Appendix A. Glossary of AbbreviationsA-1. . . . . .
TP-5660 11/98Table of Contents
Safety Precautions and Instructions
A transfer switch, like any other
electromechanical device, can pose
potential dangers to life and limb if
improperly maintained or operated.
The best way to prevent accidents is to
be aware of potential dangers and act
safely.Please read and follow the
safety precautions and instructions
below to prevent harm to yourself and
others. This manual contains several
types of safety precautions and
instructionswhich are explained below.
SAVE THESE INSTRUCTIONS.
DANGER
Danger indicates the presence of a
hazard that will cause severe personal
injury, death, or substantial property
damage.
WARNING
Warning indicates the presence of a
hazard that can cause severe personal
injury, death, or substantial property
damage.
CAUTION
Caution indicates the presence of a
hazard that will or can cause minor
personal injury or property damage.
Accidental Starting
W ARNING
Accidental starting.
Can cause severe injury or death.
Disconnect battery cables before
working on generator set. (Remove
negative(--)leadfirstwhen
disconnecting battery.Reconnect
negative(--)leadlastwhen
reconnecting battery.)
Disablingthegeneratorset.
Accidentalstartingcancause
severe injury or death.Before
working on the generator set or
connected equipment, disable the
generator set as follows: 1) Move the
generator set master switch to the OFF
position. 2) Disconnect power to the
battery charger.3) Remove battery
cables,negative (--) lead first.
Reconnect negative (--) lead last when
reconnecting battery.Follow these
precautions to prevent starting of
generator set by an automatic transfer
switch, remote start/stop switch, or
engine start command from a remote
computer.
Battery
W ARNING
Sulfuric acid in batteries.
Can cause severe injury or death.
Use protective goggles and clothes.
Battery acid can cause permanent
damage to eyes, burn skin, and eat
holes in clothing.
Battery acid.Sulfuric acid in
batteries can cause severe injury or
death. Sulfuric acid in battery can
cause permanent damage to eyes,
burn skin, and eat holes in clothing.
Alwayswear splash-proofsafety
goggles when working near the battery.
Ifbattery acidis splashed in the eyes or
on skin, immediately flush the affected
areafor15 minuteswithlarge
quantities of clean water.Seek
immediate medical aid in the case of
eye contact.Never add acid to a
battery after placing the battery in
service,as this mayresult in hazardous
spattering of battery acid.
NOTICE
Noticecommunicatesinstallation,
operation, or maintenance information
that is important but not hazard related.
Safety decals affixed to the transfer
switch in prominent places advise the
operator or service technician of
potentialhazards andhow toact safely.
The decals are reproduced here to
improve operator recognition. Replace
missing or damaged decals.
TP-5660 11/98Safety Precautions and Instructions I
W ARNING
Hazardous Voltage/
Electrical Shock
W ARNING
W ARNING
Explosion.
Can cause severe injury or death.
Relays in battery charger cause
arcs or sparks.
Locate battery in a well-ventilated
area. Isolate battery charger from
explosive fumes.
Battery gases. Explosion can cause
severe injury or death.Battery
gases can cause an explosion. Do not
smokeor permit flameor spark tooccur
near a battery at any time, particularly
when it is charging. Avoid touching
terminals with tools, etc., to prevent
burns and sparks that could cause an
explosion. Remove wristwatch, rings,
and any other jewelry before handling
battery. Never connect negative (--)
battery cable to positive (+) connection
terminal of starter solenoid. Donot test
battery condition by shorting terminals
together. Sparks could ignite battery
gases or fuel vapors. Ventilate any
compartment containing batteries to
prevent accumulation of explosive
gases. To avoid sparks, do not disturb
battery charger connections while
batteryis charging. Alwaysturnbattery
chargeroffbeforedisconnecting
battery connections. Remove negative
(--) lead first when disconnecting
battery. Reconnect negative (--) lead
last when reconnecting battery.
Hazardous voltage.
Can cause severe injury or death.
Disconnect all power sources before
opening enclosure.
(under 600 Volt)
DANGER
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before
opening enclosure.
(600 Volt and above)
W ARNING
Hazardous voltage.
Can cause severe injury or death.
Disconnect power sources before
servicing.Install barrier after
adjustments,maintenance,or
service.
(under 600 Volt)
DANGER
Hazardous voltage.
Can cause severe injury or death.
Operate generator set only with all
guards and electrical enclosures in
place.
Grounding the transfer switch.
