Krom Schroder BCU 46, BCU 460, BCU 465, BCU 480 Operating Instructions Manual

GB
F
NL
I
E
035158
D GB F NL I E
TR CZ PL RUS H
DK S N P GR
www.docuthek.com
Operating instructions
Burner control unit BCU46x,480
© 2019 Elster GmbH · Edition 05.19
Cert. version 03.19
Translation from the German

Contents

Contents
Burner control unit BCU46x,480..........1
Contents ..............................1
Safety.................................1
Checking the usage .....................
Installation ............................3
Replacing the power module/bus module/
parameter chip card ....................4
Cable selection and installation ...........5
Wiring ................................5
Connection diagram ....................7
Flame control ..........................12
Adjustment ...........................13
Commissioning........................14
Manual mode .........................15
Assistance in the event of malfunction ....16
Reading off the flame signal, fault
messages and parameters ..............5
Parameters and values .................5
Legend...............................9
Technical data ........................9
Safety instructions .....................30
Logistics .............................31
Accessories ..........................31
Certification ..........................3
Contact ..............................34

Safety

Safety
Please read and keep in a safe place
Explanation of symbols
• , 1 ,  , 3 ... = Action
= Instruction
Liability
We will not be held liable for damage resulting from non-observance of the instructions and non-com­pliant use.
Safety instructions
Information that is relevant for safety is indicated in the instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified gas technicians. Electrical interventions may only be carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM spare parts.
GB-1
GB
F
NL
I
E

Checking the usage

Burner control units BCU 460, 465 and480 are de­signed to control, ignite and monitor gas burners in intermittent or continuous operation. They replace the local control cabinet. Air and gas flow monitoring as an option.
The outputs for controlling the burners, e.g. for ac-
tuator and valves, are activated via the replaceable power module LM400. All the parameters required for operation are saved on the integrated parameter chip card.
BCU 460, BCU 465
For directly ignited burners of unlimited capacity.
BCU 480
For pilot and main burners of unlimited capacity. Pilot and main burners can be monitored independently.
LM..F0
Power module without air control interface.
LM..F1, LM..F3
Power module with air control interfaces to connect an air valve (LM..F3) or actuator IC40 (LM..F1).
This function is only guaranteed when used within the
specified limits– see page29 (Technical data). Any other use is considered as non-compliant.
Type code
Code Description BCU 4 Series 4 burner control unit 60 65 80 Q W 1 2 3 8 P0 P1 P2 P3 P6 P7 C0 C1 C2 D0 D1 D2 0 1 2 3 0 1 2 3 K0 K1 K2
Mains voltage: 120 V AC, 50/60 Hz
230 V AC, 50/60 Hz
Ignition transformer duty cycle: 100%
industrial plug connector, 16-pin
No valve proving system
With TC and POC valve proving system
With POC valve proving system
No high temperature operation
For high temperature operation
Flameless operation
Input functions: none
auxiliary gas and LDS
Pressure switches: none
gas pressure switch
air and gas pressure switch
No connection plugs
Connection plugs with screw terminals
Connection plugs with spring force
Series 460 Series 465 Series 480
20%
100%
33%
Flange plate: none
standard
M32
Profibus
conduit
auxiliary gas
LDS
air pressure switch
terminals E0 E1
Energy supply: via safety interlocks
via L1
Code Description LM Power module 400 For series 4 Q W F0 F1 F3 O0 O1 O2 E0 E1 K0 K1 K2
Mains voltage: 120 V AC, 50/60 Hz
230 V AC, 50/60 Hz
Air actuator: none
with IC40 interface
with air valve control
Optional outputs: none
not fail-safe
fail-safe
Energy supply: via safety interlocks
via L1
No connection plugs
Connection plugs with screw terminals
Connection plugs with spring force
terminals
GB-2
GB
F
NL
I
E
Part designations
9
8
7
6
1
10
5
2
3
4
10
1 LED display for program status and fault
messages
On/Off button 3 Reset/Information button 4 Connection for opto-adapter 5 BCU type label 6 Power module, replaceable 7 Power module type label 8 Parameter chip card, replaceable 9 Bus module, replaceable 10
M5 screw terminal for burner ground
Type designation (A), identification number (B), con-
struction stage(C), year/week of manufacture(D), device number(E), device ID(F), voltage(G), fre­quency(H), ambient temperature in Celsius(I)/Fahr­enheit(J), enclosure(K)– see type label.
Elster GmbH Osnabrück, Made in Germany
A
B
-
D EC
F
G
H
I J K
L

Installation

CAUTION
Please observe the following to ensure that the BCU is not damaged:
– The device must not be installed in a public
place. It must be accessible to authorized personnel only. Unauthorized personnel could make changes which could cause the system to become unsafe or dangerous.
– Dropping the device can cause permanent dam-
age. In this event, replace the entire device and associated modules.
▷ The following components are sealed: 1 upper
housing section, power module, 3 bus module,
4 HMI. The BCU may only be installed and oper-
ated with undamaged seals.
4
1
2
▷ Installation position: vertical (cable glands point-
ing downwards) or down flat.
8888
8888
Distance between BCU and burner: recom­mended <1m (3.3ft), max.5m (16.4ft).
Affix the sticker (with the program step/fault message description) in the required language (available as an accessory).
3
8888
GB-3
GB
F
NL
I
E
Screwing on the BCU
2.
From inside:
1 Open the cover of the BCU.
Screw on the BCU with four screws, Ø4mm,
min. length 15mm.
Or
To the rear:
▷ The unit remains closed.
1 Attach the BCU with four self-tapping screws.
185 mm
7.28"
6.42"
163 mm
▷ Self-tapping screws (M6 x 20 mm) are supplied
with the unit.
▷ Other mounting options are available as acces-
sories:
Mounting Order No. Fastening set 74960422 External securing bars 74960414
Identification
Each burner control unit can be labelled indi-
vidually.
1 Pull out the labelling plate at the top right of the
housing.

Replacing the power module/bus module/parameter chip card

CAUTION
Please observe the following to ensure that the BCU is not damaged:
Different power supply for the gas
valves. The following combinations of BCU and LM are allowed: BCU 4xx..E1 + LM..E1: power supply via L1, BCU 4xx..E0 + LM..E1: power supply via terminal35, power supply for air outputs via L1, BCU 4xx..E0 + LM..E0: power supply via terminal35.
1 Disconnect the unit from the electrical power
supply.
Open the cover of the BCU. 3 Remove the connection plug from the power
and bus module.
▷ Power module and bus module are secured in
the BCU by retaining lugs A. The retaining lugs must be pushed away from the respective mod­ule carefully so that the power or bus module can be removed.
4 Remove the modules in the following order to
facilitate handling:
1. power module, . bus module,
3. parameter chip card (PCC).
A
3.
Label as required and slide back in.
1.
▷ Installation of the modules in reverse order.
GB-4
GB
F
NL
I
E

Cable selection and installation

▷ Signal and control line for screw terminals max.
2.5mm2 (min.AWG24, max.AWG12), for spring force terminals max. 1.5mm2 (min.AWG24, max.AWG12).
For the ionization and ignition cables, use un-
screened high-voltage cable: FZLSi 1/7 up to 180°C, Order No. 04250410, or FZLK 1/7 up to 80°C, Order No. 04250409.
The control lines must be selected in accordance
with local/national regulations.
External electrical interference must be avoided.
Do not route BCU cables in the same cable
duct as frequency converter cables or cables
emitting strong fields.
Ionization cable, UVcable
▷ Cable length:
for internal ignition max. 5 m (16.4 ft), for external
ignition (double-electrode operation or UV con-
trol) max. 50m (164ft); observe the requirements
of the ignition transformer.
The flame signal is adversely affected by EMCin-
fluences.
Lay cables individually (with low capacitance)
and, if possible, not in a metal conduit.
Profibus, Profinet, EtherNet/IP
Use only cable and plug components which
comply with the appropriate fieldbus specifica-
tions.
Profibus, Profinet and EtherNet/IP are unen-
crypted fieldbus protocols without authentica-
tion mechanisms.
Use shielded RJ45 plugs. Cable length: max. 100m between 2subscrib-
ers.
Profinet/Profibus installation guidelines, see
www.profibus.com.
Ethernet installation guidelines, see
www.odva.org.

