Krom Schroder FCU 505, FCU 500 Operating Instructions Manual

F
NL
I
E
0506
D GB F NL I E
TR CZ PL RUS H
DK S N P GR
www.docuthek.com
Operating instructions

Protective system control FCU 500 Furnace zone control FCU 505

© 2015 Elster GmbH · Edition 03.15
Translation from the German

Contents

Contents
Protective system control FCU 500
Furnace zone control FCU 505 ............
Contents ..............................
Safety.................................
Checking the usage .....................
Installation ............................
Replacing the protective system/furnace
zone control ...........................
Cable selection.........................
Wiring ................................4
Connection diagram ....................6
FCU 500 ..............................6
FCU 505 .............................. 7
IC 20 connected to FCU..F1 ...............8
IC 20 E connected to FCU..F1..............9
IC 40 connected to FCU..F1 ..............10
RBW valve connected to FCU..F2 .......... 11
Frequency converter connected to FCU..F2 ..12
Adjustment ...........................
Commissioning........................
Manual mode .........................4
Assistance in the event of malfunction ....5
Replacing the fuse ......................21
Parameters and values .................
Legend...............................4
Technical data ........................4
Designed lifetime .......................25
Logistics .............................5
Accessories ..........................5
Certification ..........................6
Contact ..............................6

Safety

Safety
Please read and keep in a safe place
Please read through these instructions carefully before installing or operating. Following the installation, pass the instructions on to the opera­tor. This unit must be installed and commissioned in accordance with the regulations and standards in force. These instructions can also be found at www.docuthek.com.
Explanation of symbols
,  ,  ,  ... = Action
= Instruction
Liability
We will not be held liable for damage resulting from non-observance of the instructions and non-com­pliant use.
Safety instructions
Information that is relevant for safety is indicated in the instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified gas technicians. Electrical interventions may only be carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM spare parts.
Changes to edition 09.4
The following chapters have been changed: – Replacing the protective system/furnace zone
control
– Certification
GB
GB-1
F
NL
I
E

Checking the usage

The protective system control FCU 500 and furnace
zone control FCU 505 are designed for the moni­toring and controlling of central safety functions in multiple burner systems on an industrial furnace.
The FCU500 controls multiple zones acting as the
central protective system control. The FCU505 is used for protective system and capacity control in individual furnace zones.
Type code
Code Description FCU 500 FCU 505
GB
Q W C0 C1
F0 F1 F2
H0 H1
K0 K1 K2
Part designations
1
2
Mains voltage: 120 V AC, 50/60 Hz
Protective system control
Furnace zone control
230 V AC, 50/60 Hz
No valve proving system
With valve proving system
Capacity control:
none
with interface for actuator IC
with interface for RBW
Temperature monitoring:
none
with temperature monitoring
Connection terminals:
none
screw terminals
spring force terminals

Installation

Installation position: vertically upright, horizontal or tilted to the left or right.
The FCU mounting is designed for horizontally
aligned 35 × 7.5 mm DIN rails.
If the DIN rail is aligned vertically, end clamps are required (e.g. Clipfix 35 by Phoenix Contact) to prevent the FCU from slipping.
Install in a clean environment (e.g. a control cabinet) with an enclosure ≥ IP 54, whereby no condensation is permitted.
1
3
4
5
6
7
8
LED display for program status and fault
messages
Reset/Information buttonOn/Off button 4 Type label 5 Connection for opto-adapter 6 Power module, detachable 7 Power module type label 8 Parameter chip card
Type designation (FCU…), construction stage, input
voltage – see type label.
FCU
GB-2
F
NL
I
E

Replacing the protective system/ furnace zone control

Disconnect the system from the electrical power
supply.
2
Disengage the FCU from the DIN rail.
4 5
to the new FCU.
▷ Remove the parameter chip card from the old
FCU and insert into the new FCU.
CAUTION
Malfunction (fault message
new FCUs must have the same hardware confi­guration (see type designation on type label). The parameter chip card is not backward compatible. If the parameter chip card has been operated in an FCU with more recent firmware, it cannot be used in a device with older firmware.
Alternatively, the parameters values can be read from the old FCU and then read back into the new FCU using the separate BCSoft software, see pages 13 (Adjustment) and 25 (Ac­cessories).
7 Slide the power module back on. 8 Mount the FCU on the DIN rail again. 9 Reconnect the connection terminals. 0 Switch the system on again, see page 13
(Commissioning).
Fault message
: Parameter chip card from FCU construction stage B or above has been inserted into FCU construction stage A, see also page 15 (Assistance in the event of malfunc­tion).
)! The old and

Cable selection

Use cables suitable for the type of operation and complying with local regulations.
Signal and control line for screw terminals max. 2.5mm2, for spring force terminals max.
1.5mm2.
Do not route FCU cables in the same cable duct as frequency converter cables or cables emitting strong fields.
Control lines must fulfil the requirements of EN60204-1, Chapter12.
▷ Avoid external electrical interference.
GB
GB-3
F
NL
I
E

