Preface
Preface
Thank you very much for selecting KONICS products.
Please familiarize yourself with the information contained in the Safety Precautions section before using this product.
This user manual contains information about the product and its proper use, and should be kept in a place where it will be easy to access.
© Copyright Reserved KONICS Co., Ltd. iii
User Manual Guide
User Manual Guide
This user manual contains information about the product and its proper use, and should be kept in a place where it will be easy to access.
Please familiarize yourself with the information in this manual before using the product.
This manual provides detailed information on the product's features. It does not offer any
guarantee concerning matters beyond the scope of this manual.
This manual may not be edited or reproduced in either part or whole without permission.
A user manual is provided as part of the product package.
Visit our home-page (www.konics.com) to download a copy.
The manual's content may vary depending on changes to the product's software and other
unforeseen developments within KONICS, and is subject to change without prior notice.
We contrived to describe this manual more easily and correctly. However, if there are any
corrections or questions, please notify us these on our homepage.
iv © Copyright Reserved KONICS Co., Ltd.
User Manual Symbols
Symbol
Description
User Manual Symbols
Supplementary information for a particular feature.
Failure to follow instructions can result in serious injury or death.
Failure to follow instructions can lead to a minor injury or product damage.
An example of the concerned feature's use.
1
Annotation mark.
© Copyright Reserved KONICS Co., Ltd. v
Safety Precautions
Safety Precautions
Following these safety precautions will ensure the safe and proper use of the product and
help prevent accidents and minimize hazards.
Safety precautions are categorized as Warnings and Cautions, as defined below:
Warning
Caution
Cases that may cause serious injury or fatal accident if instructions are not followed.
Cases that may cause minor injury or product damage if instructions are not followed.
In case of using this unit with machinery (Ex: nuclear power control, medical equipment,
ship, vehicle, train, airplane, combustion apparatus, safety device, crime/disaster prevention equipment, etc) which may cause damages to human life or property, it is required to install fail-safe device. It may cause a fire, human injury or property loss.
It must be mounted on panel.
It may cause electric shock.
Do not connect, inspect or repair this unit when power is ON.
It may cause electric shock.
Check input power specification and check power terminal number when wiring power cable.
It may cause a fire or damage by a fire.
Lithium battery is used in this product, do not disassemble or burn up this unit.
It may cause an explosion.
Do not touch the product or connect terminal within 30 sec. after turn off the power.
It may cause electric shock.
F.G. terminal should be isolation grounded. Grounded wire should be over AWG16(1.25
2
).
mm It may cause electric shock.
Do not insert your finger or object into the vent of this unit.
It may cause electric shock or human injury.
Do not disassemble or modify this unit. Please contact us if it is required.
It may cause a fire, human injury or property loss.
This unit shall not be used outdoors.
It may shorten the life cycle of the product or cause electric shock.
When wiring power input terminal and measuring input terminal, power line should be over
AWG 20(0.50mm2). Terminal screw should be tightened with 0.74 Nm to 0.90 N•m torque.
Please observe the rated specifications. It may cause shorten the life cycle of the product and cause a fire.
vi © Copyright Reserved KONICS Co., Ltd.
Safety Precautions
Do not use the load over the rated switch capacity value of relay contact part.
It may cause insulation failure, contact melt, contact failure, relay broken, fire etc.
When connecting magnet contact as load of relay contact output, connect surge absorber
on coil part of contact. It may cause malfunction.
In cleaning the unit, do not use water or organic solvent. And use dry cloth.
It may cause electric shock or a fire.
Do not use this unit in place where there is flammable, explosive gas, humidity, direct light,
radiant heat, vibration, or impact. It may cause a fire or explosion.
Do not inflow dust or wire dregs into the unit.
It may cause a fire or malfunction.
Wire properly after checking the terminal polarity.
It may cause a fire or explosion.
Wire properly after checking the terminal polarity when connecting temperature sensor.
It may cause malfunction.
Connection should be followed as connection diagram of this manual. Before power ON,
check the connection correct. It may cause a fire.
Do not touch terminal during dielectric or insulation resistance test.
It may cause electric shock.
It is recommended to use insulation transformer and noise filter power in case of too much
noise from power. Attach noise filter on the grounded panel, etc. Wire between noise filter output part and power terminal of the product should be short as possible. It may cause damage to the product, malfunction by surge, etc.
Before connecting temperature sensor (thermocouple, RTD) and analog (voltage, current)
input, set jumper pin of universal input card as input type. It may cause damage and malfunction to this unit.
Do not connect or separate input, output card when the product power is ON.
It may cause serious damage.
Do not open the cover or insert your finger during operation.
It may cause electric shock.
Do not control with alarm output or measure data during firmware upgrade. Alarm output,
contact input, data measurement, etc do not operate normally. Therefore, this unit does not operate as intended.
Check the complete message for firmware upgrade and turn OFF to ON the power.
If do not turn OFF to ON the power, it does not operate normally.
All parameter set value is initialized after firmware upgrade. It may not operate as same way
with before upgrade operation.
Use voltage output of transmitter power output card only for transmitter power.
It may cause damage to output module.
The specifications and dimensions of this manual are subject to change without any notice.
© Copyright Reserved KONICS Co., Ltd. vii
Table of Contents
Table of Contents
Preface ............................................................................................................................. iii
User Manual Guide
User Manual Symbols
Safety Precautions
Table of Contents
1 Overview .................................................................................................... 13
1.1 Feature of KRN 100 ........................................................................................... 13
1.2
Component and sold separately ........................................................................ 14
1.2.1 Component ................................................................................................. 14
1.2.2 Accessory ................................................................................................... 14
1.3 Ordering information .......................................................................................... 15
Part description .................................................................................................. 17
1.4
1.4.1 Front and side part ..................................................................................... 17
1.4.2 Back side .................................................................................................... 19
1.4.3 Inside .......................................................................................................... 20
1.4.4 Paper cassette ........................................................................................... 20
......................................................................................................... iv
...................................................................................................... v
.......................................................................................................... vi
........................................................................................................... viii
2 Specification .............................................................................................. 21
2.1 KRN100 ............................................................................................................. 21
2.2
I/O card .............................................................................................................. 23
2.3
Input specification and measuring range .......................................................... 25
3 Dimensions ................................................................................................ 27
4 Connection ................................................................................................ 29
4.1 KRN100 ............................................................................................................. 29
4.2
I/O card .............................................................................................................. 30
5 Installation ................................................................................................. 33
5.1 Installation place ................................................................................................ 33
Installation .......................................................................................................... 34
5.2
5.2.1 Bracket mounting ....................................................................................... 34
5.2.2 Additional I/O card connection ................................................................... 35
5.3 USB to Serial driver ........................................................................................... 36
5.3.1 Driver installation ........................................................................................ 36
5.3.2 Checking driver .......................................................................................... 38
6 Display ....................................................................................................... 39
6.1 Initial booting screen .......................................................................................... 39
6.2
Screen layout ..................................................................................................... 40
6.2.1 Status display ............................................................................................. 40
6.2.2 Virtual keyboard ......................................................................................... 43
6.2.3 Parameter setting display ........................................................................... 44
7 Operation ................................................................................................... 45
viii © Copyright Reserved KONICS Co., Ltd.
Table of Contents
7.1 Screen display ................................................................................................... 46
7.1.1 Measuring value display ............................................................................. 46
7.1.2 Channel switch ........................................................................................... 48
7.2 Special operation for record ............................................................................... 50
7.3
Parameter setting group .................................................................................... 51
7.3.1 Parameter setting ....................................................................................... 51
7.3.2 Parameter ................................................................................................... 52
8 Parameter detail setup .............................................................................. 55
8.1 INPUT SETUP(Input setting) ............................................................................. 55
8.1.1 Select UI Card (Select universal input card) .............................................. 57
8.1.2 Input Set Copy (Copy input parameter) ..................................................... 57
8.1.3 LCD/Paper Record (Display and record measuring value) ........................ 58
8.1.4 Pen Color (Record color) ........................................................................... 58
8.1.5 Record Zone (Record zone) ....................................................................... 58
8.1.6 Tag Name (Channel name) ........................................................................ 59
8.1.7 Input Type (Input specification) .................................................................. 59
8.1.8 Range/Scale Point (Decimal point) ............................................................ 59
8.1.9 Display/Temp Unit (Display unit/Temperature unit) .................................... 60
8.1.10 High/Low Range & Graph Scale(Upper/Lower limit input value and graph
scale value) ............................................................................................... 61
8.1.11 Low Scale/High Scale (Lower limit/Upper limit scale value) ...................... 63
8.1.12
8.1.13 Reference Channel (Reference channel) .................................................. 69
8.1.14 Input Bias(Error correction) ........................................................................ 69
8.1.15 Span (Gradient adjustment) ....................................................................... 70
8.1.16 Record Method (Data storage method) ..................................................... 71
8.1.17 Filter Type (Input digital filter) ..................................................................... 71
8.1.18 Filter Counter (The number of digital filter) ................................................ 72
8.1.19 Burnout Action (Display setting for break) .................................................. 73
8.2 ALARM SETUP (Alarm setting) ......................................................................... 74
8.2.1 Select UI Card (Select universal card input) .............................................. 75
8.2.2 Alarm Set Copy (Copy alarm parameter) ................................................... 75
8.2.3 Alarm□ Type(Alarm□ operation mode) ....................................................... 76
8.2.4 Alarm□ Ref Channel(Alarm□ reference channel) ....................................... 78
8.2.5 Alarm□ Option(Alarm□ option) ................................................................... 79
8.2.6 Alarm□ Value(Alarm□ set value) ................................................................ 80
8.2.7 Alarm□ Hysteresis(Alarm□ hysteresis) ....................................................... 81
8.2.8 Alarm□ ON/OFF Delay(Alarm□ ON/OFF output delay time) ..................... 82
8.2.9 Alarm□ Alarm No(Alarm□ output alarm number) ....................................... 83
8.2.10 Select Alarm Card(Select alarm output card) ............................................. 83
8.2.11 Alarm-□ Status(Relay and TR output method) ........................................... 84
8.3 DIGITAL INPUT SETUP(Digital input setting) ................................................... 85
8.3.1 Select DI Card (Select digital input card) ................................................... 86
8.3.2 DI-□ Type (Select digital input □ ) ................................................................ 87
8.3.3 DI-□ Reset No (Reset alarm number) ........................................................ 88
8.3.4 DI-□ Status (Operation status) ................................................................... 88
8.4 COMMUNICATION SETUP (Communication setting) ...................................... 89
8.4.1 Modbus Address (Communication address) .............................................. 92
8.4.2 RS485 Port (Use RS485 communication) ................................................. 92
Special Function (Special function) ............................................................ 65
© Copyright Reserved KONICS Co., Ltd. ix
Table of Contents
8.4.3 Baud Rate (Baud rate) ............................................................................... 92
8.4.4 Parity Bit (Communication parity bit) .......................................................... 93
8.4.5 Stop Bit(Communication stop bit) ............................................................... 93
8.4.6 Termination Set (Terminating resistance) ................................................... 93
8.4.7 Response Wait Time (Communication response wait time) ...................... 94
8.4.8 Protocol (Communication protocol) ............................................................ 94
8.4.9 RS485 Com Write (RS485 communication write) ...................................... 94
8.4.10 Ethernet Port (Use Ethernet communication) ............................................ 95
8.4.11 IP Address (IP address) ............................................................................. 97
8.4.12 Subnet Mask (Subnet Mask) ...................................................................... 97
8.4.13 Default Gateway (Default gateway) ........................................................... 97
8.4.14 Ethernet Com Write (Ethernet communication write) ................................. 98
8.4.15 USB Device Port (Use USB communication) ............................................. 98
8.4.16 USB Com Write (USB communication write) ............................................. 98
8.5 RECORD SETUP (Record setting) ................................................................... 99
8.5.1 Record Mode (Recode mode) .................................................................. 100
8.5.2 Digital Print type (1 line record channel during numeric recording) ......... 101
8.5.3 Standard Speed (Standard record speed) ................................................ 102
8.5.4 Option Speed (Option record speed) ....................................................... 102
8.5.5 Memo Period (Digital memo period) ........................................................ 103
8.5.6 Divide Zone (Record zone division) ......................................................... 105
8.5.7 Standard Period (Standard record period) ............................................... 106
8.5.8 Option Period (Option record period) ....................................................... 106
8.5.9 Listing Language (Language for list output) ............................................. 107
8.5.10 Alarm Speed (Alarm record speed) .......................................................... 108
8.5.11 Power On Status (Record status when power ON) .................................. 108
8.5.12 Run Status (List printing at start recording) .............................................. 109
8.5.13 List Out Option (List record option) .......................................................... 110
8.5.14 Zone Dot Line Distance (Dot line for zone division) .................................. 111
8.5.15 CH Print Distance (Record interval for each channel graph) .................... 111
8.5.16 Start Line Print (Start line when starting record) ....................................... 112
8.5.17 Range Print Time (Input range record period) .......................................... 112
8.6 SYSTEM SETUP (System setting) .................................................................. 113
8.6.1 Device Name (Device name) ................................................................... 114
8.6.2 Date/Time (Date/Time) ............................................................................. 11 4
8.6.3 Date Type (Date type) .............................................................................. 114
8.6.4 Summer Time (Summer time) .................................................................. 115
8.6.5 Summer Time Period (Summer time period) ............................................ 115
8.6.6 Reservation Type (Reservation record) ................................................... 116
8.6.7 Reservation Period (Reservation record period) ...................................... 117
8.6.8 Reservation Time (Reservation record time) ............................................ 117
8.6.9 Alarm Sound (Alarm sound) ..................................................................... 118
8.6.10 Sampling Rate (Sampling period) ............................................................ 118
8.6.11 Log Speed (Save period) ......................................................................... 119
8.6.12 Backlight (LCD backlight brightness) ....................................................... 119
8.6.13 Backlight On/Off (LCD backlight ON method) .......................................... 119
8.7 FILE/MEMORY SETUP(File/Memory setting) ................................................. 120
8.7.1 Load Set File (Open parameter setting file) ............................................. 121
8.7.2 Save Set File (Save parameter setting file) .............................................. 121
8.7.3 Memory Status (Memory capacity) ........................................................... 122
8.7.4 Memory Clear (Delete memory) ............................................................... 122
x © Copyright Reserved KONICS Co., Ltd.
Table of Contents
8.7.5 USB LogData Save (USB storage function) ............................................ 123
8.7.6 Memory Save Option (Memory storage option) ....................................... 124
8.7.7 USB Memory Copy/Move (Move/Copy data) ........................................... 125
8.8 USER INFORMATION SETUP(User information setting) ............................... 126
8.8.1 Password (Password mode) .................................................................... 127
8.8.2 Login Admin (Administrator log in) ........................................................... 128
8.8.3 Change Admin Password (Change password by administrator) ............. 128
8.8.4 User Lock (Change user authority) .......................................................... 129
8.8.5 Information (Check system information) .................................................. 129
8.8.6 Firmware Upgrade (Firmware upgrade) ................................................... 130
8.9 RECORD BACKUP_ SETUP (Backup data record setting) ............................ 132
8.9.1 Record Backup (Backup data record) ...................................................... 133
8.9.2 Backup Data List (Backup data list) ......................................................... 133
8.9.3 Start Date and Time (Start time for data storage) .................................... 134
8.9.4 End Date and Time (End time for data storage) ...................................... 134
8.9.5 Backup Print Mode (Backup data record mode) ...................................... 134
8.9.6 Select Print Mode (Backup data recording mode setting) ....................... 135
9 DAQMaster .............................................................................................. 137
9.1 Overview .......................................................................................................... 137
9.2
Features ........................................................................................................... 138
Dedicated KRN100 functions .......................................................................... 139
9.3
9.3.1 Record Backup ......................................................................................... 139
9.3.2 User unit setting ....................................................................................... 140
9.3.3 Boot logo image setting ............................................................................ 141
9.3.4 Backup data checking function ................................................................ 142
10 Maintenance ............................................................................................ 145
10.1 Ink cartridge replacement ................................................................................ 145
Recording paper replacement ......................................................................... 146
10.2
11 Troubleshooting ...................................................................................... 151
11.1 Error message ................................................................................................. 152
© Copyright Reserved KONICS Co., Ltd. xi
Table of Contents
xii © Copyright Reserved KONICS Co., Ltd.
1 Overview

