kozy heat Chaska-XL, CSK-31, CSK-31-RF Operating Manual

g
Models #CSK-335
#CSK-335-RF
CHASKA - XL
Direct Vent Gas Fireplace Insert
INSTALLATION & OPERATING
MANUAL
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
phone in your building.
Immediately call your gas supplier from a
neighbor’s phone. Follow your gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire
department.
Installation & service must be performed by a qualified installer, service a
ency, or the gas supplier.
This appliance may be installed in an aftermarket permanently located, manufactured (mobile) home, where not prohibited by local codes. This appliance is only for use with the type(s) of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
IMPORTANT:
READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION.
FAILURE TO INSTALL THIS FIREPLACE CORRECTLY CAN CAUSE
SERIOUS STRUCTURAL AND FIRE HAZARDS AND MAY VOID
YOUR WARRANTY.
We recommend that our gas hearth products be installed and serviced by profes­sionals who are certified in the U.S. by the National Fireplace Institute
www.nficertified.org
NFI Gas Specialists.
®
(NFI) as
This fireplace may be covered under one or more of
the following U.S. Patents: #5,931,154 , #6,004,493, #6,029,655
www.kozyheat.com Sept. 2008
CSK-335-R05
INDEX
Fireplace Insert Specifications …………….. ...................................................................................... 1
Safety Requirements …………………………………. ....................................................................... 1-2
Requirements of Existing Fireplace …………………………………. .................................................. 2
Fireplace Insert Components …………... ........................................................................................... 3
Preparing The Existing Fireplace …………………………………. ...................................................... 4
Gas Line Installation Requirements - Minimum/Maximum Pressures ......................................... 4-5
Insert Preparation …………………………………. ............................................................................... 6
Remove the Glass Assembly …………. ................................................................... 6
Remove the Air Duct …………………………………. ................................................ 6
Fan Installation …………………………………. ................................................................................. 7-8
Model #CSK-335 ………………….... .......................................................................... 7
Model #CSK-335-RF …………………………………. ................................................. 8
Installing the Insert …………………………………. ........................................................................ 9-14
Co-Linear Vent System …………... ..................................................................... 9-11
Position the Insert ….. …………... ..................................................................... 11-12
Secure the Air Duct …………….... .......................................................................... 12
Complete the gas line installation …………... ....................................................... 13
Check millivolt board installation …………........................................................... 13
Complete fan wiring installation
(Models #CSK-335 & #CSK-335-RF) .................... 14
Assemble & Attach The Shroud …………………………………........................................................ 15
Install the lower grill …………………………………. ............................................... 15
Log Installation …………………………………. .................................................................................. 16
Complete the Installation
Initial Lighting ………….………….. ........................................................................................ 17
Replace the Glass Assembly ………….………….. ............................................................... 17
Thermostat - Remote Control - Wall Switch Installation
(Model #CSK-335 only) …………………. . 18
Model #CSK-335
Lighting & Shutdown Procedures ………………..….. ...................................... 19-20
Manifold (outgoing) & Inlet (incoming) Pressure Check Procedures ……. ....... 21
Model #CSK-335-RF
Lighting & Shutdown Procedures ………………..….. ...................................... 22-23
Manifold (outgoing) & Inlet (incoming) Pressure Check Procedures ……. ....... 24
Maintenance Requirements …………….. ......................................................................................... 25
Millivolt Board Removal / Installation Procedures …………………………………. .................... 26-27
Troubleshooting Guide …………………………………. ................................................................ 28-29
Replacement Parts ………………….……... ....................................................................................... 30
Warranty Policy ………………….…………. .................................................................................. 31-32
COMMONWEALTH OF MASSACHUSETTS
NOTE: The following requirements reference various Massachusetts and national codes not contained in this document. REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
INSTALLATION OF CARBON MONOXIDE DETECTORS
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor where the gas equipment is to be installed. In addition, the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontally vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
In the event that the requirements of the subdivision cannot be met at the time of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery ope rated carbon monoxide detector with an alarm shall be installed.
APPROVED CARBON MONOXIDE DETECTORS
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
SIGNAGE
A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than (½) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
INSPECTION
The state of local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08 (2) (a) 1 through 4.
EXEMPTIONS
The following equipment is exempt from 248 CMR 5.08 (2) (a) 1 through 4.
The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted
by the Board; and
Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separated from the dwelling,
building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS
GAS EQUIPMENT VENTING SYSTEM PROVIDED
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
Detailed instructions for the installation of the venting system design or the venting system components; and
A complete parts list for the venting system design or venting system.
GAS EQUIPMENT VENTING NOT
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and
detailed installation instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
Installation and repair must be done by a plumber or gas fitter licensed in the Commonwealth of Massachusetts.
The flexible gas line connector used shall not exceed 36 inches (92 centimeters) in length.
The individual manual shut-off must be a T-handle type.
PROVIDED
MODEL: #CSK-335 / #CSK-335-RF CHASKA-XL
DIRECT VENT GAS FIREPLACE INSERT
INSTALLATION & OPERATING INSTRUCTIONS
IMPORTANT:
READ THIS MANUAL BEFORE INSTALLING AND USING THIS FIREPLACE
This fireplace has been tested to and complies with ANSI Z21.88a-2007 V CSA 2.33a-2007 “VENTED GAS FIREPLACE HEATERS” by OMNI-Test Laboratories, Portland, OR. Installation must conform with local building codes or in the absence of local building codes, with the National Fuel Gas Code, ANSI Z223.1/ NFPA 54 ­Current Edition, or the Natural or Propane Installation Code, CSA B149.1.
SPECIFICATIONS:
Height: 23" Width: 33 3/8" Back Width: 24 3/8 " Depth: 16"
Do not use this fireplace if any part has been under water. Immediately call a qualified service technician to inspect this appliance and to replace any part of the control system and any gas control
COMMONWEALTH OF MASSACHUSETTS INSTALLATIONS
WARNING: This Product Must Be Installed By A Licensed Plumber Or Gas Fitter When Installed Within The Commonwealth of Massachusetts.
IMPORTANT: Installation of a CO detector is required in the fireplace room.
WARNING: DO NOT REPLACE THIS BURNER WITH ANY OTHER SIZED BURNER. REPLACEMENT WITH AN UNAUTHORIZED BURNER CAN RESULT IN TEMPERATURES EXCEEDING THE LIMITS FOR THIS FIREPLACE AND VOID YOUR WARRANTY.
DUE TO HIGH TEMPERATURES, THIS FIREPLACE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES.
Warning: This Product Must be Installed By A Licensed Plumber or Gas Fitter When Installed Within the Commonwealth of Massachusetts.
YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THIS FIREPLACE.
CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION. CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE.
Page 1
The efficiency rating of this appliance is a product thermal efficiency rating determined under continuous operating conditions and was determined independently of any installed system.
THIS INSERT IS APPROVED FOR INSTALLATION IN MASONRY AND FACTORY-BUILT SOLID FUEL BURNING FIREPLACES.
CAUTION: THIS APPLIANCE MUST NOT BE CONNECTED TO A CHIMNEY FLUE SERVING A SEPARATE SOLID-FUEL
BURNING APPLIANCE.
THE EXISTING FIREPLACE MUST MEET THE FOLLOWING REQUIREMENTS:
1. The existing fireplace & chimney must be in clean
and in good working order and constructed of non­combustible materials.
2. A gas line must be able to be installed to the insert.
3. Any chimney clean-outs must fit properly.
4. Existing Chimney:
Class ‘A’ metal chimney: 7” minimum inside diameter. Masonry Chimney: 6" x 8" minimum inside diameter.
Existing chimney height: Minimum: 12 ft.
To Determine the length of your existing chimney:
A) Remove the chimney cap.
Maximum: 30 ft.
NOTE: It is helpful to have two people complete the
B) With one person at the fireplace and the other person
next step in determining chimney height:
at the top of the chimney, measure from the base of the fireplace to the top of the chimney. Subtract 23” for the height of the insert. This is the total length of co-linear flexible aluminum you will require.
MEASUREMENT FROM FIREPLACE BASE TO TOP OF CHIMNEY:_____ LESS 23
" (HEIGHT OF FIREPLACE: -23" .
TOTAL CHIMNEY LENGTH REQUIRED: _____
MIN. 12 FT. MAX. 35 FT.
MAX. 35 FT
5. The minimum inside dimensions of the existing
fireplace must be:
Height (A): 23 1/2" Front Width (B): 33 1/2" Depth (C): 16 1/2" Back Width (D): 24 1/2"
MINIMUM OPENING DIMENSIONS
ALL DIMENSIONS ARE MINIMUM REQUIREMENTS
6. MINIMUM CLEARANCES FROM THE INSERT TO
COMBUSTIBLES:
Insert side to sidewall: 12"
Insert top to 9" mantel: 16"
Insert top to 3/4" trim: 12"
Bottom of insert to combustible floor in front: 6"
Bottom of insert underneath to combustible floor: 0"
Page 2
FIREPLACE COMPONENTS:
y p
Check the assembly diagram below to ensure you have all the necessary components to properly install this fireplace insert.
