Please familiarize yourself with the information in this manual before using the product.
This manual provides detailed information on the product's features. It does not offer any
guarantee concerning matters beyond the scope of this manual.
This manual may not be edited or reproduced in either part or whole without permission.
A user manual is not provided as part of the product package.
Visit our web site (www.konics.com) to download a copy.
The manual's content may vary depending on changes to the product's software and other
unforeseen developments within KONICS, and is subject to change without prior notice.
Update notice is provided through out homepage.
We contrived to describe this manual more easily and correctly. However, if there are any
corrections or questions, please notify us these on our homepage.
Following these safety precautions will ensure the safe and proper use of the product and
help prevent accidents, as well as minimizing possible hazards.
Safety precautions are categorized as Warnings and Cautions, as defined below:
Warning
Caution
Failure to follow the instructions may lead to a serious injury
or accident.
Failure to follow the instructions may lead to a minor injury
or accident.
Fail-safe device must be installed when using the unit with machinery that may cause
serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment,
ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster
prevention devices, etc.)
Failure to follow this instruction may result in personal injury, fire, or economic loss.
The unit must be installed on a device panel before use.
Failure to follow this instruction may result in electric shock.
Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in electric shock.
Check the terminal numbers before connecting the power source.
Failure to follow this instruction may result in fire or burning the unit.
Lithium battery is used in the unit. Do not disassemble or burn the unit.
Failure to follow this instruction may result in explosion.
Do not touch the unit and terminals after cut off the power within 30 sec.
Failure to follow this instruction may result in electric shock.
Ground PE terminal individually and ground cable should be over AWG16 (1.25 mm
Failure to follow this instruction may result in electric shock.
Do not insert any objects at the openings of the unit.
Failure to follow this instruction may result in electric shock or personal injury.
Do not disassemble or modify the unit. Please contact us if necessary.
Failure to follow this instruction may result in personal injury, fire, or economic loss.
Do not use the unit outdoors.
Failure to follow this instruction may result in shortening the life cycle of the unit, or electric
shock.
2
When connecting the power input and relay output cables, use AWG20 (0.05mm
) cables
and make sure to tighten the terminal screw bolt above 0.74N.m to 0.90N.m.
Failure to follow this instruction may result in fire due to contact failure.
Use the unit within the rated specifications.
Failure to follow this instruction may result in shortening the life cycle of the unit, or fire.
Do not use loads beyond the rated switching capacity of the relay contact.
Failure to follow this instruction may result in insulation failure, contact melt, contact failure,
relay broken, or fire.
When connecting magnet contact as relay contact output load, attach a surge absorber at
contact coil.
Failure to follow this instruction may result in product malfunction.
Do not use water or oil-based detergent when cleaning the unit. Use dry cloth to clearn the
unit.
Failure to follow this instruction may result in electric shock, or fire.
Do not use the unit where flammable or explosive gas, humidity, direct sunlight, radiant heat,
vibration, or impact may be present.
Failure to follow this instruction may result in fire or explosion.
Keep dust and wire residue from flowing into the unit.
Failure to follow this instruction may result in fire or product damage.
Check the polarity before connecting cables.
Failure to follow this instruction may result in fire or explosion.
Check the polarity of the measurement input contact before wiring the temperature sensor.
Failure to follow this instruction may result in fire or explosion.
Check the connection diagram of this manual before supplying power.
Failure to follow this instruction may result in fire.
Do not touch terminal during dielectric or insulation resistance test.
Failure to follow this instruction may result in electric shock.
Use insulation transformer and noise filter power for too much noise from the power. Attach
noise filter on the grounded panel, etc. Use short cables for noise filter output part and
power terminal of the unit.
Failure to follow this instruction may result in product damage, malfunction by surge.
If power line and input signal line are close each other, install line filter for noise protection
at power line and use shielded input signal line.
Do not control the alarm output or measure the data during firmware update. Failure to
follow this instruction may result in malfunction. Alarm output, contact input, data
measurement do not operate normally.
After completing firmware update, check the complete message and turn OFF to ON the
power.