Hazardousvoltagecancause
severe injury or death. Electrocution
is possible whenever electricity is
present. Open main circuit breakers of
all power sources before servicing
equipment. Configure the installation
to electrically ground the transfer
switch and related equipment and
electrical circuits to comply with
applicablecodesandstandards.
Never contact electrical leads or
appliances when standing in water or
on wet ground, as the chance of
electrocution increases under such
conditions.
Installingbatterycharger.
Hazardousvoltagecancause
severe injury or death.Electrical
shock may occur if battery charger is
not electrically grounded.Connect
battery charger enclosure to ground of
a permanent wiring system.As an
alternative,installanequipment
groundingconductorwithcircuit
conductors and connect to equipment
grounding terminal or lead on battery
charger.Perform battery charger
installation as prescribed in equipment
manual.Install battery charger in
compliance with local codes and
ordinances.
Movingrotor.
Hazardous voltage.
Will cause severe injury or death.
Disconnect power sources before
servicing.Install barrier after
adjustments,maintenance,or
servicing.
(600 Volt and above)
Connecting battery and battery
charger.Hazardous voltage can
cause severe injury or death.
Reconnect battery correctly to avoid
electrical shock and damage to battery
charger and battery(ies).Have a
qualified electrician install battery(ies).
TP-5660 11/98II Safety Precautions and Instructions
Installingaccessoriesto
transformer assembly. Hazardous
voltage can cause severe injury or
death. To prevent the possibility of
electrical shock, disconnect harness
plug before installing any accessories
involving connection to transformer
assembly primary terminals 76, 77, 78,
and 79. Terminals are at line voltage!
(Models with E33+, S340, S340+, 340,
R340, or R33 controls only.)
Installingaccessoriesto
transformer assembly. Hazardous
voltage can cause severe injury or
death. To prevent the possibility of
electrical shock, disconnect harness
plug before installing any accessories
which will be connected to transformer
assemblyprimaryterminalson
microprocessorlogicmodels.
Terminals are at line voltage!
Makinglineorauxiliary
connections.Hazardous voltage
can cause severe injury or death. To
prevent the possibility of electrical
shock, deenergize the normal power
source before making any line or
auxiliary connections.
Servicing transfer switch controls
andaccessorieswithinthe
enclosure. Hazardous voltage can
cause severe injury or death.
Disconnect transfer switch controls at
the inline connector to deenergize the
circuit boards and logic circuitry but
allow the transfer switch to continue to
supply power to the load. Disconnect
all power sources to any accessories
mountedwithin the enclosure butwhich
are not wired through the controls and
deenergizedbyinlineconnector
separation.Test circuits with a
voltmeter to verify that they are
unpowered before servicing.
Heavy Equipment
W ARNING
Unbalanced weight.
Improper lift can cause severe
injury or death and/or equipment
damage.
Use adequate lifting capacity.
Never leave transfer switch standing
upright unless it is securely bolted in
place or stabilized.
Shortcircuits.Hazardous
voltage/current can cause severe
injury or death. Short circuits can
cause bodily injury and/or equipment
damage.Do not contact electrical
connections with tools or jewelry while
makingadjustmentsorrepairs.
Remove wristwatch, rings, and jewelry
before servicing equipment.
power sources before servicing. Open
main circuit breakers of all power
sources to the transfer switch and
disable all generator sets as follows:
1) Move all generator set master
controller switches to the OFF position.
2) Disconnect power to all battery
chargers.3) Disconnect all battery
cables, negative(--)leads first.
Reconnectnegative(--)leadslastwhen
reconnecting batterycables after
servicing. Follow these precautions to
prevent starting of generator sets by an
automatic transfer switch, remote
start/stop switch, or engine start
command from a remote computer.
TP-5660 11/98Safety Precautions and Instructions III
Moving Parts
W ARNING
Hazardous voltage.
Can cause severe injury or death.
Operate generator set only with all
guards and electrical enclosures in
place.
Movingrotor.
Notice
NOTICE
Hardware damage! Transfer switch
may use both American Standard and
metric hardware. Use the correct size
tools to prevent rounding of bolt heads
and nuts.
NOTICE
When replacing hardware, do not
substitutewithinferiorgrade
hardware.Screws and nuts are
available in different hardness ratings.
American Standard hardware uses a
seriesofmarkingsand metric hardware
uses a numeric system to indicate
hardness.Check markings on bolt
head and nuts for identification.
NOTICE
Improper operator handle usage!
