd
▷ The outlet pressure pd is set at the factory with
the spring dome pointing vertically upwards. If
the VGBF is installed with the spring dome in
the horizontal position, check and adjust the
outlet pressure pd.
▷ Use the test points on the unit only for measure-
ments of zero flow or very slight flow.
21
0
p
d
43
6 mm
-+
5 Clearly mark the adjusted value of the outlet
pressure pd on the type label.
Checking the function
Request different outputs on the burner in order
to change the flow rate.
Close the manual valve at the inlet a little in order
to change the inlet pressure pu.
▷ Despite changing flow rates and inlet pressures
pu (within the capacity range of the VGBF), the
outlet pressure pd must remain constant
(±10–15%).
Reduce the capacity to low-fire rate and close
the valve downstream of the VGBF.
▷
Approx. 30 seconds after the valve has been
closed, the outlet pressure pd should not in-
crease significantly.
Check the tightness of the VGBF during operation
to detect possible leaks due to hardened rubber
materials.
54
WARNING
Risk of injury!
– The taut spring can pop out when opening the
spring dome. Therefore, decompress the spring
as far as it will go before opening. Then turn
back 5 × to relax the spring counter bearing.
6 mm
786
VGBF 5 – 50
9 Turn down the spring counter bearing slightly.
1011
Ensure that the guide grooves and bars engage
in each other.
VGBF 65 – 50
9 Turn down the spring counter bearing slightly.
1011
Ensure that the guide groove and the cylinder
engage in each other.
VGBF 5 – 50
534
5x
1413
6 mm
6 If a leak is found, replace the rubber materials.
▷ Selecting spare parts:
see www.adlatus.org, Part Detective.
7 Then check for tightness once again.
Replacing the spring
Choose a spring according to the outlet pressure
range (see page 6 (Spring table)).
Remove the cover cap.
0
p
d
5 Screw on cover cap.
6 After inserting the spring, take the spring’s label
from the packaging and stick it below the type
label on the pressure regulator.
7 Clearly mark the adjusted value of the outlet
pressure pd on the type label.
GB-4
-+
GB
F
NL
I
E
Maintenance
In order to ensure smooth operation, check the tightness and function of the gas pressure regulator every
year, or every six months if operated with biogas, see
page 4 (Checking the function) and page 3
(Tightness test).
▷
Spare parts, see www.adlatus.org, PartDetective.
▷ If gas-filled space has been opened, check the
tightness and function, see page 3 (Tightness
test) and page 4 (Checking the function).
Technical data
Gas type: natural gas, town gas, LPG (gaseous)
and biogas, VGBF..V for air.
Outlet pressure ranges:
The outlet pressure range is achieved through the
use of different springs (see page 6 (Spring
table)).
Rp 1/4 connection for test points or even for a
pilot gas line:
at the inlet: VGBF 15 and 25,
at inlet and outlet: VGBF 40 – 150.
Ambient temperature: -15 to +60°C,
VGBF..V: 0 to 60°C.
No condensation permitted.
Long-term use in the upper ambient temperature
range accelerates the ageing of the elastomer materials and reduces the service life (please contact
manufacturer).
Storage temperature: -15 to +40°C,
VGBF..V: 0 to 40°C.
Strainers that are possibly fitted serve as flow
conditioners.
Housing: aluminium,
diaphragms: NBR or Viton,
valve seat: aluminium,
valve stem: aluminium,
valve disc: vulcanized NBR or Viton seal.
Internal thread: Rp to ISO 7-1,
flanged connection: PN 16 to ISO 7005,
DN 15 – 50 with NPT thread,
DN 50 – 100 available with ANSI flange.
Impulse line connections: NPT.
Weight [kg]:
VGBF..40
Max. inlet pressure p
Feedback via impulse line:
u max.
: 4 bar.
Rp 1/4 connection for DN 15 and 25,
Rp 3/8 connection for DN 40 – 100.
EN 334, Accuracy Class AC 10, Lock up pressure
class SG 30.
VGBF..05
Max. inlet pressure p
Internal feedback.
u max.
: 500 mbar.
EN 88, Class A, Group 2.
Designed lifetime
This information on the designed lifetime is based on
using the product in accordance with these operating
instructions. Once the designed lifetime has been
reached, safety-relevant products must be replaced.
Designed lifetime (based on date of manufacture) in
accordance with EN 13611 and EN 88 for VGBF:
15 years.
You can find further explanations in the applicable
rules and regulations and on the afecor website
(www.afecor.org).
This procedure applies to heating systems. For
thermoprocessing equipment, observe local regu-
lations.
Logistics
Transport
Protect the unit from external forces (blows, shocks,
vibration). On receipt of the product, check that the
delivery is complete (see page 2 (Part designa-
tions)). Report any transport damage immediately.
Storage
Store the product in a dry and clean place.
Storage temperature: see page 5 (Technical data).
Storage time: max. 6 months before using for the
first time.
Packaging
The packaging material is to be disposed of in ac-
Rp 1/4 connection for DN 15 and 25,
Rp 3/8 connection for DN 40 – 150.
EN 334, Accuracy Class AC 10, Lock up pressure
class SG 30.
GB-5
GB
F
NL
I
E
Certification
Declaration of conformity
We, the manufacturer, hereby declare that the product VGBF with product ID No. CE-0085AQ0973 complies with the requirements of the listed Directives
and Standards.
VGBF 15 to VGBF 150:
lance procedure pursuant to Directive 2009/142/EC
AnnexII paragraph 3 (valid until 20 April 2018) and
to Regulation (EU) 2016/426 Annex III paragraph3
(valid from 21 April 2018) and for VGBF 100F40 according to annex III, module D1 of Directive 97/23/EC.
This declaration of conformity is issued under the
sole responsibility of the manufacturer.
Elster GmbH
Directive:
– 2009/142/EC – GAD (valid until 20 April 2018)
Regulation:
Scan of the Declaration of conformity (D, GB) – see
www.docuthek.com
– (EU) 2016/426 – GAR (valid from 21 April 2018)
Standards:
– DIN EN 88-1:2011
Eurasian Customs Union
– DIN EN 88-2:2008
– DIN EN 334:2009
VGBF 100F40:
Directive:
– 97/23/EC
The relevant product corresponds to the tested type
The product VGBF meets the technical specifications