Please read through these instructionscarefully before installing or operating. Following theinstallation, pass the instructions on to the opera-tor. This unit must be installed and commissionedin accordance with the regulations and standardsin force. These instructions can also be found at www.docuthek.com.
Explanation of symbols
• , 1 , 2 , ... = Action
▷= Instruction
Liability
We will not be held liable for damage resulting fromnon-observance of the instructions and non-com-pliant use.
Safety instructions
Information that is relevant for safety is indicated inthe instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualifiedgas technicians. Electrical interventions may only becarried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEMspare parts.
GB
GB-1
F
NL
I
E
Checking the usage
UV sensor for intermittent operation for flamecontrol on gas burners in conjunction with Elster Kromschröder automatic burner control units (IFS,IFD, PFS, PFD), flame detectors (IFW, PFF) or burnercontrol units (BCU,PFU).
This function is only guaranteed when used within the
specified limits– see page5 (Technical data). Anyother use is considered as non-compliant.
Type code
CodeDescriptionUVSUV sensor
GB
5Series 5
G1
Part designations
4
1
2
3
2
3
Electrical connection:
M20 cable gland
5
6
4
7
8
▷The UV sensor may only be exposed to the UV
light of its own flame. It should be protected from other sources of ultraviolet light, e.g. neigh-bouring flames (this must be observed whenmonitoring pilot and main burners in particular),ignition sparks, arcs from welding devices or lamps emitting ultraviolet light.Avoid exposing the UV sensor viewing openings
▷
to direct sunlight.
▷
Protect the viewing openings against dirt andmoisture.
21
4,5
N 24
1818
Direct at the flame from the front or side.
3
4
1M20 cable gland2HousingSpring force terminals4Sensor head5Positioning aid6Sticker7UV tube8Bracket
Installation
CAUTION
Use UV sensor only in conjunction with ElsterKromschröder automatic burner control units,flame detectors or burner control units in order toavoid damage.
▷
It is preferable to install the unit inclined fromabove or in the horizontal.
Electric shocks can be fatal! Before working onpossible live components, ensure the unit is discon-nected from the power supply.
Replacing the old UVS5 with the newUVS5G1
The old UVS5 (with non-detachable PVC cable)
▷
can be replaced with the new UVS5G1 (withcable gland and spring force terminals).
A
B
UVS 5UVS 5G1
▷
Bracket A and clamping collar B from the oldUVS5 can be used to secure the new UVS5G1.
1 Disconnect the system from the electrical power
supply.
2 Shut off the gas supply.
Old UVS 5
45
6 Attach the clamping collar from the old UVS5
to the new UVS5G1.
7 Fit the new UVS5G1 with the clamping collar in
the bracket of the old UVS5.
8 Direct UVS5G1 at the flame from the front or
side.
9 Tighten the bolt of the clamping collar to secure
the UV sensor in the required position.
▷Electrical connection of the new UVS5G1, see
page 3 (Wiring).
13
Clampingcollar
WARNING
Electric shocks can be fatal! Before working onpossible live components, ensure the unit is discon-nected from the power supply.
▷Connection cable:– Use in accordance with local regulations.– Lay individually and, if possible, not in a metal
conduit.
– Do not lay together with ignition cable but lay
them as far apart as possible.
–M20 cable gland is designed for cable diameters
of 7 to 13mm.
– Spring force terminals for wire cross-sections
>0.2mm² to ≤1.5mm² (AWG24 to AWG16).
–Max. cable length in accordance with the speci-
fications for automatic burner control units IFS,IFD, PFS, PFD, flame detectors IFW, PFF orburner control units BCU,PFU.
▷
External electrical interference must be avoided.
1 Disconnect the system from the electrical power
supply.
2 Shut off the gas supply.
4
3
4
4
3
2
1
▷Flexible wires without wire end ferrules can also
be connected to the spring force terminals. Toinsert a flexible wire, the terminal must be openedusing the push-button.
231
4
3
2
1
Wiring, see IFS,
UVS
IFD, PFS, PFD,
4321
–
µA
+
IFW, PFF, BCU orPFU connectiondiagram.
PE
GB
GB-3
F
NL
I
E
Maintenance
Replacing the UV tube
Assistance in the event ofmalfunction
WARNING
Electric shocks can be fatal! Before working onpossible live components, ensure the unit is discon-nected from the power supply.
CAUTION
Do not touch the replacement UV tube with barefingers.
▷The sensor tube must be replaced after approx.
GB
10,000 operating hours (approx. 1year).
