Operating instructions

Pressure switches for air DL..A, DL..K

© 2016 Elster GmbH · Edition 07.16
Cert. version 03.94
Translation from the German

Contents

Contents

Pressure switches for air DL..A, DL..K......
Contents ..............................
Safety.................................
Checking the usage .....................
Type code .............................2
Part designations ........................ 2
Type label.............................. 2
Installation ............................
Positive pressure measurement .............3
Negative pressure measurement . . . . . . . . . . . . 4
Differential pressure measurement ...........4
Wiring ................................4
Adjustment ............................5
Function check.........................5
Accessories ...........................5
Z-angle bracket .........................5
U-angle bracket .........................6
Standard coupler plug ....................6
Motor flange adapter . . . . . . . . . . . . . . . . . . . . . 6
Tube set ...............................6
Pilot lamp set, red or blue .................6
LED set, red/green....................... 7
External adjustment ......................7
Technical data .........................7
Designed lifetime ........................ 7
Logistics ..............................8
Certification ...........................8
Declaration of conformity ..................8
Contact ...............................8

Safety

Safety

Please read and keep in a safe place
Explanation of symbols
,  ,  , 3 ... = Action
= Instruction
Liability
We will not be held liable for damage resulting from non-observance of the instructions and non-com­pliant use.
Safety instructions
Information that is relevant for safety is indicated in the instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified gas technicians. Electrical interventions may only be carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM spare parts.
Changes to edition 0.6
The following chapters have been changed: – Accessories
GB
GB-1
F
NL
I
E

Checking the usage

DL ,5 – 3A, DL 3K, DL 5 – 50A, DL 5 – 50K
For monitoring positive, negative or differential air or flue gas pressures.
This function is only guaranteed when used within
the specified limits– see page7 (Technical data). Any other use is considered as non-compliant.

Type code

Code Description
DL Pressure switch for air ,5 – 50 Max. setting in mbar K A
GB
T T-product
-3
-4
-5
-6
-9 K T T N A External adjustment W Z-angle bracket

Part designations

Upper housing section with cover
Lower housing section 3 Hand wheel 4 M16 cable gland

Type label

With tube connection and hand wheel
Additionally with Rp¼connection
(optional: Rp
Electrical connection
via screw terminals
via screw terminals, IP 65
4-pin plug, without socket
4-pin plug, with socket
4-pin plug, with socket, IP 65
Red/green pilot LED for 24 V DC/AC
Blue pilot lamp for 230 V AC
Red/green pilot LED for 230 V AC
Blue pilot lamp for 120 V AC
22
3
4
1
D-49018 Osnabrück, Germany
DL
CE – 0085AP0466
2
3
1

