Kohler 5E, 6EF, 4EF, 7.3E Service Manual

Page 1
Service
Marine Generator Sets
Models:
5E/4EF
7.3E/6EF
TP-5986 4/03b
Page 2
Product Identification Information
Generator Set Identification Numbers
Record the product identification numbers from the generator set nameplate(s).
Model Designation
Specification Number
Serial Number
Accessory Number Accessory Description
Engine Identification
Record the product identification information from the engine nameplate.
Manufacturer
Model Designation
Serial Number
x:in:007:001a
Page 3
Table of Contents
Safety Precautions and Instructions I.........
Introduction i...............................
Service Assistance ii.........................
Service Information ii..............................
Product Information ii..............................
Service Parts/Publications iii..................
Routine Service Parts iii............................
List of Related Literature iii.........................
Section 1 Specifications 1....................
1.1 General 1..................................
1.2 Engine 1...................................
1.3 Fuel 1......................................
1.4 Cooling 1...................................
1.5 Generator 2.................................
1.6 Torque 2...................................
1.7 Service Views 3.............................
Section 2 Scheduled Maintenance 5...........
2.1 General 5..................................
2.2 Lubrication System 5.........................
Section 3 Intake and Exhaust System 7........
3.1 Backfire Flame Arrestor 7.....................
3.2 Exhaust 7..................................
Section 4 Fuel System 9.....................
4.1 General 9..................................
4.2 Float Bowl Vent System 9.....................
4.3 Fuel Pump and Filter 9.......................
4.4 Fuel Pump Troubleshooting 10.................
4.5 Carburetor Troubleshooting 10.................
4.5.1 Hard Starting 10......................
4.5.2 Stalling 10...........................
4.5.3 Flooding 11..........................
4.5.4 Hunting 11...........................
4.5.5 Leaking Carburetor 11.................
4.6 Governor 60 Hz to 50 Hz Conversion 11.........
Section 5 Cooling System 13..................
5.1 General 13..................................
5.2 Closed Heat Exchanger 14.....................
5.3 Check and Fill Coolant 14.....................
5.4 Flush and Clean Cooling System 14.............
5.5 Impeller 15..................................
5.6 Siphon Break 16..............................
5.7 Anticorrosion Zinc Anode 17...................
5.8 Generator Storage 18.........................
Section 6 Controller Troubleshooting 19........
6.1 Sequence of Operation 19.....................
6.1.1 Start 19.............................
6.1.2 Run 19..............................
6.1.3 Stop 20..............................
6.2 Engine Safety Shutdown Switches 20...........
6.2.1 Low Oil Pressure (LOP) Shutdown 20...
6.2.2 Loss of Coolant Switch (LCS)
Shutdown 20.........................
6.2.3 High Engine Temperature Switch
(HET) Shutdown 20...................
6.2.4 Controller Circuit Board 20.............
6.2.5 Troubleshooting 21...................
Section 7 Generator Troubleshooting 25........
7.1 General 25..................................
7.1.1 Troubleshooting 25...................
7.1.2 Separate Excitation 26................
7.2 PowerBoost IIIE Voltage Regulators 27..........
7.2.1 Voltage Regulator Test 27..............
7.2.2 Voltage Regulator Adjustment 28.......
7.3 Rotor 29.....................................
7.4 Stator 29....................................
7.5 Brushes 31..................................
Section 8 Component Troubleshooting 33......
8.1 Engine/Generator Components 33..............
8.2 Remote Panels (Optional) 35...................
Section 9 Generator Disassembly/
Reassembly 37...............................
9.1 Disassembly 37..............................
9.2 Collector Ring and Bearing Replacement 39......
9.3 Reassembly 39...............................
Section 10 Wiring Diagrams and Voltage
Reconnection 41..............................
10.1 Schematic Wiring Diagram 42..................
10.2 Point-to-Point Wiring Diagram 43...............
10.3 Reconnection Diagram 100--120 V,
60 & 50 Hz 44................................
10.4 Reconnection Diagram 100--120/200--240 V,
60 & 50 Hz 44................................
10.5 Reconnection Diagram 220--240 V, 50 Hz 44.....
10.6 Remote Start Panel 44........................
10.7 Remote Start and Two-Meter Panel 45..........
10.8 Remote Start and Four-Meter Panel 45..........
Appendix A Abbreviations A-1................
