Operating instructions

Gas pressure regulators VGBF

© 2018 Elster GmbH · Edition 03.18
Translation from the German

Contents

Gas pressure regulators VGBF............
Contents ..............................
Safety.................................
Checking the usage .....................
Intended use ...........................2
Type code .............................2
Part designations ........................2
Installation ............................
Installing the impulse line ................
Tightness test .........................
Changing the outlet pressure p
Checking the function ...................4
Replacing the spring ....................4
Maintenance ...........................5
Technical data .........................5
Designed lifetime ........................5
Logistics ..............................5
Certification ...........................6
Declaration of conformity ..................6
Eurasian Customs Union ..................6
Spring table............................6
Contact ...............................6
..........4
d

Safety

Please read and keep in a safe place
Please read through these instructions carefully before installing or operating. Following the installation, pass the instructions on to the opera­tor. This unit must be installed and commissioned in accordance with the regulations and standards in force. These instructions can also be found at www.docuthek.com.
Explanation of symbols
• ,  ,  ,  ... = Action
= Instruction
Liability
We will not be held liable for damage resulting from non-observance of the instructions and non-com­pliant use.
Safety instructions
Information that is relevant for safety is indicated in the instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified gas technicians. Electrical interventions may only be carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM spare parts.
Changes to edition 0.4
The following chapters have been changed: – Checking the usage – Installation – Tightness test – Maintenance – Certification
GB-1
GB
F
NL
I
E

Checking the usage

Vor dem Öffnen Feder entspannen!
Release spring before opening!
Avant d’ouvrir le dôme, détendre le ressort!
42 3

Intended use

The gas pressure regulator VGBF serves to maintain
a constant outlet pressure pd despite changing gas flow rates and inlet pressures pu in gas pipelines.
This function is only guaranteed when used within
the specified fields of application – see page 5 (Technical data). Any other use is considered as non-compliant.

Type code

Code Description
VGBF Gas pressure regulator 5 – 50 Nominal size R F 05 0 40
-
-
Screw plug at the inlet and outlet
V
Medium: air and aggressive gases
(check compatibility with Viton)

Part designations

1
9
8
2
4
10
7
3
Cover cap and adjusting screwBreather screwImpulse line connection (not on VGBF..05) 4 Outlet 5 Outlet (pd) measuring connection 6 Arrow of direction of flow 7 Inlet (pu) measuring connection 8 Inlet 9 Type label
0
Damping valve for VGBF 40 – 100..40
Inlet pressure pu, outlet pressure pd and ambient temperature: see type label.
VGBF
CE: 0085AQ0973
Rp internal thread
Flange to ISO 7005
p
500 mbar
u max.
p
1 bar
u max.
p
4 bar
Screw plug at the inlet
u max.
Material for wetted parts:
Viton (without approval)
VGBF..FVGBF..R
1
9
8
2
3
4
566
7

Installation

CAUTION
Please observe the following to ensure that the gas pressure regulator is not damaged during the
installation: – Install the unit free of mechanical stress. – Do not clamp the unit in a vice or use it as a
lever. Risk of external leakage.
– Sealing material, cuttings and other impurities
must not be allowed to get into the regulator housing.
– The installation location must be dry. Do not
store or install the unit in the open air.
– Dropping the device can cause permanent dam-
age. In this event, replace the entire device and associated modules before use.
– Installation in the horizontal position, never up-
side down. VGBF 15 – 50 can also be installed in the vertical position.
▷ The outlet pressure pd is set at the factory with
the spring dome pointing vertically upwards.
VGBF 15 – 50: if installed with the spring dome
in the horizontal position, check and adjust the outlet pressure pd, see page 4 (Changing the outlet pressure pd).
The housing must not touch any surrounding walls.
Minimum clearance 20 mm. Ensure that there is sufficient space for installation and adjustment.
Install a filter upstream of the unit, in order to
protect it against impurities in the pipeline.
VGBF..F
VGBF..R
42 3
5
GB-2
GB
F
NL
I
E

Installing the impulse line

31 2
VGBF 40 – 50..05 for 500 mbar
▷ No external impulse line required. VGBF..05 fea-
tures an internal feedback function.
VGBF 40 – 00..40 for 4 bar
▷ In order to avoid possible oscillations, a damp-
ing valve should be fitted. The damping valve is secured to the spring dome with an adhesive strip on delivery.
▷ Impulse line: 12 × 1.5 mm.
VGBF 40 – 00
CAUTION
– First apply the inlet pressure pu – then the outlet
pressure pd.
– The inlet pressure pu must always be equal to
or higher than the outlet pressure pd.
– In the event of non-compliance with the se-
quence, the inlet pressure compensation dia phragm will reverse.
2.
p
1.
d
p
u
54
-
Push union nut and compression fitting onto the impulse line.
54
76
VGBF 5 – 00..0 for  bar and VGBF 5 – 00..40 for 4 bar 6 Install the impulse line and seal with an approved
sealing material.
VGBF 5 – 5R
Rp 1/
4
5xDN
98
1110
VGBF 40 – 50
Rp 3/
8
5xDN
1.
2.
p
d
p

