Kolmeks AE-25/4FC, AE-26/2FC, AE-26/4FC, AE-32/4FC, AE-33/2 Operating Instructions Manual

...
SARJAT
AE_-, L_-, AL_-, T- and AT-
OPERATING INSTRUCTIONS
CENTRIFUGAL PUMPS WITH INTEGRATED FREQUENCY CONVERTER
FC_ -SERIES
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
1
Subject to change without prior notice
Content
1. General ............................................................................................ 3
1.1 Symbols ................................................................................................................................................ 3
1.2 Applications ........................................................................................................................................ 3
1.3 Manufacturer ...................................................................................................................................... 3
1.4 Version ................................................................................................................................................. 3
2.1 Handling, transport and storage of the pump .................................................................................. 4
2. Handling, transport and storage of the pump ............................4
3. Design and function ......................................................................4
3.1 Construction ........................................................................................................................................ 4
3.2 Technical data ..................................................................................................................................... 4
3.3 Rating plate ....................................................................................................................................... 5
3.4 Pump identification ........................................................................................................................... 5
4. Safety ............................................................................................6
4.1 Safety instructions ............................................................................................................................. 6
4.3 Elements of danger if safety regulations are not obeyed ............................................................... 6
4.4 Safety instructions for inspection and assembly ............................................................................. 6
4.2 Training ............................................................................................................................................... 6
4.5 Operating the pump........................................................................................................................... 6
5. Installation, introduction and start-up ........................................ 6
5.1 General ................................................................................................................................................. 6
5.2 Positions for installation ....................................................................................................................7
5.3 Electrical connections .........................................................................................................................7
5.4 Control methods and connections .................................................................................................... 8
5.4.1 I/O’s of the FC-pump (inputs and outputs) .................................................................................... 8
5.4.2 Factory settings .............................................................................................................................. 8
5.4.3 FCA -pump - speed reference from potentiometer ...................................................................... 9
5.4.4 FCB -pump - constant pressure between the pump flanges ......................................................10
5.4.5 FCC -pump - constant pressure between inlet- and outlet-line ...................................................11
5.4.6 FCCVAK -pump - constant pressure between supply- and return-line with
external controller in use (SETUP 1) ....................................................................................................... 12
5.4.7 FCCVAK -pump - constant pressure between supply- and return-line with
controller of the frequency converter in use (SETUP 2) ........................................................................ 13
5.4.8 FCD -pump - constant pressure in discharge flange ....................................................................14
5.4.9 FCE -pump - sensorless, pre-programmed pump curves ............................................................15
5.4.10 FCF -pump - constant temperature ............................................................................................ 16
5.4.11 FCF -pump - the speed according to temperature ...................................................................... 17
5.4.12 FCG -pump - controlled by external system ................................................................................18
5.4.13 Connections to the alarm receiving station .................................................................................19
5.4.14 Local control panel (optional) ...................................................................................................... 20
6. Service, spare parts and troubleshooting .................................. 22
6.1 Shaft seals......................................................................................................................................... 22
6.2 Other parts ....................................................................................................................................... 22
6.3 Troubleshooting ............................................................................................................................... 23
7. Declaration of Conformity ........................................................... 27
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
2
Subject to change without prior notice
1. General
1.1 Symbols
Warns that failure to observe the precaution may cause personal injury or damage to pro­perty.
Warns that failure to observe the precau­tion may cause electric shock
Indicates something to be noted by the reader.
1.2 Applications
The most common applications are heating, air condition, cooling systems. Also heat exchangers, pressure boos­ting systems, district heating systems, ice halls, public baths and industrial processies.
Pump series Applications
AE-, L-, AL-, T-, AT-
L-, ALH-
AEP-, LP-, ALP-
Clean, thin, non-aggressive liquids.
- circulating water in for heating and cooling systems
- water-glycol mixtures. Recommendation: propylene glycol
- nominal pressure 10 bar.
- like in L- and AL -series, but nominal pressure 16 bar.
Clean, thin, slightly aggressive liquids.
- domestic water, oxygen rich waters
- nominal pressure 10 bar.
Agressive, thin, not bigger solid particles containing liquids
LS-, ALS-
All types of
- in addition to above mentioned liquids various acids, salts, oxidizing and chemically active organic fluids
- nominal pressure 16 bar.
Temperature range: -10 ... + 95 °C (continuous + 80°C) Max. temperature of environment +40°C (diurnal average max. +35°C)
FC-pumps
Suitability of materials and seals for pumped liquid shall be always checked between pur­chaser and supplier.
The nominal pressure and the max. temperature of pumped liquid are stamped on the pump rating plate. Never use the pump in any other application or conditions without manufacturer’s acceptance. In the case of damage there may be danger to persons by having poisoning, burns, wounds etc. depending on the pumped liquid and it’s temperature and pressure. The pump surface temperature may cause danger depending on the working conditions.
1.3 Manufacturer
This product is manufactured by OY KOLMEKS AB, P.O.BOX 27, FIN-14201 TURENKI, FINLAND.
1.4 Version
Release date of this manual is 04.01.2005. This is version no. 5.
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
3
Subject to change without prior notice
2. Handling, transport and storage of the pump
2.1 Handling, transport and storage of the pump
Normally the pumps are stable when they are transported and don’t go down even they are bent 10°. Pumps shall be stored in a dry and cool place protected from dust. Temperature of environment must be in -10 °C ... +50°C. It is not allowed to lift the pump from frequency converter. In the case of longer storage time or the pump serves as a stand-by, it is recommended to rotate the pump manually f.ex. from the motor fan at least once a month.