Installation

CAUTION
Please observe the following to ensure that the DL
is not damaged during installation and operation: – Use approved sealing material only. – Note the max. medium and ambient tempera-
tures, see page7 (Technical data).
– Condensation must not be allowed to get into
the housing (if possible, install pipework with an ascending gradient). Otherwise, there is a risk of icing of condensation at subzero temperatures,
1
/8)
the switching point shifting or corrosion in the device which can lead to malfunctions.
– Protect the connections against dirt or moisture
in the medium to be measured or the surround­ing air. If necessary, install a filter.
– In case of highly fluctuating pressures, install a
damping nozzle/restrictor orifice.
– When installing outdoors, place the DL in a
roofed area and protect from direct sunlight (even IP65 version). To avoid condensation, the cover with pressure equalization element can be used on some types.
– In the case of an uneven mounting surface, se-
cure the pressure switch to the mounting plate or air duct with only two screws on the same side in order to avoid subjecting the pressure switch to mechanical stress.
– When using silicone tubes, only use silicone
tubes which have been sufficiently cured. Va­pours containing silicone can adversely affect the functioning of electrical contacts.
– In the case of high humidity or aggressive gas
components, we recommend using a pressure switch with gold contact due to its higher resist­ance to corrosion. Closed-circuit current moni­toring is recommended under difficult operating conditions.
The DL must not be in contact with masonry.
Minimum clearance 20mm.
Ensure that there is sufficient installation space. Ensure unobstructed view of the hand wheel.
Installation in the vertical or horizontal position, or upside down, preferably with vertical diaphragm. If installed in a vertical position, the switching pointpS will correspond to the scale valueSK.
Max. inlet pressure = withstand pressure, mains volt­age, ambient temperature, enclosure: see type label.
GB-2
F
NL
I
E
50 (1.97")
30 (1.18")
20
(0.79")
25 (0.98")
45 (1.77")
16
39 (1.53")
5,2
(0.2")
11,3 (0.44")
7 (0.27")
7,5 (0.3")
10
(0.4")
40 (1.6")
59 (2.3")
ø 5,5 (0.22") ø 6 (0.22")
ø 4,2 (0.17")
10 (0.39")
1 (0.04")
1 = Rp 1/4 (+),
2 = ø 4,75 x 1 mm (+) 3 = ø 4,75 x 1 mm (-)
(4 = Rp
1
/8 (-),
1
/8" NPT (-))
1
(4)
2
3
(1/4" NPT (+))
1 = Rp 1/4 (+),
2 = ø 4,75 x 1 mm (+) 3 = ø 4,75 x 1 mm (-)
(4 = Rp
1
/8 (-),
1
/8" NPT (-))
1 = Rp
1
/4 (+),
2 = ø 4,75 x 1 mm (+) 3 = ø 4,75 x 1 mm (-)
(4 = Rp
1
/8 (-),
1
/8" NPT (-))
1
(4)
2
3
1
Test
2
3(4)
(1/4" NPT (+))
(
1
/4" NPT (+))
1 = Rp 1/4 (+),
2 = ø 4,75 x 1 mm (+) 3 = ø 4,75 x 1 mm (-)
(4 = Rp
1
/8 (-),
1
/8" NPT (-))
1 = Rp
1
/4 (+),
2 = ø 4,75 x 1 mm (+) 3 = ø 4,75 x 1 mm (-)
(4 = Rp
1
/8 (-),
1
/8" NPT (-))
2 = ø 4,75 x 1 mm (+) 3 = ø 4,75 x 1 mm (-)
1
(4)
2
3
1
2
3
Test
2
3(4)
(1/4" NPT (+))
(
1
/4" NPT (+))
If installed in another position, the switching pointpS will change and no longer correspond to the set scale valueSK. Switching pointpS must be checked.
SK + 0.18 mbar
[+ 0.071 "WC]
SK - 0.18 mbar
[- 0.071 "WC]
DL 1,5A
DL 3K, DL 3A DL 5 – 150A, DL 5 – 150K
▷ Installation using self-tapping screws for 1mm-
thick sheets:
DL..A, DL 3K: Ø 3.5 x 8 mm or Ø 4 x 8 mm.
DL 5 – 150K: Ø3.5 x 16 mm.
Fit the DL.
DL 1,5A DL 3A DL 3K
e.g. SK = -0.5:
ps = -0.5 + 0.18
ps = -0.32 mbar
49,5 (1.9")
44,5 (1.7")
DL..A: Rp ¼ (DL..AT: ¼" NPT)
ø 6,1 (ø 0.24")
Connect the pressure line.
DL..A: upon delivery, port 2 is closed off by a rubber cap.
DL ,5A, DL 3A
1 = Rp 1/4 (+),
2
3
1
(4)
(1/4" NPT (+)) 2 = ø 4,75 x 1 mm (+) 3 = ø 4,75 x 1 mm (-)
1
(4 = Rp
/8 (-),
1
/8" NPT (-))
Positive pressure: port 1 or 2 Negative pressure: port 3 Special version DL 3A – 3Z: port 4
DL 5 – 50A
Test
2
1
3(4)
1
/4 (+),
1 = Rp
1
/4" NPT (+))
( 2 = ø 4,75 x 1 mm (+) 3 = ø 4,75 x 1 mm (-)
1
(4 = Rp
/8 (-),
1
/8" NPT (-))
Positive pressure: port 1 or 2
Negative pressure: port 3; after unscrewing port3 also port4
DL 3K
GB
3,5 (0.14")
DL 5–150A
2,7 (0.11")
3,5 (0.14")
DL 5–150K
64 (2.5")
49,5 (1.9")
54,5 (2.1")
2,7 (0.11")
DL..A: Rp ¼ (DL..AT: ¼" NPT)
44,5 (1.7")
2,7 (0.11")
45 (1.8")
2 = ø 4,75 x 1 mm (+)
Positive pressure: port 2 Negative pressure: port 3
DL 5 – 50K
Positive pressure: port 2
2
2
(5)
3 = ø 4,75 x 1 mm (-)
3
2 = ø 4,75 x 1 mm (+)
3
3 = ø 4,75 x 1 mm (-)
(5 = ø 4,75 x 1 mm (+))
Negative pressure: port 3 Optional test point for positive pressure: port5