▷Spare parts (tube, sticker, seal), see www.part-
detective.de
1 Disconnect the system from the electrical power
supply.
2 Shut off the gas supply.
253
4
6
Use newsticker.
Insert tubewith seal.
WARNING
–Electric shocks can be fatal! Before working
on possible live components, ensure the unitis disconnected from the power supply.
–Fault-clearance must only be undertaken by
authorized trained personnel!
– Do not carry out repairs on the UV sensor on
your own as this will cancel our guarantee. Un-authorized repairs or incorrect electrical con-nections can cause the UV sensor to becomedefective. In this case, fail-safe operation canno longer be guaranteed.
–(Remote) resets may only be conducted by
authorized trained personnel with continuousmonitoring of the burner to be repaired.
–Safe operation only in conjunction with Elster
Kromschröder automatic burner control units,flame detectors or burner control units.
• Measure the current in the flame signal cable(connect the positive pole of the measuring in-strument to the cable from the automatic burnercontrol unit and the negative pole to the cablefrom the UV sensor).
4
PE
3
UVS
2
1
+
–
µA
▷
The measured direct current must be greater
than 1µA (typically 20µA).
? Fault ! Cause
• Remedy
? A direct current is flowing, but no flame
present.
! The UV sensor is influenced by the flames of
other burners, e.g. by reflection on the furnacewalls.
• Position the sensor so that it can only “view” itsown dedicated flame (e.g. use viewing tube).
! Humidity inside the sensor.
• Vent sensor.
! The service life of the UV tube has expired.
• Replace UV tube in the UV sensor, see page4(Maintenance).
! The sensitivity of the flame amplifier in the auto-
matic burner control unit is too high.
• Adjust the switch-off threshold on the automaticburner control unit.
GB-4
F
NL
I
E
? No direct current although the flame is burn-
ing.
! The UV sensor is dirty, e.g. sooted.
• Clean sensor.
! Humidity inside the UV sensor.
• Vent sensor.
! The distance between the UV sensor and the
flame is too great.
• Reduce the distance.
? The automatic burner control unit ignites in
pulses.
! The sensor “sees” the ignition spark.
• Reposition the UV sensor so that it cannot “see”the ignition spark.
• Use an automatic burner control unit that is ableto distinguish between an ignition spark and aflame signal.
? The intensity of the flame signal decreases
after a longer period of operation.
! UV tube fault due to incorrect UV sensor con-
nections.
• Connect the UV sensor in accordance with thewiring instructions.
• Remove the UV sensor and return for repair.
? The automatic burner control unit performs
a fault lock-out during start-up or operation.
!The highly fluctuating flame signal temporarily
exceeds the switch-off threshold.
• Reduce the distance between UV sensor andflame.
• Position the UV sensor so that it can “view” theflame without hindrance (e.g. smoke curtain).
! The switch-off threshold in the automatic burner
control unit is set too high.
• Adjust switch-off threshold.
Technical data
Plastic housing with connection terminals.Wire cross-section for connection terminals:≤1.5mm
2
(≤AWG16).Cable gland for cable diameters of 7 to 13mm.Distance between UV sensor and flame:max.400mm (max.16").UV tube: P578,spectral range: 190–270nm,max. sensitivity: 210 nm ± 10 nm.Service life of the UV tube:approx. 10,000 operating hours.Min. DC signal: 1 μA.Enclosure:
IP40
IP54
IP54 (Nema 3) in wiring chamber, IP40 around theviewing openings with fitted tube.Ambient temperature/storage temperature:
-40 to +80°C (-40 to +176°F).Weight: 280 g (0.6 lbs).Max. length of cable UV sensor – automatic burnercontrol unit: see operating instructions for auto-matic burner control unit.
Logistics
Transport
Protect the unit from external forces (blows, shocks,vibration). On receipt of the product, check that thedeliveryis complete, seepage2(Part designa-tions). Report any transport damage immediately.
Storage
Store the product in a dry and clean place.Storage temperature: see page5 (Technical data).Storage time: 6months before using for the first time.
Packaging
The packaging material is to be disposed of in ac-
cordance with local regulations.
Disposal
Components are to be disposed of separately inaccordance with local regulations.
GB
GB-5
F
NL
I
E
Certification
Eurasian Customs Union
The product UVS5 meets the technical specifications
of the Eurasian Customs Union.
GB
Contact
Contact
If you have any technical questions, please contactyour local branch office/agent. The addresses areavailable on the Internet or from ElsterGmbH.
We reserve the right to make technical modifications