1 Overview

1.1 Feature of KRN 100

KRN100 is 100mm hybrid recorder with dot. It combines functions of paper recorder and paperless recorder by saving function with an USB memory (the world’s first) and by adopting Trend graph, Bar graph, digital number display function through graphic LCD.
KRN100 enables to print the saved data of system memory as data backup function when run out of recording paper. KRN100 improves convenience by parameter setting, data transmittion through RS485 and Ethernet communication (USB device is only for parameter setting), and backup data logger function.
It also adopts slot type input, output card to connect option card up to 12 channels. It supports several communication types, of course, and graphic user interface(GUI) with graphic display for easire and convenient use.
Combines functions of paper recorder and paperless recorder
Enables to print the saved data of inner memory when run out of recording paper (Data
logger function)
Inner data backup with an USB memory
High legibility and setting convenient by graph LCD
25ms high sampling, 240mm/h high speed record function
100mm paper record (Selectable 6 kinds of record color)
Supports system memory and external memory data backup (storage)
Supports several input up to 12 channel with slot type input card
Enables to select several option card with slot type output card
Supports several communication(RS485, Ethernet) to transfer real time data
Enables to set parameter with USB Device1
Space saving for installation with compact design (Rear length: 168mm)
Supports total 27 kinds of input sensor
Enables to order several type input card (weight, voltage, current, frequency, potential meter,
etc)
© Copyright Reserved KONICS Co., Ltd. 13
1 Overview

1.2 Component and sold separately

1.2.1 Component

Before using KRN100, check the component. If any component is left out or damaged, contact our company or seller. KONICS service center: +82-32-820-2343

1.2.2 Accessory

(1) I/O card
(2) Communication converter
Appearances of SCM-38I (RS232C to RS485 converter) and SCM-US48I (USB to RS485 converter) are same.
14 © Copyright Reserved KONICS Co., Ltd.
1 Overview
KRN100
-
12 0 0 0 - 0 0 - 0
S

1.3 Ordering information

(1) Ordering information
Item Description
Item
Input channel
Digital input
Alarm TR output
Alarm Relay output
② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨
KRN100 New KONICS 100mm Paper Type Recorder
04 4 channel (KRN-UI2 X 2ea)
06 6 channel (KRN-UI2 X 3ea)
08 8 channel (KRN-UI2 X 4ea)
10 10 channel (KRN-UI2 X 5ea)
12 12 channel (KRN-UI2 X 6ea)
0 None
1 6ea(KRN-DI6 X 1ea)
2 12ea(KRN-DI6 X 2ea)
0 None
1 6ea( KRN-AT6 X 1ea)
2 12ea( KRN-AT6 X 2ea)
0 None
1 4ea( KRN-AR4 X 1ea)
2 8ea( KRN-AR4 X 2ea)
Transmitter power output
Communication output
Power voltage
Case
3 12ea( KRN-AR4 X 3ea)
0 None
1 3ea( KRN-24V3 X1ea)
2 6ea( KRN-24V3 X 2ea)
3 9ea( KRN-24V3 X 3ea)
4 12ea( KRN-24V3 X 4ea)
0 None
1 RS485/Ethernet/USB( KRN-COM X 1ea)
0 100 to 240VAC, 50/60Hz
S Standard panel mounting type
© Copyright Reserved KONICS Co., Ltd. 15
1 Overview
(2) I/O card model name
Type Model name
Universal input
KRN-UI2 Universal input 2 channel 6ea 1 to 6
card
Digital input card KRN-DI6 Digital input 6 channel 2ea
Function and number of channel
Max. connectable card
Slot number
Alarm output card
KRN-AR4
KRN-AT6 Alarm TR output 6 channel 2ea
Transmitter power
KRN-24V3
output card
Communication
KRN-COM
output card
Alarm relay output 4
channel
Transmitter 24VDC power
output 3 channel
RS485+USB+Ethernet
communication channel
3ea
7 to
10
4ea
1ea C
1
1. Digital input card, alarm output card, transmitter power output card are connectable up to
4ea as mixed.
(3) Example of ordering
To use universal input 10 channel, digital input 4 channel, alarm relay output 5 channel, and RS485 communication output, it is ordered as KRN100-10102-01-0S and connected I/O card is as below.
KRN100(Recorder): 1ea
KRN-UI2(Universal input card): 5ea
(Universal input card 2ea is factory default. 5ea X 2 channel =10 channel)
KRN-DI6(Digital input card): 1ea
KRN-AR4(Alarm relay output card): 2ea
KRN-COM(Communication output card): 1ea
16 © Copyright Reserved KONICS Co., Ltd.
1 Overview

1.4 Part description

1.4.1 Front and side part

Display part: Displays measurement values as trend graph, bar graph, or digital number
(1/8/12 channel). Please refer to ‘7.1 Screen display ’.
Recording print part: Records measuring value of data by each channel with designated
color.
Channel information part: Write the information by each channel. Control key/Function key: Executes parameter setting and recording, and special function
Key Function
Using this key for starting/stopping recording, changing input characters on virtual keyboard status, and displaying Function key.
Press this key for 3 sec in stop state, ink cartridge moves to the center. (Use this to replace ink cartridge.)
Using this key for going out from parameter setting group or setting manual channel switch mode.
It also executes to release auto channel switch mode and printer list output (3 sec) function.
Using this key for moving parameter in setting mode, setting manual channel switch mode and forced alarm reset (3 sec).
Using this key for moving parameter in setting mode, increasing digit value, setting auto channel switch mode, and manual feed function (by pressing over 3 sec.) in stop state.
Using this key for moving parameter in setting mode, decreasing digit value, changing display mode and executing manual digital memo (3 sec) in recording state.
Using this key for entering setting mode (3 sec) and set value change mode.
USB Host: Connects an USB memory. It recognizes max. 32Gbyte and if using cable, it is
available up to 1.5m.
© Copyright Reserved KONICS Co., Ltd. 17
1 Overview
Function key: Use this key to enter virtual keyboard in parameter setting.
Press ke y, and Function key appears on lower screen as below figure. Press ,
, , , or key as below Function key, it operates the appropriate Function
key’s operation.
18 © Copyright Reserved KONICS Co., Ltd.
1 Overview

1.4.2 Back side

Slot(C) for connecting communication output card(KRN-COM) Slot(7to10) for connecting digital input card(KRN-DI6), alarm relay output card(KRN-AR4),
alarm TR output card (KRN-AT6), transmitter power output card(KRN-24V3) You can connect total 4ea by combining digital input card, alarm output card, and transmitter power output card, as below combination example.
KRN-DI6
1ea
KRN-DI6
2ea
KRN-AT6
1ea
KRN-AR4
+
1ea
KRN-AR4
+
1ea
KRN-24V3
+
3ea
KRN-AT6
+
1ea
KRN-AT6
+
1ea
= Total 4ea
KRN-24V3
+
1ea
= Total 4ea
= To ta l 4ea
Slot(1 to 6) for connecting universal input card(KRN-UI2) Power connecting part (100-240VAC, 50/60Hz)
Above back side image is connected every otuput card to help your understand. Factory
default is only connected with universal input cards (Slot1 and 2).
© Copyright Reserved KONICS Co., Ltd. 19
1 Overview

1.4.3 Inside

Ink cartridge: Record ink cartridge to record data on recording paper.
(Model name: D33006B-66X-01)
Recording paper cassette: Cassette saves the recording paper. Recording paper cassette lever: Press the lever down and this recording paper cassette is
removed from KRN100. Remove the recording paper cassette for recording paper replacement, ink cartridge replacement.

