Please read through these instructions
carefully before installing or operating. Following the
installation, pass the instructions on to the operator. This unit must be installed and commissioned
in accordance with the regulations and standards
in force. These instructions can also be found at
www.docuthek.com.
Explanation of symbols
• , , , 3 ... = Action
▷ = Instruction
Liability
We will not be held liable for damage resulting from
non-observance of the instructions and non-compliant use.
Safety instructions
Information that is relevant for safety is indicated in
the instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified
gas technicians. Electrical interventions may only be
carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM
spare parts.
Changes to edition 0.6
The following chapters have been changed:
– Accessories
GB
GB-1
F
NL
I
E
Checking the usage
DL ,5 – 3A, DL 3K, DL 5 – 50A, DL 5 – 50K
For monitoring positive, negative or differential air or
flue gas pressures.
This function is only guaranteed when used within
the specified limits– see page7 (Technical data).
Any other use is considered as non-compliant.
Type code
CodeDescription
DLPressure switch for air
,5 – 50Max. setting in mbar
K
A
GB
TT-product
-3
-4
-5
-6
-9
K
T
T
N
AExternal adjustment
WZ-angle bracket
Please observe the following to ensure that the DL
is not damaged during installation and operation:
– Use approved sealing material only.
– Note the max. medium and ambient tempera-
tures, see page7 (Technical data).
– Condensation must not be allowed to get into
the housing (if possible, install pipework with an
ascending gradient). Otherwise, there is a risk of
icing of condensation at subzero temperatures,
1
/8)
the switching point shifting or corrosion in the
device which can lead to malfunctions.
– Protect the connections against dirt or moisture
in the medium to be measured or the surrounding air. If necessary, install a filter.
– In case of highly fluctuating pressures, install a
damping nozzle/restrictor orifice.
– When installing outdoors, place the DL in a
roofed area and protect from direct sunlight
(even IP65 version). To avoid condensation,
the cover with pressure equalization element
can be used on some types.
– In the case of an uneven mounting surface, se-
cure the pressure switch to the mounting plate
or air duct with only two screws on the same
side in order to avoid subjecting the pressure
switch to mechanical stress.
– When using silicone tubes, only use silicone
tubes which have been sufficiently cured. Vapours containing silicone can adversely affect
the functioning of electrical contacts.
– In the case of high humidity or aggressive gas
components, we recommend using a pressure
switch with gold contact due to its higher resistance to corrosion. Closed-circuit current monitoring is recommended under difficult operating
conditions.
▷
The DL must not be in contact with masonry.
Minimum clearance 20mm.
▷ Ensure that there is sufficient installation space.▷ Ensure unobstructed view of the hand wheel.▷
Installation in the vertical or horizontal position, or
upside down, preferably with vertical diaphragm.
If installed in a vertical position, the switching
pointpS will correspond to the scale valueSK.
Max. inlet pressure = withstand pressure, mains voltage, ambient temperature, enclosure: see type label.
GB-2
F
NL
I
E
▷
50 (1.97")
30 (1.18")
20
(0.79")
25 (0.98")
45 (1.77")
16
39 (1.53")
5,2
(0.2")
11,3 (0.44")
7 (0.27")
7,5 (0.3")
10
(0.4")
40 (1.6")
59 (2.3")
ø 5,5 (0.22")ø 6 (0.22")
ø 4,2 (0.17")
10 (0.39")
1 (0.04")
1 = Rp 1/4 (+),
2 = ø 4,75 x 1 mm (+)3 = ø 4,75 x 1 mm (-)
(4 = Rp
1
/8 (-),
1
/8" NPT (-))
1
(4)
2
3
(1/4" NPT (+))
1 = Rp 1/4 (+),
2 = ø 4,75 x 1 mm (+)3 = ø 4,75 x 1 mm (-)
(4 = Rp
1
/8 (-),
1
/8" NPT (-))
1 = Rp
1
/4 (+),
2 = ø 4,75 x 1 mm (+)3 = ø 4,75 x 1 mm (-)
(4 = Rp
1
/8 (-),
1
/8" NPT (-))
1
(4)
2
3
1
Test
2
3(4)
(1/4" NPT (+))
(
1
/4" NPT (+))
1 = Rp 1/4 (+),
2 = ø 4,75 x 1 mm (+)3 = ø 4,75 x 1 mm (-)
(4 = Rp
1
/8 (-),
1
/8" NPT (-))
1 = Rp
1
/4 (+),
2 = ø 4,75 x 1 mm (+)3 = ø 4,75 x 1 mm (-)
(4 = Rp
1
/8 (-),
1
/8" NPT (-))
2 = ø 4,75 x 1 mm (+)3 = ø 4,75 x 1 mm (-)
1
(4)
2
3
1
2
3
Test
2
3(4)
(1/4" NPT (+))
(
1
/4" NPT (+))
If installed in another position, the switching
pointpS will change and no longer correspond
to the set scale valueSK. Switching pointpS
must be checked.