3. Design and function
3.1 Construction
The pump and motor constitute a unit, where the rotating parts of both the pump and the motor are on the same shaft (mono-block design). The motor is of a dry type and the frequency converter is integrated to the electric motor.
Electric motor: Totally enclosed, fan cooled A.C. motor, with frequency converter. Protection form: IP54 Insulating class: F
3.2 Technical data
Pump type Flanges Weight kg
power kW A (400 V) AE_-25/4,-26/4FC_ G 1 15 0,27 0,53 -
AE_-25/2,-26/2FC_ G 1 20 0,85 1,5 ­AE-32/4, -33/4FC_ G 1 1/4 20 0,5 0,9 ­AE-32/2, -33/2FC_ G 1 1/4 20 1,5 2,6 ­L_-32A/4FC_ DN32 19 0,27 0,53 T-32A/4FC_ L_-32A/2FC_ DN32 25 0,85 1,5 T-32A/2FC_ L_-40A/4FC_ DN40 25 0,5 0,9 T-40A/4FC_ L_-40A/2FC_ DN40 29 1,5 2,6 T-40A/2FC_ L_-50A/4FC_ DN50 33 0,7 1,4 T-50A/4FC_ L_-50C/2FC_ DN50 49 2,5 4,5 T-50C/2FC_ L_-65A/4FC_ DN65 47 0,7 1,4 T-65A/4FC_ L_-65A/4FC_ DN65 56 1,6 2,6 T-65A/4FC_ L_-65A/4FC_ DN65 67 2,8 4,7 T-65A/4FC_ L_-65B/2FC_ DN65 69 4,3 6,9 T-65B/2FC_ L_-65B/2FC_ DN65 100 8,0 12,4 T-65B/2FC_ L_-80A/4FC_ DN80 48 0,7 1,4 T-80A/4FC_ L_-80A/4FC_ DN80 62 1,6 2,6 T-80A/4FC_ L_-80A/4FC_ DN80 76 3 4,9 T-80A/4FC_ L_-80A/2FC_ DN80 74 4,3 6,9 T-80A/2FC_ L_-80A/2FC_ DN80 105 8,0 12,4 T-80A/2FC_ AL_-1032/4FC_ DN32 25 0,5 0,9 T-40A/4FC_ (DN40) AL_-1032/2FC_ DN32 29 1,5 2,6 T-40A/2FC_ (DN40) AL_-1066/4FC_ DN65 47 0,7 1,4 T-65A/4FC_ AL_-1066/4FC_ DN65 56 1,6 2,6 T-65A/4FC_ AL_-1066/4FC_ DN65 67 2,8 4,7 T-65A/4FC_ AL_-1065/2FC_ DN65 69 4,3 6,9 T-65B/2FC_ AL_-1065/2FC_ DN65 100 8,0 12,4 T-65B/2FC_ AL_-1081/4FC_ DN80 62 1,6 2,6 T-80A/4FC_ AL_-1081/4FC_ DN80 76 3 4,9 T-80A/4FC_ AL_-1081/2FC_ DN80 74 4,3 6,9 T-80A/2FC_ AL_-1081/2FC_ DN80 105 8,0 12,4 T-80A/2FC_ AL_-1102/4FC_ DN100 70 1,6 2,6 AT-1102/4FC_ AL_-1102/4FC_ DN100 86 3,7 5,8 AT-1102/4FC_ AL_-1106/4FC_ DN100 170 4,4 7,2 AT-1129/4FC_ AL_-1106/4FC_ DN100 200 8,3 13,0 AT-1129/4FC_ AL_-1129/4FC_ DN125 175 4,4 7,2 AT-1129/4FC_
AL_-1129/4FC_ DN125 205 8,3 13,0 AT-1129/4FC_
(*
Max. input Nominal current Twin pump
Noise level of all pump types is under 70 dB (A, 1 m).
(*
Single pump weight (AL). The weight of the twin pump (T/AT) is depending on the size of the motor and equipment
each unit. The weight of the twin pump is about two times the single pump weight.
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
4
Subject to change without prior notice
3.3 Rating plate
Shows the information about the electric motor and also design data of the pump.
LP-50A/4FCC1045 S6 K2 V1-C320001
123456/04
5
OKFC-100 B2 F15
400
5 - 30
4
1,4
10
135
PM
0,45
0,70
3.4 Pump identification
Pump series:
L_= single in-line pump, with flanges AL_= single in-line pump, with flanges AT,T = twin in-line pump, with flanges AE = single in-line pump, with pipe connection
Material of pump housing, sealing flange and impeller / nominal pressure of the pump:
no letter = grey cast iron EN-GJL-200 / 10 bar H = nodular cast iron EN-GJS-400 / 16 bar P = bronze CuPb5Sn5Zn5 / 10 bar S = stainless steel AISI 316 / 16 bar
Flange sizes:
AE_: 25/26 = G 1 32 = G1 1/4
AL_/AT: x03 = DN 32 x05 = DN 50 x06 = DN 65 x08 = DN 80 x10 = DN 100 x12 = DN 125
L_/T: 40 = DN 40 50 = DN 50 65 = DN 65 80 = DN 80 100 = DN 100 125 = DN 125
L P - 50 A / 4 FC C 10 45
Version number (AL/AT) or letter (L_ /T)
Poles of the electric motor:
2 = rotation speed 50 r/s (50 Hz) 4 = rotation speed 25 r/s (50 Hz) rotation speed 30 r/s (60 Hz)
FC = the frequency converter is integrated to the motor
Control method:
A, B, C, D, E, F, G (please check 5.4 Control methods and connections)
The range of the pressure (dierence) transmit­ter:
Examble: 10 = 0 - 1 bar 60 = 0 - 6 bar
Control range (depending on pump type): Examble:
45 = 0,5 - 4,5 m 80 = 0,5 - 8 m 20 = 2 - 20 m 60 = 1 - 6 bar
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
5
Subject to change without prior notice
4. Safety
This manual includes important information concerning installation and operating the pump. Persons who are involved in installation or/and operation of the pump, should read and understand these instruction before installation or starting the pump.
