Please observe the following to ensure that the CPS
is not damaged during installation and operation:
– Protect the connections against dirt or moisture in
the medium to be measured and the surrounding
air.
– Avoid subjecting the CPS to strong or violent vi-
brations.
– Condensation must not be allowed to get into the
housing. At subzero temperatures malfunctions/
failures due to icing can occur.
– When using silicone tubes, only use silicone tubes
which have been sufficiently cured.
▷
The switching pressure pS only corresponds to
the scale value SK on the hand wheel when the
diaphram is vertical.
CPS 300
5
CPS 1000
CPS 3000
CPS 330
to
CPS 4000
CPS 00, CPS 1000, CPS 000
1 Mount the CPS using the Z-angle bracket.
CPS 0 – 4000
1 Attach the CPS itself using screws or bolt it using
the optional Z-angle bracket.
▷
If the CPS is directly attached, use a maximum of
2 screws to prevent stresses on the CPS.
CPS 00 – 4000
2 Attach 4.75 mm diameter tube to the positive or
negative pressure port.
For measuring positive pressure
▷ Attach the tube to the positive pressure port (+).
The negative pressure port is left open to ventilate
the upper chamber of the diaphragm.
pS = SK
pS = SK
pS = SK
pS = SK
pS = SK + 18 Pa pS = SK - 18 Pa
pS = SK + 18 Pa pS = SK - 18 Pa
pS = SK + 18 Pa pS = SK - 18 Pa
pS = SK + 13 Pa pS = SK - 13 Pa
∅ 4,2
40
∅ 5,5
59
∅ 4,4
66
GB-2
GB
F
NL
I
E
For measuring negative pressure
▷ Attach the tube to the negative pressure port (-).
The positive pressure port is left open to ventilate
the lower chamber of the diaphragm.
For measuring differential pressure
▷ Attach the tube with the higher pressure to the
positive pressure port (+), attach the tube with the
lower pressure to the negative pressure port (-).
Adjusting the switching pressure p
▷
The switching pressure can be adjusted using the
S
hand wheel with scale. The switching pressure
differs from the adjusted setpoint by a maximum
of ± 15%, when it has been set for increasing
pressure and with a vertical diaphragm.
1 Disconnect the system from the electrical power
supply.
2 Generate negative and/or positive pressure on
the CPS.
Remove the CPS cover.
4 Check the contact position with a measuring
instrument.
NO
NC
1
2
NC
COM
2
3
1
NO
COM
3
▷ If the CPS..G has switched a voltage > 24 V and
a current > 0.1 A once, the gold plating on the
contacts will have been burnt through. It can then
only be operated at this power rating or higher
power rating.
▷ In the case of low switching capacities, as 24 V,
8 mA, for example, we recommend using an RC
module (22 Ω, 1 μF) in air containing silicone or oil.
1 Disconnect the system from the electrical power
supply.
2 Remove the CPS cover.
▷
CPS 300, CPS 1000, CPS 3000: remove the
cover for the connection terminals.
Feed the cable through the cable gland into the
CPS.
COM
2
NO
3
L1(+)
NC
1
4
NO
1
2
NC
3
COM
5 Replace the CPS cover and screw into place.
Maintenance
▷ We recommend a function check once a year.
5 Set the switching pressure using the hand wheel.
24 – 250 V AC:
I = 0.05 – 5 A, cos φ = 1,
I = 0.05 – 1 A, cos φ = 0.6.
CPS..G (gold contact)
12 – 250 V AC:
I = 0.01 – 5 A, cos φ = 1,
I = 0.01 – 1 A, cos φ = 0.6;
12 – 48 V DC:
I = 0.01 – 1 A.
Order No. 74919272
GB-3
GB
F
NL
I
E
Pilot lamp set
21
For indicating the switching status of the CPS.
21
Motor flange
For space-saving attachment of the pressure switch
directly on the fan motor. It is not necessary to drill
holes for mounting the motor flange.
Pilot lamp set red220/240 V AC 74920492
VoltageOrder No.
Pilot lamp set red110/120 V AC 74920430
Pilot lamp set blue220/240 V AC 74916122
Pilot lamp set blue110/120 V AC 74916121
LED set green/red24 V DC74921089
LED set green/red230 V AC74923275
External adjustment
For adjusting the switching pressure for the pressure
switches CPS 300, CPS 1000 or CPS 3000 when
the cover is closed.
Order No. 74916155
Z-angle bracket
For fast installation and removal of the CPS 330
–4000 with diverse mounting options, even with
only one screw.
The angle bracket increases the distance between
pressure switch and mounting plate.
CPS 30074916157
Order No.
CPS 1000, CPS 300074916156
CPS 330 – 400074920415
Declaration of conformity
We, the manufacturer, hereby declare that the products CPS 300 to CPS 4000 comply with the requirements of the listed Directives and Standards.
Directives:
– 2006/95/EC.
Standards:
– DIN EN 1854.
The production is subject to a Quality System pursu-
ant to DIN EN ISO 9001.
Elster GmbH
Scan of the Declaration of conformity (D, GB) – see
www.docuthek.com
Order No. 74919824
Contact
If you have any technical questions, please contact
your local branch office/agent. The addresses are
available on the Internet or from ElsterGmbH.
We reserve the right to make technical modifications
in the interests of progress.
Strotheweg 1, D-49504 Lotte (Büren)
Elster GmbH
Tel. +49 541 1214-0
Fax +49 541 1214-370
hts.lotte@honeywell.com, www.kromschroeder.com
GB-4
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.