This insert includes the following:
1. Fireplace insert. 4. Co-linear air duct.
2. Spring-loaded latch glass assembly. 5. Log set (See page #16).
3. Millivolt board with burner cover. 6. Refractory Panels.
Model CSK-335 includes 150 CFM fan with limit switch and speed control.
Model CSK-335-RF includes modulating valve on millivolt board, fan kit and remote control.
WARNING: Failure to position the parts in accordance with the diagrams in this installation manual or failure to use
Additional components which are necessary for proper installation are:
1. Vent System: Part #816-CL: For use with minimum 6” x 8” I.D. masonry or 7” I.D. Class ‘A’ metal
This insert is also approved for use with Dura-Vent, Ameri-Vent, & Selkirk Metalbestos 3" x 3" Co-linear vent systems. Refer to the instructions accompanying the vent system as well as the venting requirements and instructions in this manual.
2. Shroud - 3 pc & 4 pc.: Standard shrouds are available for this insert and will fit most applications. Custom
shrouds may be ordered on a non-returnable basis. When ordering a custom shroud, please specify the existing fireplace front opening height and width. An upper hood and lower grill are included.
3. Blank Shrouds - 3 & 4 pc. blank shrouds are available for on-site custom fit applications and are sized to the
opening after the insert has been installed. The interior pe rimeter is properly sized to fit onto the insert. The outer perimeter must be cut, formed and finished (painted). An upper hood and lower grill are included.
4. Full door shrouds: Full door decorative shrouds are available for this insert and are used in place of a
standard or blank shroud. An upper hood and lower grill are included.
onl
arts specifically approved for this appliance may result in property damage or personal injury.
chimneys - Includes 12 ft. compressed, expandable to 35 ft. co-linear 3” x 3” flexible chimney, and termination cap.
Page 3
A) PREPARE THE EXISTING FIREPLACE
WARNING: CUTTING ANY SHEET-METAL PARTS OTHER THAN COMPONENTS LISTED IN THIS SECTION OF THE
1) The refractory, glass doors, screen rails, screen mesh and log grates may be removed from the fireplace
before installing this gas fireplace insert.
2) Any smoke shelves, shields and baffles may be removed if attached by mechanical fasteners.
3) If necessary, remove the firebrick on the sides and back of the existing fireplace to obtain at least the
minimum opening requirements listed on page #2.
4) The fireplace flue damper can be fully blocked open or removed for installation of this gas fireplace insert.
5) Remove the existing chimney cap from the chimney.
6) Clean the chimney and inside of the fireplace to prevent creosote smell from entering the home.
7) Place ‘THIS UNIT HAS BEEN MODIFIED’ label in the bottom of the firebox so it will be visible if this gas
fireplace insert is removed.
EXISTING FIREPLACE IN WHICH THIS GAS FIREPLACE INSERT IS TO BE INSTALLED IS PROHIBITED.
B. RUN THE GAS LINE
CAUTION: Installation of the gas line must only be done by a qualified person in accordance with
IMPORTANT: DO NOT RUN THE GAS LINE IN A MANNER THAT WOULD OBSTRUCT THE
This fireplace is equipped with a 3/8" flexible gas line connection 18" long. CAUTION: The manual shut off valve and millivolt board flexible gas line must not extend outside the insert
1. Run the gas line into the fireplace, preferably through the left or right gas line hole provided. A gas line
knock-out is also located in the outer bottom of the insert when running the gas line through the bottom. See Figure B-1 on page #5. NOTE: If installing this insert into minimum opening dimensions, the gas line may need to be run after the
insert is in place due to space limitations. If installing this gas fireplace insert into a factory-built fireplace and the factory-built fireplace has no
access holes(s) provided, an access hole of 1 ½" or less may be drilled through the lower sides or bottom of the firebox in a proper workmanship like manner. This access hole must be plugged with non-combustible insulation after the gas supply line has been installed.
IMPORTANT: An accessible shut off valve (included with this insert) must be installed up stream from the
local building codes.
OPERATION OF THE FAN OR FAN COMPONENTS.
unit cavity. See the WARNING label affixed to the flexible gas line for additional installation instructions and warnings.
regulator.
Page 4
Figure B-1
1 3/8" FROM BOTTOM TO GAS LINE
2. This fireplace is designed to accept either a 3/8"
or 1/2" gas line approved for gas appliances. Consult local building codes to properly size the gas supply line leading to a 3/8" reduction.
3. Connect the manual shut off valve to the
previous run gas line.
4. The gas line will be connected to the millivolt
board later in this manual.
ALL CONNECTIONS WHETHER FIELD OR FACTORY MADE MUST BE CHECKED FOR LEAKS.
IMPORTANT:
NOTE: This appliance and its individual shut off
NOTE: This appliance must be isolated from the
WARNING LABEL
valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½ psi.
gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping systems at test pressures equal to or less than 1/2 psi.
Pressure check taps for both the manifold (outgoing) and inlet (inc oming) pressures are located in front of the gas valve. The right pressure tap is the manifold pressure and the left pressure tap is the incoming pressure. Follow instructions on page #21 for Model #CSK-335 and page #24 for Model CSK-335-RF for checking these pressures.
GAS SPECIFICATIONS
NATURAL GAS:
The minimum inlet gas supply pressure: 5.0 in. W.C. Recommended inlet gas supply pressure: 7.0 in. W.C. The maximum inlet gas supply pressure: 10.5 in. W.C. Manifold Pressure: 3.5 in. W.C. P4AFE:65.30 Manifold Pressure (lo setting): 1.7 in. W.C. Orifice size (0-2000 ft): 35 Input rating: 36,000 BTU/Hr. Minimum Input rating: 22,000 BTU/Hr. Venturi setting: 1/16" open
LP GAS:
The minimum inlet gas supply pressure: 11.0 in. W.C. Recommended inlet gas supply pressure: 11.0 in. W.C. The maximum inlet gas supply pressure: 13.0 in. W.C. Manifold Pressure: 10.0 in. W.C. P4AFE66.15 Manifold Pressure (lo setting): 6.3 in. W.C. Orifice size (0-2000 ft): 50 Input rating: 36,500 BTU/Hr. Minimum Input rating: 22,000 BTU/Hr. Venturi setting: 1/2" open
For high altitude installations, consult the local gas distributor or the authority having jurisdiction for proper rating methods.
Page 5
C. REMOVE THE FOLLOWING ITEMS FROM THE FIREPLACE INSERT:
C
-
C
-
2
1. GLASS ASSEMBLY:
A) Locate the spring-loaded latches securing
the glass assembly (under the firebox).
B) While holding onto the glass frame, pull the
latch handles out, then down to release from
the clips on the glass assembly.
C) Lift the glass assembly up off the tabs at the
top of the firebox.
D) Pull the bottom of the glass assembly out
and remove.
E) Set aside where it will not be broken.
2. REMOVE THE AIR DUCT. Figure C-2.
A. Remove the air duct, located at the top of the insert, by sliding it back out of the channel.
Figure
Figure
TWO GLASS LATCHES
Air Duct
1
Page 6
D. MODEL #CSK-335 ONLY: FAN INSTALLATION INSTRUCTIONS
g
p
y
g
D
-
This fireplace insert comes complete with a fan and thermostatic control switch already installed. A speed control, receptacle and 8 ft. fan cord have been installed, wired and mounted in a removable electrical box panel on the right side of the fireplace. If wiring to the pre-installed electrical box is desired, the wiring should be run prior to permanently setting the insert in place and connecting the vent system. A direct wire connection to the electrical box provided must be performed by a qualified electrician.
NOTE: If this fireplace insert is being installed in the minimum opening dimensions, the wiring may need to be
completed after the fireplace insert is set in place. The fan is equipped with a three-prong (grounding) plug attached to the end of the fan electrical cord for
protection against shock hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not remove the grounding prong from the plug. Do not allow any excess fan cord to touch the fireplace.
NOTE: Code approved line voltage wiring 14 gauge or better must be used when wiring this assembly. Refer to
your local electrical codes for specific requirements in your area.
WARNING: This appliance is equipped with a three-prong (grounding) plug for protection against shock
NOTE: The cord must be removed and wiring disassembled. Insert 115 V wiring (with ground) through the romex connector
and wire to the speed control / receptacle assembly, matching the black, white & green (ground) wires to the corresponding wires on the s
115 V
60 Hz
Incoming 115 V wiring
hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the
DIRECT WIRE INSTALLATION:
eed control / receptacle assembly.
rounding prong from this plug.
Temperature Switch
Electrical Box
Speed Control / Receptacle Assembl
Fi
ure
1
Ground
Wire
DIRECT WIRE INSTALLATION:
1. Loosen the screw securing the removable access panel (with electrical box & romex connector installed)
from the right side of the fireplace. Remove the panel.
2. Remove the (2) screws securing the speed control / receptacle to expose the wiri ng.
3. Remove existing cord and insert 115V wiring (with ground) through the romex connector and wire to the
speed control / receptacle assembly matching the black (hot) white (neutral) and green (ground) wire to the corresponding wire on the speed control / receptacle assembly. NOTE: The (3) wire nuts obtained when removing the existing cord, may be used for this purpose.
