Protective system control FCU 500 is designed to mon-
itor and control central safety functions, e.g. gas
gas
max.
, air
, pre-purge, tightness test, high tempera-
min.
ture operation or start enable for burner control units, in
multiple burner systems on industrial furnaces. In a furnace and zone control system, the FCU 500 assumes
central functions. The FCU 505 is used to monitor local
safety functions and to control the zone capacity. If the
centrally checked safety requirements, e.g. pre-purge,
flow detector and pressure switch check, have been
met, the FCUs issue the start enable signal to the burner control units.
The FCU is optionally available with integrated safety
temperature monitor or safety temperature limiter,
integrated tightness control and with an interface for
min.
,
controlling the capacity of actuators or a frequency
converter interface.
The program status and device parameters can be read
directly from the unit. The FCU can be activated manually using the integrated Manual mode for setting and
diagnostic purposes.
Thanks to the optionally integrated valve proving sys-
tem, the valves can be checked for leaks by querying
an external gas pressure switch or it can be checked
whether the gas valve on the inlet side is closed.
Using the BCSoft program, the parameters, analysis
and diagnostic information can be read from the FCU
via the optionally available opto-adapter. All valid parameters are saved on an integrated parameter chip
card. The parameter chip card can be removed from the
old unit and inserted into a new FCU to transfer the parameters, for example when replacing the unit.
FCU 500, FCU 505 · Edition 02.175
Application
The monitored outputs for the actuator and valves are
accommodated in a plug-in power module. This can
simply be replaced if necessary.
Once the plug-in power module has been removed, the param-
eter chip card and fuses are accessible.
The FCU can be installed on a DIN rail in the control
cabinet. Plug-in connection terminal strips on the FCU
make it easier to install and remove.
The external operator-control unit OCU is available as
an option for the protective system controls. The OCU
can be installed in the control cabinet door instead of
standard control units. The program status, statistics,
parameter values or fault messages can be read on
the OCU. For burner adjustment, the operating points
can be approached conveniently in Manual mode using
the operator-control unit.
Thanks to the operator-control unit OCU, display functions and
operation of the FCU can be relocated to the control cabinet
door.
The optional bus module BCM 500 makes it possible
to connect the FCU to a fieldbus interface in a Profinet
or Modbus TCP network. Networking via the fieldbus
enables multiple FCUs to be controlled and monitored
by an automation system (e.g. PLC). The bus module is
prepared for DIN rail installation. It is pushed on to the
FCU from the side.
The address for the fieldbus communication is set using three
code switches.
FCU 500, FCU 505 · Edition 02.176
Application
Roller hearth kiln in the ceramics
industry
Shaft melting furnaceSmelting and holding furnace
FCU 500, FCU 505 · Edition 02.177
Application
PZLPZHPZ
DGDGDG
DG
min
4915 131450
46
1
ϑ
2
3
FCU 500..F0
M
DG
max
µC
STM
DL
VAS
45
pu/2
P
>750°
47 4858
minDLPurge
PZLPDZ
DGDG
VAS
VAS
BCU 460..L
BCU 460..L
VCG
VR..L
VCG
VR..L
1.1 Application examples
1.1.1
ON/OFF ro tar y impul se contr ol
For processes which require a turndown of more than 10:1 and/or
those which require heavy circula-
M
TE
tion of the furnace atmosphere to
ensure a uniform temperature, e.g.
heat treatment furnaces operating
at low and medium temperatures in
the metallurgical industry.
With ON/OFF cyclic control, the
capacity supplied to the process is
controlled by means of a variable
ratio of the operating time to the
pause time. In this type of control,
the burner output pulse frequency
always maintains full momentum
and results in maximum convection
in the furnace chamber, even with
regulated heating.
The pneumatic ratio control sys-
tem controls the gas pressure on
the burner proportionally to the air
pressure and thus maintains a constant air/gas ratio. At the same time,
it acts as a low air pressure protection device.
