TECHNICAL DATA*
Performance Approx.
Normally Power Maximum Inlet Watts/ºF Weight Model in Stock Volts Amps Watts Water Temp. ºF 1 GPM 2 GPM (lbs.) KPHE24 Yes 115 0.64 72 85 33 37 34 K2PHE24 230 0.31 70 85 33 37 34
ACCESSORIES AND OPTIONS
Automatic Water Flow Control High Water Level Detector Internal Corrosion Protection Low Airflow Detector Other voltages and frequencies Special materials or finishes Special motors, line cords, or
connectors
Temperature Alarm
STANDARD FEATURES
Below-Ambient Cooling Capability Closed-Loop Cooling Heavy-Duty Steel Shell with Baked
Powder Finish NEMA 12 & 3R Ratings Maintained (UL50) UL/CUL Ball-Bearing Motors UL/CUL Listed
p
For performance at other flow rates contact the factory or visit www.kooltronic.com.
PERFORMANCE*
120 110 100
90 80 70
30
40
KPHE24 - 2 GPM
Maximum enclosure
air temperature ºF
50 60 70 80 90
Water Tem
erature (ºF)
3200
2800
2400
2000
1600
1200
800
Cooling Capacity (Watts)
400
0
8.06
[204.7]
24.00
[609.6]
8.06
[204.7]
10.50
[266.7]
24.00
[609.6]
2
WARM AIR RETURN FROM
1
1
M/TAB
2
(8) .281 [7.1] DIA. HOLES
1
1.13
[28.7]
6.60
[167.6]
TYP.
10.50
[266.7]
8.24
[209.3]
2
1
ENCLOSURE
COOL AIR OUTLET
2
TO ENCLOSURE
4.84
[122.9]
3.79
[96.3]
10.00
[254.0]
10.50
[266.7]
CONDENSATE DRAIN
3/8" [9.5] WATER OUTLET
2.71
[68.8]
1.75
[44.5]
1.25
[31.8]
7.00
[177.8]
8.00
[203.2]
3.64
[92.5]
Loading...