Kohler ZCS Operation And Installation

Operation and
Installation
Automatic Transfer Switches
Models:
ZCS
Contactors:
40 to 3000 Amperes
TP-5660 11/98
Table of Contents
Safety Precautions and Instructions I. . . . . . . . .
Introduction i. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
List of Related Materials i. . ..... . . . . . . . . . . . . . .
Service Assistance ii. . . . . . . . . . . . . . . . . . . . . . . . .
Service Information ii. . . . . . . . . . . . . . . . . . . . . . . . . .
Product Indentification ii. . . . . . . . . . . . . . . . . . . . . . .
Section 1. Specifications 1. . . . . . . . . . . . . . . . . . .
1.1 Purpose 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Components 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Nameplate 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4 Part Number Model Code 3. . . . . . . . . . . . . . . . . . . .
1.5 Standard Features 4. . . . . . . . . . . . . . . . . . . . . . . . . .
1.6 Ratings 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.7 Application Data 7.. . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 2. Operation 9. . . . . . . . . . . . . . . . . . . . . . .
2.1 Startup 9.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Automatic Operation 9. . . . . . . . . . . . . . . . . . . . . . . . .
2.2.1 Failure of Normal Power 10. . . . . . . . . . . . . .
2.2.2 Restoration of Normal Power 10. . . . . . . . . .
2.3 Manual Operation 11. . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.1 Programmed Transition Switch,
40--260 Amps 12.. . . . . . . . . . . . . . . . . . . . . .
2.3.2 Programmed Transition Switch,
400--3000 Amps 13.. . . . . . . . . . . . . . . . . . . .
2.3.3 Standard Switch, 800--3000 Amps 14. . . . . .
Section 3. Accessories 15. . . . . . . . . . . . . . . . . . . . .
3.1 Programmed Transition 15. . . . . . . . . . . . . . . . . . . . . .
3.1.1 Description 15.. . . . . . . . . . . . . . . . . . . . . . . . .
3.1.2 Adjustment 15. . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Other Accessories 16.. . . . . . . . . . . . . . . . . . . . . . . . .
Section 4. Scheduled Maintenance 17. . . . . . . . . .
4.1 Inspection and Service 18.. . . . . . . . . . . . . . . . . . . . . .
4.1.1 General Inspection 19. . . . . . . . . . . . . . . . . . .
4.1.2 Other Inspections and Service 19. . . . . . . . .
4.2 Testing 19.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.1 Weekly Generator Set Exercise 19. . . . . . . .
4.2.2 Monthly Automatic Control System
Test 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Service Schedule 20. . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 5. Diagrams and Drawings 21. . . . . . . . . .
Section 6. Installation 55. . . . . . . . . . . . . . . . . . . . . .
6.1 Upon Receipt of Unit 55. . . . . . . . . . . . . . . . . . . . . . . .
6.1.1 Inspection 55. . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.2 Lifting 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.3 Unpacking 56. . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.4 Storage 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2 Mechanical Installation 56. . . . . . . . . . . . . . . . . . . . . . .
6.3 Check Manual Operation 56.. . . . . . . . . . . . . . . . . . . .
6.4 Electrical Wiring 56.. . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4.1 AC Power Connections 58. . . . . . . . . . . . . . .
6.4.2 Generator Start Connection 59. . . . . . . . . . .
6.4.3 Accessory and Controller Connections 59. .
6.5 Prepare the Generator Set for Operation 59. . . . . . .
6.6 Functional Tests 60.. . . . . . . . . . . . . . . . . . . . . . . . . . .
6.6.1 Voltage Check 60. . . . . . . . . . . . . . . . . . . . . . .
6.6.2 Automatic Operation Test 61. . . . . . . . . . . . .
6.7 Controller Setup 61. . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.8 Ensure Warranty Registration 61. . . . . . . . . . . . . . . . .
Appendix A. Glossary of Abbreviations A-1. . . . . .
Safety Precautions and Instructions
A transfer switch, like any other electromechanical device, can pose potential dangers to life and limb if improperly maintained or operated. The best way to prevent accidents is to be aware of potential dangers and act safely. Please read and follow the safety precautions and instructions below to prevent harm to yourself and others. This manual contains several types of safety precautions and instructionswhich are explained below. SAVE THESE INSTRUCTIONS.
DANGER
Danger indicates the presence of a hazard that will cause severe personal injury, death, or substantial property damage.
WARNING
Warning indicates the presence of a hazard that can cause severe personal injury, death, or substantial property damage.
CAUTION
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage.
Accidental Starting
W ARNING
Accidental starting. Can cause severe injury or death.
Disconnect battery cables before working on generator set. (Remove negative (--) lead first when disconnecting battery. Reconnect negative (--) lead last when reconnecting battery.)
Disabling the generator set. Accidental starting can cause severe injury or death. Before
working on the generator set or connected equipment, disable the generator set as follows: 1) Move the generator set master switch to the OFF position. 2) Disconnect power to the battery charger. 3) Remove battery cables, negative (--) lead first. Reconnect negative (--) lead last when reconnecting battery. Follow these precautions to prevent starting of generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
Battery
W ARNING
Sulfuric acid in batteries. Can cause severe injury or death.
Use protective goggles and clothes. Battery acid can cause permanent damage to eyes, burn skin, and eat holes in clothing.
Battery acid. Sulfuric acid in batteries can cause severe injury or death. Sulfuric acid in battery can
cause permanent damage to eyes, burn skin, and eat holes in clothing. Always wear splash-proof safety goggles when working near the battery. Ifbattery acidis splashed in the eyes or on skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service,as this mayresult in hazardous spattering of battery acid.
NOTICE
Notice communicates installation, operation, or maintenance information that is important but not hazard related.
Safety decals affixed to the transfer switch in prominent places advise the operator or service technician of potentialhazards andhow toact safely. The decals are reproduced here to improve operator recognition. Replace missing or damaged decals.
TP-5660 11/98 Safety Precautions and Instructions I
W ARNING
Hazardous Voltage/ Electrical Shock
W ARNING
W ARNING
Explosion. Can cause severe injury or death. Relays in battery charger cause arcs or sparks.
Locate battery in a well-ventilated area. Isolate battery charger from explosive fumes.
Battery gases. Explosion can cause severe injury or death. Battery
gases can cause an explosion. Do not smokeor permit flameor spark tooccur near a battery at any time, particularly when it is charging. Avoid touching terminals with tools, etc., to prevent burns and sparks that could cause an explosion. Remove wristwatch, rings, and any other jewelry before handling battery. Never connect negative (--) battery cable to positive (+) connection terminal of starter solenoid. Donot test battery condition by shorting terminals together. Sparks could ignite battery gases or fuel vapors. Ventilate any compartment containing batteries to prevent accumulation of explosive gases. To avoid sparks, do not disturb battery charger connections while batteryis charging. Alwaysturnbattery charger off before disconnecting battery connections. Remove negative (--) lead first when disconnecting battery. Reconnect negative (--) lead last when reconnecting battery.
Hazardous voltage. Can cause severe injury or death.
Disconnect all power sources before opening enclosure.
(under 600 Volt)
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening enclosure.
(600 Volt and above)
W ARNING
Hazardous voltage. Can cause severe injury or death.
Disconnect power sources before servicing. Install barrier after adjustments, maintenance, or service.
(under 600 Volt)
DANGER
Hazardous voltage. Can cause severe injury or death.
Operate generator set only with all guards and electrical enclosures in place.
Grounding the transfer switch. Hazardous voltage can cause severe injury or death. Electrocution
is possible whenever electricity is present. Open main circuit breakers of all power sources before servicing equipment. Configure the installation to electrically ground the transfer switch and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground, as the chance of electrocution increases under such conditions.
Installing battery charger. Hazardous voltage can cause severe injury or death. Electrical
shock may occur if battery charger is not electrically grounded. Connect battery charger enclosure to ground of a permanent wiring system. As an alternative, install an equipment grounding conductor with circuit conductors and connect to equipment grounding terminal or lead on battery charger. Perform battery charger installation as prescribed in equipment manual. Install battery charger in compliance with local codes and ordinances.
Movingrotor.
Hazardous voltage. Will cause severe injury or death.
Disconnect power sources before servicing. Install barrier after adjustments, maintenance, or servicing.
(600 Volt and above)
Connecting battery and battery charger. Hazardous voltage can cause severe injury or death.
Reconnect battery correctly to avoid electrical shock and damage to battery charger and battery(ies). Have a qualified electrician install battery(ies).
TP-5660 11/98II Safety Precautions and Instructions
Installing accessories to transformer assembly. Hazardous voltage can cause severe injury or death. To prevent the possibility of
electrical shock, disconnect harness plug before installing any accessories involving connection to transformer assembly primary terminals 76, 77, 78, and 79. Terminals are at line voltage!
(Models with E33+, S340, S340+, 340, R340, or R33 controls only.)
Installing accessories to transformer assembly. Hazardous voltage can cause severe injury or death. To prevent the possibility of
electrical shock, disconnect harness plug before installing any accessories which will be connected to transformer assembly primary terminals on microprocessor logic models. Terminals are at line voltage!
Making line or auxiliary connections. Hazardous voltage can cause severe injury or death. To
prevent the possibility of electrical shock, deenergize the normal power source before making any line or auxiliary connections.
Servicing transfer switch controls and accessories within the enclosure. Hazardous voltage can cause severe injury or death.
Disconnect transfer switch controls at the inline connector to deenergize the circuit boards and logic circuitry but allow the transfer switch to continue to supply power to the load. Disconnect all power sources to any accessories mountedwithin the enclosure butwhich are not wired through the controls and deenergized by inline connector separation. Test circuits with a voltmeter to verify that they are unpowered before servicing.
Heavy Equipment
W ARNING
Unbalanced weight. Improper lift can cause severe injury or death and/or equipment damage.
Use adequate lifting capacity. Never leave transfer switch standing upright unless it is securely bolted in place or stabilized.
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can
cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove wristwatch, rings, and jewelry before servicing equipment.
Servicing the transfer switch. Hazardous voltage can cause severeinjuryor death. Deenergizeall
power sources before servicing. Open main circuit breakers of all power sources to the transfer switch and disable all generator sets as follows:
1) Move all generator set master controller switches to the OFF position.
2) Disconnect power to all battery chargers. 3) Disconnect all battery cables, negative (--) leads first. Reconnectnegative(--)leadslastwhen reconnecting battery cables after servicing. Follow these precautions to prevent starting of generator sets by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
TP-5660 11/98 Safety Precautions and Instructions III
Moving Parts
W ARNING
Hazardous voltage. Can cause severe injury or death.
Operate generator set only with all guards and electrical enclosures in place.
Movingrotor.
Notice
NOTICE
Hardware damage! Transfer switch
may use both American Standard and metric hardware. Use the correct size tools to prevent rounding of bolt heads and nuts.
NOTICE
When replacing hardware, do not substitute with inferior grade hardware. Screws and nuts are
available in different hardness ratings. American Standard hardware uses a seriesofmarkingsand metric hardware uses a numeric system to indicate hardness. Check markings on bolt head and nuts for identification.
NOTICE
Improper operator handle usage!
Use the manual operator handle provided on the transfer switch for maintenance purposes only. Return the transfer switch to the normal position. Remove manual operator handle, if used, and store it on the transfer switch in the place provided when service is completed.
NOTICE
Foreign material contamination!
Cover transfer switch during installation to keep dirt, grit, metal drill chips, etc., out of components. Cover solenoid mechanism during installation. After installation, use manual operating handle to position contactor to ensure that it operates freely. Do not use a screwdriver to force contactor mechanism.
NOTICE
Electrostatic discharge damage!
Electrostatic discharge (ESD) damages electronic circuit boards. Prevent electrostatic discharge damage by wearing an approved grounding wrist strap when handling electronic circuit boards or integrated circuits. An approved grounding wrist strap provides a high resistance (about 1 megohm), not a direct short, to ground.
TP-5660 11/98IV Safety Precautions and Instructions
Introduction
This manual provides operation and installation instructions for Kohler Model ZCS automatic transfer switchesthatusea40-to3000-amperecontactor asthe power switching device.
All information in this publication represents data availableattimeofprint. KohlerCo.reservestherightto change this literature and the products represented without incurring obligation.
Read through this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury. Read and follow the Safety Precautions and Instructions section at the beginning of this manual. Keep this manual with equipment for future reference.
Equipment service requirements are minimal but are veryimportantto safeand efficientoperation;therefore, inspect parts often and perform required service at the prescribed intervals. An authorized service distributor or dealer (authorized service center) should perform required service to keep equipment in top condition.
List of Related Materials
This manual covers operation and installation information for the transfer switch’s power switching device. Decode the transfer switch part number model codefrom the transfer switch nameplateand verifythat the transfer switch’s power switching device matches that what is shown on the front cover of this manual before proceeding with operation or installation.
a separate manual. The following table lists the available electrical controls and the related operation and installation manual part numbers.
Operation/
Installation
Electrical Controls
E33+ (Solid State) TP-5662 S340+ (Solid State) TP-5663 M340+ (Microprocessor) TP-5664
Manual
Separate manuals cover service and parts information for transfer switch power switching devices and electricalcontrols. Thefollowingtableliststheavailable manuals and the related manual part numbers.
Service/Parts
Power Switching Device
ZCS/ZCB (Contactor) TP-5668
Electrical Controls
E33+ (Solid State) TP-5670 S340+ (Solid State) TP-5671 M340+ (Microprocessor) TP-5672
Manual
Service/Parts
Manual
Transfer switches with microprocessor electrical controls and communication accessories can be monitoredand controlledwith a personalcomputer and software. Thefollowingtableliststheavailablemanuals and part numbers.
A separate operation and installation manual that covers information specific to the transfer switch’s electricalcontrols(logiccontroller)completesoperation and installation instructions for the transfer switch.
Three types of electrical controls are available on the
Communications Item
Remote Monitoring and Control Communications (Monitor) Software
Communications Kits TT-847
Operation/
Installation
Manual
TP-5823
ModelZCS transfer switch, and each typeis coveredin
TP-5660 11/98 Introduction i
Service Assistance
TransferSwitchIdentificationNumbers
Service Information
For sales, service, or other information about a Kohler Generator Division product, contact a local authorized distributor or dealer first.
To locate a local authorized distributor or dealer D Look on the product or the information includedwith
the product
D Consult the Yellow Pages under the heading
Generators—Electric
D Visit the Kohler Generator Division Web site at
www.kohlergenerators.com
D Call1-800-544-2444(insidetheU.S.A.andCanada)
or 920-565-3381 (outside the U.S.A. and Canada)
Product Identification
To ensure the supply of correct parts and information, write the product identification numbers in the spaces below. Record the identification numbers immediately after unpacking the products so that the numbers are readily available for future reference. Record the field-installed kit numbers after installing the kit.