Use the manual operator handle
provided on the transfer switch for
maintenance purposes only. Return
the transfer switch to the normal
position.Remove manual operator
handle, if used, and store it on the
transfer switch in the place provided
when service is completed.
NOTICE
Foreign materialcontamination!
Covertransferswitchduring
installation to keep dirt, grit, metal drill
chips, etc., out of components. Cover
solenoidmechanismduring
installation.After installation, use
manual operating handle to position
contactor to ensure that it operates
freely. Do not use a screwdriver to
force contactor mechanism.
NOTICE
Electrostatic discharge damage!
Electrostaticdischarge(ESD)
damages electronic circuit boards.
Preventelectrostaticdischarge
damage by wearing an approved
grounding wrist strap when handling
electronic circuit boards or integrated
circuits. An approved grounding wrist
strap provides a high resistance (about
1 megohm), not a direct short, to
ground.
TP-5660 11/98IV Safety Precautions and Instructions
Introduction
This manual provides operation and installation
instructions for Kohler Model ZCS automatic transfer
switchesthatusea40-to3000-amperecontactor asthe
power switching device.
All information in this publication represents data
availableattimeofprint. KohlerCo.reservestherightto
change this literature and the products represented
without incurring obligation.
Read through this manual and carefully follow all
procedures and safety precautions to ensure proper
equipment operation and to avoid bodily injury. Read
and follow the Safety Precautions and Instructions
section at the beginning of this manual. Keep this
manual with equipment for future reference.
Equipment service requirements are minimal but are
veryimportantto safeand efficientoperation;therefore,
inspect parts often and perform required service at the
prescribed intervals. An authorized service distributor
or dealer (authorized service center) should perform
required service to keep equipment in top condition.
List of Related Materials
Thismanualcoversoperationand installation
information for the transfer switch’s power switching
device. Decode the transfer switch part number model
codefrom the transfer switch nameplateand verifythat
the transfer switch’s power switching device matches
that what is shown on the front cover of this manual
before proceeding with operation or installation.
a separate manual.The following table lists the
available electrical controls and the related operation
and installation manual part numbers.
Separate manuals cover service and parts information
for transfer switch power switching devices and
electricalcontrols. Thefollowingtableliststheavailable
manuals and the related manual part numbers.
Transfer switches with microprocessor electrical
controls and communication accessories can be
monitoredand controlledwith a personalcomputer and
software. Thefollowingtableliststheavailablemanuals
and part numbers.
A separate operation and installation manual that
covers information specific to the transfer switch’s
electricalcontrols(logiccontroller)completesoperation
and installation instructions for the transfer switch.
Three types of electrical controls are available on the
Communications Item
Remote Monitoring and Control
Communications (Monitor) Software
Communications KitsTT-847
Operation/
Installation
Manual
TP-5823
ModelZCS transfer switch, and each typeis coveredin
TP-5660 11/98Introduction i
Service Assistance
TransferSwitchIdentificationNumbers
Service Information
For sales, service, or other information about a Kohler
Generator Division product, contact a local authorized
distributor or dealer first.
To locate a local authorized distributor or dealer
D Look on the product or the information includedwith
the product
D Consult the Yellow Pages under the heading
Generators—Electric
D Visit the Kohler Generator Division Web site at
www.kohlergenerators.com
D Call1-800-544-2444(insidetheU.S.A.andCanada)
or 920-565-3381 (outside the U.S.A. and Canada)
Product Identification
To ensure the supply of correct parts and information,
write the product identification numbers in the spaces
below. Record the identification numbers immediately
after unpacking the products so that the numbers are
readily available for future reference.Record the
field-installed kit numbers after installing the kit.
Record the product identification numbers from the
transfer switch nameplate.
Part Number
Serial Number
Accessory NumberAccessory Description
TP-5660 11/98ii Introduction
Section 1. Specifications
1.1Purpose
An automatic transfer switch (ATS) transfers critical
electrical loads from a normal (preferred) source of
electrical power to an emergency (standby) source
when the normal source fails to maintain minimum
voltage and/or frequency levels.
Upon normal source failure, the ATS signals the
generator set to start. When the emergency source
reaches a minimum voltage and/or frequency level, the
ATS transfers the load from the normal source to the
emergency source. The ATS continuously senses the
normalsource and transfers the load backto the normal
sourcewhenthe normalsourcereturns. Aftertransferof
theloadback tothenormal source,theATSremovesthe
generator set start signal, allowing the generator set to
shut down.
