Krom Schroder CPS 1000, CPS 4000, CPS 330, CPS 300, CPS 3000 Operating Instructions Manual

...
4.2.2.2 Edition 02.10
www.docuthek.com
GB
F
NL
I
E
D GB F NL I E

Safety

Please read and keep in a safe place
Operating instructions
CPS 00 – 000 CPS 0 – 4000
Translation from the German
© 2008 – 2009 Elster GmbH

Contents

CPS 00 – 000 ......................... 1
CPS 0 – 4000 ......................... 1
Contents ..............................1
Safety.................................1
Checking the usage .....................2
Installation ............................2
Adjusting the switching pressure p
Wiring ................................
Maintenance ...........................
Accessories ...........................
Tube set ...............................3
Pilot lamp set ...........................4
External adjustment ......................4
Z-angle bracket .........................4
Motor flange............................4
Declaration of conformity ................4
Contact ...............................4
S ..........
Please read through these instructions
ing the installation, pass the instructions on to the operator. These instructions can also be found at www.docuthek.com.
Explanation of symbols
• , 1 , 2 ,  ... = Action
= Instruction
Liability
We will not be held liable for damages resulting from non-observance of the instructions and non­compliant use.
Safety instructions
Information that is relevant for safety is indicated in the instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified gas technicians. Electrical interventions may only be carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM spare parts.
Transport
On receipt of the product, check that the delivery is complete (see Part designations). Report any trans­port damage immediately.
Storage
Store the product in a dry place. Ambient tempera­ture: see Technical data.
GB-1
GB
F
NL
I
E

Checking the usage

CPS
Pressure switch for air for monitoring positive, nega­tive or differential pressure, for air or non-flammable gases.
Type code
Code Description
CPS Air pressure switch
00 0 450 510 800 1000 1100 1600 2400 000 4000 G Gold contacts
Part designations
5
1
2
7
3
8
6
1
2
3
6
CPS 330 – 4000
1 Positive pressure port (+) 2 Negative pressure port (-)Cable gland
(M16 × 1.5, for cable diameters 4.5 – 10 mm)
4 Cover 5 Hand wheel with scale 6 Holes for bolting 7 Z-angle bracket for bolting to the CPS
(included in delivery for CPS 300, CPS 1000, CPS 3000)
8 Type label 9 Cover for connection terminals
Inlet pressure p type label.
and ambient temperature – see
e max
Osnabrück Germany
CPS
Adjusting range [Pa]
1
9
2
4
7
CPS 1000, CPS 3000CPS 300
6
4
5
8
8
20 – 300 20 – 330 30 – 500
100 – 510
50 – 800 100 – 1000 100 – 1100 400 – 1600 200 – 2400 250 – 3000 500 – 4000
9
4
3
7

Installation

CAUTION
Please observe the following to ensure that the CPS is not damaged during installation and operation:
– Protect the connections against dirt or moisture in
the medium to be measured and the surrounding air.
– Avoid subjecting the CPS to strong or violent vi-
brations.
– Condensation must not be allowed to get into the
housing. At subzero temperatures malfunctions/ failures due to icing can occur.
– When using silicone tubes, only use silicone tubes
which have been sufficiently cured.
The switching pressure pS only corresponds to
the scale value SK on the hand wheel when the diaphram is vertical.
CPS 300
5
CPS 1000 CPS 3000 CPS 330
to CPS 4000
CPS 00, CPS 1000, CPS 000
1 Mount the CPS using the Z-angle bracket.
CPS 0 – 4000
1 Attach the CPS itself using screws or bolt it using
the optional Z-angle bracket.
If the CPS is directly attached, use a maximum of 2 screws to prevent stresses on the CPS.
CPS 00 – 4000 2 Attach 4.75 mm diameter tube to the positive or
negative pressure port.
For measuring positive pressure
▷ Attach the tube to the positive pressure port (+).
The negative pressure port is left open to ventilate
the upper chamber of the diaphragm.
pS = SK pS = SK pS = SK
pS = SK
pS = SK + 18 Pa pS = SK - 18 Pa pS = SK + 18 Pa pS = SK - 18 Pa pS = SK + 18 Pa pS = SK - 18 Pa
pS = SK + 13 Pa pS = SK - 13 Pa
4,2
40
5,5
59
4,4
66
GB-2
GB
F
NL
I
E
For measuring negative pressure
▷ Attach the tube to the negative pressure port (-).
The positive pressure port is left open to ventilate
the lower chamber of the diaphragm.
For measuring differential pressure
▷ Attach the tube with the higher pressure to the
positive pressure port (+), attach the tube with the lower pressure to the negative pressure port (-).
Adjusting the switching pressure p
The switching pressure can be adjusted using the
S
hand wheel with scale. The switching pressure differs from the adjusted setpoint by a maximum of ± 15%, when it has been set for increasing pressure and with a vertical diaphragm.
1 Disconnect the system from the electrical power
supply.
2 Generate negative and/or positive pressure on
the CPS.
Remove the CPS cover. 4 Check the contact position with a measuring
instrument.
NO
NC
1
2
NC
COM
2
3
1
NO
COM
3
▷ If the CPS..G has switched a voltage > 24 V and
a current > 0.1 A once, the gold plating on the contacts will have been burnt through. It can then only be operated at this power rating or higher power rating.
▷ In the case of low switching capacities, as 24 V,
8 mA, for example, we recommend using an RC module (22 Ω, 1 μF) in air containing silicone or oil.
1 Disconnect the system from the electrical power
supply.
2 Remove the CPS cover.
CPS 300, CPS 1000, CPS 3000: remove the cover for the connection terminals.
Feed the cable through the cable gland into the
CPS.
COM
2
NO
3
L1(+)
NC
1
4
NO
1
2
NC
3
COM
5 Replace the CPS cover and screw into place.