Record the product identification numbers from the transfer switch nameplate.
Part Number Serial Number
Accessory Number Accessory Description
TP-5660 11/98ii Introduction
Section 1. Specifications
1.1 Purpose
An automatic transfer switch (ATS) transfers critical electrical loads from a normal (preferred) source of electrical power to an emergency (standby) source when the normal source fails to maintain minimum voltage and/or frequency levels.
Upon normal source failure, the ATS signals the generator set to start. When the emergency source reaches a minimum voltage and/or frequency level, the ATS transfers the load from the normal source to the emergency source. The ATS continuously senses the normalsource and transfers the load backto the normal sourcewhenthe normalsourcereturns. Aftertransferof theloadback tothenormal source,theATSremovesthe generator set start signal, allowing the generator set to shut down.
1.2 Components
A typical transfer switch consists of functional units mounted in an enclosure with a hinged front door. See Figure 1-1. The power switching device connects the load to the normal or emergency sources of power. An inner panel mounted on theinside of the enclosure door containsthe electrical controls (logic controller) circuitry that monitors power sources, controls the power switching device, and signals the generator to start when needed. Enclosure door-mounted controls and indicators allow the operator to control the transfer switch operation mode and obtain system status information. A wire harness with inline connectors to facilitate component replacement and door removal connects the inner panel to the power switching device.
Controls and indicators on the transfer switch are determined by the logic controller and installed accessories. For details see the operation and installation manual for the logic controller specified by the part number model code on the transfer switch nameplate. See Sections 1.3 and 1.4 to determine the logic controller on the transfer switch. See List of Related Materials in the Introduction section in this manual.
2
1
6
1. Power switching device
2. Enclosure
3. Enclosure door
4. Inner panel electrical controls (logic controller)
5. Controls and indicators (mounted on enclosure door)
6. Neutral lug
3
4
5
TS-001
Figure 1-1. Typical Transfer Switch Components
The power switching device transfers power from the normal or emergency power source to the load. See Figure 1-2. The controller electrically actuates the power switching device to select a power source, and theswitch mechanically latches inthe selected position. The switch also includes a provision for manual mechanical operation in emergency nonpowered conditions. Within the switch are two sets of multipole contacts. One set of contacts selects power from the normal source and the other set selects power from the emergency source. The two sets of contacts are mechanically interlocked within the switch, ensuring that only one set of contacts is closed simultaneously. Mechanical interlocking ensures load servicing without cross-coupling of the power sources.
Normal (Utility)
Power Switching Device
Power
Automatic Transfer Switch
To Load
Emergency (Generator) Power
Interface
Generator
Start Generator
Logic
Controller
TS-002
Figure 1-2. Typical Transfer Switch Block Diagram
TP-5660 11/98 Specifications 1
1.3 Nameplate
A nameplate providing characteristic and rating information that affects operation, installation, and servicing is attached to the inside of the transfer switch enclosure door. See Figure 1-3.
Copy the part number into the blank spaces provided in Figure 1-4 and then use Figure 1-4 to interpret the part number.
Copy the part number, factory-installed accessory numbers,and serialnumber fromthe nameplateinto the spaces provided in the Service Assistance section in this manual for use when requesting service or parts.
1
AUTOMATICTRANSFER SWITCH
PARTNO.
3
SERIAL NO. VOLTS PHASE HERTZ
1. Location for part number used to identify type of ATS.
2. Location for factory-installed accessory numbers.
3. Location for the ATSserial number.
AMPS WIRES POLES
2
TS-003
Figure 1-3. Typical Transfer Switch Nameplate
TP-5660 11/982 Specifications
1.4 Part Number Model Code
Use the diagram below to record and interpret the transfer switch part number model code.
Record the transfer switch part number in the boxes below. The transfer switch part number defines characteristics and ratings as explained in the accompanying chart.
Type of Switch Type of Logic Voltage& Frequency
Number of
Poles
Number of
Wires
Type of
Enclosure Amperage Rating Code
Kohler Part Number Key
This chart explains the Kohler transfer switch part numbering code system. The sample part number shown is for a standard contactor power switch with M340+ logic rated at 600 volts, 60 hertz, 3-phase, 3-pole, and 4 wires in a NEMA Type 1 enclosure with a contactor rating of 1000 amperes.
Classification of Power Switch
Z: Power Switch
Type of Power Switch
C: Contactor
Type of Switch
S: Standard
Type of Electrical Controls (Logic Controller)
1: S340+ 2: E33+ 3: S340+ with Programmed Transition 4: E33+ with Programmed Transition 5: M340+ 6: M340+ with Programmed Transition
Voltage Code
60: 600 Volt, 60 Hz 66: 480 Volt, 60 Hz 62: 120 Volt, 60 Hz 68: 208 Volt, 60 Hz 63: 220 Volt, 50 Hz 71: 380 Volt, 50/60 Hz 64: 240 Volt, 60 Hz
SAMPLE PART NUMBER
ZCS-560341-1000
Number of Poles
2: 2 Pole, 1 Phase 3: 3 Pole, 3 Phase
Number of Wires
3: 3 Wire 4: 4 Wire
Enclosure
0 = Open 1 = NEMA Type 1 2 = NEMA Type 12 3 = NEMA Type 3R
Amperes
Numbers Indicate Ampere Rating of Switch
4: 3 Pole, 1 Phase 6: 4 Pole, Fully Rated
Figure 1-4. Transfer Switch Model Designations
TP-5660 11/98 Specifications 3
1.5 Standard Features
UL100
8
Max.FuseSiz
e
SwitchRatin
g
Max.FuseSiz
e
The standard features listed here are for the ZCS contactor power switching device. Refer to the logic controller operation and installation manual for controller specifications. See List of Related Materials in the Introduction section in this manual.
D Provided as a complete automatic transfer switch
D Two-pole, three-pole and four-pole D Four-pole—fully rated D Can be operated manually when unpowered D Twonormallyopen (N.O.) and two normallyclosed
(N.C.) main shaft auxiliary contacts
D Withstand and closing current ratings as shown
below. with E33+ (solid state logic), S340+ (solid state logic), or M340+ (microprocessor logic) controller
1.6 Ratings
in various enclosures
D Meets UL and CSA standards D Voltage ratings up to 600 vac D Amperage ratings for Programmed Transition
Switches from 40 to 3000 amperes
D Amperage ratings for Standard Switches from
600 to 3000 amperes
D Switching device electrically and mechanically
interlocked
Withstand and Closing Current Ratings per UL 1008 and CSA *
When Used With Any Current-limiting Fuse
Maximum Current (amps) Maximum Current (amps)
(amps)
Programmed Transition Models:
40 50 200,000 150,000 22,000 18,000
80 100 200,000 150,000 22,000 18,000 100 125 200,000 150,000 22,000 18,000 150 200 200,000 150,000 30,000 25,000 225 300 200,000 150,000 30,000 25,000 260 350 200,000 150,000 30,000 25,000 400 600 200,000 150,000 35,000 30,000
Standard and Programmed Transition Models:
600 750 200,000 150,000 50,000 42,000 800 1000 200,000 150,000 50,000 42,000
1000 1250 200,000 150,000 50,000 42,000 1200 1500 200,000 150,000 50,000 42,000 1600 2500 200,000 150,000 100,000 85,000 2000 2500 200,000 150,000 100,000 85,000 2500 4000 200,000 150,000 100,000 85,000 3000 4000 200,000 150,000 100,000 85,000
* UL1008 listed at 480 vac and CSA listed at 600 vac.
(amps)
@ 480 VAC @ 600 VAC @ 480 VAC @ 600 VAC
The following tables provide information on contactor withstand and closing current ratings (WCR). Figure 1-5 provides WCR when used with any current-limiting fuse or any overcurrent protective device. Figure 1-6 and Figure 1-7 provides WCR when coordinated with specific manufacturer’s circuit breakers or fuse types. Figure 1-6 has ratings for 480 V maximum and apply to both UL and CSA listings. Figure 1-7 has ratings for 600 V maximum and apply to a CSA listing only.
When Used With Any Overcurrent
Protective Device (3 cycles)
Figure 1-5. Withstand and Closing Current Ratings
TP-5660 11/984 Specifications
Switch
40,80,J,RK5
,
40,80
,
22,000Any,150AmperesMaximum150200,000J,RK5,
200
150
,
and26
0
and26
0
RK1
G
E
MerlinGerin
40050,000IT
E
200,000RK1600
SquareD
RK1
RK1
MerlinGerin
800,1000,
and
120
0
85,000ITE
200,000L3000120
0
SquareD
Rating (amps)
WCR, RMS
Symmetrical
Amperes
Molded-case Circuit Breakers Fuses
Manufacturer Type or Class
Maximum
Size
(amps)
WCR, RMS
Symmetrical
Amperes
Type or
Class
Maximum
Size
(amps)
and 100
ABB JHB
GE TB4, TJL, TLB4, THLC4
Merlin Gerin CJ400L, CK400H
225,
400 50,000 ITE
600 65,000
800,
1600 and 2000
2500 and 3000
42,000
100,000 Any, 4000 Ampere Maximum 4000 200,000 L 2500
100,000 Any, 4000 Ampere Maximum 4000 200,000 L 4000
ITE
Square D IL
Westinghouse
Westinghouse
GE
ITE
Square D NC, SE
Westinghouse NB TRI-PAC, DSL206
GE TP, THP, TC, THC 1600
Westinghouse PC, PCC, PB TRI-PAC 1600
CJD6, SCJD6, HJD6, SHJD6
HKD, KDC, LCL, LA TRI-PAC
TB4, TLB4, THLC4 400 TB6, TJL 600 TB8, TKH, TKL, TP, THP,
TC, THC CJ400L, CK400H 400 CK800H 600 CJD6, SCJD6, HJD6,
SHJD6 CLD6, SCLD6, HLD6,
SHLD6, HHJD6, HHLD6 MD6, MXD6, SMD6,
CMD6, SCMD6, HMD6, HMXD6, SHMD6
IL 400 MH, ME, SE 600 HKD, KDC, LCL,
LA TRI-PAC HLD, LDC 600 HMC, NB TRI-PAC 800 TB8, TKL, TP, THP, TC,
THC CMD6, SCMD6, HMD6,
HMXD6, SHMD6
CK 1000L 1200 CM 1600 1600 CND6, SCND6 1200 CPD6 1600 NC, NE 1200 PH, PE, SE 1600
400 200,000
800
400
600
800
400
800 200,000
200,000
RK1
J, RK5,
RK1
J, RK5,
L, J, RK5,
400
600
750
Figure 1-6. Withstand and Closing Current Ratings (WCR) With Coordinated Circuit Breakers or Fuses,
480 V Maximum, UL and CSA Listings
TP-5660 11/98 Specifications 5
Switch
40,80,J,RK5
,
40,80
,
18,000Any,150AmperesMaximum150150,000J,RK5,
200
G
E
150
,
and26
0
400
RK1
400
G
E
MerlinGerin
MerlinGerin
J,RK5
,
ITE
Westinghous
e
60050,000
800150,00
0
750
60050,000
800150,000RK175
0
1000,
1000,
65,00
0
150,000L3000and
ITE
SquareD
Rating (amps)
WCR, RMS
Symmetrical
Amperes
Molded-case Circuit Breakers Fuses
Manufacturer Type or Class
Maximum
Size
(amps)
WCR, RMS
Symmetrical
Amperes
Type or
Class
Maximum
Size
(amps)
and 100
225,
400 42,000
800, and
1200
1600 and 2000
2500 and 3000
35,000
85,000 Any, 4000 Ampere Maximum 4000 150,000 L 2500
85,000 Any, 4000 Ampere Maximum 4000 150,000 L 4000
ABB JHB, MHB 400
TB4, SGH4, TJJ 400 TB6, SGH6 600
Merlin Gerin
ITE CJ, SKM
Westinghouse
GE
ITE CP, CN
Square D SE, SES, SEH, MA, MH
Westinghouse NB TRI-PAC, DSL206
GE
Merlin Gerin
Westinghouse PC, PCC, PB TRI-PAC 1600
CK400H, CK400L, CK400N, CK400NN
HKD, KDC, HLD, LA TRI-PAC
SGL4, SGP4 400 SGL6, SGP6 600 CJ400L, SK400N,
SK400H SK800N 600 CJD6, SCJD6, SHP,
SHK, CED6, CFD6 CLD6, SCLD6, HLD6,
SHLD6 HKD, KDC, LA TRI-PAC 400 NB TRI-PAC 800 TB8, TKL, TP, THP, TC,
THC, TKH, TBC8
TKMA, THKMA, TPMM, THMM, TPSS, TJS, TJSS, TKS, THKS, THKSS, THSS
MP16H1, MP16H2, MC16H1
CND6 1200 CPD6, HPD6, HRD6 1600 NC 1200 PHF, PCF 1600
400
400 600
1600
150,000
150,000
RK1
J, RK5,
RK1
RK1
L, J, RK5,
400
600
Figure 1-7. Withstand and Closing Current Ratings (WCR) With Coordinated Circuit Breakers or Fuses,
600 V Maximum, CSA Listings
TP-5660 11/986 Specifications
1.7 Application Data
Siz
e
Siz
e
See Figure 1-8 for application data including the range of wire sizes for the transfer switch’s power terminals.
AL/CU UL-listed Solderless Screw-type Terminals for External Power Connections
Switch
(amps)
40 1 #14 AWG to #2 AWG 800 4 #2 AWG to 600 MCM
80--100 1 #14 AWG to 1/0 AWG 1000 4 #2 AWG to 600 MCM
150 1 #8 AWG to 3/0 AWG 1200 4 #2 AWG to 600 MCM 225 1 #6 AWG to 250 MCM 1600 Bus Bar Connection 260 1 #6 AWG to 350 MCM 2000 Bus Bar Connection 400 1 #4 AWG to 600 MCM 2500 Bus Bar Connection 600 2 #2 AWG to 600 MCM 3000 Bus Bar Connection
Normal, Emergency, and Load Terminals
Cables per Pole Range of Wire Sizes
Figure 1-8. Application Data
Switch
(amps)
Normal, Emergency, and Load Terminals
Cables per Pole Range of Wire Sizes
TP-5660 11/98 Specifications 7
Notes
TP-5660 11/988 Specifications
Section 2. Operation
W ARNING
Hazardous voltage. Can cause severe injury or death.