1.4.4 Paper cassette

Recording paper holder: Movement holder of recording paper when recording Recording paper storage part: Storage part for recorded recording paper Front cover of recording paper storage: Open recording paper guide for recording paper
replacement
New recording paper storage: Storage part for new recording paper (1EA recording paper
is storable.)
Back cover of recording paper storage
20 © Copyright Reserved KONICS Co., Ltd.
2 Specification

2 Specification

2.1 KRN100

Model KRN100
Power voltage 100 - 240VAC, 50/60Hz
Allowable voltage range 85 - 264VAC
Power consumption Max. 55VA
LCD type STN Graphic LCD
Resolution 320 X 120Pixel
Screen
Adjusting
brightness
Backlight White LED, 2 level(Temp/Always)
4 level(OFF / Min / Standard / Max)
The number of input
channel
Universal input
Sampling period
Recording period in
graph mode
Storage period
Inner memory 512MByte
USB memory
Function
Dielectric
1
Temperature sensor(RTD, thermocouple), analog
4 / 6 / 8 / 10 / 12 channel(2 channel/card) – Expandable
1 to 4 channel: 25 /125 /250 , 5 to 12 channel: 125 /250
(Inner sampling period is operation unit time for average movement filter
and alarm output function.)
Max. sampling period for TC-R, U, S, and T sensor is 50ms.
10, 20, 40, 60, 120, 240mm/h
1 to 3,600 sec
(Storage interval time to inner log file is 1 sec.)
User purchased, recognizes max. 32GByte,
enables to use cable up to 1.5m
Record color, Record zone, Input special function, Input digital filter,
Reservation set, Summer time, Delay alarm, Record speed change, Data
storage, Backup data record, etc
2,500VAC 50/60Hz for 1 min. (power terminal and case)
USB Device and Ethernet are excepted
Vibration strength
(for convey and storage)
and operating vibration
Insulated resistance Min. 20MΩ (at 500VDC megger)
Noise ±2kV the square wave noise (pulse width 1µs) by the noise simulator
Time accuracy Within ±2min/year (Enables to use up to 2100 year)
Ink
Mechanism
cartridge
© Copyright Reserved KONICS Co., Ltd. 21
Vibration strength: 10to60Hz 4.9m/s2 (in X, Y, Z axes for each 1time)
Operating vibration: 10to60 1m/s2 (in X, Y, Z axes for each 10 min.)
Enables to normal print with going and returning printing max.5 times
within 7 days after opening the unit
2 Specification
Ink dry
time
Protection IP40(for front panel)
Recording paper 113mm X 9m
Installation environment
Temperat
Environ-
2
ment
Approval
Unit weight Approx. 1.7 to 2.0kg
ure
Humidity
Max. 15 minutes
It shall be used indoor, Altitude Max. 2,000m, Pollution Degree2
Installation category II
0 to 50, Storage: -20 to 60, (without ink cartridge)
35 to 85% RH, Storage: 35 to 85% RH
If using this unit at place with high humidity, it may cause paper jam.
Please do not use this unit at place with high humidity.
1. For more information of universal input, please refer to ‘2.2 I/O card’.
2. Environment resistance is rated at no freezing or condensation.
22 © Copyright Reserved KONICS Co., Ltd.
2 Specification
Type
Model
I/O specification
Description
Warm-up time: Min. 30 minutes

2.2 I/O card

Universal
input card
Digital
input card
KRN-UI2
KRN-DI6
RTD
JPT100, DPT100, DPT50, CU100,
CU50Ω(Supply current 420µA)
Input
Thermoco
B, C(W5), E, G, J, K, L, L(Russia), N, P, R, S, T, U
specific
ation
1
uple
Analog
Voltage: ±60mV ±200mV ±2V, 1-5V, ±5V, -1V to
10V
Current: 0.00to20.00 4.00to20.00
Voltage(V): Min. 150k
Input impedance
RTD, thermocouple, voltage(mV): min. 2M
current: 51
RTD
Display
accurac
2
y
Thermoco
uple
Analog
·Room temperature (25℃±5) section: ±0.1% F.S.±
1 Digit
·Out of range of room temperature: ±0.2% F.S.±1 Digit
RTD: 500 to 850 is PV value±0.5%±1 Digit
Thermocouple: Below -100℃ is ±0.3% F.S. ±1 Digit
Resolution 16Bit
ON: Max. 1V of residual voltage, OFF: Max. 0.1
Noncontact input
leakage current
Contact input
ON: Max. 1kΩ, OFF: Min. 100kΩ, Short: Approx. 4
Alarm
output
card
Transmitt
er power
output
card
Communi
cation
output
card
1. To change input specification, you must turn OFF the power of KRN100, remove universal
Capacity
250VAC 3A, 30VDC 3A, 1 Form A (resistance load)
Alarm
KRN-AR4
relay
output
Life
Mechanical: Min. 50,000,000 operations
Electrical: Min. 100,000 operations
(3A 250V AC, 3A 30V DC)
KRN-AT6 Alarm TR output
KRN-
24V3
Power output for
5
transmitter
NPN Open Collector, 12-24VDC / 30 Max.
24±2VDC, total 3 channel, max. 30 per 1 channel
built-in over-current protection circuit
Modbus RTU
RS485
Commu
Recommended to use shield cable over AWG24
KRN-
nication
Ethernet IEEE802.3(U), 10/100 BASE-T(Modbus TCP)
COM
3
output
USB
Device
USB V2.0 Full Speed(Device Control)
4
input card, set inner jumper pin (Please refer to 4.2 I/O card.) and re-connect it.
© Copyright Reserved KONICS Co., Ltd. 23
2 Specification
2. Exception range for better accuracy by sensor (Accuracy after 30min warm-up time)
R,S,C,G: 0≤T≤100 ±4.0,
B: No regulation accuracy below 400
T, U: -200T-100±3.0, -100T400±2.0,
CU50: -200≤T≤200±1.0,
DPT50: -200T500±1.5
3. RS485, Ethernet communication output are not available at the same time.
4. USB Device is available only for parameter setting.
5. It is recommended to use shield cable to decrease noise when supplying power for
transmitter.
If connecting or disconnecting input/output card when power is ON, it may cause malfunction.
To connect or disconnect input/output card, you must turn OFF the power.
24 © Copyright Reserved KONICS Co., Ltd.
2 Specification
Measuring range

2.3 Input specification and measuring range

Input sensor Mark
K(CA) TC-K -200.0 to 1350.0 -328.0 to 2462.0 73.2 to 1623.2
J(IC) TC-J -200.0 to 800.0 -328.0 to 1472.0 73.2 to 1073.2
E(CR) TC-E -200.0 to 800.0 -328.0 to 1472.0 73.2 to 1073.2
T(CC) TC-T -200.0 to 400.0 -328.0 to 752.0 73.2 to 673.2
B(PR) TC-B 100.0 to 1800.0 212.0 to 3272.0 373.2 to 2073.2
R(PR) TC-R 0.0 to 1750.0 32.0 to 3182.0 273.2 to 2023.2
Thermocouple
S(PR) TC-S 0.0 to 1750.0 32.0 to 3182.0 273.2 to 2023.2
N(NN) TC-N -200.0 to 1300.0 -328.0 to 2372.0 73.2 to 1573.2
1
C(TT)
G(TT)
L(IC) TC-L -200.0 to 900.0 -328.0 to 1652.0 73.2 to 1173.2
L (Russian type)
U(CC) TC-U -200.0 to 400.0 -328.0 to 752.0 73.2 to 673.2
Platinel TC-P 0.0 to 1350.0 32.0 to 2462.0 273.2 to 1623.2
CU50 CU50 -200.0 to 200.0 -328.0 to 392.0 73.2 to 473.2
TC-C 0.0 to 2300.0 32.0 to 4172.0 273.2 to 2573.2
※2
TC-G 0.0 to 2300.0 32.0 to 4172.0 273.2 to 2573.2
3
TC-L_R 0.0 to 600.0 32.0 to 1112 . 0 273.2 to 873.2
K
Resistance
temperature
detector
(RTD)
Analog
CU100 CU100 -200.0 to 200.0 -328.0 to 392.0 73.2 to 473.2
JPT100 JPT100 -200.0 to 600.0 -328.0 to 1112 . 0 73.2 to 873.2
DPT50 DPT50 -200.0 to 600.0 -328.0 to 111 2.0 73.2 to 873.2
DPT100 DPT100 -200.0 to 850.0 -328.0 to 1562.0 73.2 to 1123.2
-60.00 to 60.00 ±60 Resolution:10µV
Voltage
Current
-200.00 to
200.00
-2.000 to 2.000V ±2V Resolution: 1mV
1.000 to 5.000V 1 to 5V Resolution: 1mV
-5.000 to 5.000V ±5V Resolution: 1mV
-1.00 to 10.00V -1V to 10V
0.00 to 20.00 0 to 20 Resolution:10µA
4.00 to 20.00 4 to 20 Resolution:10µA
±200 Resolution:10µV
Resolution:
10mV
Depending on decimal point
position setting;
-99999 to 99999
-9999.9 to 9999.9
-999.99 to 999.99
-99.999 to 99.999
-9.9999 to 9.9999
1. C(TT): Same temperature sensor type as existing W5(TT).
2. G(TT): Same temperature sensor type as existing W(TT).
3. Russian type L type temperature sensor is divided from general purpose L type.
To change input specification, set jumper pin of KRN-UI2(Universal input card). (Please refer to ‘4.2 I/O card.)
© Copyright Reserved KONICS Co., Ltd. 25
2 Specification
26 © Copyright Reserved KONICS Co., Ltd.
3 Dimensions

3 Dimensions

(1) KRN100
Back side dimension is with installed I/O cards to every slot.
(2) Panel cut-out
Use panel which is 2 to 8mm thickness.
© Copyright Reserved KONICS Co., Ltd. 27
3 Dimensions
28 © Copyright Reserved KONICS Co., Ltd.
4 Connection

4 Connection

4.1 KRN100

This figure is back side of KRN100-04000-00-0S model.
Slot Description
1 to 6 Connects universal input card (KRN-UI2).
7 to 10
C Connects communication output card (KRN-COM).
Connect digital input card (KRN-DI6), alarm output card (KRN-AR4, KRN-AT6), and
transmitter power output card (KRN-24V3).
© Copyright Reserved KONICS Co., Ltd. 29
4 Connection
Universal input card (KRN-UI2)
Digital input card (KRN-DI6)
Transmitter power output card

4.2 I/O card

Alarm output card (KRN-AR4(Relay output))
(KRN-24V3)
Alarm output card (KRN-AT6(TR output))
Communication output card (KRN-COM)
30 © Copyright Reserved KONICS Co., Ltd.
4 Connection
Depending on input specification, set the jumper pin of universal input card (KRN-UI2) channel 1, channel 2 as below figure.
Jumper pin Input specification Input break alarm
0 to 20 ㎃, 4 to 20 ㎃ Enables only 4 to 20 ㎃
±2V, 1 to 5V, ±5V, -1 to 10V
TC, RTD, ±60mV, ±200mV
Enables
Disables
© Copyright Reserved KONICS Co., Ltd. 31
4 Connection
32 © Copyright Reserved KONICS Co., Ltd.
5 Installation

5 Installation

5.1 Installation place

Install this unit in place where the below conditions are satisfied.
Place where ventilation is well
To prevent from malfunction and damage by overheating (use temperature range: 0 to 50),
install this unit where ventilation is well. In case installing several KRN100, space each other by panel cut-out.
Place where vibration is not severe
If there is too much vibration, it may cause malfunction such as print error. For more information about vibration, please refer to ‘2 Specification’.
In case of temperature measurement with thermocouple temperature sensor at the place
where temperature is fluctuated, data error may occur. You should warm-up this unit over 30 min. to acquire accurate data before using it.
At the place where temperature and humidity is fluctuated excessively, recording paper
color may be changed.
© Copyright Reserved KONICS Co., Ltd. 33
5 Installation

5.2 Installation

5.2.1 Bracket mounting

1st Install KRN100 on the processed panel as panel cut-out diagram. Mount fixing
2nd Tighten fixing brackets on upper/lower parts to fix on the panel with phillips
screwdriver (+). (Torque: 0.4Nm)
brackets on upper/lower parts.
34 © Copyright Reserved KONICS Co., Ltd.
5 Installation

5.2.2 Additional I/O card connection

1st To connect I/O card additionally, turn OFF the power of KRN100.
Remove the proper slot cover to insert I/O card with flat-head screwdriver or knife.
2nd Insert I/O card to the proper slot and turn ON the power of KRN100.
© Copyright Reserved KONICS Co., Ltd. 35
5 Installation

5.3 USB to Serial driver

Install USB to serial driver which is applied for KRN100 sereis and connect DAQMaster and you can set parameter setting.(It is available only when communication output card (KRN-COM) is connected. Supporing OS for USB to Serial driver is Windows XP 32/64bit, Windows 7 32/64bit.)