4. Secure the speed control / receptacle assembly into the electrical box with the (2) screws provided.
This appliance, when installed, must be electrically grounded in accordance with local codes, or in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Codes, CSA C22.1.
Page 7
MODEL #CSK-335-RF ONLY: FAN INSTALLATION INSTRUCTIONS
p
D
-
2
(RF)
g
g
p
INSTALLATION OF THIS FAN WIRING SHOULD BE DONE ONLY BY A QUALIFIED INSTALLER.
IMPORTANT: A fan assembly is pre-installed and wired to the RF gas valve in the CSK-335-RF models. A receptacle and 8 ft. fan cord have been installed, wired and mounted in a removable electrical box panel on
the right side of the fireplace. If direct wiring to the pre-installed electrical box is desired, the wiring should be completed prior to permanently setting the insert in place and connecting the vent system. Code approved line voltage wiring 14 gauge or better must be used when wiring this assembly. Refer to your local electrical codes for specific requirements in your area. A direct wire connection to the electrical box provided must be performed by a qualified electrician.
NOTE: If this fireplace insert is being installed in the minimum opening dimensions, the wiring may need to be
completed after the fireplace insert is set in place. The fan is equipped with a three-prong (grounding) plug attached to the end of the fan electrical cord for
protection against shock hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not remove the grounding prong from the plug. Do not allow any excess fan cord to touch the fireplace.
WARNING: This appliance is equipped with a three-prong (grounding) plug for protection against shock
hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug.
DIRECT WIRE INSTALLATION:
NOTE: The cord must be removed and wiring disassembled.
Insert 115 V wiring (with ground) through the romex connector and wire to the receptacle matching the black, white & green (ground) wires to the corres
onding wires on the receptacle.
Gas Valve
Wires connect to valve
Wires connect
to fan cord
Rece
Electrical Box w/ Romex connector
tacle & Cover
Figure
DIRECT WIRE INSTALLATION:
1. Loosen the screw securing the removable access panel (with electrical box & romex connector installed)
from the right side of the fireplace.
2. Remove the (2) screws securing the receptacle assembly to expose the wiring.
3. Remove existing cord and insert 115V wiring (with ground) through the romex connector and wire to the
receptacle, matching the black (hot) white (neutral) and green (ground) wire to the corresponding wire on the receptacle. NOTE: The (3) wire nuts obtained when removing the existing cord may be used for this purpose.
4. Secure the receptacle assembly into the electrical box with the (2) screws provid ed.
This appliance, when installed, must be electrically grounded in accordance with local codes, or in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Codes, CSA C22.1.
115 V
60 Hz
Incomin
115 V wirin
Page 8
E. INSTALLING THE INSERT
E
-
IMPORTANT: ALL STEPS IN SECTION ‘A) PREPARE THE EXISTING FIREPLACE’ MUST BE COMPLETED BEFORE
CONTINUING WITH THIS INSTALLATION.
1. INSTALL THE VENT SYSTEM
COMBUSTION AIR VENTING:
The combustion air intake pipe may be run the complete length of the chimney (full connection method) and connected to the termination cap, or may be ‘stubbed’ into the existing chimney from inside the fireplace using a minimum of 4' combustion air intake pipe.
KOZY HEAT #816-CL CO-LINEAR VENT SYSTEM:
The co-linear pipes included in this vent system is designed to extend up to 35 ft. IMPORTANT: The 3" exhaust pipe can be identified by the red marking. It is imperative for proper
operation of this insert that the exhaust and combustion air pipes be connected to the
correct collar both on the termination kit and air duct on the insert. A. Carefully extend the 3” exhaust and combustion air intake pipes to equal the total chimney length required. NOTE: If you are using the ‘stubbed’ method for the combustion air pipe, extending it is not necessary.
Determine the length needed from the air duct on the insert to above the damper opening in the existing chimney. Remove excess combustion air pipe from the end without the collar. Continue with Step B. #2 below.
B. 1. Slide the 3" intake pipe (end without the collar) onto the collar on the termination cap and secure
with 3 self-tapping screws (provided) If using the ‘full connection method’.
2. Place a bead of sealant around the inner edge of the end of the 3" exhaust pipe (red marking) without the collar and slide onto the corresponding collar on the termination cap (collar with label). Secure with 3 selftapping screws (provided). Apply additional sealant around the joint to ensure a seal.
INTAKE COLLAR
NOTE: Collar extends through
the bottom plate
SEALANT
SEALANT
SHEET METAL SCREWS
(3 TOTAL)
FIGURE
1
EXHAUST COLLAR ON THE RIGHT SIDE.
THE EXHAUST COLLAR ON THE AIR DUCT
FOR THE FIREPLACE IS ON THE RIGHT.
TERMINATION CAP
Exhaust Collar
NOTE: Collar extends through
the middle divider plate
IMPORTANT:
INSTALL TERMINATION CAP WITH
OTHER APPROVED 3" X 3" CO-LINEAR VENT SYSTEMS:
Dura-Vent, Ameri-Vent Direct, & Selkirk Metalbestos - Follow instructions included from the vent pipe manufacturer as well as the venting installation requirements as outlined in this installation manual.
Page 9
2. RUN THE VENT SYSTEM THROUGH THE EXISTING CHIMNEY
OPTIONAL: We recommend wrapping the first 3 ft. of the vent system below the termination cap with non-
faced fiberglass insulation (secure with wire) before running it through the existing chimney. This will prevent cold air from coming down the existing chimney. DO NOT USE THIS METHOD IF YOU ARE STUBBING THE 3" COMBUSTION AIR PIPE FROM THE BOTTOM OF THE EXISTING CHIMNEY!
NOTE: If there are offsets in the existing chimney, it may be easier to place a weighted rope around the end of the each 3" pipe to guide them through it.
DO NOT ATTEMPT TO TIE ONE ROPE AROUND BOTH PIPES.
A. Guide the rope, if used, and flexible pipe(s) down the existing chimney. Figure E-2 B. To secure the chimney termination cap to the existing chimney, apply a liberal bead of sealant (provided)
around the top of the existing chimney. Set the termination cap into position as instructed in the vent system installation manual.
OPTIONAL: #816-CL kits - Secure the termination cap to the existing chimney with the 2" self-tapping screws and anchor straps provided. Screw holes are located at the side s of the termination cap.
C. From inside the opening, grasp the ropes and CAREFULLY pull the ropes down until the 3" exhaust pipe
and 3” combustion air intake, if using the ‘full connection method’, are into the existing fireplace.
D. STUB VENTING: From inside the fireplace, insert a minimum of 4' combustion air pipe (end without the
collar) past the damper opening and into the existing fireplace. See Figure E-3.
Figure E-2 Figure E-3
Minimum 4 ft. section of 3
" combustion air
flex pipe
DO NOT block pipe end with insulation or any other sealing materials
Page 10
3
" Exhaust flex pipe
must be connected to the collar on the fireplace insert and the termination cap
Seal area around the vent pipes with non-faced fiberglass insulation
OPTIONAL: We recommend placing non-faced
E
-
4
E
-
g
E
-
6
fiberglass batting insulation between the pipes and existing chimney to prevent heat loss up the chimney. (See Figure E-4)
PLACE NON-FACED FIBERGLASS BATTING INSULATION BETWEEN THE PIPES AND EXISTING CHIMNEY TO PREVENT HEAT LOSS UP THE CHIMNEY.
OPTIONAL:
Figure
3. CONNECT THE VENT SYSTEM TO THE AIR DUCT
A. Place the air duct into the existing fireplace opening. Figure E-5. B. Place a bead of sealant (provided) around the 3” exhaust pipe (red marking) and slide it inside the 3" collar
marked ‘Exhaust’ on the air duct. Secure with (3) ½" self-tapping screws, provided. Apply additional sealant around the joint to ensure an air tight seal. Figure E-6.
C. Apply a liberal bead of sealant (provided) around the 3” collar on the air duct. Slide the 3” combustion intake
pipe over the collar and secure with (3) ½" self-tapping screws, provided. To ensure an air-tight seal, apply additional sealant around the joint. Figure E-6.
Figure
5
AIR DUCT
ure
Fi
SHEET METAL S REWS C
(3 TOTAL)
Page 11
F. POSITION THE FIREPLACE INSERT:
g
F
-
2
F
-
4
g
F
-
g
F
-
1. Slide the insert into the fireplace opening.
2. Secure the air duct onto the insert by positioning the air duct into the channels at the top of the insert and sliding the air duct forward until it stops. Figures F-2 & F-3.
Fi
3. Secure air duct to the insert, at the front, with (2) ½" sheet metal screws, included in the components packet. Refer to Figure F-4.
Fi
ure
ure
1
Position air duct into the
channels and slide forward
Fi
ure
3
Figure
SECURE VENTING WITH
TWO SHEET METAL SCREWS
Page 12
F
-
4. If necessary, level the insert by threading the leveling bolts (included in the components packet) into the nuts mounted in the bottom of the insert behind the lower air passage - 2 each side. See Figure F-5.
