Koldware 2K07DBH, 2K14DB, 2K10DB, 2K10DHB, 2K14DHB Installation & Operation Manual

...
KOMPAC
SERIES
AIR CONDITIONER
KKSM-3
AND HEAT PUMP
INSTALLATION &
OPERATION
MANUAL
Koolette 7,000 Btu/Hr Cooling Kompac 9,400-16,000 Btu/Hr Cooling King Kompac 20,500-26,000 Btu/Hr Cooling
GENERAL INFORMATION AND
CAPACITY SELECTION..................................... 1, 2
SPECIFICATIONS .................................................. 3
STANDARD AND OPTIONAL FEATURES ........ 4, 5
INSTALLATION INSTRUCTIONS ...................... 6, 7
CHECKOUT OF UNIT OPERATION ...................... 7
MODES OF OPERATION ................................... 8, 9
UNIT CONSTRUCTION................................... 10-12
PARTS REPLACEMENT PROCEDURE ........ 13, 14
PREVENTIVE MAINTENANCE...................... 14, 15
TROUBLESHOOTING GUIDE ....................... 16, 17
PIPING SCHEMATICS ......................................... 18
WIRING DIAGRAMS ...................................... 19, 20
CERTIFIED DRAWINGS ...................................... 21
LIMITED WARRANTY .......................................... 22
PARTS LIST..................................................... 23,24
7,800 Btu/Hr Heating
10,900-17,900 Btu/Hr Heating
24,000-31,000 Btu/Hr Heating
KOOLETTE
KOMPAC
KING KOMPAC
GENERAL INFORMATION
DESCRIPTION
Kompac Series Air Conditioners and Heat Pumps are designed for applications where outside air is not available and spot cooling is required. The cord connected Kompac Models range from a 7,000 Btu/Hr countertop to a 26,000 Btu/Hr floor mount configuration to meet any space requirements. Kompac and King Kompac models are provided with casters f or portability.
All Models are completely self-contained with the entire refrigeration system, fan motor , w ater valve, and electrical components housed in a metal cabinet with a baked enamel finish. Only power and condenser water supply, water discharge, and condensate drain piping are required for installation. With the heat pump option, automatic changeover from cooling to heating to cooling provides the desired comfort, depending upon thermostat command.
The water-cooled condenser requires only that amount of water needed to achiev e the desired high and lo w refrigeration system pressures. The condenser water flow rate for an y entering water temperature can be obtained using the graph on page 8. Condenser w ater is regulated by a refrigeration system head pressure actuated water regulating valve.
260 NORTH ELM STREET • WESTFIELD , MA 01085 • Tel: (413) 564-5520 • F ax: (413) 564-5815
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
GENERAL REQUIREMENTS
For proper control of the water flow rate entering the automatic water valve, the minimum water pressure required for condenser water supply is 30 PSIG.
The condenser water temperature leaving the unit should not exceed 110°F. Ignoring this compliance will void the warranty on the refrigeration system. On heat pump models, it is not recommended to operate the unit in the heating cycle when the water inlet temperature is below 50°F. Doing so could reduce the specified heating capacity and may cause the freeze control to cycle the compressor off, resulting in a loss of heating.
IMPORTANT: Koldwave Air Conditioners have been designed and engineered with your comfort in mind. The length of service you can receive can be extended by following the installation and preventive maintenance instructions. It is important that the warranty card be filled out completely and returned to the factory within ten (10) days of installation of the unit in order to receive the benefits of the warranties.
CAPACITY SELECTION
Koldwave Kompac Series Air Conditioners and Heat Pumps are designed for any type of application with cooling requirements ranging from 7,000 Btu/Hr with the Koolette, 9,400 -16,000 Btu/Hr with the Kompac and 20,500-26,000 Btu/Hr with the King Kompac. Also heating requirements ranging from 7,800 Btu/Hr with the Koolette, 10,900-17,900 Btu/Hr with the Kompac and 24,000-31,000 Btu/Hr with the King Kompac. The Kompac Series cooling capacity designations are shown below.
Capacity Code:07 .................................. 7,000 Btu/Hr
10 .................................. 9,400 Btu/Hr
14 ................................ 12,500 Btu/Hr
16 ................................ 16,000 Btu/Hr
20 ................................ 20,500 Btu/Hr
26 ................................ 26,000 Btu/Hr
Kompac Model designations are:
Prefix K denotes....................Koldwave Kompac Model
Suffix D denotes....................... Air Conditioning Model
Suffix H denotes..........................................Heat Pump
Suffix T denotes ........Unit for Cooling Tower Operation
Suffix S denotes ......................... Stainless Steel Finish
KOLDWAVE NOMENCLATURE
The Koldwave Kompac Series nomeclature is listed below which explains the type of unit, the capacity, the phase, and the voltage.