5.3.1 Driver installation

1st Visit our homepage www.konics.com and downlaod 'KRN100_USB_Serial_Drivers’.
Unzip this file to the desired folder.
2nd Connect KRN100 USB port of communication output card(KRN-COM) and PC USB
port with USB cable (A-Mini 5P, 1.5m).
3rd ‘Found New Hardware Wizard’ appears.
Select ‘Install from a list or specific location (Advanced)’ and click ‘Next>’.
36 © Copyright Reserved KONICS Co., Ltd.
5 Installation
4th Select ‘Search for the best driver in these locations’ and check ‘Include this locationin
the search:’.
Click ‘Browse’ and select the folder which has 'KRN100_USB_Serial_Drivers’ and
click ‘OK’.
5th If hardware compatibility message appears, click ‘Continue Anyway’ and it processes
the next.
6th At ‘Completing the Found New Hardware Wizard’, click ‘Finish’ and driver installation
is complete.
© Copyright Reserved KONICS Co., Ltd. 37
5 Installation

5.3.2 Checking driver

To check the driver, right click 'My computer' and select 'Properties' on pop-up menu. 'System Properties' dialog appears. Select ‘Hardware’ tab and click 'Device Manager'. ‘Device Manager’dialog appears.
Check ‘Ports(COM & LPT)’ - 'KRN100 USB To Serial Converter (COMx)'.
38 © Copyright Reserved KONICS Co., Ltd.
6 Display

6 Display

6.1 Initial booting screen

Below booting screens are initially displayed when power is supplied to KRN100. These screens progresses initial settings for KRN100 to operate normally and checks inner system memory.
If there is no error for inner system memory, booting is finished and KRN100 operates normally.
Screen for progressing initial setting
Screen for checking error of inner system memory
If there are lots of log data files, booting time may take a long time. Delete log data file. For more information, refer to ‘8.7.4 Memory Clear (Delete memory)’.
Screen for error of inner system memory
Above this figure, if there is error of inner system memory, KRN100 cannot operate normally.
Please contact us. KONICS service center: +82-32-820-2343
© Copyright Reserved KONICS Co., Ltd. 39
6 Display
Section
Icon
Name
Description

6.2 Screen layout

Screen layout is divided as two; upper screen for status display, lower screen for measuring value display, virtual keyboard display, parameter display.

6.2.1 Status display

Upper screen displays recorder status and information of recorder as icon.
Record start icon
1
2
Record stop icon Stops recording measuring value.
List record icon Flashes during list recording.
Reservation record icon Flashes during reservation recording.
FEED icon Flashes during feeding recording paper.
Backup data print icon Flashes during backup data printing.
Digital mode icon Marks it for digital record mode.
Graph mode icon Marks it for graph record mode.
Record memory status
icon
Marks if for starting recording measuring value of
recordable channels.
Marks it storage capacity of record memory in
digital mode or graph mode.
40 © Copyright Reserved KONICS Co., Ltd.
6 Display
Section
Icon
Name
Description
No recording paper
1
icon
USB communication icon
Ethernet communication
3
icon
RS485 communication
4
icon
Alarm ON icon
Marks it for no recording paper. Please replace
new recording paper.
Marks icon during Modbus RTU
communication using USB.
Marks icon during ModBus TCP
communication using Ethernet.
Marks icon during Modbus RTU
communication using RS485.
Marks channel icon which alarm
occurs.
Marks the below icon according to input function
5
Digital input(DI) icon
Digital input(DI)- memo
icon
Digital input(DI)- alarm
reset icon
Digital input(DI)- start
record icon
setting during digital input (DI).
Marks it when digital memo of digital input or front
is input in recording status.
Marks it when alarm reset signal of digital input
(DI) is input.
Marks it when start record signal of digital input
(DI) is input.
Digital input(DI)- stop
record icon
Digital input(DI)- LIST
output icon
Digital input(DI)- record
speed icon
Marks it when stop record signal of digital input
(DI) is input.
Marks it when LIST output signal of digital input
(DI) is input.
Marks it when changing record speed signal of
digital input (DI) is input.
Unlock icon Marks it for unlock status.
User(general user) lock
6
icon
Marks it for user (general user) lock status.
Marks it for administrator and general user lock
Administrator lock icon
status.
Displays data capacity of internal memory as bar
graph. When an USB memory is connected, it
Inner and external (USB)
7
memory capacity icon
displays data capacity of an USB memory as bar
graph . If used memory capacity is over 90%
of total capacity, it flashes.
Displays current date and time. In summer time
8
Date/Time display
season, (S) mark is also displayed at front of year.
1. If there is no recording paper, icon flashes. After replacing recording paper, P.END
BACKUP PRINT screen as below is activated.
© Copyright Reserved KONICS Co., Ltd. 41
6 Display
Backup data recording function by P.END is same as RECORD BACKUP. Backup Data List
cannot be changed.
Starting print by P.END Backup, it prints the data but backup data file date, file name, and
backup record starting line.
42 © Copyright Reserved KONICS Co., Ltd.
6 Display
No
Front key
Description

6.2.2 Virtual keyboard

You can enter set value with vertual keyboard. (Supports only English letters for entering character.). Virtual keyboard is activated when set value is input. You can enter English letters, numbers, special characters by , , , , , and keys.
1
Press key once and English capital letters, English small
1
letters, and special character virtual keyboard is switching.
When pressing and holding key, screen of Function key
is displayed.
2
2
3
, , ,
Moves digit to select character of virtual keyboard
Enters set characters
1. Enterable characters are as below.
English capital letters
English small letters
Special character
2. Screen of Function key using
© Copyright Reserved KONICS Co., Ltd. 43
6 Display

6.2.3 Parameter setting display

Press front key for 3 sec, and it enters parameter setting group.
When entering parameter setting group, setable parameter setting groups are displayed. At parameter setting group, press key to enter parameter setting.
For more information of parameter detail setup, please refer to ‘8 Parameter detail setup’.
44 © Copyright Reserved KONICS Co., Ltd.
7 Operation

7 Operation

© Copyright Reserved KONICS Co., Ltd. 45
7 Operation

7.1 Screen display

7.1.1 Measuring value display

KRN100 displays measuring value as trend graph, bar graph, and digital number display(1 channel, 8 channels, 12 channels). You can select one by ke y.
(1) Trend graph
Displays input measuring value of each channel as trend graph (left) and digital number (right). 4 channels are displayed per one screen. To switch channel, please refer to “7.1.2 Channel switch".
(2) Bar graph
Displays input measuring value of each channel as bar graph (left) and digital number (right). You can easily check present measuring value within the set display range as level (%). 4 channels are displayed per one screen. To switch channel, please refer to “7.1.2 Channel switch".
46 © Copyright Reserved KONICS Co., Ltd.
7 Operation
(3) Digital number
Displays input measuring value of each channel as digital number. Digital number display is divided as 1 channel digital number, 8 channels digital number, 12 channels digital number.
Display of 1 channel digital number: Displays 1 channel per 1 screen with big font size.
It has high visibility.
Display of 8 channels digital number: Displays 8 channels per 1 screen.
Display of 12 channels digital number: Displays 12 channels (all channels) per 1
screen.
© Copyright Reserved KONICS Co., Ltd. 47
7 Operation

7.1.2 Channel switch

It displays measuring value of all input channels by switching channel of display types. You can set channel switch mode as auto channel switch or manual channel switch.
7.1.2.1 Auto channel switch
A screen displays 4 channels and automatically switches other screens by 3 sec period.
(1) Trend graph
(2) Bar graph
48 © Copyright Reserved KONICS Co., Ltd.
7 Operation
(3) Digital number(1 channel)
(4) Digital number(8 channels)
(5) Digital number(12 channels)
Digital number (12 channels) displays all channels (1 to 12 channel). It does not support auto/manual channel switch function.
7.1.2.2 Auto channel switch mode↔ Manual channel switch mode
1st When supplying/re-supplying power to KRN100, it is display currently display and
auto channel switch mode.
2nd If you want to change manual channel switch mode, press key or key.
3rd You can switch/select the to-be displayed channel by pressing key or
key.
4th In manual channel switch mode, press key to change to auto channel switch
mode.
© Copyright Reserved KONICS Co., Ltd. 49
7 Operation

7.2 Special operation for record

KRN100 executes special operation for record with front keys ( , , , ).
(1) Start record (RUN)/Stop record (STOP)
Press front key at once, it starts recording and press this key once again, it stops recording. When digital input operation status is set as ‘Level’, you cannot start/stop record by front
key. In case of as ‘Edge’, start record (RUN)/stop record (STOP) function is available
with front ke y.
(2) Parameter’s set information print (List Print)
This function is to record the main parameter’s set information on recording paper. Press
key for over 3 sec. during recording or stop state, and it records the set information of each menu. For more information, please refer to ‘8.5.13 List Out Option (List record option)’.
Even if you print the parameter set information with max record speed (240mm/h), it takes a lot of time. (It takes approx. 40 minutes for 12 channels.) Be sure that for printing the list.
(3) Manual feed (FEED)
In record STOP state, press front key for over 3 sec, record state icon is changed to
icon and you can feed recording paper manually.
To tear recording paper, use this manual feed function at first.
(4) Digital memo (Digital Memo)
Press for over 3 sec, during recording status, digital input icon changes to
memo icon. It records current time (hh:mm:ss) and display value of each channel as digital number on recording paper. It also displays ‘M’ which means the recording by memo at front of current time.
50 © Copyright Reserved KONICS Co., Ltd.
7 Operation

7.3 Parameter setting group

7.3.1 Parameter setting

The setting order of KRN100 basic parameters is as below.
For more information of detail setup of each parameter, please refer to ‘8 Parameter detail setup’.
To enter parameter setting group: Press key for 3 sec.
To move among setting group: ,
To move the setting:
To move upper parameter after setting: Press key and Function key is activated
which is placed at bottom right as below figure. Press OK ( ) key or Cancel ( ) ke y.
Cancel: Moves to upper parameter after not saving the setting.
OK: Moves to upper parameter after saving the setting.
© Copyright Reserved KONICS Co., Ltd. 51
7 Operation

7.3.2 Parameter

52 © Copyright Reserved KONICS Co., Ltd.
7 Operation
Dot-lined parameters are affected by set value of other parameters.
© Copyright Reserved KONICS Co., Ltd. 53
7 Operation
54 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup
Factory
Input Type (Input specification)
Refer to detail descriptions.
TC-K
Low: Input range/Min. graph scale value to upper limit
graph scale value
vacuum, static pressure)

8 Parameter detail setup

8.1 INPUT SETUP(Input setting)

You can set details for input specification and scale by universal input channel, record method, input digital filter, input error correction, etc.
Move to INPUT SETUP with , keys, press key to enter INPUT SETUP.
Parameter list
Parameter Set range
Select UI Card (Select universal input card)
Input Set Copy (Copy input parameter)
LCD/Paper Record (Display and record measuring value)
Pen Color (Record color)
Record Zone (Record zone)
Tag Name (Channel name) None/1 to 6 characters CH-1to12
Range/Scale Point (Decimal point)
Display/Temp Unit (Display unit/Temperature unit)
High/Low Range & Graph Scale(Upper/Lower limit input value and graph scale value)
CH□-S□UI-
None, CH□-S□UI-
OFF ON
1-Violet 2-Red 3-Black 4-Green 5-Blue
6-Brown
None, 1 Zone n
TC, RTD: 0 0.0
Analog: 0 0.0 0.00 0.000 0.0000
If special function is two unit: 0 0.0 0.00
TC, RTD: ˚K
Analog: Refer to detail descriptions. %
input value /Graph scale value (High Range/Graph Scale)– F. S . 5%
High: Lower limit input value/Graph scale value (Low Range/Graph Scale) + F. S 5% to input range/Max.
default
Automatica lly set
CH Select
ON
Automatica lly set
None
0.0
0.0
-200.0
1350.0
Low Scale/High Scale (Lower limit/Upper limit scale value)
Special Function (Special function)
Two Unit (Display the degree of a
Reference Channel (Reference channel)
© Copyright Reserved KONICS Co., Ltd. 55
Low: Set the range by set value of scale point -
High: Set the range by set value of scale point -
TC, RTD: None Difference
Analog: Linear Square Root Two Unit
1 to 35 -
None CH-SUI- (Activates connected universal input(2 channel per one
None
-
8 Parameter detail setup
card))
Span (Gradient adjustment)
0.100 to 5.000
-
Parameter Set range
Input Bias(Error correction) -999.9 to 999.9 0.0
Record Method (Data storage method)
Filter Type (Input digital filter)
Filter Counter (The number of digital filter)
Burnout Action (Display setting for break)
Instant Average Minimum Maximum
None Moving
1 to 128 -
OFF Up_Scale Down_Scale
Factory default
Instant
None
OFF
Shaded parameters are affected by set value of other parameters. Please refer to specific descriptions of each parameter.
Range/Scale Point(Decimal point position)
Display/Temp Unit(Display unit/Temperature unit)
Low Range & Graph Scale (Lower limit input value and
graph scale value)
When changing set value of
High Range & Graph Scale (Upper limit input value and
Input Type(input type)
graph scale value)
parameter,
Low Scale(Analog lower limit scale value)
High Scale(Analog upper limit scale value)
Special Function (Input special function)
parameters’ set values are initialized.
56 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup

8.1.1 Select UI Card (Select universal input card)

Select the channel of universal input card (KRN-UI2) to be set.
One universal input card has two channels.
KRN100 automatically searches slot connected universal input card (KRN-UI2) and displays as channel as soon as power is ON.
Channel name form is as below.
CH
Channel
- S
number
Slot
UI -
number
CH06-S3UI-2: It means 6th channel and 2nd input of 3rd slot connected universal input card.