All parameter setting values are reset after firmware update. It may not operate as same
way with before updating operation.
Use voltage output of transmitter power output only for transmitter power. Failure to follow
this instruction may result in output module damage.
Do not press the touch screen by sharp or hard objects with excessive force.
To prevent inductive noise, separate cables of the unit from high-voltage line, power line.
Do not install inductive noise or power line closely. It may cause measurement error.
Install the unit at well-ventilated place to prevent over-heat and give space over 30mm
KRN1000 is paperless recorder with LCD method to save recording data at SD / USB memory.
It displays trend graph, bar graph, or digital figures at TFT Color LCD.
Via RS422/485, Ethernet or USB device communication, it is available to set parameters,
transfer data as data logger functions for user convienent.
It supports several communication method and various input/output functions. It also provides
easy and convient graphic user interface (GUI) applying graphic display.
5.6-inch color TFT LCD (640×480) touchscreen display with excellent readability and
intuitive control interface
Supports 27 input types (thermocouple, RTD, analog voltage and current[shunt])
4 / 8 / 12 / 16 input channel models available
Various communication methods (RS422/485, Ethernet, USB) standard
25 to 250 ms high-speed sampling, 1 to 3600 s recording cycle
200 MB internal memory and external memory support (SD/USB up to 32 GB)
Store and backup internal data to external memory (SD/USB)
9 different graph types available
Various option input/output available: digital input (contact/non-contact), alarm output,
Before using KRN1000, check the components.
If any component is left out or damaged, contact our company or seller.
KONICS service center: +82-32-820-2356 to 7
1.2.2Accessories
Communication converter
SCM-38I
(RS232C to RS485 converter)
Use Autonics SCM-38I or SCM-US48I as communication converter.
SCM-38I (RS232C/RS485 converter) and SCM-US48I (USB/RS485 converter) are same
appearance.
RTD Cu50Ω (-200≤T≤200): (±0.1% F.S. or ±1.5℃, select the higher one) ±1-digit
RTD DPt50Ω (-200≤T≤500): (±0.1% F.S. or ±1.5℃, select the higher one) ±1-digit
Thermocouple R, S, C, G type (0≤T≤100): (±0.1% F.S. or ±4.0℃, select the higher one)
±1-digit
Thermocouple U, T type (-100≤T≤400): (±0.1% F.S. or ±2.0℃, select the higher one)
±1-digit
Thermocouple B type, below 400℃: There is no accuracy standards.
All thermocouples, below -100℃: (±0.3% F.S. or ±4.0℃, select the higher one) ±1-digit
◎ Out of room temperature range
RTD Cu50Ω (-200≤T≤200): (±0.2% F.S. or ±3.0℃, select the higher one) ±1-digit
RTD DPt50Ω (-200≤T≤500): (±0.2% F.S. or ±3.0℃, select the higher one) ±1-digit
※3. Input/Output is different by option. Refer to ‘1.3 Ordering information’.
※4. For supplying power for transmitter, it is recommened to use shield cable to reduce noise.
※5. RS422/485, ethernet, USB device communication outputs are not used at the same time.
※If sensor input line is longer, it is recommended to use shield cable to reduce noise.
Before the wiring, turn OFF the unit.
Be sure that the polarity of power for transmitter. If not, it may cause produc t dam age.
When supplying the over voltage at sensor input, it may cause product damage.
※1. C (TT): Same as exisitng W5 (TT) type temperature sensor.
※2. G (TT): Same as existing W (TT) type temperature sensor.
※3. Russian L type temperature sensor is divided from general purpose L type.
Install the unit in place where the below conditions are satisfied.
Place where ventilation is well
To prevent from malfunction and damage by overheating (use temperature range: 0 to
50℃), install this unit where ventilation is well.
In case installing several KRN1000, space each other by panel cut-out.
Place where vibration is not severe
If there is too much vibration, it may cause malfunction such as print error. For more
information about vibration, please refer to ‘2 Specifications’.
In case of temperature measurement with thermocouple temperature sensor at the place
where temperature is fluctuated, data error may occur. You should warm-up this unit over 30
min. to acquire accurate data before using it.