There are live parts inside the frequency converter, when the supply voltage is connected. Incorrect installation may cause damage to the pump or bodily injuries, even death. Touching the live parts may be mortal even the supply voltage is disconnected. Wait at least 4 minutes! Obey instructions of this manual and national and local requirements and standards.
- installation must be protected by fuses and insulated correctly.
- covers and cable inlet must be installed.
Attention: It is user’s or certfied electrician’s responsibility to ensure the correct earthing and protection in accor­dance with applicable national and local requirements and standards.
4.1 Safety instructions
1. FC-pump must be disconnected from the mains if repair work is to be carried out. Check that the mains supply has been disconnected and necessary time has passed (at least 4 minutes).
2. The device must be connected correctly to the earth. User must be protected from supply voltage and the pump must be protected from short circuit according to the national and local requirements and standards. The overload protection is included in FC -pump.
3. Earth leakage is more than 3,5 mA. It means, that installation of supply cable must be fixed.
4.2 Training
The persons who have responsibility for installing or/and operating the pump, should be trained.
4.3 Elements of danger if safety regulations are not obeyed
If the safety regulations are not obeyed, personal injuries or damage to the pump or related devices may occur. Vali­dity safety instructions must be obeyed.
4.4 Safety instructions for inspection and assembly
it is user’s responsibility to ensure that persons who carry out inpections and installations are qualified experts and familiarized themselves with these instructions carefully.
4.5 Operating the pump
Working safety of the delivered pump and related devices can be ensured only if these devices are operated according to the section 1.2 Applications of this manual.
5. Installation, introduction and start-up
5.1 General
The position of the motor unit with the frequency converter can be changed by removing the motor unit from the pump housing and setting it to the desired position (not in LH- and ALH-serie and in FCB, FCC ja -FCD-types with certain limitations).
When installating the pump pay attention to the following:
- space enough for service and inspection of the pump
- free visibility to the scale of the potentiometer and curve plate of the pump.
- possibility to use lifting mechanism if needed
- shut-o valves on the both sides of the pump
- the frequency converter is not too close hot pipes.
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
6
Subject to change without prior notice
5.2 Positions for installation
Allowed positions
Allowed positions, if the pipes of the pressure dierence transmitter are not installed to the flanges of the
pump
Not allowed positions
5.3 Electrical connections
All electrical work shall be carried out by qualified electrician approved by the local authorities. Supply voltage may be connected with standard cable, screened cable is not required. Ensure, that the nominal voltage of the electric motor corresponds the local supply voltage.
Use always screened control cables.
ATTN
Before starting the pump fill and vent the system. Make sure that the pump rotates freely by rotating it manually f.ex. from the motor fan. Never start or let the pump run dry.
Before starting the pump fill and vent the system. After starting make sure that there is no extra noise coming from the pump and that no leakages appear.
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
7
Subject to change without prior notice
5.4 Control methods and connections
5.4.1 I/O’s of the FC-pump (inputs and outputs)
Terminal 1 / X101 analog input 0-20 or 4-20 mA (dierent possible functions)
Terminal 2 / X101 analog input 0-10V or digital input (dierent possible functions)
Terminals 3, 4 and 5 / X101 digital input (dierent possible functions)
Terminal 6 / X101 24 V DC supply for digital inputs and feedback (max. 150 mA )
Terminal 7 / X101 10 V DC supply for potentiometer (max. 15 mA )
Terminal 8 / X101 0 V for terminals 1-7 ja 9
Terminal 9 / X101 analog or digital input (dierent possible functions,
Relay output: Terminals 1, 2 and 3 / X102 relay output (dierent possible functions), potential free change-over
contacts, max. 250 V / 5 A
5.4.2 Factory settings
Terminal 1 / X101. No operation (setup1) or Feedback 4-20 mA (setup2) depending on selected control method.
Terminal 2 / X101. Speed reference 0-10V (setup1) or Reference of controller 0-10V (setup2) depending on selected
control method.
Terminal 3 / X101. Setup selection. Terminals 6-3 open/closed means setup1/setup2 selected. If setup1 is selected, speed reference 0-10V is connected to the terminals 2-8 with potentiometer or external signal. The speed of the pump is controlled according to the voltage signal. If the voltage is selected with potentiometer, the speed is constant. When Setup2 is selected the controller of frequency converter is in use. The reference of controller 0-10V is connected to the terminals 2-8 with potentiometer or external signal. Feedback signal 4-20 mA is connected to the terminal 1. The speed of the pump changes according to the need of regulation.
Terminal 4 / X101. Stop / Start. Terminals 6-4 open means pump is not running, closed means pump is running.
