Maximum Performance
UL/CUL
Inlet Water
Watts °F/°C
Listed or Power Temperature Air In Air Out
Model Recognized Volts Amps Watts °F °C 1GPM 2GPM 1GPM 2GPM
KPHE36 Listed 115 2.0 235 85 29 68/109 79/126 133/213 188/301
K2PHE36 Listed 230 1.0 235 85 29 68/109 79/126 133/213 188/301
TECHNICAL DATA
**
**115V, 60 Hz. operation.
KPHE36 W A TER-TO-AIR
PANEL-MOUNTED HEAT EXCHANGERS
POPULAR MODELS ARE
STOCKED AND READY TO SHIP
APPRO XIMA TE WEIGHT
50 lbs. [22.7 kg]
STANDARD FEATURES
Baked Powder Finish
Precision Ball-bearing Motors
Closed-Loop Cooling
Heavy-duty Steel Enclosure
NEMA 12 Rating Maintained (UL50)
Six foot [1.8m] (minimum)
SJT 3-wire Cord
UL/CUL Listed
kphe36.qxd
12/30/02
A CCESSORIES AND OPTIONS
*
■
Automatic Water Flow Regulating Valve
■
Cooling Effect Detector
■
Excess Heat Detector
■
Height Extension
■
High Water Level Detector
■
Internal Corrosion Protection
■
Lifting Eyes
■
Low Airflow Detector
■
Mounting Hinge
■
Other voltages and frequencies
■
Parallel Water Connections
■
Special materials or finishes
■
Special motors, line cords or connectors
■
Stainless or Aluminum Cabinet
■
Water Hook-up Opposite Side
*See opposite side for more information.
KPHE36
8.38
[212.9mm]
36.00
[914.4mm]
19.00
[482.6mm]
0.50" [12.7mm] Copper tubing hook-ups.
❶
4 Equal Spaces @ 3.50" [88.9mm] = 14.00" [355.6mm]
❷
Enclosure opening should be located as high as possible within this area,
❸
and equal or exceed size of cool air outlet.
Dimensions, inches [metric], are for reference only and are subject to change.
When using height extensions consult KOOLTRONIC for installation location.
17.13
[435.1mm]
(20)
.312 [8.0mm]
DIA.
HOLES
POWER
CORD
WATER
INLET
WATER
OUTLET
1.50
[38.1mm]
DIA. POWER
CORD HOLE
if warm air
return does not
extend to this
level.
❶
❶
MOUNTING
PLAN
19.00
[482.6mm]
18.25
[463.6mm]
16.88
[428.8mm]
❸
W ARM AIR
RETURN FROM
ENCLOSURE
C
L
4.00
[101.6mm]
❷
❷
1.75
[44.5mm]
COOL AIR
OUTLET TO
ENCLOSURE
0.38 [9.7mm]
1.06 [26.9mm]
13.88
[352.6mm]
[558.8mm]
18.00
[457.2mm]
2.50 [63.5mm]
[24.5mm]
22.00
1.00
36.00
[914.4mm]