Kooltronic KDP726, KDP728, KDP876, KDP878, KDP700 Catalog Page

...
DUCT SUPPLY PACKAGED BLOWERS
E
KDP875
STANDARD FEATURES
Baked Powder Finish Capacities: 435 to 900 CFM Single or dual discharge ports Direct air to cabinet ductwork Heavy-gauge steel enclosures with
EIA-notched flanges
Attractive 19''[482.6mm] stainless
steel grilles
UL/CSA precision ball-bearing motors
Permanent filters Exhaust guards included Three foot [0.9m] (minimum)
SJT 3-wire power cord
A CCESSORIES AND OPTIONS
Adapters
Airflow Switch
EMI/RFI Shielding
Filter Recoating Adhesive
Filters for replacement
Grille Assemblies for replacement
Other voltages and frequencies
Special external paint finishes
Special line cords or connectors
*
See accompanying literature for more information.
TECHNICAL DATA
Model 0'' S.P. S.P. Nominal
KDP726 435 1.10 1140 KDP728 610 2.70 1600 KDP876 600 1.17 1100 KDP878 900 2.50 1475
KDP700 485 0.80 1140 KDP730 680 2.15 1600 KDP875 590 0.90 1140 KDP885 840 2.05 1500
Model Run L.R. Watts Lbs. [kg]
KDP726 2.5 5.5 215 40 18.2 KDP728 5.8 17.5 560 50 22.7 KDP876 3.2 7.2 265 42 19.1 KDP878 9.4 17.5 960 48 21.8
KDP700 2.6 5.5 235 38 17.3 KDP730 5.9 17.5 630 40 18.2 KDP875 2.9 6.0 280 42 19.1 KDP885 7.8 17.5 820 48 21.8
**115V, 60 Hz. operation.
CFM@ Cutoff RPM
Amps Weight
**
Approximate
*
*Discharge location for single port models, KDP726 AND KDP728. Dimensions, inches [metric], are for reference only and are subject to change.
DIMENSIONS (inches [metric])
One Discharge Port Model E F G H J K
KDP726 KDP728 KDP876 8.75 [222.3] 17.50 [444.5] 9.75 [247.7] 7.00 [177.8] 0.31 [7.9] 4.50 [114.3] KDP878 8.75 [222.3] 17.50 [444.5] 9.75 [247.7] 7.00 [177.8] 0.31 [7.9] 4.50 [114.3]
Facing grille, discharge port is on left side. See diagram above
Two Discharge Ports Model E F G H J K
KDP700 7.00 [177.8] 15.75 [400.1] 5.25 [133.4] 5.50 [139.7] 0.25 [6.4] 3.19 [81.0] KDP730 7.00 [177.8] 15.75 [400.1] 5.25 [133.4] 5.50 [139.7] 0.25 [6.4] 3.19 [81.0] KDP875 8.75 [222.3] 15.75 [400.1] 5.25 [133.4] 5.50 [139.7] 0.25 [6.4] 4.50 [114.3] KDP885 8.75 [222.3] 15.75 [400.1] 5.25 [133.4] 5.50 [139.7] 0.25 [6.4] 4.50 [114.3]
7.00 [177.8] 17.50 [444.5] 9.75 [247.7] 7.00 [177.8] 0.56 [14.2] 3.19 [81.0]
7.00 [177.8] 17.50 [444.5] 9.75 [247.7] 7.00 [177.8] 0.56 [14.2] 3.19 [81.0]
DESCRIPTION
KOOLTRONICDuct Supply Blowers generate large volumes of cooling air in limited spaces. They deliver filtered air from either one or two side discharge ports to cool every component in an electronics system by means of a single centrifugal blower wheel. The wheel, driven by a powerful, precision ball-bearing motor, delivers cooling air to side ducts, built into the enclosure, for distribution where needed. While the motor operates at a quiet, life-extending lo w speed, the pressure characteristic of the large, narrow wheel far exceeds that of conventional blower units often used to supply duct systems.
Filtered air is delivered directly from the wheel into the duct, with no twists or turns. The steep performance curves demonstrate that duct and other frictional losses cannot hamper adequate air delivery when a unit of this design is specified as the cooling source.
19.00
[482.6mm]
G
*
K
H
F
J
17.00
[431.8mm]
Kooltronic, Inc., 30 Pennington-Hopewell Road, P.O. Box 240, Pennington, NJ 08534-0240
Tel: (609) 466-3400 Fax: (609) 466-1114 Internet: www.kooltronic.com E-Mail: techserv@kooltronic.com
ductpkg.qxd
6/14/99
DUCT SUPPLY PACKAGED BLOWERS PERFORMANCE CHARTS
Airflow vs. static pressure curves are shown for 60 Hz and 50 Hz (broken line) inputs. Static pressure is in inches of water.
CONVERSION FACTORS
Multiply airflow in cubic feet per minute (CFM) by:
• 1.7 to obtain airflow in cubic
3
meters per hour (m
/hr.)