Figure
5
LEVELING LEGS (2 PER SIDE)
G. Complete the gas line installation
1. This fireplace is designed to accept either a " or ½" gas line approved for ga s appliances. Consult local building codes to properly size the gas supply line leading to a 3/8" reduction.
2. Run the gas line into the fireplace, preferably through the left gas line hole. A gas line knock-out is also located in the outer bottom of the insert when running the gas line through the bottom.
IMPORTANT: Do not run the incoming gas line in a manner that would obstruct the operation of the fan.
3. Install the manual shut off valve (included with this fireplace insert) upstream from the regulator.
4. Connect the flexible gas line (installed on the gas valve on the millivolt board) to the manual shut off valve.
:
H. Check millivolt board installation:
NOTE: Refer to pages #26 & #27 in this installation manual for complete millivolt board installation procedures.
1. Ensure that all (6) nuts are attached to the mounting studs, securing the millivolt board in position.
2. Verify that the burner venturi is properly positioned over the burner orifice and the burner /cover assembly is secured to the burner heat shield.
3. Check all gas connection for leaks, whether field or factory made.
Page 13
I. Complete the fan wiring installation:
g
I
-
Model #CSK-335 only: Refer also to Figure D-1, page #7.
1. Secure the electrical access panel to the side of the fireplace.
2. Place the thermostatic control switch on the bottom of the fireplace.
3. Plug the cord into the receptacle in the electrical box.
4. Turn the speed control counter-clockwise until it ‘clicks’. This is the ‘OFF’ position.
5. Turn the speed control ‘ON’ by turning the knob clockwise past the ‘click’ - this is the highest setting.
NOTE: The fan will not operate unless the speed control has been turned ‘ON’. The fan will not turn ‘ON’ until sufficient heat is applied to the thermostatic control switch . The fan will turn ‘ON’ and ‘OFF’ automatically when the fireplace heats and cools. Adjust fan to desired speed while it is running.
THERMOSTATIC CONTROL SWITCH POSITION: Prior to adjusting the thermostatic control switch, unplug the 3-prong plug on the fan cord from the receptacle. Adjust the position of the temperature control switch to a warmer location under the firebox to turn the fan ‘ON’ sooner or move it to a cooler location under the firebox to turn the fan ‘ON’ later. The fan will turn on when the sensor in the temperature control switch reaches 110 °F and will turn ‘OFF’ when the sensors reach 90 °F. After adjustment, plug the 3-prong plug on the fan cord into the receptacle.
NOTE: This appliance must be electrically grounded and connected in accordance with local codes, or in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70-Current edition. or the Canadian Electrical Code, CSA C22.1.
Model #CSK-335-RF only: Refer also to Figure D-2, page #8.
1. Secure the electrical access panel to the side of the fireplace.
2. Plug the cord into the receptacle in the electrical box.
3. Upon complete installation of this fireplace, follow the lighting & shutdown instructions at the back of this
ure
Fi
1
manual as well as the instructions included in the remote transmitter for complete fan operation guideline s .
Page 14
J) ATTACH THE 3 pc.SHROUD
g
J
-
g
J
-2 -
(If installing a Full Door Shroud, refer to the instructions that are included with that component.)
Shroud assembly includes: (1) Shroud top (2) 10-24 x 1" RH Philips Mch Screw (#300388) (1) Shroud left side (6) 8 x 3/8" Phillips PH-Type B Blk Zinc SMS (#300121) (1) Shroud right side (4) 10-24 x 1/2" PH Phillips Truss head Screw BZ (300338-1) You will also need the Upper Hood and Lower Grill which are included with fireplace.
ASSEMBLE THE SHROUD - Figure J-1
1. Secure the right and left shroud pieces to the top piece by aligning the (2) holes in the side pieces to the holes in the top piece. Secure with 3/8" phillips head screws provided (2 ea. side) (B).
2. Attach the upper hood to the shroud top piece by aligning the holes on the top flange on the hood to the corresponding mounting holes on lower inside flange of the shroud top piece. Secure with (2) 3/8" phillips head screws (A), provided.
ATTACH THE SHROUD - Figure J-2
1. Align the holes in the tabs located on the inside flange of the shroud side pieces to the threaded mounting nuts located on the inside side flanges of the insert. NOTE: There are (2) for each side.
2. Secure the shroud by inserting (1) 1/2" phillips head screw through the holes and into the threaded mounting nuts.
3. Adjust shroud so that is sets against the fireplace face finish material.
INSTALL THE LOWER GRILL - Figure J-2
1. Partially thread the 1" phillips head screws, provided, into the mounting nuts on each side of the grill and align to the corresponding mounting holes the inside flange of the shroud side pieces.
2. Tighten the phillips head screws to secure the lower grill in position.
NOTE: The grill may be adjusted slightly from
side to side if necessary.
Fi
ure
Lower right side of insert and shroud shown
ure
Fi
NOTE: Screws (A) & (B) are secured
1
from the bottom
Page 15
K. LOG INSTALLATION - Log Set #CXL-500
g
g
g
-
2
p
1. Install base logs, CX1, CX2, CX3, onto the
2. Install ember logs, CX4 & CX5 in front of the
3. Install top logs, CX6 - CX11 onto the base
4. Place rock wool burning embers as desired
NOTE: You will not use all the rock wool ember
This log set includes 11 logs and 1 pkg. rock wool burning embers.
Note: Each log is numbered on the bottom and should be installed according to the instructions and
dia
rams below.
burner as shown in Figure K-1, aligning the mounting holes in the bottom of the logs to the mounting studs in the burner.
IMPORTANT: Push the logs down onto the mounting studs so that the logs will be setting on the burner assembly.
burner as shown in Figure K-1.
logs aligning the logs to the corresponding notched out sections in the base logs. See Figure K-2.
onto the logs and burner to enhance glowing effect and flame appearance.
material at this time. Save for future use.
ure K-1
Fi
Fi
ure K
leted Log Set Installation
Com
Page 16
L. COMPLETE THE INSTALLATION
g
q
1. THIS STEP SHOULD ONLY BE DONE BY A QUALIFIED INSTALLER OR SERVICE TECHNICIAN:
A) Perform lighting and shutdown procedures as described on pages #19-#20 for Model #CSK-335 and pages
#22-#23 for Model #CSK-335-RF. This should be done prior to re-installing the glass so that any necessary adjustments can be made and proper operation and log position verified.
2. RE-INSTALL THE GLASS. Refer also to Figure L-1.
Fi
ure L-1
WARNING: DO NOT OPERATE THIS FIREPLACE WITH THE GLASS ASSEMBLY REMOVED, CRACKED, OR BROKEN. Replacement of the glass assembly should be done by a licensed or
ualified service person.
A. Align the 2 slots in the top of the glass assembly over
the 2 tabs on the fireplace (at the top).
B. Place the glass assembly so it is flush with the front of
the fireplace front.
C. While holding the glass assembly, pull the latches out
TWO GLASS LATCHES
and secure over the glass latch clips on the bottom of the glass frame locking it in place.
Left intentionally blank.
Page 17
M. MODEL CSK-335 ONLY: THERMOSTAT - WALL SWITCH - REMOTE INSTALLATION
If desired, a thermostat (wireless style available), wall switch, or remote control assembly may be used to turn the fireplace ‘OFF’ and ‘ON’. Only ONE of these may be installed. Follow instructions included with each assembly.
OPTIONAL: Disconnect the ON/OFF rocker switch wires from the top & bottom terminals on the back side of the gas valve. Refer to Figure Q-1, page #28 of this manual.
NOTE: INSTALLATION OF A THERMOSTAT OR WALL SWITCH SHOULD ONLY BE DONE BY A QUALIFIED INSTALLER.
Run low-voltage (thermostat) wires from the terminals on the gas valve to the desired location of the wall switch or thermostat.
Attach the appropriate connector to each wall switch / thermostat wire and connect to the top and bottom terminals on the gas valve marked ‘TH’.
Follow instructions included with the remote control.
IMPORTANT: The insulated cover included with the remote control must be placed over the remote receiver to protect it from overheating.
Remote Control Wiring Diagram
CAUTION: DO NOT CONNECT HIGH VOLTAGE (115V) WIRE TO THE GAS VALVE!
WALL SWITCH / THERMOSTAT USERS:
IMPORTANT: If the ON/OFF rocker switch wires are not disconnected, the ON/OFF rocker switch on the millivolt board must be in the ‘OFF’ position
REMOTE CONTROL USERS:
for proper operation of any of these components. If the rocker switch is ‘ON’, the fireplace burner will
operate until it is turned ‘OFF’ by the rocker switch. A wall switch, thermostat, or remote control will not turn the fireplace ‘OFF’ when it has been turned ‘ON’ by the rocker switch.
NOTE: The fireplace must be turned ‘ON’ and ‘OFF’ by the same method. For example: If the fireplace is turned ‘ON’ by the remote control, it must be turned ‘OFF’ by the remote control.