3rd Connect the USB device port at KRN1000 front cover and PC USB port via USB
cable (A-Mini B 5-pin, 1.5m).
4th After recognizing the driver, the driver is automatically installed.
5.3.2Check the driver
To check the driver, right click 'My computer' and select 'Properties' on pop-up menu. 'Device
Manager'' dialog appears. Check ‘Ports (COM & LPT)’ - 'USB To Serial Converter (COMx)'.
Below booting screens are initially displayed when power is supplied to KRN1000. These
screens progresses initial settings for KRN1000 to operate normally and checks inner system
memory.
If there is no error for inner system memory, booting is finished and KRN1000 operates normally.
Initial screen: Checking initial system memory error and processing module reset
If initial system memory error occurs,
If initial system memory error occurs, it does not operate normally.
Contact our company or seller.
The upper area is for real-time measurement value as vertical trend graph and the lower
area is for all records from start as vertical trend graph.
The lower area is available only when recording status.
Divided horizontal trend graph (DH Trend)
The right area is for real-time measurement value as horizontal trend graph and the left
area is for all records from start as horizontal trend graph.
The left area is available only when recording status.
You can enter setting value via vertual keyboard.
Virtual keyboard is activated automatically when setting value enters. For entering numbers,
number virtual keyboard is activated.
Only English is supported to enter.
1
2
3
4
5
Displays keyboard input status.
Select English capital/small letter, number or sign.
Displays group name.
Touch the name and change the group name via the virtual keyboard.
4
No. of CHs
Displays the set number of channels.
5
Background
Set the group background color via the color select dialog box.
Pen1-4/ 5-8
/9- 12/13-16
7.1.3Group Setting
It sets for group and channel information.
You can set the max. 16 channels according to input channels.
Input channel is available to set duplicated to one or several groups. Set the channel to each
group and pen color.
Groups are up to 6.
1 Group
2 CH Rotation Time
,
Set the channel automatical rotation time.
Setting range: 0 to 3600s. (0: changing channels manually by touching
3 Name
6
7
Pen □
Set the channel, color, line style, min./max. value by each pen.
Min./Max. value of each channel is input range of the input type.
For more information, refer to ‘2.3 Input type and range’.
When starting touch calibration, total 5 points are displays one by one. Touch the point and
calibrate it. For more accurate touch, it is recommended to use a stylus pen.
If touch calibration is wrong, re-boot the unit as initial system value.
Touch the right-below area over than twice of the initial booting screen.
It displays occurring alarm(channel, alarm type, relay, start/end time) during operation.
Alarm list displays alarm channel, type, relay, start/end time of occuring alarms. You can save or
delete the alarm list. Alarm list is saved as *.csv file format.
When turing OFF power of KRN1000 while alarm occurs, end time is displayed as "0000-00-00
00:00:00".
Touch ‘History’ to check the data of alarm occuring point as horizontal trend/vertical trend/divided
horizontal trend/divided vertical trend graph.
Divided trend graph is displays divided screen to compare and check different time of the one file.
When recording starts/stops several times from starting to completing alarm, several log files are
created.
If there are several log files from starting alarm to end alarm, it displays the history of first log file
which includes alarm start time.
the input range.
Setting range: Min. value of input range to high-limit graph scale value–F.S. 5%
E.g.) In case of TC-K input, -200.0 to 1350.0℃ of input range, and setting range
is -200.0 to 1272.5℃. (-F.S.=77.5)
7 Menu
No
Item
Descriptions
Graph
the input range.
In case of analog input, it displays high-limit input value.
- Temperature sensor input: 0, 0.0
(set the decimal point position for the scale value)
7
Tag Name
Set the channel name.
Low-Limit
Scale
High-Limit
Scale
Display
- Analog input: 72 display units are available. When not using unit, select blank.
Scale/
High-Limit
Input
Setting range: Low-limit graph scale value+F.S. 5% to Max. value of input range
E.g.) In case of TC-K input, -200.0 to 1350.0℃ of input range, and setting range
is -122.5 to 1350℃. (+F.S.=77.5)
6 Point
8
9
10
Unit
2
※
(set the decimal point for the measurement value)
- Analog input: 0, 0.0, 0.00, 0.000, 0.0000
Set the desired display value based on the measurement value.