Wiring

CAUTION
Please observe the following to ensure that the BCU is not damaged:
– Burner ground must be connected to the BCU
in order to avoid uncontrolled spark formation, especially in the case of single-electrode opera­tion.
Different power supply for the gas
valves. The following combinations of BCU and LM are allowed: BCU 4xx..E1 + LM..E1: power supply via L1, BCU 4xx..E0 + LM..E1: power supply via terminal35, power supply for air outputs via L1, BCU 4xx..E0 + LM..E0: power supply via terminal35.
– For use in an ungrounded mains system or for
mains supply between phases, install an isolat­ing transformer with single-side grounding.
Do not reverse phaseL1 and neutral conduc­torN. Do not connect different phases of a three-phase
current system to the inputs.
▷ Check the following screw connections for the
correct tightening torque so as to ensure safe grounding of housing, cover, (connection) flange plate and electronics unit as well as a good PE (ground) wire connection between the BCU and burner:
1
4
2
3
1 Cover screws: 2.4 NmPE terminals 3 Flange plate screws: 2.4 Nm 4 M5 screw terminal for burner ground: 1.8 Nm
GB-5
GB
F
NL
I
E
Use plastic cable glands/conduit couplings with multiple cable grommet. These can be detached with the plug-in connection terminals.
Do not supply voltage to the outputs.
A short-circuit on the outputs causes one of the replaceable fuses to trip.
▷ Do not set the remote reset so that it operates
(automatically) in cycles.
▷ Wire the safety circuit inputs via contacts (relay
contacts) only.
The limiters in the safety interlock (e.g. safety
temperature limiter, emergency stop) must iso­late terminal35, as well as the optional safety­relevant inputs, e.g. at terminals 36 to 41, if these are parameterized, from the voltage supply. If the safety interlock is interrupted, the display shows a blinking
as a warning signal and all of the
51
BCU’s gas valve outputs are disconnected from the electrical power supply.
Connected control elements must be equipped with protective circuits in accordance with the manufacturer’s instructions. The protective circuit prevents high voltage peaks which can cause malfunctioning of the BCU.
▷ Install the ignition cable in the BCU in the desig-
nated cable duct1 and feed it out of the BCU on the shortest possible route via the cable gland.
Screw terminals or spring force terminals are
available for the BCU: Screw terminals, Order No. 74924876, spring force terminals, Order No. 74924877. 3 Wire as shown on the connection diagram, see
from page7 (Connection diagram). 4 After wiring, close the housing cover again and
tighten the cover screws to 2.4Nm.
2
1
Observe the maximum duty cycle for the ignition transformer (see manufacturer’s instructions). Adjust the minimum pause timetBP (param­eterA062) correspondingly, if required.
All functions of the inputs at terminals 1 to 7 and 35to41, as well as of contacts 80to 82, 85to87, 90to 92 and 95to97, depend on parameters I050toI074.
1 Disconnect the system from the electrical power
supply.
Before wiring, ensure that the yellow parameter
chip card has been inserted in the BCU.
GB-6
GB
F
NL
I
E

Connection diagram

BCU 460/LM..F0
92 91 90
The connection diagram shows BCU..E1 with
LM..E1.
▷ Legend– see page29 (Legend).
LM 400..F0
N1
85 86 87
82 81 80 95 96 97
UA-Sk
N1
N1
V1 V2 V3
62 32
61 31
60 30
V3
V2
V1
PE PE PE
38
BCU 460
N
N1
29
L
59
U
p
TC
2
37
N1
N
28
L
58
40 41
39
LDS
35
7
F2
(BCU..E0)
F1
(BCU..E1)
F 3,15 A
6
HT
5
F3 3,15 A
4
3
N1
2
1
Start 1
N1
1
O
L
L1
I
UVS
230 V
BM
51 21
36
N1
N
27
L
57
N1
56 26
N1
55 25
N1
54 24 BM
52 53
PE
Z
2322
I
PE N
N
PE
GB-7
GB
F
NL
I
E
BCU 460/LM..F3
The connection diagram shows BCU..E1 with
LM..E1.
▷ Legend– see page29 (Legend).
67
92 91 90
85 86 87
82 81 80 95 96 97
LM 400..F3
Luft
v
UA-Sk
N1
N1
N1
N1
V1 V2 V3
65 34 66
62 32
61 31
60 30
Luft
V3
V2
V1
PE PE PE PE
38
BCU 460
N
N1
29
L
59
U
p
TC
2
37
N1
N
28
L
58
40 41
39
LDS
35
7
F2
(BCU..E0)
F1
(BCU..E1)
F 3,15 A
6
HT
A
P
5
F3 3,15 A
4
3
N1
2
1
Start 1
N1
1
O
L
L1
I
UVS
230 V
BM
51 21
36
N1
N
27
L
57
N1
56 26
N1
55 25
N1
54 24 BM
52 53
PE
Z
2322
I
PE N
N
PE
GB-8
GB
F
NL
I
E
BCU 465/LM..F3
The connection diagram shows BCU..E1 with
LM..E1.
▷ Legend– see page29 (Legend).
97
67
95 96
62 32
61 31
60 30
Luft
65 34 66
V3
V2
V1
PE PE PE PE
92 91 90
85 86 87
80
82 81
LM 400..F3
Luft
v
UA-Sk
N1
N1
N1
N1
V1 V2 V3
38
BCU 465
N
N1
29
L
59
U
p
TC
2
37
N1
N
28
L
58
40 41
36
N1
N
27
L
57
39
F3 3,15 A
N1
1
I
O
UVS
230 V
BM
51 21
N1
56 26
N1
55 25
N1
54 24 BM
52 53
PE
2322
PE N
menox
P
LDS
HT
A
35
7
6
5
4
3
F2
(BCU..E0)
F1
(BCU..E1)
F 3,15 A
2
1
N1
Start 1
L
L1
DW 2DW 1
PE PE
Z
I
N
PE
GB-9
GB
F
NL
I
E
BCU 480/LM..F3
The connection diagram shows BCU..E1 with
LM..E1.
▷ Legend– see page29 (Legend).
97
95 96
92 91 90
85 86 87
80
82 81
LM 400..F3
Luft
V
UA-Sk
67
66
65 34
63 33
62 32
61 31
60 30
Luft
PE
V4
V3
V2
V1
PE PE PE PE
N1
N1 N1
N1
N1
V1 V2 V3 V4
38
N
BCU 480
N1
29
L
59
U
p
TC
2
37
N1
N
28
L
58
40 41
36
N1
N
27
L
57
39
F3 3,15 A
N1
N1
N1
56 26
N1
55 25
N1
54 24
BM
UVS
230 V
52 53
BM
PE
51 21
2
1
I
O
2322
PE N
N
PE
LDS
35
7
F2
(BCU..E0)
F1
F 3,15 A
(BCU..E1)
6
HT
A
P
5
4
3
2
1
Start 1 Start 2
L
L1
GB-10
82 81
80
95 96
97
85 86 87
92 91 90
40 41
39
E0
GB
F
NL
I
E
IC 40 connected to BCU/LM..F1 (staged control)
Parameter I020 = 2.
Set IC 40 to operating mode 11, see Actuator
IC40 operating instructions or technical informa­tion bulletin at www.docuthek.com.
N1
56 26
57
N1
N27L
36
58
N1
N28L
37
22 21 20
N1
N29L
38
59
mA
19 18 16 15 14 12 11 10 87 54 21
A
D
BCU..F1
90°
41
56 26
N1
90°
66 67
64 6540
L N
AC
DC
IC 40
M
R..
PE
GB-11
GB
F
NL
I
E

Flame control

BCU 480
L1
61 31
V2
60 30
V1
62 32
V3
N28L
58
37
TC
N27L
57
36
N29L
59
38
F3 3,15 A
O
UA-Sk
V1 V2 V3 V4
82 81 80 95 96 97
85 86 87
55 25N156 26
N1
N1
N1
N1
N1
N1
N1
N1
p
U
2
3
1
2
4 657
40 41
35
39
P
LDS
Start 1 Start 2
A
PE PE PE PE
HT
F 3,15 A
F1
(BCU..E1)
F2 (BCU..E0)
BCU 480
N1
22
BM
23
51 21BMPE
N1
1
2
UVC 1
4 3 2 1
54 24 PE
PEN1
22
23
1
2
LM 400..F3
BCU 460, 465 = 1 flame amplifier BCU 480 = 2 flame amplifiers
In the case of UV control, use Elster UV sensors for intermittent operation (UVS5,10) or flame detectors for continuous operation (UVC1).
BCU 460, 465 Double-electrode operation:
See from page 7 (Connection diagram), BCU 460/LM..F0, BCU 460/LM..F3 and BCU465/LM..F3.
Ionization/single-electrode operation:
Parameter I004 = 0.
N1
1
51 21
BM
UVS
230 V
PE
BCU 480 Pilot burner = single-electrode operation/
main burner = ionization:
Pilot burner in single-electrode operation Ionization control for main burner Parameter I004 = 0.
1
2
I
PELN
51 21
BM
2322
PE
230 V
52 53
UVS
BM
N1
54 24
UV control:
UVS 5, 10
Parameter A001 ≥ 5 µA. Parameter I004 = 1.
1
51 21
UVC 1
▷ Parameter I004 = 2.
1
51 21
22
Z
N1
BM
PE
UVS
Z
N1
BM
PE
UVC 1
Z
PE
5222
BM
UVS
230 V
PE
5222
BM
1 2 3
54 24 PE
BM
4 3
2
1
N1
Pilot burner = single-electrode operation/
main burner = UVS:
Pilot burner = single-electrode operation/
main burner = UVC 1:
GB-12
Parameter A001 ≥ 5 µA. Parameter I004 = 3.
N1
2
1
51 21BMPE
23
Parameter I004 = 4.
N1
2
1
51 21
BM
22
23
UVS
PE
UVC 1
4 3 2 1
1 2 3
5222
230 V
BM
UVS
PE
BM
PEN1
N1
54 24 PE
GB
F
NL
I
E
Pilot burner = UVS/main burner = ionization:
N1
FU
Parameter A002 ≥ 5 µA. Parameter I004 = 5.
51 21
N1
BM
2
1
23
PE
123
UVS
UVS
230 V
PE
5222
BM
Pilot burner = UVC/main burner = UVC:
Parameter I004 = 2.
N1
2
1
51 21
BM
22
23
4
3
UVC 1
PE
BM
2
1
4 3
UVC 1
2 1
N1
54 24 PE
PEN1
Pilot burner = UVC/main burner = ionization:
Parameter I004 = 7.
2
1
51 21
BM
22
23
4
3
2
UVC 1
PE
BM
1
N1
54 24 PE
PEN1
Pilot burner = UVC/main burner = UVS:
Parameter A002 ≥ 5 µA. Parameter I004 = 8.
22
N1
2
1
51 21
BM
23
4
3
2
UVC 1
UVS
230 V
PE
52
BM
1
1 2
UVS
3
PEN1
N1
54 24 PE PE