Wiring

Do not reverse phase L1 and neutral conduc­tor N.
▷ Do not install different phases of a three-phase
current system at the inputs.
Do not connect voltage to the outputs.
A short-circuit on the outputs causes one of the
replaceable fuses to trip.
Ensure that the inputs at terminals 1 to 4 and
44 are only supplied with 24 V DC.
24 V DC power supply: + at terminal 62, - at terminal 61.
Ensure that the 24 V DC outputs at terminals
GB
41 and 42 are not connected to mains voltage.
▷ Do not set the remote reset so that it operates
automatically in cycles.
▷ Wire the safety circuit inputs via contacts (relay
contacts) only.
▷ The unit features an output for fan control (termi-
nal58). This single-pole contact can be loaded with a max. of 3A. The max. start-up current of the fan motor may not exceed a value of max. 6A for 1s– use an external contactor if required.
The limiters in the safety interlock (linking of all the
relevant safety control and switching equipment for the use of the application, for example, safety temperature limiter) must isolate terminal46 from the voltage supply. If the safety interlock is in­terrupted, the display shows a blinking a warning signal and all of the FCU’s control outputs are disconnected from the electrical power supply.
Connected control elements must be equipped with protective circuits in accordance with the manufacturer’s instructions. The protective circuit prevents high voltage peaks which can cause malfunctioning of the FCU.
Functions of terminals 51, 65, 66, 67 and 68 are
dependent on parameter values:
Terminal Dependent on parameter
51 69 65 70 66 71 67 72 68 73
See page 22 (Parameters and values).
Disconnect the system from the electrical power
supply.
Before wiring the FCU, ensure that the yellow
parameter chip card has been installed in the FCU– see page 3 (Replacing the protective system/furnace zone control).
Screw terminals or spring force terminals are available for the FCU– see page 25 (Acces­sories).
Wire as shown on the connection diagram– see
page6 (Connection diagram).
50
as
▷ Ensure a good PE (ground) wire connection to
the burner control units and burners.
FCU..H
Use type K NiCr-Ni, type N NiCrSi-NiSi or type S Pt10Rh-Pt Class 1 double thermocouples only.
Thermocouple
Temperature range
(°C) Type K NiCr-Ni -40 to 1000 Type N NiCrSi-NiSi -40 to 1000 Type S Pt10Rh-Pt 0 to 1600
Parameter 22 = 1: Type K double thermocouple NiCr-Ni
Parameter 22 = 2: Type N double thermocouple NiCrSi-NiSi
Parameter 22 = 3: Type S double thermocouple Pt10Rh-Pt
▷ STM:
Parameter 20 = 1: High temperature operation with STM. Position the double thermocouple at the coldest point in the furnace so that it can reliably detect whether the spontaneous igni­tion temperature (>750°C) has been exceeded.
▷ STL:
Parameter 20 = 2: Maximum temperature moni­toring using STL. Position the double thermo­couple at the warmest point in the furnace so that it can reliably detect whether the maximum permitted temperature has been exceeded.
▷ STL and STM:
Parameter 20 = 3: High temperature operation
with STM and maximum temperature monitor­ing with STL. Position the double thermocouple in the furnace in such a way that it can reliably detect whether the spontaneous ignition tem­perature (>750°C) has been exceeded and also whether the maximum permitted furnace temperature has been exceeded.
FCU..C
Parameter 51 = 1: Tightness test before furnace start-up.
Parameter 51 = 2: On; tightness test after fur­nace shut-down, after a fault lock-out or after mains on.
Parameter 51 = 3: On; tightness test before furnace start-up and after furnace shut-down.
Parameter 51 = 4: Permanent via proof of closure function (POC).
GB-4
F
NL
I
E
Safety interlock output in the case of higher
N
24 25 26 2718 19 20
50 5130 31 32 33 34 35 36 37 38
23
22
21
6
17
28
29
max. 2 A
253 V
max. 2 A
253 V
F3
power requirement
The burner start enable signal is issued to the
connected burner control units or automatic bur­ner control units via the safety interlock output (terminal 57). For burner control units or automatic burner
control units whose safety interlock input has a power consumption of ≤ 2 mA, the power (max. 0.5 A, cos ϕ = 1) of the FCU is sufficient to directly activate them.
In the event that a higher output current is re­quired, the output current can be increased by means of a contact multiplier using two contac­tors. Design the circuit as follows:
L1
N
K2
K1
90°
FS
90°
53 54 55 56 57 5849 50 51 52
Input BCU/IFD
5AT
3.15AT × 0.6
N
F = I
k1k1
k2k2
BCU with power supply for valves and ignition transformer via safety interlocks (terminal 5)
F1
N
5
PE
6
7 8 119 10 1 2 13 14 15
230 V AC
N N
≤ 2.5 A
Z
I
V1
L1
In the event that a higher output current is re­quired, the output current can be increased by means of a contact multiplier using three contac­tors. Design the circuit as follows:
P
Input BCU
Terminal 22
k3
L1
K3
K2
K1
1
V2
GB
N
13 14 15 16 17
53 54 55 56 5749 50 51 52
Input BCU
FCU 500
68
48
11 12
FCU 500
48
Terminal 5
× 0.6
N
F = I
k2
k1
k2
k3 k1
68
GB-5
F
NL
I
E

Connection diagram

FCU 500

Legend– see page24 (Legend).
HT
P
GB
LDS
V3
V2
V1
13 14 15 16 17 1811 123 41 2
FS
3.15AT
90°
90°
M
53 54 55 56 57 5849 50 51 52
5AT
K2 K1
IN × 0.6
k11
k21
P69
max
PZH
Gas
min
PZL
FCU 500
68
67
47 48
66
P72
P71 P73
Gas
Air
min
Air
PDZ
PZL
46
STL
STM/
+ - + -
5 6 7 8
65
P70
u
p
1
4
PZ
u
2
p
N
0.6 x I
A
Output
+24 V DC
61 62
41 42 44 45
ϑ
L1
+24 V
0 V
N
GB-6
F
NL
I
E

