The burner control units PFU 780 control, ignite and monitor
gas burners for intermittent or continuous operation. As a
result of their fully electronic design they react quickly to vari-
ous process requirements and are therefore also suitable for
frequent cycling operation.
The PFU 780 can be used for industrial burners of unlimited
capacity which are ignited by pilot burners. Pilot and main
burners are controlled and monitored independently. This
reduces the main burner start-up time. The pilot burner can
burn permanently or be switched off. The main burners may
be modulating or stage-controlled.
Theair valvecontrol on the PFU780L assists the furnace control
for cooling, purging and capacity control tasks.
The program status, the unit parameters and the level of the
flame signal can be read directly from the unit. Pilot and main
burners can be controlled manually for commissioning and
diagnostic purposes.
If the local requirements on the burner control units change,
the PC software BCSoft can be adjusted to the unit parameters
of the application by using the optical interface.
To support service personnel, BCSoft offers a convenient visualisation system of the input and output signals and the error
history.
On industrial furnaces, the PFU 780 reduces the load on the
central furnace control by taking over tasks that only relate
to the burner, for example it ensures that the burner always
ignites in a safe condition after it has been restarted.
The burner control unit is used for burners with mechanical
combustion air supply where the fan is controlled by a separate
logic and for atmospheric burners.
PFU 780 · Edition 02.124
Application
Bogie hearth forging furnace
in the metallurgical industry
Intermittent shuttle kilnin the ceramics industry
Walking beam furnace
with overhead firing
PFU 780 · Edition 02.125
VR..L
VAG
SPS PLC CPE
DI
L1, N, PE
P
2
1
t
1
2
ϑ1
ϑ2
A
P
DI
UV
02–04 02–04 06–08 06–08
VBY
PFU 780
10e
2c 4c
18a
26e 10c
22e
22a
28c 16c 18e
6a 6e
2e 4e
14a 30e 10a
TZI
2
1
ϑ1
ϑ2
µC
Application
1.1 Examples of application
1.1.1 Stage-controlled main burner with
alternating pilot burner
Control: Main burner ON/OFF.
The main burner can be started with
reduced capacity after the operating
signal from the pilot burner has been
detected. The pilot burner is switched
off automatically after the main burner
has started up. When the main burner is
switched off, the pilot burner automatically switches on again.
A UV sensor monitors the flame signal
from pilot and main burners. UV sensor
UVD 1 is used for continuous operation,
UV sensor UVS for intermittent operation.
PFU 780 · Edition 02.126
VR..R
VAG
SPS PLC CPE
DI
L1, N, PE
P
2
1
A
P
DI
VBY
PFU 780
10e
2c 4c
18a
26e 10c
22e
22a
28c 16c 18e
6a 6e
2e 4e
14a 30e 10a
TZI
t
1
2
04 02–04 06–08 06–08
04
2
1
ϑ1
ϑ2
µC
ϑ1
ϑ2
26a
Application > Examples of application
1.1.2
Stage-controlled main burner with
permanent pilot burner
Control: Main burner ON/OFF.
The main burner can be started with
reduced capacity after the operating
signal from the pilot burner has been
detected. Pilot and main burners can
be operated simultaneously. Both are
ionisation-controlled independently.
PFU 780 · Edition 02.127
VAG
VBY
SPS PLC CPE
DI
L1, N, PE
2
1
P
DI
BV+IC
mA
PFU 780
10e
2e 4e
2c 4c
6a 6e
26a
26e 10c
TZI
22a
28c
16c 18e
14a
18a
M
2
1
ϑ1
ϑ2
µC
Application > Examples of application
1.1.3 Modulating-controlled burner
Control: Main burner continuous
The butterfly valve for air BV is moved
to ignition position in order to start the
main burner. The main burner can be
started at low-fire rate after the operating signal from the pilot burner has been
detected. The control system controls the
burner capacity via the butterfly valve for
air BV after the operating state has been
signalled.Pilotand main burners can be
operated simultaneously.
PFU 780 · Edition 02.128
STWL1>750 °C
µC
PFU 780..D
18a
26a
DI
22a
µC
PFU 780..D
18a
26a
DI
22a
Application > Examples of application
1.1.4 PFU 780..D:High temperature equipment
The flame is controlled indirectly on the
basis of the temperature. During the
start-up process, as long as the wall
temperature is below auto ignition temperature the flame must be controlled by
conventional methods. When the working temperature has exceeded 750°C,
the safety temperature monitor (STW)
takes over the indirect flame control.
PFU 780 · Edition 02.129
2 Certification
Certified pursuant to SIL
For systems up to SIL 3 pursuant to EN 61508
Pursuant to EN ISO 13849-1:2006, Table 4, the PFU can be
used up to PL e.
EC type-tested and certified
pursuant to
– Gas Appliances Directive (2009/142/EC) in conjunction
with EN 298:2004-01,
Meets the requirements of the
– Low Voltage Directive (2006/95/EC),
– EMC Directive (2004/108/EC).
PFU..T is FM approved
AGA approved
AGA
Australian Gas Association, Approval No.: 5597
www.aga.asn.au/product_directory
Factory Mutual Research Class: 1997.
Suitable for applications pursuant to NFPA 86.
www.approvalguide.com
PFU 780 · Edition 02.1210
L1 (L1)
N (L2)
24 V
0 V
P
30e
26e
DI
22a
30a
20c
230 V
28c
N
26a
18a
ϑ1
10e
12e
ϑ2
14a
14e
A
10a
12a
10c
12c
32c24c
c2
c1
PFU 780
F1
1
2
sk1
µC
l
22e
v1
16c
v2
18e
N
V1
V2
3.1 Connection diagram
For cable selection and wiring, see page 49 (Project planning information).
3.1.1 PFU 780
For the explanation of symbols, see page 66 (Legend).
2a
a
4a
2e
s
4e
2c
m
n
A
S
SK
M
N
L
V2
V1
C
1
4c
6a6e
max. 1 A, 24 V
2
3 Function
Z
I
26a
28c
N
18a
26a
28c
N
UVS
18a
12
20c
3
24c
PFU 780 · Edition 02.1211
Function > Connection diagram
L1 (L1)
P
30e
26e
DI
22a
PFU 780..K2
F1
sk1
3.1.2 PFU 780..K2
l
22e
v1
16c
v2
18e
N
V1
V2
As a replacement unit for burner control unit PFU 798.
For the explanation of symbols, see page 66 (Legend).
N (L2)
24 V
0 V
Z
I
26a
ϑ2
30a
32c24c
20c
230 V
c2
28c
N
c1
26a
18a
ϑ1
10e
12e
14a
14e
A
10a
12a
10c
12c
28c
N
1
2
µC
28c
N
26a
18a
m
UVS
2a
a
4a
2e
s
4e
2c
1
4c
6a
n
6e
A
S
SK
M
N
L
V2
V1
C
18a
12
20c
3
24c
max. 1 A, 24 V
2
PFU 780 · Edition 02.1212
01
02
00
Switch onPFU 780
Pilot burner start-up
with ϑ1 signal
Safety interlocks (Limits)
In the event of fault signal:
Reset
If parameter P15 = 1:
flame simulation check
Wait until
waiting time t
W
has elapsed
If parameter P15 = 0:
Flame simulation check
If no flame detected:
next start-up attempt (P10)
or fault lock-out
Start-up position/standby
Safety time t
SA1
running (P22),
ignition in process,
V1 opens and min.
combustion time tB
starts to elapse (P20)
A
Function
▼
PFU 780
If the air valve control is used,the unit offers the following additional functions:
3.2 PFU 780 program sequence
Normal start-up
If an “old” fault is still being signalled
after switching on, it will be necessary
to reset this first.
The safety interlocks (terminal 26e) must
be closed and the burner control unit
In start-up position, the air valvecan be opened for cooling (display
A0
).
must be switched on.
The PFU 780 conducts a self-test when
in the start-up position (the burner is
switched off). If it does not determine a
malfunction of the internal electronic cir-
Using parameter 31, it can bedetermined whether the air valvecan be activated externally dur-ing start-up (display
A1
).
cuitry or of the flame sensors, the burner
can be started. The pilot burner start-up
is activated via the signal input “Startup signal ϑ1” (terminal 10e). Once the
start-up signal ϑ1 has been applied, the
PFU 780 opens valve V1 and ignites the
burner. The ignition time tZ is constant. If
The air valve can be set to open
together with V1 (display parameter 30.
A2
) via
a flame is detected during the safety time
t
, the flame proving period t
SA1
after the safety time t
SA1
has elapsed.
starts
FS1
If the pilot burner has been started successfully and its flame has stabilised, the
burner control unit issues the Enable
signal for main burner operation. The
operation signalling contact for the pilot
burner (terminals 2c/4c) closes.
PFU 780 · Edition 02.1213
03
04
05
06
If no flame detected:
next start-up attempt (P10)
or fault lock-out
In the event of flame failure:
restart or fault lock-out
Operating signal
Pilot burner closes
Flame proving period t
FS1
running (P23)
In the event of flame failure:
restart or fault lock-out
Main burner start-up
with ϑ2 signal
Wait until
min. burner pause time t
BP
has elapsed (P21)
If parameter P15 = 0:
Flame simulation check
If no flame detected:
next start-up attempt (P11)
or fault lock-out
Safety time t
SA2
running (P24),
V2 opens and
min. combustion time tB
starts to elapse (P20)
▼
Function > PFU 780 program sequence
The air valve can be set to opentogether with V1 (display parameter 30.