2 K 14 D H S T 1 1
Series 115 V olt Koldwave Single Phase Capacity Selection Air Conditioning Model Heat Pump Option Type of Finish
Number Code: Phase: 1 - Single Ø
Model
Voltage: 1 - 115V
2 - 208/230V
Cooling T o wer
2
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
PRODUCT SPECIFICATIONS FOR KOMPAC SERIES
2K07DB
2K07DBH
2K10DB
2K10DHB
2K14DB
2K14DHB
CAPACITY DATA
Cooling Capacity (A) Heating Capacity (B) & (D) Evaporator-CFM @ 0.0 ESP
7,000 7,800
250
9,400
10,900
345
12,500 14,200
410
ELECTRICAL DATA
Volts (Single Phase) Amperes (Cooling) Amperes (Heating) Watts (Cooling) Watts (Heating) E.E.R. C.O.P. Fuse/Breaker amps Compressor H.P. Blower Motor H.P. In Rush Current (amps)
115
8.00
7.50 897 840
7.80
2.70
15 1/2
1/25
45.20
115*
9.8
9.50 1,000 1,065
9.40
3.00
15 3/4
1/15
71.50
115*
11.60
10.80 1,276 1,301
9.80
3.20 15
1
1/15
71.50
CONDENSATE PUMP
Motor H.P. RPM Voltage Amperage Draw Lift (Feet of H2O)
1/80
3,000
115
0.48
11.00
1/80
3,000
115*
0.48
11.00
1/80
3,000
115*
0.48
11.00
CONDENSER WATER FLOW & PRESSURE DROP DATA (G)
GPM @ 85° F L.W .T.
Cond. Coil ∆P (P.S.I)
Water V alve P (P.S.I) GPM @ 60° F E.W .T. 100° F L.W.T. Cond. Coil ∆P (P.S.I.) Water V alve ∆P (P.S.I.)
1.75
1.40
2.00
0.44
0.60
2.00
2.25
1.70
2.00
0.56
0.70
2.00
3.00
3.00
3.00
0.75
0.80
2.00
Max. Water Side Working Pressure/With Water Valve-150 P.S.I./Without Valve-400 P.S.I.
MISC. DATA
Evap. Coil-# of Rows Coil Face Area (FT2) Refrigerant Charge R-22 in oz. Water Connections
0.83
3
/8 MF
3
14
1.05
3
/8 MF
18
3
3
1.20 20
3
/8 MF
DIMENSIONAL DATA (inches)
(A) Height-With Casters (B) Height-Without Casters (C) Length (D) Depth
165/8 161/8 223/8
12
311/2 291/8
25
103/16
311/2 291/8
25
103/16
AIR FILTER DATA (inches)
Width Height Thickness
NET WEIGHT SHIPPING WEIGHT
153/4
91/4
1/2
83 89
18 16
1/2 123 132
18 16
1/2 124 133
2K16DB
2K16DHB
16,000 17,900
480
115*
13.00
13.00 1,684 1,692
9.50
3.10 20
11/4 1/15
96.50
1/80
3,000
115*
0.48
11.00
4.00
5.30
5.00
1.00
1.00
2.00
1.20 22
3
/8 MF
311/2 291/8
25
103/16
18 16
1/2 125 134
10.40/10.10
10.50/10.10
3
2K20DB
2K20DHB
20,500 24,000
650
208/230
2,092 2,269
9.80
3.10 15
11/2
1/7
61.90
1/77
3,000
208/230
0.26
11.00
4.50
4.20
8.00
1.10
0.50
2.00
1.90 26
3
/8 MF
283/4 263/8
36
121/4
24
113/4
1/2 175 191
12.70/11.80
12.50/11.50
3
2K26DB
2K26DHB
26,000 31,000
800
208/230
2,708 2,839
9.60
3.20 20
1/7
72.90
1/77
3,000
208/230
0.26
11.00
6.00
6.80
14.00
1.50
0.80
2.00
1.90 30
3
/8 MF
283/4 263/8
36
121/4
24
113/4
1/2 183 201
2K26DHBL
12.70/11.80
12.50/11.50
2
4
2K26DBL
23,200 31,000
800
208/230
2,416 2,839
9.60
3.20 20
1/7
72.90
1/77
3,000
208/230
0.26
11.00
6.00
6.80
14.00
1.50
0.80
2.00
1.90 30
3
/8 MF
283/4 263/8
36
121/4
24
113/4
1/2 183 201
2
4
(A) Cooling Capacity Rating Test Conditions: Evaporator Air - 80°F D.B./67°F W.B .
(B) Heating Capacity Rating Test Conditions: Condenser Air - 70°F D.B./60°F W.B
(C) Time Delay Fuses and Circuit Breakers are recommended. (D) Reverse cycle units require 50°F minimum water inlet temperature during the heating cycle. (E) Total pressure drop for unit with Water Regulating Valve is sum of Condenser Coil and Water Valve Pressure Drop.
*Also available in 208/230 volt.
Condenser Water - 85°F E.W.T./95°F L.W.T.
Evaporator Water - 70°F E.W.T.
3
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
STANDARD AND OPTIONAL FEATURES
STANDARD FEATURES
All Kompac Series units have removable panels to provide full service accessibility. See Part Replace­ment Procedure on page 10 for removal of the correct panel when replacing a part.
Air Flow Flexibility
Air is discharged through four-way adjustable grilles, enabling a variety of air flow possibilities. Koolette, Kompac and King Kompac models each have three, four and five grilles respectively. Washable, aluminum air filters are installed in each unit. Periodic cleaning will ensure optimal unit performance. Kompac models have a reversible top for front or top air discharge.
Quiet, Rugged Cabinet
The Kompac Series cabinet, constructed of 20-guage, cold rolled steel with a baked enamel finish, is com­pletely insulated with a sound absorbent material for cool, quiet comfort.
Automatic Water V alve
All air conditioners and heat pumps are equipped with a direct-acting, refrigeration system head pressure actuated water regulating valve. This valve, set at the factory for 95-100°F outlet water temperature, permits only that amount of water to flow that is needed to achieve the desired refrigeration system pressures. In addition, heat pump models are equipped with a water bypass solenoid valve to provide immediate and continuous water flow on heating. All models used for cooling tower operation, “T” models, are manufactured without water valves.