1
It is activated only for analog (voltage, current (shunt)) input type.
※
- Temperature senosr input: Temperature units, ℃, ℉, ˚K are available.
※1. As below figure, for example, measured input values are ‘a’ and ‘b’ and the desired display
values are ‘A’, and ‘B’. In this case, about the input ‘a’ and ‘b’, it displays a=A, b=B as
linearly.
You can change display value about min./max. input value of the measurement value.
Displays the applied measurement value as the set special function.
Two Unit is activated only for 4-20mA (shunt) input type.
3
Ref CH
Corrects error from input (thermocouple, RTD, voltage, current (shunt)), not
(depending on the set decimal point, the range is different.)
Adjusts high-limit error by regulating display value which is about
measurement value or applied scale.
Set the recording method of measured data by each channel.
Setting
value
Instant
Saves measurement value at every recording cycle.
Saves the average value of sampling measurement value
during recording cycle.
Saves the min. value of sampling measurement value during
recording cycle.
Saves the max. value of sampling measurement value during
recording cycle.
In some applications the fluctuating measured input causes the display value
may be different with input value.
No. of
7.3.2Input Option
1 Channel
2
Func.
1
※
4 Two Unit
5 Input Bias
2
6
7
※
Span
Record
Method
8 Digital Filter
Moves channel. Touch ‘CH1’ or
to change the channel.
Depending on input type, applicable special functions are different.
Setting range
- Temperature sensor input: None, Difference (deviation)
- Analog input: Linear, Root, Square, Two Unit
from the recorder.
Setting range: -9999 to 9999, -999.9 to 999.9, -99.99 to 99.99, -9.999 to 9.999
-0.9999 to 0.9999
Descriptions
Average
Min
Max
to fluctuate. In this case accurate display/record is disable. This function is
able to make display value stable by input digital filter. Input digital filter uses
moving average method. It does not affet to display period but display value
Digital
9
Filters
3
※
menu is activated.
Setting range: 1 to 128
Set the number of samplings which apply to digital filter. Set Filter type and this
It is available to set for temperature sensor (Thermocouple, RTD) input type. It displays the
deviation of the measurement value of reference channel.
(display value = the measurement value of standard channel –the measurement value of
reference channel)
The channels which input type is analog (voltage, current (shunt)) cannot be as reference
channel. If reference channel is not set, it displays the measurement value of standard
channel.
If any one of reference channel, or standard channel is break (BURN), high-limit value
(HHHH), low-limit value (LLLL) status, it displays as correspond value. If the set reference
channel uses difference function, it displays the calcuated value based on actual
measurement value, not display value of reference channel.
It applies low-limit scale and high-limit scale to low-limit input value and high-limit input value
and displays this values.
In case of low-limit input value: -5 V, high-limit input value: +5V, low-limit scale: -1000, highlimit scale: 1000,
and current input value is 2V, display value is 400.
Display value
=
(
400 =
×
7
× 2000 1000
10
Input value Low limit input value
High limit input value Low
limit input value
High limit scale Low limit scale)+ Low limit scale
(c)Root
In case voltage, current input type, this function calculates by Root () for the input value.
Differential pressure signal of differential pressure flow meter is calculated by Root (
) for
the desired pressure flow. This function is used for measuring flux by input value.
In case of low-limit input value: -5 V, high-limit input value: +5V, low-limit scale: -1000, highlimit scale: 1000,
and current input value is 2V, display value is approx. 673.32.
Display value
=
(
×
High limit scale Low limit scale)+ Low limit scale
Input value Low limit input value
High limit input value Low
limit input value
7
673.32 =
× 2000 1000
10
(d)Square
In case voltage, current input type, this function calculates by square for the input value.
Reverse of Root, flux signal is calcualted by suqare for differential pressure signal.
In case of low-limit input value: -5 V, high-limit input value: +5V, low-limit scale: -1000, highlimit scale: 1000,
and current input value is 2V, display value is -20.