The air valve can be set to opentogether with V1 (display parameter 30.
The air valve can be set to opentogether with V1 (display parameter 30.
A3
A4
A5
) via
) via
) via
The PFU coordinates the correct program
run for the pilot and main burners. The
main burner can be started via the signal input “Start-up signal ϑ2” (terminals
14a/14c) if required.
Once the start-up signal ϑ2 has been
applied (terminals 14a and 14e), the
PFU780 opens valve V2. The main
burner is ignited by the pilot burner.
If a flame is detected during the safety
time tstarts after the safety time t
, the flame proving period t
SA2
SA2
FS2
has
elapsed. If the main burner has been
started successfully and its flame has
stabilised, the operation signalling contact (terminals 6a/6e) closes.
Start-up of the pilot burner without
flame signal
If no flame is detected during the safety
time t
, either a fault lock-out occurs
SA1
or up to three further start-up attempts
occur. (Parameter 10, “Pilot burner startup attempts”).
PFU 780 · Edition 02.1214
The air valve can be set to openwith V2 or to be activated ex-ternally (display eter30.
A6
)via param-
08
00
08
07
If no flame detected:
next start-up attempt (P11)
or fault lock-out
Normal shut-down
via ϑ signal for
pilot and main burners
If min. combustion time t
B
has elapsed:
Operation signalling contact
opens,
V1 and V2 close,
min. burner pause time tBP
starts to elapse (P21)
In the event of flame failure:
restart or fault lock-out
Operating signal
Main burner closes
Flame proving period
t
FS2
running (P25)
In the event of flame failure:
restart or fault lock-out
Function > PFU 780 program sequence
The air valve can be set to openwith V2 or to be activated exter-nally (display
30.
The air valve can be set to openwith the operating signal or to beactivated externally (display via parameter 30.
A7
) via parameter
A8
)
Behaviour of the pilot burner in the
event of flame failure during operation
If the flame fails during operation, either
an immediate fault lock-out occurs or a
restart occurs. This procedure can be
set via the optical interface (parameter
12, “Pilot burner restart”).
Behaviour of the main burner in the
event of flame failure during start-up
If no flame is detected during the safety
time t
, either a fault lock-out occurs
SA2
or up to three further start-up attempts
occur. (Parameter 11, “Main burner startup attempts”).
Behaviour of the main burner in the
event of flame failure during operation
If the flame fails during operation, either
an immediate fault lock-out occurs or a
restart occurs. This procedure can be
set via the optical interface (parameter
13, “Main burner restart”).
PFU 780 · Edition 02.1215
Function
▼
3.3 Program status and fault messages
During operation, the 7-segment display shows the program
status. In the event ofa fault, the PFU halts the program run,
the display blinks andit then displays the cause of the fault.
The burner control unit can be reset using the Reset button
or the remote reset.
Program status
Start-up position/standby
Cooling
Waiting time/Pause time
Safety time on start-up, pilot burner
Flame proving period, pilot burner
Operation, pilot burner
Waiting time, main burner
Safety time on start-up, main burner
Flame proving period, main burner
Operation, main burner
Purge
Air valve
High temperature operation**
DISPLAY
00
A0
1
2
3
4
5
6
7
8
P0
A
. .
10
32
33
35
Fault message (blinking*)
Flame simulation, pilot burnerStart-up without flame signal, pilot burner
Flame failure during flame proving period, pilot burner
Flame failure during operation, pilot burner
Flame simulation, main burnerStart-up without flame signal, main burner
Flame failure during flame proving period, main burner
Flame failure during operation, main burner
Faulty remote reset
Supply voltage too low
Faulty parameterisation
Short-circuit on a valve output
PFU 780 · Edition 02.1216
Function > Program status and fault messages
Program status
DISPLAY
36
51
52
53
* In Manual mode, two dots will blink on the display in program status 01 – 08.
** Optionally available.
Fault message (blinking*)Short-circuit on ignition or valve output
Safety interlock failure
Permanent reset
Time between two start-ups is too short
PFU 780 · Edition 02.1217
4 Parameters
▼
Description ParameterValue range
Factory default
setting
Flame signal, pilot burner010 – 30 μA
Flame signal, main burner020 – 30 μA
Program status when the most recent fault occurred03x0 – x8
Switch-off threshold, pilot burner041 – 20 µA1 µA
Switch-off threshold, main burner051 – 20 µA1 µA
Start-up attempts, pilot burner101 – 41
Start-up attempts, main burner111 – 41
Restart, pilot burner120; 10
Restart, main burner130; 10
Safety time during operation for V1 and V2 t
SB
141; 2 s1 s
Flame simulation check in start-up position/standby150; 11
Permanent pilot burner160; 11
Minimum combustion time t
Minimum burner pause time t
B
BP
Pilot burner safety time on start-up t
Pilot burner flame proving period t
FS1
Main burner safety time on start-up t
Main burner flame proving period t
SA1
243; 5 s
SA2
FS2
2025 st
SA
210 – 250 s0 s
223; 5; 10 s230 – 25 s0 s
250 – 25 s0 s
Air valve control300; 2; 30
Air valve can be activated externally on start-up310; 10
Air valve closed/can be activated in the event of malfunction320; 11
High temperature operation **332; 3
Adjustable*
PFU 780 · Edition 02.1218
Parameters
Description ParameterValue range
Factory default
setting
Manual mode limited to 5 minutes340; 11
UVS check (1 x in 24 hours)350; 10
Low fire over run time360; 5; 15; 25 s0 s
Purge420; 11
Multi-flame control450; 10
Password500000 – 99991234
* Adjustable using BCSoft software and a PC opto-adapter
** Please quote in your order.
0 = Function inactive
1 = Function active
On parameterisation, ensure that the program sequence
started matches the application. Select the parameters so that
the burner can restart as intended in all operating phases.
4.1 Scanning the parameters
During operation, the 7-segment display shows the program
status.
The flame signal and all following parameters of the PFU can
be scanned one after the other by repeatedly pressing the
Reset/Information button (for 2 s).
In the event of a fault, the PFU halts the program run, the
display blinks and it then displays the cause of the fault in
coded form.
Adjustable*
PFU 780 · Edition 02.1219
Parameters
4.2 Flame control
4.2.1 Flame signal, pilot burner
Parameter 01
Flame signal of the pilot burner, display in µA, measuring
range: 0 – 30 µA.
4.2.2 Flame signal, main burner
Parameter 02
Flame signal of the main burner, display in µA, measuring
range: 0 – 30 µA.
4.2.3 Program status when the most recent fault occurred
Parameter 03
Program status when the most recent fault occurred
This indicates the program status in which the last burner fault
occurred (e.g. the unit indicates that a flame simulation has
been detected with a blinking
In parameter 03, it is now shown which program position the
unit was in when the fault was detected (waiting time
standby
Result: A flame simulation was detected during the waiting
time or standby.
00
).
01
).
01
or
4.2.4 Switch-off threshold of the flame amplifier
Parameter 04, pilot burner switch-off threshold
Parameter 05, main burner switch-off threshold
The sensitivity at which the burner control unit still detects a
flame can be set between 1 and 20 μA.
Example: In the case of UV control with the UV sensor UVS,
the signal of the burner to be monitored is influenced by other
burners.
The set value can be incremented in parameter 04 so that only
the flame of the system’s “own” burner is detected.
The measured flame signal of the system’s “own” burner should
be at least 3 μA (empirical value) higher than the set switchoff threshold.
PFU 780 · Edition 02.1220
06070800
t
t
SA2tFS2
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
22a
V1
1
V2
2
ϑ1
ϑ2
2
1
DI
t
SA1
t
Z
040203
t
FS1
Parameters > Flame control
▼
4.2.5 High temperature operation with PFU..D
Parameter 33
Operation of firing systems at temperatures above 750°C. The
PFU features a safety-relevant DI input (Digital Input). This input
The voltage may be applied to the DI input (terminal 22a) so as
to activate High temperature mode only when the temperature
at the furnace wall has exceeded 750°C. The PFU starts the
burner as usual, without monitoring the presence of the flame.
supports the “High temperature operation” function. If firing
systems are operated above 750°C, the system is considered
to be a high temperature equipment (see EN746-2). Flame
control must be in operation until the furnace wall temperature
has exceeded 750°C. Note the requirements of the Standards!
Flame control can be dispensed with during high temperature
operation to improve the system availability. This means that
no incorrect flame signals, e.g. signals from a UV sensor which
are interpreted as extraneous signals due to reflection of UV
radiation, may lead to faults.
When the DI input is activated, the burner control unit reverts
to High temperature mode. This means: the PFU operates
without evaluation of the flame signal. The safety function of the
device-internal flame control system is placed out of operation.
In High temperature mode, the gas valves are opened without
flame control.
If the temperature in the furnace chamber drops below 750°C,
the DI input must be disconnected from the electrical power
supply and the furnace must be operated with the internal
flame control system.
The precondition for high temperature operation is that an
external flame safeguard ensures the presence of the flame
in fail-safe manner indirectly via the temperature. For this
purpose, we recommend a safety temperature monitor with
twin thermocouple (DIN 3440). Sensor discontinuity, sensor
short-circuit, failure of a component or mains failure must set
the installation to a safe state.