Figure M-2
Thermostat Wiring Diagram
Figure M-1
Page 18
N. MODEL #CSK-335 ONLY: LIGHTING AND SHUTDOWN PROCEDURES
NOTE: Prior to lighting, check all fittings for leakage. This is accomplished by applying soapy water on all connections made. If there is any leakage, bubbles will appear at the point of connection. If bubbles occur, tighten the fittings until the bubbles no longer appear.
NOTE: The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½ psi.
NOTE: The appliance must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas line at test pressures equal to or less than 1/2 psig (3.5 kPa).
Pressure check taps for the manifold (outgoing) and inlet (incoming) pressures are located in front of the gas valve. The left pressure tap is the manifold pressure and the right pressure tap is the incoming pressure. Follow instructions on page #21 for checking these pressures.
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
1. This appliance has a pilot which must be lighted by hand.
2. BEFORE LIGHTING, smell all around the appliance for gas.
3. Use only your hand to push in or turn the gas control knob.
4. Do not use this appliance if any part has been under water.
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
NOTE: Read 1-8 before lighting the fireplace for the first time. Refer to Figure N-1, page #20.
1. Set the thermostat to the lowest setting, if installed.
2. Turn off all electric power to the appliance. (Fan)
3. To access the gas valve & controls, open the doors or lower grill.
4. Push in control knob (A) slightly and turn clockwise to "OFF”.
NOTE: Knob cannot be turned from "PILOT" to "OFF" unless knob is pushed in slightly. Do not force.
5. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow the safety information
6. Find the pilot - follow metal tube from gas control. The pilot is located inside the combustion chamber.
7. Push the control knob (A) on the gas valve in slightly and turn counterclockwise to "PILOT".
8. Push in the control knob all the way and hold in. Press the BLACK piezo igniter button (B).
FOR YOUR SAFETY - READ BEFORE LIGHTING
When lighting the pilot, follow these instructions exactly.
DUE TO HIGH SURFACE TEMPERATURES, KEEP CHILDREN, CLOTHING AND FURNITURE AWAY.
Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and
Never use tools. If the knob will not push in, or turn by
ventilation air.
hand, don’t try to repair it, call a qualified service technician. Forced or attempted repair may result in a fire or explosion, and loss of warranty.
WHAT TO DO IF YOU SMELL GAS:
Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system which has been under water.
*Do not touch electrical switches. *Do not try to light any appliance. *Do not use any phone in your building. *Follow the gas supplier’s instructions. *Immediately call your gas supplier from a neighbor’s phone. *If you cannot reach your gas supplier, call the fire department.
LIGHTING INSTRUCTIONS
above and on the front cover of this installation manual. If you don't smell gas, go to the next step.
Honeywell Pilot
Page 19
The pilot will generally light with two or three pushes on the igniter. Hold the knob in for about one (1) minute after the pilot is lit. Release knob and it will pop back out. Pilot should remain lit. If it goes out, repeat steps 4 through 8.
*If knob does not pop out when released, stop and immediately call your service technician or gas supplier. *If the pilot will not stay lit after several tries, turn the gas control knob to "OFF" and call your service technician or gas supplier.
9. Push the control knob on the gas valve in slightly and turn
counterclockwise to the "ON" position.
Figure N-1
10. The burner can now be turned ‘ON’ or lit by pressing the ON/OFF rocker switch (C) located beside the valve OR by setting the thermostat or remote control to the desired setting.
11. NOTE: When the fireplace is initially lit, condensation will appear on the glass, this is normal
in all gas fireplaces, and will disappear in one to three minutes.
TO TURN THE BURNER OFF:
To turn the burner ‘OFF’, press the ON/OFF rocker switch to ‘OFF’, flip ‘off ’ the wall switch or adjust the setting on the thermostat or remote control. NOTE: The pilot will stay lit.
TO TURN THE PILOT OFF:
To turn off the pilot, push in and turn the control knob to the "OFF" position. DO NOT FORCE.
NOTE: A PAINT SMELL WILL OCCUR DURING THE FIRST FEW HOURS OF BURNING. IT IS RECOMMENDED TO LEAVE THE FAN OFF DURING THIS PERIOD AS THIS WILL SPEED UP THE PAINT CURING PROCESS.
INITIAL BURN PERIOD
DUE TO THE MAKEUP OF THE FIBER LOGS & REFRACTORY, THE CURING PROCESS MAY TAKE UP TO 4 HOURS OF BURN TIME. DURING THIS PERIOD, THE LOGS & REFRACTORY WILL DISCOLOR, BUT WILL RETURN TO THEIR TRUE COLOR ONCE THE CURING PROCESS IS COMPLETE. DO NOT BURN THIS FIREPLACE WITHOUT THE GLASS PROPERLY IN PLACE.
**MAKE SURE THE HOMEOWNER IS AWARE OF THIS**
NOTE: Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition. Young children should be carefully supervised when they are in the same room as the appliance.
Clothing or other flammable material should not be placed on or near the appliance.
NOTE: THIS FIREPLACE MAY PRODUCE NOISES OF VARYING DEGREE AS IT HEATS AND COOLS DUE TO
METAL EXPANSION AND CONTRACTION. THIS IS NORMAL AND DOES NOT AFFECT THE PERFORMANCE OR LONGEVITY OF THE FIREPLACE.
Page 20
MODEL #CSK-335 ONLY: PRESSURE TEST - MANIFOLD & INLET PRESSURE
prop
IMPORTANT NOTICE: A pressure check tap for both the manifold (outgoing) and inlet (incoming) pressure has been incorporated into
the valve. The left pressure tap is the manifold pressure and the right pressure tap measures the incoming pressure. Follow the instructions below for
TO CHECK THE MANIFOLD PRESSURE:
1. Light pilot.
2. Loosen the manifold pressure tap [D] by turning the screw counter-clockwise.
3. Attach manometer to pressure tap using a 5/16" I.D. hose [F].
4. Push the control knob [A] on the gas valve in slightly and turn to the ‘ON’ position.
5. Turn the burner ‘ON’ by pressing the rocker switch [C] to the ‘ON’ position and note manometer reading.
6. Depress the rocker switch [C] to the ‘OFF’ position.
7. Disconnect manometer hose and tighten screw (clockwise). Screw should be snug, do not over tighten.
8. Attach manometer to manifold pressure tap to verify that it is completely sealed.
Manometer should read no pressure when the rocker switch is depressed to the ‘ON’ position.
NOTE: If manifold pressure reading is within the normal range, an incoming pressure check is not necessary. A too high or too low pressure reading warrants an inlet (incoming) gas pressure check.
TO CHECK THE INLET PRESSURE:
1. Loosen Inlet pressure tap screw [E] by turning screw counter-clockwise.
2. Attach manometer using a 5/16" I.D. hose [F].
3. Light the pilot.
4. Push the control knob on the gas valve (A) in slightly and turn to the ‘ON’ position, (burner should not come ‘ON’) and note
manometer reading.
5. Turn the burner ‘ON’ by pressing the rocker switch [C] to the ‘ON’ position. Check the pressure to ensure that it stays near the
maximum inlet pressure.
6. Press the rocker switch [C] to the ‘OFF’ position.
7. Turn the pilot ‘OFF’ by pushing the control knob in slightly and turning to the ‘OFF’ position.
8. Disconnect hose and tighten screw (clockwise). Screw should be snug, do not over tighten.
9. Relight pilot. Push the control knob [A] in slightly and turn to the ‘ON’ position. Attach manometer to the inlet pressure tap to verify
that it is completely sealed. Manometer should read no pressure.
NOTE: If Inlet pressure reading is too high or too low, contact the gas company. Only a qualified gas service technician should adjust the incoming gas pressure.
CAUTION: A LOW PRESSURE READING
CAN CAUSE DELAYED IGNITION.
er pressure testing procedures.
Figure N-2
Page 21
MODEL #CSK-335-RF ONLY: LIGHTIN G AND SHUTDOWN PROCEDURES
NOTE: Prior to lighting, check all fittings for leakage. This is accomplished by applying soapy water on all connections made. If there is any leakage, bubbles will appear at the point of connection. If bubbles occur, tighten the fittings until the bubbles no longer appear.
NOTE: The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½ psi.
NOTE: The appliance must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas line at test pressures equal to or less than 1/2 psig (3.5 kPa).
Pressure check taps for the manifold (outgoing) and inlet (incoming) pressures are located in front of the gas valve. The left pressure tap is the manifold pressure and the right pressure tap is the incoming pressure. Follow instructions on page #24 for checking these pressures.
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
1. This appliance has a pilot which must be lighted by hand.
2. BEFORE LIGHTING, smell all around the appliance for gas.
3. Use only your hand to push in or turn the gas control knob.
4. Do not use this appliance if any part has been under water.
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
NOTE: Read 1-8 before lighting the fireplace for the first time. Refer to Figure N-3, page #23.
1. Set the thermostat to the lowest setting.
2. Turn off all electric power to the appliance.
3. Open the doors or lower grill to access the gas valve & controls.
4. Push in control knob slightly and turn clockwise to the "OFF” position.
NOTE: Knob cannot be turned from "PILOT" to "OFF" unless knob is pushed in slightly. Do not force.
5. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP!
