Operating instructions
Safety shut-off valve JSAV 50 – 100
Translation from the German
© 2012 Elster GmbH

Contents

Safety shut-off valve JSAV 50 – 100 ........1

Contents ..............................1
Safety.................................1
Checking the usage .....................2
Type code .............................2
Part designations ........................2
Type label.............................. 2
Installation ............................2
Connecting the impulse line ..............3
Tightness test ..........................3
Checking the function ...................4
Checking the trip pressure p
Checking the tightness of the valve disc.......4
Setting the trip pressure p
Replacing the spring ....................4
Resetting..............................5
Replacing the measuring unit.............5
Replacing the valve disc .................6
Maintenance ...........................7
Technical data .........................7
Designed lifetime ........................ 7
Declaration of conformity ................8
Contact ...............................8
.............4
do
.............4
do

Safety

Please read and keep in a safe place
Explanation of symbols
, 1 , 2 , 3 ... = Action
= Instruction
Liability
We will not be held liable for damage resulting from non-observance of the instructions and non-com- pliant use.
Safety instructions
Information that is relevant for safety is indicated in the instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified gas technicians. Electrical interventions may only be carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM spare parts.
Transport
On receipt of the product, check that the delivery is complete (see Part designations). Report any trans- port damage immediately.
Storage
Store the product in a dry place. Ambient tempera- ture: see Technical data.
Changes to edition 08.12
The following chapters have been changed: Declaration of conformity JSAV 25 40, see operating instructions
for safety shut-off valves JSAV 25 – 40 www.docuthek.com Elster Kromschröder Products 02 Pressure regulators Safety shut-off valves JSAV Kind of document: Op- erating instructions JSAV 25 – 40
GB
GB-1
F
NL
I
E

Checking the usage

JSAV
Safety shut-off valve for securing downstream fittings against excess gas pressure. This function is only guaranteed when used within the specified limits see page 7 (Technical data). Any other use is considered as non-compliant.

Type code

Code Description
JSAV Safety shut-off valve 50 – 100 Nominal size F A
GB
40 Inlet pressure p /1 Trip pressure p
-0 Without pressure test point

Part designations

2
3
4
1 Measuring unit 2 Breather screw plug 3 Impulse line connection 4 Inlet 5 Outlet 6 Arrow of direction of flow 7 Reset
8 Arrow of direction of reset
9 Reset lever

Type label

Max. inlet pressure, upper trip pressure pdo, ambient temperature: see type label.
D-49018 Osnabrück, Germany
JSAV
Flange to ISO 7005
ANSI flange
= 4 bar (58 psig)
u max.
1
7
5
8
6
P
max:
u
Wh
:
o
p
:
do
AGo: +/- 10%
9

Installation

CAUTION
Please observe the following to ensure that the JSAV is not damaged during installation:
Sealing material, cuttings and other impurities
must not be allowed to get into the housing.
We recommend installing a filter upstream of the
JSAV in order to protect it against impurities in the pipe.
The installation location must be dry. Do not
store or install the JSAV in the open air.
Install the JSAV in the pipe free of mechanical
stress.
Do not clamp the unit in a vice or use it as a
do
lever. Risk of external leakage. Max. inlet pressure p Installation in the vertical or horizontal position,
4bar (58 psig).
u max.
never upside down.
1 The housing must not be in contact with ma-
sonry. Minimum clearance 20 mm (0.78"). Ensure that there is sufficient space for installation and adjustment.
2 Insert seal between pipe and unit. 3 Remove the adhesive foil from the inlet and outlet
on the JSAV.
Note direction of flow.
We recommend installing a manual valve AKT25
in the pipe leading to the safety relief valve
VSBV25, so that the annual function check of the safety shut-off valve JSAV can be carried out without having to remove it.
TS=
GB-2
F
NL
I
E
To prevent the VSBV from being unintentionally
shut off, we recommend removing the manual valve lever after commissioning and attaching it to the pipe.
JSAV
_>
VSBV
5DN

Connecting the impulse line

Remove the blind plug and connect an Rp¼ (¼ NPT) impulse line.
1 Install the impulse line and seal with an approved
sealing material. Ensure that there is sufficient tube length for the
impulse line.
Rp ¼ (¼ NPT)
0

Tightness test

WARNING
An additional tightness test must be carried
out on the JSAV at all joints which have been opened for maintenance work or replacement of spare parts.
Ensure that the valve seat of the JSAV is open,
see page 5 (Resetting).
1 Block the pipeline at the inlet and outlet.
Note max. test pressure.
JSAV inlet and outlet: max. 6 bar (87psig),
impulse line: max. 750 mbar (10.9 psig).
2 Slowly apply test pressure.
0
p
do
p
d
3
GB
N2 = max. 6 bar
4
N2 = max. 750 mbar
GB-3
F
NL
I
E