PFU 780 · Edition 02.1221
06070808
t
t
SA2tFS2
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
22a
V1
1
V22
ϑ1
ϑ2
2
1
DI
t
SA1
t
Z
04020301
t
FS1
t
W
2a–4a
FA
06070808
t
t
SA2tFS2
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
22a
V1
1
V2
2
ϑ1
ϑ2
2
1
DI
t
SA1
t
Z
04020301
t
FS1
t
W
2a–4a
Parameters > Flame control > High temperature operation with PFU..D
▼
The PFU then responds, depending on setting:
Parameter 33 = 1
If the flame fails during high temperature operation, the ready
contact opens for the duration of the flame failure (FA).
When High temperature mode is ended, the PFU switches off
the burner and restarts with flame simulation check (recom-
mended in the case of UV control with UVS).
Parameter 33 = 2
When High temperature mode is ended, the PFU switches off
the burner and restarts with flame simulation check (recom-
mended in the case of UV control with UVS).
PFU 780 · Edition 02.1222
08
08
t
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
22a
V1
1
V22
ϑ1
ϑ2
2
1
DI
t
04 04
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
22a
V11
V2
2
ϑ1
ϑ2
2
1
DI
08
t
08
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
22a
V1
1
V2
2
ϑ1
ϑ2
2
1
DI
08
08
t
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
22a
V1
1
V2
2
ϑ1
ϑ2
2
1
DI
2a–4a
Parameters > Flame control > High temperature operation with PFU..D
Parameter 33 = 3
When High temperature mode is ended, the burner remains
in operation and the PFU performs flame control again
(recommended in thecase of ionisation control or UV control
with UVD).
If no flame signal is present when High temperature mode
is ended, the burner control unit performs a fault lock-out,
regardless of parameter 33.
Fault, pilot burner
Fault, main burner
Parameter 33 = 4
If the flame fails during high temperature operation, the ready
PFU 780 · Edition 02.1223
contact is opened for the duration of the flame failure.
When High temperature mode is ended, the burner remains
in operation and the PFU performs flame control again
(recommended in the case of ionisation control or UV control
with UVD).
Parameters > Flame control
4.2.6 UVS check
Parameter 35
An automatic restart of the burner control unit can be activated
every 24 hours via this parameter. The time starts each time
the start-up signal (ϑ) is applied.
Parameter 35 = 0: Unlimited burner operation.
Parameter 35 = 1: An automatic restart is activated once every
24hours.
It must be ensured in this case that the program sequence
started matches the application. This parameter may be set
in this way only if the burner can restart as intended in all
operating phases.
PFU 780 · Edition 02.1224
t
1
2
ϑ1
ϑ2
88 02–04 06–08 04 06–08 04
Parameters
4.3 Pilot and main burner monitoring
Burner control unit PFU 780 for pilot and main burner combi-
nation of unlimited capacity.
Pilot burner: single-stage-controlled.
Main burner: modulating or stage-controlled.
The burner control unit PFU 780 has separate start-up signal
inputs for the pilot burner (terminal 10e) and the main burner
(terminal 14a). The burnercontrolunitcoordinatestheprogram
run (the interplay) of both burners. If required, the main burner
can be started once the pilot burner has reached its operating
position. Benefit: The time for starting up the main burner can
be reduced as low as its safety time. By using two flame ampli-
fiers, the pilot and main burners can be monitored separately.
The PFU 780 can also be used on indirectly ignited surface
burners with end point monitoring.
Three different operating modes are possible:
Permanent pilot burner
For applications which require a high system availability or
where a continuously burning flame is necessary. The pilot
burner is ignited once and remains constantly in operation.
The main burner is controlled separately.
Intermittent pilot burner
88 02–04 06–08 00 02–04 06–08 00
ϑ
1
2
t
Pilot and main burners are controlled with one start-up signal
(terminals 10e and 14a in parallel). The main burner starts
automatically after the operating signal from the pilot burner
has been detected. Operation is terminated simultaneously
for both burners.
Interrupted pilot burner
88 02–04 06–08 02–04 06–08
ϑ1
1
ϑ2
2
t
The pilot burner is switched off during the main burner safety
time t
. This type of flame control isrequired if no distinc-
SA2
tion can be made between the flame signals of the pilot and
main burners (e.g. if both burners can be monitored with a
single UV sensor). If the start-up signal for the pilot burner is
applied continually, the pilot burner restarts immediately after
the main burner has been switched off.
PFU 780 · Edition 02.1225
Parameters > Pilot and main burner monitoring
t
SA1
t
Z
04 06 07 08 02 03 00
t
t
FS1
t
SA2
t
FS2
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
V1
1
V2
2
ϑ1
ϑ2
2
1
4.3.1 Permanent pilot burnerParameter 16 = 1
Operating mode: Permanent pilot burner
In the “Permanent pilot burner” operating mode, the pilot
burner remains in operation until its start-up signal drops.
If this parameter is activated (P16 = 1), both flames are con-
trolled independently in the case of pilot and main burner
monitoring.
ϑ
L1
PFU 780
A
P
VBY
VAG
VR..R
1
SPS
2
PLC CPE
TZI
1
2
Operating mode: Intermittent pilot burner
Start-up as in the illustration “Permanent pilot burner” with
the difference being that the start-up signal for pilot and main
burners is applied synchronously and that immediately after
the flame proving period t
, the main burner is started.
FS1
PFU 780 · Edition 02.1226
Parameters > Pilot and main burner monitoring
t
SA1
t
Z
04 06 07 08 02 03 00
t
t
FS1
t
SA2
t
FS2
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
V11
V2
2
ϑ1
ϑ2
2
1
4.3.2 Interrupted pilot burnerParameter 16 = 0
Operating mode: Interrupted pilot burner
If parameter 16 = 0, the pilot burner is switched off once the
safety time t
can be connected to terminals 18a or 26a.
The pilot burner is switched off after the main burner safety
time t
SA2
has elapsed. In this setting, the flame signal
SA2
has elapsed.
ϑ
A
P
VR..R
PFU 780
VAS
VAG
1
SPS
2
PLC CPE
TZI
1
2
UV
L1
PFU 780 · Edition 02.1227
t
LV
00
t
01
26a16c18e2c–4c
88
10e
26e
30a
28c
2e–4e
V1V2
ϑ1
1
t
ϑ1
ϑ2
88 00 02 06
V1
V2
t
ϑ1
ϑ2
88 00 01 05
V1
V2
02
06
t
W1
t
W2
t
ϑ1
ϑ2
88 00 02 06
V1
V2
t
W1
t
W2
t
ϑ1
ϑ2
88 00 01 05
V1
V2
02
06
Parameters
4.4 Behaviour in start-up position/standby
4.4.1 Flame simulation check in start-up position/standby
Parameter 15
Flame simulation check depending on parameter 16 (Pilot
burner operating mode):
Parameter 15 = 1, Parameter 16 = 1
This defines the instant for the flame simulation check.
Parameter 15 = 0, Parameter 16 = 1
If the PFU notices an extraneous signal during the flame simu-
lation check, it starts the flame simulation delay time tLV (25s).
If the extraneous signal is discontinued during this period,
Parameter 15 = 1, Parameter 16 = 0
the burner can start up. Otherwise, a fault lock-out occurs.
1
blinks on the display if an extraneous signal is detected
by the pilot burner and 5 blinks if an extraneous signal is
detected by the main burner.
Parameter 15 = 0: The flame simulation check is conducted
after applying the start-up signal (ϑ) during the waiting timetW.
Parameter 15 = 0, Parameter 16 = 0
Parameter 15 = 1: Theflame simulation check is conducted
provided no start-up signal (ϑ) is applied (during the so-called
start-up position/standby). This allows fast start-up of the
burner since there is no waiting time tW.
The burner must have been switched off for at least 4s before
start-up in order for theflamesimulation checktobecon-
ducted correctly.
PFU 780 · Edition 02.1228
t
SA2
88 08 06 07 08
t
t
BP
t
FS2
4
5
1
7 9
18-19
12
V1
14 V2
16-17
05 04
1
28-29
2
21
1
9
2
ϑ
1
ϑ
2
Parameters > Behaviour in start-up position/standby
4.4.2 Minimum burner pause time tBP
Parameter 21
Programmable time between 0 and 250 s.
The time should be set such that the system can be moved to
ignition position, i.e. butterfly valves can be closed and, possibly, gas can be flared off, before a restart occurs.
See examples of application Stage-controlled main burner
with alternating pilot burner and Stage-controlled main burner
with permanent pilot burner.
The pause time has an effect on the behaviour of the main
burner only. Background: The pilot burner is only used in singlestage operation.
An immediate restart of the main burner after a normal shut-
down, a start-up attempt, restart, cooling or purging is pre-
vented by the pause time. The pause time starts when the air
valve is switched off. If a start-up signal (ϑ2) is applied before
expiry of this time, the start-up is delayed until the end of the
pause time.
After the pause time, the burner is started if the start-up signal
(ϑ) is applied.
The minimum burner pause time t
serves to adapt the pro-
BP
gram sequence to the requirements of the application.