Positive pressure measurement

1 or 2 = positive pressure port(+). If port2 is used, close off port1.
3 or 4 = remains open to ventilate the upper
diaphragm chamber.
GB-3
F
NL
I
E

Negative pressure measurement

3 or 4 = negative pressure port(-).
1 or 2 = remains open to ventilate the upper
diaphragm chamber.

Differential pressure measurement

Disconnect the system from the electrical power
supply.
3 42
6 75
GB
▷ 1 or 2 = port for the higher positive pressure or
lower negative pressure(+).
▷ 3 or 4 = port for the lower positive pressure or
higher negative pressure(-).
3 Seal the ports that are not in use.

Wiring

If the DL..G (DL..TG) has switched a voltage
>24V (>30V) and a current >0.1A at cosφ=1
or >0.05A at cosφ=0.6 once, the gold plating on the contacts will have been burnt through. It can then only be operated at this power rating or higher power rating.
CAUTION
To ensure that the DL is not damaged during opera-
tion, note the switching capacity, see page7 (Technical data).
▷ In the case of low switching capacities, such as
24V, 8mA, for example, we recommend using an RCmodule (22 Ω, 1μF) in air containing silicone or oil.
C = 1 µF R = 22 Ω
NO
NC
2
1
COM 3
M16 x 1,5:
ø 4–10 mm
Contacts 3 and close when subject to increas­ing pressure. Contacts and 3 close when sub­ject to falling pressure. With the NO contact, the NC contact is omitted.
NO
L1
3
COM
2
NC
1
NO
1
2
NC
DL ,5A
The connection depends on the positive or nega-
tive adjusting range.
-
0
,
5
-
0
r
,
a
2
b
5
m
5
,
1
0
,
0
5
,
0
-
DL 1,5A
Negative adjusting range 0 to -0.5 mbar: con-
0
,
2
5
0
,
5
5
,
1
1
m
b
a
r
5
=
2
,
1
0
1
0
P
a
0
,
1
5
7
,
0
tacts 3 and 1 close when subject to increasing negative pressure. Contacts 2 and 3 close when subject to falling negative pressure.
NO
NC
2
1
µ
COM
3
3
COM
GB-4
F
NL
I
E

Adjustment

NO
2
NC
1
COM
3
COM
3
NC
1
NO
2
The switching point is adjustable via hand wheel.
Disconnect the system from the electrical power
supply.
Detach the housing cover, see page7 (Tech-
nical data).
3 Connect an ohmmeter.
NO
1
2
NC
3
COM
NO
COM
2
NC
3
1
4 Set the switching point using the hand wheel. 5 Connect a pressure gauge.
0
Deviation from the switching point during testing pursuant to EN1854:
Air pressure switches:
DL 5 – 150A, DL 5 – 150K DL 1,5A
DL 3A, DL 3K
If the DL does not trip at the desired switch-
Deviation
± 15%
± 15% or ± 6 Pa ± 15% or ± 6 Pa
ing point, correct the adjusting range using the hand wheel. Relieve the pressure and repeat the process.