Adjustment

In certain cases, it may be necessary to change the parameters set at the factory. Using the separate software package BCSoft and an opto-adapter, it is possible to modify parameters on the BCU, such as the safety time or the behaviour in the event of a flame failure. 1 Set the parameters using BCSoft.
For reasons of network security, it is not possible to access the unit via the network using BCSoft.
The software package and the opto-adapter are
available as accessories.
Changed parameters are saved on the integrated parameter chip card.
The factory settings are secured with a program-
mable password. The default password is 1234. We recommend changing the password upon commissioning.
Hardware parameters (e.g. type of flame con­trol or type of air actuator) are set via interface parameters I004 to I074.
▷ Once parameters have been changed, a check
is automatically carried out to ensure that the changes have been accepted and the display shows
Press the Reset/Information button on theBCU.
.
V
FY
The first parameter value that was changed is
displayed.
Press the Reset/Information button again.
3
▷ The next parameter value that was changed is
displayed.
▷ Repeat this procedure until
is displayed.
Y
GB-13
GB
F
NL
I
E
3 Press the Reset/Information button on theBCU
to confirm the new parameter settings.

Commissioning

During operation, the 7-segment display shows the program status:
Standby
00
Delay
H0
Approaching minimum capacity
A
Cooling
A0
Fan run-up time
01
Pre-ventilation
A1
Approaching maximum capacity
A
Delay
H1
Pre-purge
P0
Pre-purge
P1
Approaching ignition capacity
A
Valve check Safety time 1 t
02
Safety time 1 t
A2
Flame proving period 1 t
03
Flame proving period 1 t
A3
Burner 1 operation
04
Burner 1 operation
A4
Burner 2 waiting time
05
Delay
A5
Delay time during burner 2 waiting time
H5
Safety time 2 t
06
Safety time 2 t
A6
Flame proving period 2 t
07
Flame proving period 2 t
A7
Burner 2 operation
08
Burner 2 operation
A8
Delay
H8
Device Off
––
Data transfer (programming mode) (blinking dots) Manual mode
0.0.
Low NOx operation in program stepXX
XX
High temperature operation in program
XX
stepXX
Units with SafetyLink function (BCU with bus module BCM..S1) may only be commissioned using BCSoft. Further information can be found in Technical Information bulletin BCU46x or BCU480.
SA1
SA1
SA2
SA2
FS1
FS1
FS2
FS2
WARNING
Risk of explosion! Check the system for tightness before commissioning. Do not start the BCU until the parameter settings and wiring are correct and the faultless processing of all input and output signals complies with the local standards.
1 Switch on the system.
▷ The display shows
Switch on the BCU by pressing the On/Off but-
ton.
The display shows
The display blinks and indicates
table fault message is signalled. Reset the BCU
by pressing the Reset/Information button.
▷ The display blinks without indicating “E”. A warn-
ing message is signalled. Once the fault has been
eliminated, the display stops blinking and the
BCU continues the program run.
BCU 460..F0 3 Apply the start-up signal to terminal1.
The display shows
The display shows 02. The gas valves open and
the burner ignites. Safety time1 starts to elapse.
▷ The display indicates 03 during flame proving
period1.
▷ The display shows
tion.
BCU 46x..F1, BCU 46x..F3
▷ If the air actuator is activated externally for cool-
ing in the start-up position, the display indicates
.
A0
3 Apply the start-up signal to terminal1.
▷ The display indicates 01 or A1 if the air actua-
tor has been activated.
▷ The display indicates 02 or A2 if the air actua-
tor has been opened. The gas valves open and
the burner ignites. Safety time1 starts to elapse.
The display indicates 03 during flame prov-
ing period1 or A3 if the air actuator has been
opened.
▷ The display indicates 04 or A4 if the air actua-
tor has been opened. The burner is in operation.
BCU 480..F1/F3
▷ If the air actuator is activated externally for cool-
ing in the start-up position, the display indicates
.
A0
3 Apply the start-up signal to terminal1.
▷ The display indicates 01 or A1 if the air actua-
tor has been opened.
▷ The display indicates 02 or A2 if the air actua-
tor has been opened. The gas valves open, the
pilot burner (burner1) ignites and safety time1
starts to elapse.
The display indicates 03 during flame prov-
ing period1 or A3 if the air actuator has been
opened.
GB-14
.
––
.
00
.
01
. The burner is in opera-
04
EXXX
. A reset-
GB
F
NL
I
E
....S X
The display indicates 04 or A4 if the air ac
tuator has been opened. The pilot burner is in operation.
▷ The display indicates 06 or A6 if the air actua-
tor has been opened. The main burner (burner2) ignites and safety time2 starts to elapse.
The display indicates 07 during flame prov-
ing period2 or A7 if the air actuator has been opened.
The display indicates 08 or A8 if the air ac
tuator has been opened. The main burner is in operation. The controller enable signal has been issued.
▷ After 3 seconds in this position, the μA value for
­the flame signal
XX.X
is displayed instead of the
program status.
3 Press the Reset/Information button for 1s.
The display shows
The BCU will start the second stage of the burner.
▷ The display runs to
After 3 seconds in this position, the μA value
S. . .3.
. .0.4.
(step3).
.
for the flame signal is displayed instead of the
-
program status.
BCU 46x/LM..F1/F3  Press the Reset/Information button for 1s.
The display shows
S. . .1.
(step1).
▷ The BCU will start to purge the burner.

Manual mode

▷ For adjustment of the burner control unit or for
fault-finding.
In Manual mode, the BCU operates indepen­dently of the status of the inputs for start-up signal (terminal1), external air valve control (terminal4) and remote reset (terminal2). The function of the controller enable/emergency stop input (terminal35) is retained.
▷ Manual mode is terminated by switching off the
BCU or in the event of a power failure.
Parameter A067 = 0: Manual mode unlimited in time.
Parameter A067 = 1: the BCU will terminate Manual mode 5minutes after the last time the Reset/Information button is pressed. It switches to the start-up position/standby (display
1 Switch on the BCU while holding the Reset/
Information button. Hold the Reset/Information button until 4dots start to flash in the display.
00
The display shows
WARNING
Risk of explosion! The pre-purge time is not includ­ed in the program. Maintain state P.0. until the com­bustion chamber has been adequately ventilated.
3 Press the Reset/Information button for 1s.
The display shows The BCU will start the first stage of the burner.
The display runs to
than a 0 appears if the air actuator is activated).
After 3 seconds in this position, the μA value for the flame signal is displayed instead of the program status.
4 Press the Reset/Information button for 1s.
).
The display shows
The BCU will start the second stage of the burner.
The display runs to After 3 seconds in this position, the μA value for
the flame signal
. .P.0.
.
S. . .2
(step2).
. .0.2.
S. . .3.
. .0.4. ( . .A.4.
XX.X
. .0.3.
or
(an A rather
(step3).
).
is displayed instead of the
program status.
....
Air actuator control: The air actuator is activated externally (parameter A048 = 0). 5 Press the Reset/Information button for 1s.
If the Reset/Information button is pressed briefly, the current step in Manual mode is shown and
S.X.X.X.
is displayed.
If the Reset/Information button is pressed for >1s, the BCU proceeds to the next program step.
The display shows The BCU will open the air actuator.
Each time the button is pressed, the air actuator is closed or opened again.
The air actuator opens under program control (parameter 48 = 1, , 3, 4, 5 or 6).
The air actuator opens under program control
S . .4
(step4).
with valves V1, V2, V3 or when it reaches the operating position.
5 Press the Reset/Information button for 1s.
▷ The display shows
S. . .4
(step4).
▷ The BCU will start the shut-down procedure.
BCU 460/LM..F0  Press the Reset/Information button for 1s.
The display shows
S. . .2.
(step2).
▷ The BCU will start the first stage of the burner.
. .0.2.
▷ The display runs to
or
. .0.3.
.
BCU 480  Press the Reset/Information button for 1s.
The display shows
S. . .1.
(step1).
The BCU will start to purge the burner. The display shows
. .P.0.
.
GB-15
GB
F
NL
I
E
WARNING
Risk of explosion! The pre-purge time is not includ­ed in the program. Maintain state P.0. until the com­bustion chamber has been adequately ventilated.
3 Press the Reset/Information button for 1s.
The display shows The BCU will start the pilot burner.
The display runs to
appears if the air actuator is activated).
▷ After 3 seconds in this position, the μA value for
the flame signal program status.
4 Press the Reset/Information button for 1s.
The display shows
The BCU will start the first stage of the main
burner.
The display runs to After 3 seconds in this position, the μA value for
the flame signal program status.
Air actuator control:
The air actuator is activated externally
(parameter A048 = 0). 5 Press the Reset/Information button for 1s.
The display shows The BCU will open the air actuator. The display shows
Each time the button is pressed, the air actuator is closed or opened again.
▷ Press the On/Off button to switch the unit off.
The air actuator opens under program control
(parameter 48 = 1, , 3, 4, 5 or 6).
The air actuator opens under program control
with valves V1, V2, V3, V4 or when it reaches the operating position.
If the Reset/Information button is pressed for 1s, the display shows starts the shut-down procedure.
S. . .2.
(step2).
. .0.4.
(an A rather than a 0
XX.X
is displayed instead of the
S. . .3.
(step3).
. .0.8.
.
XX.X
is displayed instead of the
S. . .4.
(step4).
. .A.4.
.
S. . .4.
(step4) and the BCU

