KONVEKTA UL500, UL700, UL800 Operating Instructions Manual

Page 1
Konvekta AG
Am Nordbahnhof 5 34613 Schwalmstadt Germany
Operating Instructions
for KONVEKTA
Air Conditioning units
UL500 / UL700 / UL800
with Wabco control system
R134a 24 Volt DC
ID#: BBA-KL6U022AA Version: A03
Page 2
BAKL6U022AA Edition: 28.02.2017 Page: 2/9
Contents
Page:
Introduction ............................................................................................................................ 3
Information on the operating instructions ................................................................................ 4
1. Technical data .................................................................................................................. 4
1.1. Air conditioner .................................................................................................................... 4
1.2. Compressors ..................................................................................................................... 5
2. Intended Use .................................................................................................................... 5
2.1. Operating Conditions ......................................................................................................... 5
3. Operation .......................................................................................................................... 5
3.1. Operation panel / function of the keys ................................................................................ 6
3.1.1. Flap for windshield/floor ..................................................................................................... 6
3.1.2. Desired value of front box temperature .............................................................................. 6
3.1.3. Blower speed ..................................................................................................................... 6
3.1.4. Smog ................................................................................................................................. 6
3.1.5. Heater passenger’s compartment ...................................................................................... 7
3.1.6. Additional heater ................................................................................................................ 7
3.1.7. Reheat ............................................................................................................................... 7
3.1.8. Driver’s seat air conditioning .............................................................................................. 7
3.1.9. General .............................................................................................................................. 7
4. Wartung ............................................................................................................................ 7
4.1. Troubleshooting ................................................................................................................. 8
5. Warranty Conditions ........................................................................................................ 8
6. Waste disposal in accordance with legal provisions .................................................... 9
7. History of modification .................................................................................................... 9
Appendix:
Maintenance Schedule Bus WP07050618
Page 3
BAKL6U022AA Edition: 28.02.2017 Page: 3/9
Introduction
These operating instructions have been written for drivers, operators and the maintenance staff of your air conditioning unit.
In this context, we refer implicitly to the compliance with our general installation guide­lines. These can be obtained from the KONVEKTA technical after sales service:
TKD@konvekta.com.
Please observe our valid safety instructions, available under www.konvekta.de/asv.html. In case of order placement or any other conclusion of contract the safety instructions get integral part of the contract
These operating instructions have to be read carefully and made use of before the first start-up and after that regularly by each person who is involved in handling the machine:
Operation including troubleshooting and waste disposal of fuels and auxiliary agents. Servicing, inspection, repair Transport
This facilitates the handling and avoids trouble caused by improper operation. Working in compli­ance with these operating instructions increases operation reliability and service life of the air conditioning unit and reduces life cycle costs.
Please complete these instructions by adding the national provi-
sions for prevention of accidents and environmental protection.
These instructions are part of the air conditioning unit. Always have a copy at hand in the driver’s cabin.
You will certainly understand that we will not recognize any warranty claims due to improper han­dling, inadequate maintenance, applications that do not correspond with the determined use, utili­zation of non-admitted fuels or the non-observance of safety provisions. KONVEKTA will annul without notice all obligations concerning guarantee, service contracts etc. regardless if granted by KONVEKTA or its distributors in case other than original KONVEKTA spare parts or parts bought from KONVEKTA AG have been used for maintenance and repair. These operating instructions contain all necessary information to operate your air conditioning unit. In case you need more explanations please contact the next KONVEKTA service station
.
On our website www.konvekta.com in category >service< you will find a survey of contact details of all
our service partners close to your location.
Page 4
BAKL6U022AA Edition: 28.02.2017 Page: 4/9
Information on the operating instructions
These operating instructions are valid fort he air conditioners type:
UL500 UL700 UL800
With Wabco control system
When taking the unit into operation we recommend adding the following data.
This will also be important for your orders of spare parts, and in case of warranty
.
Serial number of the unit: ......................................................
Order No.: ......................................................
Year of construction: ...................................................... (MM/YY)
Date of first operation: ...................................................... (DD/MM/YY)
The machine is in accordance with the EC machinery directive 2006/42/EC.
The unit contains or needs fluorinated greenhouse gas for operation and is subject to identification requirements in accordance with F-Gas Regulation 517/2014.
Due to the fact that scope of supply depends on the order, equipment of your product may differ in some parts of description.
In case your product is equipped with details not shown or described in the operating in­struction, your KONVEKTA -Service-Station will always be at disposal for informing you about correct operation.
In the course of further developments we reserve the right to technical modifications without no­tice. Guarantee and liability conditions of KONVEKTA AG’s general business conditions are not enlarged by the above notes.
Indications and photos should neither be copied and circulated nor used for competitor’s purpos­es. All rights according to the copyright remain expressly reserved.