The cooling only thermostat ranges from 60-95°F with a differential of ± 3°F. The range of the heat pump thermostat is 63-93°F in the cooling mode and
59.5-93.5°F in the heating mode with a differential of
3.5°F. The three position rocker switch located in the control
panel has three functions:
1. It provides fan only operation when depressed to right.
2. It turns the unit off when set in the center position.
3. It activates the cooling or heating mode when depressed to left, depending on unit model and thermostat setting.
The two position switch located under the three position switch provides high fan speed when depressed to the right, and low fan speed when depressed to the left.
When illuminated, the blue light above the thermostat indicates cooling and the amber light (on heat pumps only) indicates heating.
Built-In Condensate Pump
Each unit contains a condensate pump for the positive removal of evaporator condensate. The condensate pump is capable of pumping against an 11 ft. head.
Condenser Coil
The water-cooled, tube-in tube type condenser coil is designed for a maximum water side working pressure of 400 PSI.
Safety Engineered
All units incorporate within the refrigeration system, a high pressure switch for maximum safety of the compressor. The cut-out pressure setting is 375 PSIG ± 3 PSIG. During the heating cycle of the heat pump models, a freeze control sensor set at 37 ± 2°F monitors the water temperature leaving the condenser to cut-out the unit and protect the condenser from freezing.
Reliable Controls
All models have self-contained thermostats to provide the desired amount of cooling, which can be selected by adjusting the thermostat to warmer or cooler. On heat pump units, when the thermostat is set at the desired position, the unit will automatically provide heating or cooling, whichever is desired.
Filter
All units are equipped with 1/2" thick, washable, aluminum mesh air filter located behind the front panel that can easily be removed and cleaned. Just pull the filter end cap tab at bottom of filter and slide out.
Discharge Air Grilles
The Koolette is equipped with three, the Kompac with four, and the King Kompac with five 5" x 5", four-way adjustable, plastic grilles located in the upper front panel, enabling a variety of air flow possibilities. Lift each black grille (approximately 3/4") and rotate to the desired position. Release the grille and allow it to return to the set position within the cabinet. By this means, air flow can be positioned in any of four directions.
4
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
Service Cord
The six ft. long service cords employed in the Kompac Series units have plug configurations and receptacle requirements as shown in the chart below.
ELECTRICAL SERVICE PLUG CONFIGURATION
Conditioner
Model Plug Configuration Receptacle
2K07-14DB 15A - 125V 115V Nema 5 - 15P
2K16DB 20A - 125V 115V Nema 5 - 20P
2K10-26DB 20A - 250V 208/230V Nema 6-20P
Nema 5 - 15R
Nema 5 - 20 R
Nema 6 - 20R
OPTIONAL FEATURES
Hose Kit
When employing one of The 7, 20 or 40 reinforced plastic HK22 hose kits in applications with water pressures exceeding 50 PSIG, a water pressure reducing valve must be installed in the water supply line prior to the hose kit; otherwise warranty of the hose kit will be void. The water-out and condensate lines of the three-section flexible plastic hose can be fed to a sink or permanent drain. Additional hose kit fittings and washers are provided to fit most water faucets. When using a hose kit, avoid sharp corners hot water pipes, and kinking or close bends to ensure proper water flow of the supply and return lines.
Cupro-Nickel Condenser
When using chemicals to treat water in cooling tower applications or when water contains process contaminants, it is recommended that the air conditioner be equipped with a 90/10 Naval Spec. Cupro/nickel condenser.
High Pressure Water Valve
High pressure water regulating valves, designed for use with up to 350 PSI water inlet pressure, are available.
Treated Evaporator Coils
For air conditioning applications where airborne contaminants are a problem, acrylic coated evaporator coils are recommended to guard against pitting or corrosion.
Hard Start Kit
A hard start kit consists of a start capacitor and potential relay. The kit is available for all models when they are expected to operate at low voltages and/or ambient temperatures which drive up the equalization pressure in the compressor. Compressors used by Koldwave are designed to operate on 115 and 208/230 volts ± 10%.
Starting Component Wiring Diagram
0240019A
5
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
INSTALLATION INSTRUCTIONS
Before installing: Check the air conditioner for any shipping damage. Air conditioners are thoroughly inspected at the factory and carefully packed. If any damage is evident, file a claim with the delivering carrier immediately.
Electrical Requirements
Check the data plate on the back of the unit to make certain that the proper power is available. Refer to the “Specifications” section for voltage and fuse requirements. Check for proper wall outlet as described in “Standard Features”. Operating the unit on improper voltages will void the warranty.
CAUTION: The use of an extension cord rated at least 15 amps at 115 volts for (2K07-14D); 20 amps at 115 volts for (2K16D); 20 amps for (2K10-26D) at 250 volts and with grounding-type attac hment plug, and grounding-type connector (load fitting) may be used.
Water Fitting Location
Prior to placing the air conditioner in the desired position, note the exact location of the water fittings on the valve plate on the unit rear panel. Water lines should be securely attached to water valve plate fittings. Be sure the line attached to the water source is also attached to the “WATER IN” connection of the unit.
Refer to diagrams and photographs below when installing unit.
Water Out Water In Drain Data Plate
Koolette Kompac King Kompac
6
Water Out Water In Drain Data Plate
Water Out Water In Drain Data Plate
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
Conventional Installation
For proper installation, follow these simple steps: A. Shut off cold water supply.