Tightness test

u
 Relieve the outlet pressure pd.
WARNING
 Relieve the inlet pressure pu.
If gas-filled spaces have been opened, check them for tightness.
Block the pipeline at the inlet and outlet. Slowly apply inlet pressure p
(pu ≤ 1.5 × p
Slowly apply outlet pressure p
(p
≤ 1.5 × pd, see type table)
d
u max.
, see type label)
.
u
.
d
GB-3
GB
F
NL
I
E

Changing the outlet pressure pd

▷ The outlet pressure pd is set at the factory with
the spring dome pointing vertically upwards. If the VGBF is installed with the spring dome in the horizontal position, check and adjust the outlet pressure pd.
▷ Use the test points on the unit only for measure-
ments of zero flow or very slight flow.
21
0
p
d
43
6 mm
-+
5 Clearly mark the adjusted value of the outlet
pressure pd on the type label.

Checking the function

Request different outputs on the burner in order
to change the flow rate.
Close the manual valve at the inlet a little in order
to change the inlet pressure pu.
▷ Despite changing flow rates and inlet pressures
pu (within the capacity range of the VGBF), the outlet pressure pd must remain constant (±10–15%).
Reduce the capacity to low-fire rate and close
the valve downstream of the VGBF.
Approx. 30 seconds after the valve has been closed, the outlet pressure pd should not in-
crease significantly. Check the tightness of the VGBF during operation to detect possible leaks due to hardened rubber materials.
54
WARNING
Risk of injury!
– The taut spring can pop out when opening the
spring dome. Therefore, decompress the spring as far as it will go before opening. Then turn back 5 × to relax the spring counter bearing.
6 mm
7 86
VGBF 5 – 50 9 Turn down the spring counter bearing slightly.
10 11
 Ensure that the guide grooves and bars engage
in each other.
VGBF 65 – 50 9 Turn down the spring counter bearing slightly.
10 11
 Ensure that the guide groove and the cylinder
engage in each other.
VGBF 5 – 50
53 4
5x
1413
6 mm
6 If a leak is found, replace the rubber materials.
▷ Selecting spare parts:
see www.adlatus.org, Part Detective.
7 Then check for tightness once again.

Replacing the spring

Choose a spring according to the outlet pressure
range (see page 6 (Spring table)). Remove the cover cap.
0
p
d
5 Screw on cover cap. 6 After inserting the spring, take the spring’s label
from the packaging and stick it below the type label on the pressure regulator.
7 Clearly mark the adjusted value of the outlet
pressure pd on the type label.
GB-4
-+
GB
F
NL
I
E

Maintenance

In order to ensure smooth operation, check the tight­ness and function of the gas pressure regulator every year, or every six months if operated with biogas, see page 4 (Checking the function) and page 3 (Tightness test).
Spare parts, see www.adlatus.org, PartDetective.
▷ If gas-filled space has been opened, check the
tightness and function, see page 3 (Tightness test) and page 4 (Checking the function).

Technical data

Gas type: natural gas, town gas, LPG (gaseous) and biogas, VGBF..V for air. Outlet pressure ranges:
The outlet pressure range is achieved through the
use of different springs (see page 6 (Spring table)). Rp 1/4 connection for test points or even for a pilot gas line: at the inlet: VGBF 15 and 25, at inlet and outlet: VGBF 40 – 150. Ambient temperature: -15 to +60°C, VGBF..V: 0 to 60°C. No condensation permitted. Long-term use in the upper ambient temperature range accelerates the ageing of the elastomer ma­terials and reduces the service life (please contact manufacturer). Storage temperature: -15 to +40°C, VGBF..V: 0 to 40°C. Strainers that are possibly fitted serve as flow conditioners. Housing: aluminium, diaphragms: NBR or Viton, valve seat: aluminium, valve stem: aluminium, valve disc: vulcanized NBR or Viton seal. Internal thread: Rp to ISO 7-1, flanged connection: PN 16 to ISO 7005, DN 15 – 50 with NPT thread, DN 50 – 100 available with ANSI flange. Impulse line connections: NPT. Weight [kg]:
VGBF..40
Max. inlet pressure p Feedback via impulse line:
u max.
: 4 bar.
Rp 1/4 connection for DN 15 and 25, Rp 3/8 connection for DN 40 – 100. EN 334, Accuracy Class AC 10, Lock up pressure class SG 30.
VGBF..05
Max. inlet pressure p Internal feedback.
u max.
: 500 mbar.
EN 88, Class A, Group 2.