FCU 505

Legend – see page 24 (Legend).
HT
P
V1
LDS
V2
STM/
V3
STL
+ - + -
K2 K1
IN × 0.6
k11
90°
FS
13 14 15 16 17 1811 123 41 2
3.15AT
90°
53 54 55 56 57 5849 50 51 52
5AT
M
k21
GB
P69
max
PZH
Gas
min
PZL
FCU 505
68
67
47 48
66
P72
P71 P73
Gas
Air
min
Air
PDZ
PZL
46
65
5 6 7 8
P70
u
p
1
4
PZ
u
2
p
N
0.6 x I
A
L1
Output
+24 V DC
61 62
41 42 44 45
N
0 V
+24 V
GB-7
F
NL
I
E
IC 0 connected to FCU..F
V1
V2
V3
LDS
HT
P
STW/
STB
Parameter 40 = 1.
Continuous control via three-point step controller.
GB
6 7 8
46
65
47 48
66
FCU 500
67
13 14 15 16 17 1811 12
3.15AT
5AT
90°
FS
90°
53 54 55 56 57 5849 50 51 52
68
L1 N PE
90°
S11
90°
3 2 116 67 4812 1115 13
S3 S4
IC 20
PE
S10
90°
S1S2
M
GB-8
F
NL
I
E
IC 0 E connected to FCU..F
V1
V2
V3
LDS
HT
P
STW/
STB
Parameter 40 = 1. Continuous control via analogue input.
6 7 8
46
65
66
FCU 500
47 48
67
3.15AT
68
OUT
IN
20 19 18 3 2 167 4812 11
A
D
A
D
ON
1 2 3 4 5 6
90°
+ +
131516
S2
5AT
13 14 15 16 17 1811 12
FS
GB
90°
90°
53 54 55 56 57 5849 50 51 52
L1 N
IC 20..E
R
S4
PE
90°
OK
90°
517
S1
PE
S10
R
S3
µC
R
M
GB-9
F
NL
I
E
IC 40 connected to FCU..F
V1
V2
V3
LDS
HT
P
STW/
STB
Parameter 40 = 2. Continuous control via analogue input. Set IC 40 to operating mode 27, see operating
instructions Actuators IC 20, IC 40, IC 40S.
GB
7 8
46
66
FCU 500
47 48
67
22 21 20
13 14 15 16 17 1811 12
3.15AT
FS
5AT
90°
90°
53 54 55 56 57 5849 50 51 52
68
mA
19 18 16 15 14 12 11 10 8 7 5 4 2 1
A
D
AC
IC 40
L N
DC
R..
M
PE
GB-10
F
NL
I
E
RBW valve connected to FCU..F
V1
V2
V3
LDS
HT
P
STW/
STB
+ - + -
V1
V2
V3
LDS
HT
P
+ - + -
STW/
STB
Parameter 40 = 3.
Continuous control via three-point step controller
5 6 7 8
45
Continuous control via analogue input
5 6 7 8
65
46
66
FCU 500
47 48
67
68
90°
RBW
5AT
90°
13 14 15 16 17 1811 12
FS
COM
HI
AUTO
LO
GB
53 54 55 56 57 5849 50 51 52
R B W
M
13 14 15 16 17 1811 12
L1 N
45
65
46
66
FCU 500
47 48
67
68
5AT
COM
53 54 55 56 57 5849 50 51 52
AUTO
LO
HI
OUT
mA
+
A
D
­PLC
+ F -
90°
RBW
M
L1 N
GB-11
F
NL
I
E
Frequency converter connected to FCU..F
V1
V2
V3
LDS
HT
P
+ - + -
STW/
STB
Parameter 40 = 4. Continuous control via speed-controlled fan.
5 6 7 8
GB
45
46
65
66
FCU 500
47 48
67
68
PLC
mA
0–100%
5AT
Target = actual
M
13 14 15 16 17 1811 12
COM
53 54 55 56 57 5849 50 51 52
PDZ
FS
HI
AUTO
LO
L1
P
DI 3DI 2DI 1
FC
GB-12
F
NL
I
E

Adjustment

In certain cases, it may be necessary to change the parameters set at the factory. Using the separate software package BCSoft and a PC opto-adapter, it is possible to modify parameters on the FCU, such as the pre-purge time or the behaviour in the event of a flame failure.
The software package and the opto-adapter
are available as accessories– see page 25 (Accessories).
Changed parameters are saved on the integrated parameter chip card.
The factory settings are secured with a program-
mable password. If the password has been changed, the end cus-
tomer can look up the changed password in the plant documentation or ask the system supplier.

Commissioning

During operation, the 7-segment display shows the program status:
Device Off
––
Start-up position/standby
00
Switch-on delay/min. pause time
H0
Waiting for purge signal from furnace FCU
H1
Waiting for start enable
H2
Approaching minimum capacity
A
“No flow” state check on fan
0
Fan run-up time t
01
Approaching maximum capacity
A
Air pressure cut-out check
1
Pre-purge
P1
Approaching ignition capacity
A
Valve check Controller enable switch-on delay
H7
Waiting for burner operating signal
H8
Operation/controller enable
08
Post-purge
P9
Controlled air flow
C1
Remote control (with OCU)
U I
Data transfer (programming mode) High temperature mode
X.X.
(blinking dots) Manual mode
0.0.
GV
WARNING
Risk of explosion! Check the system for tightness before commissioning. Do not start the FCU until you are certain that the wiring is correct, the parameters have been set correctly and all input and output signals are be­ing processed perfectly by means of conducting a function check and reading the parameters on the device.
Switch on the system.
▷ The display indicates
Switch on the FCU by pressing the On/Off button.
The display indicates
If the display blinks (fault), reset the FCU by press­ing the Reset/Information button, see also page
15 (Assistance in the event of malfunction).
Apply the start-up signal to terminal1.
▷ The display indicates
are checked during the switch-on delay time/ min. pause time.
The display indicates The display indicates
out check starts.
The display indicates FCU..C1: the valve check runs in parallel to pre-
purge. If the valve check lasts longer than pre­purge, the display indicates
.
––
.
00
The safety interlocks
H0
.
. The fan starts.
01
. The air deficiency cut-
1
. Pre-purge starts.
P1
.
GB
GB-13
F
NL
I
E
The display indicates
. After pre-purge (and the
H7
end of the valve check on FCU..C1), the valves in the gas inlet section are opened.
The display indicates
. The FCU issues the
08
enable signal to the burner control units to start the burners.
High temperature operation
The FCU..H1 is fitted with an integrated temperature
module for high temperature operation. As soon as the FCU has received the signal from the connected double thermocouples that the temperature defined in parameter24 has been reached, a signal is sent to the high temperature inputs of the burner control
GB
units by the output at terminal 18. If voltage is applied to the high temperature inputs, the burner flames will no longer be monitored by the burner control units.
WARNING
Risk of explosion! High temperature operation is only permitted if the temperature in the furnace chamber is so high that the gas/air mixture is reli­ably combusted. In countries where EN746/NFPA86 is applicable, if the furnace wall temperature is greater than or equal to 750°C (1400°F), the flame may be moni­tored by a fail-safe temperature monitoring device that complies with the standard. Only if the temperature is greater than or equal to 750°C (1400°F) may voltage be applied to the high temperature inputs of the burner control units. Comply with the local safety regulations.
▷ In high temperature mode, the two dots in the
display are lit permanently.
The flame control system is placed out of op-
eration.
Once the furnace temperature falls below the value defined in parameter24, terminal18 is isolated from the voltage supply. The burner con­trol units continue operating with flame control, depending on their setting.