8.1.2 Input Set Copy (Copy input parameter)

You do not need to repeat the setting of same parameter for each channel. KRN100 copies set values of the set-completed channel to other channels.
Copyable parameters are as following.
Input Type (Input specification) Range/Scale point (Decimal point)
Display/Temp Unit (Display/Temperature unit) Low Scale (Lower limit scale)
High Scale (Upper scale) Special Function (Special function)
Two Unit (Display the degree of a vacuum, static
pressure)
Input Bias (Error correction) Span (Gradient adjustment)
Record Method (Data storage method) Filter Type (Input digital filter)
Filter Counter (The number of digital filter) Burnout Action (Display setting for break)
High Range & Graph Scale (Upper limit input value and
graph scale value)
Set range: None/CH-SUI-
Reference Chanel (Reference channel)
Low Range & Graph Scale (Lower limit input value and
graph scale value)
card
input
Factory default: CH Select
© Copyright Reserved KONICS Co., Ltd. 57
8 Parameter detail setup

8.1.3 LCD/Paper Record (Display and record measuring value)

Set whether to record measuring value.
If you set ON, KRN100 displays and records measuring value on LCD screen, and recording paper. If you set OFF, KRN100 does not display and record measuring value on LCD screen, and recording paper.
Set range: ON OFF
Factory default: ON

8.1.4 Pen Color (Record color)

Designate record color when recordingmeasuring value.
Set range: 1-Violet 2-Red 3-Black 4-Green 5-Blue 6-Brown
Factory default: Automatically set

8.1.5 Record Zone (Record zone)

In case record mode is graph mode, you can select record zone for to graph measuring value when recording. Set range is set accoridng to the set value of ‘8.5.6 Divide Zone (Record zone division)’ from RECORD SETUP .
If the set is ‘None’, record zone is full width(100mm) of recording paper.
Set range: None, 1 Zone n (n: set value of Divide Zone (Record zone division))
Factory default: None
58 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup

8.1.6 Tag Name (Channel name)

Designate channel name with virtual keyboard. You can enter max. 6 characters with English capital letters, English small letters, and speical characters.
Set range: 1 to 6 characters
Factory default: CH-1 to CH-12(Channel number by slot)
Some special character may be printed in low quality due to low print resolution.

8.1.7 Input Type (Input specification)

Set input specification of channel.
Set input speicfication is total 27 such as thermocouple, RTD, voltage, and current. For more details, please refer to ‘2.3 Input specification and measuring range’. For jumper pin setting of universal input card (KRN-UI2) by inpust specification, refer to ‘4.2 I/O card’.
Set range: Refer to ‘2.3 Input specification and measuring range’
Factory default: TC-K

8.1.8 Range/Scale Point (Decimal point)

In case Input Type(Input specification) is temperature sensor(thermocouple, RTD), set wheter to display decimal point to measuring value. In case analog(voltage, current), set decimal point position of Low Scale(Lower limit scalevalue), High Scale(Upper limit scale value).
Set range
In case Input Type(Input specification) is temperature sensor(thermocouple, RTD): 0 0.0
In case analog(current, voltage): 0 0.0 0.00 0.000 0.0000
Factory default: 0.0
If you want high accuracy display, select ‘0.0(decimal point)’. If you want to stable accuracy display, select ‘0 (no dicimal point)’.
© Copyright Reserved KONICS Co., Ltd. 59
8 Parameter detail setup

8.1.9 Display/Temp Unit (Display unit/Temperature unit)

In case Input Type(Input specification) is temperature sensor(thermocouple, RTD), temperature unit is activated. In case analog(current, voltage), display unit is actiaved.
Set range
In case Input Type(Input specification) is temperature sensor(thermocouple, RTD): ˚K
In case analog : Refer to below table.
Factory default:
Set range in case analog (current, voltage)
No Unit No Unit No Unit No Unit No Unit
1 °C 17 % 32 V 48 mA
2 °F 18 Wt% 33 mV 49 A
3 °K 19 mass% 34 µV 50 kg/cm2
4 Kcal/m3 20 Vol% 35 kV 51 Pa
5 Kcal 21 ppm 36 52 kPa
6 cal 22 ppb 37 m□ 53 MPa
7 j 23 mol 38 µ□ 54 N/m2
8 Btu 24 Blank 39 s 55 N/mm2
9 l 25 lx 40 µs 56 inH2O
10 ml 26 cd 41 VA 57 mmH2O
11 t 27 lm 42 W 58 bar
12 gal 28 cd/m2 43 kW 59 Tor r
13 lb 29 rpm 44 MW 60 mmHg
14 oz 30 Hz 45 Var 61 mmAq
15 barrel 31 m2/s 46 kVar 62 psi
16 - 32 cp 47 MVar 63 Blank
64 User0
65 User1
66 User2
67 User3
68 User4
69 User5
70 User6
71 User7
72 User8
73 User9
You can use user-defined unit image by selecting user-defined (User0 to User9) unit. Please refer to ‘9.3.2 User unit setting’.
The unit with multiplier such as kg/cm
2
or complicated unit may be printed in low quality due to
low print resolution.
60 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup

8.1.10 High/Low Range & Graph Scale(Upper/Lower limit input value and graph scale value)

Set the actual used input range (Lower limit input value/Upper limit input value) in analog input.
If input range becomes small, the resoultion also becomes low in proportion to total range. Decimal point position is changed by ‘Scale Point(Scale decimal point position)’ setting.
(1) Low Range (Lower limit input value)
Set the actual used lower limit input value within input range of Input Type(Input specification).
Set range: Min. input range value to upper limit input value(High Range) – F. S. 5%
In case input range is 0 to 100, set range is 0 to 95.
Factory default: -
(2) High Range (Upper limit input value)
Set the actual used upper limit input value within input range of Input Type(Input specification).
Set range: Lower limit input value(Low Range) + F. S. 5% to max. input range value
In case input range is 0 to 100, set range is 5 to 100.
Factory default: -
Set the displayed graph scale value on recording paper and LCD in temperature sensor input type (Thermocouple, RTD), (They does not displayed in analog input type.). You can designate the record range and record specific section as detail graph by these parameters. ( If graph scale range is small, resoultion is also lower in proportion to recording range.)
(3) Low Graph Scale (Lower limit graph scale value)
Within the input range of Input Type (Input specification), set lower limit graph scale value.
Set range: Min. value of input range to upper limit graph scale value (High Graph
Scale) – F. S . 5% When TC-K input range is -200.0 to 1350, set range is -200.0 to 1272.5.
Factory default: -200.0
© Copyright Reserved KONICS Co., Ltd. 61
8 Parameter detail setup
(4) High Graph Scale (Upper limit graph scale value)
Within the input range of Input Type (Input specification), set upper limit graph scale value. They does not displayed in analog input type.
Set range: Lower limit graph scale value (Low Graph Scale) + F.S. 5% to Max. value of
input range When TC-K input range is -200.0 to 1350, set range is -122.5 to 1272.5℃.
Factory default: 1350.0
62 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup

8.1.11 Low Scale/High Scale (Lower limit/Upper limit scale value)

This function is for set the desired display value based on measuring value. It is applied to analog (voltage, current) input type only. As below figure, for example, measuring input value are ‘a’ and ‘b’ and the desired display value are ‘A’ and ‘B’ . In this case, about the input ‘a’ and ‘b’, it displays a=A, b=B as linearly.
You can change display value about min./max. input value of measuring value.
In case input specification is 0 to 20
Set Low Scale (Lower limit scale value) = 0.0, High Scale (Upper limit scale value) = 10.0,
20.0, 30.0, -20.0.
Set Low Scale (Lower limit scale value) = 20.0, High Scale (Upper limit scale value) = -20.0.
© Copyright Reserved KONICS Co., Ltd. 63
8 Parameter detail setup
Set Low Scale (Lower limit scale value) = -20.0, High Scale (Upper limit scale value) = 20.0.
(1) Low Scale(Lower limit scale value)
Set scale value for lower limit input value (Low Range).
Set range: -99999 to 99999 -9999.9 to 9999.9 -999.99 to 999.99 -99.999 to
99.999 -9.9999 to 9.9999 (Depending on Scale Point setting, the range is different.)
Factory default: -
(2) High Scale(Upper limit scale value)
Set scale value for upper limit input value (High Range).
Set range: -99999 to 99999 -9999.9 to 9999.9 -999.99 to 999.99 -99.999 to
99.999 -9.9999 to 9.9999 (Depending on Scale Point setting, the range is different.)
Factory default: -
64 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup

8.1.12 Special Function (Special function)

It dispalys the applied measuring value of the set special function. Depending on Input Type(Input specification), appliable special function is different.
Set range
When input type(input specification) is temperature sensor (thermocouple, RTD): None Difference
analog (voltage, current): Linear Root Squre ↔ Two Unit (Two Unit is displayed
when Input Type (input specification) is set as 0 to 20 , 4 to 20 .)
Factory default: None
Below graph’s patterns are liner, root, square for analog input.
Lower limit input value: -5V, Upper limit input value: +5V, Lower limit scale: -1000, Upper limit scale: 1000
© Copyright Reserved KONICS Co., Ltd. 65
8 Parameter detail setup
(1) Difference(Deviation)
It is available to set when Input Type(input specification) is temperature sensor (thermocouple, RTD). It displays the deviation of Reference Channel (Reference channel) measuring value. (Display value = standard channel measuring value – reference channel measuring value)
The set channel as analog (current, voltage) of Input Type (Input specification) is not
able to set as Reference Channel (reference channel).
If there is no set reference channel, it displays standard channel measuring value.
If any one of reference channel, or standard channel is break (BURN), upper limit
value (HHHH), lower limit value(LLLL) status, it displays as correspond value. If you select the channel which is used Difference function as reference channel, it displays the value based on calculating actual measuring value, not display value of reference channel.
(2) Linear
It applies lower limit scale and upper limit scale to lower limit input value and upper limit input value and displays this values.
In case lower limit input value: -5V, Upper limit input value: +5V and in case lower limit scale: -1000, upper limit scale: 1000 if current input value is 2V, display value is 400.
Display value =
Input value Lower limit input value
Upper limit input value Lower limit input value
Lower limit scale
400 =
7
× 2000 1000
10
(
×
Upper limit scale Lower limit scale
)
+
(3) Root
In case voltage, current input type, this mode is used when input value is calculated by Root
(
) for the desired display value. Differential pressure signal of differential pressure flow
meter is calculated Root(
) for the to-be measured flux. This function is used to measure
flux by input value.
In case lower limit input value: -5V, upper limit input value: +5V and in case lower limit scale: -1000, upper limit scale: 1000, if current input value is 2V, display value is approx. 673.32.
Display value =
Input value Lower limit input value
Upper limit input value Lower limit input value
66 © Copyright Reserved KONICS Co., Ltd.
Lower limit scale
7
673.32 =
× 2000 1000
10
(
×
Upper limit scale Lower limit scale
)
+
8 Parameter detail setup
(4) Square
In case of voltage, current input type, this mode is used when input value is calculated by square for the desired display value. Reverse of Root, flux signal is calculated by square for differential pressure signal.
In case lower limit range: -5V, upper limit range: +5V and in case lower limit scale: -1000, upper limit scale: 1000, if current input value is 2V, display value is -20.
Display value
20 =
(5) Two Unit
For compound pressure, if input pressure is lower than atmospheric pressure(0), it displays the degree of a vacuum with Hg unit. If input pressure is higher than or same as
atmospheric pressure(0), it displays positive pressure with kg/ unit. When using Two Unit function, lower limit value is fixed as -760mmHg and kg/cm
able to set within set range 1 to 35. Two Unit limits scale point as 0 □ 0.0 □ 0.00. When using Two Unit, display unit is automatically changed as mmHg or kg/cm The calculation with Record Method (Data storage method) and Filter type (Input digital filter) is impossible and ignored due to different type of two unit value.
Set range: 1 to 35
Factory default: -
=
Upper limit input value Lower limit input value
(
×
Upper limit scale Lower limit scale
7
2× 2000 1000
10
Input value Lower limit input value
)
+ Lower limit scale
2
.
2
2
value is
© Copyright Reserved KONICS Co., Ltd. 67
8 Parameter detail setup
2
If pressure range is -760mmHg to 3kg/cm
, and pressure transmitter outputs 4 to 20 , for 4
input it displays -760 mmHg, 8mA input is unit changing point. For 20 input, it displays
2
3kg/cm
Unit changing point = (
16
X Max. pressure range value (Ex. For 760 to 3 kg/cm2 , it is " 3 ". )
1.033 Converted value from 760 mmHg to kg/cm2 unit value (same unit)
.
16
X+1.033
4 to 20 output interval
× Y) + 4
Range
-760mmHg to 1kg/cm2 12.130
-760mmHg to 5kg/cm2 6.740
-760mmHg to 10kg/cm2 5.498
-760mmHg to 15kg/cm2 5.031
-760mmHg to 20kg/cm2 4.786
-760mmHg to 25kg/cm2 4.635
-760mmHg to 30kg/cm2 4.533
-760mmHg to 35kg/cm2 4.459
Unit changing
point (㎃)
Y Use pressure + 1.033 (Ex. Use pressure is ‘0’, Y is 1.033.)
4
Set range
Output value for zero, 4.00
In case Input Type(Input specification) is temperature sensor(thermocouple, RTD): None
Difference In case Input Type(Input specification) is analog(voltage, current): Linear Root
Square Two Unit (Two Unit is activated for current input(0 to 20 ㎃, 4 to 20 ㎃).)
Factory default: None
68 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup

