Kooltronic, Inc., 30 Pennington-Hopewell Road, P.O. Box 240, Pennington, NJ 08534-0240
Tel: (609) 466-3400 Fax: (609) 466-1114 Internet: www.kooltronic.com E-Mail: sales@kooltronic.com
KXNP47 TRIMLINE AIR-TO-AIR
PANEL-MOUNTED HEAT EXCHANGERS
Dimensions, inches [mm], are for reference only and subject to change.
* 60 Hz. operation. For 50 Hz. operation, consult Kooltronic.
kxnp47.qxd 10/18/11
NEMA
TYPE 12
MAINTAINED
MOUNTING PLAN
ACCESSORIES
AND OPTIONS
Filter Recoating Adhesive
Lifting Eyes
Low Airflow Detector
Other voltages and frequencies
Replacement Filters
Special materials or finishes
Special motors, line cords or
connectors
Stainless or Aluminum Shell
Temperature Alarm
Weather Protection Kit
STANDARD FEATURES
Closed-Loop Near-Ambient Cooling
Convoluted Aluminum Element
Epoxy-coated element
Filter
Heavy-duty Steel Shell
NEMA 12 Rating Maintained (UL50)
Removable Element Access Panel
UL/CUL Listed
DIMENSIONS
KXNP47
A 47.25 [1200.2]
B 15.13 [384.3]
C 9.75 [247.7]
D 14.81 [376.2]
E 0.75 [19.1]
F 3.00 [76.2]
G 12.50 [317.5]
H 23.88 [606.6]
J 18.00 [457.2]
K 12.00 [304.8]
L 13.31 [338.1]
M 10.13 [257.3]
N 7.00 [177.8]
P12
PERFORMANCE*
TECHNICAL DATA*
Maximum Performance Approx.
Power Temperature ºF Watts/ºF Weight
Model Volts Amps Watts Enclosure Ambient (Air In) (lbs.)
KXNP47 115 3.40 354 160 -20 to 131 56 79
K2XNP47 230 1.70 354 160 -20 to 125 56 79
4800
130
4200
120
3600
110
3000
100
2400
1800
1200
Cooling Capacity (Watts)
600
0
40
50 60
KXNP47
Maximum enclosure
air temperature ºF
70 80 90 100 110 120 130
Ambient Tem
erature (ºF)
C
POWER
CORD
3
M/TAB
4
D
B
2
A
1
FILTE
FILTERED CONDENSER
1
AIR INLET (Ambient Air In)
CONDENSER OUTLET
2
(Warm Ambient Air Out)
WARM AIR RETURN FROM
3
ENCLOSURE
COOL AIR OUTLET
4
TO ENCLOSURE
B
C
(P) .250 [6.4]
DIA. HOLES
2
REMOVABLE
ACCESS PANEL
POWER
CORD
3
(P) .312 [7.9]
DIA. HOLES
J
L
K
3
1
B
FILTER
A
H
4
F
E
4
G
N
TYP.
M
A