Manual mode

For adjustment of the furnace system or for fault-finding.
In Manual mode, the FCU operates indepen­dently of the status of the inputs for start-up signal (terminal1), controlled air flow (terminal2) and remote reset (terminal3). The function of the controller enable/emergency stop input (termi­nal46) is retained.
▷ Manual mode is terminated by switching off the
FCU or in the event of a power failure.
Parameter 67 = 0: Manual mode unlimited in time. The furnace may continue to be operated manually in the event of failure of the control system or the bus.
Parameter 67 = 1: The FCU will terminate Manual mode 5minutes after the last time the Reset/ Information button is pressed. It switches to the start-up position/standby(display
Switch on the FCU while holding the Reset/In-
formation button. Hold the Reset/Information button until the two dots in the display start to blink.
▷ If the Reset/Information button is pressed, the
current step in Manual mode is shown. After the button has been held for 1 second, the next step will be shown. The FCU now executes its program sequence until the display indicates
FCU..F with IC 0
Following controller enable (display IC20 can be opened and closed as required.
Press the Reset/Information button.
If the button continues to be held down, the actuator opens further until maximum capacity has been reached.
The display indicates
Once the button has been released, the butterfly
with blinking dots.
A.1.
valve stops in the relevant position.
Press the Reset/Information button again.
If the button continues to be held down, the actuator closes further until minimum capacity has been reached.
▷ The display indicates
with blinking dots.
A.0.
▷ A change of direction takes place each time the
button is released and pressed again. When the butterfly valve has reached its final position, the dots disappear.
FCU 500..F with IC40, FCU500..F with RBW or frequency converter
Following controller enable (status display is possible to approach binary positions between minimum and maximum capacity.
).
00
), actuator
0.8.
0.8.
08
), it
.
GB-14
F
NL
I
E