Display value
=
×
(
Input value Low limit input value
High limit input value Low
limit input value
High limit scale Low limit scale)+ Low limit scale
20 =
7
× 2000 1000
10
(e)Two Unit
For compound pressure, if input pressure is lower than atmospheric pressure (0), it displays
the degree of a vacuum with mmHg unit. If input pressure is higher than or same as
2
atmospheric pressure (0), it displays positive pressure with kg/cm
When using Two Unit function, low-limit value is fixed as -760mmHg and the setting range of
2
kg/cm
In case of Two Unit, decimal point position is limited among 0, 0.0, 0.00. When using Two
Unit function, display unit is changed as mmHg or kg/cm
is 1 to 35.
2
automatically.
unit..
This function has two different unit values and it is impossible to calcuate by recording
method and digital filter and ignore it.
Setting range: 1 to 35
Two Unit function is available only when connecting shunt resistance 250Ω, and 4-
Max. value of pressure range (E.g.: For -760mmHg to 3kg/cm2, it means "3")
1.033
Converted value from 760 mmHg to kg/cm2 unit value (same unit)
Y
Use pressure + 1.033 (E.g.: used pressure is ‘0’, it is 1.033)
4
Min. value of output (when output is 0) 4.00mA
Low-limit
value
High-limit
value
Gradient
value
Display
range
Low-limit
value
High-limit
value
Gradient
nt value
Unit changing point
(mA)
If pressure range is -760mmHg to 3kg/cm
displays -760mmHg for 4mA input and 8mA is unit changing point. For 20mA input, it displays
3kg/cm
2
.
2
, pressure transmitter outputs 4 to 20mA, and it
Range
-760mmHg to 1kg/cm2 12.130
-760mmHg to 5kg/cm2 6.740
-760mmHg to 10kg/cm2 5.498
-760mmHg to 15kg/cm2 5.031
-760mmHg to 20kg/cm2 4.786
-760mmHg to 25kg/cm2 4.635
-760mmHg to 30kg/cm2 4.533
-760mmHg to 35kg/cm2 4.459
Unit changing point = (
16
X+1.033
× Y) + 4
※2. When fixing low-limit scale value and high-limit scale value and set gradient, input range is 0
to 10V, low-limit scale value is 0.00, high-limit scale value is 10.00, the display values are as
below by changing gradient as 0.500, 1.000, 1.500.
scale
0.00 10.00 0.500
0.00 10.00 1.000
0.00 10.00 1.500
scale
adjustment
value
0.00 to
5.00
0.00 to
10.00
0.00 to
15.00
Same
result
=
scale
scale
adjustme
0.00 5.00 1.000
0.00 10.00 1.000
0.00 15.00 1.000
When fixing low-limit scale value and high-limit scale value and set gradient (subtraction
gradient), input range is 0 to 10V, low-limit scale value is 10.00, high-limit scale value is 0.00,
the display values are as below by changing gradient as 0.500, 1.000, 1.500.
Set alarm type for operation. You can set alarm type for each channel. When
alarm occurs, alarm icon appears and you can check alarm by channel.
It activates when alarm type is deviation high-limit alarm (DV.Hi) or deviation
channel, deviation high-limit alarm or deviation low-limit alarm occurs.
Set alarm setting value.
Setting range: Within the input/display range of the set input type
Set delay time (unit: sec.) to prevent alarm malfunction by wrong input from
output turns OFF. (Alarm ON channel clears the display.)
Set the output relay number to execute contact output by each alarm type.
9
Save Event
Set as ON to save alarm information when alarm occurs at alarm event file.
7.3.3Alarm
You can set alarm up to 4. Alarm 1 to 4 are same setting items.
1 Channel
1
Type
※
2
3 Ref. CH
Option
※
4
2
5 Setting Value
3
Hys
※
6
ON/OFF
7
Delay
4
※
8 Alarm No.
Moves channel. Touch ‘CH1’ or
to change the channel.
low-limit alarm (DV.Lo). Set the reference channel for deviation high-limit
alarm (DV.Hi) or deviationlow-limit alarm (DV.Lo). When the display value of
the channel is smaller or larger than the display value of the set reference
Set alarm output operation for alarm type.