Assistance in the event of malfunction

DANGER
To avoid harm to persons and damage to the unit,
please observe the following:
Electric shocks can be fatal! Before working
on possible live components, ensure the unit is disconnected from the power supply.
Fault-clearance must only be undertaken by
authorized trained personnel!
▷ Faults may be cleared only using the measures
described below.
If the BCU does not respond even though all faults have been remedied: remove the unit and return it to the manufacturer for inspection.
In the event of a fault lock-out, the fault signalling contact closes, the display blinks and shows the current program step. The gas valves are disconnected from the electrical power supply.
After a fault lock-out, the BCU must be reset
manually using the button on the front panel or the remote reset input (terminal2).
The BCU cannot be reset by mains failure (non-
volatile fault lock-out). The fault signalling contact does, however, open as soon as the mains volt­age fails.
? Faults ! Cause
• Remedy
? The 7-segment display does not light up. ! Mains voltage is not applied.
Check the wiring, apply mains voltage (see type
label).
0 1E
A 1E
E 01
? The display blinks and indicates
!
The BCU has detected an incorrect flame signal
or
E A1
.
without the burner having been ignited (extrane­ous signal).
Direct the UV sensor exactly at the burner to be
monitored.
!
The UV tube in the UV sensor is defective (service
life ended) and issues a continuous flame signal.
Replace the UV tube, see UV sensor operating
instructions.
!
Flame signal through conductive ceramic insula-
tion.
Increase value of parameterA001 in order to
adapt the switch-off threshold of the flame ampli­fier for burner1.
GB-16
GB
F
NL
I
E
0 2E
A 2E
? Start-up – no ignition spark – the display
blinks and indicates
! The ignition cable is too long.
Shorten it to 1 m (max. 5 m).
! Gap between spark electrode and burner head
is too great.
Adjust gap to max. 2mm.
!
Ignition cable has no contact in the terminal boot.
Screw the cable on firmly.
!
Ignition cable has no contact in the ignition trans-
former.
Check the connection.
! Ignition cable has short-circuited to ground.
Check installation, clean the spark electrode.
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer for inspection.
? Start-up without flame – no gas supply – the
display blinks and indicates
! A gas valve does not open.
Check the gas pressure. Check voltage supply to the gas valve.
! There is still air in the pipe, e.g. after installation
work has been carried out or if the system has not been in operation for a long period.
“Purge” the pipeline and reset the BCU.
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer for inspection.
E 02
or
E A2
E 02
.
or
E A2
.
! Terminal boot not properly connected to flame
rod.
! Gas/air ratio incorrect. !
Flame not contacting burner ground as the result
of excessively high gas or air pressure.
! Burner or BCU not (adequately) grounded. ! Short-circuit or discontinuity on the flame signal
cable.
! Soiled UV sensor. ! UV sensor wiring is defective.
Remedy fault.
0 5E
?
The display blinks and indicates
A 5E
E 05
E A5
or
! The BCU has detected an incorrect flame sig-
nal without burner2 (main burner) having been ignited (extraneous signal).
Direct the UV sensor exactly at burner 2 to be
monitored.
!
The UV tube in the UV sensor is defective (service
life ended) and issues a continuous flame signal.
Replace the UV tube, see UV sensor operating
instructions.
! Flame signal through conductive ceramic insula-
tion.
Increase value of parameterA002 in order to
adapt the switch-off threshold of the flame ampli­fier for burner2.
0 8E
A 8E
.
0 2E
A 2E
?
Start-up– flame burning – nevertheless, the
display blinks and indicates the pilot burner/burner (burner1) or
E 07
on the main burner (burner).
! Flame failure on start-up.
Read off the flame signal.
If the flame signal is lower than the switch-off threshold for the flame signal from burner1 (pa­rameterA001) or burner2 (parameterA002), this may be attributable to the following causes:
!
The set value for the cut-off sensitivity is too high.
!
Short-circuit on the flame rod as the result of
soot, dirt or moisture on the insulator.
0 3E
A 3E
0 6E
A 6E
E 02
or
0 7E
E 03
E 06
A 7E
on
or
! Flame rod not correctly positioned at the flame
edge.
? Operation – flame burning – burner inter-
rupted– the display blinks and indicates
E 08
E A8
or
! Flame failure during operation or during delayed
controller enable.
Read off the flame signal, see page25 (Read-
ing off the flame signal, fault messages and pa­rameters).
If the flame signal is lower than the switch-off threshold for the flame signal from burner2 (pa­rameterA002), this may be attributable to the following causes:
!
The set value for the cut-off sensitivity is too high.
!
Short-circuit on the flame rod as the result of
soot, dirt or moisture on the insulator.
.
! Flame rod not correctly positioned at the flame
edge.
! Gas/air ratio incorrect. !
Flame not contacting burner ground as the result
of excessively high gas or air pressure.
! Burner or BCU not (adequately) grounded.
GB-17
GB
F
NL
I
E
! Short-circuit or discontinuity on the flame signal
cable.
! Soiled UV sensor.
Remedy fault.
1 0E
? The display blinks and indicates ! Actuation of the remote reset input is faulty. ! Too many remote resets. More than 5resets
have been conducted within the last 15minutes, either automatically or manually.
! Consecutive fault caused by a previous fault
whose actual cause has not been remedied.
Pay attention to previous fault messages.
Remedy cause.
▷ The cause will not be remedied by performing a
reset every time a fault lock-out occurs.
Check whether remote reset complies with
standards (EN746 allows resetting only under supervision) and correct if necessary.
▷ The BCU may only be reset manually under su-
pervision.
Press the Reset/Information button on theBCU.
E 10
.
1 1E
? The display blinks and indicates ! Too many restarts for burner1. More than 5re-
starts initiated within the last 15minutes.
Check burner settings.
Ensure that the flame signal is above the switch­off threshold during operation.
Check the settings for capacity control during
operation.
Press the Reset/Information button on theBCU.
E 11
.
1 2E
? The display blinks and indicates ! Too many restarts for burner2. More than 5re-
starts initiated within the last 15minutes.
Check burner settings.
Ensure that the flame signal is above the switch­off threshold during operation.
Check the settings for capacity control during
operation.
Press the Reset/Information button on theBCU.
E 12
.
2 1E
? The display blinks and indicates ! Inputs 40 and 41 are activated simultaneously.
E 21
.
Check input 41.
Input 41 may only be activated if the valve is open.
Check input 40.
▷ Input 40 may only be activated if the valve is in
the position for ignition capacity.
2 2E
? The display blinks and indicates ! The butterfly valve position is not constantly sig-
nalled back to theBCU.
Check the wiring and ensure that the position for
max. capacity/ignition capacity of the butterfly valve is constantly signalled back via terminals 41 and 42.
3 0E
? The display blinks and indicates ! Abnormal data change in the parameters set for
theBCU.
Reset the parameters to their original values using
the BCSoft software.
Establish the cause of the fault to avoid repeat
faults.
Ensure that the cables have been installed prop-
erly– see page5 (Cable selection and instal­lation).
If the measures described above do not help,
remove the unit and return it to the manufacturer for inspection.
3 1E
3 2E
? The display blinks and indicates ! Supply voltage too low or too high.
Operate the BCU in the specified mains voltage
range (mains voltage +10/-15%, 50/60Hz).
! An internal device error occurred.
Remove the unit and return it to the manufacturer
for inspection.
3 3E
? The display blinks and indicates ! Faulty parameterization.
Check parameter settings using BCSoft. ! An internal device error occurred.
Remove the unit and return it to the manufacturer
for inspection.
GB-18
E 22
.
E 30, E 31
E 32
.
E 33
.
.
GB
F
NL
I
E
43E
? The display blinks and indicates ! Faulty actuation of the air valve. ! Voltage is applied to the air valve outputs
(65–67).
Check the wiring and ensure that the voltage