Checking the function

Checking the trip pressure pdo

The JSAV is checked for the required trip pressure pdo. 1 Vent the system.
Ensure that the valve seat of the JSAV is open,
see page 5 (Resetting). Ensure that the breather screw plug is screwed in.
2 Close all manual valves at the inlet and outlet,
and in the relief line.
CAUTION
Please observe the following to ensure that the regulator is not damaged during the function check:
GB
Do not exceed the maximum outlet pressurep
of the regulator.
3 Increase the outlet pressure p
until the required trip pressure pdo is reached.
p
do
p
d
The JSAV closes at the set trip pressure pdo.
4 5
klack
The JSAV has closed successfully: to restart the
system, the JSAV must be opened again, see page 5 (Resetting).
The JSAV does not close at the required trip
pressure pdo and must be readjusted, see page
4 (Setting the trip pressure pdo).

Checking the tightness of the valve disc

Ensure that the outlet is closed.
1 Vent the system. 2 Slowly open the manual valve at the inlet. 3 The outlet pressure p
d
on the regulator
d
0
must not rise.

Setting the trip pressure pdo

1 Select the trip pressure pdo according to the
outlet pressure pd of the pressure regulator.
500 450 400 350
[mbar]
300
do
p
250 200 150 100
50
d
20040 60 80 100 140 180 220 260 300 340
JSAV
2 Remove the breather screw plug. 3 Set the trip pressure pdo.
+–
4 Reset the JSAV, see page 5 (Resetting). 5 Check the required trip pressure pdo again, see
page 4 (Checking the function).
6 Screw the breather screw plug back in.

Replacing the spring

Various trip pressure ranges can be achieved by
using different springs on the JSAV.
1 Choose a spring according to the required trip
pressure range.
Trip pressure p
[mbar] [psig]
35 – 70 0.51 – 1.02 light blue 0 308 906 3
60 – 170* 0.9 – 2.5
120 – 220 1.74 – 3.2 crimson 0 308 906 5
190 – 400 2.8 – 5.8
300 – 550 4.35 – 8
* Standard spring
2 Remove the breather screw plug.
3 4
Spring table
do
Marking Order No.
reddish
brown
orange/
yellow
orange/
green
VSBV
pd [mbar]
0 308 906 4
0 308 906 6
0 308 906 7
5 Insert new spring. 6 Follow the reverse procedure when reassem-
bling.
7 Set the required trip pressure pdo, see page 4
(Setting the trip pressure pdo).
GB-4
F
NL
I
E
8 Screw in the breather screw plug.
5
5 76
9 After inserting the spring, take the spring’s label
from the packaging and stick it below the type label on the JSAV.
10 Clearly mark the adjusted value of the trip pres-
sure pdo on the sticker.

Resetting

Ensure that the impulse line is depressurized.
CAUTION
Please observe the following to ensure that the JSAV is not damaged during resetting:
Turn the reset lever gently and do not go further
than specified.
1 Remove the breather screw plug. 2 Press the reset lever and turn through 10° until
resistance can be felt.
~10°
3 Hold the reset lever in this position until the lever
can be easily turned further following pressure equalization.
4 Press and turn the reset lever until the valve disc
opens and clicks into place.
klack
The pin in the measuring unit must be at the top
after the valve disc has clicked into place.
6 Screw in the breather screw plug.
The JSAV is ready for operation.

Replacing the measuring unit

The measuring unit has to be replaced if the JSAV no longer opens or can no longer be reset.
We recommend cleaning the O-ring seats and
lightly greasing the O-rings with Klüber Nontrop
ZB91 DIN before installation.
1 Depressurize the system.
The measuring unit is supplied with 1 O-ring and
4 screws.
2 Ensure that the JSAV is closed. 3 Remove the breather screw plug.
The pin in the measuring unit must be at the
bottom when the JSAV is closed.
If the JSAV is open, apply pressure to the impulse line to close the valve.
4 Detach the impulse line from the JSAV.
8 Install the new O-ring in the housing. 9 Follow the reverse procedure when reassem-
bling.
10 Connect the impulse line to the JSAV. 11 Check tightness and function, see page 3
(Tightness test) and page 4 (Checking the function).
GB
GB-5
F
NL
I
E