Set the interval between ON and OFF of alarm output.
external disturbance and noise.
- ON delay time: Even after standby the set time when alarm ON condition
(alarm ON channel flashes on screen), if it is still alarm condition, alarm
output turns ON. (Alarm ON channel flashes on screen).
- OFF delay time: Even after standby the set time when alarm clear condition
(alarm ON channel display is hold), if it is still alarm clear condition, alarm
If setting as ‘None’ and when alarm occurs, it displays alarm at screen and
saves alarm type and alarm occuring time but alarm does not output.
If setting output relay for alarm, the set relay turns ON. Alarm output displays
as Relay-□.
10 Copy Copies settings of the current channel to the other channel.
If it is alarm condition, alarm output is ON. If it is a clear alarm condition,
alarm output is OFF.
Latch
Alarm latch
If it is alarm condition, alarm output is ON and maintains ON status.
When power is supplied and it is alarm condition, this first alarm condition
value setting or clear alarm forcedly
Alarm latch
sequence
If it is alarm condition, it operates both alarm latch and standby sequence.
is ignored and from the second alarm condition, alarm latch operates.
※1. Alarm type
Absolute
value
2
high-limit
alarm
Absolute
value
3
low-limit
alarm
Deviation
4
high-limit
alarm
Deviation
5
low-limit
alarm
Input
6
break
alarm
PV.Hi
(▲)
PV.Lo
(▼)
DV.Hi
(△)
DV.Lo
(▽)
SBA
(S)
Alarm setting value: 90℃
If display value is same or
higher than alarm setting
value, alarm output turns
ON.
Alarm setting value: 90℃
If display value is same or
lower than alarm setting
value, alarm output turns
ON.
If the deviation between
value: -10℃
value: 10℃
display value and the
display value of reference
channel is same or higher
than alarm setting value,
alarm output turns ON.
If the deviation between
value: 10℃
value: -10℃
display value and the
display value of reference
channel is same or lower
than alarm setting value,
alarm output turns ON.
In case input is not connected, or input cable is break during controlling,
alarm output turns ON. You can check whether input cable is break by
external contact of alarm output using buzzer or other devices.
H: Alarm output hysteresis
※2. Option
Normal
is ignored and from the second alarm condition, standard alarm operates.
StBy
Standby
alarm
When power is supplied and it is not alarm condition, from the first alarm,
standard alarm operates.
Condition of re-applied standby sequence: Power ON, change the alarm
La+St
and standby
When power is supplied and it is alarm condition, this first alarm condition
In case of alarm by alarm latch, to clear alarm output, use digital input for alarm clear or turn
OFF the power and turn ON it.
To clear alarm output by digital input, digital input function should be set as ‘Alarm Reset’.
Clearing alarm output is only when alarm option is alarm latch and alarm latch and standby
sequence, or alarm is out of operation range. Alarm output operates normally form the next
alarm output ON.
Set communication speed, baud rate.
Setting range: 2400, 4800, 9600, 19200, 38400 (unit: bps)
Set communication parity bit.
- Setting range: None, Odd, Even
Set communication stop bit.
- Setting range: 1, 2 (unit: bit)
To prevent possible error due to communicating with low speed Master
- Setting range: 5 to 99 (unit: ms)
6
Protocol
Set communication protocol. It supports only RTU.
Set enable/disable writing parameter setting values of KRN1000 via
regardless of communication write enable/disable setting.
8
RS422/485 Port
Set using/not using RS422/485 communication.
7.4.3RS422/485
It sets about RS422/485 communication. Communication setting is available only at KRN1000
parameter. You can only check the items and by communication but cannot change the set.
RS422/485 communication makes set or monitor parameters at extenral upper system (PC or
graphic panel, etc.) and uses transfer data.
It is recommended to use our dedicated software program DAQMaster for monitoring. If you
want to develop monitoring program not using our DAQMaster program or to use the related
Modbus program, please refer to user manual for communication.
Visit our homepage (www.konics.com) to download DAQMaster program, and user manual for
communication.