1.2Components
A typical transfer switch consists of functional units
mounted in an enclosure with a hinged front door. See
Figure 1-1. The power switching device connects the
load to the normal or emergency sources of power. An
inner panel mounted on theinside of the enclosure door
containsthe electrical controls (logic controller) circuitry
that monitors power sources, controls the power
switching device, and signals the generator to start
when needed. Enclosure door-mounted controls and
indicators allow the operator to control the transfer
switch operation mode and obtain system status
information. A wire harness with inline connectors to
facilitate component replacement and door removal
connects the inner panel to the power switching device.
Controls and indicators on the transfer switch are
determined by the logic controller and installed
accessories.For details see the operation and
installation manual for the logic controller specified by
the part number model code on the transfer switch
nameplate. See Sections 1.3 and 1.4 to determine the
logic controller on the transfer switch.See List of
Related Materials in the Introduction section in this
manual.
5. Controls and indicators (mounted on enclosure door)
6. Neutral lug
3
4
5
TS-001
Figure 1-1. Typical Transfer Switch Components
The power switching device transfers power from the
normal or emergency power source to the load. See
Figure 1-2.The controller electrically actuates the
power switching device to select a power source, and
theswitch mechanically latches inthe selected position.
The switch also includes a provision for manual
mechanical operation in emergency nonpowered
conditions. Within the switch are two sets of multipole
contacts. One set of contacts selects power from the
normal source and the other set selects power from the
emergency source.The two sets of contacts are
mechanically interlocked within the switch, ensuring
that only one set of contacts is closed simultaneously.
Mechanical interlocking ensures load servicing without
cross-coupling of the power sources.
Normal
(Utility)
Power
Switching
Device
Power
Automatic Transfer Switch
To Load
Emergency
(Generator)
Power
Interface
Generator
Start Generator
Logic
Controller
TS-002
Figure 1-2. Typical Transfer Switch Block Diagram
TP-5660 11/98Specifications 1
1.3Nameplate
A nameplate providing characteristic and rating
information that affects operation, installation, and
servicing is attached to the inside of the transfer switch
enclosure door. See Figure 1-3.
Copy the part number into the blank spaces provided in
Figure 1-4 and then use Figure 1-4 to interpret the part
number.
Copy the part number, factory-installed accessory
numbers,and serialnumber fromthe nameplateinto the
spaces provided in the Service Assistance section in
this manual for use when requesting service or parts.
1
AUTOMATICTRANSFER SWITCH
PARTNO.
3
SERIAL NO.
VOLTS
PHASE
HERTZ
1. Location for part number used to identify type of ATS.
2. Location for factory-installed accessory numbers.
3. Location for the ATSserial number.
AMPS
WIRES
POLES
2
TS-003
Figure 1-3. Typical Transfer Switch Nameplate
TP-5660 11/982 Specifications
1.4Part Number Model Code
Use the diagram below to record and interpret the transfer switch part number model code.
Record the transfer switch part number in the boxes below. The transfer switch part number defines
characteristics and ratings as explained in the accompanying chart.
Type of Switch Type of Logic Voltage& Frequency
Number of
Poles
Number of
Wires
Type of
EnclosureAmperage Rating Code
Kohler Part Number Key
This chart explains the Kohler transfer switch part numbering code system.
The sample part number shown is for a standard contactor power switch with
M340+ logic rated at 600 volts, 60 hertz, 3-phase, 3-pole, and 4 wires in a
NEMA Type 1 enclosure with a contactor rating of 1000 amperes.
Classification of Power Switch
Z: Power Switch
Type of Power Switch
C: Contactor
Type of Switch
S: Standard
Type of Electrical Controls (Logic Controller)
1: S340+
2: E33+
3: S340+ with Programmed Transition
4: E33+ with Programmed Transition
5: M340+
6: M340+ with Programmed Transition
Voltage Code
60: 600 Volt, 60 Hz66: 480 Volt, 60 Hz
62: 120 Volt, 60 Hz68: 208 Volt, 60 Hz
63: 220 Volt, 50 Hz71: 380 Volt, 50/60 Hz
64: 240 Volt, 60 Hz
SAMPLE PART NUMBER
ZCS-560341-1000
Number of Poles
2: 2 Pole, 1 Phase
3: 3 Pole, 3 Phase
Number of Wires
3: 3 Wire
4: 4 Wire
Enclosure
0 = Open
1 = NEMA Type 1
2 = NEMA Type 12
3 = NEMA Type 3R
Amperes
Numbers Indicate Ampere Rating of Switch
4: 3 Pole, 1 Phase
6: 4 Pole, Fully Rated
Figure 1-4. Transfer Switch Model Designations
TP-5660 11/98Specifications 3
1.5Standard Features
UL100
8
Max.FuseSiz
e
SwitchRatin
g
Max.FuseSiz
e
The standard features listed here are for the ZCS
contactor power switching device. Refer to the logic
controller operationand installationmanual for
controller specifications. See List of Related Materials
in the Introduction section in this manual.