Disconnect all power sources before opening enclosure.
(under 600 Volt)
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening enclosure.
(600 Volt and above)
Have preventive maintenance performed on the transferswitch at regularintervals afterinstallation. See Section 4 for preventive maintenance.
Contact an authorized service center to inspect and service the transfer switch when any wear, damage, deterioration, or malfunction of the transfer switch or its components is evident or suspected; DO NOT
ENERGIZE THE SWITCH.
2.1 Startup
Use this section when power sources have been disconnected to the transfer switch for an extended period after maintenance or service of the standby system, NOT FOR INITIAL STARTUP.
For initial startup, follow the instructions in the installation section of the operation and installation manual for the logic controller and Section 6—Installation in this manual.
Follow the following steps to power up the transfer switch and prepare it for automatic operation.
Powerup Procedure
1. Move the generator set master switch to the OFF position to prevent the generator set from starting.
2. Ensure that BOTH the normal and emergency power sources are disconnected by opening upstream circuit breakers or switches to the transfer switch.
3. Open the enclosure and check that the wire harnesses for the power switching device and the controller are plugged together at the inline disconnect plugP1. See thedrawings in Section 5 to locate the disconnect plug on the contactor.
4. Follow the manual operation procedure to prepare the transfer switch for automatic operation. See Section 2.3.
5. Close and lock the transfer switch enclosure door.
6. Prepare the generator set that provides standby power for operation. Check the oil level, coolant level, fuel supply, batteries, and items specified by the generator set installation or operation checklist or manual.
7. Move the generator set masterswitch to the AUTO position. The generator set should start.
8. When loads can be safely energized, reapply power sources to the transfer switch by closing circuit breakers or switches.
NOTE
Wheninitially applyingpower tothetransfer switch, the engine start contacts remain closed signalling the generator to run until the ATS’s Time Delay Engine Cooldown (TDEC), if equipped, ends.
9. Perform an automatic operation test. See the logic controller operation and installation manual.
Refer to the logic controller operation and installation manual for other startup and setup procedures.
2.2 Automatic Operation
The logic controller installed in the unit provides automatic operation. Refer to the logic controller operation and installation manual for automatic operation details and procedures. See List of Related Materials in the Introduction section in this manual.
TP-5660 11/98 Operation 9
The transfer switch logic controller circuitry, programming, or accessories determine when a power source is acceptable, has failed, or has been restored and operates accordingly. Failure of a power source occurswhen the the voltage and/or frequency on oneor more phases fall below preset limits. A power source is acceptable when the voltage and/or frequency on all monitored phases rise above preset levels. A power source is restored when it becomes acceptable after failing. Typical ATS operation is divided into two sequences.
D Failure of the normal power source and the
resulting transfer to the emergency source or Emergency.
D Restorationof the normalpower sourceandthe
resulting transfer back to the normal source or Normal.
The following sections briefly explain these sequences of operation. Installed controller accessories can change the sequence of operation. See the logic controller operation and installation manual for specifications on time delays, voltage and frequency limits, control adjustments, and accessory information.
2.2.2 Restoration of Normal Power
After normal power source restoration, the controller starts a time delay called Time Delay Emergency to Normal(TDEN). Ifthe normal power source fails before TDEN ends, the time delay resets. TDEN ensures normal power source stabilization before load reconnection.
When the controller determines that the normal power source has maintained an acceptable level and TDEN ends, the controller signals the power switching device to reconnect the load to the normal source.
Afterload transferthe switchmechanically latchesin the normal position and the controller starts a time delay called Time Delay Engine Cooldown (TDEC), if equipped. TDECallowsthe engineand generatorto run unloadedand cooldownbefore shutdown. WhenTDEC expires the controller signals the generator set to shut down.
The generator set controller may allow the generator to run for an additional cooldown period after the transfer switch signals a shutdown. Consult the generator set operation manual for more information.
2.2.1 Failure of Normal Power
When the normal power source fails, the controller starts a time delay called Time Delay Engine Start (TDES). TDES prevents unnecessary generator startup during short normal power interruptions. If the normalpower source is restoredbefore TDES ends, the controller resets the time delay. If the normal power failure persists and TDES ends, the controller issues a signal to start the standby (emergency) generator to produce the emergency power source.
After signalling the generator to start, the controller monitors the emergency power source. When the controller determines that the emergency (generator) power source is acceptable it starts a time delay called Time Delay Normal to Emergency (TDNE). TDNE allows emergency power source stabilization before loadconnection and prevents nuisance transfersduring short power interruptions. When TDNE ends the controller signals the transfer switch toconnect the load to the emergency source.
Afterload transferthe switchmechanically latchesin the emergency position, supplying emergency source power to the load until normal power source restoration and stabilization.
TP-5660 11/9810 Operation
2.3 Manual Operation
To test or troubleshoot the transfer switch, or when the controller fails in an emergency situation, manually operatethe power switching deviceas described below.
W ARNING
W ARNING
Accidental starting. Can cause severe injury or death.
Disconnect battery cables before working on generator set. (Remove negative (--) lead first when disconnecting battery. Reconnect negative (--) lead last when reconnecting battery.)
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator set as follows: 1) Move the generator set master switch to the OFF position. 2) Disconnect power to the battery charger.
3) Remove battery cables, negative (--)lead first. Reconnect negative(--)lead last whenreconnecting battery. Follow these precautions to prevent starting of generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
W ARNING
Hazardous voltage. Can cause severe injury or death.
Disconnect all power sources before opening enclosure.
(under 600 Volt)
DANGER
Hazardous voltage. Can cause severe injury or death.
Disconnect power sources before servicing. Install barrier after adjustments, maintenance, or service.
(under 600 Volt)
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect power sources before servicing. Install barrier after adjustments, maintenance, or servicing.
(600 Volt and above)
Servicing the transfer switch. Hazardous voltage can cause severe injury or death. Deenergizeall powersources
before servicing. Open main circuit breakers of all power sourcesto the transferswitch and disable all generatorsets as follows: 1) Move all generator set master controller switches to the OFF position. 2) Disconnect power to all battery chargers. 3) Disconnect all battery cables, negative (--)leads first. Reconnect negative (--) leads last when reconnecting battery cables after servicing. Follow these precautions to prevent starting of generator sets by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
NOTICE
Improper operator handle usage! Use the manual operator
handle provided on the transfer switch for maintenance purposes only. Return the transfer switch to the normal position. Remove manualoperatorhandle, if used,andstore it on the transfer switch in the place provided when service is completed.
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening enclosure.
(600 Volt and above)
A contactor in normal and serviceable condition transfers smoothly without binding when operated manually. Do notplace the transfer switchinto service if the contactor does not manually operate smoothly without binding; contact an authorized service center to
NOTE
service the contactor.
TP-5660 11/98 Operation 11
2.3.1 Programmed Transition Switch, 40--260 Amps
Manual Operation Procedure
1. Prevent the generator set, which provides the emergency power source to the transfer switch, from starting by moving the generator set master switch to the OFF position; disconnecting power to the generator engine start battery charger, if installed; and disconnecting all generator engine start batteries, negative (--) leads first.
2. Disconnect BOTH the normal and emergency power sources by opening upstream circuit breakers or switches to the transfer switch.
3. Open the transfer switch enclosure door.
4. Set the disconnect switch (DS) to the INHIBIT position to preventthe controller fromenergizing the solenoid(s). See Figure 2-1.
5. Attach the manual operating handle to the switch lever.
6. If the handleis notin the middle(off) position,move thehandle upor downtobring itinto themiddle(off) position. The switch should operate smoothly without binding. Both normal and emergency sources are disconnected from the load in the middle (off) position.
7. Locate the mid-position manual release handle on the left side of the switch. See Figure 2-1.
8. Pull and hold the mid-position manual release handle to the left. This releases the mechanism that allows manual switching to the normal or emergency source from the off position. Move the handle up to the normal position to manually connect the load to the normal source or down to the emergency position to manually connect the load to the emergency source. The switch should operate smoothly in both directions without binding.
9. Manually connect the load to the normal source for automatic operation.
1
4
1. Mid-position manual release handle
2. Switch lever, middle (off) position shown
3. Disconnect switch, INHIBIT position shown
4. Manual operating handle, typical
NORMAL
LOCK
LOCK
EMERGENCY
AUTO INHIBIT
Figure 2-1. Manual Operation, Programmed
Transition Switch 40--260Amps
2
3
5660201
10. Remove and return the manual operator handle to the holder provided.
11. Move the disconnect switch (DS) to the AUTO position for automatic operation.
12. Close and lock the transfer switch enclosure door.
13. Reconnect power supplies to the transfer switch.
NOTE
Wheninitially applyingpower tothetransfer switch, the engine start contacts remain closed signalling the generator to run until the ATS’s Time Delay Engine Cooldown (TDEC), if equipped, ends.
14. Reconnect generator engine start battery cables, negative (--) leads last; reconnect power to the generator engine start battery charger, if installed; and move the generator set master switch to the AUTO (automatic) position. The generator may start and run for a while (see NOTE above).
TP-5660 11/9812 Operation
2.3.2 Programmed Transition Switch, 400--3000 Amps
Manual Operation Procedure
1. Prevent the generator set, which provides the emergency power source to the transfer switch, from starting by moving the generator set master switch to the OFF position; disconnecting power to the generator engine start battery charger, if installed; and disconnecting all generator engine start batteries, negative (--) leads first.
2. Disconnect BOTH the normal and emergency power sources by opening upstream circuit breakers or switches to the transfer switch.
3. Open the transfer switch enclosure door.
4. Set the disconnect switch (DS) to the INHIBIT position to preventthe controller fromenergizing the solenoid(s). See Figure 2-2.
1
NORMAL
LOCK
LOCK
5. Attach the manual operator handle to the normal switchleverand moveit uptothe normalposition to manually connect the load to the normal source andmove itdown todisconnect. Theswitchshould operate smoothly in both directions without binding.
6. Attach the manual operator handle to the emergency switch lever. Move the handle down to the emergency position to manually connect the load to the emergency source and move it up to disconnect. Theswitchshould operatesmoothly in both directions without binding.
NOTE
A mechanical interlock prevents simultaneous emergency and normal source connection to the load. Both sources can be manually disconnected from the load simultaneously.
7. Manually connect the load to the normal source for automatic operation.
8. Remove and return the manual operator handle to the holder provided.
9. Move the disconnect switch (DS) to the AUTO position for automatic operation.
10. Close and lock the transfer switch enclosure door.
11. Reconnect power supplies to the transfer switch.
2
LOCK
4
1. Normal switch lever, normal source shown connected to load
2. Emergency switch lever, emergency source shown disconnected from load
3. Disconnect switch, INHIBIT position shown
4. Manual operating handle, typical
LOCK
EMERGENCY
AUTO
INHIBIT
3
5660202
Figure 2-2. Manual Operation, Programmed
Transition Switch 400--3000Amps
NOTE
Wheninitially applyingpower tothetransfer switch, the engine start contacts remain closed signalling the generator to run until the ATS’s Time Delay Engine Cooldown (TDEC), if equipped, ends.
12. Reconnect generator engine start battery cables, negative (--) leads last; reconnect power to the generator engine start battery charger, if installed; and move the generator set master switch to the AUTO (automatic) position. The generator may start and run for a while (see NOTE above).
TP-5660 11/98 Operation 13
2.3.3 Standard Switch, 800--3000 Amps
Manual Operation Procedure
1. Prevent the generator set, which provides the emergency power source to the transfer switch, from starting by moving the generator set master switch to the OFF position; disconnecting power to the generator engine start battery charger, if installed; and disconnecting all generator engine start batteries, negative (--) leads first.
5. Attach the manual operating handle to the switch lever.
6. Move the handle up to the normal position to connect the load to the normal source or down to the emergency position to connect the load to the emergency source. Switch should operate smoothly between both positions without binding.
7. Manually connect the load to the normal source for automatic operation.
2. Disconnect BOTH the normal and emergency power sources by opening upstream circuit breakers or switches to the transfer switch.
3. Open the transfer switch enclosure door.
4. Set the disconnect switch (DS) to the INHIBIT position to preventthe controller fromenergizing the solenoid(s). See Figure 2-3.
1
NORMAL
LOCK
LOCK
EMERGENCY
8. Remove and return the manual operator handle to the holder provided.
9. Move the disconnect switch (DS) to the AUTO position for automatic operation.
10. Close and lock the transfer switch enclosure door.
11. Reconnect power supplies to the transfer switch.
NOTE
Wheninitially applyingpower tothetransfer switch, the engine start contacts remain closed signalling the generator to run until the ATS’s Time Delay Engine Cooldown (TDEC), if equipped, ends.
12. Reconnect generator engine start battery cables, negative (--) leads last; reconnect power to the generator engine start battery charger, if installed; and move the generator set master switch to the AUTO (automatic) position. The generator may start and run for a while (see NOTE above).
3
AUTO INHIBIT
1. Switch lever, normal source shown connected to load
2. Disconnect switch, INHIBIT position shown
3. Manual operating handle, typical
2
5660203
Figure 2-3. Manual Operation, Standard Switch
600--3000 Amps
TP-5660 11/9814 Operation
Section 3. Accessories
3.1 Programmed Transition
NOTE
ATSs using microprocessor logic control do not use this section. The programmed transition function takes place within the microprocessor and no time relays are required. See TP-5664, operation and installation manual for the M340+ controller, for operational details. Relays K3 and K4 on the interface board are replaced with a standard form C relay.
3.1.1 Description
The Programmed Transition accessory consists of two timing relays that plug into an interface circuit board. See Figure 3-1. If these relays are present, power transfers from normal to emergency or emergency to normalin threesteps: (1)the switch orcircuit breakerfor the previously connected power source opens, (2) a delay period, adjustable from 2 to 40 seconds, allows any residual voltage in the load circuit to decay, and (3) the switch or circuit breaker for the new power source closes.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator set as follows: 1) Move the generator set master switch to the OFF position. 2) Disconnect power to the battery charger.
3) Remove battery cables, negative (--)lead first. Reconnect negative(--)lead last whenreconnecting battery. Follow these precautions to prevent starting of generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
W ARNING
Hazardous voltage. Can cause severe injury or death.
Disconnect all power sources before opening enclosure.
(under 600 Volt)
DANGER
3.1.2 Adjustment
Two separate timing relays are used. One relay, K4 (TDOE), produces the time delay for the normal to emergencypower transfer.The other relay,K3(TDON), produces the time delay for the emergency to normal power transfer. Each relay has a separate adjustment. To make the adjustment, proceed as follows.
W ARNING
Accidental starting. Can cause severe injury or death.