Terminal 5 / X101. Reference freeze (both setup’s). When terminals 5 and 6 are connected, the speed reference (se-
tup 1) or the reference of the controller (setup 2) is freezed (not possible to change with potentiometer). By discon­necting the wire between terminals 5 and 6, reference (0-10V) to the terminal 2 / X101 is in use.
Terminal 9 - (8) / X101. Digital output signal (24VDC, max. 25 mA) - fault. The voltage in termina indicast the fault in the pump / inverter. Voltage is zero, if the supply voltage is not connected or there is no fault. If the potential free contact is needed, the separate relay (24 VDC, < 25 mA) is needed. Please check the wiring diagram in section 5.4. This terminal is possible to program with separate local control panel (not included is standard delivery) to an other digital or analog output. E.g. 0 (4) - 20 mA analog output for frequency, reference, feedback, etc.
Relay output: Terminals 1, 2 and 3 / X102. Terminals 1 and 2 are connected when motor is running. Terminals 1 and 3 are connected when motor is not running (or the supply voltage is not connected).
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
8
Subject to change without prior notice
5.4.3 FCA -pump - speed reference from potentiometer
Applications
Systems, where the duty point remains constant and where is no need for continuous automated regulation.
Accessories
Pump, frequency converter and potentiometer.
Operation principle
The speed of electric motor can be adjusted manually at the site. Useful feature for commissioning of the pump. The pump will run with constant speed. The reference can be freezed by connecting wire between terminals 5 and 6.
ATTN
Mark the position of the potentiometer to the sticker in cover of the frequency converter.
Pump curve
QH-curve of the pump is equal with that of single speed pump.
Standard control connections
FACTORY DEFAULT: SETUP 1 SETUP 1 = speed reference (FCA) SETUP 2 = controller of the frequency converter in use, e.g. FCB, FCC
m
l/s
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
30
10
min.
An example of curve plate of FCA -pump.
The control range is shown in curve plate which is located in cover of the frequency converter.
9
Subject to change without prior notice
50
70
90
max.
%
5.4.4 FCB -pump - constant pressure between the pump flanges
Applications
Systems, where are variations in the flow and where pressure losses are generated mainly on the consumption equipment. Heating circulation, where the pressure loss on the heat exchanger is small.
Accessories
Pump, frequency converter, potentiometer and dierential pressure transducer with pipes to the pump flange.
Operation principle and flow adjustment
The level of the constant pressure dierence between the pump flanges can be adjusted by potentiometer. The set value for the pressure dierence can be found from the curve plate of the pump. The pump will run with variable speed. When adjusting the flow of the system, the main control valve must be opened as open as possible and then the flow is adjusted by potentiometer. The reference can be freezed by connecting wire between terminals 5 and 6.
ATTN
Mark the position of the potentiometer to the sticker in cover of the frequency converter.
Pump curve
QH-curve of the pump is controlled to a horizontal line.
Standard control connections
FACTORY DEFAULT: SETUP 2 SETUP 2 = constant pressure dierence (FCB, controller of the frequency converter in use) SETUP 1 = speed reference (FCA)
m
l/s
By disconnecting the wire from potentio­meter to the terminal 2 and connecting the external 0-10V signal to the terminals 2-8, the reference for pressure dierence is gi­ven externally. Please check section 5.4.7.
dierential pressure transducer
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
30
10
min.
An example of curve plate of FCB -pump.
The control range is shown in curve plate which is located in cover of the frequency converter.
10
Subject to change without prior notice
50
70
90
max.
%
5.4.5 FCC -pump - constant pressure between inlet- and outlet-line
Applications
Systems, where are variations in the flow and where pressure losses are generated mainly on the source of heat equipment. Heating and cooling circulations and the pressure boosting of parellel circulations.
Accessories
Pump, frequency converter, potentiometer and dierential pressure transducer with pipes. One pipe to be installed to the suction or pressure flange of the pump and the another one on to the system, inlet or outlet pipe.
Operation principle and flow adjustment
The level of the constant pressure dierence between the inlet- and outlet-line of the system can be adjusted by potentiometer. The set value for the pressure dierence can be found from the curve plate of the pump. The pump will run with variable speed. When adjusting the flow of the system, the main control valve must be opened as open as possible and then the flow is adjusted by potentiometer. The reference can be freezed by connecting wire between terminals 5 and 6.
ATTN
Pump curve
QH-curve of the pump is controlled to a quadratic. The relation of pressure loss in the source of heat (cold) to the loss in the system de­fines the shape of the curve.When the losses in the heat exchanger are large part of the whole losses in the system the curve is more steep.
Mark the position of the potentiometer to the sticker in cover of the frequency converter.
m
Standard control connections
FACTORY DEFAULT: SETUP 2 SETUP 2 = constant pressure dierence (FCC, controller of the frequency converter in use) SETUP 1 = speed reference (FCA)
l/s
By disconnecting the wire from potentio­meter to the terminal 2 and connecting the external 0-10V signal to the terminals 2-8, the reference for dierential pressure is given externally. Please check section 5.4.7.
50
30
10
min.
70
90
max.
%
An example of curve plate of FCC -pump.
dierential pressure transducer
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
The control range is shown in curve plate which is located in cover of the frequency converter.
11
Subject to change without prior notice
5.4.6 FCCVAK -pump - constant pressure between supply- and return-line with external controller in use (SETUP 1)
Operation principle (speed reference 0-10 V for pump)
The level of the constant pressure dierence between the inlet- and outlet-line of the system can be adjusted by external control system (speed reference 0-10 V to the terminal 2).