1 Comm. Address
2 Buad Rate
3 Parity Bit
4 Stop Bit
Response Wait
5
Time
7 Comm. Write
The set communication address is applied to RS422/485, Ethernet, USB
device communication. Duplicated communication address setting is not
(PC, PLC, etc), set communication response wait time.
If setting too short communication response wait time, communication
error may occur in Master.
RS422/485 communication. Reading parameter setting value is available
Over two communications among RS422/485, Ethernet, USB Device communication are not
activated at the same time. Set one communication and the others are automatically not
activated.
Set the IP address to recognize deivce on the network.
IP conflict.
To recognize network ID part and host ID part of IP address, set 32-bit
address allowing to IP packet receiver.
3
Default Gateway
Set IP address to connect Iprouter directly.
Set enable/disable writing parameter setting values via ethernet
of communication write enable/disable setting.
Set enable/disable ethernet communication.
When ethernet port is setting as enable, USB device is disable.
Set enable/disable writing parameter setting values via USB
of communication write enable/disable setting.
Set enable/disable USB communication.
When USB device is setting as enable, ethernet port is disable.
7.4.4Ethernet/USB
This function is for remove transferring/managing data at the long distance via ethernet/USB
communication.
You can manage each device data by assigning the fixed IP at the dedicated device.
1 IP Address
2 Subnet Mask
4 Comm. Write
5 Ethernet Port
USB Comm.
6
Write
7 USB Device
If there are same IP on the network, communication does not operate by
communication. Reading parameter setting value is available regardless
communication. Reading parameter setting value is available regardless
※1. In case of Ethernet connection, and connecting through the network such as network hub
(HUB) and gateway, etc, there is no distance limit, but it is recommaned to use min. network.
Please use communication cables which is satisfied the below conditions.
USB device is recognized as USB to Serial device and communication speed: 115200bps, start
bit: 1-bit, data bit: 8-bit, parity bit: none, stop bit: 1-bit are fixed.
USB Device communication may cause recognition error by external noise and environment
during connecting PC. If there is error, please re-connect this. Please use USB Device as for
setting. During communication, if you chaging the communication settings, it may cause
communication error.
RS422/485 communication port of KRN1000 has 5 terminals; RXD0-, RXD0+, TXD0-, TXD0+,
GND.
When using terminal resistance, connect the terminal resistance at the end of recordor at
connected communication line and turn ON the terminal resistance which is connected with PC.
Set the summer time duration. Set enable to summer time and designate
start date and end date of summer time.
Set the summer time bias.
Setting range: -1 hour, -30 min, 30 min, 1 hour
7.5System Info.
It sets about KRN1000 system such as date, time, reservation recording, and option, etc.
7.5.1Date/Time
It sets system date, time of KRN1000. Based on the set date (year, month, day) and time (hour,
min, sec), data is recorded and saved. You can check the record time based on the set time.
Must set the current time before recording the data.
It manages parameter setting files which are saved at KRN1000 memory, resets parameters.
Parameter
1
Setting File
Internal
2
Memory
3 SD Memory
4 USB Memory
Reset
5
Parameters
Screen
6
Simulation
(Demo)
Displays parameter setting file name.
Save the set parameter information at the dedicated memory or open it.
Reset parameter settings as factory default.
Execute simulation the set parameters.
Touch ‘Start’ and re-boot the unit and simulation mode starts.
Touch ‘Stop’ to exit simulation mode and re-boot the unit.
Displays model name, firmware version, memory usage, communication, slot
If error is continued, contact our service center.
Update firmware.
When completes firmware update, re-boot the unit.
Set the booting screen.
4
License
Displays open source license and download path of KRN1000.
7.5.6System Info.
It displays system information and executes firmware update and sets booting screen.
1 System Info.
2 Update
Booting
3
Screen
information.
If actually connected input/output slot information is different with the screen,
check the connections and re-boot the recorder.
Download the firmware at our web site (www.konics.com).
Save the downloaded firmware at the top-level folder on USB/SD memory
and insert the memory KRN1000 and update it.
Touch ‘Update’ and update setting menu displayed.