Disconnect battery cables before working on generator set. (Remove negative (--) lead first when disconnecting battery. Reconnect negative (--) lead last when reconnecting battery.)
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening enclosure.
(600 Volt and above)
W ARNING
Hazardous voltage. Can cause severe injury or death.
Disconnect power sources before servicing. Install barrier after adjustments, maintenance, or service.
(under 600 Volt)
TP-5660 11/98 Accessories 15
DANGER
Hazardous voltage. Will cause severe injury or death.
NOTE
Wheninitially applyingpower tothetransfer switch, the engine start contacts remain closed signalling the generator to run until the ATS’s Time Delay Engine Cooldown (TDEC), if equipped, ends.
Disconnect power sources before servicing. Install barrier after adjustments, maintenance, or servicing.
(600 Volt and above)
Servicing the transfer switch. Hazardous voltage can cause severe injury or death. Deenergizeall powersources
before servicing. Open main circuit breakers of all power sourcesto the transferswitch and disable all generatorsets as follows: 1) Move all generator set master controller switches to the OFF position. 2) Disconnect power to all battery chargers. 3) Disconnect all battery cables, negative (--)leads first. Reconnect negative (--) leads last when reconnecting battery cables after servicing. Follow these precautions to prevent starting of generator sets by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
Time Delay Off Adjustment Procedure
1. Prevent the generator set, which provides the emergency power source to the transfer switch, from starting by moving the generator set master switch to the OFF position; disconnecting power to the generator engine start battery charger, if installed; and disconnecting all generator engine start batteries, negative (--) leads first.
2. Disconnect BOTH the normal and emergency power sources by opening upstream circuit breakers or switches to the transfer switch.
3. Open the transfer switch enclosure door.
8. Reconnect generator engine start battery cables, negative (--) leads last; reconnect power to the generator engine start battery charger, if installed; and move the generator set master switch to the AUTO (automatic) position. The generator may start and run for a while (see NOTE above).
9. Perform an automatic operation test to verify time delays. See the logic controller operation and installation manual. See List of Related Materials in the Introduction section in this manual.
1
1. K3 (TDON)
2. K4 (TDOE)
2
A-320687
Figure 3-1. Interface Circuit Board with
Time Delay Off Relays
4. Locate the appropriaterelay on the interfacecircuit board. See Figure 3-1.
5. Insert a screwdriver into the slot of the adjustment screw, which is visible through the cover of the relay, and turn the adjustment screw to the desired time delay period. Turnclockwise to increase time, counterclockwise to decrease time.
6. Close and lock the transfer switch enclosure door.
7. Reconnect power supplies to the transfer switch.
3.2 Other Accessories
With the exception of the Time Delay Off accessory, all other accessories for this automatic transfer switch are controller accessories. For controller accessory information and procedures, refer to the appropriate logic controller operation and installation manual. See List of Related Materials in the Introduction section in this manual.
TP-5660 11/9816 Accessories
Section 4. Scheduled Maintenance
Scheduled preventive maintenance ensures safe and reliable operation and extends the life of the transfer switch. Preventive maintenance includes periodic testing, cleaning, inspection, and replacement of worn or missing components.
A local authorized distributor or dealer (authorized service center) can provide complete preventive maintenance and services tokeep the transfer switch in top condition. Contact a local distributor or dealer for additional information. See the Service Assistance sectionin thismanual forhow to locatea localdistributor or dealer.
Read this entire section carefully before attempting any maintenance or service. Unless otherwise specified, have maintenance or service performed by an authorized service center that has trained and qualified personnel who follow all applicable codes and standards.
Keep records of all maintenance or service. Replace all barriers and close and lock the enclosure
dooraftermaintenance orservice andbeforereapplying power.
W ARNING
Accidental starting. Can cause severe injury or death.
Disconnect battery cables before working on generator set. (Remove negative (--) lead first when disconnecting battery. Reconnect negative (--) lead last when reconnecting battery.)
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator set as follows: 1) Move the generator set master switch to the OFF position. 2) Disconnect power to the battery charger.
3) Remove battery cables, negative (--)lead first. Reconnect negative(--)lead last whenreconnecting battery. Follow these precautions to prevent starting of generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
W ARNING
Hazardous voltage. Can cause severe injury or death.
Disconnect all power sources before opening enclosure.
(under 600 Volt)
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening enclosure.
(600 Volt and above)
TP-5660 11/98 Scheduled Maintenance 17
W ARNING
Hazardous voltage. Can cause severe injury or death.
Disconnect power sources before servicing. Install barrier after adjustments, maintenance, or service.
(under 600 Volt)
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect power sources before servicing. Install barrier after adjustments, maintenance, or servicing.
(600 Volt and above)
W ARNING
Servicing the transfer switch. Hazardous voltage can cause severe injury or death. Deenergizeall powersources
before servicing. Open main circuit breakers of all power sourcesto the transferswitch and disable all generatorsets as follows: 1) Move all generator set master controller switches to the OFF position. 2) Disconnect power to all battery chargers. 3) Disconnect all battery cables, negative (--)leads first. Reconnect negative (--) leads last when reconnecting battery cables after servicing. Follow these precautions to prevent starting of generator sets by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
Servicingtransfer switch controlsand accessories within the enclosure. Hazardous voltage can cause severe injury or death. Disconnect transfer switch controls at the
inline connector to deenergize the circuit boards and logic circuitry but allow the transfer switch to continue to supply power to the load. Disconnect all power sources to any accessories mounted within the enclosure but which are not wired through the controls and deenergized by inline connector separation. Test circuits with a voltmeter to verify that they are unpowered before servicing.
NOTICE
When replacing hardware, do not substitute with inferior grade hardware. Screws and nuts are available in different
hardness ratings. American Standard hardware uses a series of markings and metric hardware uses a numeric system to indicate hardness. Check markings on bolt head and nuts for identification.
Hazardous voltage. Can cause severe injury or death.
Operate generator set only with all guards and electrical enclosures in place.
Grounding the transfer switch. Hazardous voltage can cause severe injury or death. Electrocution is possible
whenever electricity is present. Open main circuit breakers of all power sources before servicing equipment. Configure the installation to electrically ground the transfer switch and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground, as the chance of electrocution increases under such conditions.
Short circuits. Hazardous voltage/current can cause severe injury or death. Shortcircuits can cause bodily injury
and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove wristwatch, rings, and jewelry before servicing equipment.
Movingrotor.
NOTICE
Hardware damage! Transferswitch may use both American
Standard and metric hardware. Use the correct size tools to prevent rounding of bolt heads and nuts.
NOTICE
Electrostatic discharge damage! Electrostatic discharge
(ESD) damages electronic circuit boards. Prevent electrostatic discharge damage by wearing an approved grounding wrist strap when handling electronic circuit boards or integrated circuits. An approved grounding wrist strap provides a high resistance (about 1 megohm), not a direct short, to ground.
4.1 Inspection and Service
Contact an authorized service center to inspect and service the transfer switch when any wear, damage, deterioration, or malfunction of the transfer switch or its components is evident or suspected.
TP-5660 11/9818 Scheduled Maintenance
4.1.1 General Inspection
External Inspection Keep the transfer switch clean
and in good condition by performing a weekly general external inspection of the transfer switch for any condition of vibration, leakage, noise, temperature, contamination, or deterioration. Remove accumulations of dirt, dust, and other contaminants from the transfer switch’s external components or enclosure with a vacuum cleaner or by wiping with adry cloth or brush. Do not use compressed air to clean the
switch because it can cause debris to lodge in the components and cause damage. Replace any worn,
missing, or broken external components with manufacturer-recommended replacement parts. Contact a local authorized service center for specific part information and part ordering. Tighten loose external hardware.
Internal Inspection Disconnect all power sources, open the transfer switch enclosure door, and inspect internal components monthly or when any condition noticedduring an externalinspection may haveaffected internal components.
Contact an authorized service center to inspect and service the transfer switch if any of the following conditions are found inside the transfer switch.
D Accumulations of dirt, dust, moisture, or other
contaminants
D Signs of corrosion D Worn, missing, or broken components D Loose hardware D Wire or cable insulation deterioration, cuts, or
abrasion
D Signs of overheating or loose connections:
discoloration of metal, melted plastic, or a burning odor
D Other evidence of wear, damage, deterioration, or
malfunction of the transfer switch or its components.
4.1.2 Other Inspections and Service
Have an authorized service center perform scheduled maintenance, service, and other maintenance that ensures the safe and reliable operation of the transfer switch including annual inspection and testing. See Section 4.3—Service Schedule for the recommended maintenance items and service intervals.
Have an authorized service center repair or replace components inside the transfer switch enclosure with manufacturer-recommended replacement parts.
4.2 Testing
4.2.1 Weekly Generator Set Exercise
Use a plant exerciser or manual test to start and run the generatorset under a load oncea week to maximizethe reliabilityof theemergency powersystem. See thelogic controller operation and installation manual for the procedure to exercise the generator set. See List of Related Materials in the Introduction section in this manual.
4.2.2 Monthly Automatic Control System Test
Test the transfer switch’s automatic control system monthly. See the logic controller operation and installationmanual forthe testprocedure. Verifythat the expected sequence of operations occurs as the switch transfers the load to the emergency source when a normal source failure occurs or is simulated. Observe the indicators (incandescent lamps and LEDs) included on the transfer switch to check their operation. When the switch transfers the load to the emergency source (after a time delay in the off position on programmed transition units), end the test and verify that the expectedsequence of operations occursas the transfer switchretransfers tothe availablenormalsource (aftera time delay in the off position on programmed transition units) and signals the generator set to shut down after a cooldown period.
If the power interruption required to perform an internal inspection is unacceptable in the application, have an internal inspection performed by an authorized service center.
TP-5660 11/98 Scheduled Maintenance 19
4.3 Service Schedule
D,R
abrasionandrepairorreplacewiringtoregainthe
D,R
vibration,leakage,noise,temperature,contamination
,
vibration,leakage,noise,temperature,contamination
,
Follow the service schedule below for the recommended service intervals. Have all service performed by an authorized service center except for activities limited to the items designated by an X.
System Component or Procedure
See
Section
Visually
Inspect
Check Change Clean Test
Frequency
ELECTRICAL SYSTEM
Check for signs of overheating or loose connections: discoloration of metal, melted plastic, or a burning odor
Check the contactor’s external operating mechanism for cleanliness and clean and relubricate if dirty *
Check wiring insulation for deterioration, cuts, or properties of the original wiring
Check the transfer switch’s main power switching mechanisms’ mechanical operation and integrity
Tighten control and power wiring connections to specifications
Check the transfer switch’s main power switching contacts’ condition and clean or replace the main contacts or replace the contactor assembly as necessary
Perform a thermal scan or millivolt drop test to check for high contact resistances on power circuits. Tighten connections, clean main contacts, adjust or replace main contacts or contactor assembly to eliminate high contact resistances
Test wire and cable insulation for electrical breakdown 4.1.2 D Every 3 Years Check calibration of voltage-sensing circuitry and
setpoints, and recalibrate circuitry as necessary
4.1.1 X X M
4.1.1 X
4.1.1 X
4.1.2 D D
4.1.2 D D D Y
4.1.2, 6.4, L D D Y
4.1.2 D D, R D Y
4.1.2 D D, R D D Y
4.1.2 D D Every 5 Years
D, R
(lubricant)
(wiring)
D M
M
Q
CONTROL SYSTEM
Exercise the generator set under load 4.2.1, L X W Test the transfer switch’s automatic control system 4.2.2, L X X M Test all indicators (incandescent lamps and LEDs) and
all remote control systems for operation
L D D D, R D Y
GENERAL EQUIPMENT CONDITION
Inspect the outside of the transfer switch for any condition of vibration, leakage, noise, temperature, contamination, or deterioration to keep the transfer switch clean and in good condition *
Check that all external hardware is in place, tightened, and not badly worn
Inspect the inside of transfer switch for any condition of or deterioration to keep the inside of the transfer switch
clean, dry, and in good condition * Check that all internal hardware is in place, tightened,
and not badly worn
* Service more frequently if operated in dusty or dirty areas.
See Section Read these sections carefully for additional information before attempting maintenance or service. Visually Inspect Examine these items visually. Check Requires physical contact with or movement of system components, or the use of nonvisual indications. Change May require replacement of components depending upon the severity of the problem. Clean Removeaccumulationsofdirtandcontaminantsfromexternaltransferswitch’scomponentsorenclosurewithavacuum
cleaner or by wiping with a dry cloth or brush. Do not use compressed air to clean the switch because it can cause debris to lodge in the components and cause damage.
Test May require tools, equipment, or training available only through an authorized service center. L See the transfer switch logic controller operation and installation manual for more information. D Have service performed by an authorized service center. X Operator action. R May require replacement of components.
4.1.1 X X W
4.1.1 X X R W
4.1.1 X X D M
4.1.2 D D D Y
4.1.2 X D M W=Weekly
M=Monthly Q=Quarterly S=SixMonths Y=Yearly
TP-5660 11/9820 Scheduled Maintenance
Section 5. Diagrams and Drawings
Diagram or Drawing Drawing Number Page Enclosure Dimensions Drawings
40--260 Amp, NEMA Type 1 and Type 3R ADV-6180- 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
400 Amp, NEMA Type 1 and Type 3R ADV-5934-C 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
600--1200 Amp, NEMA Type 1 and 3R ADV-5936A-F 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
600--1200 Amp, NEMA Type 12 ADV-5936B-B 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1600--2000 Amp, NEMA Type 1 ADV-5941-E 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1600--2000 Amp, NEMA Type 3R, E33+ and S340+ Logic ADV-5990-A 28. . . . . . . . . . . . . . . . . . .
1600--2000 Amp, NEMA Type 3R, M340+ Logic ADV-5989-A 29. . . . . . . . . . . . . . . . . . . . . . . . . . . .
2500--3000 Amp, NEMA Type 1 ADV-6242-B 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2500--3000 Amp, NEMA Type 3R, E33+ and S340+ Logic ADV-6241-A 31. . . . . . . . . . . . . . . . . . .
2500--3000 Amp, NEMA Type 3R, M340+ Logic ADV-6240-A 32. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Open Units Dimensions Drawings*
600--3000 Amp, M340+ Logic and Inner Panel Mounting ADV-5975A-B *. . . . . . . . . . . . . . . . . . . . .
600--3000 Amp, E33+ and S340+ Logic and Inner Panel Mounting ADV-5975B-B *. . . . . . . . . . . .