outputs and inputs have the same polarity and are not reversed.
! Fuse F3 defective.
Replace fuse F3. ! An internal device error occurred.
Replace the power module.
Remove the unit and return it to the manufacturer
for inspection.
E 34
.
53E
? The display blinks and indicates ! Bus module and control unit are incompatible.
Check the bus system and PLC for compatibility. ! Bus module does not support the selected func-
tion.
Check the setting of parameterA075.
E 35
.
Check parameterA056 (Measurement timeVp1)
and change using BCSoft.
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer for inspection.
4 1E
? The display blinks and indicates ! The downstream gas solenoid valve (V2, V3 or
V4) is leaking.
Check the downstream solenoid valve. ! The gas pressure switch DGpu/2 for the tightness
test has been set incorrectly.
Check the inlet pressure.
Set DGpu/2 to the correct pressure.
Check the wiring. ! The test period is too long.
Check parameterA056 (Measurement timeVp1)
and change using BCSoft.
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer for inspection.
E 41
.
4 4E
3 6E
? The display blinks and indicates ! Voltage is applied to the device outputs.
Check the wiring and ensure that the voltage
outputs and inputs have the same polarity and are not reversed.
! Fuses defective.
Replace the fuses. ! An internal device error occurred.
Replace the power module.
Remove the unit and return it to the manufacturer
for inspection.
E 36
.
4 0E
? The display blinks and indicates ! The gas solenoid valve V1 is leaking.
Check the gas solenoid valve V1. ! The gas pressure switch DGpu/2 for the tightness
test has been set incorrectly.
Check the inlet pressure.
Set DGp
Check the wiring. ! The test pressure between V1 andV2 has not
decreased.
Check the installation. ! The test period is too long.
/2 to the correct inlet pressure.
u
E 40
.
? The display blinks and indicates ! Faulty pressure switch signal.
Check the wiring and setting of the pressure
switch/gas valve.
5 1
? The display blinks and indicates ! Interruption of signal at the “Safety interlock/
Controller enable/Emergency stop” input (ter­minal35).
Check voltage supply to terminal35.
5 2
? The display blinks and indicates ! The BCU is permanently reset by remote reset.
Check remote reset activation (default termi-
nal=2 or bus).
To reset the unit, only apply voltage to the remote
reset terminal for approx. 1second.
E 44
51
52
.
.
.
GB-19
GB
F
NL
I
E
5 3
8 9E
9 4E
9 5E
9 6E
? The display blinks and indicates ! The time between two starts is less than the
min.time (timingcycle).
Comply with max. number of start-ups (n) per
minute:
t
SA
[s] Ignition transformer ID number [n/min.]
3 5 6
10 3
3 5 2
10 1
3 5 4
10 2
3 5 3
10 2
Device type
BCU..Q1
34340581
BCU..Q2
34340582
BCU..Q3
34340583
BCU..Q8
34340584
BCU..W1
34340585
BCU..W2
34340586
BCU..W3
34340587
BCU..W8
34340588
53
Max.
number
.
6
3
6
4
5 4
? The display blinks and indicates ! Faulty feedback signal of the control element
position for ignition capacity.
Check wiring from central actuator to BCU (ter-
minal39).
Check whether parameter I072=13 (LDS ignition
position check) and A089=2.
54
.
5 7E
? The display blinks and indicates ! Faulty actuation of the input for high tempera-
ture operation. The BCU is prompted to go into menox mode, even though there is no signal for high temperature operation (>750°C).
Check the wiring.
E 57
.
9 7E
? The display indicates
E 97, E 98
! System fault – the BCU has performed a safety
shut-down. The cause may be a unit defect or abnormal EMC influence.
Ensure that the ignition cable has been installed
properly– see page5 (Cable selection and installation).
Ensure that the EMC regulations for the sys-
tem are satisfied– particularly for systems with frequency converters – see page 5 (Cable selection and installation).
Reset the unit.
Disconnect the burner control unit from the mains
supply and then switch it on again.
Check mains voltage and frequency.
If the measures described above do not help, the
unit has probably suffered a hardware defect– remove the unit and return it to the manufacturer for inspection.
or
E 99
9 8E
.
9 9E
E 89, E 94, E 95, E 96
9 1E
? The display blinks and indicates ! Flame amplifier is defective.
Check the wiring. ! Fuses defective.
Replace the fuses.
If the measure described above does not help,
the unit has probably suffered a hardware de­fect– remove the unit and return it to the manu­facturer for inspection.
E 91
.
,
8 0E
? The display blinks and indicates ! Burner 1 flame amplifier is defective.
Remove the unit and return it to the manufacturer
for inspection.
E 80
.
8 5E
? The display blinks and indicates ! Burner 2 flame amplifier is defective.
Remove the unit and return it to the manufacturer
for inspection.
E 85
.
9 2E
? The display blinks and indicates ! DC voltage is supplied to the inputs. ! The signal inputs and L are supplied with different
phases of a three-phase current system.
Check the wiring and ensure that the device and
the inputs are supplied with the same phase.
9 4E
? The display blinks and indicates ! The inputs are supplied with different phases of
a three-phase current system.
GB-20
E 92
E 94
.
.
GB
F
NL
I
E
Check the wiring and ensure that the device and
the inputs are supplied with the same phase.
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer for inspection.
9 7E
? The display blinks and indicates ! No PCC.
Insert compatible PCC. ! Contact problems on the power module.
Remedy contact problems. ! Power module is defective.
Replace power module.
If the measures described above do not help, the
unit has probably suffered a hardware defect– remove the unit and return it to the manufacturer for inspection.
E 97
.
AE
? The display blinks and indicates ! No “Minimum capacity reached” signal from
actuator.
Check the butterfly valve and the function of the
limit switches in the actuator.
Check the wiring.
Check the actuator.
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer for inspection.
E A
.
AE
EE
? The display blinks and indicates ! Internal communication with bus module has
suffered a fault.
Connected control elements must be equipped
with protective circuits in accordance with the manufacturer’s instructions.
This prevents high voltage peaks which can
cause malfunctioning of the BCU.
Use interference-suppressed terminal boots
(1kΩ).
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer for inspection.
! Bus module is defective.
Replace the bus module.
E E
.
0E
? The display blinks and indicates ! Faulty connection to master.
Check the connection.
Check whether the slave is configured in the
master.
E 0
.
1E
? The display blinks and indicates ! No “Maximum capacity reached” signal from
actuator.
Check the butterfly valve and the function of the
limit switches in the actuator.
Check the wiring.
Check the actuator.
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer for inspection.
AE
? The display blinks and indicates ! No “Ignition capacity reached” signal from actua
tor.
Check the butterfly valve and the function of the
limit switches in the actuator.
Check the wiring.
Check the actuator.
E A
E A
.
? The display blinks and indicates ! Incorrect K-SafetyLink address.
Check that the set address matches the address
configured for K-SafetyLink.
Only use addresses in the range of 0x001
to0xFEF.
2E
? The display blinks and indicates ! Plausibility check failed, K-SafetyLink configura-
tion invalid.
.
Check SafetyLink configuration in BCSoft and
transfer to the device again.
-
4E
? The display blinks and indicates ! K-SafetyLink awaiting configuration.
GB-21
E 1
E 2
E 4
.
.
.
GB
F
NL
I
E
Create a SafetyLink project with BCSoft and
transfer the configuration to the device.
1E
5E
? The display blinks and indicates ! Slave configuration check not executed or failed.
Start and complete the verification of the con-
figuration in the SafetyLink master assigned to the slave using BCSoft.
E 5
.
7E
? The display blinks and indicates ! Incompatible or defective bus module.
Replace bus module with a functional device (for
K-SafetyLink).
E 7
.
8E
? The display blinks and indicates ! The unit is accessed by two or more devices
with the same address.
Check the configuration in BCSoft.
▷ Each device must have a unique address.
Remove any device with an incorrect address
configuration from the network or reconfigure it.