8.1.13 Reference Channel (Reference channel)

In case Input Type(Input specification) is temperature sensor(thermocouple, RTD), set Special Function(special function) as Difference to set reference channel.
Set range: None / CH
Factory default: -
□-S□UI-□

8.1.14 Input Bias(Error correction)

This function is for error correction from input (thermocouple, RTD, voltage, current) not from this recorder.
When temperature sensor cannot be installed near measured subject, there may be the temperature deviation between temperature sensor area and measured subject area. This function calculates and corrects this errors. Several kinds of temperature sensor has specified grade. High accuracy type is high price and ordinary product is generally used. To correct input by measuring error from each helps more accurate temperature measurement.
For using this error correction function, you should accurately measure the deviation from input part , at first. If this deviation is not correct, the error may be higher.
Set range: -9999 to 9999 -999.9 to 999.9 -99.99 to 99.99 -9.999 to 9.999
-0.9999 to 0.9999 (Depending on the set scale point, range is different.)
Factory default: 0.0
In case actual temperature is 80but display temprature from recorder is 78℃, set Input
Bias(Error correction) as ‘2’ and display temperature is 80.
© Copyright Reserved KONICS Co., Ltd. 69
8 Parameter detail setup

8.1.15 Span (Gradient adjustment)

This menu is for adjusting upper limit error by regulating display value which is about measuring value or applied scale.
In case Low Scale(Lower limit scale value) and High Scale(Upper limit scale value) are fixed, and Span (Gradient adjustment) is only set. When Input range is 0 to 10V, Low Scale(Lower limit scale) value is 0.00, and High Scale(Upper limit scale) value is 10.00.
If changing gradient adjustment value as 0.500, 1.000 or 1.500, display value by each changed gradient adjustment value is below.
Lower
limit scale
value
0.00 10.00 0.500 0.00 to 5.00 0.00 5.00 1.000
0.00 10.00 1.000 0.00 to 10.00 0.00 10.00 1.000
Upper
limit scale
value
Gradient
adjustment
value
Range of
display value
Same
result
=
Lower
limit scale
value
Upper
limit scale
value
Gradient
adjustment
value
0.00 10.00 1.500 0.00 to 15.00 0.00 15.00 1.000
In case Low Scale(Lower limit scale value) and High(Upper limit scalevalue) are fixed, and Span (Gradient adjustment) is only set (reverse gradient). When Input range is 0 to 10V, Low Scale(Lower limit scale) value is 10.00, High Scale(Upper limit scale) value is 0.00.
If changing gradient adjustment value as 0.500, 1.000, or 1.500, display value by each changed gradient adjustment value is below.
Lower
limit scale
value
10.00 0.00 0.500 10.00 to 5.00 10.00 5.00 1.000
10.00 0.00 1.000 10.00 to 0.00 10.00 0.00 1.000
Upper
limit scale
value
Gradient
adjustment
value
Range of
display value
Same
result
=
Lower
limit scale
value
Upper
limit scale
value
Gradient
adjustment
value
10.00 0.00 1.500 10.00 to -5.00 10.00 -5.00 1.000
70 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup

8.1.16 Record Method (Data storage method)

Set storage method for measured data by channel to inner/external memory. Display and print method is Record Method.
Set value Description
Instant(Instant value) Saves measuring value by every record period (Log Speed)
Average(Average value) Saves averaged measuring value during record period (Log Speed).
Minimum(Min. value) Saves min. measuring value during record period (Log Speed).
Maximum(Max. value) Saves max. measuring value during record period (Log Speed).
Set range: Instant Average Minimum Maximum
Factory default: Instant

8.1.17 Filter Type (Input digital filter)

In some applications the fluctuating measuring input causes the display value to fluctuate. In this case accurate display/record is disable. This function is able to make display value stable by input digital filter.
Input digital filter uses moving average method (Moving Average Filter). It does not affet to display period but display value may be different with input value.
Set range: None Moving
Factory default: None
© Copyright Reserved KONICS Co., Ltd. 71
8 Parameter detail setup

8.1.18 Filter Counter (The number of digital filter)

Designate the number of sampling which apply to digital filter.
When you set Filter Type(Input digital filter), this parameter is activated.
Set range: 1 to 128
Factory default: -
When the set value of input digital filter is ‘4’, it does moving average input sampling values for
0.1 sec (100ms) and displays this value.
D1=S1
4
4
4
S1 + S2 + S3
3
, D5 =
, D7 =
S2 + S3 + S4 + S5
S4 + S5 + S6 + S7
4
4
S1 + S2
D2 =
Display values of D1, D2, D3 is the initial operation before averaging 4 sampling values.
S1 + S2 + S3 + S4
D4 =
S3 + S4 + S5 + S6
D6 =
S5 + S6 + S7 + S8
D8 =
72 © Copyright Reserved KONICS Co., Ltd.
2
, D3 =
8 Parameter detail setup
Set value
Description

8.1.19 Burnout Action (Display setting for break)

In case Input Type(Input specification) is temperature sensor(thermocouple, RTD), set alarm operation and alarm option for break input. (In case Input Type(Input specification) is analog(voltage, current), this function does not operate.)
OFF
Up Scale
Down Scale
When input break, after moving display value downward or upward according to
circuit structure
When input break, after moving display value only upward (records max. value in
graph record state) it displays BURN.
When input break, after moving display value only downward (records min. value
in graph record state) it displays BURN.
1
(max. or min. value in graph record state) it displays BURN.
Set range: OFF Up Scale Down Scale
Factory default: OFF
According to circuit structure, when thermocouple(Thermo Couple) temperature sensor, RTD(RTD) temperature sensor’s A-B terminal or voltage input ±6 0 mV, ±200mV input is break, it displays Down Scale. When RTD(RTD) temperature sensor’s B-B' terminal input is break, it displays Up Scale.
© Copyright Reserved KONICS Co., Ltd. 73
8 Parameter detail setup
Factory
channel)

8.2 ALARM SETUP (Alarm setting)

You can set alarm output specification such as alarm operation mode and alarm option by input channel, alarm ON/OFF delay, alarm output relay, relay contact, etc.
Move to ALARM SETUP with , keys, press key to enter ALARM SETUP.
Parameter list
Parameter Set range Unit
Select UI Card (Select universal card input)
Alarm Set Copy (Copy alarm parameter)
Alarm□ Type(Alarmoperation mode)1
Alarm□ Ref Channel(Alarm□ reference
Alarm□ Option(Alarm□ option)1 None Latch St By La+St
Alarm□ Value(Alarmset value)1
Alarm□ Hysteresis(Alarm□ hysteresis)1
Alarm□ ON/OFF Delay(Alarm□ ON/OFF
output delay time)
1
CH□-S□UI-□
No Select/ CH□-S□UI-□
OFF PV. Hi PV.Lo DV. H i
D V. L o SBA P. EN D
None / CH□-S□UI-□
F.S. of INPUT TYPE by channel Digit
F.S. of INPUT TYPE by channel Digit 0.0
0 to 3600 sec 0s
-
- CH Select
-
- -
- None
default
Automaticall y set
Alarm1 Type: PV. H i
Alarm2 Type to Alarm4 Type: None
Alarm1 Value:
1350.0
Alarm2 Value to Alarm4 Value: -
Alarm□ Alarm No(Alarm□ output alarm
number)
Select Alarm Card(Select alarm output card)
Alarm- Status(Relay and TR output
method)
1
1
None / SAO-
- -
N.O.N.C.
N.O.N.C.
N.O.N.C.
N.O.N.C.
N.O.N.C.
N.O.N.C.
When connecting Relay type KRN-AR4 (alarm output card), AL1 to AL4 are activated. When connecting TR type KRN-AT 6 (alarm output card), AL1 to AL6 are activated.
- None
Automaticall y set
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
74 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup
1. Alarm□ Type to Alarm Alarm No parameters are displayed as the number of connected
alarm output card.
Shaded parameters are affected by set value of other parameters. Please refer to specific descriptions of each parameter.

8.2.1 Select UI Card (Select universal card input)

Select the channel of universal input card (KRN-UI2) to be set.
One universal input card has two channels.
KRN100 automatically searches connected input/output card on slot power when power ON and recognizes the number of universal input card(KRN-UI2).
Set range: CH-SUI-(Activated connected universal input(2 channels per input card))
Factory default: Automatically set

8.2.2 Alarm Set Copy (Copy alarm parameter)

You do not need to set same parameter settings repeatedly for other channels. This function is to copy set value of alarm parameter of the set channel and applys it to other channels. Copiable parameters are as below.
Alarm Type
(Alarm operation mode)
Alarm Value
(Alarm Set value)
Alarm OFF Delay
(Alarm OFF delay time)
Set range: No Select/CH-SUI-(Activated connected universal input(2 channels per
input card)
Alarm Ref Channel
(Alarm reference channel)
Alarm Hysteresis
(Alarm hysteresis)
Alarm Alarm No
(Alarm output relay number)
Alarm Option
(Alarm option)
Alarm ON Delay
(Alarm ON delay time)
Factory default: CH Select
© Copyright Reserved KONICS Co., Ltd. 75
8 Parameter detail setup
Type
Record
Alarm operation
Description