600 Amp ADV-5975C-A *. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
800--1200 Amp ADV-5975D-A *. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1600--2000 Amp ADV-5975E-B *. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2500--3000 Amp ADV-5975F-B *. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40--3000 Amp, M340+ Logic and Inner Panel Mtg., Prog. Transition ADV-5976A-C *. . . . . . . . . . .
40--3000 Amp, E33+ and S340+ Logic and Inner Panel Mtg., Prog. Transition ADV-5976B-C *. .
40--260 Amp, Programmed Transition ADV-5976C-A *. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
400 Amp, Programmed Transition ADV-5976D-B *. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
600 Amp, Programmed Transition ADV-5976E-A *.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
600--1200 Amp, Programmed Transition ADV-5976F-B *. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1600--2000 Amp, Programmed Transition ADV-5976G-B *. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2500--3000 Amp, Programmed Transition ADV-5976H-B *. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Schematic Diagrams, E33+ Logic
600--1200 Amp 321283-C 33.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1600--3000 Amp 321296-B 34.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
400 Amp with Programmed Transition 321295-C 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
600--3000 Amp with Programmed Transition 321285-B 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Schematic Diagrams, S340+ Logic
600--1200 Amp 321096-C 37.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1600--3000 Amp 321097-A 38.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40--260 Amp with Programmed Transition
120 VAC 346311- 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
208 VAC 353185- 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
240 and 480 VAC 353184- 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
380 and 416 VAC 353183- 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
600 VAC 353182- 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
400 Amp with Programmed Transition 321098-B 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
600--3000 Amp with Programmed Transition 321099-B 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Schematic Diagrams, M340+ Logic
600--1200 Amp 321287-C 46.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1600--3000 Amp 321301-B 47.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40--260 Amp with Programmed Transition
120 VAC 346312- 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
208 VAC 353174- 49. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
240 and 480 VAC 353175- 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
380 and 416 VAC 353176- 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
600 VAC 353177- 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
400 Amp with Programmed Transition 321300-B 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
600--3000 Amp with Programmed Transition 321286-A 54. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
* Contact your local distributor or dealer for a copy of these drawings. They are not included in this manual.
TP-5660 11/98 Diagrams and Drawings 21
Notes
TP-5660 11/9822 Diagrams and Drawings
ADV-6180-
Enclosure Dimensions Drawing, 40--260 Amp, NEMA Type 1 and Type 3R
TP-5660 11/98 Diagrams and Drawings 23
ADV-5934-C
Enclosure Dimensions Drawing, 400 Amp, NEMA Type 1 and Type 3R
24 Diagrams and Drawings TP-5660 11/98
ADV-5936A-F
Enclosure Dimensions Drawing, 600--1200 Amp, NEMA Type 1 and Type 3R
TP-5660 11/98 Diagrams and Drawings 25
ADV-5936B-B
Enclosure Dimensions Drawing, 600--1200 Amp, NEMA Type 12
26 Diagrams and Drawings TP-5660 11/98
ADV-5941-E
Enclosure Dimensions Drawing, 1600--2000 Amp, NEMA Type 1
TP-5660 11/98 Diagrams and Drawings 27
ADV-5990-A
Enclosure Dimensions Drawing, 1600--2000 Amp, NEMA Type 3R, E33+ and S340+ Logic
28 Diagrams and Drawings TP-5660 11/98
ADV-5989-A
Enclosure Dimensions Drawing, 1600--2000 Amp, NEMA Type 3R, M340+ Logic
TP-5660 11/98 Diagrams and Drawings 29
ADV-6242-B
Enclosure Dimensions Drawing, 2500--3000 Amp, NEMA Type 1
30 Diagrams and Drawings TP-5660 11/98
ADV-6241-A
Enclosure Dimensions Drawing, 2500--3000 Amp, NEMA Type 3R, E33+ and S340+ Logic
TP-5660 11/98 Diagrams and Drawings 31
ADV-6240-A
Enclosure Dimensions Drawing, 2500--3000 Amp, NEMA Type 3R, M340+ Logic
32 Diagrams and Drawings TP-5660 11/98
GD
AT
MECHANISM
P1--34
TB6
P3--2P3--1 P3--3
P15--1 P15--2 NA NB
NB
P15--4
P15--7
AB1
AB2
P3--4 P3--7 P3--8
FOR 3
NORMAL
SENSING
TRANSFORMER
CONNECTION
SEE ABOVE
OPTION DA--26
GD
AT INNER PANEL
P15--3
NC
OPTION
NT3NT2
DA--26
3 NORMAL
SENSING
P15--8
P15--9
BC2
BC1
P3--9
P3--1 P3--2 P3--3 P3--4 P3--7 P3--8 P3--9
REMOVE JUMPER ”JA” TO INSTALLTEST SWITCH, ENABLING TESTING OF N/AC VOLTAGESENSING CIRCUIT FROM DOOR.
FROM NORMAL
SOURCE
77
76
P1--36P1--35
76 77
NA
NC
NB
NA
NA
P1--23
NC
NB
P1--24
NA
8180797877767574
P1--22
NC
NA
NC
NB
NA
P2--9 P2--11
P2--1P2--4P2--7
SENSING
CIRCUIT
+12V
1 2 3 4 5 6 7 8 9 10 11 12
TB1
JA J J
61
60
TEST
NA
NB NC
T2 T3
T3
T2
24VAC
TO
12VDC
POWER SUPPLY
NC
NCNBNA
NT1
T2
T3
1
TO LOAD
2 2
NTS ETS
NTS
NTS
NTS
76 77
CN1
3
DS
K5K3
K4
ES3
P1--30
8
P1--25
7
P8--10
209
NR
4 7
ES4
P1--12 P1--11
8
NO
NC
7
P1--6
P8--11
16
57
REMOTE
3
ENGINE START
58
4
SN--2
1
206
TB2
P1--18
P8--9
P1--13
26
NC
P4--1
P9--1
CN1 CE1
2 1
52 53
10 4 5 6 3 2 1 7 8
K5 K2
NORMAL
POSITION
NR
LOGIC
P4--2
N1
N2
P9--2
CN CE
SN--1
D1
NR
10 11
NR
NORMAL
SWITCH
POSITION
NORMAL
P8--15
33
T1
63
EMERGENCY
G
EMERGENCY
W W
P4--3
P9--3
LNNN
LC
LB
LA
SWITCH
POSITION
R
SOURCESOURCE
AVAILABLEAVAILABLE
K1
E1
D2
ER
6762
1110
P1--3
P1--14
21
J1J2
K3
EMERGENCY
POSITION
P4--4
P9--4
NR
82
ETS
ETS
ETS
306
ERNR
693996
SE--1
NC
T6T2
91112
N/CA
VOLT R17 NORMAL C--AVOLTAGE SENSING
N/AB
VOLT R34 NORMALA--BVOLTAGE SENSING
N/BC
ER
LOGIC
E2
VOLT R37 NORMAL B--CVOLTAGESENSING
NOTE: JP1, JP2, JP3, JP4 JUMPER REMOVED FOR VOLTAGE SENSING ABOVE 240 VAC
5
P8--4
P8--2P1--7
330
LOGIC BOARD
JP2
JP3
JP4
3
CE1
35
307
ER
DS
P8--1
74
E FREQ.
R42 EMERGENCY FREQUENCY
AND VOLTAGE SENSING.
JP1
ENGINE
K4
START
R29
EC
P1--10
ECNC
EC EB EA
P2--12
E VOLT
LED1
EMERGENCY
VOLTAGE
EB
EA
P1--9
EA
P1--8
EC
EA
EA
EBEC
ET1
T6 T7
T7T6
T7
T6
P2--10
24VAC
TO
12VDC
POWER SUPPLY
K2
NOTE: JP5 JUMPER REMOVED
EN
EC
EB
EA
EA
P2--3
SENSING
CIRCUIT
NORMAL SOURCE AVAILABLE
EMERGENCY SOURCE
K1
AVAILABLE
SENSING.
FOR 3
FROM EMERGENCY SOURCE
EC
P2--6
JP5
SN--1
SN--2
SE--1
C
C
C
X
NC NO NC NO NC
X
X
X X
X
LEGEND
EMERGENCY TRANSFER OPERATOR (TRANSFER TO EMERGENCY)
CE
CE1 TRANSFER COIL CONTROL RELAY (TO EMERGENCY)
NORMALTRANSFER OPERATOR (TRANSFER TO NORMAL)
CN
TRANSFER COIL CONTROL RELAY (TO NORMAL)
CN1
DS DISCONNECT SWITCH ER
EMERGENCY RELAY
ET
EMERGENCY TRANSFORMER
ETS EMERGENCY CONTACTOR POWER CONTACTS
J
JUMPER K1 EMERGENCY SOURCE AVAILABLE RELAY K2 NORMALSOURCE AVAILABLERELAY K3 EMERGENCYPOSITION RELAY
K4 ENGINE START RELAY
K5 NORMALPOSITION RELAY
LED
LIGHT EMITTING DIODE
NORMAL CONTACTORAUX. SWITCHN
NR
NORMAL RELAY NT
NORMALTRANSFORMER
NTS
NORMAL CONTACTOR POWER CONTACTS
LIMITSWITCH (EMERGENCY)SE SN LIMITS SWITCH (NORMAL)
T SENSING TRANSFORMER
COMPONENT CONNECTION
###
CONNECTION NODE #
LEAD
P#--#
PLUG/SOCKET CONNECTOR
A4--1
TERMINAL BLOCK ON TRANSFER SWITCH
4
TERMINAL BLOCK ON LOGIC BOARD
EA
TERMINAL BLOCK PRIMARY OF TRANSFORMER
TERMINAL BLOCK SECONDARYOF TRANSFORMER
T7
INDICATORLAMP
R
W -- WHITE R -- RED G -- GREEN
NOTES:
1.ATS SHOWN IN NORMAL POSITION WITH NORMAL POWER PRESENT
NEUTRAL CONTACTS NTS & ETS PRESENT
2
ON 4 POLE UNITS ONLY.
OPTIONAL NEUTRAL BUS
3
NO
EMERG.NORMAL
AUXILIARYCONTACTS
15A, 240VAC
A4--1
A4--1A4--1
NO
A4--2
A4--2 A4--2
A3--1 A3--1
A3--1
A3--2
NO
NO
A3--2A3--2
NO
321283-C
Schematic Diagram, E33+ Logic, 600--1200 Amp
TP-5660 11/98 Diagrams and Drawings 33
GD
AT
MECHANISM
P1--34
TO LOAD
2 2
NTS ETS
FROM NORMAL
SOURCE
77
76
P1--36P1--35
76 77
AT INNER PANEL
GD
TB6
NC
NA
NC
NB
NA
8180797877767574
P1--22
NA
NC
NB
NA
NA
NA
P1--23
NA
NB
P1--24
NC
NB NC
NC
NC
CN1 CE1
6 4
DS
209R
209
AC
206R
NCNBNA
NTS
NTS
NTS
76 77
206
+
RN
AC
P1--18
-- --
CN
LNNN
LC
LB
LA
ETS
ETS
ETS
306
307R
P1--3
+
AC
AC
RE
306R
CE
3
EN
EC
P1--10
P1--9
EC
4
6
307
DS
EC
EC EB EA
EC
EB
EB
EA
EA
FROM EMERGENCY SOURCE
EMERG.NORMAL
NO
C
SN--1
EA
P1--8
EA
EA
EBEC
SN--2
SE--1
SE--2
C
C
C
X
NC NO NC NO NC NO NC
X
X
X X
X
X
X
AUXILIARYCONTACTS
15A, 240VAC
A4--1
A4--2
A4--2 A4--2
A3--1
A3--1 A3--1
A3--2
A4--1A4--1
NO
NO
NO
A3--2A3--2
NO
P3--2P3--1 P3--3
P15--1 P15--2 NA NB
NB
P15--4
P15--7
AB1
AB2
P3--4 P3--7 P3--8
FOR 3
NORMAL
SENSING
TRANSFORMER
CONNECTION
SEE ABOVE
OPTION DA--26
P15--3
NC
OPTION
NT3NT2
DA--26
3 NORMAL
SENSING
P15--8
P15--9
BC2
BC1
P3--9
P3--1 P3--2 P3--3 P3--4 P3--7 P3--8 P3--9
REMOVE JUMPER ”JA” TO INSTALLTEST SWITCH, ENABLING TESTING OF N/AC VOLTAGESENSING CIRCUIT FROM DOOR.
NT1
T2 T3
T3
T2
T2
T3
P2--9 P2--11
P2--1P2--4P2--7
24VAC
TO
12VDC
POWER SUPPLY
SENSING
CIRCUIT
+12V
1 2 3 4 5 6 7 8 9 10 11 12
TB1
JA J J
61
60
TEST
7
1
ET1
T6 T7
T7T6
N/CA VOLT
N/AB VOLT
N/BC VOLT
330
P8--4
ER
P8--2P1--7
JP2
JP3
JP4
74
LOGIC BOARD
P8--1
E
E
VOLT
FREQ.
R29
R42 EMERGENCY FREQUENCY
AND VOLTAGE SENSING.
JP1
K4
ENGINE
EMERGENCY
START
VOLTAGE
T7
T6
P2--12
LED1
24VAC 12VDC
POWER SUPPLY
EA
EC
P2--10
TO
K2
K1
NOTE: JP5 JUMPER REMOVED
FOR 3
P2--6
P2--3
SENSING
CIRCUIT
NORMAL SOURCE AVAILABLE
EMERGENCY SOURCE AVAILABLE
SENSING.