• 0.47 to obtain airflow in liters per second (L/S)
Multiply static pressure in inches of water (''H2O) by:
• 25.4 to obtain static pressure in millimeters of water (mm H
2
O)
• 249 to obtain static pressure in Pascals (Pa)
1.0
.5
STATIC PRESSURE
.1
25
0
1.0
.5
STATIC PRESSURE
.1
50
0
KDP726
ONE DISCHARGE PORT
125 250 375 500
AIRFLOW C.F.M.
KDP876
250 500 750 1000
AIRFLOW C.F.M.
TWO DISCHARGE PORTS
KDP700
3.0
1.5
STATIC PRESSURE
.3
40
0
2.5
1.25
STATIC PRESSURE
.25
50
0
KDP728
200 400 600 800
AIRFLOW C.F.M.
KDP878
250 500 750 1000
AIRFLOW C.F.M.
KDP730
HOW TO ORDER
Specify model number. For 230 VAC operation, add a 2 after the K. Example: K2DP875.
For assistance in model selection, refer to the Blo contact KOOLTRONIC, or use one of our design aid software programs, available FREE.
wer and Fan Selection Guides,
1.0
.5
STATIC PRESSURE
.1
25
0
1.0
.5
STATIC PRESSURE
.1
30
0
125 250 375 500
AIRFLOW C.F.M.
KDP875
150 300 450 600
AIRFLOW C.F.M.
2.0
1.0
STATIC PRESSURE
.2
40
0
2.0
1.0
STATIC PRESSURE
.2
50
0
200 400 600 800
AIRFLOW C.F.M.
KDP885
250 500 750 1000
AIRFLOW C.F.M.
CALL 1-800-321-KOOL (5665)
or FAX 609-466-1114
POPULAR MODELS ARE
STOCKED AND READY TO SHIP
STANDARD FEATURES
RUGGED CONSTRUCTION: Precision-engineered heavy-gauge steel construction insures blower will stand up under tough industrial applications. EIA-notched flanges extend 17
BAKED POWDER FINISH: Durable, baked-on gray powder finish is standard. Other finishes are available. PRECISION BALL-BEARING MOTORS: All motors, whether permanent split capacitor or shaded pole, are UL/CSA Recognized, and include
automatic-reset thermal overload protection. Designed for low temperature rise, KOOLTRONIC motors are also cooled by the blowers' intake air, for maximum motor life. All motors meet Federal Specification CC-M-1807A, and include double-sealed or double-shielded precision ball bearings which meet Federal Specification FF-B-171A. Special permanent lubricants perform over a broad temperature range: -20ºF (-28.9ºC) to 250ºF (121.1ºC). Consult KOOLTRONIC for motors designed to meet military or extreme environmental specifications.
POWER: 115 VAC or 230 VAC, 50/60 Hz is standard. For multi-phase power, other voltages and frequencies or brushless DC applications, consult KOOLTRONIC.
GRILLE:All units include attractive 19 and complies with OSHA and UL safety standards.
PERMANENT FILTERS: Designed to last the life of the unit, the filters included with all packaged blowers consist of a multi-layer grid of sturdy, corrugated aluminum in a one-piece aluminum frame. Adhesive coated to trap particulate matter, they are easy to remove, wash and treat with KOOLTRONIC A-16, an adhesive-rejuvenating spray. Filters must be kept free of accumulations, to prevent reduction or loss of performance and/or damage to equipment.
POWER CORD: All 115 VAC, 50/60 Hz units are supplied with a minimum of 36 internally grounded and securely locked to the case by a strain relief bushing. 230 VAC, 50/60 Hz blowers are supplied without a plug. Special lengths and/or plugs are available.
EXHAUST GUARDS: Included on all packaged blowers.
''
[431.8mm] blower cabinet to 19''[482.6mm] panel width.
''
[482.6mm] wide stainless steel grilles with knurled captive fasteners for easy removal. Grille area is 65% open
''
[914.4mm] type SJT three-wire cord with molded plug included,
A CCESSORIES AND OPTIONS
ADAPTERS: (Set of two) These extend the width of any 19 to permit mounting in a cabinet designed for 24 a plate of mirror-finish stainless steel to match KOOLTRONIC Standard Grilles.
These adapters are non-structural. Therefore, Packaged Blowers must be supported at the rear, due to their weight.
Models Mirror Brushed Height Finish Finish Inches [metric]
KA24-7M KA24-7 7.00 [177.8] KA24-8M KA24-8 8.75 [222.3]
AIRFLOW SWITCH: See accompanying literature for more information. EMI/RFI SHIELDING: See EMI/RFI-Shielded Twin Packaged Blowers. FILTER RECOATING ADHESIVE: This compound is a superior product for recoating all permanent filters after washing. The adhesives penetrate
dirt layers to keep the filter surface tacky for longer effective performance between washings. Part No. A-16 - one pint container. FILTERS FOR REPLACEMENT:All KOOLTRONIC filters consist of a multi-layer grid of sturdy corrugated aluminum, securely held in a one-piece
aluminum frame. Filters are required wherever air is drawn into an electronics enclosure or related cooling equipment to keep internal parts as clean as possible.