PFU 780 · Edition 02.1229
t
SA1
t
Z
04 02 03 00
t
t
FS
26a16c18e2c–4c
88
10e
26e
30a
28c
2e–4e
V1
1
V2
ϑ1
1
t
SA1
t
Z
04 06 07 08 02 03 00
t
t
FS1
t
SA2
t
FS2
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
V1
1
V2
2
ϑ1
ϑ2
2
1
Parameters
4.5 Behaviour during start-up
4.5.1 Safety time on start-up tSA
Pilot burner
Parameter 22
Safety time on start-up t
for the pilot burner.
SA1
Main burner
Parameter 24
Safety time on start-up t
for the main burner.
SA2
PFU 780 · Edition 02.1230
t
SA1
t
Z
04 02 03 00
t
t
FS
26a16c18e2c–4c
88
10e
26e
30a
28c
2e–4e
V1
1
V2
ϑ1
1
t
SA1
t
Z
04 06 07 08 02 03 00
t
t
FS1
t
SA2
t
FS2
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
V11
V2
2
ϑ1
ϑ2
2
1
04 06 07
t
t
B
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
2e–4e
6a–6e
V1
1
V2
2
ϑ1
ϑ2
2
1
Parameters > Behaviour during start-up
4.5.2 Flame proving period tFS
Pilot burner
Parameter 23
Main burner
Parameter 25
4.5.3 Minimum combustion time t
B
Parameter 20Programmable time to maximum 25 s during which the main
burner remains in operation. In the case of brief activation of
the start-up signal input (ϑ2) (e.g. with a pulse), the combustion
time tB is started, and the main burner remains in operation
for at least this period.
Programmable time between 0 and 25 s.
This time elapses before the PFU starts the next program step
so as to give the flame time to stabilise.
PFU 780 · Edition 02.1231
t
SA
t
Z
02 00
t
02
26a16c18e2c–4c
88
10e
26e
30a
28c
2e–4e
V1V2
ϑ1
t
SA1
t
Z
02 00
t
t
SA1
t
Z
26a
16c
18e
2c–4c
88
10e
26e
30a
28c
2e–4e
V1
V2
ϑ1
1
Parameters > Behaviour during start-up
4.5.4 Burner start-up attempts
Pilot burner
Parameter 10
This indicates the number of possible start-up attempts of
the burner.
In accordance with EN 746-2, three start-ups are permitted in
specific cases in the event of flame failure during start-up, if
the safety of the installation is not impaired. Note the require-
ments of the Standards!
If no flame is detected during start-up, either a fault lock-out
is performed or further start-up attempts in accordance with
EN 746-2 occur.
Pursuant to NFPA 86, only one start-up attempt is permitted in
the event of flame failure during start-up. For units approved
by FM Approval (see type label), it is only possible to select
one start-up attempt.
1 start-up attempt
Parameter 10 = 1
2 or 3 start-up attempts
Parameter 10 = 2, 3
If several start-up attempts are set and if the PFU detects a
flame failure during start-up, it closes valve V1 after the safety
time t
has expired and attempts to start up again. After the
SA1
last programmed start-up attempt has been completed, the
burner control unit conducts a fault lock-out. The display blinks
and shows the cause of the fault.
If no flame forms during start-up, a fault lock-out is performed
after expiry of time tSA. The display blinks and shows the cause
of the fault.
PFU 780 · Edition 02.1232
t
SA1
t
Z
04 06 02 03 00
t
t
FS1
t
SA2
06
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
V1
1
V2
2
ϑ1
ϑ2
2
1
t
SA2
t
SA2
t
SA2
t
SA1
t
Z
04 06 02 03 00
t
t
FS1
06
t
W
06
06
05
05
t
W
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
V1
1
V2
2
ϑ1
ϑ2
2
1
Parameters > Behaviour during start-up > Burner start-up attempts
Main burner
Parameter 11
This indicates the number of possible start-up attempts of the
main burner.
In accordance with EN 746-2, three start-ups are permitted in
specific cases in the event of flame failure during start-up, if
the safety of the installation is not impaired. Note the require-
ments of the Standards! If no flame is detected during start-up,
either a fault lock-out is performed or further start-up attempts
in accordance with EN 746-2 occur.
Pursuant to NFPA 86, only one start-up attempt is permitted in
the event of flame failure during start-up. For units approved
by FM Approval (see type label), it is only possible to select
one start-up attempt.
1 start-up attempt
Parameter 11 = 1
2 or 3 start-up attempts
Parameter 11 = 2, 3
If several start-up attempts are set and if the PFU does not
detect a flame signal during start-up, it closes valve V2 after
the safety time t
has expired and attempts to start up again.
SA2
After the last programmed start-up attempt has been completed, the burner control unit conducts a fault lock-out. The
display blinks and shows the cause of the fault.
If no flame forms during the start-up of the main burner, a
fault lock-out is performed after expiry of time t
blinks and shows the cause of the fault.
PFU 780 · Edition 02.1233
. The display
SA2
04
t
t
SB
04
26a
16c
18e
2c–4c
88
10e
26e
30a
28c
2e–4e
V1
1
V2
ϑ1
1
Parameters
▼
4.6 Behaviour during operation
4.6.1
Safety time during operation tSB for pilot and main burners
Parameter 14
This indicates the safety time during operation tSBfor valves V1
and V2. The default in accordance with EN 298 is 1 s. The PFU
has also the available option of a safety time during operation
tSB of 2 s. Prolonging the time increases the installation avail-
ability in the case of brief-duration signal fades (e.g. fades of
the flame signal). In accordance with EN 746-2, the safety time
4.6.2 Fault lock-out or restart, pilot burner
Parameter 12This parameter determines whether the PFU starts a one-off
restart or performs an immediate fault lock-out for the burner
after an installation fault such as a flame failure or failure of
air flow (see also Project planning information).
Immediate fault lock-out following flame failure
Parameter 12 = 0:Pilot burner fault lock-out.
of the installation during operation (including closing time of
the valves) may not exceed 3 seconds (note the requirements
of the Standards).
After a fault lock-out, the burner control unit can be reset,
either with the button on the front panel or using an external
button. Several burner control units can be reset in parallel
using the external button.
The PFU cannot be reset by mains failure. The fault signalling
contact does, however, open as soon as the mains voltage fails.
See also parameter 32, Behaviour ofthe air valve in the event
of a fault lock-out.
PFU 780 · Edition 02.1234
t
SA1
t
Z
04 04 03 01
t
t
FS1
t
W
t
SB
1x
>2 s
26a16c2c–4c
88
10e
26e
30a
28c
2e–4e
V1
1
ϑ1
1
Parameters > Behaviour during operation > Fault lock-out or restart, pilot burner
Restart following flame failure
Parameter 12 = 1:
Restart following flame failure.
If the PFU detects a flame failure after a minimum operating
time of 2 s, the valves are closed and the operation signalling
contact is opened within time tSB.
The burner control unit now attempts to restart the burner
once. If the burner does not function, a fault lock-out occurs.
The display blinks and shows the cause of the fault.
In accordance with EN 746-2, a restart may be conducted
only if the safety of the installation is not impaired. Restart is
recommended for burners which occasionally display unstable
behaviour during operation.
The precondition for a restart is that activation of the restart
allows the burner to restart as intended (in all operating
phases). In this case,it must be ensured that the program
sequence started by the PFU matches the application.
PFU 780 · Edition 02.1235
08
t
t
S
B
08
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
V11
V2
2
ϑ1
ϑ2
2
1
Parameters > Behaviour during operation
▼
4.6.3 Fault lock-out or restart, main burner
This parameter determines whether the PFU starts a one-off
restart or performs an immediate fault lock-out for the main
burner after a flame failure (see also Project planning infor-
mation).
Immediate fault lock-out following flame failure
Parameter 13 = 0:
Main burner fault lock-out
After a fault lock-out, the burner control unit can be reset,
either with the button on the front panel or using an external
button. Several burner control units can be reset in parallel
using the external button.
The PFU cannot be reset by mains failure. The fault signalling
contact does, however, open as soon as the mains voltage fails.
See also “Behaviour of the air valve in the event of a fault
lock-out”.
After a flame failure, the burner control unit performs a fault
lock-out within the safety time during operation tSB. This in-
volves disconnecting the power from the gas valves and the
ignition transformer. The fault signalling contact closes, the
display blinks and shows thecurrent program status(see
table “Program status and fault messages”).
PFU 780 · Edition 02.1236
06
05
07
08
08
t
t
SA2
t
FS2
1x
t
W2
t
SB
>2 s
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
V1
1
V22
ϑ1
ϑ2
2
1
Parameters > Behaviour during operation > Fault lock-out or restart, main burner
Restart following flame failure
Parameter 13 = 1:
Restart following flame failure.
If the PFU detects a flame failure after a minimum operating
time of 2 s, valve V2 is closed and the operation signalling
contact is opened within time tSB.
The burner control unit now attempts to restart the main burner
once. If the burner does not function, a fault lock-out occurs.
The display blinks and shows the cause of the fault.
In accordance with EN 746-2, a restart may be conducted
only if the safety of the installation is not impaired. Restart is
recommended for burners which occasionally display unstable
behaviour during operation.
The precondition for a restart is that activation of the restart
allows the burner to restart as intended (in all operating
phases). In this case,it must be ensured that the program
sequence started by the PFU matches the application.