JP5
P8--9
NR
P8--15
NR
P1--12 P1--11
4 7
8
7
P8--11
57
3
58
4
SN--2
NO NC
P8--10
K5K3
K4
ES3
ES4
P1--30
8
P1--25
16
1
P1--6
REMOTE ENGINE START
SN--1
TB2
P1--13
26
NC
10 4 5 6 3 2 1 7 8
K5 K2
NORMAL
POSITION
NR
LOGIC
P4--1
P4--2
N1
P9--2
N2
P9--1
D1
NR
10 11
33
CCN CCE
2 1
T1
63
NORMAL
EMERGENCY
SWITCH
POSITION
POSITION
52 53
G
EMERGENCY
NORMAL
SOURCESOURCE
AVAILABLEAVAILABLE
W W
P4--3
E1
P9--3
SWITCH
R
K1
D2
ER
21
6762
J1J2
EMERGENCY
P4--4
P9--4
1110
P1--14
K3
POSITION
LOGIC
NR
82
ERNR
693996
SE--1
NC
T6T2
91112
R17 NORMAL C--AVOLTAGE SENSING
R34 NORMALA--BVOLTAGE SENSING
ER
R37 NORMAL B--CVOLTAGESENSING
NOTE: JP1, JP2, JP3, JP4 JUMPER REMOVED FOR VOLTAGE SENSING ABOVE 240 VAC
E2
LEGEND
EMERGENCY TRANSFER OPERATOR (TRANSFER TO EMERGENCY)
CE
CCE TRANSFER COIL CONTROL RELAY (TO EMERGENCY)
NORMALTRANSFER OPERATOR (TRANSFER TO NORMAL)
CN
TRANSFER COIL CONTROL RELAY (TO NORMAL)
CCN
DS DISCONNECT SWITCH ER
EMERGENCY RELAY
ET
EMERGENCY TRANSFORMER
ETS EMERGENCY CONTACTOR POWER CONTACTS
J
JUMPER K1 EMERGENCY SOURCE AVAILABLE RELAY K2 NORMALSOURCE AVAILABLERELAY K3 EMERGENCYPOSITION RELAY
K4 ENGINE START RELAY
K5 NORMALPOSITION RELAY
LED
LIGHT EMITTING DIODE
NORMAL CONTACTORAUX. SWITCHN
NR
NORMAL RELAY NT
NORMALTRANSFORMER
NTS
NORMAL CONTACTOR POWER CONTACTS
LIMITSWITCH (EMERGENCY)SE SN LIMITS SWITCH (NORMAL)
T SENSING TRANSFORMER
COMPONENT CONNECTION
###
CONNECTION NODE #
LEAD
P#--#
PLUG/SOCKET CONNECTOR
A4--1
TERMINAL BLOCK ON TRANSFER SWITCH
4
TERMINAL BLOCK ON LOGIC BOARD
EA
TERMINAL BLOCK PRIMARY OF TRANSFORMER
TERMINAL BLOCK SECONDARYOF TRANSFORMER
T7
INDICATORLAMP
R
W -- WHITE R -- RED G -- GREEN
NOTES:
1.ATS SHOWN IN NORMAL POSITION WITH NORMAL POWER PRESENT
NEUTRAL CONTACTS NTS & ETS PRESENT
2
ON 4 POLE UNITS ONLY.
OPTIONAL NEUTRAL BUS
3
321296-B
Schematic Diagram, E33+ Logic, 1600--3000 Amp
34 Diagrams and Drawings TP-5660 11/98
GD
AT
MECHANISM
P1--34
AT INNER PANEL
TB6
P3--2P3--1 P3--3
P15--1 P15--2
NA NB
NB
P15--4
P15--7
AB1
AB2
P3--4 P3--7 P3--8
FOR 3 NORMAL SENSING
TRANSFORMER
CONNECTION
SEE ABOVE
OPTION DA--26
FROM NORMAL
76
GD
76 77
P15--3
NC
OPTION
NT3NT2
DA--26
3 NORMAL
SENSING
P15--8
P15--9
BC2
BC1
P3--9
P3--1 P3--2 P3--3 P3--4 P3--7 P3--8 P3--9
REMOVE JUMPER ”JA” TO INSTALLTEST SWITCH, ENABLING TESTING OF N/AC VOLTAGESENSING CIRCUIT FROM DOOR.
77
SOURCE
P1--36P1--35
TO LOAD
2 2
NTS ETS
16
9
NO
REMOTE ENGINE START
P1--6
P1--15
NTS
NTS
NTS
76 77
TB2
SN--1
SEO--1
P4--1
P9--1
P1--18
P1--33
P1--17
P1--5
P8--9
P1--13
26
NO
2 1
P1--26
29
NC
52 53
10 4 5 6 3 2 1 7 8
K5 K2
NORMAL
POSITION
NR
LOGIC
P4--2
N1
N2
P9--2
206NC
209
406
309
D1
NR
10 11
NC
NB
NA
P1--22
NA
P1--23
NC
NB
P1--24
CN1
6 4
8
7
4
15
TDON
B A
57
58
SN--2
NC NO
CN1
5 3
CEO
6 4
CE0
35
P8--12
7
P8--11
SEO--2
3 4
1
NA
8180797877767574
T3T7
NA
TO T3
NC
TO T7
NA
NC
NB
NA
NA
T2 T3
T2
P2--1P2--4P2--7
24VAC
12VDC
POWER SUPPLY
SENSING
CIRCUIT
+12V
1 2 3 4 5 6 7 8 9 10 11 12
TB1
JA J J
61
60
TEST
NA
TO
NC
NB NC
NT1
T3
T2
T3
15
P2--11P2--9
NC
NCNBNA
TO TB6--81
NR
P8--10
P4--7
7
1
7
4
P1--1
P9--7 P1--4P8--7
T2 40 50
K5K3
K4
ES3
ES4
P1--12
P1--11
P1--30
8
P1--25
SCN
NO
DS
201
SCEO
NO
DS
502
NR
96
P8--15
CN1 CE1
33
CEO
12 1 2
T1
63
NORMAL
EMERGENCY
SWITCH
POSITION
G
EMERGENCY
NORMAL
W W
P4--3
P9--3
LNNN
LC
LB
LA
+
AC
AC
RTN
-­401R
+
AC
AC
RTE
-­500R
NR ER
9
30
21
24
CNO
SWITCH
POSITION
R
SOURCESOURCE
AVAILABLEAVAILABLE
6762
J1J2
K1
EMERGENCY
P4--4
E1
P9--4
D2
ER
1110
209
400R
217
501R
307
P1--14
P1--28
K3
POSITION
LOGIC
NR
82
ETS
ETS
ETS
CN/0
SCNO
CE/0
SCE
P8--4
6
93
SE--1
P1--7
NO
SNO--1
P1--27
NC
P1--21
T6T2
91112
ER
E2
21
N/CA
VOLT R17 NORMAL C--AVOLTAGE SENSING
N/AB
VOLT R34 NORMALA--BVOLTAGE SENSING
N/BC
VOLT R37 NORMAL B--CVOLTAGESENSING
NOTE: JP1, JP2, JP3, JP4 JUMPER REMOVED FOR VOLTAGE SENSING ABOVE 240 VAC
P1--2
NO
P1--3
NO
TDOETDON
P8--3
3
7
P8--2
SNO--2
NO
P8--6 P9--6
TDOE
B A
LOGIC BOARD
JP2
JP3
JP4
3
506
309
306
ER
4
4
P1--16
2
E FREQ.
R42 EMERGENCY FREQUENCY
AND VOLTAGE SENSING.
JP1
ENGINE
START
CNO
3 5
CNO
4 6
CE1
3 5
CE1
7
T6
P4--6
R29
K4
P8--1
P1--10
64
E VOLT
EMERGENCY
EC
EB
EC
EC
EBEC
EC
EC EB EA
T6 T7
T7
T6
P2--12
POWER SUPPLY
LED1
VOLTAGE
EN
EC
EB
EA
EA
P1--8P1--9
EA
EA
EA
EA
ET1
TO
TB6--80
T7T6
2
EA
P2--3
24VAC
TO
12VDC
SENSING
CIRCUIT
NORMAL SOURCE
K2
AVAILABLE EMERGENCY SOURCE
K1
AVAILABLE
NOTE: JP5 JUMPER REMOVED
SENSING.
FOR 3
FROM EMERGENCY SOURCE
OFF
C
SE--1
C
SE--2
C
SN--1
C
SN--2
SCN
C NO
SCEO
CE1 COILCONTROL EMERGENCY RELAY
CEO COILCONTROL EMERGENCYRELAY(TRANSFEROPERATOR)
CN1 COILCONTROLNORMAL RELAY
CN/0
COIL CONTROL NORMAL RELAY (TRANSFER OPERATOR)
CE TRANSFER OPERATOR (CLOSE TO EMERGENCY)
CE/0 TRANSFER OPERATOR(OPEN FROM EMERGENCY)
CN
TRANSFER OPERATOR(CLOSETO NORMAL)
CN0
TRANSFER OPERATOR(OPEN FROM NORMAL) DISCONNECTSWITCH
DS
EFR EMERGENCY FREQUENCY RELAY
ER EMERGENCY RELAY
LED LIGHT EMITTING DIODE
NORMALRELAYNR
NR1 NORMALRELAY #1
BRIDGE RECTIFIER (EMERGENCYTRANSFER OPERATOR)RE
REO BRIDGERECTIFIER (EMERGENCY TRANSFER OPERATOR)
RN BRIDGE RECTIFIER (NORMALTRANSFER OPERATOR)
RNO BRIDGERECTIFIER (NORMAL TRANSFER OPERATOR)
SE, SEO
LIMIT SWITCH (EMERGENCY)
SN, SNO
LIMIT SWITCH (NORMAL)
TDES
TIME DELAY ENGINE START RELAY
TDOE
TIME DELAY ON EMERGENCYRELAY
TDON
TIME DELAY ON NORMALRELAY JUMPER
J
EC
P2--6P2--10
JP5
NORMAL EMERG.
NO
X
NC NO
X
NC NO NC
X
NO NC NC
X
NOC NC
X
NC
X
NOTES:
1.ATS SHOWN IN NORMAL POSITION WITH NORMAL POWER PRESENT
NEUTRAL CONTACTS NTS & ETS PRESENT
2
ON 4 POLE UNITS ONLY.
OPTIONAL NEUTRAL BUS
3
AUXILIARYCONTACTS
15A, 240VAC
A4--1
A4--2
A4--2 A4--2
A3--1
A3--1 A3--1
A3--2
NO
X
X
X
X
X
X
X
X
XX
X
X
SE0--1
SE0--2
SNO--1
SNO--2
SCNO
SCE
LEGEND
C
NC NO
C
NC NO
C
NC NO
C
C NO
NC NOC NC
COMPONENT CONNECTION TERMINAL
###
#
LEAD
P#--#
PLUG/SOCKET CONNECTOR LOGIC BOARD DIP CONNECTOR
#
CONNECTION NODE
TERMINAL BLOCK ON TRANSFER SWITCH PANEL
A4--1
4
TRANSFER SWITCH POWER TERMINALS
EA
TERMINAL BLOCK PRIMARY OF TRANSFORMER TERMINAL BLOCK SECONDARYOF TRANSFORMER
T7
INDICATORLAMP
R
G -- GREEN R -- RED W -- WHITE
NC
NC
NC
NC
X
X
X
X X
XXX
OFF
A4--1A4--1
A3--2A3--2
EMERG.NORMAL
X
X
X
X
X
X
X
X
X
X
321295-C
Schematic Diagram, E33+ Logic, 400 Amp with Programmed Transition
TP-5660 11/98 Diagrams and Drawings 35
GD
AT
MECHANISM
P1--34
GD
AT
INNER
PANEL
TB6
P15--2P15--1 NBNA
NB
NT2 NT3
P15--8
P15--7
P15--4
BC2
AB2
AB1
P3--8P3--7P3--4
P3--1 P3--2
FOR 3 NORMAL SENSING
TRANSFORMER
CONNECTION
SEE ABOVE
OPTION DA--26
P3--3 P3--4 P3--7 P3--8 P3--9
FROM NORMAL
SOURCE
77
76
P1--36P1--35
76 77
NA
NC
P3--3P3--1 P3--2
P15--3
NC
OPTION
DA--26
3 NORMAL
SENSING
P15--9
BC1
P3--9
P2--7 P2--4
REMOVE JUMPER ”JA” TO INSTALLTEST SWITCH, ENABLING TESTING OF N/AC VOLTAGESENSING CIRCUIT FROM DOOR.
SENSING
CIRCUIT
TB1
8180797877767574
P2--1
T3T7
TO T7
NC
61
P1--22
TO T3
NB
TEST
NC
NB
NA
NA
P1--23
NA
NA
NA
T2 T3
T2 T3
24VAC
12VDC POWER SUPPLY +12V
60
NA
TO
NB
P1--24
NC
NB NC
NT1
T2
T3
15
P2--11P2--9
JJJA
TO LOAD
2 2
NTS ETS
NTS
NC
NTS
NTS
76 77
LNNN
LC
LB
LA
206R
CCN
P1--18
NC
206
46
+
AC
AC
RN
-­208R
CN
DS
209
DS
307
406R
CCEO
406
6 4
NCNBNA
TO TB6--81
NR
P8--10
4
T2 40 50
P4--7
K3 K5
ES3
8
7
1
4
7
P1--1
15
P9--7 P1--4P8--7
K4
ES4
121110987654321
P1--12 P1--11
P1--30
8
NO
P1--25
NC
7
+
AC
AC
REO
--
209R
P1--6
P8--12
16
7
P8--11
P1--15
9
SEO--2
NO
TDON
AB B A
57
REMOTE
3
ENGINE START
58
4
SN--2
1
209
CEO
P1--13
P1--26
NORMAL
POSITION
P4--2
P9--2
NR
9
6
26
CCN
2 1
29
CCEO
2 1
NORMAL
SWITCH
POSITION
52 53
G
NORMAL
W W
K2K5
NR
LOGIC
N2
P8--15
33
T1
63
P4--3
P9--3
P8--9
SN--1
NC
SEO--1
NC
TB2
12 11 9
P4--1
N1
P9--1
D1
NR
1110
NR ER
9
30
CCE
1 2
24
CCNO
1 2
EMERGENCY
SWITCH
POSITION
R
EMERGENCY
SOURCESOURCE
AVAILABLEAVAILABLE
6762
J1J2
K1
E1
D2
ER
10 11
2 8
307
P1--14
P1--28
EMERGENCY
POSITION
P4--4
P9--4
NR
ETS
ETS
ETS
306R
AC
RE
307R
CE
506R
AC
RNO
308R
CNO
P8--4
6
93
SE--1
P1--7
NC
SNO--1
P1--27
NC
P1--21
T6T2
8712365410
N/CA VOLT
R17
K3
NORMAL C--AVOLTAGE SENSING
N/AB
VOLT R34 NORMALA--BVOLTAGE SENSING
N/BC
ER
LOGIC
E2
VOLT R37 NORMAL B--CVOLTAGESENSING
NOTE: JP1, JP2, JP3, JP4 JUMPER REMOVED FOR VOLTAGE SENSING ABOVE 240 VAC
+
P1--3
AC
--
+
AC
--
3
21
P8--6 P9--6
306
P1--2P1--17
506
TDOETDON
P8--3
4
7
P8--2
SNO--2
NO
TDOE
LOGIC BOARD
JP2
JP3
JP4
3
EN
EC
EB
EB
EA
EA
FROM EMERGENCY SOURCE
P1--10
EC
P1--9
EA
EMERG.NORMAL
OFF
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
LEGEND
P#--#
#
A4--1
POWER PRESENT
NEUTRAL CONTACTS NTS & ETS PRESENT ON 4 POLE UNITS ONLY.