D Provided as a complete automatic transfer switch
D Two-pole, three-pole and four-pole
D Four-pole—fully rated
D Can be operated manually when unpowered
D Twonormallyopen (N.O.) and two normallyclosed
(N.C.) main shaft auxiliary contacts
D Withstand and closing current ratings as shown
below.
with E33+ (solid state logic), S340+ (solid state
logic), or M340+ (microprocessor logic) controller
1.6Ratings
in various enclosures
D Meets UL and CSA standards
D Voltage ratings up to 600 vac
D Amperage ratings for Programmed Transition
Switches from 40 to 3000 amperes
D Amperage ratings for Standard Switches from
600 to 3000 amperes
D Switching device electrically and mechanically
interlocked
Withstand and Closing Current Ratings per UL 1008 and CSA *
* UL1008 listed at 480 vac and CSA listed at 600 vac.
(amps)
@ 480 VAC@ 600 VAC@ 480 VAC@ 600 VAC
The following tables provide information on contactor
withstandandclosingcurrentratings(WCR).
Figure 1-5 provides WCR when used with any
current-limiting fuse or any overcurrent protective
device. Figure 1-6 and Figure 1-7 provides WCR when
coordinatedwithspecificmanufacturer’scircuit
breakers or fuse types. Figure 1-6 has ratings for
480 V maximum and apply to both UL and CSA listings.
Figure 1-7 has ratings for 600 V maximum and apply to
a CSA listing only.
Figure 1-7. Withstand and Closing Current Ratings (WCR) With Coordinated Circuit Breakers or Fuses,
600 V Maximum, CSA Listings
TP-5660 11/986 Specifications
1.7Application Data
Siz
e
Siz
e
See Figure 1-8 for application data including the range of wire sizes for the transfer switch’s power terminals.
AL/CU UL-listed Solderless Screw-type Terminals for External Power Connections
Switch
(amps)
401#14 AWG to #2 AWG8004#2 AWG to 600 MCM
80--1001#14 AWG to 1/0 AWG10004#2 AWG to 600 MCM
1501#8 AWG to 3/0 AWG12004#2 AWG to 600 MCM
2251#6 AWG to 250 MCM1600Bus Bar Connection
2601#6 AWG to 350 MCM2000Bus Bar Connection
4001#4 AWG to 600 MCM2500Bus Bar Connection
6002#2 AWG to 600 MCM3000Bus Bar Connection
Normal, Emergency, and Load Terminals
Cables per PoleRange of Wire Sizes
Figure 1-8. Application Data
Switch
(amps)
Normal, Emergency, and Load Terminals
Cables per PoleRange of Wire Sizes
TP-5660 11/98Specifications 7
Notes
TP-5660 11/988 Specifications
Section 2. Operation
W ARNING
Hazardous voltage.
Can cause severe injury or death.
Disconnect all power sources before
opening enclosure.
(under 600 Volt)
DANGER
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before
opening enclosure.
(600 Volt and above)
Have preventive maintenance performed on the
transferswitch at regularintervals afterinstallation. See
Section 4 for preventive maintenance.
Contact an authorized service center to inspect and
service the transfer switch when any wear, damage,
deterioration, or malfunction of the transfer switch or its
components is evident or suspected; DO NOT
ENERGIZE THE SWITCH.
2.1Startup
Use this section when power sources have been
disconnected to the transfer switch for an extended
period after maintenance or service of the standby
system, NOT FOR INITIAL STARTUP.
For initial startup, follow the instructions in the
installation section of the operation and installation
manualforthelogiccontrollerand
Section 6—Installation in this manual.
Follow the following steps to power up the transfer
switch and prepare it for automatic operation.
Powerup Procedure
1. Move the generator set master switch to the OFF
position to prevent the generator set from starting.
2. Ensure that BOTH the normal and emergency
power sources are disconnected by opening
upstream circuit breakers or switches to the
transfer switch.