PFU 780 · Edition 02.1237
Parameters
4.7 Air valve control PFU..L
Parameter 30, Behaviour of the air valve during operation
Parameter 31, Behaviour of the air valve during start-up
Parameter 32, Behaviour of the air valve in the event of a
fault lock-out
The PFU..L features an adjustable air valve control. The display
shows that purging is currently being carried out with
A
indicates that the air valve is being activated for cooling
or heating.
The PFU..L supports the following functions:
– Purge
– Cooling in start-up position/standby
– Switching of the burner between low and high burner out-
put during operation via the air valve
– To start up the burner as intended, external activation of
the air valve can be blocked during start-up (prevents
synchronisation problems between the PFU and the cen-
tral control system)
– Controlling the air valve so that it
– opens with valve V2,
– opens once the main burner has reached its operating
position
– Low fire over run time t
after a normal shut-down
KN
P 0
4.7.1 Purge
Parameter 42 = 0: The air valve is closed when voltage is
applied to terminal 30e.
Parameter 42 = 1: The air valve is opened when voltage is
applied to terminal 30e.
In the case of multiple burner applications, burners with mechanical combustion air supply are used. The air for combus-
.
tion and pre-purge is supplied by a central fan controlled by
a separate logic. This logic determines the purging time.
The PFU..L supports centrally-controlled pre-purge or postpurge. The PFU..L is informed that purging is currently being
performed by input 30e. It then opens the air valve, regardless of the status of the other inputs (purging has priority). The
display indicates
PFU 780..K2: For purging, the safety interlock (limits) must
activate input 26e and input 30e of the PFU.
4.7.2 Cooling in start-up position/standby
The air valve can be activated externally via input 10a for cooling in the start-up position. During activation of the air valve
the display shows being carried out.
4.7.3 Burner start
Parameters 30 and 31 determine the behaviour of the air valve
during burner start.
P 0
.
A 0
, indicating that cooling is currently
PFU 780 · Edition 02.1238
02
00 A0 00
A0
t
SA2
A807
04
t
t
FS2
06
t
SA1
t
Z
t
FS1
03
A
10a22e
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
V11
V2
2
ϑ1
ϑ2
2
1
PFU 780
A
P
L1
1
2
SPS PLC CPE
ϑ
VR..R
VAG
TZI
2
1
UV
VAS
Parameters > Air valve control PFU..L
4.7.4 Air valve opens in the case of external activation (not
during start-up)
Parameter 30 = 0:The air valve opens if it is activated externally by input 30e.
Parameter 31 = 0:The air valve remains closed during start-up
even if it is activated externally.
These settings are required on burners on which the gas/air
ratio is controlled via a pneumatic link and which also need
to be started at low fire, e.g. on two-stage-controlled burners.
In this case, activation of the air valve during burner start via
input 10a must be prevented.
External control allows switchover between low fire and high
fire during operation.
The air valve can be activated externally via input 10a for cooling the burner in the start-up position/standby.
PFU 780 · Edition 02.1239
A2
00 A0 00
A0
t
SA2
A8 A7
A4
t
t
FS2
A6
t
SA1
t
Z
t
FS1
A3
A
10a22e
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
V11
V2
2
ϑ1
ϑ2
2
1
Parameters > Air valve control PFU..L
4.7.5 Air valve opens in the case of external activation (even
during start-up)
ϑ
A
P
PFU 780..L
VAS 1
VAG
1
2
TZI
1
2
L1
UV
Parameter 30 = 0:The air valve opens if it is activated externally via input 10a.
Parameter 31 = 1:The air valve can be activated even during start-up.
These settings may be selected only if the burner can start
with full air capacity.
The air valve can be activated externally via input 10a for cooling the burner in the start-up position/standby.
VAS
PFU 780 · Edition 02.1240
02
00 A0
00
t
SA2
A8 A7
04
t
t
FS2
A6
t
SA1
t
Z
t
FS1
03
A
10a22e
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
V1
1
V22
ϑ1
ϑ2
2
1
Parameters > Air valve control PFU..L
4.7.6 Air valve opens with valve V2
ϑ
PFU 780..L
A
P
VBY
VAG
TZI
1
L1
Parameter 30 = 2:The air valve opens simultaneously with valve V2.
Application:Single-stage-controlled main burner is switched ON/OFF via
the ϑ input.
The air valve can be activated externally via input 10a for cooling the burner in the start-up position/standby.
SPS PLC CPE
1
2
2
VR..R
PFU 780 · Edition 02.1241
t
SA
A8 07
04
t
t
FS
06
A
10a22e
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
V1
1
V2
2
ϑ1
ϑ2
2
1
Parameters > Air valve control PFU..L
4.7.7 Air valve opens with operating signal
ϑ
L1
PFU 780..L
A
P
VBY
VAG
1
SPS
2
PLC CPE
TZI
1
2
Parameter 30 = 3:The air valve opens simultaneously with the operating signal.
Application:Two-stage-controlled main burner is switched ON/OFF via
the ϑ input.
The air valve can be activated externally via input 10a for cooling the burner in the start-up position/standby.
VR..R
PFU 780 · Edition 02.1242
00
A8
t
t
KN
22e
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
V1
1
V2
2
ϑ1
ϑ2
2
1
ϑ
Parameters > Air valve control PFU..L
4.7.8 Low fire over run time tKN after a normal shut-down
PFU 780..L
L1
A
P
VG..N
VR..R
GIK..B
VAS 1
1
2
TZI
1
2
SPS PLC CPE
Parameter 36Settings: 0; 3; 5; 10; 15; 25 or 60 (low fire over run time in
seconds)This parameter is applicable to systems with a pneumatic link
between gas and air and On/Off control.
Parameter 36 = 0 (low fire over run time t
= 0 s):
KN
Without low fire over run, the gas side is closed immediately
owing to the quick-closing gas valve in the case of On/Off
control. The air side closes more slowly. The air flowing in
during the closing time increases the O2 content in the combustion chamber.
Parameter 36 = 3; 5; 10; 15; 25 or 60 (low fire over run time
t
= 3, 5, 10, 15, 25 or 60 s):
KN
The air valve closes slowly after the activation signal has
been switched off. The gas valve remains open for tKN. This
means that the burner, after deactivation of the main burner
start-up signal (ϑ2), is initially adjusted down to low fire and
then switched off completely.
Using the low fire over run function reduces the O
content in
2
the furnace atmosphere.Flame control is still operational. Can be used only in the case
of pneumatic link and On/Off control. It must be ensured that
no excess gas occurs.
The low fire over run time has an effect on the behaviour of
the main burner only.
Background: The pilot burner is only used in single-stage
operation.
PFU 780 · Edition 02.1243
Parameters > Air valve control PFU..L
4.7.9
Behaviour of the air valve in the event of a fault lock-out
Parameter 32:
This determines whether the air valve can be activated in the
case of a fault lock-out.
Parameter 32 = 0:
The air valve is closed in the event of a fault. It cannot be
activated externally via terminal 10a.
Parameter 32 = 1:
The air valve can be activated externally via input 10a even
during a fault, e.g. for cooling.
PFU 780 · Edition 02.1244
Parameters
4.8 Manual operation
For convenient setting of the burner or analysing faults.
The parameter display is not available in Manual mode.
Manual mode can be accessed only if the unit was not in
Fault state before switching off. The following times/functions
are not active in Manual mode: start-up attempts, restart,
minimum combustion time and cycle lock.
If the Reset/Information button is pressed for 2 s during switch-
on, the PFU reverts to Manual mode. Two dots blink on the
display.
In this operating mode, the burner control unit operates inde-
pendently of the status of the inputs (apart from the pre-purge
input and the safety interlocks. These are of higher priority and
will be processed first).
Each time after the button is pressed again, the PFU moves
to the next section of the program sequence and stops there.
After approx. 3 s, the flame signal will be displayed instead of
the program parameter. Briefly pressing the Reset/Informa-
tion button (< 1 s) displays the relevant Manual mode step. If
there is flame simulation during the start-up, the flame signal
is displayed immediately.
On units with air valve control, the air valve can be opened
and closed repeatedly by pressing the button during operation.
Manual mode can be terminated by switching off the PFU
(On/Off button).
4.8.1 Manual mode limited to 5 minutes
Parameter 34:Parameter 34 determines when Manual mode is terminated.
Parameter 34 = 0:Manual mode is not limited in time. If this function has been
selected, operation of the furnace may be continued manually
in the event of failure of the central control system.
Parameter 34 = 1:Manual mode ends automatically five minutes after the last
time the button was pressed. The PFU then moves abruptly
back to start-up position/standby.
PFU 780 · Edition 02.1245
Parameters
4.9 Password
Parameter 50:
(Four-digit) password saved to protect parameter settings.
To prevent unauthorised changes to parameter settings, a
password is stored in parameter 50. Changes to parameter
settings can only be made once this number has been entered.
The password can be changed using BCSoft.
Note the effect of parameter settings on the safe functioning
of your system.
The password set at the factory can be found in the delivery
note supplied.
U*Preparation for UV sensor for continuous operation UVD 1
K2*Compatible with PFU 798
to interrupt fl ame control
Digital input
PFU 780 · Edition 02.1248
6 Project planning information
6.1 Cable selection
Use mains cable suitable for the type of operation and com-
plying with local regulations. Do not route PFU cables in the
same cable duct as frequency converter cables or cables
emitting strong fields.
