Operating instructions

Pressure switches for gas DG..S for NH3 and O2

© 2012 Elster GmbH · Edition 08.12
Translation from the German

Contents

Contents
Pressure switches for gas DG..S for NH3
and O2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Checking the usage . . . . . . . . . . . . . . . . . . . . . 2
Type code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Part designations . . . . . . . . . . . . . . . . . . . . . . . . 2
Type label. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Tightness test . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . 4
Declaration of conformity . . . . . . . . . . . . . . . . 4
Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Safety

Safety
Please read and keep in a safe place
carefully before installing or operating. Following the installation, pass the instructions on to the opera­tor. This unit must be installed and commissioned in accordance with the regulations and standards in force. These instructions can also be found at www.docuthek.com.
Explanation of symbols
• , 1 , 2 , 3 ... = Action
= Instruction
Liability
We will not be held liable for damages resulting from non-observance of the instructions and non­compliant use.
Safety instructions
Information that is relevant for safety is indicated in the instructions as follows:
Please read through these instructions
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified gas technicians. Electrical interventions may only be carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM spare parts.
Transport
On receipt of the product, check that the delivery is complete (see Part designations). Report any trans­port damage immediately.
Storage
Store the product in a dry place. Ambient tempera­ture: see Technical data.
GB-1
GB
F
NL
I
E

Checking the usage

DG
To monitor rising and falling pressure.
DG..S
This function is only guaranteed when used within
the specified limits– see page4 (Technical data). Any other use is considered as non-compliant.

Type code

Code Description
DG Gas pressure switch 6 – 500 Max. setting in mbar S Positive pressure (NH G With gold-plated contacts
-3
-4
-5
-6
-9 K2 T T2 N A External adjustment

Part designations

1 Upper housing section with cover
2 Lower housing section 3 Hand wheel 4 M16 cable gland
Positive
pressure
NH
3
air
, O2,
Negative pres-
sure
Electrical connection
via screw terminals
via screw terminals, IP 65
4-pin plug, without socket
4-pin plug, with socket
4-pin plug, with socket, IP 65
Red/green pilot LED for 24 V DC/AC
Blue pilot lamp for 230 V AC
Red/green pilot LED for 230 V AC
Blue pilot lamp for 120 V AC
3
2
1
4
Differential
pressure
, O2)
3

Installation

CAUTION
Please observe the following to ensure that the DG is not damaged during installation and operation:
– As the temperature increases, the diffusion rate
of NH3 through the diaphragm also increases which can cause corrosion of the contacts. For this reason, query the closed contacts for opening.
– The medium NH3 must not condense as this can
lead to increased corrosion of the lower section (pressure supply can become blocked) and de­formation of the diaphragm (causing the switching point to shift).
– Continuous operation at high temperatures accel-
erates the ageing of elastomer materials. In places where a high thermal capacity is required, thermal equipment trips must be installed upstream of
theDG. – Use approved sealing material only. – Check max. ambient temperature – see
page4 (Technical data). – Condensation or vapours containing silicone must
not be allowed to get into the housing. At subzero
temperatures malfunctions/failures due to icing
can occur. – The service life will be shorter if subject to ozone
concentrations exceeding 200μg/m3. When in-
stalling outdoors, place the DG in a roofed area
and protect from direct sunlight (even IP65 ver-
sion). To avoid condensation, the cover with pres-
sure equalization element can be used. – Avoid subjecting the DG to strong or violent vibra-
tions.
▷ Installation position as required, preferably with
vertical diaphragm. Then the switching pointp corresponds to the scale valueSK set on the hand wheel. In other installation positions, the switching pointpS will change and no longer correspond to the scale valueSK set on the hand wheel. Check the switching point.
S

Type label

Max. inlet pressure, mains voltage, ambient tem­perature, enclosure: see type label.
D-49018 Osnabrück, Germany
DG
2
3
1
ps = SK
The DG must not be in contact with masonry.
ps = SK + 0,18 mbar
ps = SK - 0,18 mbar
Minimum clearance 20mm.
Ensure that there is sufficient installation space. Ensure unobstructed view of the hand wheel.
1 Disconnect the system from the electrical power
supply.
2 Shut off the medium supply. 3 Ensure that the pipeline is clean.
GB-2
GB
F
NL
I
E
3 42
NO
2
NC
1
COM
3
COM
3
NC
1
NO
2
Contacts 3 and 2 close when subject to increas-
1
Positive pressure
1
(Rp ¼)
4
4
Atmospheric pressure
1
(Rp
/8)
ing pressure. Contacts 1 and 3 close when sub­ject to falling pressure.
NO
L1
3
COM
2
1
NC
1
2
NC
NO
COM
3
Positive pressure
1
DG..S
4 If the electrical contacts in the DG..S could be
soiled by dirt particles in the surrounding air or in the medium, use a filter pad at port4.