3. Open the enclosure and check that the wire
harnesses for the power switching device and the
controller are plugged together at the inline
disconnect plugP1. See thedrawings in Section 5
to locate the disconnect plug on the contactor.
4. Follow the manual operation procedure to prepare
the transfer switch for automatic operation. See
Section 2.3.
5. Close and lock the transfer switch enclosure door.
6. Prepare the generator set that provides standby
power for operation. Check the oil level, coolant
level, fuel supply, batteries, and items specified by
the generator set installation or operation checklist
or manual.
7. Move the generator set masterswitch to the AUTO
position. The generator set should start.
8. When loads can be safely energized, reapply
power sources to the transfer switch by closing
circuit breakers or switches.
NOTE
Wheninitially applyingpower tothetransfer switch,
the engine start contacts remain closed signalling
the generator to run until the ATS’s Time Delay
Engine Cooldown (TDEC), if equipped, ends.
9. Perform an automatic operation test. See the logic
controller operation and installation manual.
Refer to the logic controller operation and installation
manual for other startup and setup procedures.
2.2Automatic Operation
The logic controller installed in the unit provides
automatic operation.Refer to the logic controller
operation and installation manual for automatic
operation details and procedures. See List of Related
Materials in the Introduction section in this manual.
TP-5660 11/98Operation 9
Thetransferswitchlogiccontrollercircuitry,
programming, or accessories determine when a power
source is acceptable, has failed, or has been restored
and operates accordingly. Failure of a power source
occurswhen the the voltage and/or frequency on oneor
more phases fall below preset limits. A power source is
acceptable when the voltage and/or frequency on all
monitored phases rise above preset levels. A power
source is restored when it becomes acceptable after
failing.Typical ATS operation is divided into two
sequences.
D Failure of the normal power source and the
resulting transfer to the emergency source or
Emergency.
D Restorationof the normalpower sourceandthe
resulting transfer back to the normal source or
Normal.
The following sections briefly explain these sequences
of operation.Installed controller accessories can
change the sequence of operation.See the logic
controller operationand installationmanual for
specifications on time delays, voltage and frequency
limits, control adjustments, and accessory information.
2.2.2Restoration of Normal Power
After normal power source restoration, the controller
starts a time delay called Time Delay Emergency to
Normal(TDEN). Ifthe normal power source fails before
TDEN ends, the time delay resets. TDEN ensures
normalpowersourcestabilizationbeforeload
reconnection.
When the controller determines that the normal power
source has maintained an acceptable level and TDEN
ends, the controller signals the power switching device
to reconnect the load to the normal source.
Afterload transferthe switchmechanically latchesin the
normal position and the controller starts a time delay
called Time Delay Engine Cooldown (TDEC), if
equipped. TDECallowsthe engineand generatorto run
unloadedand cooldownbefore shutdown. WhenTDEC
expires the controller signals the generator set to shut
down.
The generator set controller may allow the generator to
run for an additional cooldown period after the transfer
switch signals a shutdown. Consult the generator set
operation manual for more information.
2.2.1Failure of Normal Power
When the normal power source fails, the controller
starts a time delay called Time Delay Engine Start
(TDES).TDES prevents unnecessary generator
startup during short normal power interruptions. If the
normalpower source is restoredbefore TDES ends, the
controller resets the time delay. If the normal power
failure persists and TDES ends, the controller issues a
signal to start the standby (emergency) generator to
produce the emergency power source.
After signalling the generator to start, the controller
monitors the emergency power source.When the
controller determines that the emergency (generator)
power source is acceptable it starts a time delay called
Time Delay Normal to Emergency (TDNE).TDNE
allows emergency power source stabilization before
loadconnection and prevents nuisance transfersduring
short power interruptions.When TDNE ends the
controller signals the transfer switch toconnect the load
to the emergency source.
Afterload transferthe switchmechanically latchesin the
emergency position, supplying emergency source
power to the load until normal power source restoration
and stabilization.
TP-5660 11/9810 Operation
2.3Manual Operation
To test or troubleshoot the transfer switch, or when the
controller fails in an emergency situation, manually
operatethe power switching deviceas described below.
W ARNING
W ARNING
Accidental starting.
Can cause severe injury or death.
Disconnect battery cables before
working on generator set. (Remove
negative(--)leadfirstwhen
disconnecting battery.Reconnect
negative(--)leadlastwhen
reconnecting battery.)