Assistance in the event of malfunction

DANGER
Electric shocks can be fatal! Before working on possible live components, ensure the unit is discon­nected from the power supply. Fault-clearance must only be undertaken by author­ized trained personnel.
▷ Faults may be cleared only using the measures
described below.
If the FCU does not respond even though all faults have been remedied: remove the unit and return it to the manufacturer for inspection.
? Faults ! Cause
Remedy
? The 7-segment display does not light up. ! Mains voltage is not applied.
Check the wiring, apply mains voltage (see type label).
2 1
? The display blinks and indicates ! Inputs 51 and 52 are activated simultaneously.
Check input 51.
Input 51 may only be activated if the valve is open.
Check input 52. ▷ Input 52 may only be activated if the valve is in
the ignition position.
21
.
2 2
? The display blinks and indicates ! Valve IC 20 has been wired incorrectly.
Check the wiring. Wire the outputs and inputs
of connection terminals 52–55 as shown in the connection diagram – see page 8 (IC 20 connected to FCU..F1).
! The unit has suffered an internal fault in the power
module.
Replace the power module.
22
.
GB
1 0
? The display blinks and indicates ! Actuation of the remote reset input is faulty. ! Too many remote resets. More than 5× resets
have been conducted within the last 15minutes, either automatically or manually.
! Consecutive fault caused by a previous fault
whose actual cause has not been remedied.
Pay attention to previous fault messages.
Remedy cause.
▷ The cause will not be remedied by performing a
reset every time a fault lock-out occurs.
Check whether remote reset complies with standards (EN746 allows resetting only under supervision) and correct if necessary.
▷ The FCU may only be reset manually under su-
pervision.
Press the Reset/Information button on the FCU.
.
10
2 0
? The display blinks and indicates ! Voltage is applied to the output at terminal 56.
Check the wiring and ensure that the voltage outputs and inputs have the same polarity and are not reversed.
! The unit has suffered an internal fault in the power
module.
Replace the power module.
.
20
2 3
? The display blinks and indicates ! The valve position is not constantly signalled
back to theFCU.
Check the wiring and ensure that the open/igni­tion position of the valve is constantly signalled back via terminal52.
23
.
2 4
? The display blinks and indicates ! Faulty activation via the bus. Requirements for
“Open” and “Close” set simultaneously.
Ensure that “Open” and “Close” are not activated simultaneously.
3 0
? The display blinks and indicates ! Abnormal data change in the parameters set for
theFCU.
Reset the parameters to their original values using the BCSoft software.
Establish the cause of the fault to avoid repeat faults.
Ensure that the cables have been installed prop­erly– see page3 (Cable selection).
24
.
30
.
GB-15
F
NL
I
E
If the measures described above do not help, remove the unit and return it to the manufacturer for inspection.
3 1
? The display blinks and indicates ! Abnormal data change in the parameters set for
theFCU.
Reset the parameters to their original values using the BCSoft software.
Establish the cause of the fault to avoid repeat faults.
GB
Ensure that the cables have been installed prop­erly– see page3 (Cable selection).
If the measures described above do not help, remove the unit and return it to the manufacturer for inspection.
31
.
3 2
? The display blinks and indicates ! Supply voltage too low.
Operate the FCU in the specified mains voltage range (mains voltage +10/-15%, 50/60Hz).
! The unit has suffered an internal fault.
Remove the unit and return it to the manufacturer for inspection.
32
.
3 8
? The display blinks and indicates ! Interruption of signal at the “Fan feedback” input
(terminal44).
Check voltage supply to terminal44.
Check the setting of parameter31.
38
.
4 0
? The display blinks and indicates ! The gas solenoid valve V1 is leaking.
Check the gas solenoid valve V1.
! The gas pressure switch DGpu/2 (DGpu¾) for
the tightness test has been set incorrectly.
Check the inlet pressure.
Set DGpu/2 (DGpu¾) to the correct inlet pressure.
Check the wiring.
! The test pressure between V1 andV2 has not
decreased.
Check the installation. ! The test period is too long.
Change parameter56 (Measurement time) using BCSoft.
If the fault cannot be remedied by doing this, remove the unit and return it to the manufacturer for inspection.
40
.
3 3
? The display blinks and indicates ! Faulty parameterization.
Check parameter settings using BCSoft.
! The unit has suffered an internal fault.
Remove the unit and return it to the manufacturer for inspection.
33
.
3 6
? The display blinks and indicates ! The unit has suffered an internal fault.
Remove the unit and return it to the manufacturer for inspection.
36
.
3 7
? The display blinks and indicates ! Faulty feedback from contactors.
Check voltage supply to terminal 68– see page 5 (Safety interlock output in the case of higher power requirement).
Check the setting of parameter73.
37
.
4 1
? The display blinks and indicates ! The gas solenoid valve V2 or V3 is leaking.
Check the gas solenoid valves V2/V3.
! The gas pressure switch DGpu/2 (DGpu¾) for
the tightness test has been set incorrectly.
Check the inlet pressure.
Set DGpu/2 (DGpu¾) to the correct inlet pressure.
Check the wiring.
! The test period is too long.
Change parameter56 (Measurement time) using BCSoft.
If the fault cannot be remedied by doing this, remove the unit and return it to the manufacturer for inspection.
4 2
? The display blinks and indicates ! Test volume V ! The gas solenoid valve V3, one of the burner-side
valves or the pipework is leaking.
Check the gas solenoid valves and pipework.
GB-16
is leaking.
p2
41
42
.
.
F
NL
I
E
! The gas pressure switch DGpu/2 (DGpu¾) has
been set incorrectly.
Check the inlet pressure.
Set DGpu/2 (DGpu¾) to the correct inlet pressure.
Check voltage supply to terminal 45 (65).
! The set test period Vp1+Vp2 is too long.
Change the test period using parameter57.
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer for inspection.
4 4
? The display blinks and indicates ! The FCU could not supply one of the test vol-
umes (Vp1 orVp2).
! The FCU could not reduce the pressure of Vp1
Faulty wiring of the activated valves.
Check valve actuation.
Faulty wiring of the pressure switches.
Check voltage supply to terminal 46 (65).
orV
.
p2
44
.
5 2
? The display blinks and indicates ! The FCU is being permanently reset.
Check voltage supply to terminal3.
Apply voltage to terminal3 only for reset, approx.
1second.
52
.
6 0
? The display blinks and indicates ! The safety temperature limiter (STL) has detected
an overtemperature condition.
Check the temperature control.
Check the wiring of terminals 5, 6, 7 and8.
! The double thermocouple is defective.
Replace the double thermocouple.
If the fault cannot be remedied by doing this,
remove the FCU and return it to the manufacturer for inspection.
60
.
GB
4 5
? The display blinks and indicates ! Faulty valve actuation. ! Reversed valve connection.
Check the wiring of the valves.
5 0
? The display blinks and indicates ! Interruption of signal at the “Enable/Emergency
stop” input (terminal46).
Check voltage supply to terminal46.
Check the setting of parameter10.
5 1
? The display blinks and indicates ! Short-circuit on one of the outputs of the safety
circuit.
Check the wiring.
Check fine-wire fuseF1 (3.15A, slow-acting,H).
The fine-wire fuse can be replaced once the
power module has been removed, see also page 21 (Replacing the fuse)
Then check the faultless processing of all input and output signals.
! The unit has suffered an internal fault in the power
module.
Replace the power module.
45
50
51
.
.
.
6 2
? The display blinks and indicates ! A cable discontinuity has been detected in the
thermocouple at terminals 5 and 6.
Check the wiring of terminals 5 and6.
Replace the double thermocouple.
If the fault cannot be remedied by doing this,