B. Install “T” between supply valve and faucet of cold
water line. C. Connect water shut-off valve to branch of “T”. D. Insert 3/8" pipe nipple in discharge end of water
shut-off valve. E. Apply coupling over 3/8" pipe nipple and secure.
CHECKOUT OF UNIT OPERATION
Kompac Series air conditioners and heat pumps provide cooling and heating,respectively. This is accomplished by setting the operating controls on either of the following panels:
Fan Only
Plug unit in. Depress the upper mode selector switch to the right for fan only operation. Press down on the two position switch located below the three position switch to the right for high fan speed; to the left for low fan speed.
Cooling Cycle
Depress the upper mode selector switch to the left (cool) for cooling. Set the thermostat knob by turning it clockwise, below the actual room dry bulb temperature level. The blue-colored light located next to the upper rocker switch on the panel will illuminate, indicating cooling mode operation. Allow unit ot run with fan speed set on high for twenty minutes, record temperature of air entering the filter and temperature of air leaving the air discharge grille. In a room temperature of approximately 80°F dry bulb, air coming from the grille should be approximately 15°F cooler than the air going to the filter. This cycle reduces the dry bulb temperature and lowers the wet bulb temperature by condensing water on the cooling coil surface. The condenser leaving water temperature should be between 95-100°F if water flow adjusted propertly.
Note: An alternate installation method can be achieved by drilling a 5/16" diameter hole in the cold water line and assembling a saddle valve to the line. Complete installation by following steps “D” and “E”.
Heating Cycle
Depress the upper mode selector switch to the left (heat) for heating. Set the thermostat knob, by turning it counterclockwise, above actual room dry bulb temperature level. The amber-colored light located next to the upper rocker switch on the panel will illuminate, indicating heating mode operation. Allow unit to run with fan speed set on high for twenty minutes, record temperature of air entering the filter and temperature of air leaving the air discharge grille. In a room temperature of approximately 70°F dry bulb, air coming from the grille should be approximately 30°F warmer than the air going to the filter. The condenser entering water temperature must not be lower than 50°F. The temperature of the water coming from the “water out” fitting should be 7-8 degrees colder than the water going into the unit.
Water temperatures described for cooling and heating modes are based on units with pressure actuated water regulating valves installed as standard equipment at the factory.
Cooling Only Control Panel
Cooling/Heating Control Panel
7
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
WATER FLOWS AT VARIOUS ENTERING WATER TEMPERA TURES
The rated water flow rate at 85°F entering water temperature (E.W.T.) is given in the specification chart earlier in this manual. Water flow rates in that chart will be significanly different from rated water flow at other entering water temperatures. The variance from rated water flow rate is found using the graph below. Using your actual E.W.T., multiply the percentage by the condenser flow rate at 85°F E.W.T. to obtain the actual water flow rate required.
Water Flow Chart
For Example:
What is the actual condenser water flow rate at 50°F E.W.T. (2K14D)?
1. The condenser water flow rate at 85°F E.W.T. is 3.0 G.P.M. from the Water Flow chart.
2. At 50°F E.W.T., the water flow rate percentage would be 25% as seen on the graph.
3. Multiply .25 by 3.0 G.P.M. to get an actual water flow rate of 0.75 G.P.M.
8
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
MODES OF OPERATION
Kompac Series conditioners are available in either a “Cooling Only” or “Cooling/Heating” Model.
The “Cooling” mode directs refrigerant from the compressor to the water-to-refrigerant condenser when the dry bulb temperature is above the desired thermostat setting.
Cooling Only Unit
The Heat Pump Model operates in the cooling or heating modes, depending on thermostat command. A solenoid activated, reverse-cycle valve controls the flow of refrigerant gas through the unit. In the cooling mode, the solenoid is de-energized and the refrigerant is directed from the compressor to the water-to­refrigerant condenser. If heating is required, the solenoid coil is energized, reversing the cycle and directing refrigerant from the compressor to the air-to­refrigerant condenser, i.e., air-to-refrigerant evaporator in the cooling mode.
Heat Pump Unit
0240023A
0240025A
9
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
UNIT CONSTRUCTION
KOOLETTE
Blue Color Light
Cool/Fan/Off Switch
Fan Speed Switch
Thermostat Knob
Fan Housing
Fan Motor
Evaporator
Condensate Pump
Front Air Discharge
Cooling Only Unit Shown
Grille Knob (Spring Retainer)
Return Air Louvers
Air Conditioner Cutaway
Data Name Plate
Water Fittings
Run Capacitor
High Pressure Control
Suction and Discharge Access Valv es
Terminal Block
Condenser Coil
Condensate Drain Pan
Water Regulating Valve
Compressor
Accumulator
10
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
UNIT CONSTRUCTION
KOMPAC
Blue Color Light
Front Air Discharge
Grille Knob (Spring Retainer)
Data Name Plate
Cool/Fan/Off Switch
Fan Speed Switch
Thermostat Knob
Return Air Louvers
Water Fittings
Twin Wheel Plastic Casters
Cooling Only Unit Shown
Air Conditioner Cutaway
Suction and Discharge Access Valv es
Cabinet Insulation
Condenser Coil
Water Regulating Valve
Controls Back of Front Panel
Thermostat Sensing Bulb
Control Panel Cutaway
High Pressure Control
Terminal Block
Run Capacitor
11
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
UNIT CONSTRUCTION
KING KOMPAC
Controls Enclosure
Fan Motor
Fan Motor Capacitor
Front Air Discharge
Twin Wheel Plasitc Casters
Air Discharge Grilles
Grille Knob (Spring Retainer)
Return Air Louvers
Air Conditioner Cutaway
Data Name Plate
Water Fittings
Supply Cord
Suction and Discharge Access Valv es
Condenser Coil
Condensate Pump
Evaporator
Accumulator
12
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
PROCEDURE FOR PARTS REPLACEMENT
A. Fan Motor
1. Remove the entire cabinet on models K10, 14 and 16D. Remove discharge air grilles first. Sides and back are one piece, with screws located at bottom of cabinet.