Flow adjustment and balansing the system
Before adjusting and balancing the system the dierential pressure transducer is connected to the external control system. The main control valve must be opened as open as possible and then the flow is adjusted by potentiometer, which is connected to the terminal 2 (constant speed) to replace external speed reference while adjusting and balan­cing the system. When the system has adjusted and balanced, the value of the pressure dierence is read and saved to the control system as a reference value.
Alternatively the correct pressure dierence value can be adjusted with potentiometer when the pump is connected as a standard FCC -pump (check the previous page). When the system has adjusted and balanced, the reference of the pressure dierence (m) can be read from the scale of the potentiometer (e.g. 20 % = 1.7 m), which is then saved as a reference value to the external control system.
Check and update the connections!
Standard control connections
FACTORY DEFAULT: SETUP 1 SETUP 1 = speed reference from external controller (FCCVAK1) SETUP 2 = reference for dierential pressure from external control system (controller of the frequency converter is in use, FCCVAK2)
In the cover of the frequency converter is curve plate, where the set value for the pressure dierence can be found in ratio (%) to the range of the reference of the pressure dierence and to the position of the potentiometer. Curve plate is valid, when setup2 is selected, terminal 6-3 is closed. According to the factory default, the setup1 is selected, speed reference 0 V corresponds the minimum speed and 10 V corresponds maximum speed. The rotation speed unit is r/s, which is marked in the rating plate. The corresponding frequencies are minimum 10 Hz and maximum 50 or 60 Hz. The datas­heet, where the pump curves can be read with dierent frqeuncies, is also delivered with this version.
The switch in external control system between terminals 4-6 väliin (e.g. automatic summer stoppage).
*) When pump is delivered from the factory, the wire of the potentiometer is connected to the terminal 2 then the pump can be operated as FCA -pump. By disconnecting the wire and connecting the external voltage signal to the terminal 2, the pump is control­led externally.
dierential pressure transducer
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
12
An example of curve plate of FCCVAK -pump.
The control range is shown in curve plate which is located in cover of the frequency converter.
Subject to change without prior notice
5.4.7 FCCVAK -pump - constant pressure between supply- and return-line with controller of the frequency converter in use (SETUP 2)
Operation principle (reference for pressure dierence 0-10 V for pump)
The level of the constant pressure dierence between the inlet- and outlet-line of the system can be adjusted by external control system (reference for dierential pressure 0-10 V to the terminal 2). The operation and connections are the same like in FCC -pump (section 5.4.5), except the reference for pressure dierence in given from the external control system.
Standard control connections
FACTORY DEFAULT: SETUP 2 SETUP 2 = reference for dierential pressure from external control system (control­ler of the frequency converter is in use, FCCVAK2) SETUP 1 = speed reference from external controller (FCCVAK1)
The switch in external control system between terminals 4-6 (e.g. automatic summer stoppage).
*) When pump is delivered from the factory, the wire of the potentiometer is connected to the terminal 2 then the pump can be operated as FCA -pump. By disconnecting the wire and connecting the external voltage signal to the terminal 2, the pump is controlled externally.
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
13
Subject to change without prior notice
5.4.8 FCD -pump - constant pressure in discharge flange
Applications
Pressure boosting or other open systems, where constant pressure is required.
Accessories
Pump, frequency converter, potentiometer and pressure transmitter with pipes. The pressure transmitter is installed to the pressure flange of the pump or near to the consumtion in the pipe line.
Operation principle
The level of the constant pressure on the pressure flange of the pump or on the outlet-line of the system can be adju­sted by potentiometer. The set value for the pressure dierence can be found from the curve plate of the pump. The pump will run with variable speed. The reference can be freezed by connecting wire between terminals 5 and 6.
ATTN
Mark the position of the potentiometer to the sticker in cover of the frequency converter.
Standard control connections
FACTORY DEFAULT: SETUP 2 SETUP 2 = constant outlet pressure (controller of the frequency converter is in use, FCD) SETUP 1 = speed reference from potentiometer (FCA)
10
30
min.
50
70
90
max.
%
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
14
An example of curve plate of FCD
-pump.
The control range is shown in curve plate which is located in cover of the frequency converter.
*) Pressure switch for dry run protection can be connected between terminals 6-4. Pressure switch is not included in standard delivery.
Subject to change without prior notice
5.4.9 FCE -pump - sensorless, pre-programmed pump curves
Applications
Systems, where are variations in the flow. Heating and cooling circulations and the pressure boosting of parellel circulations.
Accessories
Pump, frequency converter and potentiometer.
Operation principle, pump curve and adjusting the flow
The pump curve is selected with potentiometer from the curve plate. The selection is stepless. When adjusting the flow of the system, the main control valve must be opened as open as possible and then the flow is adjusted by potentiometer.
ATTN
Mark the position of the potentiometer to the sticker in cover of the frequency converter.
Standard control connections
FACTORY DEFAULT: SETUP 2 SETUP 2 = variable pressure (FCE) SETUP 1 = speed reference from potentiometer (FCA)
m
l/s
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
15
50
30
10
min.
70
max.
%
Subject to change without prior notice
90
5.4.10 FCF -pump - constant temperature
Applications
Heating and cooling systems, where the constant temperature is required.
Accesories
Pump, frequency converter, potentiometer, temperature transmitter (and sensor).
Operation principle
The constant temperature, which is adjusted by potentiometer, is kept up by regulating the flow. The reference can be freezed by connecting wire between terminals 5 and 6.
ATTN
When ordering the pump, the response of the control must be informed. In the heating system the res­ponse is normal, in the cooling system inverse.