▼
FCU 500, FCU 505 · Edition 02.178
Application
PZLPZHPZ
VAS
BCU 460..L
The ignition and monitoring of the
individual burners is ensured by
burner control unit BCU 460..L.
The centrally checked safety func-
tions such as pre-purge, tightness
M
test, flow detector and pressure
switch check (gas
air
) are provided by the FCU 500.
min.
min.
, gas
max.
,
45
P
>750°
VAS
pu/2
VAS
VCG
VR..L
BCU 460..L
DGDGDG
DG
46
1
ϑ
2
3
min
4915 131450
DG
max
µC
FCU 500..F0
47 4858
STM
DL
minDLPurge
M
PZLPDZ
DGDG
FCU 500, FCU 505 · Edition 02.179
VCG
VR..L
TE
Application
PZLPZHPZ
DGDGDG
DG
min
4915 131450
46
1
ϑ
2
3
FCU 500..F1
M
DG
µC
STM
DL
minDLPurge
VAS
max
45
P
>750°
TC
0°➔90°
53
90°➔0°
54
55
47 4858
PZLPDZ
DGDG
pu/2
1.1.2 Modulating burner control
For processes that do not require
heavy circulation in the furnace, e.g.
aluminium smelting furnaces.
This system is suitable for process-
VAS
BCU 460..L
M
es in which infiltrated air may flow
into the furnace through switched
off burners. The capacity can be
adjusted continuously by activating
the air control valve (analogue or
VAS
VCG
3-point step signal). The pneumatic
ratio control system controls the
gas pressure proportionally to the
air pressure and thus maintains a
constant air/gas ratio. At the same
BCU 460..L
time, it acts as a low air pressure
protection device.
One burner control unit per burner
is required for ignition and monitor-
VCG
M
ing.
The centrally checked safety func-
tions such as pre-purge, setting the
TE
valve to ignition position via a butterfly valve control system, tightness test, flow detector and pressure switch check (gas
air
) are provided by the FCU 500.
min.
min.
, gas
max.
,
FCU 500, FCU 505 · Edition 02.1710
Application
PZLPZHPZ
DGDGDG
DG
min
4915 131450
1
ϑ
2
3
FCU 500..F1
M
DG
µC
STM
DL
minDLPurge
VAS
max
45
P
57
16
>750°
TC
0°➔90°
53
90°➔0°
54
55
47 4858
PZLPDZ
DGDG
pu/2
1.1.3 Safety limits (LDS) for
modulating burner control
The centrally checked safety func-
tions such as pre-purge, setting the
valve to ignition position via a but-
VAS
BCU 560..F0
66
M
terfly valve control system, tightness test, flow detector and pressure switch check (gas
air
) are provided by the FCU 500.
min.
min.
, gas
max.
,
The capacity can be adjusted con-
VAS
VCG
tinuously by activating the control
element (analogue or 3-point step
signal).
To ensure that the correct air vol-
ume is available for ignition (start
BCU 560..F0
66
fuel flow rate) when starting the
burners, the FCU sends the burner
start enable signal to the BCUs via
the “LDS (limits during start-up)”
output.
VCG
M
The circuit design of the safety
interlock and LDS outputs on the
FCU and the corresponding in-
TE
puts on the BCUs ensures that the
burners can only start if the safety
interlocks and the LDS output have
enabled burner start-up.
FCU 500, FCU 505 · Edition 02.1711
Application
1.1.4 Flame control using the temperature
FCU 500..H1
HT
18
5-8
STM
HT
49
HT
49
BCU 56x..D
µC
5
BCU 56x..D
µC
5
M
In high temperature systems (temperature > 750°C),
the flame may be controlled indirectly via the temperature. As long as the temperature in the furnace chamber
is below 750°C, the flame must be controlled by conventional methods.