remove the FCU and return it to the manufacturer for inspection.
6 3
? The display blinks and indicates ! A cable discontinuity has been detected in the
thermocouple at terminals 7 and 8.
Check the wiring of terminals 7 and8.
Replace the double thermocouple.
If the fault cannot be remedied by doing this,
remove the FCU and return it to the manufacturer for inspection.
GB-17
62
63
.
.
F
NL
I
E
6 4
? The display blinks and indicates ! A malfunction (sensor short-circuit) has been de-
tected in the thermocouple at terminals 5 and6.
Check the wiring of terminals 5 and 6.
Replace the double thermocouple.
If the fault cannot be remedied by doing this,
remove the FCU and return it to the manufacturer for inspection.
64
.
7 0
? The display blinks and indicates ! The connected burner control units have not
signalled “Operating position reached (burner started)” within the time defined by parameter47.
Check voltage supply to “Operating signal” input (terminal4).
Check the setting of parameter47.
70
.
GB
? The display blinks and indicates ! A malfunction (sensor short-circuit) has been de-
tected in the thermocouple at terminals 7 and8.
Check the wiring of terminals 7 and 8.
Replace the double thermocouple.
If the fault cannot be remedied by doing this,
remove the FCU and return it to the manufacturer for inspection.
6 5
65
.
6 6
? The display blinks and indicates ! Limit value of the temperature difference set via
Parameter 23 between the thermocouples at terminals 5 and 6, and terminals 7 and 8 has been exceeded.
Check parameter 23 and adjust correctly.
Replace the double thermocouple.
If the fault cannot be remedied by doing this,
remove the FCU and return it to the manufacturer for inspection.
66
.
6 7
? The display blinks and indicates ! The thermocouples are being operated outside
of the allowed temperature range.
Use type K NiCr-Ni, type N NiCrSi-NiSi or typeS Pt10Rh-Pt Class 1 double thermocouples:
Thermocouple Temperature range (°C) Typ K NiCr-Ni -40 to 1000 Typ N NiCrSi-NiSi -40 to 1000 Typ S Pt10Rh-Pt 0 to 1600
67
.
7 2
? The display blinks and indicates ! The connected burner control units are not ready
for operation.
Check voltage supply to terminal67.
Check the setting of parameter72.
8 9
9 7
? The display blinks and indicates
96, 97, 98
! System fault– the FCU has performed a safety
shut-down. The cause may be a unit defect or abnormal EMC influence.
Ensure that the ignition cable has been installed properly– see page3 (Cable selection).
Ensure that the EMC regulations for the sys­tem are satisfied– particularly for systems with frequency converters – see page 3 (Cable selection).
Reset the unit.
Disconnect the protective system control from
the mains supply and then switch it on again.
Check mains voltage and frequency.
If the measures described above do not help, the
unit has probably suffered a hardware defect– remove the unit and return it to the manufacturer for inspection.
9 4 9 5 9 6
9 8 9 9
.
99
or
72
.
89, 94, 95
,
GB-18
F
NL
I
E
0
? The display blinks and indicates ! The “no flow” state check of the air pressure
switch has failed.
Check the function of the air pressure switch. Before the fan is switched on, there must be no high signal at the input for air monitoring (termi­nal47) when air monitoring is activated.
0
.
1
? The display blinks and indicates ! The operating check of the air pressure switch
has failed. The air monitor has not switched after fan start-up.
Check the air monitor wiring.
Check the air pressure switch setpoint.
Check the function of the fan.
1
.
P
? The display blinks and indicates ! The input signal (terminal48) for the air pressure
switch has dropped out during pre-purge.
Check the air supply during the purging process.
Check the electrical wiring of the air pressure
switch.
Check voltage supply to terminal48.
Check the air pressure switch setpoint.
P
.
X
? The display blinks and indicates ! The signal for monitoring the max. gas pressure
(terminal50) has dropped out at position stepX.
Check the wiring.
Check the gas pressure.
X
.
X
? The display blinks and indicates ! The signal for monitoring the min. gas pressure
(terminal49) has dropped out at position stepX.
Check the wiring.
Check the gas pressure.
X
.
A
? The display blinks and indicates ! No “Closed” signal from actuator.
Check the butterfly valve for air and the function of the limit switches in the actuator.
Check the wiring.
Check the actuator.
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer for inspection.
A
.
A
GB
1 0
? The display blinks and indicates ! The input signal for the air pressure switch has
dropped out during start-up/operation at position stepX.
! Failure of the air supply at position stepX.
Check the air supply.
Check the air pressure switch setpoint.
X
.
? The display blinks and indicates ! No “Open” signal from actuator.
Check the butterfly valve for air and the function of the limit switches in the actuator.
Check the wiring.
Check the actuator.
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer for inspection.
GB-19
A
.
F
NL
I
E
A
? The display blinks and indicates ! No “Ignition position” signal from actuator.
Check the butterfly valve for air and the function of the limit switches in the actuator.
Check the wiring.
Check the actuator.
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer for inspection.
GB
A
.
E
? The display blinks and indicates ! Internal communication with bus module has
suffered a fault.
Connected control elements must be equipped with protective circuits in accordance with the manufacturer’s instructions.
This prevents high voltage peaks which can
cause malfunctioning of the FCU.
Use suppressed electrode adapters (1 kΩ).
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer for inspection.
! The bus module is defective.
Replace the bus module.
? The display blinks and indicates ! Incorrect or defective parameter chip card (PCC).
Only the parameter chip card provided is to be used.
Replace defective parameter chip card.
E
.
.
1
? The display blinks and indicates ! No input signal for the proof of closure switch
during standby.
Check the wiring.
Mains voltage must be supplied to the FCU if the valve is closed and no voltage is to be applied if the valve is open.
Check that the proof of closure switch and valve function perfectly, replace defective valves.
1
.
8
? The display blinks and indicates ! The FCU is receiving no information as to whether
the POC switch contact is still open.
Check the wiring.
During start-up, mains voltage must be supplied
to the FCU if the valve is closed and no voltage is to be applied if the valve is open.
Check that the proof of closure switch and valve function perfectly, replace defective valves.
0
? The display blinks and indicates ! BCU waiting for connection to PLC.
Check whether the PLC is switched on.
Check the network wiring.
Check the PLC programming.
Check whether the correct device name and
IPaddress for the FCU have been entered in the PLCprogram.
1
? The display blinks and indicates ! An invalid address has been set on the bus mod-
ule.
Adapt the bus module’s address with the code switches to the address allocated in the PLCpro­gram.
Check whether the bus module’s address is in the permitted address range (001toFEF).
2
? The display blinks and indicates ! The bus module has received an incorrect con-
figuration from thePLC.
Check whether the correct GSD file was imported into the PLC.
3
? The display blinks and indicates ! The device name for the FCU is invalid in the
PLC program.
▷ Device name on delivery:
not-assigned-fcu-500-xxx
(xxx = code switch setting on the FCU).
The device name must at least consist of the
expression fcu-500-xxx.
GB-20
8
0
1
2
3
.
.
.
.
.
F
NL
I
E
Check whether the code switch setting is identi­cal to the entry(xxx) in the PLCprogram.
Delete the expression “not-assigned-” in the PLC program or replace it with an individual name part (e.g. Furnacezone1-).
4
? The display blinks and indicates ! The PLC is set to Stop.
Start the PLC.
4
.