2. For models K20D and K26D, remove cabinet back panel first. Sides, front and top are one piece with screws located on the bottom of the cabinet.
3. For all models, remove fan motor wires from terminal block and fan speed rocker switch. On Kompac and King Kompac models, remove screws from blower housings located by discharge of blower. Remove locknuts retaining motor to motor base. Remove motor, blower housings and blower wheels as an assembly. On model K07D, the cabinet is in two pieces. Remove front and top first, then back and sides. All screws are external and visible. Loosen set screw in blower wheel. Loosen clamp around motor housing and remove motor.
4. Install new motor, reversing the removing procedure.
B. Thermostat and Rocker Switches
1. For model K07D, remove return air grille and filter. Remove front-top panel and pull away towards left. Remove thermostat sensor bulb from clip. Disconnect wires from controls. Unscrew hex nut retaining thermostat. Remove wires from rocker switches, press down four positive-locking legs of rocker switches used for snap-in mounting and pull out. Replace controls and reverse above procedure.
2. For models K10, 14 and 16D, remove return air grille and filter. Take off panel on which controls are mounted by removing two screws on the left side of the unit by the corner, and two screws on the bottom of the control panel. Follow same removal procedure and controls replacement as described for Model K07D.
3. To replace thermostat and rocker switches on models K20-K26D, remove back and left side panels. Follow same removal procedure and controls replacement as described for Model K07D.
C. Pilot Light(s) To remove pilot light(s) on all models, disconnect
wires from controls, bend Tinnerman clip retaining light and pull out. Install new light, reversing the above procedure.
D. Condensate Pump
1. To replace condensate pump on models K07D, remove the entire cabinet. Disconnect pump wire leads from terminal block. Remove retainer clamp and tygon tubing. Replace pump, reversing
the above procedure.
2. On models K10-16D, remove return air grille, filter and control panel. Disconnect pump wire leads from terminal block. Remove retainer clamp and tygon tubing. Replace pump, reversing the above procedure.
3. For models K20-26D, remove the back and right side panels only. Follow the same procedure as described for models K07-16D to replace pump.
E. Pressure Actuated Water Valve
1. Gain access as outlined above.
2. Disconnect sensing probe from Shrader valve on discharge line. Doing it quickly will minimize the amount of refrigerant loss.
3. Remove valve from mounting bracket.
4. Install new valve.
MISCELLANEOUS PARTS REPLACEMENT AND/OR ADJUSTMENTS
Part Name
A) High Pressure Control B) Compressor Run Capacitor C) Start Capacitor & Relay (if required) D) Freeze Control E) Terminal Block
Remove return air grille, filter and control panel on Kompac models; back panel on King Kompac models, top and front panels on Koolette models.
F) Compressor Overload
Remove return air grille, filter and control panel on Kompac models. Take off top/front panel on model K07D.
G) Reversing Valve H) Reversing Valve Solenoid Coil
Remove front return panel on models K10-16D. Take off back panel on K20-26D. Remove entire cabinet on K07D .
13
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
ABC’S OF TROUBLESHOOTING
A. Read this manual to determine installation,
electrical power, water pressure and flow requirements necessary to allow the air conditioner to perform at its maximum.
B. Refer to general description, wiring diagrams and
photographs to get an understanding of how the unit functions.
C. Establish which part or parts controls the particular
operation. Parts can be tested by the “bypass method”, “the light method”, or “the direct line method”.
PREVENTATIVE MAINTENANCE
Kompac Series units have been designed to give maximum performance and reliability with minimum maintenance. Maintenance of the system is concentrated in three areas covered in the following paragraphs.
The “bypass method” would be used on switches, thermostats, overloads, or any part that completes an electrical circuit. A jumper wire is connected across the terminals of the suspected part. If the trouble is eliminated, the part shorted out is defective and must be replaced.
Motors, compressors and pumps can be tested by the “direct line method”. A line cord with a series fuse is connected directly to the suspected part. The unit under test is then proved inoperative.
The “light method” utilizes a light bulb in the line cord, instead of the fuse as in #2. When this test is applied and the light bulb lights to full brightness, the part tested is shorted. No light indicates the circuit is open.
Koolette
Blower Motor
The only required maintenance to the blower motor is to oil it every six months (every three months for King Kompac models with SAE20 non-detergent oil. On model K07D, remove the one piece front and top cabinet panel to reach the motor oil ports. On models K20-K26D , remove cabinet back panel to oil the motor. Take off the front louvered panel on models K10-K16D to gain access to fan motor oil ports.
Oil Ports
Kompac
Oil PortOil Port
King Kompac
Oil Port Oil Port
14
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
Filter
The life of a filter depends entirely on its environment and use. It is recommended that the filter be inspected on a regular basis every five to six weeks. A clogged filter will cause the unit to operate at greatly reduced efficiency. Washable aluminum air filters located behind the front panel can easily be removed by pulling filter end cap at bottom of filter, slightly lifting up and pulling out. The filter must be washed periodically as needed this may be done as follows:
1. Soak in solution of warm water and detergent for 15 minutes.
2. Rinse in clean hot water, and shake excess moisture from filter.
3. Spray one side of filter with light film of oil.
4. Re-install with oiled surface facing out from unit.
Koolette
Condensate Pump
To gain access to condensate pump, refer to “Procedure for P arts Replacement” section. The pump motor requires oiling every six months with SAE20 non-detergent oil. The pan beneath the condensate pump should be cleaned when mineral deposits are visible. A clean pan will prolong the life of the pump and its operation.