Replacing the valve disc

8
The valve disc has to be replaced if the JSAV is
leaking or has been damaged during resetting.
We recommend cleaning the O-ring seats and
lightly greasing the O-rings with Klüber Nontrop
ZB91 DIN before installation.
1 Depressurize the system.
We also recommend replacing the entire seal set and the bellows when replacing the valve disc.
The seal set with bellows is available separately
as a spare part.
Ensure that the JSAV is closed.
GB
The pin in the measuring unit must be at the
bottom when the JSAV is closed.
If the JSAV is open, apply pressure to the impulse line to close the valve.
2 Detach the impulse line from the JSAV.
3
6
4 5
Press the reset lever and turn until the valve disc is on top.
7
Press the spring wire into the notch in the plate.
9
10
11
12 1413
15 16
Insert new O-rings from the seal set.
17 Follow the reverse procedure when reassembling
using the new valve disc and the O-rings from the seal set.
To ensure that the valve disc is pushed onto the seat by the spring, the spring wire must be
released from the notch in the plate and rest
against the housing wall.
WARNING
Risk of injury!
The spring wire is under high stress.
18 Connect the impulse line. 19 Check tightness and function, see page 3
(Tightness test) and page 4 (Checking the function).
GB-6
F
NL
I
E

Maintenance

In order to ensure smooth operation: check the func- tion and tightness of the JSAV every year, or every six months if operated with biologically produced methane, see page 4 (Checking the function) and page 3 (Tightness test).
In the case of malfunctioning, check the
measuring unit and valve disc and replace if necessary. Selecting spare parts: see free PartDetective DVD: www.kromschroeder.com Products DVD PartDetective, (D/GB). Replacing spare parts: see page 5 (Replacing the measuring unit), see page 6 (Replacing the valve disc).
After carrying out maintenance work or replacing
spare parts, check for tightness and function, see page 3 (Tightness test) and page 4 (Checking the function).

Technical data

Gas type: natural gas, town gas, LPG (gaseous), biologically produced methane (max. 0.02 %-by- vol. H2S) or air.
The gas must be dry in all temperature conditions
and must not contain condensate. Max. inlet presure p Max. test pressure for testing the JSAV: temporarily < 15 min. 6 bar (87 psig). Max. test pressure for testing the impulse line:
temporarily < 15 min. 750 bar (10.8 psig). Trip pressure pdo set at the factory: 120 mbar (46.8 "WC).
Adjusting range for trip pressure pdo, see page
4 (Replacing the spring), Spring table.
Accuracy group: AG 10.
Ambient temperature:
-15 to +60°C (5 to 140°F). Connection for housing: JSAV..F: flange to ISO 7005, JSAV..A: ANSI flange. Connection for impulse line: Rp ¼ (NPT ¼). Housing: GGG 40. Diaphragm: NBR, valve seat: aluminium, valve stem: stainless steel, valve disc: aluminium with vulcanized NBR seal.
4 bar (58 psig).
u max.

Designed lifetime

The Pressure Equipment Directive (PED) and the
Energy Performance of Buildings Directive (EPBD) demand regular checks on and maintenance of heating systems in order to ensure a high level of use in the long term, a clean method of operation and safe function.
The service life on which the construction is based,
hereinafter referred to simply as the “designed lifetime”, is compiled from the relevant standards.
You can find further explanations in the applicable
rules and regulations and on the afecor website (www.afecor.org).
This information on the designed lifetime is based on
using the product in accordance with these operat- ing instructions.
The product must be serviced at regular intervals.
Once the specified designed lifetime has been reached, the safety-related functions must be checked in accordance with the section entitled
“Maintenance”.
If the product passes the aforementioned function tests, you can continue to use it until the next sched- uled maintenance operation. At this point, these tests must be repeated. If the product fails one of the aforementioned tests, it must be replaced immediately.
This procedure applies to heating systems. For
thermoprocessing equipment, observe national regulations. Designed lifetime (based on date of manufacture) in accordance with DIN EN14382 Safety devices for gas pressure regulating stations and installations:
Designed lifetime
Switching cycles Time [years]
JSAV 15
Long-term use in the upper ambient temperature range accelerates the ageing of the elastomer ma- terials and reduces the service life (please contact manufacturer).
GB
GB-7
F
NL
I
E

Declaration of conformity

We, the manufacturer, hereby declare that the prod- ucts JSAV 50 – 100, marked with the product ID No. CE-0085AR0246, comply with the requirements of the listed Directives and Standards.
Directives: – 90/396/EEC 97/23/EC
Standard: DIN 3381 (06/84)
GB
The relevant product corresponds to the type tested
by the notified body 0085.
The production is subject to the surveillance pro-
cedure pursuant to DIN EN ISO 9001 according to
annex II, paragraph 3 of Directive 90/396/EEC and
annex III, module D of Directive 97/23/EC.
Elster GmbH
Scan of the Declaration of conformity (D, GB), see
www.docuthek.com.

Contact

Contact
If you have any technical questions, please contact
your local branch ofce/agent. The addresses are
available on the Internet or from ElsterGmbH.
We reserve the right to make technical modifications