Replacing the fuse

The device fuses F1 and F2 can be removed
for inspection.
Disconnect the system from the electrical power
supply.
Disconnect the connection terminals from the
FCU.
▷ The connection cables may remain screwed to
the connection terminals.
Disconnect the power module, see page5
(Safety interlock output in the case of higher power requirement).
4 Remove the fuse holder (with fine-wire fuse F1
orF2).
F1:T3,15A H
F2:T5A H
5 Check fine-wire fuse F1 or F2 for correct func-
tioning.
6 Replace the fine-wire fuse if defective.
When replacing the fuse, use only the approved fuse type (F1:3.15A, slow-acting, H, F2: 5A, slow-acting,H; pursuant to ICE60127-2/5).
First reconnect the power module, then recon­nect the connection terminals and restart the system/FCU, see also page13 (Commission­ing).
GB
GB-21
F
NL
I
E

Parameters and values

Scanning the parameters
Press the Reset/Information button for 2s. The
display changes to parameter10.
Release the button. The display stops at this parameter and indicates the related value.
Press the button again for 2s. The display changes to the next parameter. All parameters can be recalled one after the other in this way.
▷ If the button is pressed only briefly, the display
indicates what parameter is currently being dis­played.
The normal program status is displayed again
GB
approx. 60seconds after the last time the but­ton is pressed.
Parameter values
▷ For all FCU 500 unit variants
Pa-
Name
ram-
Values
eter
Emergency stop
0 = Off
10
1 = With safety shut-down 2 = With fault lock-out
High gas pressure protection
0 = Off
12
1 = With safety shut-down 2 = With fault lock-out
Low gas pressure protection
0 = Off
13
1 = With safety shut-down 2 = With fault lock-out
Low air pressure protection
0 = Off
15
1 = With safety shut-down 2 = With fault lock-out
Safety time during operation
19
0; 1; 2 = Time in seconds
Fan in the event of fault
0 = Off
29
1 = On
Fan run-up time tGV
30
0 – 6000 = Time in seconds
Fan ready for operation
0 = Off
31
1 = With safety shut-down 2 = With fault lock-out
Air flow monitoring during controlled air flow
0 = Off; maximum capacity
32
1 = On; maximum capacity 2 = Off; controller enable
Pre-purge time tPV
34
0 – 6000 = Time in seconds
Air flow monitoring during pre-purge
0 = Off
35
1 = With safety shut-down 2 = With fault lock-out
Post-purge time tPN
37
0 – 6000 = Time in seconds
GB-22
Pa-
Name
ram-
Values
eter
Air flow monitoring during post-purge
0 = On; maximum capacity
1 = Off; maximum capacity
38
2 = Off; ignition capacity 3 = Off; controller enable
Controller enable signal delay time tRF
44
0; 10; 20; 30 – 250 = Time in seconds
Minimum pause time tfp
62
0 – 3600 = Time in seconds
Switch-on delay time tE
63
0 – 250 = Time in seconds
Operating time in Manual mode
0 = Unlimited
67
1 = 5 minutes
Function of terminal 51
0 = Off
1 = IC 40/RBW max. capacity feedback
2 = AND with emergency stop (trm.46)
69
3 = AND with air min. (trm.47) 4 = AND with air flow monitoring (trm.48) 5 = AND with gas min. (trm.49) 6 = AND with gas max. (trm.50)
Function of terminal 65
0 = Off
1 = Reduced DG test duration
2 = AND with emergency stop (trm.46)
70
3 = AND with air min. (trm.47) 4 = AND with air flow monitoring (trm.48) 5 = AND with gas min. (trm.49) 6 = AND with gas max. (trm.50)
Function of terminal 66
0 = Off
1 = FCU as zone control unit
2 = External HT signal 3 = AND with emergency stop (trm.46)
71
4 = AND with air min. (trm.47) 5 = AND with air flow monitoring (trm.48) 6 = AND with gas min. (trm.49)
7 = AND with gas max. (trm.50) Function of terminal 67
0 = Off
1 = BCU ready; safety shut-down
2 = BCU ready; fault lock-out 3 = AND with emergency stop (trm.46)
72
4 = AND with air min. (trm.47) 5 = AND with air flow monitoring (trm.48) 6 = AND with gas min. (trm.49)
7 = AND with gas max. (trm.50) Function of terminal 68
0 = Off
1 = Contactor feedback
2 = AND with emergency stop (trm.46)
73
3 = AND with air min. (trm.47) 4 = AND with air flow monitoring (trm.48) 5 = AND with gas min. (trm.49) 6 = AND with gas max. (trm.50)
Password
77
0000 – 9999
F
NL
I
E
▷ Additional parameters for FCU..H1
Pa-
Name
ram-
Values
eter
Temperature monitoring mode
0 = Off 1 = STM function (high temperature operation)
20
2 = STL function 3 = STM and STL functions
Thermocouple
1 = Type K
22
2 = Type N 3 = Type S
Temperature difference limit value
23
10 – 100
=
Temperature in °C
STM limit value (high temperature operation)
24
650 – 1200 (temperature in °C)
STL/FSTL limit value (system protection)
25
200 – 1600 (temperature in °C)
Temperature hysteresis
26
10 – 100
=
Temperature in °C
Pre-purge in high temperature operation
0 = Off
27
1 = On
▷ Additional parameters for FCU..F1
Pa-
Name
ram-
Values
eter
Capacity control
0 = Off
40
1 = IC 20
2 = IC 40
Running time
42
0 – 250 = Time in seconds
Minimum enable time
45
0 – 250 = Time in seconds
Burner operating signal
0 = Off
46
1 = On; controller enable
Controller enable time limit
47
0 – 60
= Time in minutes
▷ Additional parameters for FCU..F2
Pa-
Name
ram-
Values
eter
Capacity control
0 = Off
40
3 = RBW 4 = Frequency converter
RBW running time selection
0 = Off; position check 1 = On; for min./max. capacity
41
2 = On; for max. capacity 3 = On; for min. capacity
RBW running time
0 – 250 = Running time in seconds, if
42
parameter41= 1, 2 or3 Minimum enable time
45
0 – 250 = Time in seconds
Burner operating signal
0 = Off
46
1 = On; controller enable
▷ Additional parameters for FCU..C1
Pa-
Name
ram-
Values
eter
Valve proving system
0 = Off 1 = Tightness test before start-up 2 = Tightness test after shut-down
51
3 = Tightness test before start-up & after
shut-down 4 = POC function Tightness control test volume
1 = Vp1 2 = Vp1; pressure reduction via V3
53
3 = Vp1 + Vp2; pressure reduction via V3 4 = Vp1 + Vp3; pressure reduction via V3 5 = Vp1 + Vp2 + Vp3; pressure reduction via V3
Pressure reduction of Vp2
0 = In standby
54
1 = Upon start-up
Relief valve V3 opening time tL3
0 – 6000
=
55
Venting time before Vp1test in seconds Measurement time Vp1
3 = Time in seconds
56
5 – 25 = (in 5 s steps) 30 – 3600 = (in 10 s steps)
Measurement time Vp1 + Vp2
3 = Time in seconds
57
5 – 25 = (in 5 s steps) 30 – 3600 = (in 10 s steps)
Valve opening time 1 tL1
59
2 – 25
=
Time for filling or pressure reduction in seconds Valve opening time 2 t
2 – 25 = Time for filling or pressure reduction in
60
L2
seconds Filling time before start-up
65
0 – 25 = Time in seconds
▷ Additional parameters for FCU with BCM500
Pa-
Name
ram-
Values
eter
Capacity control (bus)
0 = Off 1 = MIN to MAX; STBY = MIN 2 = MIN to MAX; STBY = CLOSED
75
3 = IGNITION to MAX; STBY = CLOSED 4 = MIN to MAX; STBY = MIN; quick start 5 = IGNITION to MAX; STBY = MIN; quick start
Bus communication
0 = Off
80
1 = On; with address check 2 = On; no address check
GB
GB-23
F
NL
I
E