8.2.3 Alarm□ Type(Alarm□ operation mode)

Designate alarm operation when alarm ON. You can set up to 4 operations by each channel and alarm operations are as below.
No alarm
1
2
3
4
5
6
Absolute value upper limit alarm
Absolute value lower limit alarm
Deviation upper limit alarm
Deviation lower limit alarm
Input break alarm
- - -
PV.Hi
Alarm set value: 90
()
PV.Lo
Alarm set value: 90
()
Alarm set value:
-10
Alarm set value:
10
DV.Hi
()
DV.Lo
Alarm set value:
10
Alarm set value:
-10
()
In case input is not connected, or input cable is break during controlling,
SBA
alarm output turns ON. You can check whether input cable is break by
(S)
external contact of alarm output using buzzer or other devices.
If display value is same or
higher than alarm set value,
alarm output turns ON.
If display value is same or
lower than alarm set value,
alarm output turns ON.
If the deviation between
display value and the
display value of reference
channel is same or higher
than alarm set value, alarm
output turns ON.
If the deviation between
display value and the
display value of reference
channel is same or lower
than alarm set value, alarm
output turns ON.
76 © Copyright Reserved KONICS Co., Ltd.
In case of no recording paper during recording, record operation stops
and this alarm output turns ON. (Measuring value is saved at system
memory automatically.)
Alarm is automatically cleared when recording paper is replaced (in
7
No recording paper alarm
P.End
(P)
case of general alarm). P.END BACKUP PRINT window is activated
and it is available to output backup data.
8 Parameter detail setup
No.
Name
Alarm sign
H: Alarm output hysteresis(Hysteresis)
If even one alarm occurs, alarm ON icon marks the specified channel to check whether alarm has occurred.
(1) Record Mode(Record mode) is Graph
It records alarm sign, alarm operation mode, and occurrence time on recording paper with the set record color in 'Pen Color' of INPUT SETUP. Alarm sign is recorded at alarm set value position.
Alarm ON from 1 channel, Records alarm sign of corresponding channel’s graph.
Records also alarm and time information at right.
Alarm ON at the same time
from over 2 channels,
Over 2 alarms ON from 1
channel,
Records alarm sign of corresponding channel’s graph. Records
only time information at right.
Records alarm sign and ‘CH1 AL-(the number of alarm)
14:00:33’ form.
If alarm occurs at digital memo time, memo information includes alarm information. Therefore, as below figure, alarm sign, alarm information, time information is not recorded and is replaced as digital memo.
[Alarm sign]
1 Absolute value upper limit alarm
2 Absolute value lower limit alarm
3 Deviation upper limit alarm
4 Deviation lower limit alarm
5 Input break alarm S
6 No recording paper P
© Copyright Reserved KONICS Co., Ltd. 77
8 Parameter detail setup
(2) Record Mode(Record mode) is Digital
It records alarm ON channel, data information, alarm abbreviation, time with the set record color of corresponding channel. In front of ON time, as below, ‘A’ is marked to mean the data by alarm.
After alarm recording, if it maintains same alarm or alarm is cleared, it does not record the relevant data. In case of record by digital memo, it prints alarm abbreviation of occurring alarm as below.
No. Name
1 Absolute value upper limit alarm PH -
2 Absolute value lower limit alarm PL -
3 Deviation upper limit alarm DH -
4 Deviation lower limit alarm DL -
5 Input break alarm SB -
6 No recording paper PE -
7 Several alarm ON AL
Alarm abbreviation
Note
It is used when printing 2
channels in one line.
Set range: OFF PV. H i PV. L o DV.Hi DV. Lo SBA P.E nd
Factory default
Alarm1 Type: PV.Hi, Alarm2 Type to Alarm4 Type: None

8.2.4 Alarm□ Ref Channel(Alarm□ reference channel)

Designate reference channel which is standard of deviation upper limit alarm(DV.Hi) or deviation lower limit alarm(DV.Lo). If display value of relevant channel is lower than the display value of set reference channel, deviation upper limit alarm or deviation lower limit alarm turns ON.
This parameter is activated when AlarmType(Alarm operation mode) is set as deviation upper limit alarm(DV.Hi) or deviation lower limit alarm(DV.Lo).
Set range: None / CH-SUI-
Factory default: -
78 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup

8.2.5 Alarm Option(Alarm option)

Set alarm output by alarm operation.
Set value Description
None
Latch
StBy
La+St
1
2
Standard
alarm
Alarm latch
Standby
sequence
Alarm latch
and standby
sequence
If it is an alarm condition, alarm output is ON. If it is a clear alarm
condition, alarm output is OFF.
If it is an alarm condition, alarm output is ON and maintains ON status.
(Alarm output HOLD)
First alarm condition is ignored and from second alarm condition,
standard alarm operates.
If it is an alarm condition, it operates both alarm latch and standby
sequence. When power is supplied and it is an alarm condition, this first
alarm condition is ignored and from the second alarm condition, alarm
latch operates.
1. In case Alarm□ Type (Alarm operation mode) is SBA(Input break alarm) or P.End(No
recording paper alarm), you can only select Latch(Alarm latch).
2. Condition of re-applied standby sequence: Power ON, changing the set alarm temperature,
forced alarm reset.
Set range: NoneLatchStByLa+St
Factory default: None
In case for input break alarm(SBA), no recording paper alarm (P. EN D ), standby sequence, or alarm latch and standby sequence option does not operates and you cannot set it. In case of alarm by alarm latch, to reset alarm output, press key for 3 sec at not alarm condition, use alarm reset function by digital input, or turn OFF the power and ON.
To reset alarm output by digital input, DI- Type(Select digital input□) from DIGITAL INPUT SETUP is should be set as ‘Alarm Reset’.
Reset alarm output is available only when alarm option is set as alarm latch or alarm latch and standby sequence, or when current temperature is out of alarm operation range. At the next alarm output ON, alarm output operates normally.
Alarm□ Type(Alarmoperation mode): PV. Lo (Absolute value lower limit alarm)
Alarm□ Val ue (Alarm□ set value): 90
Alarm□ Hysteresis(Alarm□ hysteresis): 5
Alarm□ Option(Alarm□ option): StBy(Standby sequence)
© Copyright Reserved KONICS Co., Ltd. 79
8 Parameter detail setup
When power is ON, it is alarm condition and it is ignored. From second alarm conditions, it operates as standard alarm.
8.2.6 Alarm□ Value(Alarm□ set value)
Set alarm set value based on alarm output operation mode, it executes alarm operation.
Set range: Using set input from Input Type(Input specification)/within display range
Factory default: Alarm1 value: 1350.0, Alarm2 Value to Alarm4 Value: -
80 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup

8.2.7 Alarm Hysteresis(Alarm hysteresis)

Set the interval between alarm output ON and OFF.
If PV is over or below alarm output SV, output turns ON and it sets OFF time by hysteresis settings.
When input value is changed near SV, alarm output is often. Set hysteresis and it can be prevent from often alarm output.
Set range: 0.0 to 9999.9 (Decimal point position is different by the set decimal point position
of input.)
Factory default: 0.0
The below graph is when Alarm□ Type(Alarm□ operation mode) is set as absolute value
upper limit alarm, Alarm Value(Alarm set value) is set as 200, and Alarm
Hysteresis(Alarm hysteresis) is set as 10.
© Copyright Reserved KONICS Co., Ltd. 81
8 Parameter detail setup
Item
Description

8.2.8 AlarmON/OFF Delay(AlarmON/OFF output delay time)

Set delay time (unit: sec.) to prevent alarm malfunction by wrong input from external disturbance and noise.
Even after standby the set time when alarm ON condition (alarm ON
Alarm On Delay
Alarm OFF Delay
channel flashes on screen), if it is still alarm condition, alarm output turns
ON. (Alarm ON channel flashes on screen).
Even after standby the set time when alarm reset condition (alarm ON
channel display is hold), if it is still alarm reset condition, alarm output turns
OFF. (Alarm ON channel resets the display.)
Set range: 0 to 3600
Factory default: 0s
82 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup

8.2.9 AlarmAlarm No(Alarm output alarm number)

Select alarm output number to output alarm in alarm ON.
If the setting as ‘None’ and when alarm operation occurs, it displays alarm on the screen and records alarm operation mode, and alarm occurrence time on recording paper, but it does not output alarm.
There are two alarm output types; TR and RELAY output. KRN recognizes automatically the connected type and displays it.
In this parameter, TR output type is displayed as TR-SAL-(), and RELAY output type is
displayed as RELAY-SAL-().
These parameter’s meaning is as below. S: The number of module connected SLOT,
AL-: Alarm output channel number,
Number in parenthesis ‘()’: the number of designated alarm as output in the specified channel
Set range: None / -SAO-()
Factory default: None

8.2.10 Select Alarm Card(Select alarm output card)

Select alarm output card(KRN-AR4, KRN-AT6 ) to set output type (Normally Open, Normally Closed) of alarm output. In front of output card name, RELAY or TR abbreviation is displayed for easy to know connected module type when selecting output card.
© Copyright Reserved KONICS Co., Ltd. 83
8 Parameter detail setup

8.2.11 Alarm- Status(Relay and TR output method)

Set alarm output method (Normally Open, Normally Closed) of each alarm output channel from the set alarm output card in Select Alarm Card (Select alarm output card). You can use alarm output as relay output or TR output by inserting the desired alarm output card(Relay output: KRN-AR4, TR output: KRN-AT 6).
Set value
N.O.
N.C.
Description
Normally
Open
Normally
Closed
In normal status it is open.
If alarm occurs, it is closed.
In normal status it is closed.
If alarm occurs, it is open.
Alarm occurrence
OFF
ON Contact Close TR ON
OFF Contact Close TR ON
ON Contact Open TR OFF
Alarm output
Relay TR
Contact Open
TR OFF
This function displays as Alarm- Status and it is connected Relay or TR Type’s output card information. One card for relay has 4 outputs(Alarm-1 Status to Alarm-4 Status), for TR has 6
outputs (Alarm-1 Status to Alarm 6 Status).
Relay output card(KRN-AR4) is connectable up to 3, and TR output card (KRN-AT 6) is connectable up to 2 at Slot7 to 10.
Alarm output turns ON or OFF by total 4 alarm conditions and relay, TR output are able to output by max. 48 alarm conditions. However, every relay output and TR output condition is OR operation (Among several alarm conditions connected one alarm output, even one alarm condition is met, output must turn ON.).
Set range: N.O. N.C.
Factory default: N.O.
RE A LY and TR type output is basically fixed as Normally Opened method and H/W when power is ON. Therefore, KRN100 takes booting time max. 20sec and maintains Normally open status. In case of RUN mode after booting, it maintains use-defined output type; Normally Open or Normally Closed.
84 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup

8.3 DIGITAL INPUT SETUP(Digital input setting)

You can set executing function by digital input card, operation stauts, etc.
Move to DIGITAL INPUT SETUP with , keys, press key to enter DIGITAL INPUT SETUP.
Parameter list
Parameter Set range Factory default
Select DI Card (Select digital input card) S7DI S8DI S9DI S10DI Automatically set
DI- Type (Select digital input □)
DI- Reset No (Reset alarm number) None ALL SAL- -
DI- Status (Operation status) Edge Level -
None Run Memo ListOut Speed
Alarm Reset
None
Shaded parameters are affected by set value of other parameters. Please refer to specific descriptions of each parameter.
© Copyright Reserved KONICS Co., Ltd. 85
8 Parameter detail setup

8.3.1 Select DI Card (Select digital input card)

Select digital input card (KRN-DI6) to be selected. KRN100 searches connected digital input card automatically on slot and recognizes the number of digital input card as soon as power is ON.
Channel name is as below.
S Slot number DI
Set range: S7DI S8DI S9DI S10DI
Factory default: Automatically set
S9DI: This means connected digital input card on 9th slot
86 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup

8.3.2 DI- Type (Select digital input )

Select digital input.
Mode
Operation name
Operation description
Level Edge
Min. signal
Open Short
input
2
Icon
1
None - No function - - -
Run※3
Memo Digital memo
ListOut List output
Speed
Alarm Reset
Start/Stop recording
Record speed (graph) and period (digital)
Forced alarm reset
Starts/Stops recording on recording paper.
Executes digital memo function
Outputs parameter set information
Executes to record with set option record speed and period (Option speed, period).
In case alarm option is alarm latch, alarm output is reset by force.
STOP RUN
- - Memo
- - ListOut
Standa rd
- - Alarm Reset
Option
STOP↔RU N
Standard
Option
,
1. At every min. signal input width (over 0.3 sec.), it executes the function repeatedly.
2. The appropriate icon is displays on the screen, digital input function is operating.
3. When digital input operation status is set as Level in RUN mode, you cannot operate
starting/stopping recording with front key. (If it set as ‘Edge’, front key
operates starting/stopping recording.)
When reservation record(Reservation) is set and now is reservation recording state, digital
input function is not available as RUN mode. This is available in record stop state by
reservation record.
Set range: None Run Memo ListOut Speed Alarm Reset
Factory default: None
© Copyright Reserved KONICS Co., Ltd. 87
8 Parameter detail setup

8.3.3 DI- Reset No (Reset alarm number)

Select alarm to reset at digital input. Set DI- Type(Select digital input□) as forced alarm recet (Alarm Reset), it is activated.
Alarm reset is available when alarm option is Alarm latch or Alarm latch and standby sequence and it is not alarm condition.
Set range: NoneALL S-AL-
Factory default: -

8.3.4 DI- Status (Operation status)

Designate operation status of set digital input.
Set value Description
Edge
Level
Set range: Edge Level(Please refer to ‘8.3.2 DI- Type (Select digital input )’.)
Factory default: -
In digital input setting, when DI- Type is set as Run or Seed, and DI- Status is set as Edge,
overlap setting is available. But DI- Status is set as Level, overlap setting is not available.
If even one Level is set, DI- Status’s overlap setting to Level or setting to Edge is not available.
In case DI- Status(operation status) is Edge: You can execute to start/stop recording with front k e y.
In case DI- Status(operation status) is Level: You cannot execute to start/stop recording with front key.
When digital input is input over 0.3 sec., the set function operates. If digital input is re-
input the reverse function operates.
When digital input is short over 0.3 sec., the set function operates. If digital input is
open over 0.3 sec., the operation is stop.
88 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup
time)