Maintenance

We recommend a function check once a year.
5 Set the switching pressure using the hand wheel.
Adjusting range
[Pa]
Switching hys-
teresis [Pa]

Accessories

Tube set

For connecting the CPS to an air duct. CPS 300 20 – 300 7 – 16 CPS 330 20 – 330 8 – 18 CPS 450 30 – 500 10 – 25 CPS 510 100 – 510 13 – 25 CPS 800 50 – 800 15 – 40 CPS 1000 100 – 1000 25 – 40 CPS 1100 100 – 1100 15 – 40 CPS 1600 400 – 1600 20 – 60 CPS 2400 200 – 2400 35 – 75 CPS 3000 250 – 3000 60 – 80 CPS 4000 500 – 4000 40 – 100

Wiring

CPS (silver contact)
24 – 250 V AC: I = 0.05 – 5 A, cos φ = 1, I = 0.05 – 1 A, cos φ = 0.6.
CPS..G (gold contact)
12 – 250 V AC:
I = 0.01 – 5 A, cos φ = 1, I = 0.01 – 1 A, cos φ = 0.6;
12 – 48 V DC:
I = 0.01 – 1 A.
Order No. 74919272
GB-3
GB
F
NL
I
E

Pilot lamp set

21
For indicating the switching status of the CPS.
21
Motor flange
For space-saving attachment of the pressure switch directly on the fan motor. It is not necessary to drill holes for mounting the motor flange.
Pilot lamp set red 220/240 V AC 74920492
Voltage Order No.
Pilot lamp set red 110/120 V AC 74920430 Pilot lamp set blue 220/240 V AC 74916122 Pilot lamp set blue 110/120 V AC 74916121 LED set green/red 24 V DC 74921089 LED set green/red 230 V AC 74923275

External adjustment

For adjusting the switching pressure for the pressure switches CPS 300, CPS 1000 or CPS 3000 when the cover is closed.
Order No. 74916155

Z-angle bracket

For fast installation and removal of the CPS 330
–4000 with diverse mounting options, even with
only one screw.
The angle bracket increases the distance between
pressure switch and mounting plate.
CPS 300 74916157
Order No.
CPS 1000, CPS 3000 74916156 CPS 330 – 4000 74920415

Declaration of conformity

We, the manufacturer, hereby declare that the prod­ucts CPS 300 to CPS 4000 comply with the require­ments of the listed Directives and Standards. Directives:
– 2006/95/EC.
Standards:
– DIN EN 1854.
The production is subject to a Quality System pursu-
ant to DIN EN ISO 9001. Elster GmbH
Scan of the Declaration of conformity (D, GB) – see www.docuthek.com
Order No. 74919824

Contact

If you have any technical questions, please contact your local branch office/agent. The addresses are available on the Internet or from ElsterGmbH.
We reserve the right to make technical modifications in the interests of progress.