If the temperature in the furnace chamber rises above
the spontaneous ignition temperature of the gas/air
mixture (> 750°C), the FCU signals to the burner control
units via the fail-safe HT output that the furnace system is in High temperature mode (HT). When the HT input is activated, the burner control units switch to High
temperature mode. They operate without evaluation of
the flame signal and their internal flame control system
is non-functional.
If the furnace temperature falls below the spontaneous
ignition temperature (< 750°C), the FCU disconnects
the HT output from the electrical power supply. There
is no active signal at the HT inputs of the burner control
units. The flame signals are monitored once again by
the UV sensor or flame rod.
In the event of a fault in a temperature monitoring component (e.g. sensor discontinuity, sensor short-circuit)
or in the event of a mains failure, the flame control task
is transferred to the burner control units.
FCU 500, FCU 505 · Edition 02.1712
Application
PZLPZHPZ
66
46
4
FCU 505..F1
+24V
L1
4915 131450
1
2
3
FCU 500..F0
µC
475848
45
67
57
17
P
M
PZLPDZ
1.1.5 Furnace and zone control
The FCU 500 (furnace FCU) performs central tasks
such as checking the safety interlocks, fan control, system leak tightness check and pre-purge.
It signals to the FCU 505 in the zones that the butterfly
valves can be moved to the purge position. Signals are
1
µC
54 55
53
BCU
V1
V1
BCU
M
L1
BCU
+24V
BCU
V1
V1
66
46
1
4
FCU 505..F1
µC
54 55
53
M
sent to the butterfly valves by the FCU 505. The butterfly valves move into position. A signal is sent to the
FCU 505 via their safety interlock input that the central
FCU 500 has issued the enable signal for the burners.
FCU 500, FCU 505 · Edition 02.1713
Certification
2 Certification
Certificates – see Docuthek.
Certified pursuant to SIL
For systems up to SIL 3 pursuant to EN 61508.
Pursuant to EN ISO 138491:2006, Table 4, the FCU
can be used up to PL e.
EU certified pursuant to
– Gas Appliances Directive (2009/142/EC) in conjunc-
Factory Mutual Research Class: 7610 “Combustion Safe-
guards and Flame Sensing Systems”. Suitable for applications pursuant to NFPA 86. www.approvalguide.com
FCU 500, FCU 505 · Edition 02.1714
Function
3 Function
3.1 Connection diagram
3.1.1 FCU 500
Detailed connection diagrams for actuators and fre-
quency converters, see from page 91 (Capacity control)
ϑ
PZL
PZL
Air
min
p
u
PZL
GZL
2
PZH
PZH
Gas
Air
PDZ
Gas
P72
P72
PDZ
min
PZL
PZL
max
Electrical connection, see page 120 (Project planning
information)
Explanation of symbols, see page 144 (Legend)
1 2 3 46 47 48 49 50 4 6752 45 51 65 66 68
62 615 6 7 811
44
STM/
STL
+ - + -
24V
DC
88
12
3,15AT
41 4216
17 18 57
13 14 1553
I
N
× 0.6
LDS
k11 k21
K2
K1
HT
P
V2
V1
V3
µC
FCU 505
FCU 500
5AT
54 55 56
58
M
0 V
N
L1
+24 V
0.6 × I
P69
P70
P70
P71
P71
P73
P73
N
FCU 500, FCU 505 · Edition 02.1715
Function
3.1.2 FCU 505
Detailed connection diagrams for actuators and fre-
quency converters, see from page 91 (Capacity control)
Electrical connection, see page 120 (Project planning
information)
Explanation of symbols, see page 144 (Legend)
L1
+24 V
PZH
PZH
0.6 × I
Gas
N
STM/
STL
ϑ
1 2 3 46 47 48 49 50 4 6752 45 51 65 66 68
62 615 6 7 811
PZL
PZL
Air
Air
PDZ
Gas
P72
P72
PDZ
min
PZL
PZL
max
min
+ - + -
24V
DC
88
12
3,15AT
41 4216
17 18 57
13 14 1553
p
u
PZL
GZL
2
P69
P70
P70
P71
P71
P73
P73
µC
FCU 505
54 55 56
I
N
× 0.6
LDS
V1
k11 k21
K2
K1
HT
P
V2
M
V3
0 V
N
