Kold-Draft GT350 Service Manual

Page 1
SEQUENTIAL CIRCUIT DIAGRAM – GT350 MODELS
Diagram #1 Water Fill
Bin thermostat closed; Switch in “ice” position; Contactor closed; Water plate closed (pump & defrost switch up)
Liquid level control is low, actuator thermostat warm—power to the water valve. Pump and defrost switch up (water plate closed)—power to the water pump.
Page 2
SEQUENTIAL CIRCUIT DIAGRAM – GT350 MODELS
Diagram #2 Water Fill Complete—Evaporator Temperature Above 26°F.)
Bin thermostat closed; Switch in “ice” position; Contactor closed; Water plate closed (pump & defrost switch up)
Page 3
SEQUENTIAL CIRCUIT DIAGRAM – GT350 MODELS
Diagram #3 Ice Forming—Evaporator Temperature Below 26°F.)
Bin thermostat closed; Switch in “ice” position; Contactor closed; Water plate closed (pump & defrost switch up)
Liquid level control high—power off to the water valve. Pump and defrost switch up (water plate closed)—power to the water pump. Actuator thermostat switches cold.
Page 4
SEQUENTIAL CIRCUIT DIAGRAM – GT350 MODELS
Diagram #4 Defrost- Start of Defrost
Bin thermostat closed; Switch in “ice” position; Contactor closed; Water plate closed (pump & defrost switch up)
Liquid level control switches to low—triggers defrost. Actuator switch up—power to water valve. Actuator thermostat cold—power to defrost valve, power to actuator motor (motor turns CCW). Pump and defrost switch up (water plate closed)—power to water pump.
Page 5
SEQUENTIAL CIRCUIT DIAGRAM – GT350 MODELS
Diagram #5 Defrost- Water Plate Lowering
Bin thermostat closed; Switch in “ice” position; Contactor closed; Water plate open (pump & defrost switch down)
Liquid level control switch low. Actuator switch up—power to water valve. Actuator thermostat cold—power to defrost valve, power to actuator motor (actuator switch up, motor rotation CCW).
Pump and defrost switch down (water plate open)—no power to water pump.
Page 6
SEQUENTIAL CIRCUIT DIAGRAM – GT350 MODELS
Diagram #6 Defrost- Water Plate Full Open
Bin thermostat closed; Switch in “ice” position; Contactor closed; Water plate open (pump & defrost switch down)
Liquid level control switch low. Actuator switch down—power off to actuator motor and water valve. Actuator thermostat cold—power to defrost valve. Pump and defrost switch down (water plate open)—no power to water pump.
Page 7
SEQUENTIAL CIRCUIT DIAGRAM – GT350 MODELS
Diagram #7 End of Defrost- Water Plate Closing
Bin thermostat closed; Switch in “ice” position; Contactor closed; Water plate open (pump & defrost switch down)
Liquid level control switch low. Actuator thermostat switch warm—power to water valve and actuator motor (actuator switch down, motor rotation CW). Pump and defrost switch down (water plate open)—power to defrost valve, no power to water pump.
Page 8
SEQUENTIAL CIRCUIT DIAGRAM – GT350 MODELS
Diagram #8 Defrost Ending- Water Plate Almost Closed
Bin thermostat closed; Switch in “ice” position; Contactor closed; Water plate almost closed (pump & defrost switch up)
Liquid level control switch low. Actuator thermostat switch warm—power to water valve and actuator motor (actuator switch down, motor rotation CW). Actuator switch down—power to defrost valve.
Pump and defrost switch up (water plate almost closed)—power to water pump.
Page 9
SEQUENTIAL CIRCUIT DIAGRAM – GT350 MODELS
Diagram #9 End of Defrost- Water Plate Closed
Bin thermostat closed; Switch in “ice” position; Contactor closed; Water plate closed (pump & defrost switch up)
Liquid level control switch low. Actuator thermostat switch warm—power to water valve. Actuator switch up—power off to actuator motor and defrost valve. Pump and defrost switch up (water plate closed)—power to water pump.
Page 10
SEQUENTIAL CIRCUIT DIAGRAM – GT350 MODELS
Diagram #10 Bin Full- Bin Thermostat Open
Bin thermostat open; Switch in “ice” position; Contactor open; Water plate closed or open
Bin thermostat opens when ice contacts bulb tube—no power to components.
Page 11
SEQUENTIAL CIRCUIT DIAGRAM – GT350 MODELS
Diagram #11 Abnormal Opening of Water Plate
Bin thermostat closed; Switch in “ice” position; Contactor closed; Water plate cannot close (pump & defrost switch down)
Liquid level control switch low. Actuator thermostat switch warm—power to water valve. Actuator switch is pushed up—but power is maintained to actuator motor by pump and defrost switch. Pump and defrost switch cannot be pushed up (water plate obstructed)—red circuit remains energized and water plate re-opens—power to defrost valve, no power to water pump.
Page 12
SEQUENTIAL CIRCUIT DIAGRAM – GT350 MODELS
Diagram #12 Wash Mode
Bin thermostat closed; Switch in “wash” position; Contactor open; Water plate closed (pump & defrost switch up)
Liquid level control switch high. Actuator thermostat switch warm—power to water valve. Actuator switch up—power off to actuator motor. Pump and defrost switch up (water plate closed)—power to water pump, no power to defrost valve. If liquid level control switch low, power to water valve.