General
If necessary maintenance steps outlined above are carried out regularly, the unit will provide long and reliable service which you should expect from a Koldwave quality product. The refrigeration and electrical circuits of the system should only be serviced by a fully qualified service technician.
If you experience any problems or have comments on your Koldwave product, we are always pleased to hear from you. This is the main way in which we can improve our equipment and assist you in meeting your requirements.
Kompac
King Kompac
15
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
TROUBLE SHOOTING GUIDE
Service other than routine maintenance should be performed only by a qualified refrigeration serviceman. In service troubleshoooting, there is no substitute for a good understanding of the Kompac Series modes of operation, control systems, components and safety systems.
PROBLEM POSSIBLE CAUSE REMEDY
The entire unit does not operate.
Fan runs but compressor does not start.
1. Power interruption.
2. Thermostat not operating.
1. Low voltage.
2. Thermostat.
3. Hi pressure or freeze control (heat pump models) tripping compressor.
4. Refrigerant leak; no gas.
5. Loose or defective wires.
6. Stuck compressor.
7. Compressor shorted, open or burned.
8. Shorted or open run capacitor.
9. Defective thermostat.
1. Check external supply power. Check for blown fuses or tripped circuit breakers. Replace or reset if necessary.
2. Setting may be too high; check unit and reset. Thermostat may be out of calibration or otherwise defective; replace. Also check for loose connection.
1. Check power supply for proper voltage at unit; ± 10% of rated nameplate voltage.
2. Check the control unit for loose wires.
3. Check for loose wire connection, broken or burned contacts. If switch is defective, replace.
4. Locate leak, repair, evacuate and recharge unit.
5. Tug on wires to see if they will separate from connections. Replace terminals if necessary.
6. Try a start capacitor across the run capacitor momentarily (three seconds).
7. Check for shorts, opens and grounds. Remove and replace compressor.
8. Remove or replace.
9. Replace; check location of thermostat bulb. Make certain that it does not touch evaporator coil.
Compressor starts and runs, but fan does not run.
Insufficient cooling.
1. Faulty rocker switch.
2. Open fan motor coil circuit.
3. Shorted or open fan motor capacitor on King Kompac models.
1. Improper sizing of unit.
2. Insufficient air flow through evaporator due to:
a) Dirty air filter in unit.
b) Dirty evaporator. c) Ice on evaporator coil.
d) Obstructed intake.
16
1. Replace.
2. Replace fan motor.
3. Replace fan motors.
1. Check if the unit is undersized for the load. Add supplemental unit(s).
2. Correct as follows:
a) Clean filter (see “Preventative
Maintenance” section of this manual.
b) Unusual condition requires
cleaning.
c) Defrost; use fan only by
depressing the upper rocker switch to right. Check for refrigeration leaks.
d) Remove obstruction.
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
PROBLEM POSSIBLE CAUSE REMEDY
Insufficient heating (heat pump models only)
1. Electric water bypass valve closed or not operating.
2. Water inlet temperature too cold.
3. Reverse cycle v alve stuck open. Solenoid coil not switching valve to heating.
4. Thermostat not set for heating
1. Loose connection in electrical circuit.
2. Air restriction.
3. Partial restriction in refrigeration system.
4. Water regulating valve inoperative or restricted.
5. Water temperature too high.
6. Water to unit not turned on, or adjusted correctly.
1. Check 115 volt circuit for power at valve. Also see if valve coil is open (use ohmmeter).
2. Check water inlet temperature using a thermometer. Inlet water temperature should never be below 50°F.
3. Check for power to solenoid coil, to verify that coil is functional. If the unit still does not switch to heating, replace reversing valve, evacuate and recharge unit.
4. Refer to “Check of Unit Operation” section.
1. Trace and repair.
2. If air filter is dirty or if another air restriction exists, determine problem cause and control.
3. Restriction can be located by inspecting refrigerant lines for temperature changes. Remove restriction, evacuate and recharge.
4. Flush or blow dirty out of valve if necessary.
5. “Water Out” not to exceed 110°F.
6. Turn water on before starting unit. Adjust flow rate if necessary.
Noisy operation.
Water leaking from unit.
Unit give electric shock.
1. Copper T ubing vibrating.
2. Loose cabinet or internal component.
3. Loose blower wheel.
4. Machine vibrating out of level.
5. Blower motor bearing defective.
6. Blower wheel hitting housing.
1. Leaking drain pan.
2. Defective condensate pump or excessive lift on pump.
3. Loose evaporator drain or condensate pump hose.
1. Grounded electric circuit.
1. Adjust by bending slightly to firm position. Separate tubes touching cabinet or each other.
2. Check and tighten loose screws.
3. Tighten screws on blower wheel to shaft.
4. Level unit base.
5. Replace blower motor.
6. Adjust wheel position on motor shaft.
1. Locate leak and repair.
2. Check to see if elevation is over 11 ft. (if it is over 11 ft., a larger pump is required). Otherwise, replace pump if defective. Pump will operate properly against 11 ft. of water total head pressure on pump. If combination of vertical height and horizontal drain line exceeds 11 ft. of water pressure drop, problem may occur.