OPTIONAL NEUTRAL BUS
AUXILIARYCONTACTS
15A, 240VAC
A4--1
A4--1 A4--1
A3--2 A3--2
###
#
4
EA T7
R
NO
A4--2
NO
A3--1
NO
A3--2
NO
COMPONENT CONNECTION TERMINAL
LEAD
PLUG/SOCKET CONNECTOR LOGIC BOARD DIP CONNECTOR
CONNECTION NODE TERMINAL BLOCK ON TRANSFER SWITCH PANEL
TRANSFER SWITCH POWER TERMINALS TERMINAL BLOCK PRIMARY OF TRANSFORMER TERMINAL BLOCK SECONDARYOF TRANSFORMER
INDICATORLAMP G -- GREEN R -- RED W -- WHITE
CCE
EC
64
CCNO
64
ER
P8--1
7
4
P1--16
2
T6
P4--6
E
E
FREQ.
JP1
K4
ENGINE
START
R29
VOLT
EMERGENCY
R42 EMERGENCY FREQUENCY
AND VOLTAGE SENSING.
EBEC
EC
EC EB EA
T6 T7
T6
T7
P2--12
POWER SUPPLY
LED1
VOLTAGE
P1--8
EA
EA
ET1
TO
TB6--80
T7T6
2
EA
P2--3
P2--10
24VAC 12VDC
SENSING
TO
CIRCUIT
NORMAL SOURCE
K2
AVAILABLE EMERGENCY SOURCE
K1
AVAILABLE
NOTE: JP5 JUMPER REMOVED
SENSING.
FOR 3
SN--1
SN--2
SE--1
SE0--1
SE0--2
SNO--1
SNO--2
CCE COIL CONTROL EMERGENCY RELAY
CCEO COIL CONTROLEMERGENCY RELAY(TRANSFER OPERATOR)
CCN COILCONTROLNORMAL RELAY
CCN0
COIL CONTROL NORMAL RELAY (TRANSFER OPERATOR)
CE TRANSFER OPERATOR (CLOSE TO EMERGENCY)
CE0 TRANSFER OPERATOR (OPEN FROM EMERGENCY)
CN
TRANSFER OPERATOR(CLOSETO NORMAL)
CN0
TRANSFER OPERATOR(OPEN FROM NORMAL) DISCONNECTSWITCH
DS
EFR EMERGENCY FREQUENCY RELAY
ER EMERGENCY RELAY
LED LIGHT EMITTING DIODE
NORMALRELAYNR
NR1 NORMALRELAY #1
BRIDGE RECTIFIER (EMERGENCYTRANSFER OPERATOR)RE
REO BRIDGERECTIFIER (EMERGENCY TRANSFER OPERATOR)
RN BRIDGE RECTIFIER (NORMALTRANSFER OPERATOR)
RNO BRIDGERECTIFIER (NORMAL TRANSFER OPERATOR)
SE, SEO
LIMIT SWITCH (EMERGENCY)
SN, SNO
LIMIT SWITCH (NORMAL)
TDES
TIME DELAY ENGINE START RELAY
TDOE
TIME DELAY ON EMERGENCYRELAY
TDON
TIME DELAY ON NORMALRELAY JUMPER
J
EC
P2--6
NC NO
C
NC NO
C
NC NO
C
NC NO
C
NC NO
C
NC NO
C
NC
NOTES:
1.ATS SHOWN IN NORMAL POSITION WITH NORMAL
NO
C
2
3
JP5
Schematic Diagram, E33+ Logic, 600--3000 Amp with Programmed Transition
A4--2A4--2
A3--1A3--1
321285-B
36 Diagrams and Drawings TP-5660 11/98
321096-C
Schematic Diagram, S340+ Logic, 600--1200 Amp
TP-5660 11/98 Diagrams and Drawings 37
Schematic Diagram, S340+ Logic, 1600--3000 Amp
321097-A
38 Scheduled Maintenance
TP-5660 11/98
346311-
Schematic Diagram, S340+ Logic, 120 VAC, 40--260 Amp with Programmed Transition
TP-5660 11/98 Diagrams and Drawings 39
Schematic Diagram, S340+ Logic, 208 VAC, 40--260 Amp with Programmed Transition
353185-
40 Scheduled Maintenance
TP-5660 11/98
353184-
Schematic Diagram, S340+ Logic, 240 and 480 VAC, 40--260 Amp with Programmed Transition
TP-5660 11/98 Diagrams and Drawings 41
Schematic Diagram, S340+ Logic, 380 and 416 VAC, 40--260, Amp with Programmed Transition
353183-
42 Scheduled Maintenance
TP-5660 11/98
353182-
Schematic Diagram, S340+ Logic, 600 VAC, 40--260 Amp with Programmed Transition
TP-5660 11/98 Diagrams and Drawings 43
Schematic Diagram, S340+ Logic, 400 Amp with Programmed Transition
321098-B
44 Scheduled Maintenance
TP-5660 11/98
321099-B
Schematic Diagram, S340+ Logic, 600--3000 Amp with Programmed Transition
TP-5660 11/98 Diagrams and Drawings 45
321287-C
Schematic Diagram, M340+ Logic 600--1200 Amp
46 Diagrams and Drawings TP-5660 11/98
321301-B
Schematic Diagram, M340+ Logic, 1600--3000 Amp
TP-5660 11/98 Diagrams and Drawings 47
346312-
Schematic Diagram, M340+ Logic, 120 VAC, 40--260 Amp with Programmed Transition
48 Diagrams and Drawings TP-5660 11/98
353174-
Schematic Diagram, M340+ Logic, 208 VAC, 40--260 Amp with Programmed Transition
TP-5660 11/98 Diagrams and Drawings 49
353175-
Schematic Diagram, M340+ Logic, 240 and 480 VAC, 40--260 Amp with Programmed Transition
50 Diagrams and Drawings TP-5660 11/98
353176-
Schematic Diagram, M340+ Logic, 380 and 416 VAC, 40--260 Amp with Programmed Transition
TP-5660 11/98 Diagrams and Drawings 51
353177-
Schematic Diagram, M340+ Logic, 600 VAC, 40--260 Amp with Programmed Transition
52 Diagrams and Drawings TP-5660 11/98
321300-B
Schematic Diagram, M340+ Logic, 400 Amp with Programmed Transition
TP-5660 11/98 Diagrams and Drawings 53
321286-A
Schematic Diagram, M340+ Logic, 600--3000 Amp with Programmed Transition
54 Diagrams and Drawings TP-5660 11/98
Section 6. Installation
Kohler automatic transfer switches are shipped factory wired and tested, ready for installation. Installation of the switch consists of the following.
D Unpackingand inspecting thetransfer switch upon
receipt.
D Protecting the switch against damage before and
during installation.
D Wiring of normal source (utility), emergency
source (generator), and load circuits.
D Wiring of control connections such as generator
start signals and accessories.
D Checking voltages and functions. D Connecting and initializing the controller.
Follow this installation section first when installing the transfer switch. Refer to the logic controller operation and installation manual packed with the transfer switch for details on electrical controls and accessories. See Sections 1.3 and 1.4 for nameplate and model number informationto identify typeof logic controller. See List of Related Materials in the Introduction section in this manual.
6.1 Upon Receipt of Unit
6.1.1 Inspection
At time of delivery,inspect the automatic transfer switch for signs of shipping damage. If damage and/or rough handling is evident, file a damage claim immediately with the transportationcompany and promptly notify the distributor or dealer.
6.1.2 Lifting W ARNING
See Figure 6-1 for the approximate weight of each transfer switch covered in this manual. Use a spreader bar for lifting. Attach the bar only to the enclosure’s mounting holes or lifting brackets; do not lift the unit at anyotherpoints. Replace,close,andlock theenclosure door before moving or mounting the unit.
Transfer Switch
Rating (amps)
40
80
100
150
225
260
400 Any 524 (238)
600
800
1000
1200
1600
2000
2500
3000
Number of
Poles
2, 3
4
2, 3
4
2, 3
4
2, 3
4
2, 3
4
2, 3
4
2,3
4
2, 3
4 3
4 3
4 3
4 3
4 3
4 3
4
Approximate
Weight lb. (kg)
237 (108)
242 (110)
237 (108)
242 (110)
237 (108)
242 (110) 242 (110)
247 (112) 242 (110)
247 (112) 242 (110)
247 (112)
638 (290) 658 (298)
678 (308) 761 (345)
678 (308) 761 (345)
678 (308) 761 (345)
975 (442)
1100 (499)
975 (442)
1100 (499) 1155 (524)
1295 (587)
1155 (524)
1295 (587)
Figure 6-1. Approximate Transfer Switch Weight
Unbalanced weight. Improper lift can cause severe injury or death and/or equipment damage.
Use adequate lifting capacity. Never leave transfer switch standing upright unless it is securely bolted in place or stabilized.
TP-5660 11/98 Installation 55
6.1.3 Unpacking
Unpack the transfer switch immediately after receipt and inspect for shipping damage. Failureto perform an immediate inspection impedes recovery of losses causedby shippingdamage. Use carewhenunpacking to avoid damaging any of the transfer switch components. Remove all dirt and packing material that mayhaveaccumulatedin thetransferswitch oranyof its components.
If the equipment has been stored at cold temperatures, allow equipment to warm to room temperature for 24 hours (minimum) before unpacking to prevent condensation on the electrical apparatus from surrounding moist air.
such as a wall. When mounting these units either way, plumb the enclosure to ensure that the door hinges are vertical to avoid any distortion of the enclosure or door. For floor mounting, bolt the mounting feet to the floor and shim the mounting feet as needed to plumb the enclosure. Keyholeslots for wallmounting areprovided intherearpanelof theenclosure. Placewashersbehind themounting bracket key holes to shim the enclosureto a plumb condition.
Bolt the 600- through 3000-ampere automatic transfer switches directly to floor mounting pads. When mountingone of these units, level themounting pads so that the doorhinges are plumb when the unit is installed to avoid distorting the enclosure or door.
6.1.4 Storage
Store the transfer switch in its protective packing until ready for final installation. Protect the automatic transfer switch at all times from excessive moisture, construction grit, and metal chips. Avoid storage in low temperature and high humidity areas where condensation could occur on the unit.
6.2 Mechanical Installation
Check the System Voltage and Frequency Do not
install a transfer switch if the system voltage and frequency shown on the transfer switch nameplate are differentfrom the nominal normal(utility)source voltage and frequency and the nominal emergency source voltage and frequency shown on the generator set nameplate.
To plan theinstallation,use the dimensions given on the enclosure dimension drawings in Section 5. Select the
mounting site to comply with local electrical code restrictions for the enclosure type. Mount the transfer switch as close to the load and power sources as
possible. Allow adequate space to open the enclosure door fully and to service the switch.
6.3 Check Manual Operation
Follow a procedure in Section 2.3 to manually operate thecontactor but stopbefore reapplyingpower sources. Verify that the contactor operates smoothly without binding and prepare it for automatic operation. If the contactor does not operate smoothly without binding, STOP! Call an authorized service center to service the contactor before proceeding!
6.4 Electrical Wiring
All internal electrical connections are prewired. The onlywiringnecessary wheninstallingthetransferswitch is to connect the unit to external devices.
Observe all applicable national, state, and local electr ical codes during installation.
Install DC, control, and communication system wiring in raceways, cables, or conduit separate from AC power wiring.
See Section 5 for schematic diagrams and enclosure drawings.
W ARNING
Vertically mount the 40- through 260-ampere transfer switches covered in this manual to a wall or other rigid vertical supporting structure. Keyhole slots for mounting purposes are provided in the mounting brackets on the top and bottom of each unit. When mounting these units, plumb the enclosure to ensure thatthe doorhingesare verticalto avoidanydistortionof the enclosure or door. Place washers behind the mounting bracket key holes to shim the enclosure to a plumb condition.
Floor mount or attach the 400-ampere transfer switch covered in this manual to a rigid supporting structure
Accidental starting. Can cause severe injury or death.
Disconnect battery cables before working on generator set. (Remove negative (--) lead first when disconnecting battery. Reconnect negative (--) lead last when reconnecting battery.)
TP-5660 11/9856 Installation
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator set as follows: 1) Movethe generator set master switch to the OFF position. 2) Disconnect power to the battery charger.
3) Remove battery cables, negative (--)lead first. Reconnect
negative(--) l ead lastwhenreconnecting battery. Follow these precautions to prevent starting of generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
W ARNING
Hazardous voltage. Can cause severe injury or death.
Disconnect all power sources before opening enclosure.
(under 600 Volt)
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect all power sources before opening enclosure.
(600 Volt and above)
W ARNING
DANGER
Hazardous voltage. Will cause severe injury or death.
Disconnect power sources before servicing. Install barrier after adjustments, maintenance, or servicing.
(600 Volt and above)
Grounding the transfer switch. Hazardous voltage can cause severe injury or death. Electrocution is possible
wheneverelectricity is present. Open main circuit breakers of all power sources before servicing equipment. Configure the installation to electrically ground the transfer switch and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground, as the chance of electrocution increases under such conditions.
Installing battery charger. Hazardous voltage can cause severe injury or death. Electrical shock may occur if battery
charger is not electrically grounded. Connect battery charger enclosure to ground of a permanent wiring system. As an alternative, install an equipment grounding conductor with circuit conductors and connect to equipment grounding terminal or lead on battery charger. Perform battery charger installation as prescribed in equipment manual. Installbattery charger in compliance with local codes and ordinances.
Connecting battery and battery charger. Hazardous voltage c an cause severe injury or death. Reconnect
battery correctly to avoid electrical shock and damage to battery charger and battery(ies). Have a qualified electrician install battery(ies).
Installing accessories to transformer assembly.
Hazardous voltage. Can cause severe injury or death.
Disconnect power sources before servicing. Install barrier after adjustments, maintenance, or service.
(under 600 Volt)
TP-5660 11/98 Installation 57
Hazardous voltage can cause severe injury or death. To prevent the possibility of electrical shock, disconnect harness plug before installing any accessories involving connection to transformer assembly primary terminals 76, 77, 78, and 79. Terminals are at line voltage! (Models with E33+, S340,
S340+, 340, R340, or R33 controls only.)
Installing accessories to transformer assembly. Hazardous voltage can cause severe injury or death. To
prevent the possibility of electrical shock, disconnect harness plugbefore installing any accessories which will be connected to transformer assembly primaryterminals on microprocessor logic models. Terminals are at line voltage!