6.1.1 Ignition cable
Use unscreened high-voltage cable, see page 55 (Acces-
sories). Cable length: max. 5 m, recommended < 1 m. Screw
the ignition cable securely into the ignition transformer and
run to the burner by the shortest possible route.
The longer the ignition cable, the lower the ignition capacity.
Only use radio interference suppressed electrode adapters
(with 1 kΩ resistor) for ignition electrodes, see see page 55
(Accessories) . Do not lay UV/ionisation cable and ignition
cables together and lay them as far apart as possible.
6.1.2 Ionisation cable
Use unscreened high-voltage cable, see page 55 (Acces-
sories) . Cable length: max. 100 m. Avoid external electrical
interference. Install as far as possible from mains and igni-
tion cables and interference from electro-magnetic sources.
If possible, do not layin a metal conduit. Several ionisation
cables can be routed together.
6.1.3 UV-Leitung
Cable length: max. 100 m. Avoid external electrical interference.
Install as far as possible from mains and ignition cables and
interference from electro-magnetic sources. If possible, do
not lay in a metal conduit. Several UV cables can be routed
together.
6.2 Ignition electrode
6.2.1 Electrode gap
Gap between electrode and burner earth: 2 mm ± 0.5mm.
6.2.2 Star electrodes
We recommend using 7.5kV ignition transformers on burners
with star electrodes.
PFU 780 · Edition 02.1249
Project planning information
04 06 07
t
t
B
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
2e–4e
6a–6e
V1
1
V2
2
ϑ1
ϑ2
2
1
6.3 Minimum combustion time
Even if the start-up signal (ϑ) is applied only briefly, the time
set under parameter 20 elapses before the burner control
unit shuts down the burner or signals a fault. To stabilise the
burner operation, a minimum combustion time can be set
independently of the central control system. If the start-up
signal (ϑ) drops once the second safety time t
to elapse, the burner remains in operation for at least time tB.
The minimum combustion time tB starts to elapse following
controller enable. If the start-up signal drops before the second
safety time t
, e.g. during pre-purge, the control unit reverts
SA2
directly to standby and the burner is not ignited.
The signal inputs for the pilot/main burner start-up signal can-
not be used for a safety shut-down because the unit controls
the valves until the minimum combustion time has elapsed.
has started
SA2
6.4 Safety interlocks (Limits)
The limiters in the safety interlock (linking of all the relevant
safety control and switching equipment for the use of the
application, e.g. safety temperature limiter, minimum and
maximum gas pressure, tightness control) must isolate terminal 26e from the voltage supply. If the safety interlock is
interrupted, this is indicated by a blinking
51
on the display.
If the safety interlocks fail, an immediate program abort with
switch-off of all outputs occurs (even during the safety time).
If the safety interlocks are operational again or the unit is
switched back on, the program run is restarted in standby.
6.5 Emergency stop
6.5.1 In the event of fire or electric shock
If there is a risk of fire, electric shock or similar, inputs L1, N
and 26e (safety interlocks) of the PFU should be disconnected
from the electrical power supply – this should be reflected in
the wiring on site.
6.5.2 Via the safety interlocks (limits)
The safety interlock turns off the power to input 26e, such as
in the event of air deficiency or similar.
In the case of pilot/main burner monitoring, the minimum
combustion time only has an effect on the behaviour of the
main burner. The minimum combustion time for the pilot burner
is limited to the safety time on start-up (t
Background: The pilot burner is only used in single-stage
operation.
PFU 780 · Edition 02.1250
SA1
).
Project planning information
6.6 Reset
6.6.1 Parallel reset
Several burner control units can be reset in parallel using the
external button. The PFU cannot be reset by mains failure.
6.6.2 Permanent remote reset
Permanent remote reset gives rise to a malfunction. If a remote
reset signal is permanently applied to terminals 10c/12c,
flashes on the display to indicate a fault.
Reset with a pulse < 1 s.
6.6.3 Automatic remote reset (PLC)
In the case of automatic remote reset (PLC), the reset pulse
duration should not exceed 1 second. Check compliance with
standards.
If a fault is acknowledged by remote reset too often, error
(Too many remote resets) is displayed. The error can only be
acknowledged with the Reset/Information button on the unit.
The burner malfunction must be remedied. The malfunction
can not be remedied by changing the method of activation.
52
10
6.6.4 Burner start
A furnace start may only be initiated, if it has been ensured
using an appropriate procedure that there is no combustible
mixture in the combustion/processing chamber, in the connected areas or in the exhaust gas system (heat exchanger,
dust collector). This can be achieved by pre-purge, which
occurs immediately before ignition or within the period specified in the operating instructions.
In the case of multiple burner applications, pre-purge is not
necessary after a normal burner shut-down.
Note the requirements of the Standards. For exceptions, see
Standards.
6.6.5 Restart and start-up attempts
The precondition for a restart/start-up attempt is that activation
of the restart allows the burner to restart as intended (in all
operating phases). In this case, it must be ensured that the
program sequence started by the PFU matches the application.
Note the requirements of the Standards. For exceptions, see
Standards.
PFU 780 · Edition 02.1251
Project planning information
6.7 Fault message
The fault signalling contact opens, as soon as the mains vol-
tage fails.
6.8 Protecting the pilot burner from overload
To protect the unit against overload by frequent cycling, the
maximum number of start-ups per minute is limited for the
PFU. Excessive cycling triggers a fault message (blinking
The max. number of start-ups per minute depends on the
safety time tSA:
t
[s]Ignition transformer TZIMax. start-ups/min.
SA
35-15/1006
55-15/1005
105-15/1004
53
6.9 Installation
Installation position: any.Installation in 19” module subracks only, see page 56 (So-
cket connectors)Install in clean environment ensuring enclosure IP 54 or higher,
whereby no condensation is permitted.
Cable length between PFU and burner: max. 100 m.
).
6.10 Wiring
The PFU is suitable for hard wiring only. Do not reverse phase
and neutral conductor. Different phases of a three-phase
current system must not be installed at the PFU. No voltage
may be connected to the valve and ignition outputs.
6.10.1 UVS sensor wiring
Connect the UVS sensor directly to the PFU. Operating the
sensor with incorrect polarity or voltage can lead to destruction
of the sensor.
6.11 PFU switched off
The PFU cannot be activated when no mains voltage is applied
or when it is switched off. The fault signalling contact is only
closed when the unit is supplied with voltage and switched on.
If the unit is switched off, an immediate program abort with
switch-off of all outputs occurs (even during the safety time).
When the unit is switched on, the program run is restarted
in standby.
PFU 780 · Edition 02.1252
Project planning information
6.12 Furnace control
Switch on the system to start up the furnace, then release the
burner start via the safety interlocks and afterwards start the
burner control so thatthe burner control unit may monitor the
burners as intended. To shut down the furnace, first disconnect
the burner control unit from the temperature control (burner
ON signal), then disconnect the safety interlocks and finally
switch off the system.
6.13 Note on EC type-examination
Since EN 298 (1993) does not describe all functions of the PFU,
the operator is responsible for ensuring that all parameters
and functions are matched to the respective application.
6.14 Mains switch
The mains switch in the unit isolates the PFU on two poles from
the mains. It does not meet the requirements of EN50156-
1:2004 (5.2.2 Switch disconnectors) set out in chapter5 for a
device to disconnect the power supply. Although the mains
switch cannot be used for disconnecting from the electrical
power supply in accordance with EN50156, it does allow
the burner to be isolated functionally from the central control
system. This function is required for manual operation and,
in the case of PROFIBUS units, to switch off the unit without
causing BUS errors. Disconnection for electrical maintenance
work is to be implemented with an external switch per unit or
group only, in accordance with Standard “EN50156”.
6.15 Changing parameters
In certain cases, it may be necessary to change the default
settings. Using a separate software package and a PC optoadapter, it is possible to modify certain parameters on the
PFU, such as the switch-off threshold of the flame amplifier,
the behaviour in the event of a flame failure or if the pilot
burner is to burn permanently in the case of pilot and main
burner monitoring.
The software package with PC opto-adapter, as well as
“Changed parameters” stickers, are available as accesso-
ries– see section entitled page 55 (Accessories) .
The unit parameters set at the factory are specified in the
delivery note.Document changed parameters in BCSoft using the protocol
function and enclose the protocol with the plant documentation.
If a replacement is ordered for a PFU with changed parameters,
refer to the protocol for details.
PFU 780 · Edition 02.1253
7 Flame control
7.1 With ionisation sensor
The PFU generates an alternating voltage (230 V AC) between
the sensing electrode and burner earth. The flame rectifies
this voltage. Only the DC signal (depending on the switch-off
threshold for the pilot and main burners) is recognised by the
burner control unit as a flame signal.
A flame cannot be simulated. Ignition and monitoring with a
single electrode is possible.
7.2 With UV sensor
A UV tube inside the UV sensor detects the ultraviolet light of
a flame. It does not respond to sunlight, incandescent bulb
light or infrared radiation emitted by hot workpieces or red-
hot furnace walls.
In the event of incident UV radiation the UV sensor rectifies
the supplied alternating voltage. As with ionisation control,
the burner control unit only detects this DC signal.
When using UV sensors of Type UVS, the burner control unit
may be used for intermittent operation only. This means that
operation must be interrupted at least once every 24 hours.