Check the correct assignment of the master and
slave devices using the verification procedure.
E 8
.
9E
? The display blinks and indicates ! The unit is accessed by one or more devices
with unknown addresses.
Check the configuration in BCSoft.
Each slave may only be assigned to one master.
Remove any device with an incorrect address
configuration from the network or reconfigure it.
Check the correct assignment of the master and
slave devices using the verification procedure.
CCE
E 9
.
? The display blinks and indicates ! No input signal for the valve proof of closure
switch (POC) during standby.
Check the wiring.
▷ Mains voltage must be supplied to the BCU (ter-
minals36, 37 and 38) if the valve is closed and no voltage is to be applied if the valve is open.
Check that the proof of closure switch and valve
function perfectly, replace defective valves.
E 1
.
8E
? The display blinks and indicates ! The BCU is receiving no information as to wheth-
er the POC switch contact is still open.
Check the wiring.
During start-up, mains voltage must be supplied to the BCU (terminals36, 37 and 38) if the valve is closed and no voltage is to be applied if the valve is open.
Check that the proof of closure switch and valve
function perfectly, replace defective valves.
E 8
.
0E
? The display blinks and indicates ! The “no flow” state check of the air pressure
switch has failed.
Check the function of the air pressure switch.
▷ Before the fan is switched on, there must be no
high signal at the input for air monitoring (ter­minals36/37) when air monitoring is activated.
E 0
.
1E
? The display blinks and indicates ! The operating check of the air pressure switch
has failed. The air monitor has not switched after activation of the air supply.
Check the air monitor wiring.
Check the air pressure switch setpoint.
Check the function of the fan or air supply.
E 1
.
? The display blinks and indicates ! Incorrect or defective parameter chip card (PCC).
Only the intended parameter chip card is to be
used.
Upload the current parameter settings again.
Replace defective parameter chip card.
E CC
.
PE
? The display blinks and indicates ! The input signal (terminal37) for the air pressure
switch has dropped out during pre-purge.
Check the air supply during the purging process.
GB-22
E P
.
GB
F
NL
I
E
Check the electrical wiring of the air pressure
switch.
Check voltage supply to terminal37.
Check the air pressure switch setpoint.
2E
6E
? The display blinks and indicates
E 4, E 5, E 6, E 7
! The input signal for the air pressure switch has
dropped out during start-up/operation at pro­gram stepX (02to08).
!
Failure of the air supply at program stepX
Check the air supply.
Check the air pressure switch setpoint.
3E
7E
or
E 8
4E
5E
8E
E 2, E 3
.
.
0
? The display blinks and indicates ! No connection established between BCU
andPLC.
Check the wiring.
Check the PLC program to ensure that the net-
work name and IPconfiguration of the BCU are valid.
Switch on the PLC. Or ? A bus fault is indicated on the automation
system.
! The PROFIBUS DP data traffic has suffered a
fault.
! Bus cable interrupted.
Check cable. ! Incoming and outgoing bus cables confused in
the plug.
Check the wiring. ! A and B cables confused.
Check the wiring. ! Terminal resistors connected incorrectly.
Switch on the terminal resistors on the first and
last subscriber in the segment and switch them off for all other subscribers.
! Incorrect PROFIBUS address set.
Correct the address setting – switch the unit off
and then on again to save the address.
! Bus cables too long.
Reduce cable length or baud rate – see
page14 (Commissioning).
If the transfer rate is reduced, remember that this will increase the signal running times to and from the individual units.
0
.
! Poor shielding.
Check whether the shield is connected to the
shield clips in the PROFIBUSDP plugs in full and over a wide area.
! Poor equipotential bond.
Check whether the PROFIBUS DP shield is con-
nected at all points to the same ground potential via the grounding system of the units.
If necessary, an equipotential bonding cable must
be laid.
▷ If faults occur sporadically in the PROFIBUSDP
,
system, and are only indicated briefly in the bus master, the following points in particular should be checked:
– Terminal resistors, – Shielding, – Cable lengths/routes, – Equipotential bond, – Use of interference-suppressed spark electrode
terminal boots (1kΩ).
For information on planning and the structure of a Profinet network and the components to be used (e.g. cables, lines and switches), see www.profibus.com or the instructions for the automation system.
1
? The display blinks and indicates
▷ Fault occurs on devices with fieldbus communi-
cation with address check (A080=1) only.
! An invalid or incorrect address has been set on
the bus module.
Assign the correct address (001toFEF) to the
bus module.
2
? The display blinks and indicates ! The bus module has received an incorrect con-
figuration from thePLC.
Check whether the correct GSD file was imported.
3
? The display blinks and indicates
▷ Fault occurs on devices with fieldbus communi-
cation with address check (A080=1) only.
! The BCU has been assigned an invalid network
name or has not been assigned a network name in thePLC.
1
2
3
.
.
.
GB-23
GB
F
NL
I
E
Assign a network name corresponding to the
F1
F2
F3
default network name (bcu-460-xxx) or use the default name as a suffix of an individually as­signed name in the following form: “individual­partofnamebcu-460-xxx”.
“xxx” stands for the address set on the device
(e.g. 4A5).
4
? The display blinks and indicates ! PLC in STOP position.
Check whether the PLC can be started.
4
.
TO
Replacing the fuse
The device fuses F1, F2 and F3 can be removed
for inspection.
▷ The fuses are located under the power module.
CAUTION
BCU..E0 and BCU..E1 do not have the same power supply connection. Always replace fuse F1 or F2 such that the required power supply is ensured.
F1 = BCU..E1: power supply via L1.
F = BCU..E0: power supply via safety in­terlocks.
Disconnect the system/BCU from the electrical
power supply.
Open the BCU.
Remove the power module.
? The display blinks and indicates ! The ambient temperature is too high for the BCU
(excessive temperature).
▷ The display disappears as soon as the tempera-
ture has dropped to the specified setpoint.
OT
.
TU
2E
6E
UT
.
E 0, E 1
E 9
or
3E
7E
.
? The display blinks and indicates ! The ambient temperature is too low for the BCU
(insufficient temperature).
▷ The display disappears as soon as the tempera-
ture has risen to the specified setpoint again.
0E
4E
1E
5E
8E 9E
? The display blinks and indicates
E 2, E 3, E
! The signal for monitoring the min. gas pressure
(terminals36, 37 and 38) has dropped out at program stepX (00to09).
Check the wiring.
Check the gas pressure.
4, E 5, E 6, E 7, E 8
Remove fuse F1, F2 or F3 and check for correct
functioning.
F3
F2
F1
,
When replacing the fuse, use only the approved
fuse type: F1, F2, F3: T 3.15A H, pursuant to IEC 60127-2/5.
GB-24
GB
F
NL
I
E
Reading off the flame signal, fault messages and parameters
▷ If the unit is switched on, information about the
flame signal intensity, the last 10event messages (e.g. Power ON, error E002) and the parameter values can be read off by repeatedly pressing the Reset/Information button.
Display Information
F1 F2
H0
to
H9 001
to
999
* Only on BCU 480
Press the Reset/Information button for approx.
2s until the display indicates
Release the button. The display indicates the
flame signal intensity inµA.
Press the Reset/Information button again for
2s to go to the next item of information (event message, parameter value). Each time the button is released, the corre-
sponding event message or parameter value is displayed.
▷ To go to one of the last event messages or to a
parameter more quickly, hold the Reset/Infor mation button pressed down for longer (≥2s).
▷ If the button is pressed briefly, the display indi-
cates what parameter number is currently being displayed.
The normal program status is displayed again
approx. 60seconds after the last time the but­ton is pressed.
▷ For the parameters and the corresponding val-
ues, see Technical Information bulletins BCU46x and BCU 480.
Flame signal intensity: Burner 1
*
Burner 2* Last event message to tenth to last event message Parameter 001 to parameter 999
F1
.