Disabling the generator set.Accidental starting can
cause severe injury or death.Before working on the
generator set or connected equipment, disable the generator
set as follows: 1) Move the generator set master switch to the
OFF position. 2) Disconnect power to the battery charger.
3) Remove battery cables, negative (--)lead first. Reconnect
negative(--)lead last whenreconnecting battery. Follow these
precautions to prevent starting of generator set by an
automatic transfer switch, remote start/stop switch, or engine
start command from a remote computer.
W ARNING
Hazardous voltage.
Can cause severe injury or death.
Disconnect all power sources before
opening enclosure.
(under 600 Volt)
DANGER
Hazardous voltage.
Can cause severe injury or death.
Disconnect power sources before
servicing.Install barrierafter
adjustments,maintenance,or
service.
(under 600 Volt)
DANGER
Hazardous voltage.
Will cause severe injury or death.
Disconnect power sources before
servicing.Install barrierafter
adjustments,maintenance,or
servicing.
(600 Volt and above)
Servicing the transfer switch. Hazardous voltage can
cause severe injury or death. Deenergizeall powersources
before servicing. Open main circuit breakers of all power
sourcesto the transferswitch and disable all generatorsets as
follows: 1) Move all generator set master controller switches
to the OFF position. 2) Disconnect power to all battery
chargers. 3) Disconnect all battery cables, negative (--)leads
first. Reconnect negative (--) leads last when reconnecting
battery cables after servicing. Follow these precautions to
prevent starting of generator sets by an automatic transfer
switch, remote start/stop switch, or engine start command
from a remote computer.
NOTICE
Improper operator handle usage! Use the manual operator
handle provided on the transfer switch for maintenance
purposes only. Return the transfer switch to the normal
position. Remove manualoperatorhandle, if used,andstore it
on the transfer switch in the place provided when service is
completed.
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before
opening enclosure.
(600 Volt and above)
A contactor in normal and serviceable condition
transfers smoothly without binding when operated
manually. Do notplace the transfer switchinto service if
the contactor does not manually operate smoothly
without binding; contact an authorized service center to
NOTE
service the contactor.
TP-5660 11/98Operation 11
2.3.1Programmed Transition Switch,
40--260 Amps
Manual Operation Procedure
1. Prevent the generator set, which provides the
emergency power source to the transfer switch,
from starting by moving the generator set master
switch to the OFF position; disconnecting power to
the generator engine start battery charger, if
installed; and disconnecting all generator engine
start batteries, negative (--) leads first.
2. Disconnect BOTH the normal and emergency
power sources by opening upstream circuit
breakers or switches to the transfer switch.
3. Open the transfer switch enclosure door.
4. Set the disconnect switch (DS) to the INHIBIT
position to preventthe controller fromenergizing the
solenoid(s). See Figure 2-1.
5. Attach the manual operating handle to the switch
lever.
6. If the handleis notin the middle(off) position,move
thehandle upor downtobring itinto themiddle(off)
position.The switch should operate smoothly
without binding.Both normal and emergency
sources are disconnected from the load in the
middle (off) position.
7. Locate the mid-position manual release handle on
the left side of the switch. See Figure 2-1.
8. Pull and hold the mid-position manual release
handle to the left. This releases the mechanism
that allows manual switching to the normal or
emergency source from the off position. Move the
handle up to the normal position to manually
connect the load to the normal source or down to
the emergency position to manually connect the
load to the emergency source. The switch should
operate smoothly in both directions without
binding.
9. Manually connect the load to the normal source for
automatic operation.
1
4
1. Mid-position manual release handle
2. Switch lever, middle (off) position shown
3. Disconnect switch, INHIBIT position shown
4. Manual operating handle, typical
NORMAL
LOCK
LOCK
EMERGENCY
AUTO INHIBIT
Figure 2-1. Manual Operation, Programmed
Transition Switch 40--260Amps
2
3
5660201
10. Remove and return the manual operator handle to
the holder provided.
11. Move the disconnect switch (DS) to the AUTO
position for automatic operation.
12. Close and lock the transfer switch enclosure door.
13. Reconnect power supplies to the transfer switch.
NOTE
Wheninitially applyingpower tothetransfer switch,
the engine start contacts remain closed signalling
the generator to run until the ATS’s Time Delay
Engine Cooldown (TDEC), if equipped, ends.
14. Reconnect generator engine start battery cables,
negative (--) leads last; reconnect power to the
generator engine start battery charger, if installed;
and move the generator set master switch to the
AUTO (automatic) position. The generator may
start and run for a while (see NOTE above).