Mark the position of the potentiometer to the sticker in cover of the frequency converter.
Standard control connections
FACTORY DEFAULT: SETUP 2 SETUP 2 = constant temperature (FCF1, controller of the frequency converter in use) SETUP 1 = speed reference (FCA).
By disconnecting the jumper between terminals 3-6 (setup1), the pump is running at constant speed (FCA -pump).
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
16
50
30
10
min.
70
90
max.
%
An example of curve plate of FCF
-pump.
The control range is shown in curve plate which is located in cover of the frequency converter.
Subject to change without prior notice
5.4.11 FCF -pump - the speed according to temperature
Applications
Heating and cooling systems, where the flow is controlled by temperature.
Accesories
Pump, frequency converter, potentiometer, temperature transmitter (and sensor).
Operation principle
The speed reference is given by temperature transmitter.
ATTN
When ordering the pump, the response of the control must be informed. In the heating system the res­ponse is normal, in the cooling system inverse.
Mark the position of the potentiometer to the sticker in cover of the frequency converter.
Standard control connections
FACTORY DEFAULT: SETUP 2 SETUP 1 = speed reference (FCA) constant temperature (FCF, controller of the frequency converter in use) SETUP 2 = speed referense according to the temperature (FCF2)
By disconnecting the jumper between terminals 3-6 (setup1), the pump is running at constant speed (FCA -pump).
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
17
Subject to change without prior notice
5.4.12 FCG -pump - controlled by external system
Applications
Systems, where are variations in the flow and/or where the flow is controlled mainly with the pump. The pump is controlled by external system or controller.
Accessories
Pump, frequency converter, potentiometer (for FCA -connections).
Operation principle
The speed reference for pumps is given from external control system, external controller, process control, etc.
Standard control connections
FACTORY DEFAULT: SETUP 1 SETUP 1 = speed reference 0-10 V (FCA, from potentiometer or FCG from external controller) SETUP 2 = controller of the frequency converter in use (e.g. FCB, FCC)
The switch in external control system between terminals 4-6 väliin (e.g. automatic summer stoppage). When pump is delivered from the factory, the wire of the potentiometer is connected to the terminal 2 then the pump can be operated as FCA -pump
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
18
*) When pump is delivered from the factory, the wire of the potentiometer is connected to the terminal 2 then the pump can be operated as FCA -pump. By disconnecting the wire and connecting the external voltage signal to the terminal 2, the pump is control­led externally.
Subject to change without prior notice
5.4.13 Connections to the alarm receiving station
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
19
Subject to change without prior notice
5.4.14 Local control panel (optional)
The FC_ -pump optionally features a Local Control Panel - LCP, which makes up the complete interface for operation and monitoring of the FC_ -pump.
LCP installation
LCP is connected to the terminal X100, 1-4
LCP functions
The functions of the control panel can be divided into three groups:
- display
- keys for changing program parameters
- keys for local operation
All data are indicated by means of 4-line alpha-numeric display, which in normal operation is able to show 4 me­asurements and 3 operation conditions continuously. During programming, all the information required for quick, eective parameter setup of the FC_ -pump will be displayed. As a supplement to the display, there are three LEDs for voltage, warning and alarm. All programming parameters of the FC_ -pump can be changed immediately from the control panel, unless this function has been blocked vial parameter 018.
Control panel is connected to these terminals
Reference, value of potentiometer (or other value which is defined in
parameter 010))
Motor current or other value which is defined in parameter 011
Feedback value or other value which is defined in parameter 012
Frequency or other va­lue which is defined in parameter 009. Active warnings and alarms.
Mode. Normal: REM RUN OK
DISPLAY STATUS - chan­ges the first line from headline to analog values. If button is hold, the titles of the analog values are shown: REF. , CURR. , FEEDB. eferense, motor current and feedback)
By pushing CHAN- GE DATA button the submenu of paramater setup is selected.
Active setup. Setup1 speed reference (A- or G-version ), Setup2 Reference control ( B,C,D)
With MENU button the parame­ter mode is selected.
With OK button the changes are confirmed. Sometimes the change is confirmed without pushing OK.
With CANCEL button you'll get back without confirming the changes, if OK is not pushed.
START button. FC-pump must be left to RUNNING MODE before disconnecti­on of control panel!!
After pushing MENU button, parameter group 0 … 9 are selected with these narrow buttons or after pushing CHANCE DATA but- ton the required decimal is selected with these narrow buttons.
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
With +/- buttons the large reading can be selected. 23 dierent option eg. the feedback mA or reference V also motor power, current, temperatures etc. Parameters are selected with +/- button after pushing MENU button and selection parameter group with narrow buttons. After pushing CHANCE DATA button with +/- buttons is the new value of the parameter selected
20
Subject to change without prior notice
Exambles
Checking of the duty poin of the pump:
Push DISPLAY STATUS button once and read the values of first line. Normally the first value is reference, the second is motor current and the third is feedback (if the setup 1 is selected the third value is power). If DISPLAY STATUS is hold, the titles of the analog values are shown. ( REF. (reference), CURR. (motor current) and FEEDB. (feedback)
Checking and changing of the numerical parameter: e.g. swithing frequency from 8000 Hz to 7000 Hz ( parameter No 411 ). Push MENU button once, then the number of the parameter group is on the bottom line. If necessary push narrow buttons until required group (4..) is selected. Push + or - buttons until parameter 411 is on the bottom line. Also the present value is shown. Push CHANCE DATA button to select the parameter changing mode. Move the flashing cursor with narrow buttons to the digit which is to be changed. Change the digit with + or - but­tons. The new value becomes eective immediately, but the selection must be confirmed with OK button. Push DISPLAY
STATUS button to return to the first display.