6. Find the pilot - follow metal tube from gas control. The pilot is located inside the combustion chamber.
7. Push the control knob on the gas valve in slightly and turn counterclockwise to "PILOT".
8. Push in the control knob all the way and hold in. Push the plunger on the piezo until the pilot is lit.
FOR YOUR SAFETY - READ BEFORE LIGHTING
When lighting the pilot, follow these instructions exactly.
Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
Never use tools. If the knob will not push in, or turn by hand, don’t try to repair it, call a qualified service technician. Forced or attempted repair may result in a fire or explosion, and loss of warranty.
Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system which has been under water.
Follow the safety information above. If you don't smell gas, go to the next step.
The pilot will generally light with two or three pushes on the igniter. When the pilot is lit, the LED on the control will come on after approximately 60 seconds and will blink continuously. Release knob and it will pop back out. Pilot should remain lit. If it goes out, repeat steps 4 through 8.
DUE TO HIGH SURFACE TEMPERATURES, KEEP CHILDREN, CLOTHING AND FURNITURE AWAY.
This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air.
WHAT TO DO IF YOU SMELL GAS: *Do not touch electrical switches.
*Do not try to light any appliance. *Do not use any phone in your building. *Follow the gas supplier’s instructions. *Immediately call your gas supplier from a neighbor’s phone. *If you cannot reach your gas supplier, call the fire department.
CSK-335-RF
Pilot
Page 22
*If knob does not pop out when released, stop and immediately call your service technician or gas supplier.
R
R
*If the pilot will not stay lit after several tries, turn the gas control knob to "OFF" and call your service technician or gas supplier.
9. Push the control knob on the gas valve in slightly and turn counterclockwise to the "ON" position. If the manual switch is in the
LOCAL position, the main burner will turn on immediately.
IMPORTANT: On the initial use of a transmitter, a
recognition operation is required between the receiver /
OUTLET PRESSURE TAP
MOTO COVER
MOTO
INLET PRESSURE TAP
PIEZO
WIRING TERMINALS
valve and the transmitter.
1. Turn the gas control to the PILOT position.
2. Move the LOCAL / REMOTE switch to the LOCAL
position for at least two seconds, then move the switch to the REMOTE position.
3. Press the FAN or FLAME button on the transmitter
within 30 seconds of the switch change.
4. Turn the gas control knob to the ON position.
WRENCH BOSS
M16681A
LOCAL
REMOTE
GAS CONTROL KNOB
Figure N-3
LED
PILOT ADJUSTMENT SCREW
FUEL CONVERSION PLUG
The LED will blink indicating that the transmitter will now work with the receiver / valve. If the switch stays in the REMOTE position, the RT8220A Transmitter will control the main valve, flame modulation level and fan control.
If the LOCAL / REMOTE switch is in the LOCAL position, the receiver / valve will be at the highest fixed pressure setting.
NOTE: When this fireplace insert is initially lit, condensation will appear on the glass, this is normal in all gas fireplaces, and will
disappear as the fireplace heats.
TO TURN THE BURNER OFF: LOCAL SETTING: Turn the control knob clockwise to the pilot position. REMOTE SETTING: The RT8220A transmitter can shut off the main burner and fan, however, the control is still ‘ON’ and a command
from the transmitter can turn the main burner and fan ‘ON’.
TO TURN OFF THE SYSTEM:
1. Open the doors or lower grill to access the gas valve & controls.
2. Turn the gas control knob clockwise to the ‘OFF’ position. This closes the main gas and safety valves. The transmitter cannot turn
on the main burner or the fan.
NOTE: A PAINT SMELL WILL OCCUR DURING THE FIRST FEW HOURS OF BURNING. IT IS RECOMMENDED TO LEAVE THE FAN OFF DURING THIS PERIOD AS THIS WILL SPEED UP THE PAINT CURING PROCESS.
INITIAL BURN PERIOD
DUE TO THE MAKEUP OF THE FIBER LOGS & REFRACTORY, THE CURING PROCESS MAY TAKE UP TO 4 HOURS OF BURN TIME. DURING THIS PERIOD, THE LOGS & REFRACTORY WILL DISCOLOR, BUT WILL RETURN TO THEIR TRUE COLOR ONCE THE CURING PROCESS IS COMPLETE. DO NOT BURN THIS FIREPLACE WITHOUT THE GLASS PROPERLY IN PLACE.
**MAKE SURE THE HOMEOWNER IS AWARE OF THIS**
NOTE: Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition. Young children should be carefully supervised when they are in the same room as the appliance.
Clothing or other flammable material should not be placed on or near the appliance.
NOTE: THIS FIREPLACE MAY PRODUCE NOISES OF VARYING DEGREE AS IT HEATS AND COOLS DUE
TO METAL EXPANSION AND CONTRACTION. THIS IS NORMAL AND DOES NOT AFFECT THE
Page 23
MODEL #CSK-335-RF ONLY: PRESSURE TEST - MANIFOLD & INLET PRESSURE
p
R
R
A
IMPORTANT NOTICE: A pressure check tap for both the manifold (outgoing) and inlet (incoming) pressure has been incorporated into
the valve by HONEYWELL Controls. The left pressure tap is the manifold pressure and the right pressure tap measures the incoming
ressure. Follow the instructions below for proper pressure testing procedures.
NOTE: Both the inlet and outlet pressure taps have a captive screw.
1. Be sure the gas control knob is in the PILOT position.
2. Light the pilot.
3. Loosen, but do not remove the outlet tap captive screw.
4. Attach a plastic tube with a 1/4" shell ID and connect the manometer.
5. Turn the gas control knob to the ON position.
6. Check the outlet tap pressure.
7. Turn the gas control knob to the OFF position.
8. Shut off the gas supply at the manual valve in the gas piping to the appliance or, for LP, at the tank.
9. Loosen, but do not remove the inlet tap captive screw.
10. Attach a plastic tube with a 1/4" shell ID and connect the manometer.
11. Turn on the gas supply at the manual valve.
12. Check the inlet tap pressure.
13. Turn the gas control knob to the OFF position.
14. Repeat the Gas Leak Test at the pressure tap with the main burner operating.
15. Always tighten the screws in the pressure taps after disconnecting the plastic tubes.
Figure N-4
OUTLET PRESSURE TAP
MOTO COVER
MOTO
WRENCH BOSS M16681A
GAS LEAK TEST:
1. Paint the pipe connec tion upstream of the gas valve with a rich soap and water solution. Bubbles indicate a gas leak.
2. If a leak is detected, tighten the pipe connections.
3. Light the main burner.
4. With the main burner in operation, paint the pipe joints (including adaptors) and valve inlet and outlet with a rich soap and water solution.
5. If another leak is detected, tighten the adapter screws, joint, and pipe connections.
6. Replace the part if the leak cannot be stopped.
LOCAL
REMOTE
GAS CONTROL KNOB
INLET PRESSURE TAP
PIEZO
LED
WIRING TERMINALS
PILOT
DJUSTMENT
SCREW
FUEL CONVERSION PLUG
Page 24
O. MAINTENANCE REQUIREMENTS
1. The appliance should be inspected at least once a year
by a professional service person.
NOTE: INSTALLATION AND REPAIR SHOULD BE DONE ONLY BY A QUALIFIED SERVICE PERSON. THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A QUALIFIED SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIALS, ETC. IT IS IMPERATIVE THAT CONTROL COMPARTMENTS, BURNERS AND CIRCULATION AIR PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN.
2. The compartment below the firebox (behind the lower
grill) must be cleaned at least once a year, more frequent cleaning may be required due to excessive lint from carpeting, bedding materials, or other fibrous materials. It is imperative that the burner be cleaned once a year.
FAN The fan should be disconnected from electrical current, and cleaned (vacuumed) every six months. The bearings are sealed and require no oiling.
VENT SYSTEM Annual examination of the venting system by a qualified agency is required.
IF THE VENT-AIR INTAKE SYSTEM IS DISASSEMBLED FOR ANY REASON, REINSTALL PER THE INSTRUCTIONS PROVIDED WITH THE INITIAL INSTALLATION.
The flow of combustion and ventilation air must not be obstructed.
IMPORTANT: ANY SAFETY SCREEN OR GUARD
REMOVED FOR SERVICING MUST BE REPLACED PRIOR TO OPERATING THE APPLIANCE.
CAUTION: LABEL ALL WIRES PRIOR TO
DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. VERIFY PROPER
OPERATION AFTER SERVICING.
MILLIVOLT BOARD SYSTEM
1. Annual cleaning of the burner is required. The burner
& cover assembly may be removed for easier access.
2. Refer to pages #26-#27 for complete instruction on
removing & reinstalling the burner & cover assembly.
3. Visually check for blocked port holes, especially near
the pilot. Blocked port holes may cause delayed ignition.
4. Replace the burner & cover following instructions on
pages #26-#27.
5. Visually check the pilot light and burner when they are burning. The flames should be steady, not lifting or
floating.
CSK-335 Pilot CSK-335-RF Pilot
Burner Orifice
GLASS CLEANING & REPLACEMENT
Clean glass only when cool and only with nonabrasive
cleansers.
Do not operate this fireplace with the glass/frame
assembly removed, cracked or broken.