Adjustment

The switching point is adjustable via hand wheel.
1 Disconnect the system from the electrical power
supply.
2 Detach the housing cover, see page3 (Wir-
ing).
3 Connect an ohmmeter.
Connect Seal Free

Wiring

If the DG..SG has switched a voltage >24V and a current >0.1A once, the gold plating on the contacts will have been burnt through. It
NO
NC
COM
2
3
1
NO
1
2
NC
3
COM
can then only be operated at this power rating or higher power rating.
Pressure switch DG can be used in Zone1 and2 hazardous areas if an isolating ampli-
4 Set the switching point using the hand wheel. 5 Connect a pressure gauge.
fier is installed upstream in the safe area as
“Ex-i” equipment pursuant to EN 60079-11
0
(VDE0170-7):2007. DG as “simple electrical equipment” pursuant to
EN60079-11:2007 corresponds to the Tempera­ture classT6, GroupII. The internal inductance/ capacitance is Lo = 0.2μH/Co = 8 pF.
▷ In the case of low switching capacities, such as
24V, 8mA, for example, we recommend using an RCmodule (22Ω, 1μF) in air containing silicone or oil.
CAUTION
Please observe the following to ensure that the DG is not damaged during operation:
– Note the switching capacity, see page4 (Tech-
nical data).
1 Disconnect the system from the electrical power
supply.
3 42
5 6 7
1 cm = 1 mbar
6 Apply pressure. In doing so, monitor the switch-
ing point on the ohmmeter and the pressure gauge.
Switching dif-
ferential**
[mbar]
Type
Adjusting range*
[mbar]
DG 6 0.4 – 6 0.2 – 0.3 DG 10 1 – 10 0.25 – 0.4 DG 30 2.5 – 30 0.35 – 0.9 DG 50 2.5 – 50 0.8 – 1.5 DG 150 30 – 150 3 – 5 DG 400 50 – 400 5 – 15 DG 500 100 – 500 8 – 17
* Adjusting tolerance = ± 15% of the scale value. ** Mean switching differential at min. and max. setting.
If the DG does not trip at the desired switch­ing point, correct the adjusting range using the hand wheel. Relieve the pressure and repeat the process.
ø 4,5–10 mm
M16 x 1,5:
GB-3
GB
F
NL
I
E

Tightness test

1 Shut off the downstream pipeline close to the
valve.
2 Open the valve and the medium supply.
▷ Check all used ports for tightness.
3 4
N2 900 mbar max. 2 bar < 15 min

Maintenance

In order to ensure smooth operation: check the tight­ness and function of the DG every year.
▷ After carrying out the maintenance work, check
for tightness, see page4 (Tightness test).
Max. medium temperature: -15to+80°C. Storage and transport temperature: -40to+80°C. RoHS compliant pursuant to 2002/95/EC. Diaphragm pressure switch, silicone-free. Diaphragm: IIR. Housing: glass fibre reinforced PBT plastic with low gas release. Lower housing section: AlSi 12. Enclosure: IP54 or IP65. Safety class: 1. Line entrance: M16 x 1.5, clamping range: diam­eters of 4 to 10mm. Electrical connection type: screw terminals. Weight: 270 g – 320 g.

Declaration of conformity

Technical data

Gas type: NH3, O2 and air. Max. test pressure for testing the entire system: temporarily <15minutes 2bar. Switching capacity: DG, U = 24 – 250 V AC: I = 0.05 – 5 A at cos ϕ = 1, I = 0.05 – 1 A at cos ϕ = 0.6.
DG..G, U = 5 – 250 V AC: I = 0.01 – 5 A at cos ϕ = 1, I = 0.01 – 1 A at cos ϕ = 0.6.
DG..G, U = 5 – 48 V DC: I = 0.01 – 1 A.

Contact

Contact
We, the manufacturer, hereby declare that the prod­uct DG..S complies with the essential requirements of the following Directive:
– 2006/95/EC
The production is subject to the Quality System pur-
suant to DIN EN ISO 9001:2008, TÜV NORD CERT. Elster GmbH
Scan of the Declaration of conformity (D, GB) – see www.docuthek.com
RoHS compliant
RoHS
2002/95/EC
If you have any technical questions, please contact your local branch office/agent. The addresses are available on the Internet or from ElsterGmbH.
We reserve the right to make technical modifications in the interests of progress.