FCU 500, FCU 505 · Edition 02.1716
Function
3.1.3 Assignment of connection terminals
TerminalTypeDesignationFunction
1
2Controlled air flow
24 V DC input
3Remote resetInput for ex ternal signal (button) to reset the unit after a fault lock-out
4Operating signal
5, 6
and
7, 8
11, 12V AC inputSupply voltage
13
14Gas valve V2Connection of phase for gas valve V2
15Gas valve V3Connection of phase for gas valve V3
57Safety interlocks (limits)Safety enable signal to the burner control units
16Safety limits (limits during start-up)
17PurgeSignal to FCU 505 or burner control units to inform them that purge is in process
18High temperature operationEnable signal from the FCU indicating that the furnace system is in High temperature mode
41
42Operating signalOperation signalling output, 24 V DC, max. 0.1 A
4424 V DC inputFan ready for operationFeedback signal from fan indicating readiness for operation, see Parameter 31
Double
thermocouple
Safety circuit output
24 V DC output
Start-up signalSignal applied: FCU start; no signal: FCU stop
Signal applied: fan is started to supply air to the combustion chamber for cooling, for
example. Only functional in standby. The function is deactivated as soon as a signal is
received at terminal 1 (FCU start).
Signal from the burner control units to inform the FCU that a sufficient number of burners is
available for temperature control
Safety temperature monitor and/or
safety temperature limiter
Gas valve V1Connection of phase for gas valve V1
FaultFault signalling output, 24 V DC, max. 0.1 A
Monitor the spontaneous ignition temperature of the gas/air mixture in High temperature
mode and/or the maximum furnace or flue gas temperature using the integrated
temperature module of the FCU..H1
Voltage to operate the FCU,
11 = phase (L1), 12 = neutral conductor (N)
To ensure that the correct air volume is available for ignition (start fuel flow rate) when
starting the burners, the FCU sends the burner start enable signal to the burner control
units via this output.
▼
FCU 500, FCU 505 · Edition 02.1717
Function
TerminalTypeDesignationFunction
45
46Controller enable/emergency stop
47Minimum air pressure
48Minimum air flow
49Minimum gas pressureConnection for pressure switch to monitor the minimum gas pres sure, see Parameter 13
50Maximum gas pressureConnection for pressure switch to monitor the maximum gas pressure, see Parameter 12
51, 65,
66, 67,
68
52
53, 54,
55, 56
58Fan
Safety circuit input
V AC output
Valve proving system
Programmable inputs
Feedback from actuator/frequency
converter
Capacity control
Connection for the sensor of the valve proving system (tightness control pressure switch or
POC switch for checking the closed position).
Connection for higher-level safety devices and interlocks (e.g. emergency stop, safety
temperature monitor), see Parameter 10
Connection for pressure switch to monitor the minimum air pressure, see
Parameter 15
Connection for a sensor to monitor the minimum air flow during pre-purge or post-purge,
see Parameters 35, 38
The terminals can be assigned a function using parameters. To do so, logical AND gatings
with terminals 46, 47, 48, 49 or 50 are possible.
Connection for the position feedback signal from the actuator/frequency converter
Connection for capacity control using an actuator or frequency converter,
see Parameter 40 to 47
Connection for fan control. Alternatively, this output can be used to activate a valve to check
the function of the air pres sure switch.