Do not turn OFF the power during firmware update.
Booting screen image name should be “boot.png”. Save the image at the
top-level folder on USB/SD memory and insert the memory KRN1000 and
update it.
Touch ‘Booting Screen’ and booting screen setting menu displayed.
It captures the current screen at internal, SD/USB memory as *.bmp file.
Internal memory saves the set number of screen captures at Menu > Memory Info. > Internal
Memory.
8 Integrated device management program (DAQMaster)
8 Integrated device management program
(DAQMaster)
8.1 Overview
DAQMaster is the comprehensive device management program and is able to utilize for
temperature controller product line, meter product line, counter product line and recorder product
line, etc.
DAQMaster provides graph user interface (GUI) for easy and convenient integrated several
products’ parameter setting and data monitoring.
Visit our homepage (www.konics.com) to download ‘DAQMaster user manual’.
This ‘KRN1000 user manual’ describes only for dedicated KRN1000 functions. For more
information about DAQMaster, please refer to ‘DAQMaster user manual’.
8 Integrated device management program (DAQMaster)
8.2Features
DAQMaster has the following features.
Supports multiple device
DAQMaster is able to simultaneously monitor multiple devices and set parameters of the
devices. The units with different addresses in a single device are connectable at the same
time. In Modbus RTU communication, several RS232 port are available.
Device scan
In case multiple units (with different addresses) are connected together, use unit scan
function to automatically search for units.
Convenient user interface
User can arrange windows, attributes, and project screens, etc to monitor the data as
convenient. When saving the project, set screen is also saved.
Project management
You can save the setting of monitoring for added device and data, selection of I/O source,
etc as the project. When loading the project, this file has the saved setting status. You can
also construct project list for convenient project file management.
Monitoring data log
It logs the data during monitoring and is able to save it as one of DAQMaster data file (*.ddf)
or CSV file (*.csv). You can load the saved CSV file in Microsoft Excel directly. You can
also designate file name, storage rules, and storage folders for easy file management.
Data analysis
You can analyze data file (*.ddf) with DAQMaster’s data analysis function as spread or
graph. You can save the analysis as *.rtf, *.txt, *.html, or *.csv file on spread.
Modbus map table reporting output
It can output the registered Modbus device address map as report. You can save the report
for Modbus map table as HTML file (*.html) or PDF file (*.pdf).
Supports multi-language
It supports Korean, English, Japanese and Simplified Chinese. To add a different language,
modify the files in the Lang folder, rename, and save it.
Supports script
You can designate each other different I/O process by device using Lua scr ipt language.
8 Integrated device management program (DAQMaster)
8.3.1Record Backup
You can download backup data which is saved in KRN1000 internal memory from “Record
Backup” section.
Directory form is year, month, day. Click the relevant icon and check below list.
To download backup file, click the file name with right mouse button and select "Download Log
File" menu.
Backup files are strucured as tree type directory at KRN1000 internal memory. You can easily
fine and download the desired file.
Displays error messages on screen and print data when error occurs.
Descriptions
When input type is temperature sensor (Thermocouple, RTD) and the
measurement value is higher than high-limit value of input range, it flashes
HHHH. It is cleared when the measurement value is within the high-limit range.
HHHH
LLLL
BURN
When input type is analog (voltage, current (shunt)) and the measurement value
is over 10% of high-limit input range, it flashes HHHH. It is cleared when the
measurement value is within 10% of high-limit input range.
When input type is temperature sensor (Thermocouple, RTD) and the
measurement value is lower than low-limit value of input range, it flashes LLLL. It
is cleared when the measurement value is within the low-limit range.
When input type is analog (voltage, current (shunt)) and the measurement value
is over 10% of low-limit input range, it flashes LLLL. It is cleared when the
measurement value is within 10% of low-limit input range.
When input type is temperature sensor (Thermocouple, RTD) and input is break,
it flashes BURN. It is cleared when input is connected.
Refer to Burn-out Action of ‘7.3.2 Input Option’.
When forgetting and entering unvaild password 3 times, “ASKey” appears with
error message. Contact our service center with ASKey.