Function check

We recommend a function check once a year. Press the test key during operation– the pres-
sure switch switches.
GB
1 cm = 1 mbar
TEST
+
6 Apply pressure. In doing so, monitor the switch-
ing point on the ohmmeter and the pressure gauge.
▷ Max. inlet pressure = withstand pressure
Max.
inlet
pressure
mbar
Switching
differential**
mbar
Type
Adjusting
range*
mbar
min. max. min. max.
DL 1,5A -0.5 1.5 50 0.1 0.16
▷ In case of differential pressure, press both keys
simultaneously.
TEST
TEST
+
DL 3A, ..3K 0.2 3 50 0.1 0.16 DL 3AT, ..3KT 0.3 3 150 0.1 0.16 DL 5A, ..5K 0.4 6 300 0.2 0.3 DL 5AT, ..5KT 0.5 5 300 0.2 0.3 DL 10A, ..10K,
..10AT, ..10KT
1 10 300 0.25 0.4
DL 30A, ..30K 2.5 30 300 0.35 0.9 DL 50A, ..50K,
..50AT, ..50KT
DL 150A,
..150K
Type
2.5 50 300 0.8 1.5
30 150 300 3 5
Adjusting
range*
"WC
min. max. min. max.
Max.
inlet
pressure
"WC
Switching
differential**
"WC
DL 3AT, ..3KT 0.12 1.2 58.5 0.04 0.06 DL 5AT, ..5KT 0.2 2 117 0.08 0.12 DL 10AT,
..10KT
DL 50AT,
..50KT
* Adjusting tolerance ±15% of the scale value, but
min. ±4Pa
0.4 4 117 0.1 0.16
1 20 117 0.3 0.6

Accessories

Z-angle bracket

DL 5 – 150K: Order No.: 74916158 DL 3 – 150A, DL 3K: Order No.: 74913661
7,5 (0.3")
1 (0.04") 10 (0.39")
40 (1.6")
59 (2.3")
ø 4,2 (0.17") ø 5,5 (0.22") ø 6 (0.22")
7 (0.27")
11,3 (0.44")
** Mean switching differential at min. and max. setting
GB-5
F
NL
I
E

U-angle bracket

47,5 (1.87"
DL 1,5 – 150A, DL 3 – 150K: Order No.: 74916185

Tube set

To be used with air only.
75 (2.95")
20
(0.79")
GB
50 (1.97")
30 (1.18")
(0.79")
45 (1.77")
25 (0.98")
6 (0.24")
24 (0.94")
43
-0,3
64 (2.52")

Standard coupler plug

M4 x 12
20
16
(0.63")
(1.69")
)
40 (1.57")
M4 x 10
5,2
(0.2")
+0,1
(0.17")
4,20
10
(0.4")
39 (1.53")
Order No.: 74912952
Order No.: 74919272

Pilot lamp set, red or blue

DL..T, DL..N
Pilot lamp, red:
110/120 V AC, I = 1.2 mA, Order No.: 74920430;
220/250 V AC, I = 0.6 mA, Order No.: 74920429. Pilot lamp, blue:
110/120 V AC, I = 1.2 mA, Order No.: 74916121;
220/250 V AC, I = 0.6 mA, Order No.: 74916122.
2 31
4
N
3
COM
NO
L1
2
NC
1
NO
2
NC
NO
1
3
COM
N
Order No.: 74916159
Motor flange adapter
Set including retaining screws
DL..A, DL 3 – 5K: Order No.: 74916157, DL 5 – 150K: Order No.: 74916156.
GB-6
NO
NC
L1
3
COM
2
1
NC
N
NO
1
2
NC
3
COM
N
F
NL
I
E

LED set, red/green

DL..K2, DL..T2
24 V DC, I = 16 mA; 24 V AC, I = 8 mA, Order No.: 74921089; 230 V AC, I = 0.6 mA, Order No.: 74923275.
2 31
4
NO
2
+
3 COM
1 NC
1
2
NC
NO
3
COM
N

External adjustment

In order to set the switching pressure from the out­side, the cover for external adjustment (6mm Allen key) for DL..A, DL5 – 150K can be retrofitted.
Order No.: 74916155
2 31