SK + 0.18 mbar
[+ 0.071 "WC]
SK - 0.18 mbar
[- 0.071 "WC]
DL 1,5A
DL 3K,
DL 3A
DL 5 – 150A,
DL 5 – 150K
▷ Installation using self-tapping screws for 1mm-
thick sheets:
DL..A, DL 3K: Ø 3.5 x 8 mm or Ø 4 x 8 mm.
DL 5 – 150K: Ø3.5 x 16 mm.
Fit the DL.
DL 1,5A
DL 3A
DL 3K
e.g. SK = -0.5:
ps = -0.5 + 0.18
ps = -0.32 mbar
49,5 (1.9")
44,5 (1.7")
DL..A: Rp ¼
(DL..AT: ¼" NPT)
ø 6,1 (ø 0.24")
Connect the pressure line.
▷
DL..A: upon delivery, port 2 is closed off by a
rubber cap.
DL ,5A, DL 3A
1 = Rp 1/4 (+),
2
3
1
(4)
(1/4" NPT (+))
2 = ø 4,75 x 1 mm (+)
3 = ø 4,75 x 1 mm (-)
1
(4 = Rp
/8 (-),
1
/8" NPT (-))
▷ Positive pressure: port 1 or 2▷ Negative pressure: port 3▷ Special version DL 3A – 3Z: port 4
DL 5 – 50A
Test
2
1
3(4)
1
/4 (+),
1 = Rp
1
/4" NPT (+))
(
2 = ø 4,75 x 1 mm (+)
3 = ø 4,75 x 1 mm (-)
1
(4 = Rp
/8 (-),
1
/8" NPT (-))
▷ Positive pressure: port 1 or 2▷
Negative pressure: port 3; after unscrewing
port3 also port4
DL 3K
GB
3,5
(0.14")
DL 5–150A
2,7
(0.11")
3,5
(0.14")
DL 5–150K
64 (2.5")
49,5 (1.9")
54,5 (2.1")
2,7
(0.11")
DL..A: Rp ¼
(DL..AT: ¼" NPT)
44,5 (1.7")
2,7
(0.11")
45 (1.8")
2 = ø 4,75 x 1 mm (+)
▷ Positive pressure: port 2▷ Negative pressure: port 3
DL 5 – 50K
▷ Positive pressure: port 2
2
2
(5)
3 = ø 4,75 x 1 mm (-)
3
2 = ø 4,75 x 1 mm (+)
3
3 = ø 4,75 x 1 mm (-)
(5 = ø 4,75 x 1 mm (+))
▷ Negative pressure: port 3▷ Optional test point for positive pressure: port5
Positive pressure measurement
▷ 1 or 2 = positive pressure port(+).▷ If port2 is used, close off port1.
3 or 4 = remains open to ventilate the upper
▷
diaphragm chamber.
GB-3
F
NL
I
E
Negative pressure measurement
▷ 3 or 4 = negative pressure port(-).▷
1 or 2 = remains open to ventilate the upper
diaphragm chamber.
Differential pressure measurement
Disconnect the system from the electrical power
supply.
342
675
GB
▷ 1 or 2 = port for the higher positive pressure or
lower negative pressure(+).
▷ 3 or 4 = port for the lower positive pressure or
higher negative pressure(-).
3 Seal the ports that are not in use.
Wiring
▷
If the DL..G (DL..TG) has switched a voltage
>24V (>30V) and a current >0.1A at cosφ=1
or >0.05A at cosφ=0.6 once, the gold plating
on the contacts will have been burnt through. It
can then only be operated at this power rating
or higher power rating.
CAUTION
To ensure that the DL is not damaged during opera-
tion, note the switching capacity, see page7
(Technical data).
▷ In the case of low switching capacities, such as
24V, 8mA, for example, we recommend using
an RCmodule (22 Ω, 1μF) in air containing
silicone or oil.
C = 1 µFR = 22 Ω
NO
NC
2
1
COM
3
M16 x 1,5:
ø 4–10 mm
▷
Contacts 3 and close when subject to increasing pressure. Contacts and 3 close when subject to falling pressure. With the NO contact, the
NC contact is omitted.
NO
L1
3
COM
2
NC
1
NO
1
2
NC
DL ,5A
▷
The connection depends on the positive or nega-
tive adjusting range.