Legend

P
ϑ
LDS
GB
PZ
PZ
PZ
PZ
P
pu/2 pu/4
3pu/4
Ready for operation
Safety interlocks (limits)
HT
High temperature operation
Safety limits during start-up
Gas valve
Air valve
Air/gas ratio control valve
Burner
Purge
Controlled air flow
Burner operating signal
FCU start-up signal
Emergency stop
Pressure switch for tightness control (TC)
Pressure switch for maximum pressure
Pressure switch for minimum pressure
Differential pressure switch
Input signal depending on param-
xx
eterxx
M
Control element with butterfly valve
Tightness control
TC
Half of the inlet pressure
A quarter of the inlet pressure
Three-quarters of the inlet pressure
Outlet pressure
p
d
GZL
Valve with proof of closure switch
Input/Output, safety circuit
24VDC input and output

Technical data

Electrical data
Mains voltage: FCU..Q: 120 V AC, -15/+10%, 50/60 Hz, ± 5%, FCU..W: 230 V AC, -15/+10%, 50/60 Hz, ± 5%. Power consumption: at 230 V AC approx. 6 W/11 VA, plus approx.
0.15W/0.4VA per ACinput, at 120 V AC approx. 3 W/5.5 VA, plus approx.
0.08W/0.2VA per ACinput. Contact rating: control outputs LDS (terminal16), purge (termi­nal17), HT (terminal18), safety interlocks (termi­nal57): max. 0.5 A, cos ϕ = 1, gas valves V1 (terminal13), V2 (terminal14), V3 (terminal15): max. 1 A, cos ϕ = 1, air valve (terminals 53, 54 and55): max. 50 mA, cos ϕ = 1.
The total current for the simultaneous activation of
outputs V1, V2, V3, HT, purge, LDS, safety inter­locks and air valve must not exceed 2.5A. 24 V DC signal for fault/operation: max. 0.1 A, fan: max. 3A (start-up current: 6A<1s). Number of operating cycles: FCU: 24 V DC signal for fault/operation: max. 10,000,000, On/Off button, Reset/Information button:
1000,
power module: control outputs LDS (terminal16), purge (terminal17), HT (terminal18), safety interlocks (terminal57), gas valves V1 (terminal 13), V2 (terminal14), V3 (terminal15), air valve (terminals 53, 54 and55), fan (terminal 58): max. 250,000. Input voltage of signal inputs:
Rated value 120 V AC 230 V AC Signal “1” 80 – 132 V 160 – 253 V Signal “0” 0 – 20 V 0 – 40 V
Inherent current:
Signal “1” typ. < 2 mA
Rated value 24 V DC Signal “1” 24 V, ± 10% Signal “0” < 1 V
Inherent current:
Signal “1” typ. 5 mA
Fuses, replaceable, F1: T 3.15A H, F2: T 5A H, pursuant to IEC 60127-2/5.
Mechanical data
Weight: 0.7 kg. Dimensions (W × H × D): 102 × 115 × 112 mm.
GB-24
F
NL
I
E
Connections: Screw terminals: nominal cross-section 2.5mm², wire cross-section (rigid) min. 0.2mm², wire cross-section (rigid) max. 2.5mm², wire cross-section AWG/kcmil min.24, wire cross-section AWG/kcmil max.12, 12 A. Spring force terminals: nominal cross-section 2 x 1.5mm², wire cross-section min. 0.2mm², wire cross-section AWG min.24, wire cross-section AWG max.16, wire cross-section max. 1.5mm², rated current 10 A (8A UL), to be observed in case of daisy chain.
Environment
Ambient temperature:
-20 to +60°C (-4 to +140°F), no condensation permitted. Storage temperature: -20 to +60°C (-4 to +140°F). Enclosure: IP 20 pursuant to IEC 529. Installation location: min. IP 54 (for installation in a control cabinet).

Designed lifetime

This information on the designed lifetime is based on
using the product in accordance with these operating instructions. Once the designed lifetime has been reached, safety-relevant products must be replaced. Designed lifetime (based on date of manufacture):
10 years. You can find further explanations in the applicable
rules and regulations and on the afecor website (www.afecor.org).
This procedure applies to heating systems. For
thermoprocessing equipment, observe local regu­lations.

Accessories

BCSoft
The current software can be downloaded from our
Internet site at http://www.docuthek.com. To do so, you need to register in the DOCUTHEK.
Opto-adapter PCO 00
Including BCSoft CD-ROM, Order No.: 74960625.
Bluetooth adapter PCO 00
Including BCSoft CD-ROM, Order No.: 74960617.
Stickers for labelling
FCU 500 Zone 2
For printing with laser printers, plotters or engraving machines, 27 × 18mm or 28 × 17.5mm. Colour: silver.
Connection plug set
For wiring the FCU.
GB

Logistics

Transport
Protect the unit from external forces (blows, shocks, vibration). On receipt of the product, check that the delivery is complete, see page2 (Part designa­tions). Report any transport damage immediately.
Storage
Store the product in a dry and clean place. Storage temperature: see page24 (Technical data). Storage time: 6months in the original packaging before using for the first time. If stored for longer than this, the overall service life will be reduced by the corresponding amount of extra storage time.
Packaging
The packaging material is to be disposed of in ac-
cordance with local regulations.
Disposal
Components are to be disposed of separately in accordance with local regulations.
74923998 74924000
Plug-in, with screw terminal, Order No.: 74923998. Plug-in, with spring force terminal, 2connection options per terminal, Order No.: 74924000.
GB-25
F
NL
I
E
Certification
Declaration of conformity
We, the manufacturer, hereby declare that the product FCU500 complies with the essential requirements of the following Directives and Standards:
Directives: – 2006/95/EC – 2004/108/EC
Standards: – EN 298
GB
– EN 1643 – EN 14597 – EN 60584 – EN 60730 – EN 61508, Parts 1 – 7 for Safety Integrity Level
SIL3
The production is subject to a Quality System pursu-
ant to DIN EN ISO 9001.
Elster GmbH
Scan of the Declaration of conformity (D,GB)– see
www.docuthek.com
Eurasian Customs Union
The products FCU 500 meet the technical specifica-
tions of the Eurasian Customs Union (the Russian Federation, Belarus, Kazakhstan).

Contact

Contact
If you have any technical questions, please contact your local branch office/agent. The addresses are available on the Internet or from ElsterGmbH.
We reserve the right to make technical modifications
Elster GmbH Postfach 28 09, D-49018 Osnabrück Strotheweg 1, D-49504 Lotte (Büren)
T +49 541 1214-0
F +49 541 1214-370
in the interests of progress. info@kromschroeder.com, www.kromschroeder.com
GB-26
Loading...