This can be programmed using parameter 35.
For further information, see brochure UVS.
The burner control unitPFU..U is prepared for UV sensor UVD1.
This enables continuous operation. For further information, see
Technical Information Bulletin UVD.
7.3 Via the temperature in high temperature
equipment
High temperature equipment is defined as a thermoprocessing
installation, in which the wall temperature of the combustion
chamberand/ortheprocessingchamber exceeds 750°C.
Burner control unit PFU..D features a special “High temperature
operation” function. During heating up, standard monitoring
methods (ionisation or UV) must be used for flame control.
When the working temperature has exceeded 750°C, indirect
flame control can be taken over by a central monitoring device.
When the DI input (terminal 22a) is activated, the burner control
unit reverts to this operating mode.
Important: In “High temperature operation”, i.e. with the DI input being activated, burner control unit PFU..D does not evaluate the flame signal. The safety function of the burner control
unit’s flame control is deactivated during this operating phase.
PFU 780 · Edition 02.1254
8 Accessories
Brenner 1Zone 3
D-49018 Osnabrück, Germany
Achtung, geänderte Parameter!
Die Angaben auf dem Typenschild gelten nicht mehr in vollem Umfang.Aktuelle Parameter direkt auslesen.
Important, changed parameters!
The details on the type label are no longer completely accurate. Read the current parameters direct from the unit.
Attention, paramètres modifiés !
Les informations figurant sur la plaque signalétique ne sont plus valables dans leur intégralité. Veuillez vous référer directement aux paramètres actualisés.
8.1 High-voltage cable
FZLSi 1/7 up to 180°C,
Order No.: 04250410.
FZLK 1/7 up to 80°C,
Order No.: 04250409.
8.2 BCSoft
Opto-adapter including BCSoft CD-ROM,
Order No.: 74960437.
The current software can be downloaded from our Internet site
at http://www.docuthek.com. To do so, you need to register
in the DOCUTHEK.
8.3 Stickers for labelling
For printing with laser printers, plotters or engraving
machines, 27 × 18 mm or
28 × 17.5 mm.
Colour: silver
8.4 “Changed parameters” stickers
Affix on the connection diagram of
the PFU following changes to unit
parameters set at the factory.
100 pcs,Order No.: 74921492.
PFU 780 · Edition 02.1255
Accessories
8.5 Radio interference suppressed electrode
adapters
Plug cap, 4 mm, interference-suppressed,
Order No. 04115308.
Straight adapter, 6 mm, interference-suppressed,
Order No. 04115306.
8.6 Socket connectors
Type
Socket connector E, 48-pin solder tag connection
Socket connector E, 48-pin wire-wrap connection
Order No.0412014804120158
8.7 Module subrack
Module subrack BGT SM-8/1/1 for MPT 700, PFU 780
comprising:module subrack, printed-circuit board with rear terminal strip,
function-tested, standard documentation, guide rails, without
partial front plates, screw terminals at the rear, single-zone
operation for MPT 700 operating modes 1 – 4, two-zone operation for MPT 700 operating modes 1 – 4, but max. 4 burners
per zone.
Slot 1 for MPT 700, slots 2–9 for PFU 760/780, slot 10 for PFP700
Order No. 84402282 (no illustration provided)
Module subrack BGT SA for PFA 700/PFU 760 and PFA 710/
PFU 780
consisting of: odule subrack, printed-circuit board with rear terminal strip,
function-tested, standard documentation, guide rails, without
partial front plates, screw terminals at the rear, relays and
screw terminals for four free inputs and four free outputs,
connection to PROFIBUS DP with D-Sub socket.
BGT SA-9: slot 1 for PFA 700, slots 2-10 for PFU 760,
BGT SA-8: slot 1 for PFA 710, slots 2-9 for PFU 780
Order no.BGT SA-9U/1 DP700: 84402291BGT SA-8U/1 DP710: 84402292 (no illustration provided)
Module subrack BGT S-9U/1 for PFP 700, PFU 780
comprising:
module subrack, printed-circuit board with rear terminal strip,
function-tested, standard documentation, guide rails, without
partial front plates, screw terminals at the rear.
Slots 1 – 9 for PFU 760/780, slot 10 for PFP 700,
Order No. 84402281
PFU 780 · Edition 02.1256
8ace
30a
32c
F1
12ace
N
L1
PFP 700
UI
24 V=600 mA
0 V
O
I
S0
230 V
115 V
S1
Accessories
8.8 Power supply PFP 700
For supplying the control inputs of burner control unit PFU or
for supplying the auxiliary voltage to relay module PFR 704.
Operating status display on the front plate. PFP switches off
in the event of an output overload.
Output voltage 24 V, output rating 14 VA.
Order No. 84366510
PFU 780 · Edition 02.1257
2e2a2c
4e
6c
8e
1
115 V~
8c
max. 2 A, 264 Vmax. 2 A, 264 Vmax. 2 A, 264 Vmax. 2 A, 264 V
PFR 704
8a
6e
6a
230 V~
24 V=/~
0 V
10e10a10c
12e
16c
14e
2
14c
14a
16e
16a
0 V
18e18a18c
20e
24c
22e
3
22c
22a
24e
24a
0 V
26e26a26c
28e
32c
30e
4
30c
30a
32e
32a
0 V
115 V~
230 V~
24 V=/~
115 V~
230 V~
24 V=/~
115 V~
230 V~
24 V=/~
Accessories
8.9 Relay module PFR 704
For contact multiplication, e.g. if several air valves are activated
via a single control signal for pre-purge, or for heating/cooling switchover when using an MPT. Switching status display
on the front plate.
Input voltage:110/120 V AC, -15/+10%, 50/60 Hz,220/240 V AC, -15/+10%, 50/60 Hz,24 V AC/DC, ± 10%.
Current per relay: 25 mA.Contact rating of floating outputs: max. 2 A, 264 V (not
fused internally).Order No. 84373510
PFU 780 · Edition 02.1258
32b30a
N
L1
8b11b12b
PFA 700
µC
15b16b
1c
9c
VP
1. PFU
9. PFU
RxD/TxD-P
RxD/TxD-N
DGND
0 V
24 V=
…
…
ϑ
10c
1. PFU
9. PFU
…
2
1
1a
9a
1. PFU
9. PFU
…
10a
18a
1. PFU
9. PFU
…
19a
23a
1. PFU
5. PFU
…
20c
23c
6. PFU
9. PFU
30c
…
24 V
0 V
24 V
…
1
4
14b
18b
21b22b
…
…
1
4
23b
26b
24 V
24 V
I/O
18c
PFU
19c
17b
30e
26e
PFU
24 V
L1
PROFIBUS DP
Accessories
8.10 Field bus interface PFA 700
For connection of up to nine automatic burner control
units PFU760 to industrial communication networks using
PROFIBUS-DP, in order to transfer measuring, control and
regulation signals as a bundle.
4 digital inputs:24 V DC, ± 10%, < 10 mA,4 digital outputs:relay contact, max. 1 A, 264 V (not fused internally).
Mains voltage: 110 – 240 V AC, -15/+10%, 50/60 Hz.
Further information can be found in Technical information
PFA.
PFU 780 · Edition 02.1259
F1
2b4b
MPT 700
12–24 V
0 V
12–24 V
0
–
100%
GND
16b
14z
E1
14d
E2
16z
E3
14b
10b
12b
0 V
2z
A1
6b8b
COM
L1
30b
30z
30d
N
28b
28z
28d
PE
32b
32z
32d
20b
20z
mA
1
20d
mA
2
GND
100% – 0
18b
18z
18d
2d
A2
4z
A3
4d
A4
6z
A5
6d
A6
8z
A7
8d
A8
10z
1
12z
10d
µC
/
2
/
8888
88
Accessories
8.11 Impulse system MPT 700
With 11 outputs for activation of burner control units PFU 780.
The furnace atmosphere is circulated thanks to intermittent
operation, and thereby constant temperature distribution and
shorter heating-up periods for all gas-fired heat treatment
furnaces are ensured.
Mains voltage: 95–240 V AC, ± 10%, 50/60 Hz.
Power consumption: 10 VA.Additional auxiliary voltage: 12–24 V DC, ± 10%, max. 1.1 A.
Controller inputs: 2 x 0(4)–20 mA with common earth, floating,
approx. 2.7 kΩ.Digital inputs E1–E3: with common earth, floating, 12–24 V DC,
load impedance approx. 2.7 kΩ.Order No. 84395050Further information can be found in brochure MPT.
PFU 780 · Edition 02.1260
9 Technical data
▼
Mains voltage:
220/240 V AC, -15/+10%, 50/60 Hz or
110/120 V AC, -15/+10%, 50/60 Hz,
for grounded and ungrounded mains.
Power consumption: < 8 VA.
Control inputs:
Input voltage/current:
Pilot burner, main burner, air valve, multi-flame control and
remote reset:
24 V DC, ± 10%, < 7 mA per input.
Input voltage for safety interlocks, digital input DI and purge
= mains voltage.
Input voltage of signal inputs:
Rated value110/120 V AC220/240 V AC
Signal “1”80 – 132 V160 – 264 V
Signal “0”0 – 20 V0 – 40 V
Frequency50/60 Hz50/60 Hz
Rated value24 V DC
Signal “1”24 V, ±10%
Signal “0”< 1 V
Inherent current:
Signal “1”typ. 5 mA
Output voltage for voltage-related outputs = mains voltage.