-
0
,
5
-
0
r
,
a
2
b
5
m
5
,
1
0
–
,
0
5
,
0
-
DL 1,5A
▷
Negative adjusting range 0 to -0.5 mbar: con-
0
,
2
5
0
,
5
5
,
1
1
m
b
a
r
5
=
2
,
1
0
1
0
P
a
0
,
1
5
7
,
0
tacts 3 and 1 close when subject to increasing
negative pressure. Contacts 2 and 3 close when
subject to falling negative pressure.
NO
NC
2
1
µ
COM
3
3
COM
GB-4
F
NL
I
E
Adjustment
NO
2
NC
1
COM
3
COM
3
NC
1
NO
2
▷
The switching point is adjustable via hand wheel.
Disconnect the system from the electrical power
supply.
Detach the housing cover, see page7 (Tech-
nical data).
3 Connect an ohmmeter.
NO
1
2
NC
3
COM
NO
COM
2
NC
3
1
4 Set the switching point using the hand wheel.
5 Connect a pressure gauge.
0
▷
Deviation from the switching point during testing
pursuant to EN1854:
Air pressure switches:
DL 5 – 150A,
DL 5 – 150K
DL 1,5A
DL 3A, DL 3K
▷
If the DL does not trip at the desired switch-
Deviation
± 15%
± 15% or ± 6 Pa
± 15% or ± 6 Pa
ing point, correct the adjusting range using the
hand wheel. Relieve the pressure and repeat
the process.
Function check
▷ We recommend a function check once a year.▷ Press the test key during operation– the pres-
sure switch switches.
GB
1 cm = 1 mbar
TEST
+
6 Apply pressure. In doing so, monitor the switch-
ing point on the ohmmeter and the pressure
gauge.
▷ Max. inlet pressure = withstand pressure
Max.
inlet
pressure
mbar
Switching
differential**
mbar
Type
Adjusting
range*
mbar
min. max.min. max.
DL 1,5A-0.51.5500.1 0.16
▷ In case of differential pressure, press both keys
* Adjusting tolerance ±15% of the scale value, but
min. ±4Pa
0.441170.1 0.16
1201170.30.6
Accessories
Z-angle bracket
DL 5 – 150K: Order No.: 74916158
DL 3 – 150A, DL 3K: Order No.: 74913661
7,5 (0.3")
1 (0.04")
10 (0.39")
40 (1.6")
59 (2.3")
ø 4,2 (0.17")
ø 5,5 (0.22")
ø 6 (0.22")
7 (0.27")
11,3 (0.44")
** Mean switching differential at min. and max. setting
GB-5
F
NL
I
E
U-angle bracket
47,5 (1.87"
DL 1,5 – 150A, DL 3 – 150K: Order No.: 74916185
Tube set
To be used with air only.
75 (2.95")
20
(0.79")
GB
50 (1.97")
30 (1.18")
(0.79")
45 (1.77")
25 (0.98")
6 (0.24")
24 (0.94")
43
-0,3
64 (2.52")
Standard coupler plug
M4 x 12
20
16
(0.63")
(1.69")
)
40 (1.57")
M4 x 10
5,2
(0.2")
+0,1
(0.17")
4,20
10
(0.4")
39 (1.53")
Order No.: 74912952
Order No.: 74919272
Pilot lamp set, red or blue
DL..T, DL..N
Pilot lamp, red:
110/120 V AC, I = 1.2 mA, Order No.: 74920430;
220/250 V AC, I = 0.6 mA, Order No.: 74920429.
Pilot lamp, blue:
110/120 V AC, I = 1.2 mA, Order No.: 74916121;
220/250 V AC, I = 0.6 mA, Order No.: 74916122.
231
4
N
3
COM
NO
L1
2
NC
1
NO
2
NC
NO
1
3
COM
N
Order No.: 74916159
Motor flange adapter
Set including retaining screws
DL..A, DL 3 – 5K: Order No.: 74916157,
DL 5 – 150K: Order No.: 74916156.
GB-6
NO
NC
L1
3
COM
2
1
NC
N
NO
1
2
NC
3
COM
N
F
NL
I
E
LED set, red/green
DL..K2, DL..T2
24 V DC, I = 16 mA; 24 V AC, I = 8 mA,
Order No.: 74921089;
230 V AC, I = 0.6 mA, Order No.: 74923275.
231
4
NO
2
+
3 COM
1 NC
1
2
NC
NO
–
3
COM
N
External adjustment
In order to set the switching pressure from the outside, the cover for external adjustment (6mm Allen
key) for DL..A, DL5 – 150K can be retrofitted.