FCU 500, FCU 505 · Edition 02.1718
Function
3.2 Program sequence
3.2.1 FCU 500..F0
Example of application, see page 8 (ON/OFF rotary
impulse control)
Switch on the FCU
▼
In the event of fault signal: reset
▼
00
H0
Switch-on delay time t
01
1
P1
08
Enable signal to burner control units for the burner start via the “safety
Start-up position/standby
▼
Start-up with ϑ signal
▼
running (parameter 63)
Safety interlocks check
Fan run-up time tGV running (parameter 30)
Pre-purge time tPV running (parameter 34)
Tightne ss test (if equipped with TC)
Gas enable via valves V1 and V2
E
▼
Pre-purge starts
▼
Air flow monitoring
▼
▼
interlock” output
▼
Operation
FCU 500, FCU 505 · Edition 02.1719
Function
3.2.2 FCU 500..F1, FCU 500..F2
Example of application, see page 10 (Modulating
burner control)
Switch on the FCU
▼
In the event of fault signal: reset
▼
00
H0
01
A
P1
A
H7
H8
08
Switch-on delay time t
Actuator moves to the position for maximum capacity
1
Actuator moves to the position for ignition capacity
Enable signal to burner control units for the burner start via the
Controller enabler signal delay time t
Start-up position/standby
▼
Start-up with ϑ signal
▼
running (parameter 63)
Safety interlocks check
E
▼
Fan run-up time t
running (parameter 30)
GV
Pre-purge starts
▼
▼
Air flow monitoring
▼
Pre-purge time t
Tightne ss test (if equipped with TC)
running (parameter 34)
PV
▼
▼
Gas enable via valves V1 and V2
“safety interlock” output
▼
▼
Operation/controller enable
running
RF
FCU 500, FCU 505 · Edition 02.1720
Function
3.2.3 FCU 505..F1, FCU 505..F2
Example of application, see page 13 (Furnace and
zone control)
Switch on the FCU
▼
In the event of fault signal: reset
▼
00
H0
01
A
P1
H8
08
Switch-on delay time t
Actuator moves to the position for maximum capacity
A
Actuator moves to the position for ignition capacity
Controller enabler signal delay time t
Start-up position/standby
▼
Start-up with ϑ signal
▼
running (parameter 63)
Safety interlocks check
E
▼
Fan run-up time t
running (parameter 30)
GV
Pre-purge starts
▼
▼
FCU 500 pre-purge time t
Tightne ss test (if equipped with TC)
▼
▼
▼
Operation/controller enable
running
PV
running
RF
FCU 500, FCU 505 · Edition 02.1721
Function
3.3 Animation
The interactive animation shows the function of the
protective system control FCU 500.
Click on the picture. The animation can be controlled
using the control bar at the bottom of the window (as
on a DVD player).
To play the animation, you will need Adobe Reader 9 or a
FCU 500, FCU 505 · Edition 02.1722
newer version. If you do not have Adobe Reader on your
system, you can download it from the Internet. Go to
ww w.adobe.com, click on “Adobe Reader” at the bottom
of the page and follow the instructions.
If the animation does not start to play, you can download it from the document library (www.docuthek.com)
as an independent application.
Temperature monitoring
4 Temperature monitoring
The FCU..H1 is fitted with an integrated temperature
module.
This module can be used as a safety temperature moni-
tor (STM) to monitor the spontaneous ignition temperature of the gas/air mixture or as a safety temperature
limiter (STL) to monitor the maximum furnace/flue gas
temperature. Double thermocouples are connected to
the temperature module to measure the temperature.
The functions STM and STL can also be combined. In
this case, the connected double thermocouple must reliably detect whether the spontaneous ignition temperature (> 750°C) has been exceeded and also whether
the maximum permitted furnace temperature has been
exceeded.
The safety temperature monitor and safety temperature
limiter functions can be adjusted to the requirements of
the system using parameters 20, 22, 23, 24 and 25, see
page 82 (High temperature operation).
FCU 500, FCU 505 · Edition 02.1723
Temperature monitoring
4.1 High temperature operation with safety
temperature monitor function (STM function)
As soon as the temperature in the furnace chamber
is above the spontaneous ignition temperature of the
gas/air mixture (> 750°C), the FCU signals to the downstream burner control units via the fail-safe HT output
that the furnace system is in High temperature mode
(HT). When the HT input is activated, the burner control
units switch to High temperature mode. They operate
without evaluating the flame signal and their internal
flame control is non-functional.