The glass assembly, Part #CXL-057T, shall only be
replaced as a complete unit, as supplied by Hussong Mfg. Co., Inc.
Replacement of the glass assembly, Part #CXL-057T,
must only be performed by a licensed or qualified service person. DO NOT SUBSTITUTE MATERIALS.
Do not strike or slam glass door assembly.
CAUTION: KEEP THE APPLIANCE AREA CLEAR OF
COMBUSTIBLE MATERIALS, SUCH AS GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
Page 25
P. MILLIVOLT BOARD REMOVAL & INSTALLATION. See Figures P-1 - P-3.
REMOVE THE MILLIVOLT BOARD ASSEMBLY:
1. Open the doors and/or lower grill to access the gas valve & controls. NOTE: It is not necessary to remove the shroud or full door shroud to remove the millivolt board.
2. Turn the black control knob to the ‘OFF” position.
3. Shut off the gas supply at the manual shut off valve.
4. Disconnect gas flex line tube from the manual shut off valve.
5. Model #CSK-335: Disconnect any wall switch, remote control, or thermostat wire from the’TH’ terminals on the gas valve.
6. Model #CSK-335-RF: Unplug the fan cord from the receptacle, then disconnect the (2) wires from the fan cord. Note: The wires will remain connected to the back of the gas valve. Refer to wiring diagram, Figure D­2, page #8.
7. Remove the glass assembly, refer to Figure C-1, page #6. Set aside on a protected surface where it will not become damaged.
8. Remove the log set and place on a protected surface where they will not beco me damaged.
9. Loosen and remove the (2) nuts securing the burner assembly. Refer to Figure P-1. Remove the burner assembly from the insert firebox.
10. Lift up the front edge of the heat shield and slide out of the firebox. Figure P-2.
Figure P-1
securing burner assembly
11. Loosen and remove the (6) nuts securing the millivolt board, Figure P-3. Carefully lift the board up and remove from the firebox.
Remove (2) nuts
Figure P-2
Heat Shield
Burner Assembly
Figure P-3
(6) nuts securing the millivolt board
Page 26
INSTALL THE MILLIVOLT BOARD ASSEMBLY:
)
NOTE: The millivolt board must be fitted with a gasket, (included) to seal the board. Mak e certain this gasket is properly placed around the opening before installing the millivolt board.
1. Grasp the millivolt board with both hands and place into the insert firebox, aligning the (6) mounting holes in the board to the mounting studs on the bottom of the firebox. IMPORTANT: BE CAREFUL NOT TO DAMAGE THE GASKET UNDER THE BOARD.
CAUTION: BEFORE SECURING THE BOARD INTO PLACE, MAKE CERTAIN THAT ALL OF THE WIRES (ATTACHED UNDER
2. Secure the board in place with the (6) nuts removed in step #11, page #26. Refer to Figure P-3, page #26.
3. Re-install the heat shield by positioning the cut-out sections in the heat shield over the pilot assembly and burner orifice. Center the heat shield side to side and slide all the way to the back. Refer to Figure P-2, page #26.
4. Re-install the burner assembly onto the heat shield, aligning the burner venturi over the burner orifice and the (2) mounting holes to the mounting holes in the heat shield. Secure with the sheet metal screws removed in step #9, page #26. Refer to Figure P-1, page #26.
5. Re-install the logs. Refer to page #16 for proper placement if necessary.
6. Connect the flexible gas line to the manual shut-off valve.
7. Model #CSK-335: Re-connect any wall switch, remote control or thermostat wires onto the top & bottom terminals on the gas valve marked ‘TH’.
8. Model #CSK-335-RF: Re-connect the wires from the valve to the fan cord. Refer to wiring diagram, Figure Q-2, page #29. Plug the 3-prong plug on the fan cord into the receptacle.
9. Re-install the glass assembly.
10. Check all connections for gas leaks, whether field or factory made.
11. Verify proper operation of the fireplace & log position. Refer to the lighting instructions in this manual.
12. Close doors and/or lower grill.
THE BOARD
IMPORTANT: CHECK ALL CONNECTIONS, WHETHER FIELD OR FACTORY MADE, FOR LEAKS!
ARE CLEAR AND UNOBSTRUCTED.
Page 27
O. TROUBLE SHOOTING GUIDE
NOTE: The millivolt board includes the following items: Valve, pilot assembly, piezo, electrode, on/off rocker switch, burner, burner venturi tube, & burner orifice. If any of these items are defective, contact your dealer for the appropriate repair / replacement procedures to follow.
WARNING: DO NOT ATTEMPT TO SERVICE THIS INSERT IF YOU ARE NOT A QUALIFIED INSTALLER OR REPAIRMAN.
1. If the fireplace insert fails to ignite, a qualified service person should check the fireplace install ation.
2. It is imperative that the control compartment, burner and circulation air passageways of this insert be kept clean. This is necessary to provide adequate combustion and ventilation air.
3. All of the working parts of this fireplace can be removed at one time. Before removing millivolt board, check for loose wires.
PROBLEM
1. No spark when piezo Wire on back of piezo button is loose or off. Push wire back into place.
button is depressed.
2. Pilot won't light Gas shut ‘OFF”. Turn Gas ‘ON’.
3. Pilot won't stay lit Not holding black control knob in long enough. Hold button in longer to heat thermocouple
(or Generator - RF Valve).
against firebox back & sides. high-temp sealant.
WIRING DIAGRAM
MODEL #CSK-335
CAUSE SOLUTION
Wire from piezo to electrode is loose at electrode. Reconnect wire.
Electrode moved out of position. Realign electrode with 1/8" space between it & the pilot.
Gas line not purged. Hold black control knob in long enough to purge line.
Not holding black control knob in long enough. Hold in longer.
No spark at piezo. See problem #1.
Thermocouple (or Generator - RF Valve) Check connection on valve and tighten if connection loose at valve connection. necessary.
Pilot hood misdirecting pilot flame Check pilot flame location. Flame must be
from thermocouple (or Generator - RF Valve). burning on generator(s) and thermocouple (CSK-335).
Refractory panels not positioned Secure refractory panels with
Page 28
PROBLEM CAUSE SOLUTION
4. Burner won't light. Pilot not lit. Relight pilot.
Regulator valve not turned “ON”. Turn valve to "ON"
Rocker switch not turned “ON”. (Model CSK-335). Depress switch.
Rocker switch wires not connected. (Model CSK-335). Check wiring diagram Figure Q-1 to ensure that all wires are secure.
Generator wires loose at regulator terminals Reposition wire an tighten screws. See Figures Q-1 & Q-2 for wiring instructions.
Generator wire grounded out Nuts securing millivolt board may need due to pinching of wires. loosening to remove pinched wire.
Generator is not producing enough Replace generator. millivolts to operate burner.
Wall switch, remote control or thermostat not Connect properly or disconnect connected properly or turned to wrong setting. and use ON/OFF switch only. See Figures M-1 & M-2, page #18. (Model CSK-335).
5. Burner won't stay lit. Generator wires loose on Reposition wires and tighten screws
valve terminals. See Figures Q-1 & Q-2 for wiring instructions.
Generator wire grounded out Nuts securing millivolt board may need due to pinched wires. loosening to remove pinched wire.
Generator is not producing enough Check millivolt reading, replace millivolts to sustain burner operation. generator if necessary.
Refractory panels not positioned Secure refractory panels with against firebox. high-temp sealant.
WIRING DIAGRAM
Model CSK-335-RF
Figure Q-2
FAN
BURNER
PILOT
L1 (HOT)
L2
OUTLET PRESSURE TAP
INLET PRESSURE TAP
PIEZO
BURNER ASSEMBLY
PILOT TUBE
THERMOPILE LEADWIRE
THERMOPILE LEADWIRE
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
GAS CONTROL KNOB
LED
Page 29
REPLACEMENT PARTS
Replacement parts are available through your local dealer. Information on optional components not listed
MILIIVOLT BOARD AND PARTS - CSK-335
CXL-770 Chaska Millivolt Board - Natural Gas 700-098 Pilot Hood CXL-771 Chaska Millivolt Board - LP Gas 700-203 Manual Shut off Valve 700-023 On/Off Rocker Switch 700-213B 18" Flexible Gas Line – Black (gas line to valve) 700-057 Honey well gas valve- Natural Gas 700-226F Flexible Gas Line ( 700-057-1 Honeywell gas valve - LP Gas 700-235 Natural Gas orifice #35 700-063 Pilot/Generator/Thermocouple - Natural Gas 700-250 LP Gas orifice #50 700-063-1 Pilot/Generator/Thermocouple - LP Gas OCK-H35L Natural Gas conversion kit 700-090 Piezo Igniter w/ wire OCK-H50L LP Gas conversion kit 700-060 Flexible Pilot Tubing 700-092 Millivolt Generator 700-075 Conv ersion Screw - NG 700-076 Conversion Screw - LP
MILIIVOLT BOARD AND PARTS - CSK-335-RF
CXL-800RF Chaska XL Modulating Millivolt Board - Natural Gas 700-213B 18" Flexible Gas Line - Black 700-107 Honeywell RF Valve - Natural Gas 700-224 3/8" Flexible Gas Line- Valve to Burner connection 700-108 Remote control - RF Valve 700-235 Natural Gas orifice #35 700-109 Honeywell RF Pilot Assembly 700-250 LP Gas orifice #50 700-060 Flexible Pil ot T ubing (Valve to Pilot) CXL-H35N-RF Natural Gas Conversion Kit 700-083 Piezo Ignitor w/ wire CXL-H50L-RF LP Gas conversion kit 700-092 Millivolt Generator 700-203 Manual Shut off Valve CXL-135 Burner assembly
GLASS & GLASS GASKET FAN ASSEMBLIES - REPLACEMENT
CXL-057T Valance w/ glass & gasket CSK-028 Fan Assembly - Model #CSK-335 600-083 Speed control / receptacle assembly - #CSK-335 CSK-028-RF Fan Assembly - Model #CSK-335-RF
LOG SET REFRACTORY PANELS
CXL-500 Log Set CXL-G900 Refractory Panel Set - 3 pc. back & sides Base Logs: CX1 Log CX4 Log CXL-G900B Back Refractory panel CX2 Log C5X Log CXL-G900S Side Refractory panel - 1 pc. CX3 Log CXL-G902 Top Refractory panel
Top Logs: CX6 Log CX9 Log CX7 Log CX1 0 Log CX8 Log CX11 Log
900-REMB Rock wool Embers
*Consult your dealer for information on optional accessories available for this fireplace.