TP-5660 11/9812 Operation
2.3.2Programmed Transition Switch,
400--3000 Amps
Manual Operation Procedure
1. Prevent the generator set, which provides the
emergency power source to the transfer switch,
from starting by moving the generator set master
switch to the OFF position; disconnecting power to
the generator engine start battery charger, if
installed; and disconnecting all generator engine
start batteries, negative (--) leads first.
2. Disconnect BOTH the normal and emergency
power sources by opening upstream circuit
breakers or switches to the transfer switch.
3. Open the transfer switch enclosure door.
4. Set the disconnect switch (DS) to the INHIBIT
position to preventthe controller fromenergizing the
solenoid(s). See Figure 2-2.
1
NORMAL
LOCK
LOCK
5. Attach the manual operator handle to the normal
switchleverand moveit uptothe normalposition to
manually connect the load to the normal source
andmove itdown todisconnect. Theswitchshould
operate smoothly in both directions without
binding.
6. Attach the manual operator handle to the
emergency switch lever. Move the handle down to
the emergency position to manually connect the
load to the emergency source and move it up to
disconnect. Theswitchshould operatesmoothly in
both directions without binding.
NOTE
A mechanical interlock prevents simultaneous
emergency and normal source connection to the
load. Both sources can be manually disconnected
from the load simultaneously.
7. Manually connect the load to the normal source for
automatic operation.
8. Remove and return the manual operator handle to
the holder provided.
9. Move the disconnect switch (DS) to the AUTO
position for automatic operation.
10. Close and lock the transfer switch enclosure door.
11. Reconnect power supplies to the transfer switch.
2
LOCK
4
1. Normal switch lever, normal source shown connected to load
2. Emergency switchlever,emergencysourceshown
disconnected from load
3. Disconnect switch, INHIBIT position shown
4. Manual operating handle, typical
LOCK
EMERGENCY
AUTO
INHIBIT
3
5660202
Figure 2-2. Manual Operation, Programmed
Transition Switch 400--3000Amps
NOTE
Wheninitially applyingpower tothetransfer switch,
the engine start contacts remain closed signalling
the generator to run until the ATS’s Time Delay
Engine Cooldown (TDEC), if equipped, ends.
12. Reconnect generator engine start battery cables,
negative (--) leads last; reconnect power to the
generator engine start battery charger, if installed;
and move the generator set master switch to the
AUTO (automatic) position. The generator may
start and run for a while (see NOTE above).
TP-5660 11/98Operation 13
2.3.3Standard Switch, 800--3000 Amps
Manual Operation Procedure
1. Prevent the generator set, which provides the
emergency power source to the transfer switch,
from starting by moving the generator set master
switch to the OFF position; disconnecting power to
the generator engine start battery charger, if
installed; and disconnecting all generator engine
start batteries, negative (--) leads first.
5. Attach the manual operating handle to the switch
lever.
6. Move the handle up to the normal position to
connect the load to the normal source or down to
the emergency position to connect the load to the
emergency source.Switch should operate
smoothly between both positions without binding.
7. Manually connect the load to the normal source for
automatic operation.
2. Disconnect BOTH the normal and emergency
power sources by opening upstream circuit
breakers or switches to the transfer switch.
3. Open the transfer switch enclosure door.
4. Set the disconnect switch (DS) to the INHIBIT
position to preventthe controller fromenergizing the
solenoid(s). See Figure 2-3.
1
NORMAL
LOCK
LOCK
EMERGENCY
8. Remove and return the manual operator handle to
the holder provided.
9. Move the disconnect switch (DS) to the AUTO
position for automatic operation.
10. Close and lock the transfer switch enclosure door.
11. Reconnect power supplies to the transfer switch.
NOTE
Wheninitially applyingpower tothetransfer switch,
the engine start contacts remain closed signalling
the generator to run until the ATS’s Time Delay
Engine Cooldown (TDEC), if equipped, ends.
12. Reconnect generator engine start battery cables,
negative (--) leads last; reconnect power to the
generator engine start battery charger, if installed;
and move the generator set master switch to the
AUTO (automatic) position. The generator may
start and run for a while (see NOTE above).
3
AUTOINHIBIT
1. Switch lever, normal source shown connected to load
2. Disconnect switch, INHIBIT position shown
3. Manual operating handle, typical
2
5660203
Figure 2-3. Manual Operation, Standard Switch
600--3000 Amps
TP-5660 11/9814 Operation
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.