Contact ratingGas valve V1, V2Max. 1 A resistive
Air valveMax. 1 A resistive
IgnitionMax. 1 A resistiveNumber of operat-
ing cycles
Max. 1,000,000,
typically 400,000
Max. 1 A cos ϕ 0.3
Max. 1 A cos ϕ 0.3
Max. 1 A cos ϕ 0.3
Max. 250,000,
typically 100,000
Output current: max. 2 A per output, but total current for
valves and ignition transformer max. 2.5 A.
Operation and fault signalling contacts:
dry contact (floating), max. 1 A, 24 V, not fused internally.
Number of operating cycles:Mains switch: 1000,Reset/Information button: 1000.
PFU 780 · Edition 02.1261
Technical data
Flame control:
Sensor voltage: approx. 230 V AC.
Sensor current: > 1 µA,
Length of sensor cable: max. 100 m.
Fuse in unit:
F1: 3.15 A, slow-acting, H pursuant to IEC 127-2/5,
F2: 3.15 A, slow-acting, H pursuant to IEC 127-2/5.
Ambient temperature:
-20 to +60 °C (-4 to +60.00 °C),
Climate: no condensation permitted.
Enclosure: IP 00 pursuant to IEC 529,
after installing in a 19” module subrack according to the in-
structions, e.g. type BGT, the front corresponds to IP 20.
Input/Output safety circuit:
All the inputs and outputs marked “
grams) may be used for safety tasks.
Weight: approx. 650 g (23 oz.).
” (see connection dia-
PFU 780 · Edition 02.1262
Technical data
9.1 Safety-specific characteristic values
In the case of ionization
control, suitable for Safety
Integrity Level
Diagnostic coverage DC97.9%
Type of subsystem
Mode of operation
Mean probability of dange-
rous failure PFH
D
Mean time to dangerous
failure MTTF
d
Safe failure fraction SFF99.2%
The specified values apply for the combination with ionization
electrode (sensor) and PFU 780 (logic).
Relationship between the Performance Level (PL) and the
Safety Integrity Level (SIL)
PLSIL
a–
b1
c1
d2
e3
SIL 3
Type B to EN 61508-2,
7.4.3.1.4High demand mode pursu-ant to EN 61508-4, 3.5.12
1.34 x 10-8 l/h
Max. service life under operating conditions:
20 years after date of production, plus max. 1/2 year in stor-
age prior to first use.For a glossary of terms, see page 67 (Glossary).
Pursuant to EN ISO 13849-1:2006, Table 4, the PFU can be
used up to PL e.
PFU 780 · Edition 02.1263
Technical data
3 HE =
133.4 (5.3“)
A
B
8 TE =
40.6 (1.6“)
D
9.2 Operating controls
A: 2-digit 7-segment displayB: Reset/Information button to reset the system after a fault
or to scan parameters on the displayC: Mains switchD: Optical interface
C
F2
F1
E: Type label
E
PFU 780 · Edition 02.1264
10 Maintenance cycles
Burner control unit PFU requires little servicing.
PFU 780 · Edition 02.1265
11 Legend
88
ϑ
1
ϑ
2
DI
1
2
Display
Blinking display
88
Ready
Safety interlocks (Limits)
Start-up signal, pilot burner
Start-up signal, main burner
Digital input
Ignition transformer
Gas valve
Air valve
P
Purge
A
Ext. air valve control
Flame signal
Operating signal, pilot burner
Operating signal, main burner
Fault signal
Reset
Input signal
Output signal
Flame simulation check
t
Waiting time ≥ 2 s
W
Safety time on start-up 3 s, 5 s or 10 s
t
SA
Safety time during operation < 1 s or < 2 s
t
SB
Ignition time 2 s, 3 s or 6 s
t
Z
Flame simulation delay time 25 s
t
LV
Flame proving period 0 – 25 s
t
FS
tBMinimum combustion time tSA up to max. 25 s
Minimum burner pause time 0 – 250 s
t
BP
Low fire over run time 0 s, 5 s, 15 s or 25 s
t
KN
Input/Output safety circuit
PFU 780 · Edition 02.1266
12 Glossary
t
12.4
Flame simulation/Flame simulation delay time t
LV
12.1 Waiting time t
01
t
W
W
02 02
t
Z
t
SA
30e
10e28c
16c
26a
18e
2c–4c
2e–4e
88
L1
ϑ
V1
V2
t
Once the start-up signal ϑ has been applied, the waiting time
tW starts to elapse. During this time, a self-test is conducted
to detect errors in internal and external circuit components. If
no malfunction is detected, the burner will start up.
12.2 Safety time on start-up tSA
This refers to the period of time between switching on and
switching off of the gas valve, when no flame signal is detected.
The safety time on start-up tSA(3, 5 or 10 s) is the minimum
operating time of the burner and burner control unit.
12.3 Ignition time tZ
If no malfunction is detected during the waiting time tW, the
ignition time tZ then starts to elapse. Voltage is supplied to
the pilot gas valve V1and the ignition transformer and the
burner is ignited. Theduration of the ignition time is either 2,
3 or 7seconds (depending on safety time tSA selected).
01 88
t
W
t
LV
01
30e
10e
28c
16c
26a
18e
2c–4c
2e–4e
L1
ϑ
V1
V2
t
An extraneous signal (flame simulation) is a flame signal that
is detected, although there should be no flame according to
the program sequence. If such an extraneous signal is detected, the flame simulation delay time tLV starts to elapse. If the
flame simulation is discontinued during the flame simulation
delay time tLV, start-up can be initiated or operation continued.
Otherwise, a fault lock-out occurs.
12.5 Safety time during operation t
04 04
2c–4c
2e–4e
t
SB
30e
10e
28c
16c
26a
18e
SB
88
L1
ϑ
V1
V2
t
If the flame fails during operation, the valve outputs are disconnected within the safety time tSB.
PFU 780 · Edition 02.1267
Glossary
The default safety time during operation tSB in accordance with
EN 298 is 1 second. In accordance with EN 746-2, the safety
time of the installation during operation (including closing time
of the valves) may not exceed 3 seconds (see “Project plan-
ning information”). Note the requirements of the Standards!
12.6 Flame signal
If a flame is detected, the flame detector will supply a flame
signal.
12.7 Fault lock-out
In the event of a fault lock-out, all valves and the ignition trans-
former are disconnected from the electrical power supply,
and a fault is signalled. Resetting must take place manually
following a fault lock-out.
12.8 Safety interlocks (Limits)
The limiters in the safety interlock (linking of all the relevant
safety control and switching equipment for the use of the ap-
plication, e.g. safety temperature limiter, minimum/maximum
gas pressure) must isolate input () from the voltage supply.
12.9 Pilot gas valve V1
The start fuel flow rate for the pilot burner is released by pilot
gas valve V1. It opens when the safety time on start-up t
starts to elapse. It remains open until the burner is switched
off again by a normal shut-down or fault lock-out.
SA1
12.10 Main gas valve V2
The start fuel flow rate for the main burner is released by main
gas valve V2. It opens when the safety time on start-up t
SA2
starts to elapse. It remains open until the burner is switched
off again by a normal shut-down or fault lock-out.
L1 (L1)
N (L2)
P
30e
26e
DI
22a
30a
20c230 V
32c24c
PFU 780
F1
sk1
l
22e
v1
16c
v2
18e
2a
a
4a
N
V1
V2
12.11 Continuous operation
The gas burner runs continuously for more than 24 hours.
12.12 Air valve
The air valve can be used
– for cooling,– for purging,– to control the burner capacity in ON/OFF mode and in
High/Low mode when using a pneumatic air/gas ratio
control system.
PFU 780 · Edition 02.1268
Glossary
12.13 Diagnostic coverage DC
Measure of the effectiveness of diagnostics, which may be
determined as the ratio between the failure rate of detected
dangerous failures and the failure rate of total dangerous
failures
NOTE: Diagnostic coverage can exist for the whole or parts
of a safety-related system. For example, diagnostic cover-
age could exist for sensors and/or logic system and/or final
elements. Unit: %.
from EN ISO 13849-1:2008
12.14 Mode of operation
High demand mode or continuous mode
Operating mode, where the frequency of demands for opera-
tion made on a safety-related system is greater than one per
year or greater than twice the proof-test frequency
from EN 61508-4:2001
12.15 Safe failure fraction SFF
Fraction of safe failures related to all failures, which are as-
sumed to appear
from EN 13611/A2:2011
12.16 Probability of dangerous failure PFHD
Value describing the likelihood of dangerous failure per hour
of a component for high demand mode or continuous mode.
Unit: 1/h
from EN 13611/A2:2011
12.17 Mean time to dangerous failure MTTFd
Expectation of the mean time to dangerous failure
from EN ISO 13849-1:2008
PFU 780 · Edition 02.1269
Feedback
Kromschröder AG
Michael Rehkamp
m.rehkamp@kromschroeder.com
Osnabrüc
k
Finally, we are offering you the opportunity to assess this “Technical Information (TI)” and to give us your opinion, so that we
can improve our documents further and suit them to your needs.
Clarity
Found information quickly
Searched for a long time
Didn’t find information
What is missing?
No answer
Use
To get to know the product
To choose a product
Planning
To look for information