Parameters and values

Application parameters
Parameter name
Param­eter No.
Parameter value
Switch-off threshold1
A001
2 – 20 = µA
Switch-off threshold2
A002
2 – 20 = µA
Flame simulation check
0 = In standby
A003
1 = Upon start-up
High temperature operation
0 = Off 2 = Burner 1 UVS Burner 2 UVS
A006
3 = Continuous operation 6 = Burner 1 UVS Burner 2 ionization
Burner 1 start-up attempts
1 = 1 start-up attempt
A007
2 = 2 start-up attempts 3 = 3 start-up attempts
Burner 2 start-up attempts
1 = 1 start-up attempt
A008
2 = 2 start-up attempts 3 = 3 start-up attempts
Restart
0 = Off 1 = Burner 1 2 = Burner 2
A009
3 = Burner 1 and burner 2 (pilot and main burners) 4 = Max. 5 times in 15 min. for burner1 5 = Max. 5 times in 15 min. for burner2
-
6 = Max. 5 times in 15 min. for burners1 and2 Low air pressure protection delay
0 = Off
A016
1 = On
Safety time operation
A019
0; 1; 2; 3; 4 = Time in seconds
Pre-ventilation/flameless
A028
0 – 250 = Time in seconds
Cooling priority
0 = Start-up overrides cooling
A029
1 = Cooling overrides start-up
Staged cooling
0 = Start-up overrides cooling
A030
1 = Stage 2 via signal at terminal5 2 = After delay time
Staged cooling delay
A031
0 – 6000 = Time in seconds
Pre-purge time tPV
A034
0 – 6000 = Time in seconds
Pre-ventilation
A036
0 – 250 = Time in seconds
Over-run time
A039
0 – 60 = Time in seconds
Running time selection 0 =
Off; position check
1 =
A041
On; for min./max. capacity
2 =
On; for maximum capacity 3 = On; for minimum capacity Running time
A042
0 – 250 = Time in seconds
GB-25
GB
F
NL
I
E
Param­eter No.
A043
A044
A048
A049
A050
A051
A052
A056
A059
A060
A061
A062
A064
A067
A074
Parameter name Parameter value
Over-run
0 = Off 1 = Post-ventilation 2 = Low fire; actuator feedback 3 = Low fire; time-bound
Controller enable signal delay timetRF 0 – 250 = Time in seconds Air actuator control 0 =
Opens on external activation
1 =
Opens with gas stage1
2 =
Opens with gas stage2
3 =
Controller enable op./standby
4 =
Opens with V4 burner 1
5 =
Controller enable following operating signal
6 =
Opens with gas stage3 Air actuator can be activated externally on start-up 0 =
Cannot be activated
1 =
Can be activated externally Air actuator in the event of fault 0 =
Cannot be activated
1 =
Can be activated externally Valve proving system
0 = Off
1 =
Tightness test before start-up
2 =
Tightness test after shut-down 3 = Tightness test before start-up and after
shut-down 4 = POC function Relief valve (VPS)
0 = V0
1 = V1
2 = V2 3 =
V3
4 = V4 5 = V5
Measurement time Vp1 0 – 3600 = Time in seconds Valve opening time 1 tL1 2 – 25 = Time in seconds POC test period
=
Time in seconds
0 – 250
Minimum operating time tB
0 – 6000
=
Time in seconds
Minimum pause time tBP
0 – 3600
=
Time in seconds
Flameless operation
0 = Upon next burner start
1 = Immediate burner start
2 = Immediate switchover
Operating time in Manual mode
0 = Unlimited 1 = 5 minutes
Combustion mode
0 = Flame mode
1 = menox
2 = HT without ignition 3 =
HT without burner1 start 4 =
FLOX
Parameter name
Param­eter No.
Parameter value
Air actuator (bus) 0 = Of
f
1 = MAX to MIN
2 = MAX to LOW FIRE
A075
3 =
MAX to IGNITION
4 = MAX to MIN; red. purge flow 5 = MAX to IGN; r
ed. purge flow Function of V5 0 = Of
f
1 = Flame mode
A076
2 = Flameless operation 3 =
Operation Auxiliary gas function 0 = Of
f
1 = Flame mode
A077
2 = Flameless operation 3 =
Operation Burner application
0 =
Burner 1
1 =
Burner 1 with pilot gas
2 =
Burner 1 & burner 2 3 =
Br. 1 & Br. 2 with pilot gas 4 =
Two-stage burner 1
5 =
A078
Br. 1 & two-stage br.2
11 =
menox 1/0 and burner 1/0
12 =
menox 1/0 and burner L/H/O
13 =
menox 1/0 with 2 gas paths
14 = menox L/H/O with 2 gas paths
21 =
CBFF flame
22 =
CBFF flame Flox
Gas pilot
0 = With shut-down
A079
1 = In continuous operation
2 = With shut-down & restart
Fieldbus communication
0 = Off
A080
1 = With address check
2 = No address check
K” Safety Link
0 =
1 =
Off
On
A081
Safety interlocks (bus) 0 =
Off
1 =
Via FS bus
2 =
A085
Via terminal 3 =
Via NFS bus 4 =
Via FS bus or terminal 5 =
Via FS bus and terminal FLOX800 (bus) 0 =
Off
1 =
Via FS bus
2 =
A086
Via terminal 3 =
Via NFS bus 4 =
Via FS bus or terminal 5 =
Via FS bus and terminal
GB-26
GB
F
NL
I
E
Parameter name
Param­eter No.
Parameter value
Purge (bus)
0 =
Off
1 =
A087
Via FS bus
2 =
Via terminal
3 =
Via NFS bus
4 =
Via NFS, FS bus or terminal
5 =
Via NFS, FS bus and terminal
High temperature operation (bus)
0 =
Off
1 =
Via FS bus
2 =
A088
Via terminal
3 =
Via NFS bus
4 =
Via FS bus or terminal
5 =
Via FS bus and terminal
LDS (bus)
0 =
Off
1 =
Via FS bus
2 =
A089
A093
A094
A095
A096
A097
Via terminal
3 =
Via NFS bus
4 =
Via FS bus or terminal
5 =
Via FS bus and terminal
Pre-ignition time
0 – 5 = Time in seconds
Safety time 1 t
2
15 = Time in seconds
Flame proving period 1 t
0
25 = Time in seconds
Safety time 2 t
2
10 = Time in seconds
Flame proving period 2 t
0
25 = Time in seconds
SA1
SA2
Parameter name
Param­eter No.
Parameter value
Function of sensor 1 0 =
No function
1 =
APS Purge
2 =
APS Stage 1
3 =
APS Purge & Stage 1
4 =
APS Stage 2
5 =
APS Purge & Stage 2
6 =
APS Stage 1 & Stage 2
7 =
APS Purge & Stage1 & Stage2
8 =
APS Flameless
9 =
APS Purge & Flameless
10 =
APS Stage 1& Flameless
11 =
APS Purge&Stage1&Flameless
12 =
APS Stage 2 & Flameless
13 =
APS Purge&Stage2&Flameless
14 =
A101
FS1
FS2
A102
A103
APS Stage 1&2 & Flameless
15 =
APS Purge & Stage1&2 & Flameless
32 =
APS External Low
33 =
APS External Low & Purge
34 =
APS External High
35 =
APS External High & Purge
36 =
APS External Low & High
37 =
APS Ext. Low&High & Purge
48 =
POC V1
49 =
POC V2
50 =
POC V3
51 =
POC V4
52 =
POC V5
53 =
TC
54 =
GPS Flame mode
55 =
GPS Flameless operation
56 =
GPS Operation
Function of sensor 2
See parameter
A101 for parameter values
Function of sensor 3
See parameter
A101 for parameter values
GB-27
GB
F
NL
I
E
Interface parameters
▷ Interface parameters I040 to I099 are set at the
factory and normally do not need to be adjusted.
CAUTION
Changing the default settings of the interface pa­rameters will change the functions of the inputs at terminals 1 to 41 and terminals 85 to 90, see page7 (Connection diagram).
Param­eter No.
I004
I020
I040
I050
I051
I052
I053
I054
Parameter name Parameter value
Flame control
0 = Ionization 1 = UVS 2 = UVC 3 = Ionization 1 and UVS 2 4 = Ionization 1 and UVC 2 5 = UVS 1 and ionization 2 6 = UVC 1 and UVC 2 7 = UVC 1 and ionization 2 8 = UVC 1 and UVS 2
Air actuator
1 = IC 20 2 = IC 40 3 = RBW 4 = Frequency converter 5 = Air valve
Function of terminal 64
0 = Off 1 = Controller enable 2 = V5 3 =
Bus output 1
Contact 80, 81/82 function
0 = Off
1 = Ready signal
2 = Air signal 3 = Purge signal 4 = Cooling air valve 5 = Flue gas valve
6 = Fault signal
7 = Burner 1 operating signal
8 = Burner 2 operating signal
Contact 90, 91/92 function
See parameter
I050 for parameter values
Function of contact 95/96
See parameter
I050 for parameter values
Function of contact 95/97
See parameter
I050 for parameter values
Contact 85/86, 87 function
See parameter
I050 for parameter values
Param­eter No.
Parameter name Parameter value
Function of input 1
0 = Of
1 = Sensor 1
2 = Sensor 2 3 = Sensor 3 4 = Safety interlocks 5 = Air
6 = Cooling air
7 = Air actuator R1
I061
8 = Air actuator R2
9 = Start 1
= Start 2
10 11 = Reset 12 = Purge 13 = LDS 14 = HT 15 = Flame mode 16 = Flameless operation 17 = menox 19 = Auxiliary gas
I062
I063
I064
I065
I066
I067
I068
I069
I070
I071
I072
I073
I074
Function of input 2
See parameter
Function of input 3
See parameter
Function of input 4
See parameter
Function of input 5
See parameter
Function of input 6
See parameter
Function of input 7
See parameter
Function of input 35
See parameter
Function of input 36
See parameter
Function of input 37
See parameter
Function of input 38
See parameter
Function of input 39
See parameter
Function of input 40
See parameter
Function of input 41
See parameter
f
I061 for parameter values
I061 for parameter values
I061 for parameter values
I061 for parameter values
I061 for parameter values
I061 for parameter values
I061 for parameter values
I061 for parameter values
I061 for parameter values
I061 for parameter values
I061 for parameter values
I061 for parameter values
I061 for parameter values
GB-28
GB
F
NL
I
E
P
PZ
PZH
PZL
PDZ
P
xx
M
90°
90°

Legend

pu/2
Ready for operation
Safety interlocks (limits)
HT
High temperature operation
Gas valve
Air valve
Burner
Purge
Controlled air flow
Burner operating signal
Start-up signal (BCU)
Pressure switch for tightness control (TC)
Pressure switch for maximum pressure
Pressure switch for minimum pressure
Differential pressure switch
Input signal depending on parameterxx
Control element with butterfly valve
Tightness control
TC
Half of the inlet pressure
Outlet pressure
p
d
GZL
Valve with proof of closure switch
Input/Output, safety circuit
xx
Optional input
Approaching/checking ignition position
Approaching max. capacity
Checking position for max. capacity
I
Current consumption of sensor/contactor
N

