Kramer BCLS-33OR-5 User Manual

KRAMER
Product Description
CAT 6 A F/U TP, 23AWG solid bare copper, LSZH. With cross filler. Overall metal foil screen with drain wire.
Product Features
High performance of transmission. High quality of safet y proper ties. Sweep frequency up to 650 MHz.
Applications
Structure cabling for horizontal and building backbone cable. Designed for IT, LAN and Ethernet installations. IEEE 802.3an 10GBASE-T and legacy speeds. CDDI / ATM / Token Ring IEEE 802.3af (PoE) / IEEE 802.3at (PoE+)
Applicable Standard
Performance Standards:
ANSI/T IA-568-C.2 (20 09) Balanced Twisted-Pair Telecommunications Cabling and Components Standards
ISO/IEC 11801 (Edition 2.2) Information technology - Generic cabling for customer premises
IE C 6 115 6-5 (Edition 2.0) Multicore and symmetrical pair/quad cables for digital
communications - Part 5: Symmet rical pair/q uad cables with transmission characteristics up to 1000 MHz - Horizontal floor wiring - Sectional specification
EN 50288-10-1:2012 Multi-element metallic cables used in analogue and digital communication and control - Part
10 -1: Sectional specification for screened cables characterized up to 500 MHz - Horizontal floor and building backbone cables
EN 5 017 3 -1:2 011 Information technology. Generic cabling systems, General requirements
Standards for flammability, acidity and smoke:
IEC 60332 -1-2 Tests on electric and optical fibre cables under fire conditions - Part 1-2: Test for vertical
flame propagation for a single insulated wire or cable - Procedure for 1 kW pre-mixed flame
IE C 610 34-1 / 610 3 4-2 Measurement of smoke density of cables burning under defined conditions
IEC 60754-2 Test on gases evolved during combustion of materials from cables
EU Directive 2011/6 5/ E C (RoHS 2)
EU Directive 2006/95/E C (LV D)
CE compliance date: 2010.01.01
WELL CONNECTED WITH KRAMER
BCLS-33OR-5
CAT6A F/UTP LSZH Cable
Kramer’s BCLS-33OR is a high performance CAT6A F/UTP cable designed for IT, LAN and Ethernet installations. Constructed with 23AWG solid bare copper conductors with a cross filler and overall metal foil screen with a drain wire in a LSZH jacket with sequential markings every meter and packed on a fumigated plywood reel make this cable exceed CAT6A specifications to provide additional performance and bandwidth over the basic standard
Al-Mylar
Conductor
Drain Wire
Insulation Jacket
Mylar
Filler
© 2015 KRAMER ELECTRONICS, Ltd. All rights reserved. Reproduction in whole or in part without written permission is prohibited. 1/5
MATERIAL AND CONSTRUCTION
Conductor Material 23AWG solid bare copper
Material Polyolefin (PO)
Blue & white/blue Stripe 1.15 ± 0.02 mm
Insulation
Color code & diameter
Orange & white/orange stripe 1.11 ± 0.02 mm
Green & white/green stripe 1.15 ± 0.02 mm
Brown & white/brown stripe 1.11 ± 0.02 mm
Twisted Description Left hand direction
Filler Material Polyolefin (PO)
Assembly Description Left hand direction
Shield Material Mylar tape
Drain wire Material 24AWG solid tinned copper
Shield
Material Al Mylar tape
Description 100 % coverage and mylar side facing out
Material Low smoke zero halogen (LSZH)
Jacket
Diameter 7.60 ± 0.2 mm
Thickness 0.55 ± 0.05 mm
Color Orange[Pantone 1485C]
USAGE & ENVIRONMENTAL CONDITION
Storage & shipping -20°C to 60°C
Temperature range
Minimum bending radius ≥ 4 times of overall diameter
Maximum pulling tension ≤ 110 N
Installation 0°C to 60°C
Operation -20°C to 60°C
PHYSICAL & ELECT RIC AL CHA RACTERISTICS (AT 20°C)
Temperature & voltage rating 60°C / 300V
Spark test 2.5 KV DC
AC leakage current through overall jacket ≤ 10mA (1.5KV AC)
Cable cold bend -20°C for 4 hr
Conductor DC resistance ≤ 9.38 Ω/100m
Resistance unbalance ≤ 5%
Dielectric strength 1.5 KV ac for 2 s
Insulation resistance ≥ 5000 MΩ•m
Mutual capacitance ≤ 5.6 nF/100m
Capacitance unbalance pair-to-ground ≤ 330 pF/100m
Characteristic Impedance @1~100MHz,100±15 Ohm
Coupling Attenuation AT 30 MHz 55dB; AT 500 MHz 41 dB
Insulation Tensile Strength 2400 PSI MIN. (1.69 Kg/m2)
NVP 67%
TRANSMISSION PERFORMANCE (AT 20°C)
Min.