Appendix B Common Hardware Application
Guidelines A-3...............................
Appendix C General Torque
Specifications A-4............................
Appendix D Common Hardware
Identification A-5.............................
Appendix E Common Hardware List A-6.......
TP-5986 4/03 Table of Contents
Page 4
Page 5
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS. Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS.
This manual has several types of safety precautions and instructions: Danger, Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a hazard that will cause severe
personal injury,death,orsubstantial property damage.
WARNING
Warning indicates the presence of a hazard that can cause severe
personal injury,death, or substantial property damage.
CAUTION
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage.
NOTICE
Notice communicates installation, operation, or maintenance information that is safety related but not hazard related.
Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals.
Accidental Starting
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before
working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Place the generator set start/stop switch in the STOP position. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
Battery
WARNING
Sulfuric acid in batteries. Can cause severe injury or death.
Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
Battery electrolyte is a diluted sulfuric acid. Batteryacid can cause severe injury or death. Battery acid
can cause blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid.
Battery acid cleanup. Battery acid can cause severe injury or death.
Battery acid is electrically conductive and corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a containerwith4L(1gal.)ofwaterand mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area.
Battery gases. Explosion can cause severe injury or death. Battery gases
can cause an explosion. Do not smoke or permitflames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metalsurface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases.
TP-5986 4/03 Safety Precautions and Instructions I
Page 6
Battery short circuits. Explosion can cause severe injury or death.
Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (-- ) lead first when disconnecting the battery. Reconnect the negative (-- ) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Engine Backfire/Flash Fire
WARNING
Fire. Can cause severe injury or death.
Do not smoke or permit flames or sparks near fuels or the fuel system.
Servicing the fuel system. A flash fire can cause severe injury or death.
Do not smoke or permit flames or sparks near the carburetor, fuel line, fuel filter, fuel pump, or other potential sources of spilled fuels or fuel vapors. Catch fuels in an approved container when removing the fuel line or carburetor.
Servicing the backfire flame arrester. A sudden backfire can cause severe injury or death. Do not operate the
generator set with the backfire flame arrester removed.
Combustible materials. A sudden flash fire can cause severe injury or death. Do not smoke or permit flames
or sparks near the fuel system. Keep the compartment and the generator set clean and free of debris to minimize the risk of fire. Wipe up spilled fuels and engine oil.
Combustible materials. A fire can cause severe injury or death.
Generator set engine fuels and fuel vapors are flammable and explosive. Handle these materials carefully to minimize the risk of fire or explosion. Equip the compartment or nearby area with a fully charged fire extinguisher. Select a fire extinguisher rated ABC or BC for electrical fires or as recommended by the local fire code or an authorized agency. Train all personnel on fire extinguisher operation and fire prevention procedures.
Exhaust System
WARNING
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in exhaust gases. Carbon monoxide poisoning symptoms include but are not limited to the following:
D Light-headedness, dizziness D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate or speak clearly, blurred vision
D Stomachache, vomiting, nausea If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.
Inspecting the exhaust system. Carbon monoxide can cause severe nausea, fainting, or death. For the
safety of the craft’s occupants, install a carbon monoxide detector. Consult the boat builder or dealer for approved detector location and installation. Inspect the detector before each generatorset use. In addition to routine exhaust system inspection, test the carbon monoxide detector per the manufacturer’s instructions and keep the detector operational at all times.
Operating the generator set. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide
is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Use the following precautions when installing and operatingthe generator set. Do not installthe exhaust outlet where exhaust can be drawn in through portholes, vents, or air conditioners. If the generator set exhaust discharge outlet is near the waterline, water could enter the exhaust discharge outlet and close or restrict the flow of exhaust. Never operate the generator set without a functioning carbon monoxide detector. Be especially careful if operating the generator set when moored or anchored under calm conditions because gases may accumulate. If operating the generator set dockside, moor the craft so that the exhaust discharges on the lee side (the side sheltered from the wind). Always be aware of others, making sure your exhaust is directed away from other boats and buildings. Avoid overloading the craft.
II Safety Precautions and Instructions TP-5986 4/03
Page 7
Fuel System
WARNING
Explosive fuel vapors can cause severe injury or death. Ta k e
additional precautions when using the following fuels:
Gasoline—Store gasoline only in approved red containers clearly marked GASOLINE.