Manufacturer: KONVEKTA AG, P.O.Box 2280, D-34607 Schwalmstadt
1. Technical data
1.1. Air conditioner
Type
UL 500
UL 700
UL 800
Refrigerant
R 134a
GWP
1.430
Refrigerant quantity ca.
kg 8,5 9,5 10,5
Operating voltage
Volt DC 26 26 26
Power consumption
A 72 104 136
Cooling capacity
W 24.000 33.000 39.000
Evaporator – air volume
m3/h 4.320 6.480 8.640
Page 5
BAKL6U022AA Edition: 28.02.2017 Page: 5/9
1.2. Compressors
Important:
To avoid leakage a the shaft seals of the compressor:
The compressor must be switched on every 4 weeks for about 15 minutes! Even if the vehicles or the air conditioner has not been used for a longer period of time!
Compressor is dependent on delivery, see nameplate on the compressor.
2. Intended Use
The KONVEKTA air conditioning unit is an air conditioning system that works with the ozone friendly refrigerant R134a and which creates a pleasant and individually adjustable room tem­perature by means of forced convection. The determined use includes also the observance of the operating instructions as well as the proof of regular inspections.
2.1. Operating Conditions
NOTE:
KONVEKTA uses components made of copper and aluminium, which last a whole unit lifetime under normal environmental conditions. Should the units be operated under aggressive environ­mental conditions, i.e. air containing salt-, phosphate- or ammoniac extremely, a corrosion of the cupper- and aluminium components cannot be ruled out. The cupper- and aluminium components of the KONVEKTA systems are not suitable for such extreme application conditions. We indicate emphatically, that corrosion is not subject to warranties for defects. KONVEKTA does not take over any warranties for defect, neither for corrosion nor for consequential damage resulting there from, nor for damages caused by cleaning the systems with highly compressed or corrosion ad­vancing substances.
3. Operation
Attention in case of roof top a/c units: Never switch on the a/c unit during car­wash!
Danger of accidents!
- Focussing your attention on the road traffic is of top priority
- Only operate your air conditioning unit when the traffic situation allows it.
- Make sure you can clearly recognize and read all operation- and display-elements at any time
- Protect all displays against irritating sun glare and any other optical disturbances
- Please note that the control panel keys have not been designed for heavy stressing
- Excessive or fast pressing of the keys for adjusting the set temperature does not accelerate the cooling down process. It possibly damages the control panel and so affects the general per­formance of the air conditioning unit
Page 6
BAKL6U022AA Edition: 28.02.2017 Page: 6/9
3.1. Operation panel / function of the keys
You operate the air conditioning unit via the original WABCO – control unit (see original WABCO- operation instructions „ATC-CAN„)
For operation the driver can use 3 rotary potentiometer and maximal 5 keys. Depending on the serial-model modification of the bus different control desks are used. In order to release the driver from extensive adjustments for the passenger’s compartment he is able to switch off the complete control for this area. All other functions on the control desk serve for the individual adjustments of the driver’s cabin.
3.1.1. Flap for windshield/floor
The flap for windshield respectively floor are controlled according to the symbolism.
Arrow down:
flap for floor
The whole air is lead to the floor.
Arrow down/up: mid-position Air circulation is split up between floor and windshield.
Arrow up: flap for windshield The whole air is lead to the windshield
Symbol windshield: defrost Water valve completely opened; air to windshield; max-
imal blower speed.
The conversion is realized via characteristic curves which also facilitate intermediate positions.
3.1.2. Desired value of front box temperature
The blowout temperature of the front box can be set between 14 and 60º C.
3.1.3. Blower speed
The potentiometer serves for setting speed of the front box. The air velocity is increased by turn­ing the potentiometer clockwise.
3.1.4. Smog
With the smog key you can stop supply of fresh air for the whole bus. If smog function is activated the key is illuminated. If this function is activated, the openings in the roof as well as the fresh air flaps are closed for a certain time prescribed by the manufacturer.
Heater pas­sengers compart-
Driver’s seat climate
Frontbox
temperat
ure
Smog
Flap windshield
/ floor
Reheat
Additional
heater
Blower
speed
Page 7
BAKL6U022AA Edition: 28.02.2017 Page: 7/9
3.1.5. Heater passenger’s compartment
The driver doesn’t have the possibility to intervene in the fully automatic control of the passengers compartment. This control is merely turned off during routes without passengers (e.g. transporta­tion of bus). If automatic function is activated the key is illuminated.
3.1.6. Additional heater
Normally the additional heater is turned on manually. If additional heater is activated, the key is illuminated.
3.1.7. Reheat
With the key Dry / Reheat the air conditioning unit is put into operation. The air is dried by cooling down and re-heating.