Propagation
Delay
Max.
ns/100m
Delay Skew PS ANEXT PS AACR-F
Max.
ns/100m
45.00
Min.
dB/100m
75.00 71.00
Freq.
MHz
1 2.08 75.30 73.30 73.22 71.22 71.80 68.80 20.00 570.00
4 3.80 66.27 64.27 62.47 60.47 59.76 56.76 23.01 552.00 75.00 70.16
8 5.31 61.75 59.75 56.44 54.44 53.74 50.74 24.52 546.73 75.00 64.14
10 5.93 60.30 58.30 54.37 52.37 51.80 48.80 25.00 545.38 75.00 62.20
16 7.49 57.24 55.24 49.75 47.75 47.72 44.72 25.00 543.00 75.00 58.12
20 8.38 55.78 53.78 47.41 45.41 45.78 42.78 25.00 542.05 75.00 56.18
25 9.38 54.33 52.33 44.95 42.95 43.84 40.84 24.32 541.20 75.00 54.24
31.25 10.50 52.88 50.88 42.37 40.37 41.90 38.90 23.64 540.44 75.00 52.30
62.5 14.99 48.36 46.36 33.37 31.37 35.88 32.88 21.54 538.55 73.56 46.28
100 19.14 45.30 43.30 26.17 24.17 31.80 28.80 20.11 537.60 70.50 42.20
150 23.68 42.66 40.66 18.98 16.98 28.28 25.28 18.87 536.94 67.86 38.68
200 27.58 40.78 38.78 13.21 11.21 25.78 22.78 18.00 536.55 65.98 36.18
250 31.07 39.33 37.33 8.26 6.26 23.84 20.84 17.32 536.28 64.53 34.24
300 34.27 38.14 36.14 3.88 1.88 22.26 19.26 16.77 536.08 63.34 32.66
350 37.25 37.14 35.14 N.A. N.A. 20.92 17.92 16.30 535.92 62.34 31.32
400 40.05 36.27 34.27 N.A. N.A. 19.76 16.76 15.89 535.80 61.47 30.16
450 42.71 35.50 33.50 N.A. N.A. 18.74 15.74 15.53 535.70 60.70 29.14
500 45.26 34.82 32.82 N.A. N.A. 17.82 14.82 15.21 535.61 60.02 28.22
550 47.70 34.19 32.19 N.A. N.A. 16.99 13.99 14.92 535.54 59.39 27.39
600 50.05 33.63 31.63 N.A. N.A. 16.24 13.24 14.66 535.47 58.83 26.64
650 52.33 33.11 31.11 N.A. N.A. 15.54 12.54 14.42 535.41 58.31 25.94
*Values above 500 MHz are for information only
IL NEXT PS NEXT ACR PS ACR ACRF PS ACR-F RL
Max.
dB/100m
Min.
dB/100m
Min.
dB/100m
Min.
dB/100m
Min.
dB/100m
Min.
dB/100m
Min.
dB/100m
dB/100m
Min.