Checking and changing of the text parameter:
e.g. parameter 437 changing from NORMAL to INVERSE (application: temp. control in coolling system). Push MENU button once, then the number of the parameter group is on the bottom line. If necessary push narrow buttons until required group (4..) is selected. Push + or - buttons until parameter 437 is on the bottom line. Also the present value is shown. Push CHANCE DATA button to select the parameter changing mode. Change the value with + or - buttons. Confirm the selection with OK button. ATTENTION! All parameters are not allowed to change without stoppage of the pump with STOP RESET button. After changing parameters start the frequency converter always with START button.
Checking of the analog mA -value of the feedback transmitter (terminal N:o 1):
In first display (if necessary push first DISPLAY STATUS) push + or - buttons until to the first line comes the text ANALOG INPUT 1. The large value in display is the mA -value of the feedback transmitter. The value must be over 4 mA lower than 20 mA in the normal situation. In the same way is checked the reference V -value ANALOG INPUT 2. The value must be over 0 V but lower than 10 V in the normal situation.
Checking of fault log (parameter 615):
Push MENU button once, then the number of the parameter group is on the bottom line. If necessary push narrow buttons until required group (6..) is selected. Push + or - buttons until parameter 615 is on the bottom line. Push CHANCE DATA button to select the parameter reading mode.
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
21
Subject to change without prior notice
6. Service, spare parts and troubleshooting
The pump doesn’t need any regular servicing. As a shaft seal is used an adjustment free mechanical seal. It is a wea­ring part which has to be replaced if it starts to leak. Note that few drops leakage per hour can be quite normal espe­cially when coolants (f.ex. glycol) are pumped.
6.1 Shaft seals
Pump type Shaft O-ring mm / gasket mm AE_-25/-26 FC_ 12 123x2,5 L-32A FC_ 12 100x2,5 L_-40A, AL_-1032, AE_-32/-33 FC_ 12 145x2,5 L_-50A, AL_-1054 FC_ 12 150x3 L_-50C, AL_-1055 FC_ 18 150x3 L_-65A, L_-65B, AL_-1065, -1066, L_-80A, AL-1081, -1102 FC_ 18 179,3x5,7 AL_-1106, -1129 FC_ 32 309/295x1
The motor is equipped with ball bearings which are lubricated for life and therefore do not need any service. In the case of any motor malfunction it is recommended to replace the whole motor unit.
1 Rotating ring 2 Stationary ring 3 Body / bellows 4 Spring 5 O-ring
6.2 Other parts
1 Electric motor 2 Pump housing 3 Impeller 5 Sealing flange 8 Foot (not always) 24 Screw or nut 25 Washer 26 Key 40 Shaft seal 50 O-ring or gasket 60 Screw or nut 67 Screw 80 Pipe union (L- and ALH -serie) 81 Pipe union (L- and ALH -serie) 86 Cooling pipe (L- and ALH -serie) 103 Frequency converter 111 Fixing plate (FCB, FCC) 112 Pipe joints (FCB, FCC) 113 Pipes (FCB, FCC) 114 Transmitter for pressure, pressure
dierence or temperature (FCB, FCC,FCD, FCF)
115 Cable (FCB, FCC, FCD, FCF) 117 Screws (FCB, FCC)
WHEN ORDERING SPARE PARTS, PLEASE SPECIFY THE TYPE IDENTIFICATION, SERIAL NUMBER, THE SIZE OF THE IMPELLER, THE MOTOR TYPE AND POWER AND THE POSITION NUMBER OF THE SPARE PART.
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
22
Subject to change without prior notice
6.3 Troubleshooting
Trouble
Shaft seal is
Wearing.
Fault Fixing
leaking.
Pump has run dry.
Pump don’t run. The shaft of the pump is blocked.
Fuses have worked.
No electricity.
The disorder has stopped the pump.
Change the seal.
Change the seal.
Check the free rotation of the shaft by tur­ning the motor fan. If required, loosen the motor unit from the pump housing and repair the cause of the block.
Repair the cause of the fault. Change the fuses. If necessary, call the expert.
Check and repair connections. If necessary, call the expert.
Reset the pump by disconnecting the supply voltage at least for 10 seconds.
Pump stops by itself or runs irregular and noisy.
Control wiring is not correct.
The parametres of the frequency conver­ter are changed or the pump is stopped with local control panel.
The frequency converter or electric motor is damaged.
If the pump is operated when cover of the frequency conver­ter is open, the special careful­ness must be observed.
The supply voltage is defective. One phase is possible missing.
The frequency converter or electric mo­tor is damaged.
Check the wiring in accordance with the cont­rol diagram. Between terminals 4-6 must be jumper or closed switch.
Correct the parameters or start the pump with the local control panel (not included in standard delivery). If necessary, call the expert.
Replace the frequency converter and/or electric motor with a new one. Contact to Kolmeks.
Check the supply voltage. Check and repair fuses and connections of the cables.
Replace the frequency converter and/or electric motor with a new one. Contact to Kolmeks.
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
23
Subject to change without prior notice
Trouble
Fault
Fixing
The pump is run­ning with mini­mum frequency.
The reference value is missing or in minimum.
The pipes of the pressure or dierential pressure transducer are blocked or incor­rectly connected.