3.1.8. Driver’s seat air conditioning
Diese Funktion schaltet das Kältemittelmagnetventil bzw. die Kompressormagnetkupplung ein. Bei aktivierter Klimaanlage leuchtet die Taste.
3.1.9. General
Roof ventilator: Roof ventilators are activated from a certain minimum speed of the roof evapora­tor blowers. In circulated air operation the roof ventilators are switched off.
4. Wartung
For maintenance works we refer to our maintenance instructions BWA-KL6U022AA, which have been written exclusively for maintenance personal. Please arrange regular dates for maintenance works and services with a KONVEKTA service station, as indicated in maintenance schedule bus no. WP07050618.
- Only qualified staff is allowed to carry out these works! -
For general instructions on repair – and maintenance works please contact via email:
TKD@konvekta.com
Danger of accidents!
Qualified staff in charge of installation and maintenance have to be trained in accordance with EN 378-Part 4 and (EC) No.307/2008 and must strictly follow the legal provisions.
Any works or modifications at the air conditioner which are carried out improperly can lead to mal­function and so endanger operational reliability. We recommend having all works and modifica­tions carried out at an authorized KONVEKTA Service Station.
Before carrying out any maintenance works at your air conditioning unit, carefully read the KONVKETA safety provisions (TD00052A) in order to avoid any dangers and accidents!
On our website www.konvekta.com in category >service< you will find a survey of contact details of all
our service partners close to your location
Page 8
BAKL6U022AA Edition: 28.02.2017 Page: 8/9
4.1. Troubleshooting
Only qualified staff is allowed to carry out these works!
Trouble Cause Repair by authorized Service Station only
a/c is not running
thermostat open
check inside temperature 
re-adjust thermostat  electric connections disconnected check electric connections at switchboard relay defective check relay, replace if necessary defrost thermostat has switched off check evaporator blower, replace if neces-
sary outside temperature too low (possible
icing of evaporator)
switch on "ventilation" only
evaporator coil dirty clean evaporator coil with compressed air magnetic clutch check connections at magnetic clutch compressor does not compress check high and low pressure, replace com-
pressor if necessary excess pressure (pressure too high) check axial fans
check fuses at switchboard
clean condenser coil with compressed air excess pressure caused by high out-
side temperature
run unit until pressure has stabilized
leakage in a/c unit, lack of refrigerant check a/c unit for leakages, refill refrigerant low pressure, dryer clogged replace dryer low pressure, screen of expansion
valve clogged
clean screen; replace dryer
Loud noise at compres­sor
defective bearing at compressor replace either bearing or entire compressor slack V-belt check V-belt at compressor drive
By operator
5. Warranty Conditions
The current „General Warranty Conditions KONVEKTA AG“ will apply. A copy will be furnished by the warranty department. Please contact gwl@konvekta.com
Page 9
BAKL6U022AA Edition: 28.02.2017 Page: 9/9
6. Waste disposal in accordance with legal provisions
After the phase of use the last proprietor is responsible for the adequate waste manage­ment. The environmental regulations in the exporting country must be observed.
The following list contains the most important regulating literature, valid for the Federal Rep. of Germany:
Resolution for dangerous substances
Law for waste circulation (KRW/AfgG))
Resolution for the proofs of utilization and
removal
Criminal Code (StGB) 28th section „crimi­nal acts against the environment” §326 ­Environment jeopardizing waste manage­ment
Law of chemicals § 27 - penal prescriptions
Resolution for used oil
Law of water balance
Resolution for the waste management of old
cars and the adaptation of road prescrip­tions
Resolution (EC) No. 2037/2000 of the Euro­pean Parliament and of the Council for ma­terials that affect the ozone layer
Resolution to prohibit certain ozone destroy­ing halogen hydrocarbons.
The used refrigerant endangers the environment. When dealing with refrigerants the existing pre­scriptions and regulations are to be followed. Only qualified staff is allowed to carry out these
works!
Water endangering substances - acc. to §§19g-19l - are solid, liquid, and gaseous substances. e.g.: mineral and tar oils (cooling oils), halogen containing organic combinations (refrigerants).
Source of supply:
-
Bundesanzeiger
-
Beuth Verlag
-
dtv (Deutscher Taschenbuch Verlag
7. History of modification
V
ersion Date N
ame
Remark
File
A00 03.02.2010 B. Keßler Source file BAKL6U022AA
A01 21.01.2014 B. Keßler Added safety instructions (Foreword), Ma-
chinery Directive p.4 updated, updated risk of accidents Pkt.4 and item 5 mail address
BAKL6U022AA
A02 03.11.2016 B. Keßler Item 1.2 pressure switches deleted BAKL6U022AA
A03 28.02.2017 B. Keßler Information on the operating instructions and
technical data expanded with F-gas­regulation
BAKL6U022AA