If the furnace temperature falls below the spontaneous
ignition temperature (< 750°C), the FCU disconnects
the HT output from the electrical power supply. As soon
as the signal to the HT inputs of the burner control
units is no longer present, the flame signals are once
again monitored by a UV sensor or flame rod.
In the event of a fault in a temperature monitoring component (e.g. sensor discontinuity, sensor short-circuit)
or in the event of a mains failure, the flame control task
is transferred to the burner control units.
Either the temperature module integrated in the FCU..
H1 or an external safety temperature monitor (STM)
can be used for High temperature mode. Pre-purge
can be disabled for both versions in High temperature
mode, see page 86 (Pre-purge during high temperature operation).
4.1.1 With integrated STM
The integrated temperature module (STM) can be used
for high temperature operation. Pre-purge can be disabled in High temperature mode, see page 86 (Prepurge during high temperature operation).
FCU 50x..H1
HT
18
5-8
STM
HT
6
HT
6
BCU 4xx..D
µC
9
BCU 4xx..D
µC
9
M
FCU 500, FCU 505 · Edition 02.1724
Temperature monitoring
M
BCU 4xx..D
µC
9
BCU 4xx..D
µC
9
HT
18
6
6
HT
HT
4.1.2 With external STM
An external safety temperature monitor (STM) can be
used for high temperature operation. Pre-purge can
be disabled in High temperature mode, see page 86
(Pre-purge during high temperature operation).
FCU 50x..H0
FCU 50x..H1
HT
18
66
BCU 4xx..D
µC
HT
6
9
BCU 4xx..D
µC
HT
6
9
STM
M
4.1.3 With integrated and external STM
The integrated temperature module can also be used in
conjunction with an external safety temperature monitor (STM). The spontaneous ignition temperature can
then be monitored at two different points in the furnace.
FCU 50x..H1
5-8
STM
66
STM
FCU 500, FCU 505 · Edition 02.1725
Temperature monitoring
4.2 Maximum temperature monitoring with
(flue gas) safety temperature limiter (STL/FSTL
function)
As soon as the maximum permitted temperature limit
is reached in the furnace or in the flue gas or an error
occurs on the monitoring equipment within the permitted temperature range (e.g. sensor discontinuity, sensor
short-circuit), the FCU will perform a fault lock-out. The
safety interlock output will no longer be set.
The temperature module integrated in the FCU..H1 or
an external safety temperature limiter (STL) can be
used for this function.
4.2.1 With integrated STL/FSTL
FCU 50x..H1
5-8
57
STL
BCU 4xx..D
5
BCU 4xx..D
BCU 4xx..D
5
9
9
9
4.2.2 With external STL/FSTL
FCU 50x..H0
FCU 50x..H1
57
46
BCU 4xx..D
STL
M
M
5
9
BCU 4xx..D
BCU 4xx..D
5
9
9
FCU 500, FCU 505 · Edition 02.1726
Air control
M
PZLPZHPZ
PZLPDZ
TE
BCU 580..F3
FCU 500..F0
µC
P
DGDGDG
VAS
VAS
VAGVAS
VAS
VR..L
VR..L
DGDG
DG
minDGmax
4915131450
45
474858
>750°
pu/2
ϑ
1
46
2
3
DL
minDLPurge
BCU 580..F3
VAGVAS
VAS
M
5 Air control
Acting as the furnace protective system, the FCU 500
assumes the task of central air control on a furnace. It
controls and monitors the required air volume for startup, during operation and after the furnace has been
shut down. The fan is activated by the FCU for this purpose. The static air pressure and the air volume for prepurge can be monitored by pressure switches.
