carefully before installing or operating. Following the
installation, pass the instructions on to the operator. This unit must be installed and commissioned
in accordance with the regulations and standards
in force. These instructions can also be found at
www.docuthek.com.
Explanation of symbols
• , 1 , 2 , 3 ... = Action
▷ = Instruction
Liability
We will not be held liable for damages resulting
from non-observance of the instructions and noncompliant use.
Safety instructions
Information that is relevant for safety is indicated in
the instructions as follows:
Please read through these instructions
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified
gas technicians. Electrical interventions may only be
carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM
spare parts.
Transport
On receipt of the product, check that the delivery is
complete (see Part designations). Report any transport damage immediately.
Storage
Store the product in a dry place. Ambient temperature: see Technical data.
GB-1
GB
F
NL
I
E
Checking the usage
DG
To monitor rising and falling pressure.
DG..S
This function is only guaranteed when used within
the specified limits– see page4 (Technical data).
Any other use is considered as non-compliant.
Please observe the following to ensure that the DG
is not damaged during installation and operation:
– As the temperature increases, the diffusion rate
of NH3 through the diaphragm also increases
which can cause corrosion of the contacts. For
this reason, query the closed contacts for opening.
– The medium NH3 must not condense as this can
lead to increased corrosion of the lower section
(pressure supply can become blocked) and deformation of the diaphragm (causing the switching
point to shift).
– Continuous operation at high temperatures accel-
erates the ageing of elastomer materials. In places
where a high thermal capacity is required, thermal
equipment trips must be installed upstream of
theDG.
– Use approved sealing material only.
– Check max. ambient temperature – see
page4 (Technical data).
– Condensation or vapours containing silicone must
not be allowed to get into the housing. At subzero
temperatures malfunctions/failures due to icing
can occur.
– The service life will be shorter if subject to ozone
concentrations exceeding 200μg/m3. When in-
stalling outdoors, place the DG in a roofed area
and protect from direct sunlight (even IP65 ver-
sion). To avoid condensation, the cover with pres-
sure equalization element can be used.
– Avoid subjecting the DG to strong or violent vibra-
tions.
▷ Installation position as required, preferably with
vertical diaphragm. Then the switching pointp
corresponds to the scale valueSK set on the
hand wheel. In other installation positions, the
switching pointpS will change and no longer
correspond to the scale valueSK set on the
hand wheel. Check the switching point.
S
Type label
Max. inlet pressure, mains voltage, ambient temperature, enclosure: see type label.
D-49018 Osnabrück, Germany
DG
2
3
1
ps = SK
▷
The DG must not be in contact with masonry.
ps = SK + 0,18 mbar
ps = SK - 0,18 mbar
Minimum clearance 20mm.
▷ Ensure that there is sufficient installation space.▷ Ensure unobstructed view of the hand wheel.
1 Disconnect the system from the electrical power
supply.
2 Shut off the medium supply.
3 Ensure that the pipeline is clean.
GB-2
GB
F
NL
I
E
342
▷
NO
2
NC
1
COM
3
COM
3
NC
1
NO
2
Contacts 3 and 2 close when subject to increas-
1
Positive pressure
1
(Rp ¼)
4
4
Atmospheric pressure
1
(Rp
/8)
ing pressure. Contacts 1 and 3 close when subject to falling pressure.
NO
L1
3
COM
2
1
NC
1
2
NC
NO
COM
3
Positive
pressure
1––
DG..S
4 If the electrical contacts in the DG..S could be
soiled by dirt particles in the surrounding air or
in the medium, use a filter pad at port4.
Adjustment
▷
The switching point is adjustable via hand wheel.
1 Disconnect the system from the electrical power
supply.
2 Detach the housing cover, see page3 (Wir-
ing).
3 Connect an ohmmeter.
ConnectSealFree
Wiring
▷
If the DG..SG has switched a voltage >24V
and a current >0.1A once, the gold plating
on the contacts will have been burnt through. It
NO
NC
COM
2
3
1
NO
1
2
NC
3
COM
can then only be operated at this power rating
or higher power rating.
▷
Pressure switch DG can be used in Zone1
and2 hazardous areas if an isolating ampli-
4 Set the switching point using the hand wheel.
5 Connect a pressure gauge.
fier is installed upstream in the safe area as
“Ex-i” equipment pursuant to EN 60079-11
0
(VDE0170-7):2007.
DG as “simple electrical equipment” pursuant to
▷
EN60079-11:2007 corresponds to the Temperature classT6, GroupII. The internal inductance/
capacitance is Lo = 0.2μH/Co = 8 pF.
▷ In the case of low switching capacities, such as
24V, 8mA, for example, we recommend using
an RCmodule (22Ω, 1μF) in air containing
silicone or oil.
CAUTION
Please observe the following to ensure that the DG
is not damaged during operation:
– Note the switching capacity, see page4 (Tech-
nical data).
1 Disconnect the system from the electrical power
supply.
342
567
1 cm = 1 mbar
6 Apply pressure. In doing so, monitor the switch-
* Adjusting tolerance = ± 15% of the scale value.
** Mean switching differential at min. and max. setting.
▷
If the DG does not trip at the desired switching point, correct the adjusting range using the
hand wheel. Relieve the pressure and repeat
the process.
ø 4,5–10 mm
M16 x 1,5:
GB-3
GB
F
NL
I
E
Tightness test
1 Shut off the downstream pipeline close to the
valve.
2 Open the valve and the medium supply.
▷ Check all used ports for tightness.
34
N2
900 mbar
max. 2 bar
< 15 min
Maintenance
In order to ensure smooth operation: check the tightness and function of the DG every year.
▷ After carrying out the maintenance work, check
for tightness, see page4 (Tightness test).
Max. medium temperature: -15to+80°C.
Storage and transport temperature: -40to+80°C.
RoHS compliant pursuant to 2002/95/EC.
Diaphragm pressure switch, silicone-free.
Diaphragm: IIR.
Housing: glass fibre reinforced PBT plastic with
low gas release.
Lower housing section: AlSi 12.
Enclosure: IP54 or IP65.
Safety class: 1.
Line entrance: M16 x 1.5, clamping range: diameters of 4 to 10mm.
Electrical connection type: screw terminals.
Weight: 270 g – 320 g.
Declaration of conformity
Technical data
Gas type: NH3, O2 and air.
Max. test pressure for testing the entire system:
temporarily <15minutes 2bar.
Switching capacity:
DG, U = 24 – 250 V AC:
I = 0.05 – 5 A at cos ϕ = 1,
I = 0.05 – 1 A at cos ϕ = 0.6.
DG..G, U = 5 – 250 V AC:
I = 0.01 – 5 A at cos ϕ = 1,
I = 0.01 – 1 A at cos ϕ = 0.6.
DG..G, U = 5 – 48 V DC:
I = 0.01 – 1 A.
Contact
Contact
We, the manufacturer, hereby declare that the product DG..S complies with the essential requirements
of the following Directive:
– 2006/95/EC
The production is subject to the Quality System pur-
suant to DIN EN ISO 9001:2008, TÜV NORD CERT.
Elster GmbH
Scan of the Declaration of conformity (D, GB) – see
www.docuthek.com
RoHS compliant
RoHS
2002/95/EC
If you have any technical questions, please contact
your local branch office/agent. The addresses are
available on the Internet or from ElsterGmbH.
We reserve the right to make technical modifications
in the interests of progress.
Strotheweg 1, D-49504 Lotte (Büren)
Elster GmbH
Tel. +49 541 1214-0
Fax +49 541 1214-370
hts.lotte@honeywell.com, www.kromschroeder.com
GB-4