Hazardous Noise
CAUTION
Explosion. Gasoline vapors can cause explosion and severe injury or death.
Before starting the generator set, operate the blower 4 minutes and check the engine compartment for gasoline vapors.
WARNING
Explosive fuel vapors. Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly
explosive. Use extreme care when handling and storing fuels. Store fuels in a well-ventilated area away from spark-producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts or from sparks. Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors. Keep the fuel lines and connections tight and in good condition. Do not replace flexible fuel lines with rigid lines. Use flexible sections to avoid fuel line breakage caused by vibration. Do not operate the generator set in the presence of fuel leaks, fuel accumulation, or sparks. Repair fuel systems before resuming generator set operation.
Draining the fuel system. Explosive fuel vapors can cause severe injury or death. Spilled fuel can cause an
explosion. Use a container to catch fuel when drainingthe fuel system. Wipe up spilled fuel after draining the system.
Installing the fuel system. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an
explosion. Do not modifythe tank or the propulsion engine fuel system. Equip the craft with a tank that allows one of the two pickup arrangements described in the installation section. The tank and installation must conform to USCG Regulations.
Pipe sealant. Explosive fuel vapors can cause severe injury or death.
Fuel leakage can cause an explosion. Use pipe sealant on all threaded fittings to prevent fuel leakage. Use pipe sealant that resists gasoline, grease, lubrication oil, common bilge solvents, salt deposits, and water.
Ignition-protected equipment. Explosive fuel vapors can cause severe injury or death. Gasoline
vapors can cause an explosion. USCG Regulation 33CFR183 requires that all electrical devices (ship-to-shore transfer switch, remote start panel, etc.) must be ignition protected when used in a gasoline and gaseous-fueled environment. The electrical devices listed above are not ignition protected and are not certified to operate in a gasoline and gaseous-fueled environment such as an engine room or near fuel tanks. Acceptable locations are the wheelhouse and other living areas sheltered from rain and water splash.
Hazardous noise. Can cause hearing loss.
Never operate the generator set without a muffler or with a faulty exhaust system.
Engine noise. Hazardous noise can cause hearing loss. Generator sets
not equipped with sound enclosures can produce noise levels greater than 105 dBA. Prolonged exposure to noise levels greater than 85 dBA can cause permanent hearing loss. Wear hearing protection when near an operating generator set.
Hazardous V oltage/Electrical Shock
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
CAUTION
Welding the generator set. Can cause severe electrical equipment damage.
Moving rotor.
TP-5986 4/03 Safety Precautions and Instructions III
Never weld components of the generator set without first disconnecting the battery, controller wiring harness, and engine electronic control module (ECM).
Page 8
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution
is possible whenever electricity is present. Open the main circuit breakers of all power sources before servicing the equipment. Configure the installation to electrically ground the generator set, transfer switch, and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Disconnecting the electrical load. Hazardous voltage can cause severe injury or death. Disconnect
the generator set from the load by opening the line circuit breaker or by disconnecting the generator set output leads from the transfer switch and heavily taping the ends of the leads. High voltage transferred to the load during testing may cause personal injury and equipment damage. Do not use the safeguard circuit breaker in place of the line circuit breaker. The safeguard circuit breaker does not disconnect the generator set from the load.
Welding the generator set. Can cause severe electrical equipment damage. Before welding the generator
set perform the following steps: (1) Remove the battery cables, negative (--) lead first. (2) Disconnect all engine electronic control module (ECM) connectors. (3) Disconnect all generator set controller and voltage regulator circuit board connectors. (4) Disconnect the engine battery­charging alternator connections. (5) Attach the weld ground connection close to the weld location.
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can
cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
Testing the voltage regulator. Hazardous voltage can cause severe injury or death. High voltage is
present at the voltage regulator heat sink. To prevent electrical shock do not touch the voltage regulator heat sink when testing the voltage regulator.
(PowerBoostt, PowerBoostt III, and PowerBoostt V voltage regulator models only)
Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death.
Connect the generator set to the building/marina electrical system only through an approved device and after the building/marina main switch is opened. Backfeed connections can cause severe injury or death to utility personnel working on power lines and/or personnel near the work area. Some states and localities prohibit unauthorized connection to the utility electrical system. Install a ship-to-shore transferswitch to prevent interconnection of the generator set power and shore power.