VAS
BCU 580..F3
4915 131450
46
1
ϑ
2
3
FCU 500..F0
M
µC
P
>750°
47 4858
STM
DL
minDLPurge
PZLPDZ
DGDG
45
VR..L
BCU 580..F3
VR..L
The capacity control function provided by the FCU 500..
F1/F2 and FCU 505..F1/F2 allows an additional central actuator or a frequency-controlled fan to be controlled and monitored. While the furnace is starting up,
the capacity control system controls and monitors the
required air volumes for purging and for starting the
burners. During operation, the FCU enables the external temperature control system for capacity control.
FCU 500, FCU 505 · Edition 02.1727
Air control
ϑ
PZL
PZL
Air
min
p
u
PZL
GZL
2
P71
P71
P73
P73
L1
+24 V
PZH
PZH
0.6 × I
Gas
N
Air
PDZ
Gas
P69
P72
P72
PDZ
min
P70
P70
PZL
PZL
max
5.1 Controlled air flow
On FCU 500, actuation of the input at terminal 2 acti-
vates the controlled air flow function. The fan (terminal 58) is started in standby (with no start-up signal).
Air is fed to the combustion chamber, e.g. for cooling.
1 2 3 46 47 48 49 50 4 6752 45 51 65 66 68
62 615 6 7 811
44
STM/
STL
+ - + -
24V
DC
88
µC
FCU 505
FCU 500
5AT
12
3,15AT
41 4216
17 18 57
13 14 1553
54 55 56
58
I
N
× 0.6
LDS
k11 k21
K2
K1
HT
P
V3
V2
V1
M
The FCU starts the fan depending on the functions
defined using parameters, see also page 81 (Low air
pressure protection), page 88 (Air monitoring during
controlled air flow) and page 89 (Air flow monitoring
during pre-purge).
The controlled air flow function is no longer performed
once the start-up signal has been received at terminal 1.
0 V
N
FCU 500, FCU 505 · Edition 02.1728
Air control
CU
V1
CU
V1
µC
5455
53
1
6
(
)
V
M
1
7
▼
5.2 Capacity control
As soon as a start-up signal has been received by the
FCU..F1/F2 (terminal 1), the fan of an FCU 500..F1/F2
is started via terminal 58 after the switch-on delay time
has elapsed. The air volume for pre-purge is requested
via the outputs for central capacity control (terminals
53 to 56). Air flow monitoring (terminal 48) starts. The
pre-purge time starts if there is adequate air flow.
After the elapse of the pre-purge time, the air volume
for ignition is requested. After the program has ended
(limits during start-up, pre-purge and also tightness
test for FCU..C1), the gas enable signal is issued via the
valve outputs V1 (terminal 13) and V2 (terminal 14) and
the burner start enable signal is issued to the burner
control units via the “safety interlock” output (terminal 57).
The correct air volume for ignition (start fuel flow rate)
must be available for each burner start, restart or startup attempt. To this end, the FCU sends the burner start
enable signal to the BCUs via the “LDS (limits during
start-up)” output.
A corresponding circuit design between the FCU and
the BCUs ensures that the burners can only start if the
safety interlocks and the LDS output are active.
7
BCU..F0
+24
4
FCU 500..F1
M
6
16
57
5
1
B
B
FCU 500, FCU 505 · Edition 02.1729
Air control
CU
V
CU
V
µC
5455
53
1
6
(
)
V
M
After the burner operating signal from the burner con-
trol units has been received, the FCU enables the control system for operation. For pertinent parameter settings, see page 101 (Burner operating signal).
7
BCU..F0
+24
+24V
4
4
FCU 500..F1
1
B
1
54 55
53
B
1
M
Depending on parameter 40, actuators IC 20 and IC 40,
an actuator with an RBW interface or a fan controlled
by a frequency converter can be actuated via the outputs for central capacity control, see page 91 (Capacity control).
FCU 500, FCU 505 · Edition 02.1730
Loading...
+ 118 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.