Technical data

Gas type: air or flue gas, no flammable gases, no aggressive gases. Max. inlet pressure = withstand pressure: see type label or page 5 (Adjustment). Micro switch to EN 61058-1. Switching capacity: DL..: 24 V (min. 0.05 A) to 250 V AC (max. 5 A, at cos φ 0.6 = 1 A), max. 6 A, temporarily (<1 s) 20A. DL..G: 5 V (min. 0.01 A) to 250 V AC (max. 5 A, at cos φ 0.6 = 1 A), 5 V (min. 0.01 A) to 48 V DC (max.1A), DL..T: 30 – 240 V AC, 50/60 Hz, 5 A resistive or
0.5 A inductive (cos φ= 0.6), DL..TG: < 30 V AC/DC,
0.1 A resistive or
0.05 A inductive (cos φ= 0.6). Contact gap < 3 mm (μ). Safety class II to VDE 0106-1. Max. medium and ambient temperatures: DL: -20 to +80°C (-4 to +176°F), DL..T: -40 to +60°C (-40 to +140°F). Long-term use in the upper ambient temperature range accelerates the ageing of the elastomer ma­terials and reduces the service life (please contact manufacturer). Storage temperature:
-20 to +40°C (-4 to +104°F). Diaphragm pressure switch, NBR, silicone-free. Housing: glass fibre reinforced PBT plastic with low gas release. Enclosure to IEC 60529: IP54, IP65. Line entrance: M16 x 1.5 (1/2" NPT conduit), clamping range: diameters of 4 to 10mm.
Type of connection: screw terminals.
Weight: DL..A: 190g (6.7oz), DL..K: 220 g (7.8oz).
GB

Designed lifetime

This information on the designed lifetime is based on
using the product in accordance with these operating instructions. Once the designed lifetime has been reached, safety-relevant products must be replaced. Designed lifetime (based on date of manufacture) in accordance with EN13611, EN1854 for pressure switches: 10 years.
You can find further explanations in the applicable
rules and regulations and on the afecor website (www.afecor.org).
This procedure applies to heating systems. For
thermoprocessing equipment, observe local regu­lations.
GB-7
F
NL
I
E

Logistics

Transport
Protect the unit from external forces (blows, shocks, vibration). On receipt of the product, check that the delivery is complete, see page2 (Part designa­tions). Report any transport damage immediately.
Storage
Store the product in a dry and clean place. Storage temperature: see page7 (Technical data). Storage time: 6months before using for the first time. If stored for longer than this, the overall service life will be reduced by the corresponding amount of extra storage time.
GB
Packaging
The packaging material is to be disposed of in ac-
cordance with local regulations.
Disposal
Components are to be disposed of separately in accordance with local regulations.
Certification

Declaration of conformity

We, the manufacturer, hereby declare that the prod­uct DL, marked with product ID No. CE-0085AP0466, complies with the requirements of the listed Directives.
Directives: – 2009/142/EC – 2006/95/EC
The relevant product corresponds to the type tested
by the notified body 0085.
The production is subject to the surveillance proce-
dure pursuant to Directive 2009/142/EC AnnexII
paragraph3 and pursuant to DIN EN ISO 9001:2008.
Elster GmbH
FM approval
Factory Mutual Research Class: 3510 Flow and pressure safety switches. Designed for applications pursuant to NFPA 85 and NFPA 86.
UL approval
UL 353 Limit control
AGA approval
Australian Gas Association, Approval No.: 5484
AGA
Eurasian Customs Union
The product DL meets the technical specifications
of the Eurasian Customs Union.
RoHS compliant
Scan of the Declaration of conformity (D, GB) – see
www.docuthek.com

Contact

Contact

Elster GmbH
If you have any technical questions, please contact
your local branch office/agent. The addresses are
available on the Internet or from ElsterGmbH.
We reserve the right to make technical modifications
Elster GmbH
Elster GmbH
Postfach 28 09, D-49018 Osnabrück
Postfach 28 09, D-49018 Osnabrück
Postfach 28 09, D-49018 Osnabrück
Strotheweg 1, D-49504 Lotte (Büren)
Strotheweg 1, D-49504 Lotte (Büren)
Strotheweg 1, D-49504 Lotte (Büren)
T +49 541 1214-0
T +49 541 1214-0
T +49 541 1214-0
F +49 541 1214-370
F +49 541 1214-370
F +49 541 1214-370
in the interests of progress. info@kromschroeder.com, www.kromschroeder.com
GB-8
Loading...