3. Tighten connections.
1. Test with an ohmmeter or high potential tester. Determine what is grounded and replace or rewire.
17
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
PIPING SCHEMATICS
Air Conditioner
0240023A
Heat Pump
0240025A
18
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
WIRING DIAGRAMS
HEAT PUMP
19
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
WIRING DIAGRAMS
AIR CONDITIONER
0240015A
20
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
CERTIFIED DRAWINGS
21
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
LIMITED W ARRANTY
The manufacturer warr ants to the original owner that the Product will be free from defects in material or workmanship for a period not to exceed one (1) year from startup or eighteen months from date of shipment from the factory, whichever occurs first. If upon examination by the Manufacturer the Product is shown to have a defect in material or workmanship during the warranty period, the Manufacturer will repair or replace, at its option, that part of the Product which is shown to be defective.
The Manufacturer further warrants that the sealed refrigeration system (the product’s compressor, condenser and evaporator) will be free from defects in materials and workmanship for five (5) years from date of start-up or sixty­six (66) months from date of shipment from the factory, whichever occurs first. If upon examination by the Manufacturer the Product is shown to have a defect in material or workmanship during the warranty during the warranty period, the Manufacturer will repair or replace, at its option, that part of the Product which is shown to be defective . Electrical parts (such as relays, overloads, capacitors, etc...) are included in the one year limited warranty but not with the five year limited warranty of the sealed refrigeration system.
This limited warranty does not apply:
(a) if the Product has been subjected to misuse or neglect, has been accidentally or intentionally damaged,
has not been installed, maintained or operated in accordance with the furnished written instructions, or
has been altered or modified in any way. (b) to any expenses, including labor or material, incurred during removal or reinstallation of the Product. (c) to any workmanship of the installer of the Product.
This limited warranty is conditional upon:
(a) shipment, to the Manufacturer, of that part of the Product thought to be defective . Goods can only be returned
with prior written approval from the Manufacturer. All return must be freight prepaid. (b) determination, in the reasonable opinion of the Manufacturer that there exists a defect in material or
workmanship.
Repair or replacement of any part under this Limited Warranty shall not extend the duration of the warranty with respect to such repaired or replaced part beyond the stated warranty period.
THIS LIMITED WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EITHER EXPRESS OR IMPLIED, AND ALL SUCH OTHER WARRANTIES, INCLUDING WITHOUT LIMITATION IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS LIMITED WARRANTY. IN NO EVENT SHALL THE MANUFACTURE BE LIABLE IN ANY WAY FOR ANY CONSEQUENTIAL, SPECIAL, OR INCIDENTAL DAMAGES OF ANY NATURE WHATSOEVER, OR FOR ANY AMOUNTS IN EXCESS OF THE SELLING PRICE OF THE PRODUCT OR ANY PARTS THEREOF FOUND TO BE DEFECTIVE. THIS LIMITED WARRANTY GIVES THE ORIGINAL OWNER OF THE PRODUCT SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHE RIGHTS WHICH MAY VARY BY EACH JURISDICTION.
22
KOLDWAVE KOMPAC SERIES (KOOLETTE, KOMPAC, AND KING KOMPAC)
KOLDWAVE KOMPAC SERIES
SERVICE AND REPLACEMENT PARTS LIST
PART # DESCRIPTION K07 K10 K14 K16 K20 K26 STRAINERS
010-A-049 STRAINER 750171-1 XXXX 010-A-050 STRAINER 750011-6 XX
ASSEMBLIES,STRAINER & CAP TUBE
SA010-A-060 STRAINER & CAP TUBE ASSY. X SA010-A-061 STRAINER & CAP TUBE ASSY. X X X SA010-A-062 STRAINER & CAP TUBE ASSY. X SA010-A-063 STRAINER & CAP TUBE ASSY. X
ACCUMULATORS
010-A-058 ACCUMULATOR 118001-03 X 010-A-052 ACCUMULATOR 137043-1 X X X 010-A-051 ACCUMULATOR 162032-1 XX