The signal of the feedback transmitter (pressure or temperature) is too high. Possible short circuit.
The mechanical or electrical connections of the temperature transmitter of the FCF -pump are incorrect or the transmit­ter is damaged.
Adjust the correct value with the potentio­meter (if intention to use the potentiometer as source of the reference signal). Check the wiring of the potentiometer. Check and correct the reference if the reference is given by exter­nal controller.
Check and repair the connections and blockings of the pipes. Open the possible valves, which are installed to the pipes.
Disconnect the cable from the transmitter, the speed should increase, if there is a fault in transmitter or the signal. Check the connec­tions, transmitter. If necessary, replace the transmitter with the new one.
Check and repair of the connections or the transmitter.
The pump is run­ning only with the maximum frequency, which don’t vary in accordance with the requirements of flow changes.
Parameters of the FCF -pump are wrong. ( cooling and heating pumps have die­rent parameters)
The incorrect setup selection or wrong parameters.
Reference signal is too high.
Feedback transmitter is missing or the signal is wrong.
Check and correct the parameters with the local control panel. If necessary, call the expert.
Check the selected setup. Terminals 6-3 closed = setup2, opened = setup1. Check and correct the parameters with the local control panel. If necessary, call the expert.
Adjust the correct value with the potentiometer (if intention to use the potentiometer as source of the reference). Check the wiring of the poten­tiometer. Check and correct the reference if the reference is given by external controller.
Check and repair the feedback signal and/or connections. If necessary, replace the transmit­ter with the new one.
The pipes of the pressure or dierential pressure transducer are blocked or incor­rectly connected.
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
24
Check and repair the connections and blockings of the pipes. Open the valves, which may be installed to the pipes.
Subject to change without prior notice
Trouble
Fault
Fixing
The pump is run­ning only with the maximum frequency, which don’t vary in accordance with the requirements of flow changes.
The mechanical or electrical connec­tions of the temperature transmitter of the FCF -pump are incorrect or the transmitter is damaged.
Parameters of the FCF -pump are wrong. (cooling and heating pumps have dierent parameters)
The incorrect setup selection or wrong parameters.
The maximum speed is required by the system.
Check and repair of the connections or the transmitter.
Check and correct the parameters with the lo­cal control panel. If necessary, call the expert.
Check the selected setup. Terminals 6-3 closed = setup2, opened = setup1. Check and correct the parameters with the local control panel. If necessary, call the expert.
Check the adjustments and the need of the pumping in the system. Balance the parallel circulations. It can be the normal situation, then there is no need for any further measu­res. Solve the actual rotation speed by measu­ring or with the local control panel. Contact to Kolmeks. Maximum frequency is not allowed to change (factory default).
Green LED 302
Yellow LED 301
Red LED 300
Operation
o o o Connect the supply voltage. on o o Connect the start and reference signal on o on Disconnect the supply voltage as long as all LEDs are o.
on on on Disconnect the supply voltage as long as all LEDs are o.
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
25
Subject to change without prior notice
Trouble
Fault
Fixing
The pump is not pumping.
The pump is noisy.
There is air in the pump or the sys­tem.
The suction pressure is too low.
Circulation is closed with the valves
Cavitation.
The pressure dierence of the pump is too high.
There is a faulty shaft seal or bearings.
Deairate the system. Fill the pumps and the pipes with the fluid. Try to run the pump a moment with the high speed, then possible air pockets leave the system easier.
Increase the suction pressure.
Open the valves.
Increase the suction pressure. Decrease the flow.
Decrease the pressure reference. If possible, open the control valves and decrease the pressure reference, then the head of the pump is lower and the flow remains the same.
Continuous rough noise refers to the faulty bearings. High noise, few seconds long, occasionally refers to the faulty shaft seal. Replace faulty bearings and shaft seal with the new ones. If necessary, contact Kolmeks.
Electrical noise from the frequency converter or electric motor.
Replace the motor with the new one. If necessary, cor­rect the parameters of the frequency converter. Contact Kolmeks.
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
26
Subject to change without prior notice
7. Declaration of Conformity
We, OY KOLMEKS AB, P.O.Box 27 FI-14201 Turenki, FINLAND
declare under our sole responsibility that the products
FC_ - PUMP SERIE,
types AE, AEP, L, LH, LP, LS, AL, ALH, ALP, ALS, T and AT,
to which this declaration relates, are in conformity with the
– Council Directive 98/37/EY on the approximation of the laws of the Member States relating to machinery – Low voltage directive 2006/95/EY – Pumps and pump units for liquids. Common safety requirements. EN 809.
EMC STANDARDS
Generic standards
The generic standards are stated in the EMC directive (89/336/ETY).
FC_ -pump complies with:
EN 50081-11), EN 50082-1.
Residental, commercial and light industrial environment.
EN 50081-2, EN 50082-2.
Industrial environment.
1)
Emission levels stated by EN 50081-1 are only fulfilled by FC_ -pumps with class B-1 optional filter. Class
B-1 filter is included in FC_ -pumps as a standard.
Turenki 02.05.2008
Kimmo Issakainen Managing Director
OY KOLMEKS AB
P.O.BOX 27 FI-14201 TURENKI, FINLAND tel. +358 20 7521 31 fax +358 20 7521 200 www.kolmeks.fi export@kolmeks.fi
\\W2s\users\minnara\käyttöhjeet\Kolmeks_FCkäyttöohje\Manual_FCpumps_en_20080506.indd
27
Subject to change without prior notice
Loading...