SHROUDS: Contact your dealer for available styles & finishes.
This appliance tested & certified by: OMNI-Test Laboratories, Inc. 13327 NE Airport Way Portland, Oregon 97230
Models #CSK-335 / CSK-335-RF - US & CANADIAN INSTALLATIONS 204 Industrial Park Drive September 2008 Lakefield, MN 56150
below, is also available through your dealer.
Valve to burner connection)
(Valve to Pilot) CXL-135 Burner assembly
Hussong Manufacturing Company, Inc.
www.kozyheat.com
Page 30
KOZY HEAT
3
LIMITED 10 YEAR WARRANTY
This Limited 10 Year Warranty will not become effective until the warranty registration form has been completed and mailed to Hussong Manufacturing Co., Inc., P.O. Box 577, Lakefield, MN 56150. This registration form must be received within 30 days of installation. Failure to do so may result in delayed warranty coverage and submission of proof of purchase will be required.
Hussong Manufacturing Co., Inc. warranties to the original purchaser of this Kozy Heat Fireplace, that it is free of defects in materials and workmanship at the time of manufacture.
Subject to the following conditions & requirements, Hussong Manufacturing Co., Inc. extends the following limited warranty under normal use and service, with respect to the Kozy Heat line of gas burning fireplaces.
YEAR 1: Subject to the conditions & requirements listed below, within the first year from date of purchase, Hussong Manufacturing Co., Inc. shall, at its discretion, replace or repair any such defect in material or workmanship, at Hussong Manufacturing Co., Inc.’s expense, including reasonable labor costs to repair or replace the defective component, if a factory pre­authorization is given for the repair.
YEARS 2 - 10: Subject to the conditions & requirements listed below, beginning with the first day of the second year and continuing through the tenth year, Hussong Manufacturing Co., Inc., will at its discretion, provide repair or replacement parts at current list prices for any defect in material or workmanship of components, including optional components and accessories (if available). Hussong Manufacturing Co., Inc. shall not be responsible for any installation, labor, transportation or other indirect costs.
To make a claim under this warranty, the purchaser must first contact the dealer/installer from whom the fireplace was purchased.
This limited warranty will be void if the fireplace is not installed by a qualified installer and according to the installation instructions. Use of unauthorized components will make this warranty null and void.
This limited warranty also is void if the fireplace is not operated, at all times, according to the operating instructions furnished.
This warranty is limited to defects in material and workmanship. It does not apply to any product that has been subject to negligence, misapplication, improper installation. Remote control warranties are covered by Ambient Technologies, Inc., and are excluded from this Limited Warranty.
No person is authorized to extend the time of this warranty or to accept on Hussong Manufacturing Co., Inc.’s behalf any additional obligation of liability connected with the unit.
LIMITATION OF LIABILITY
It is expressly agreed and understood that this warranty is Hussong Manufacturing Co., Inc.’s sole obligation and purchaser’s exclusive remedy for defective fireplace equipment. Hussong Manufacturing Co., Inc. shall not be liable for any consequential, incidental or contingent damages whatsoever. The foregoing warranty is exclusive and in lieu of all other expressed warranties. Hussong Manufacturing Co., Inc. shall not be held to implied warranties, including but not limited to the implied warranties or merchantability and fitness for a particular purpose. This warranty replaces all previous warranty policies.
Some states do not allow the exclusion or limitation of incidental or consequential damages or limitations on how long an implied warranty lasts, so the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
Hussong Manufacturing Co., Inc. reserves the right to make changes at any time, without notice, in design, material, specifications and prices. Hussong Manufacturing Co., Inc. reserves the right to discontinue models and products.
1. You are the orig inal purchaser. This warranty is not transferable.
2. Installation of the fireplace is performed by a qualified in staller.
3. Installation and operation must comply with installation and operation instructions.
4. Paint and g lass gaskets are covered for 30 days from date of purchase.
5. Components broken, (including glass panels), during shipping, careless handling of components, or defects resulting from improper installation, misuse of the fireplace and components are not covered under this warranty.
6. This warranty does no t cover any part of the fireplace or any components which have been exposed to or submerged under water.
7. Hussong Manufacturing Co., Inc. must be notified by the dealer the fireplace was purchased from or a qualified installer or service technician of the defect.
8. Annual service of the fireplace as required in the installation manual, is performed by a qualified installer/service tech nician. (Copies of such service records may be required to claim a warranty.)
9. All previous warranty/service has been performed by a qualified installer or service technician. (Copies of such service record s may be required to claim a warranty.)
WARRANTY CONDITIONS & REQUIREMENTS:
Effective July 01, 200
Page 31
LIFETIME WARRANTY
THIS LIFETIME WARRANTY COVERAGE WILL BE EXTENDED AS DESCRIBED BELOW PROVIDED ALL WARRANTY
CONDITIONS AND REQUIREMENTS ARE MET AS OUTLINED IN THE 10 YEAR LIMITED WARRANTY POLICY.
LIFETIME WARRANTY IS EXTENDED AS FOLLOWS: Hussong Manufacturing warranties to the original purchaser that the firebox, heat
exchanger, fiber logs, burner tube and glass of this Kozy Heat fireplace will not be defective in material or workmanship under normal use and service for as long as you own this product. If any of these components fail due to defects in material or workmanship under normal use and service, Hussong Manufacturing Co., Inc. will, at its sole discretion, repair or replace the defective component. This LIFETIME WARRANTY does not cover any installation, labor, transportation or other indirect costs arising from defective components.
This Lifetime warranty will be void if the fireplace is not installed by a qualified installer and according to the installation instructions. Use of unauthorized components will make this warranty null and void. This lifetime warranty also is void if the fireplace is not operated, at all times, according to the operating instructions furnished. This warranty is limited to defects in material and workmanship of components specified. It does not apply to any product that has been subject to negligence, misapplication, improper installation.
No person is authorized to extend the time of this Lifetime warranty or to accept on Hussong Manufacturing Co., Inc.’s behalf any additional obligation of liability connected with the unit.
Hussong Manufacturing Co., Inc. may fully discharge all obligations with respect to this Lifetime warranty by refunding the wholesale price of the defective component(s).
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TO ACTIVATE THIS LIFETIME WARRANTY COVERAGE, THIS REGISTRATION CARD MUST BE COMPLETED AND MAILED WITH YOUR COMPLETED 10 YEAR LIMITED WARRANTY FORM WITHIN 30 DAYS OF INSTALLATION.
PURCHASER’S NAME: INSTALLATION DATE:
ADDRESS: MODEL#: SERIAL #:
TELEPHONE #
INSTALLER NAME:
ADDRESS: TELEPHONE #
LIFETIME WARRANTY COVERAGE
LIMITATION OF LIABILITY
It is expressly agreed and understood that this Lifetime warranty is Hussong Manufacturing Co., Inc.’s sole obligation and original purchaser’s exclusive remedy for defective fireplace equipment. Hussong Manufacturing Co., Inc. shall not be liable for any consequential, incidental or contingent damages whatsoever other than those incurred by Hussong Manufacturing Co., Inc. to repair or replace the defective component. The foregoing warranty is exclusive and in lieu of all other expressed warranties. Hussong Manufacturing Co., Inc. shall not be held to implied warranties, including but not limited to the implied warranties or merchantability and fitness for a particular purpose. This lifetime warranty replaces all previous lifetime warranty policies.
Hussong Manufacturing Co., Inc. reserves the right to make changes at any time, without notice, in design, material, specifications and prices. Hussong Manufacturing Co., Inc. reserves the right to discontinue models and products.
(CUT ALONG DOTTED LINE)
JUNE 1998
Page 32
Loading...