Technical data

Ambient conditions
Avoid direct sunlight or radiation from red-hot surfaces on the unit. Avoid corrosive influences, e.g. salty ambient air
.
or SO
2
The unit may only be stored/installed in enclosed
rooms/buildings that are not accessible to the public.
This unit is not suitable for cleaning with a high-
pressure cleaner and/or cleaning products. Ambient temperature:
-20 to +70°C (-4 to +158°F), no condensation permitted. Storage temperature: -20 to +70°C (-4 to +158°F).
Transport temperature = ambient temperature.
Enclosure: IP65 pursuant to IEC529. Safety class: 1. Pollution degree: internal environment:2, external environment:4. Permitted operating altitude: < 2000 m AMSL.
Mechanical data
Weight: 5 kg. Dimensions (W × H × D): 200 × 230 × 135 mm. Connections: Screw terminals: nominal cross-section 2.5mm², wire cross-section (rigid) min. 0.2mm², wire cross-section (rigid) max. 2.5mm², wire cross-section AWG/kcmil min.24, wire cross-section AWG/kcmil max.12. Spring force terminals: nominal cross-section 2 x 1.5 mm², wire cross-section min. 0.2 mm², wire cross-section AWG min.24, wire cross-section AWG max.16, wire cross-section max. 1.5mm².
Electrical data
Mains voltage: BCU..Q: 120VAC, -15/+10%, 50/60Hz, ±5%, BCU..W: 230VAC, -15/+10%, 50/60Hz, ± 5%. Power consumption: 10VA, for grounded and ungrounded mains. Flame control: with UV sensor or flame rod. For intermittent or continuous operation. Flame signal current: Ionization control: 1 – 25 μA, UV control: 1 – 35 μA. Ionization cable, UV cable: max. 50 m (164ft). Contact rating: Valve outputs V1, V2, V3 andV4 (terminals60, 61, 62, 63 and64): max.1A each, cosφ Actuator outputs (terminals 65, 66 and 67): max.1A each, cosφ=1. Air valve output (terminal 65): max.1A, cosφ=1. Ignition transformer (terminal 51): max.2A.
GB-29
=1
.
GB
F
NL
I
E
Total current for the simultaneous activation of the
valve outputs (terminals 60, 61, 62, 63 and64) and of the ignition transformer (terminal51), pro­tected by F1/F2: max.2.5A.
Total current for the simultaneous activation of the
outputs for air valve and actuator (terminals 65, 66 and67): max.2A. Signalling contact for operating and fault signals: max.1A, cosφ=1 (external fuse required). Number of operating cycles:
The fail-safe outputs (valve outputs V1, V2, V3
andV4) and the air valve output are monitored for correct functioning and are thus not subject to a max. number of operating cycles. Control actuator (terminals60, 61, 62, 63 and64):
1,000,000,
signalling contact for operating signals (terminals95, 96 and97):
1,000,000,
signalling contact for fault signals (terminals80, 81 and82): max. 25,000, On/Off button: max. 10,000, Reset/Information button: max. 10,000. Input voltage of signal inputs:
Rated value 120 VAC 230 VAC Signal “1” 80 – 132 V 160 – 253 V Signal “0” 0 – 20 V 0 – 40 V
Signal input current:
Signal “1” max. 5 mA
Fuses, replaceable, F1/F2/F3: T 3.15A H, pursuant to IEC 60127-2/5. Does not meet the requirements for safety extra-low voltage (SELV/PELV).
Designed lifetime
This information on the designed lifetime is based on
using the product in accordance with these operating instructions. Once the designed lifetime has been reached, safety-relevant products must be replaced.
Designed lifetime (based on date of manufacture): 10years. You can find further explanations in the applicable
rules and regulations and on the afecor website
(www.afecor.org). This procedure applies to heating systems. For
thermoprocessing equipment, observe local regu-
lations.

Safety instructions

Scope of application: as set out in “Industrial thermoprocessing equipment– Part 2: Safety re­quirements for combustion and fuel handling sys­tems” (EN746-2) when used with fuels and oxidants.
The BCU4 is suitable for continuous operation (pur-
suant to EN298:2012-12, Section 3.126) and for
intermittent operation (pursuant to EN298:2012-11, Section 3.127). Action:
Type 2 pursuant to EN60730-1.
Behaviour under fault conditions:
The output signals are switched off electronically
in accordance with the criteria of automatic action type B.V.AC.AD.AF.AG.AH (pursuant to EN 60730­2-5:2015, Section 6.4.3.). Maximum reaction time in the event of a flame failure:
This corresponds to the safety time during operation
and can be parameterized to between 1and4s. Software class: Corresponds to software classC which operates in a similar double-channel architecture with comparison.
Interfaces
Type of wiring:
Attachment type X to EN 60730-1. Grounding: via PE wire connection. Internal voltages are neither SELV nor PELV. Floating contacts meet the requirements for SELV.
Communication
Safety over EtherCAT over EtherCAT) is used for K-SafetyLink communica­tion. Safety over EtherCAT® is a registered trademark and patented technology licensed by Beckhoff Au­tomation GmbH, Germany.
The K-SafetyLink technology complies with SIL3
in accordance with EN61508 and is standardized
pursuant to IEC61784-3-12 and ETG5100. Safety over EtherCAT® uses the fail-safe principle which means that a safe state is restored in the case of an inactive signal. In the case of communication
errors, all signals are interpreted as inactive. Safety-relevant data are transmitted on the basis of the black channel principle. All devices connected to the communication system
must meet the requirements for safety extra-low volt­age (SELV/PELV) (EN6730-1).
The end user must ensure the unique setting and
parameterization of the SafetyLink address within the Ethernet network.
The setting and assignment of the addresses must be
verified before commissioning using the verification
procedure described in the extended documentation.
®
technology (FSoE, FailSafe
GB-30
GB
F
NL
I
E

Logistics

174 mm
200 mm
Transport
Protect the unit from external forces (blows, shocks, vibration).
Transport temperature: see page 29 (Technical
data).
Transport is subject to the ambient conditions de-
scribed. Report any transport damage on the unit or packag­ing without delay. Check that the delivery is complete, see page3 (Part designations).
Storage
Storage temperature: see page 29 (Technical data). Storage is subject to the ambient conditions de­scribed. Storage time: 6months before using for the first time. If stored for longer than this, the overall service life will be reduced by the corresponding amount of extra storage time.
Packaging
The packaging material is to be disposed of in ac-
cordance with local regulations.
Disposal
Components are to be disposed of separately in accordance with local regulations.

Accessories

BCSoft
The current software can be downloaded from our
Internet site at http://www.docuthek.com. To do so, you need to register in the DOCUTHEK.
Opto-adapter PCO 00
Including BCSoft CD-ROM, Order No. 74960625.
Fastening set
To ensure a gap between the BCU and the
mounting surface with higher temperatures.
22 mm
16.5 mm
12 mm
7 mm
20 mm
230 mm
45 mm
263 mm
222 mm
74960422
External securing bars
▷ The external securing bars are screwed on from
inside the unit.
225 mm
212 mm
185 mm
74960414
Bus module BCM 400
Communication interface for connecting the BCU to an automation system.
Ø 4mm
Connection plug set
For wiring the BCU.
74924876 74924877
Connection plugs with screw terminals, Order No. 74924876. Connection plugs with spring force terminals, Order No. 74924877.
Bus module Bus system Order No. BCM 400S0B1/1-0 Profibus 74960690 BCM 400S0B2/3-0 Profinet 74960691 BCM 400S0B3/3-0 EtherNet/IP 74960692
Set of language stickers
To affix to the cover, with program step/fault message de-
scriptions in English, French, Dutch, Spanish and Italian, Order No. 34336970.
GB-31
GB
F
NL
I
E
Certification
Declaration of conformity
We, the manufacturer, hereby declare that the prod­ucts BCU460, BCU465 and BCU480 comply with the requirements of the listed Directives and Standards.
Directives: – 2014/30/EU – 2014/35/EU
Regulation: – (EU) 2016/426 – GAR
Standards: – EN 298:2012 – EN 1643:2014 – EN 60730-2-5 – EN 61508:2010, suitable for SIL 3
The production is subject to the surveillance proce-
dure pursuant to Regulation (EU) 2016/426 AnnexIII
paragraph3.
Elster GmbH
Scan of the Declaration of conformity (D,GB)– see
www.docuthek.com
1)
There is no need for any additional EMC measure-
ment when installed.
1)
SIL, PL
For systems up to SIL 3 pursuant to EN61508. Pursuant to EN ISO 13849-1, Table 4, the BCU can
be used up to PLe.
Safety-specific characteristic values Diagnostic coverage DC 91.3%
Type of subsystem
Type B to EN 61508-
2:2010 High demand mode
Mode of operation
pursuant to EN61508-4:2010
32.9 × 10-9 1/h on Mean probability of dan­gerous failure PFH
Mean time to dangerous failure MTTF
d
BCU4xx..F1,
38.3 × 10-9 1/h on
D
BCU4xx..F3
1/PFH
D
Safe failure fraction SFF 99.0%
Mean probability of dangerous failure PFHD (70°C) of individual safety functions
Burner control with 2 gas valves Burner control with 3 gas valves Valve check Proof of closure 3.3 × 10-9 1/h Flame control 8.4 × 10
Temperature monitoring 2.2 × 10
Air pressure switch monitoring 3.3 × 10 Gas pressure switch monitoring 3.3 × 10 Purge with air pressure switch 4.3 × 10 K-SafetyLink 1.0 × 10 Safety interlocks (limits) 2.2 × 10 Valve check with redundant pres-
sure switch Air pressure switch monitoring
with red. pressure switch Gas pressure switch monitoring
with red. pressure switch Purge with red. air pressure
switch
23.2 × 10-9 1/h
28.5 × 10-9 1/h
15.0 × 10-9 1/h
-9
1/h
-9
1/h
-9
1/h
-9
1/h
-9
1/h
-9
1/h
-9
1/h
12.9 × 10-9 1/h
1.3 × 10-9 1/h
-9
1.3 × 10
2.3 × 10
-9
1/h
1/h
GB-32
GB
F
NL
I
E
FM approved
Factory Mutual (FM) Research Class:
7610 “Combustion Safeguards and Flame Sensing
Systems” Suitable for applications pursuant to NFPA 86.
Directive on the restriction of the use of hazardous substances (RoHS) in China
Scan of the Disclosure Table China RoHS2 – see certificates at www.docuthek.com
GB-33
GB
F
NL
I
E

Contact

Contact
If you have any technical questions, please contact your local branch office/agent. The addresses are available on the Internet or from ElsterGmbH.
We reserve the right to make technical modifications in the interests of progress.
Strotheweg 1, D-49504 Lotte (Büren)
Elster GmbH
Tel. +49 541 1214-0
Fax +49 541 1214-370
hts.lotte@honeywell.com, www.kromschroeder.com
GB-34
Loading...