8.4 COMMUNICATION SETUP (Communication setting)

Set the related parameters with communication output card(KRN-COM).
You can only check the item of COMMUNICATION SETUP by communication but cannot change the set.
This parameter is for setting and monitoring parameters from external upper system (PC and graph panel, etc) or transmitting the data to external devices by RS485, Ethernet, or USB Device communication
It is recommended to use our dedicated software program DAQMaster for monitoring. If you want to develop monitoring program not using our DAQMaster program or to use the related Modbus program, please refer to user manual for communication.
Visit our homepage (www.konics.com) to download DAQMaster program, and user manual for communication.
Move to COMMUNICATION SETUP with , keys, press key to enter COMMUNICATION SETUP.
Parameter list
Parameter Set range Factory default
Modbus Address (Communication address) 1 to 127 1
RS485 Port (Use RS485 communication)
Baud Rate (Baud rate)
Parity Bit (Communication parity bit)
Stop Bit(Communication stop bit)
Termination Set (Terminating resistance)
Response Wait Time (Communication response wait
Protocol (Communication protocol) Modbus RTU Modbus RTU
RS485 Com Write (RS485 communication write)
Ethernet Port (Use Ethernet communication)
IP Address (IP address) 0.0.0.0 to 255.255.255.255 -
Subnet Mask (Subnet Mask) 0.0.0.0 to 255.255.255.255 -
Default Gateway (Default gateway) 0.0.0.0 to 255.255.255.255 -
Ethernet Com Write (Ethernet communication write)
USB Device Port (Use USB communication)
USB Com Write (USB communication write)
Enable Disable
240048009600 19200 38400
None ↔ Odd ↔ Even
1 ↔ 2
Disable Enable
5 to 99ms 20ms
EnableDisable
EnableDisable
Enable Disable
Enable Disable
Enable Disable
Enable
9600
None
2
Disable
Enable
Disable
-
Enable
Enable
KRN100 does not supports RS485 port, Ethernet port at the same time for preventing system overload. If you change one as ‘Enable’, the other is changed ‘Disable’ automatically. In case USB Device, it is able to set 'Enable', 'Disable' regardless of RS485 or Ethernet setting.
© Copyright Reserved KONICS Co., Ltd. 89
8 Parameter detail setup
Item
RS485
Ethernet
USB Device
Interface
Application standard
Max. connection
Communication
distance
1
Communication
method
Communication
synchronization
method
Communication
speed
Compliance with EIA
Compliance with USB
-
RS485
V2.0
1 units
31 units
(number of occupations
1 units
(address: 1 to 127)
per a unit)
Single cable within
Max. 1Km
(Below 9600bps)
100m
(Recommended over
Single cable within
1.5m
CAT5E)
Half Duplex Full Duplex -
Asynchronous Asynchronous Asynchronous
2400/4800/9600/19200
10/100Mbps 12Mbps(Full Speed)
/38400bps
Communication
5to99 ms - -
response wait time
Start Bit 1 bit(fixed) - -
Data Bit 8 bit(fixed) - -
Parity Bit
None, Odd, Even
- -
Stop Bit 1, 2 bit - -
Protocol Modbus RTU Modbus TCP Modbus RTU
1. When connecting through the network such as network hub (HUB) and gateway, etc, there
is no distance limit, but it is recommaned to use min. network.
Please use communication cables which is satisfied the below conditions.
Shield Twist Pair over AWG24, characteristic impedance
RS485 communication
100Ω, capacity component 50pF/m cable length max. 1km
Ethernet communication Over CAT5E, cable max. length: 100m
USB Device communication Single cable built-in ferrite core within 1.5m
USB Device communication may cause recognition error by external noise and environment during connecting PC. If there is error, please re-connect this. Please use USB Device as for setting.
90 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup
During communication, if you chaging the communication settings, it may cause communication error.
RS485 communication port of KRN100 is connected for 3 A, B, SG terminals. SG terminal is connectable with shield or SG of converter, and you do not need to connect SG terminal. To remove noise during RS485 communication, use shield cable. There are three methods for shield processing.
Connects shield cable only for
1
SG terminal of communication
module.
Connects shield for both SG
terminal of communication
2
module and the grounding of
computer.
Connects shield for one of SG
terminal of communication
3
module or the grounding of
computer.
When electric potential occurs between computer and
recorder grounded, connect shield cable for SG terminal of
recorder to minimize noise effect not to flow current on
shield cable. (It is used generally.)
When electric optional does not occur between computer
and recorder grounded, it is effective to minimize noise
influence.
It can minimize noise effect in case of connecting non-
polarity condenser in series.
It is recommended to use SCM-US 48I(USB/RS485 converter) or SCM-38I(RS232C/RS485 converter) for RS485 communication between PC and KRN100.
If using the non-grounded converter between FG and SG, it may cause damage to KRN100 and communication error by electric potential of between ground during long-distance communication.
For using terminating resistance, turn ON only terminal resistance of recoder on end of connected communication line (Enables to set using terminating resistance in communication set function), and also turn ON terminal resistance of connected communication to PC.
© Copyright Reserved KONICS Co., Ltd. 91
8 Parameter detail setup

8.4.1 Modbus Address (Communication address)

Designate communication address. The designated communication address is able to apply to RS485, USB Device, also Ethernet communication. However, duplicated communication address setting in same communication line does not allow.
Set range: 1 to 127
Factory default: 1

8.4.2 RS485 Port (Use RS485 communication)

Set whether using RS485 communication. If you set RS485 Port’s set value as ‘Enable’, Ethernet Port’s set value is changed ‘Disable’ automatically.
Set range: Enable Disable
Factory default: Enable

8.4.3 Baud Rate (Baud rate)

Designate baud rated.
Set range: 2400 4800 9600 19200 38400 (unit: bps)
Factory default: 9600
92 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup

8.4.4 Parity Bit (Communication parity bit)

Designate communication parity bit.
Set range: None Odd Even
Factory default: None

8.4.5 Stop Bit(Communication stop bit)

Designate communication stop bit.
Set range: 1 2 (unit: bps)
Factory default: 2

8.4.6 Termination Set (Terminating resistance)

Desigante wheter using terminating resistance .
You do not need to external terminating resistance (120Ω) because KRN100 is enable to use terminating resistance by parameter setting.
Set range: Enable □ Disable
Factory default: Disable
© Copyright Reserved KONICS Co., Ltd. 93
8 Parameter detail setup

8.4.7 Response Wait Time (Communication response wait time)

To prevent possible error due to communicating with low speed Master (PC, PLC, etc), set communication response wait time.
If you set too short communication response wait time, communication error may occur in Master.
Set range: 5 to 99 (unit: ms)
Factory default: 20ms

8.4.8 Protocol (Communication protocol)

It supports Modbus RTU(Remote Terminal Uint) as communication protocol.
(Data Length: 8bit, Data interval: 24bits or less,Error Detection: CRC-16)
Set range: Modbus RTU
Factory default: Modbus RTU

8.4.9 RS485 Com Write (RS485 communication write)

Set whether changing the set value of KRN100 parameter by RS485 communication.
To read the set value of each parameter is available regardless of the communication write enable/disable setting.
Set range : Enable Disable
Factory default : Enable
94 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup

8.4.10 Ethernet Port (Use Ethernet communication)

Set whether using Ethernet communication. If you set Ethernet Port as ‘Enable’, RS485 Port is changed as ‘Disable’ automatically.
Set range: Enable Disable
Factory default: Disable
You can monitor or set parameter KRN100 with DAQMaster or the related Modbus program (Modbus Poll, etc). For more information, refer to ‘KRN100 user manual for communication.’
[Modbus TCP communication] The following is based on Windows X P.
1st First of all connect Ethernet slot of KRN-100 communication output card (KRN-COM)
and LAN slot of PC with LAN cable.
2nd Execute Start > Run to check IP address of PC.
© Copyright Reserved KONICS Co., Ltd. 95
8 Parameter detail setup
3rd Enter “ipconfig” at “Open” in Run dialog box and you can check IP address of PC.
4th Set KRN100 Ethernet Port(Use Ethernet communication) as ‘Enable’ at
COMMUNICATION SETUP (Communication setting) of KRN100. Set IP Address(IP
address) as installation environment.
PC KRN100
IP Address 192.168.1.1 192.168.1.2
Subnet Mask 255.255.255.0
Default Gateway 192.168.1.1
IP address set for Modbus TCP communication is complete.
96 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup

8.4.11 IP Address (IP address)

Designate used IP address to identify the device on the network. If there is same IP address on the network, communication does not operate by IP conflict.
Set range: 0.0.0.0 to 255.255.255.255
Factory default: -

8.4.12 Subnet Mask (Subnet Mask)

To recognize network ID part and host ID part of IP address, set 32 bit address allowing to IP packet receiver.
To enter correct set value, whenever press , keys, it displays inputable subnet mask value is displayed.
Set range: 0.0.0.0 to 255.255.255.255
Factory default: -

8.4.13 Default Gateway (Default gateway)

Designate IP address to connect IP router directly.
Set range: 0.0.0.0 to 255.255.255.255
Factory default: -
© Copyright Reserved KONICS Co., Ltd. 97
8 Parameter detail setup

8.4.14 Ethernet Com Write (Ethernet communication write)

Set whether changing the set value of KRN100 parameter by Ethernet communication.
To read the set value of each parameter is available regardless of the communication write enable/disable setting.
Set range: Enable Disable
Factory default: -

8.4.15 USB Device Por t (Use USB communication)

Set whether using USBcommunication.
USB communication is available regardless of RS485 Port or Ethernet Port setting.
Set range: Enable Disable
Factory default: Enable

8.4.16 USB Com Write (USB communication write)

Set whether changing the set value of KRN100 parameter by USB communication.
To read the set value of each parameter is available regardless of the communication write enable/disable setting.
Set range: Enable Disable
Factory default: Enable
98 © Copyright Reserved KONICS Co., Ltd.
8 Parameter detail setup
Parameter
Set range
Factory default

8.5 RECORD SETUP (Record setting)

You can set record mode, record speed, record language, and digital memo, etc.
Depending on record mode (Digital, Graph), below parameters are changed.
Move to RECORD SETUP with , keys, press key to enter RECORD SETUP.
Parameter list
Record Mode (Recode mode) Graph Digital Graph
Digital Print type (1 line record channel during numeric
recording)
Standard Speed (Standard record speed)
OneCH ↔ TwoCH TwoC H
10 20 40 ↔ 60 ↔ 120 240mm/h 20mm/h
Option Speed (Option record speed) 10 20 40 ↔ 60 ↔ 120 240mm/h 20mm/h
Memo Period (Digital memo period) Refer to detail descriptions. 2hour
Divide Zone (Record zone division) None, 2 to 12 None
Standard Period (Standard record period) 00m01s to 99m99s -
Option Period (Option record period) 00m01s to 99m99s -
Listing Language (Language for list output) Korea ↔ English English
Alarm Speed (Alarm record speed) 10 20 40 ↔ 60 ↔ 120 240mm/h 20mm/h
Power On Status (Record status when power ON) Hold Run ↔ Stop Hold
Run Status (List printing at start recording) OFF ON OFF
List Out Option (List record option) Standard Option Standard
Zone Dot Line Distance (Dot line for zone division) None to 8.0mm 4.0mm
CH Print Distance (Record interval for each channel
graph)
Start Line Print (Start line when starting record) ON OFF ON
Range Print Time (Input range record period) Disable,1to 24 hour Disable
None to 100.0mm 20.0mm
Shaded parameters are affected by set value of other parameters. Please refer to specific descriptions of each parameter.
© Copyright Reserved KONICS Co., Ltd. 99
8 Parameter detail setup

8.5.1 Record Mode (Recode mode)

Set record mode to record display value on recording paper. KRN100 supports Graph, and Digital record modes.
(1) Graph
Records display value as graph type on recording paper. It records current time (hh:mm:ss), display value by channel in set Memo Period(Digital memo record period)
(2) Digital
Records display value as numeric on recording paper. It records current time (hh:mm:ss), display value by channel in set Standard Period (Print/Record period) and also records current date (Year-Month-Day) and time in every 00:00:00.
You can record digital memo manually by front key (press key for 3 sec), or digital input terminal.
Set range: Graph Digital
Factory default: Graph