BLOWERS & BLOWER ACCESSORIES
013-D-090 BLOWER HOUSING 50-5R 1222 013-A-039 BLOWER HOUSING 60-6 22 013-A-040 BLOWER WHEEL CW 5/16" BORE S47-25/25 1 013-A-081 BLOWER WHEEL CW 1/2" BORE S47-25/25 1 1 1 013-A-082 BLOWER WHEEL CCW 1/2" BORE S47-25/25 1 1 1 013-A-041 BLOWER WHEEL CW 1/2" BORE S63-29/34 1 1 013-A-098 BLOWER WHEEL CCW 1/2" BORE S63-29/34 1 1 013-C-115 BLOWER RING 50-5R 2444 013-A-078 BLOWER RING 60-6 44
COMPRESSORS
020-A-178 1/2 HP 115V. AE233AT X 020-A-186 3/4 HP 115V. AK149BT X 020-A-213 3/4 HP 230V. AK149ET X 020-A-179 1HP 115V. AK144AT X 020-A-180 1HP 230V. AK144ET X 020-A-154 1-1/4 HP 115V. AK147AT X 020-A-155 1-1/4 HP 230V. AK147ET X 020-A-223 1-1/2 HP 230V. AW103FT X 020-A-224 2 HP 230V. AW105FT X
CASTERS
021-A-026 CASTER PPN-05748 BLACK XXXXX
ELECTRICAL COMPONENTS
025-A-691 SOLENOID COIL REV. VALVE L30-320
115 V. HEAT PUMP
025-A-692 SOLENOID COIL REV. VALVE L30-420
230 V. HEAT PUMP 025-A-031 SERVICE CORD 115V. X 025-A-468 SERVICE CORD 115V. 15 AMP X X 025-A-469 SERVICE CORD 115V. 20 AMP X 025-A-470 SERVICE CORD 230V. 20 AMP XXXXX 025-A-608 ROCKER SWITCH TIGM721 COOL/OFF/FAN XXXXXX 025-A-609 ROCKER SWITCH TIGB51 LOW/HI XXXXXX 025-A-585 AMBER LIGHT 3LF4LAN1 115V. XXXX 025-A-610 AMBER LIGHT 3LF4LAN2 230V. XXXXX 025-A-621 BLUE LIGHT 3LF4LB21 115V. XXXX 025-A-622 BLUE LIGHT 3LF4LB22 230V. XXXXX 019-A-063 MOUNTING CLIP FOR INDICATOR LIGHT XXXXXX
FILTERS/AIR
030-A-034 9-1/8" x 15-3/4" x 1/2" X 030-A-041 15-7/8" x 18- 7/8" x 1/2" X X X 030-A-010 24" x 11-3/4" x 1/2" XX
EVAPORATORS
013-A-077 3 ROW #1557 X 031-A-092 3 ROW #1128 X 031-A-076 3 ROW #1522 X X 031-A-094 3 ROW #1186 X 031-A-127 4 ROW #2229 X
XXXX
XXXXX
23
PART # DESCRIPTION K07 K10 K14 K16 K20 K26 CONDENSERS
SA031-A-130 CONDENSER ASSY. 1/2 ROW X SA031-A-131 CONDENSER ASSY. 1 ROW X X X SA031-A-153 CONDENSER ASSY. RECTANGULAR X SA031-A-154 CONDENSER ASSY. RECTANGULAR X 031-A-084 CONDENSER (HEAT PUMPS) XX
* When ordering condensers, please specify model and serial number of the unit
GRILLES
SA038-D-013 AIR DISCHARGE 5" x 5" PLASTIC XXXXXX 076-A-921 SPRING CLIP XXXXXX
MOTORS/BLOWERS
050-A-097 BLOWER MOTOR 115V. 7163-7481 X 050-D-039 BLOWER MOTOR 115V. 7108-5262 X X X 050-A-056 BLOWER MOTOR 230V. DE2E075N XXXXX
PUMPS, CONDENSATE
050-A-105 CONDENSATE PUMP MOTOR 115V. 7121-4633 XXXX 050-A-106 CONDENSATE PUMP MOTOR 230V. 7121-4634 XXXXX SA035-A-004 PLASTIC PUMP HOUSING (LESS MOTOR) XXXXXX 057-A-020 CONDENSATE PUMP IMPELLER XXXXXX SA057-A-021 CONDENSATE PUMP ASSY. 115V. XXXX SA057-A-022 CONDENSATE PUMP ASSY. 230V. XXXXX
CONTROLS
041-A-015 THERMOSTAT CONTROL KNOB XXXXXX 066-A-059
FREEZE CONTROL A30-1700-37 (HEAT PUMPS)
XXXXXX 066-A-061 HI PRESSURE SWITCH AP27-1033 XXXXXX 066-A-098 THERMOSTAT C12-2027 (COOLING ONLY) XXXXXX 066-A-099 THERMOSTAT C17-2025 (HEAT PUMP) XXXXXX
CAPILLARY TUBES
067-D-117 .070 ID x 60" LONG CAP. TUBE 1 3 067-A-103 .070 ID x 40" LONG CAP. TUBE 1 1 1 067-A-121 .064 ID x 40" LONG CAP. TUBE 3
VALVES
068-A-157 WA TER V ALVE 3/8 V46AA-41 XXXXXX 068-A-069 REVERSING VALVE V26-158 (HEAT PUMPS) X X 068-A-183*** REVERSING VALVE V2-308 (HEAT PUMPS) XXXX 068-A-007 WATER BYPASS S30-115V. XXXX 068-A-008 WATER BYPASS S30-230V. XXXXX 068-A-009 RELIEF VALVE-HENRY #5220 (CHICAGO ONL Y) XXXXXX 068-A-031 CHARGING VAL VE STEM XXXXXX
*** When ordering # 068-A-183, a new solenoid coil must also be ordered with the replacement valve
ASSEMBLIES/CABINET (CABINET ASSY., LESS GRILLES)
076-C-2189 TOP/FRONT PANEL X 076-C-1060 BACK/SIDES WRAPPER X
CABINET ASSY., LESS GRILLES
076-C-1043 TOP/FRONT PANEL X X X 076-C-1046 BACK/SIDES WRAPPER X X X 076-C-2188 ELECTRICAL CONTROL PANEL X X X 076-B-1044 RETURN AIR GRILLE X X X
CABINET ASSY., LESS GRILLES
076-C-1080 TOP/FRONT PANEL XX 076-C-1081 BACK PANEL XX 076-C-1480 LEFT PANEL XX 076-C-1082 RIGHT PANEL XX MP076-A-1085 CONTROLS COVER XX
*** Unit front is panel with Koldwave logo***
MISCELLANEOUS
040-A-002 HOSE KIT ADAPTERS FOR HK22-7, 20, & 40 XXXXXX
260 NORTH ELM STREET • WESTFIELD , MA 01085 • Tel: (413) 564-5520 • F ax: (413) 564-5815