Kooltronic K2PHE20, KPHE20 Technical Data

Dimensions, inches [mm], are for reference only and subject to change.
* 60 Hz. operation. For 50 Hz. operation, consult Kooltronic.
kphe20.qxd 12/9/15
3/8" [9.5] WATER INLET 3/8" [9.5] WATER OUTLET
POWER CORD
20.00
10.02
4.15
1
2
NEMA
TYPE 12 & 3R
MAINTAINED
STANDARD FEATURES
Below-Ambient Cooling Capability Closed-Loop Cooling Heavy-Duty Steel Shell with
Baked Powder Finish NEMA 12 & 3R Ratings Maintained (UL50) UL/CUL Ball-Bearing Motors UL/CUL Listed
ACCESSORIES AND OPTIONS
Internal Corrosion Protection Other voltages and frequencies Special materials or finishes Special motors, line cords, or
connectors
TECHNICAL DATA*
Performance Approx.
Normally Power Maximum Inlet Watts/ºF Weight Model in Stock Volts Amps Watts Water Temp. ºF 0.25GPM 0.50GPM (lbs.) KPHE20 Yes 115 0.30 33 85 20.5 21.5 15 K2PHE20 230 0.13 25 85 20.5 21.5 15
For performance at other flow rates contact the factory or visit www.kooltronic.com.
PERFORMANCE*
MOUNTING PLAN
KPHE20 WATER-TO-AIR
PANEL-MOUNTED HEAT EXCHANGERS
2000
1750
1500
1250
1000
750
500
Cooling Capacity (Watts)
250
KPHE20 - .50 GPM
120 110
100
90 80 70
0
30
40
Water Temperature (ºF)
Maximum enclosure
air temperature ºF
50 60 70 80 90
10.00
20.00
4.15
POWER CORD
(6) .281 [7.1] DIA. HOLES
2
1
3/8" [9.5] WATER OUTLET
1.55
[39.4]
1
2
5.90
8.00
3.29
[83.6]
WARM AIR RETURN FROM ENCLOSURE
COOL AIR OUTLET TO ENCLOSURE
7.05
1.49
[37.8]
2
1
7.75
10.02
8.00
TYP.
2.69
[68.3]
1.13
[28.7]
20.00
3/8" [9.5] WATER INLET
Loading...