A non-drying adhesive coating traps a high percentage of particulate matter. These washable, reusable filters are designed to last the life of the cooling unit. Replacements are available for those which become damaged or otherwise non-serviceable.
KDP700, 726, 728, 730 Part No. 7001F (16.63 KDP875, 876, 878, 885 Part No. 8751F (16.63
''
[609.6mm] units. The EIA-notched adapters are covered by
''
x 6.63''x 0.50''[422.3mm x 168.4mm x 12.7mm])
''
x 8.38''x 0.50''[422.3mm x 212.9mm x 12.7mm])
*
''
[482.6mm] KOOLTRONIC Packaged Blower
Adapter
Cover plate
*
Contact KOOLTRONIC for information.
A CCESSORIES AND OPTIONS
Dimensions, inches [metric], are for reference only and are subject to change.
1.25
[31.8mm]
0.38
[9.7mm]
0.44
[11.2mm]
0.75
[19.1mm]
0.63
[16.0mm]
1.50
[38.1mm]
.375 x .187
[9.5mm x 4.7mm]
SLOT
1.75
[44.5mm]
0.06
[1.5mm]
Tap hole for #8-32 or drill a .187 [4.7mm] DIA. HOLE
0.75
[19.1mm]
.625 [15.9mm] DIA. HOLE
BLACK
N.O.
L
SJ CORD
WHITE
COMMON
RED
N.C.
DIRECTION
OF AIRFLOW
21
o
11
o
*
(continued)
GRILLE ASSEMBLIES: These assemblies are ideal for venting applications on the enclosure. These attractive grilles are made of mirror-finish stainless steel. All are 19
''
[482.6mm] wide. They are 65% open, comply with OSHA and UL safety standards, and include knurled captive fasteners for
easy attachment and removal.
Model
Filter
Grilles Grilles Height
Assemblies Assemblies Inches [metric]
KPG700-19 KFG700-19 7.00 [177.8] KPG875-19 KFG875-19 8.75 [222.3] Overall depth, including fasteners:
''
[12.7mm] 0.75''[19.1mm]
0.50
OTHER V OLTA GES AND FREQUENCIES SPECIAL EXTERNAL PAINT FINISHES SPECIAL LINE CORD OR CONNECTORS
*
Contact KOOLTRONIC for information.
KOOLTRONIC also designs and manufactures a variety of Packaged Blowers to meet unique specifications. We invite your inquiries about our modification and custom-design capabilities.
AIRFLOW SWITCH
Protects equipment against damage caused by loss of cooling airflow, by activating an alarm or turning off power. The switch can be mounted on any suitable surface which allows the stainless steel air vane to be placed in the critical airstream. This switch is a single-pole double-throw type, with normally open and normally closed
Refer to the chart consult KOOLTRONIC Engineering for assistance.
For other switch orientations or where air velocity cannot be measured by conventional means, KOOLTRONIC can supply additional individual or sets of air vanes to determine the optimum
size. contacts. The UL rating for the rotary snap action
switch is 5 amps at 250 volts AC. A 36
''
[914.4mm], three wire SJT power cord is provided, allowing connection to normally open or normally closed circuits.
The choice of air vanes is determined by location and orientation in the airstream, and the normal operating air velocity at the point of installation.
TECHNICAL DATA
V ertical Airstr eam Horizontal Airstream
Dim.
“L” Vane
Max. Length
Inches Inches
Model [metric] [metric]
KV-1 3.38 [85.9] 2.88 [73.2] 660 590 - - 620 530 630 520 KV-2 2.75 [69.9] 2.25 [57.2] 840 750 - - 790 670 800 660 KV-3 2.44 [62.0] 1.94 [49.3] 980 870 - - 860 750 860 770 KV-4 2.19 [55.6] 1.69 [42.9] 1010 960 640 610 980 870 980 820 KV-5 1.94 [49.3] 1.44 [36.6] 1180 1130 880 720 1070 930 1050 960 KV-6 1.56 [39.6] 1.06 [26.9] 1520 1370 1210 1050 1370 1260 1410 1290 KV-7 1.44 [36.6] 0.94 [23.9] 1670 1520 1380 1290 1570 1430 1600 1430 KV-8 1.25 [31.8] 0.75 [19.1] 2020 1880 1940 1780 2010 1710 2080 1780 KV-9 1.13 [28.7] 0.63 [16.0] 2360 2180 2350 1930 2340 2060 2510 2150
Airstream Up Airstream Down Arm Horizontal Vane Down
Increasing Decreasing Increasing Decreasing Increasing Decreasing Increasing Decreasing
Air Air Air Air Air Air Air Air
Actuate Deactuate Actuate Deactuate Actuate Deactuate Actuate Deactuate
ft/min ft/min ft/min ft/min ft/min ft/min ft/min ft/min
Orientation of Airflow Switch
Arm V ertical