Krom Schroder CPS 1000, CPS 4000, CPS 330, CPS 300, CPS 3000 Operating Instructions Manual

...
4.2.2.2 Edition 02.10
www.docuthek.com
GB
F
NL
I
E
D GB F NL I E

Safety

Please read and keep in a safe place
Operating instructions
CPS 00 – 000 CPS 0 – 4000
Translation from the German
© 2008 – 2009 Elster GmbH

Contents

CPS 00 – 000 ......................... 1
CPS 0 – 4000 ......................... 1
Contents ..............................1
Safety.................................1
Checking the usage .....................2
Installation ............................2
Adjusting the switching pressure p
Wiring ................................
Maintenance ...........................
Accessories ...........................
Tube set ...............................3
Pilot lamp set ...........................4
External adjustment ......................4
Z-angle bracket .........................4
Motor flange............................4
Declaration of conformity ................4
Contact ...............................4
S ..........
Please read through these instructions
ing the installation, pass the instructions on to the operator. These instructions can also be found at www.docuthek.com.
Explanation of symbols
• , 1 , 2 ,  ... = Action
= Instruction
Liability
We will not be held liable for damages resulting from non-observance of the instructions and non­compliant use.
Safety instructions
Information that is relevant for safety is indicated in the instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified gas technicians. Electrical interventions may only be carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM spare parts.
Transport
On receipt of the product, check that the delivery is complete (see Part designations). Report any trans­port damage immediately.
Storage
Store the product in a dry place. Ambient tempera­ture: see Technical data.
GB-1
GB
F
NL
I
E

Checking the usage

CPS
Pressure switch for air for monitoring positive, nega­tive or differential pressure, for air or non-flammable gases.
Type code
Code Description
CPS Air pressure switch
00 0 450 510 800 1000 1100 1600 2400 000 4000 G Gold contacts
Part designations
5
1
2
7
3
8
6
1
2
3
6
CPS 330 – 4000
1 Positive pressure port (+) 2 Negative pressure port (-)Cable gland
(M16 × 1.5, for cable diameters 4.5 – 10 mm)
4 Cover 5 Hand wheel with scale 6 Holes for bolting 7 Z-angle bracket for bolting to the CPS
(included in delivery for CPS 300, CPS 1000, CPS 3000)
8 Type label 9 Cover for connection terminals
Inlet pressure p type label.
and ambient temperature – see
e max
Osnabrück Germany
CPS
Adjusting range [Pa]
1
9
2
4
7
CPS 1000, CPS 3000CPS 300
6
4
5
8
8
20 – 300 20 – 330 30 – 500
100 – 510
50 – 800 100 – 1000 100 – 1100 400 – 1600 200 – 2400 250 – 3000 500 – 4000
9
4
3
7

Installation

CAUTION
Please observe the following to ensure that the CPS is not damaged during installation and operation:
– Protect the connections against dirt or moisture in
the medium to be measured and the surrounding air.
– Avoid subjecting the CPS to strong or violent vi-
brations.
– Condensation must not be allowed to get into the
housing. At subzero temperatures malfunctions/ failures due to icing can occur.
– When using silicone tubes, only use silicone tubes
which have been sufficiently cured.
The switching pressure pS only corresponds to
the scale value SK on the hand wheel when the diaphram is vertical.
CPS 300
5
CPS 1000 CPS 3000 CPS 330
to CPS 4000
CPS 00, CPS 1000, CPS 000
1 Mount the CPS using the Z-angle bracket.
CPS 0 – 4000
1 Attach the CPS itself using screws or bolt it using
the optional Z-angle bracket.
If the CPS is directly attached, use a maximum of 2 screws to prevent stresses on the CPS.
CPS 00 – 4000 2 Attach 4.75 mm diameter tube to the positive or
negative pressure port.
For measuring positive pressure
▷ Attach the tube to the positive pressure port (+).
The negative pressure port is left open to ventilate
the upper chamber of the diaphragm.
pS = SK pS = SK pS = SK
pS = SK
pS = SK + 18 Pa pS = SK - 18 Pa pS = SK + 18 Pa pS = SK - 18 Pa pS = SK + 18 Pa pS = SK - 18 Pa
pS = SK + 13 Pa pS = SK - 13 Pa
4,2
40
5,5
59
4,4
66
GB-2
Loading...