Making line or auxiliary connections. Hazardous voltage can cause severe injury or death. Toprevent the possibility
of electrical shock, deenergize the normal power source before making any line or auxiliary connections.
NOTICE
Hardware damage! Transferswitch may use both American
Standard and metric hardware. Use the correct size tools to prevent rounding of bolt heads and nuts.
NOTICE
Electrostatic discharge damage! Electrostatic discharge
(ESD) damages electronic circuit boards. Prevent electrostatic discharge damage by wearing an approved grounding wrist strap when handling electronic circuit boards or integrated circuits. An approved grounding wrist strap provides a high resistance (about 1 megohm), not a direct
short, to ground.
compressedairtocleanthe switchbecauseitcancause debris to lodge in the components and cause damage.
Use watertight conduit hubs approved for outdoor use for installing the transfer switch outdoors.
Before connecting wiring cables to terminal lugs, remove surface oxides from cables by cleaning with a wire brush. If using aluminum conductors, apply a joint compound to cables. After tightening terminal lugs, carefully wipe off excess joint compound.
Connection points for the normal power, emergency power, and load are clearly marked on the contactor assembly and are also shown on the drawings in Section4. Be suretoheed thephase markings (A,B,C, and N).
NOTE
Connect source and load phases as indicated by the markings and drawings. Improper connections may cause short circuits or cause phase-sensitive load devices to malfunction or operate in reverse.
NOTE
For easy access during installation wiring, remove the front door of the enclosure. Disconnect the cable plug that connects the front door components to the internal components and then lift the door off its hinge pins.
6.4.1 AC Power Connections
All conductors should enter the enclosure at the locations shown on the drawings. When drilling entry holes for any conductors, cover the transfer switch components for protection from metal chips and construction grit. Remove any debris from the enclosure with a vacuum cleaner. Do not use
NOTE
When making power connections to the power switching device, leave sufficient slack in the power leads to reach all of the power connecting lugs on the power switching device.
NOTE
The power source leads must be phased A-B-C for option DD-34-Z (phase sequence and loss monitoring) to function correctly. If the power source phase sequence is not A-B-C and option DD-34-Z is enabled the controller consider the source to have failed.
Connectthe normal, emergencyand load conductors to the clearly marked terminals on the transfer switch. Verify that all connections are consistent with drawings before tightening the lugs. Tighten all cable lug connections to the torque values shown in Figure 6-2.
TP-5660 11/9858 Installation
SocketSiz
e
Torque
SocketSiz
e
Bol
t
Across Flat
1/8 45 4 5.1 5/32 100 8 11.3 3/16 120 10 13.6 7/32 150 12 17.0
1/4 200 17 22.6 5/16 275 23 31.1
3/8 375 31 42.3
1/2 500 42 56.5 9/16 600 50 67.8
in. lbs. ft. lbs. Nm
Figure 6-2. Tightening Torque for Lugs
In cases where the normal, emergency, and load connections are made to a rear connected bus bar,use a compression washer, flat washer, and a minimum grade 5 bolt and torque to the values in Figure 6-3.
Torque Bolt (Grade 5)
Size
1/4-20 72 6 8.1
5/16-18 132 11 14.9
3/8-16 300 25 33.9 1/2-13 720 60 81.4
in. lbs. ft. lbs. Nm
Figure 6-3. Tightening Torque for Bus Bars
6.4.2 Generator Start Connection W ARNING
position; disconnecting power to the generator engine start battery charger, if installed; and disconnecting all generatorenginestart batterycables, negative(--)leads first.
Connect the generator set remote starting circuit to the generator start signal connections located on terminals 3and 4 of the transferswitch contactor assembly. Ared decal identifies the location of the terminal block. See the enclosure dimension drawings in Section 5. The transfer switch controller provides a contact closure through the wiring harness to these terminals to signal the generator set to start.
6.4.3 Accessory and Controller Connections
Complete any external connections for accessories. See Section the transfer switch logic controller operation and installation manual. See Sections 1.3 and1.4 fornameplate and model number informationto identify type of logic controller. See List of Related Materialsin the Introduction section in this manual. See the logic controller operation and installation manual for additional control connection information. Connect the powerswitching device and controller wiring harnesses together at the inline disconnect plug after performing the voltage check procedure to complete installation.
6.5 Prepare the Generator Set for
Operation
Accidental starting. Can cause severe injury or death.
Disconnect battery cables before working on generator set. (Remove negative (--) lead first when disconnecting battery. Reconnect negative (--) lead last when reconnecting battery.)
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator set as follows: 1) Movethe generator set master switch to the OFF position. 2) Disconnect power to the battery charger.
3) Remove battery cables, negative (--)lead first. Reconnect negative(--) l ead lastwhenreconnecting battery. Follow these precautions to prevent starting of generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
Prevent the generator set that provides the emergency power source to the transfer switch from starting by moving the generator set master switch to the OFF
W ARNING
Hazardous voltage. Can cause severe injury or death.
Operate generator set only with all guards and electrical enclosures in place.
Disconnect all power sources to the transfer switch by opening upstream circuit breakers or switches to the transfer switch.
Prepare the generator set that provides the emergency powersourcetothetransferswitchforoperation. Check the oil level, coolant level, fuel supply, batteries, and items specified by the generator set installation or operation checklist or manual.
Move the generator set master switch to the OFF position; reconnect generator engine start battery
Movingrotor.
TP-5660 11/98 Installation 59
cables, negative (--) leads last; and reconnect power to the generator engine start battery chargers, if installed.
6.6 Functional Tests
3. Move the generator set master switch to the OFF position to inhibit generator set starting.
4. Manually transfer the load to the emergency source. See Section 2.3.
6.6.1 Voltage Check
Perform a voltage check to verify that the voltages and phasing of all power sources are compatible with the transferswitch beforeenergizing the load orconnecting the power switching device and controller wire harnesses together.
Thenominalvoltage andfrequencyof thenormal(utility) source, transfer switch nameplate, and generator set output and nameplate should all be the same to avoid damage to loads and the transfer switch.
W ARNING
Hazardous voltage. Can cause severe injury or death.
Operate generator set only with all guards and electrical enclosures in place.
Short circuits. Hazardous voltage/current can cause severe injury or death. Shortcircuits can cause bodily injury
and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove wristwatch, rings, and jewelry before servicing equipment.
Read and understand all instructions on installation drawings and labels affixed to the switch. Note any optional accessories that have been furnished with the switch and review their operation.
V oltage Check Procedure
Perform voltage checks in the order given to avoid damaging the transfer switch.
1. Disconnect all power sources before opening the transfer switch enclosure by opening upstream circuit breakers or switches to the transfer switch.
Movingrotor.
NOTE
5. Reapply the normal source by closing circuit breakers or switches.
6. Use an accurate voltmeter to check the normal source phase-to-phase and phase-to-neutral terminal voltages. Use accurate test equipment to check the phase rotation at the normal source terminals. If the nominal normal source voltage or frequency is not what is shown on the transfer switch nameplate, STOP! Do not proceed further in installation because the transfer switch is not designed for the application—call a local service center to order the correct transfer switch. Rewire the transfer switch normal source terminals to obtain a phase sequence of A-B-C if required on transfer switches with microprocessor controls (see NOTE.)
NOTE
Thepower sourceleads must be phased A-B-Cfor option DD-34-Z (phase sequence and loss monitoring) to function correctly on microprocessor-based controls. If the power source phase sequence is not A-B-C and option DD-34-Z is enabled the controller considers the source to have failed.
7. Disconnect the normal power source by opening upstream circuit breakers or switches to the transfer switch.
8. Manually transfer the load to the normal source. See Section 2.3.
9. Reapply the emergency source by closing circuit breakers or switches.
10. Move the generator set master switch to the RUN position. The generator set should start.
11. Use anaccuratevoltmeterto checktheemergency source phase-to-phase and phase-to-neutral terminal voltages. Use accurate test equipment to check the phase rotation at the emergency-source terminals. Rewire the transfer switch emergency source terminals if the emergency source phase rotation is not the same as the normal source.
2. Disconnect the power switching device and the logic controller wire harnesses at the inline disconnect plug if they are connected.
TP-5660 11/9860 Installation
12. Follow the generator set manufacturer’s instructions to adjust the generator output voltage and frequency to match the nominal system voltage and frequency shown on the transfer switch nameplate if they are different. The automatictransferswitch willoperatecorrectly only to the rated system voltage and frequency specified on the nameplate.
13. Move the generatorset master switch to the AUTO position.
14. Disconnect the emergency power source by opening upstream circuit breakers or switches to the transfer switch.
15. Connect the power switching device and controller wiring harnesses together at the inline disconnect plug.
16. Close and lock the transfer switch enclosure door.
17. Reconnect power sources by closing circuit breakers or switches. The transfer switch may signal the generator set to run for TDEC, if equipped.
6.6.2 Automatic Operation Test
Test thetransfer switch’sautomatic controlsystem. See the logic controller operation and installation manual for the test procedure.
6.7 Controller Setup
See the logic controller operation and installation manual for controller startup and setup procedures.
6.8 Ensure Warranty Registration
The transfer switch seller must complete a Startup Notification Form and submit it to the manufacturer within 60 days of the initial startup date. A Startup Notification Form is included with generator sets and covers all equipment in the standby system. Standby systems not registeredwithin 60 days of the initial date are automatically registered using the manufacturer’s ship date as the startup date.
NOTE
Wheninitially applyingpowertothe transferswitch, the engine start contacts remain closed signalling the generator to run until the ATS’s Time Delay Engine Cooldown (TDEC), if equipped, ends.
Installation of the transfer switch’s power switching device is complete. Close and lock the enclosure door.
TP-5660 11/98 Installation 61
Notes
TP-5660 11/9862 Installation
Appendix A. Glossary of Abbreviations
Abbreviations are used throughout this manual. Normally in the text they will appear in complete form with the abbreviation following in parenthesis the first time they are used. After that they will appear in the abbreviated form. The commonly used abbreviations are shown below.
AC alternating current AISI American Iron and Steel Institute Amp ampere Amps amperes ANSI American National Standard
Institute API American Petroleum Institute approx. approximate, approximately A/R as required, as requested A/S as supplied, as stated,
as suggested ASA American Standards Association ASME American Society of Mechanical
Engineers assy. assembly ASTM American Society for Testing
Materials ATDC after top dead center aux. auxiliary AWG American Wire Gauge AWM appliance wiring material BBDC before bottom dead center BDC before dead center BHP brake horsepower bmep brake m ean effective pressure Btu British thermal unit °C Celsius degree cc cubic centimeter CCA cold cranking Amps. CEC Canadian Electrical Code cfh cubic feet per hour cfm cubic feet per minute CID cubic inch displacement cm centimeter, centimeters cmm cubic meters per minute co. company cont’d. continued CSA Canadian Standards Association CT current transformer cu. in. cubicinch, cubic inches cyl. cylinder dB decibel dBA decibels (A weighted) DC direct current DCR direct current resistance deg. degree dept. department dia. diameter e.g. example given EIA Electronic Industries Association EMI electromagnetic interference EPA Environmental Protection
Agency etc. et cetera (and so forth) ext. external °F Fahrenheit degree fl. oz. fluid ounce, fluid ounces FM frequency modulation ft. foot, feet ft. lbs. foot pound, foot pounds ga. gauge(meters, wire size)
gal./ gals.gallon, gallons gph gallons per hour gpm gallons per minute gr. grade gnd. ground HCHT high cyli nder head temperature HET high exhaust (or engine)
temperature Hg mercury (element) H2O water HP horsepower hr, hrs hour Hz hertz (cycles per second) ID inside diameter IEEE Institute of Electrical and
Electronic Engineers in. inch(es) inc. incorporated in. lbs. inch pounds int. internal int.-ext. internal-external ISO International Standards
Organization J joule, joules JIS Japanese Industry Standard kg kilogram, kilograms kg/cm2kilograms per square centimeter kgm kilogram meter(s) kJ kilojoules (btu cal) km kilometer, kilometers kPa kiloPascal, kiloPascals kph kilometers per hour kV kilovolt kVA kilovolt amperes kW kilowatt, kilowatts kWH kilowatt hour L liter, liters LxWxH length x width x height LED(s) light emitting diode lb., lbs. pound, pounds L/hr. liter per hour, liters per hour L/min. liter(s) per minutes LOP low oil pressure LP liquefied petroleum m meter, meters
3
m max. maximum MCM one t housand circular mils. meggar megohmmeter MHz megahertz mi. mile, miles mil one one-thousandth of an inch min. minimum mJ millijoule, millijoules MJ mega joule, mega joules mm millimeter, millimeters m3/min cubic meters per minute MPa m egaPascal mW milliwatt, milliwatts MW megawatt, megawatts N/A not available or not applicable
cubic meter, cubic meters
NBS National Bureau of Standards N.C. normally closed NEC National Electrical Code NEMA National Electrical
Manufacturers Association
NFPA National Fire Protection
Association Nm Newton meter, Newton meters no., nos number, numbers NPT National Standard taper pipe
thread per general use N/R not required OC overcrank OD outside diameter OEM original equipment manufacturer OS overspeed, oversize O/S oversize OSHA Occupational Safety and Health
Act OV overvoltage oz. ounce, ounces PF power factor PMG permanent magnet generator pot. potentiometer ppm parts per million psi pounds per square inch pt., pts. pint, pints PVC polyvinyl chloride qt., qts. quart, quarts qty. quantity ref. reference RFI radio frequency interference r.h.m. round-head machine (screw) rms root mean square RPM revolutions per minute RTV room temperature vulcanization SAE Society of Automotive Engineers SCR silicon-controlled rectifier sec. second, seconds spec. specs, specification sq. square sq. cm square centimeters sq. in. square inch, square inches tach tachometer TDC top dead center tech. pub.technical publications temp. temperature TIF telephone i nfluence factor TP, TPs technical publications turbo turbocharger UHF ultrahigh frequency UNC Unified coarse thread (was NC) UNF Unified fine thread (was NF) UL Underwriter’s Laboratories, Inc. U/S undersize U.S.A. United States of America V volt, volts vac volts alternating current vdc volts direct current VHF very high frequency W watt, watts
Appendix A-1TP-5660 11/98
TP-5660 11/98
E Kohler Co.1994, 1997, 1998. All rights reserved.
KOHLER CO. Kohler, Wisconsin 53044 Phone 920-565-3381, Web site www.kohlergenerators.com Fax 920-459-1646 (U.S.A. Sales), Fax 920-459-1614 (International) For the nearest sales and service outlet in U.S.A. and Canada Phone 1-800-544-2444
Kohlerr Power Syst ems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65)264-6422, Fax (65)264-6455
Loading...