Designed lifetime

This information on the designed lifetime is based on
using the product in accordance with these operating instructions. Once the designed lifetime has been reached, safety-relevant products must be replaced. Designed lifetime (based on date of manufacture) in
accordance with EN 13611 and EN 88 for VGBF: 15 years. You can find further explanations in the applicable
rules and regulations and on the afecor website
(www.afecor.org). This procedure applies to heating systems. For
thermoprocessing equipment, observe local regu-
lations.

Logistics

Transport
Protect the unit from external forces (blows, shocks,
vibration). On receipt of the product, check that the
delivery is complete (see page 2 (Part designa-
tions)). Report any transport damage immediately.
Storage
Store the product in a dry and clean place.
Storage temperature: see page 5 (Technical data).
Storage time: max. 6 months before using for the
first time.
Packaging
The packaging material is to be disposed of in ac-
cordance with local regulations.
Disposal
Components are to be disposed of separately in
accordance with local regulations.
Type Weight Type Weight VGBF 15R 0.9 VGBF 65F 12.0 VGBF 25R 1.9 VGBF 80F 16.1 VGBF 40R 2.9 VGBF 100F 26.0 VGBF 40F 4.8 VGBF 150F 46.5 VGBF 50F 7.7
VGBF..0
Max. inlet pressure p Feedback via impulse line:
u max.
: 1 bar.
Rp 1/4 connection for DN 15 and 25, Rp 3/8 connection for DN 40 – 150. EN 334, Accuracy Class AC 10, Lock up pressure class SG 30.
GB-5
GB
F
NL
I
E
Certification

Declaration of conformity

We, the manufacturer, hereby declare that the prod­uct VGBF with product ID No. CE-0085AQ0973 com­plies with the requirements of the listed Directives and Standards. VGBF 15 to VGBF 150:
lance procedure pursuant to Directive 2009/142/EC AnnexII paragraph 3 (valid until 20 April 2018) and to Regulation (EU) 2016/426 Annex III paragraph3 (valid from 21 April 2018) and for VGBF 100F40 ac­cording to annex III, module D1 of Directive 97/23/EC.
This declaration of conformity is issued under the
sole responsibility of the manufacturer. Elster GmbH
Directive:
2009/142/EC – GAD (valid until 20 April 2018)
Regulation:
Scan of the Declaration of conformity (D, GB) – see www.docuthek.com
(EU) 2016/426 – GAR (valid from 21 April 2018)
Standards:
DIN EN 88-1:2011

Eurasian Customs Union

DIN EN 88-2:2008 – DIN EN 334:2009
VGBF 100F40: Directive:
– 97/23/EC
The relevant product corresponds to the tested type
The product VGBF meets the technical specifications
of the Eurasian Customs Union.
sample. The production is subject to the surveil-

Spring table

Outlet pressure pd [mbar]
VGBF 15 VGBF 25 VGBF 40 VGBF 50 5 – 12.5 75421911 75421961 75421961 75422031 – 10 – 30** 75421921 75421971 75421971 75422041 red 25 – 45 75421931 75421980 75421980 75422051 yellow 40 – 60 75421941 75421990 75421990 75422061 green 55 – 75 75421951 75422000 75422000 75422071 blue 70 – 90 75442046 75422010 75422010 75422081 black 85 – 105 75442047 75422020 75422020 75422091 white 100 – 160 75442048 75438978 75438978 75438981 black/red 150 – 230 75442049 75438979 75438979 75438982 black/yellow 220 – 350 75442050 75438980 75438980 75438983* black/green
Outlet pressure pd [mbar]
VGBF 65 VGBF 80 VGBF 100 VGBF 150 5 – 12.5 75426160 75426230 75426310 75426450 – 10 – 30** 75426170 75426240 75426320 75426460 red 25 – 45 75426180 75426250 75426330 75426470 yellow 40 – 60 75426190 75426260 75426340 75426480 green 55 – 75 75426200 75426270 75426350 75426490 blue 70 – 90 75426210 75426280 75426360 75426500 black 85 – 105 75426220 75426290 75426370 75426510 white 100 – 160 75446329 75438984 75438987 75438990 black/red 150 – 230 75438985 75438988 black/yellow 220 – 350 75428986 75438989 black/green
* Spring set comprising two springs. ** Standard spring
Mark the new outlet pressure on the type label – adhesive label supplied.
Order No.
Order No.
Marking
Marking

Contact

Contact
If you have any technical questions, please contact your local branch office/agent. The addresses are available on the Internet or from ElsterGmbH.
We reserve the right to make technical modifications in the interests of progress.
Strotheweg 1, D-49504 Lotte (Büren)
Elster GmbH
Tel. +49 541 1214-0
Fax +49 541 1214-370
hts.lotte@honeywell.com, www.kromschroeder.com
GB-6