dB/100m
© 2015 KRAMER ELECTRONICS, Ltd. All rights reserved. Reproduction in whole or in part without written permission is prohibited. 2/5
TEST REPORT ( Len g t h 10 0 m )
RL (NE)(dB)NEXT (dB)
0.0
-6.0
-12.0
-18.0
-24.0
-30.0
-36.0
-42.0
-48.0
-54.0
-60.0
-30.0
RL (NE) vs. Frequency
Max. Graph Point: -25.3 at 1.39 MHz
Min. Graph Point: -65.2 at 82.18 MHz
2 3 4 5 10 20 30 40 100 200 300 500
Frequency (1 - 650 MHz; 401 scan points)
Pair 1 Pair 2 Pair 3 Pair 4
NEXT vs. Frequency
Max. Graph Point: -40.5 at 500.00 MHz
Min. Graph Point: -131.1 at 1.51 MHz
0.0
-6.0
-12.0
-18.0
-24.0
-30.0
RL (FE)(dB)
-36.0
-42.0
-48.0
-54.0
-60.0
-30.0
RL (FE) vs. Frequency
Max. Graph Point: -24.1 at 479.97 MHz
Min. Graph Point: -66.2 at 97.83 MHz
2 3 4 5 10 20 30 40 100 200 300 500
Frequency (1 - 650 MHz; 401 scan points)
Pair 2
Pair 1
NEXT (FE) vs. Frequency
Max. Graph Point: -38.6 at 500.00 MHz
Min. Graph Point: -122.1 at 1.29 MHz
Pair 3
Pair 4
-37.0
-44.0
-51.0
-58.0
-65.0
-72.0
-79.0
-86.0
-93.0
-100.0 2 3 4 5
Frequency(1 - 500 MHz; 401 scan points)
Pair1-2 Pair1-3 Pair1-4 Pair2-3 Pair2-4 Pair3-4
20 30 40 100 200 300 500
10
-37.0
-44.0
-51.0
-58.0
-65.0
NEXT (FE)(dB)
-72.0
-79.0
-86.0
-93.0
-100.0 2 300 500
3 4 5 10 20 30 40 100 200
Frequency(1 - 500 MHz; 401 scan points)
Pair1-2 Pair1-3 Pair1-4 Pair2-3 Pair2-4 Pair3-4
© 2015 KRAMER ELECTRONICS, Ltd. All rights reserved. Reproduction in whole or in part without written permission is prohibited. 3/5
TEST REPORT ( Len g t h 10 0 m )
IL (dB)PS NEXT (dB)
0.0
-6.0
-12.0
-18.0
-24.0
-30.0
-36.0
-42.0
-48.0
-54.0
-60.0
-10.0
IL vs. Frequency
Max. Graph Point: -1.75 at 1.00 MHz
Min. Graph Point: -40.45 at 500.00 MHz
2 3 4 5 10 20 30 40 100 200 300 500
Frequency(1 - 500 MHz; 401 scan points)
Pair 1 Pair 2 Pair 3 Pair 4
PS NEXT vs. Frequency
Max. Graph Point: -39.7 at 500.00 MHz
Min. Graph Point: -99.3 at 1.00 MHz
-10.0
-19.0
-28.0
-37.0
-46.0
-55.0
ACR-F (dB)
-64.0
-73.0
-82.0
-91.0
-100.0
-10.0
ACR-F vs. Frequency
Max. Graph Point: -40.8 at 479.97 MHz
Min. Graph Point: -115.4 at 1.92 MHz
3 4 5 10 20 30 40 100 200 300 500
2
Frequency (1 - 500 MHz; 401 scan points)
Pair1-2 Pair1-3 Pair1-4 Pair2-3 Pair2-4 Pair3-4
PS NEXT (FE) vs. Frequency
Max. Graph Point: -38.3 at 500.00 MHz
Min. Graph Point: -99.7 at 1.27 MHz
-17.0
-24.0
-31.0
-38.0
-45.0
-52.0
-59.0
-66.0
-73.0
-80.0 2 300 500 3 4 5 10 20 30 40 100 200
Frequency (1 - 500 MHz; 401 scan points)
Pair 1 Pair 2 Pair 3 Pair 4 Pair 1 Pair 2 Pair 3 Pair 4
-17.0
-24.0
-31.0
-38.0
-45.0
PS NEXT (dB)
-52.0
-59.0
-66.0
-73.0
-80.0 2 300 500
3 4 5 10 20 30 40 100 200
Frequency (1 - 500 MHz; 401 scan points)
© 2015 KRAMER ELECTRONICS, Ltd. All rights reserved. Reproduction in whole or in part without written permission is prohibited. 4/5
TEST REPORT ( Len g t h 10 0 m )
PS ACR-F vs. Frequency
Max. Graph Point: -39.4 at 486.65 MHz
-10.0
-19.0
-28.0
-37.0
-46.0
-55.0
PS ACR-F (dB)
-64.0
-73.0
-82.0
Min. Graph Point: -98.3 at 1.74 MHz
-91.0
-100.0 2 300 500 3 4 5 10 20 30 40 100 200
Frequency (1 - 650 MHz; 401 scan points)
Pair 1 Pair 2 Pair 3 Pair 4
SHIPPING INFORMATION:
Item
KRAMER ELECTRONICS
E-mail: info@kramerel.com Web: www.KramerAV.com
© 2015 KRAMER ELECTRONICS, Ltd. All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Cable 500 m
Plywood reel D450 x d220 x H330 x h300 mm
Pallet 1150 x1150 x120 mm
Dimension
Nominal net weight
28.45 kg (62.72 lb)
3.9 kg
14.1 kg
D
hH
d
5/5