Order No.: 74916155
231
Technical data
Gas type: air or flue gas, no flammable gases, no
aggressive gases.
Max. inlet pressure = withstand pressure: see type
label or page 5 (Adjustment).
Micro switch to EN 61058-1.
Switching capacity:
DL..: 24 V (min. 0.05 A) to 250 V AC
(max. 5 A, at cos φ 0.6 = 1 A),
max. 6 A, temporarily (<1 s) 20A.
DL..G: 5 V (min. 0.01 A) to 250 V AC
(max. 5 A, at cos φ 0.6 = 1 A),
5 V (min. 0.01 A) to 48 V DC (max.1A),
DL..T: 30 – 240 V AC, 50/60 Hz,
5 A resistive or
0.5 A inductive (cos φ= 0.6),
DL..TG: < 30 V AC/DC,
0.1 A resistive or
0.05 A inductive (cos φ= 0.6).
Contact gap < 3 mm (μ).
Safety class II to VDE 0106-1.
Max. medium and ambient temperatures:
DL: -20 to +80°C (-4 to +176°F),
DL..T: -40 to +60°C (-40 to +140°F).
Long-term use in the upper ambient temperature
range accelerates the ageing of the elastomer materials and reduces the service life (please contact
manufacturer).
Storage temperature:
-20 to +40°C (-4 to +104°F).
Diaphragm pressure switch, NBR, silicone-free.
Housing: glass fibre reinforced PBT plastic with
low gas release.
Enclosure to IEC 60529: IP54, IP65.
Line entrance: M16 x 1.5 (1/2" NPT conduit),
clamping range: diameters of 4 to 10mm.
Type of connection: screw terminals.
Weight: DL..A: 190g (6.7oz), DL..K: 220 g
(7.8oz).
GB
Designed lifetime
This information on the designed lifetime is based on
using the product in accordance with these operating
instructions. Once the designed lifetime has been
reached, safety-relevant products must be replaced.
Designed lifetime (based on date of manufacture) in
accordance with EN13611, EN1854 for pressure
switches: 10 years.
You can find further explanations in the applicable
rules and regulations and on the afecor website
(www.afecor.org).
This procedure applies to heating systems. For
thermoprocessing equipment, observe local regulations.
GB-7
F
NL
I
E
Logistics
Transport
Protect the unit from external forces (blows, shocks,
vibration). On receipt of the product, check that the
delivery is complete, see page2 (Part designations). Report any transport damage immediately.
Storage
Store the product in a dry and clean place.
Storage temperature: see page7 (Technical data).
Storage time: 6months before using for the first
time. If stored for longer than this, the overall service
life will be reduced by the corresponding amount of
extra storage time.
GB
Packaging
The packaging material is to be disposed of in ac-
cordance with local regulations.
Disposal
Components are to be disposed of separately in
accordance with local regulations.
Certification
Declaration of conformity
We, the manufacturer, hereby declare that the product DL, marked with product ID No. CE-0085AP0466,
complies with the requirements of the listed Directives.
Directives:
– 2009/142/EC
– 2006/95/EC
The relevant product corresponds to the type tested
by the notified body 0085.
The production is subject to the surveillance proce-
dure pursuant to Directive 2009/142/EC AnnexII
paragraph3 and pursuant to DIN EN ISO 9001:2008.
Elster GmbH
FM approval
Factory Mutual Research Class: 3510 Flow and
pressure safety switches.
Designed for applications pursuant to NFPA 85 and
NFPA 86.
UL approval
UL 353 Limit control
AGA approval
Australian Gas Association, Approval No.: 5484
AGA
Eurasian Customs Union
The product DL meets the technical specifications
of the Eurasian Customs Union.
RoHS compliant
Scan of the Declaration of conformity (D, GB) – see
www.docuthek.com
Contact
Contact
Elster GmbH
If you have any technical questions, please contact
your local branch office/agent. The addresses are
available on the Internet or from ElsterGmbH.
We reserve the right to make technical modifications
Elster GmbH
Elster GmbH
Postfach 28 09, D-49018 Osnabrück
Postfach 28 09, D-49018 Osnabrück
Postfach 28 09, D-49018 Osnabrück
Strotheweg 1, D-49504 Lotte (Büren)
Strotheweg 1, D-49504 Lotte (Büren)
Strotheweg 1, D-49504 Lotte (Büren)
T +49 541 1214-0
T +49 541 1214-0
T +49 541 1214-0
F +49 541 1214-370
F +49 541 1214-370
F +49 541 1214-370
in the interests of progress.info@kromschroeder.com, www.kromschroeder.com
GB-8
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.