Testing live electrical circuits. Hazardous voltage or current can cause severe injury or death. Have
trained and qualified personnel take diagnostic measurements of live circuits. Use adequately rated test equipment with electrically insulated probes and follow the instructions of the test equipment manufacturer when performing voltage tests. Observe the following precautions when performing voltage tests: (1) Remove all jewelry. (2)Stand on a dry, approved electrically insulated mat. (3) Do not touch the enclosure or components inside the enclosure. (4) Be prepared for the system to operate automatically.
(600 volts and under)
Hot Parts
WARNING
Hot coolant and steam. Can cause severe injury or death.
Before removing the pressure cap, stop the generator set and allow it to cool. Then loosen the pressure cap to relieve pressure.
WARNING
Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
Checking the coolant level. Hot coolant can cause severe injury or death. Allow the engine to cool.
Release pressure from the cooling system before removing the pressure cap. To release pressure, cover the pressure cap with a thick cloth and then slowly turn the cap counterclockwise to the first stop. Remove the cap after pressure has been completely released and the engine has cooled. Check the coolant level at the tank if the generator set has a coolant recovery tank.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts.
The engine and exhaust system components become extremely hot during operation.
IV Safety Precautions and Instructions TP-5986 4/03
Page 9
Moving Parts
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
WARNING
Rotating parts. Can cause severe injury or death.
Operate the generator set only when all guards, screens, and covers are in place.
WARNING
Airborne particles. Can cause severe injury or blindness.
Wear protective goggles and clothing when using power tools, hand tools, or compressed air.
Moving rotor.
Tightening the hardware. Flying projectiles can cause severe injury or death. Loose hardware can cause
the hardware or pulley to release from the generator set engine and can cause personal injury. Retorque all crankshaft and rotor hardware after servicing. Do not loosen the crankshaft hardware or rotor thruboltwhen making adjustments or servicing the generator set. Rotate the crankshaft manually in a clockwise direction only. Turning the crankshaft bolt or rotor thrubolt counterclockwise can loosen the hardware.
Servicing the generator set when it is operating. Exposed moving parts can cause severe injury or death.
Keep hands, feet, hair, clothing, and test leads away from the belts and pulleys when the generator set is running. Replace guards, screens, and covers before operating the generator set.
Sound shield removal. Exposed moving parts can cause severe injury or death. The generator set
must be operating in order to perform some scheduled maintenance procedures. Be especially careful if the sound shield has been removed, leaving the belts and pulleys exposed.
(Sound-shield-equipped models only)
Notice
NOTICE
This generator set has been rewired from its nameplate voltage to
NOTICE
Voltage reconnection. Affix a notice to the generator set after reconnecting the set to a voltage different from the voltage on the nameplate. Order voltage reconnection decal 246242 from an authorized service distributor/dealer.
NOTICE
Hardware damage. The engine and generator set may use both American Standard and metric hardware. Use the correct size tools to prevent rounding of the bolt heads and nuts.
NOTICE
When replacing hardware, do not substitute with inferior grade hardware. Screws and nuts are
available in different hardness ratings. To indicate hardness, American Standard hardware uses a series of markings, and metric hardware uses a numeric system. Check the markings on the bolt heads and nuts for identification.
NOTICE
Fuse replacement. Replace fuses with fuses of the same ampere rating and type (for example: 3AB or 314, ceramic). Do not substitute clear glass-type fuses for ceramic fuses. Refer to the wiring diagram when the ampere rating is unknown or questionable.
NOTICE
Saltwater damage. Saltwater quickly deteriorates metals. Wipe up saltwater on and around the generator set and remove salt deposits from metal surfaces.
TP-5986 4/03 Safety Precautions and Instructions V
246242
Page 10
Notes
VI Safety Precautions and Instructions TP-5986 4/03
Page 11
Introduction
This manual provides troubleshooting and repair instructions for 5E/4EF and 7.3E/6EF model generator sets, controllers, and accessories.
Refer to the engine service manuals (TP-6002 and TP-6008) for generator set engine service information.
This manual may be used for models not listed on the front cover.
Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this publication and the products represented without notice and without any obligation or liability whatsoever.
Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury. Read and follow the Safety Precautions and Instructions section at the beginning of this manual. Keep this manual with the equipment for future reference.
The equipment service requirements are very important to safe and efficient operation. Inspect the parts often and perform required service at the prescribed intervals. Maintenance work must be performed by appropriately­skilled and suitably-trained maintenance personnel, familiar with generator set operation and service.
Introduction iTP-5986 4/03
Page 12
Service Assistance
For professional advice on generator power requirements and conscientious service, please contact your nearest Kohler distributor or dealer.
D Consult the Yellow Pages under the heading
Generators—Electric
D Visit the Kohler Power Systems website at
KohlerPowerSystems.com
D Look at the labels and stickers on your Kohler product
or review the appropriate literature or documents included with the product
D Call toll free in the US and Canada 1-800-544-2444
D Outside the US and Canada, call the nearest regional
office
Africa, Europe, Middle East
London Regional Office Langley, Slough, England Phone: (44) 1753-580-771 Fax: (44) 1753-580-036
Asia Pacific
Power Systems Asia Pacific Regional Office Singapore, Republic of Singapore Phone: (65) 264-6422 Fax: (65) 264-6455
China
North China Regional Office, Beijing Phone: (86) 10 6518 7950
(86) 10 6518 7951 (86) 10 6518 7952
Fax: (86) 10 6518 7955
East China Regional Office, Shanghai Phone: (86) 21 6288 0500 Fax: (86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office Bangalore, India Phone: (91) 80 3366208
(91) 80 3366231
Fax: (91) 80 3315972
Japan, Korea
North Asia Regional Office Tokyo, Japan Phone: (813) 3440-4515 Fax: (813) 3440-2727
Latin America
Latin America Regional Office Lakeland, Florida, USA Phone: (863) 619-7568 Fax: (863) 701-7131
X:in:008:001a
TP-5986 4/03ii Introduction
Page 13
Service Parts/Publications
Routine Service Parts
The following table contains a list of recommended spare parts. Contact your Kohler generator distributor/dealer for a complete list of service parts for your generator set.
Part Description Part Number
Battery Charging Fuse (25 amp) 262389
Input Fuse (10 amp) 223316
Oil Filter 359771
Seawater Pump Impeller Kit 359978
Spark Plug For Engine Model AS 04
Spark Plug For Engine Model BS 04
Spray Paint (White) 221335
Touch-Up Paint (White) GM19490
Voltage Regulator Fuse (10 amp) 223316
Zinc Anode 267928
359796
359979
List of Related Literature
The following table identifies literature available for the generator sets covered in this manual. Only qualified persons should install or service the generator set.
Literature Type Part Number
Installation Manual TP-5982
Operation Manual (Generator) TP-5985
Operation Manual (Engine) TP-6001
Parts Catalog* TP-5987
Service Manual (Generator) TP-5986
Service Manual (Engine) TP-6002
Service Manual Supplement (Engine) TP-6008
* One manual combines Generator and Engine information.
TP-5986 4/03 Introduction iii
Page 14
Notes
TP-5986 4/03iv Introduction
Page 15
Section 1 Specifications
(
19(
0
)
(mixi
l
bow
1(2.00)
1.1 General
The 7.3E/6EF and 5E/4EF units are powered by a two-cylinder, water-cooled, four-cycle gasoline engine with heat exchanger.
Kohler Co. develops all Kohler marine generator set ratings using accepted reference conditions of 25_C (77_F) and pressure of 99 kPa (29.2 in. Hg) dry barometer. ISO 3046 and ISO 8528-1 include reference conditions and output calculations. Obtain technical information bulletin (TIB-101) on ratings guidelines for complete ratings definitions.
1.2 Engine
Generator Model 7.3E/6EF 5E/4EF
Engine manufacturer Kawasaki
Engine model FD501D
Number of cylinders 2
Cylinder block material Aluminum
Cylinder head material Aluminum
Piston rings 2 compression/1 oil
Governor Gear driven centrifugal
Bore x stroke, mm (in.) 67 (2.64) x 62 (2.44)
Displacement, L (CID) 0.4 (26.7)
Compression ratio 9.3:1
Horsepower, 60/50 Hz 16 13.8
RPM, 60/50 Hz 3600 3000
Lubrication system Pressure; mechanical
Lube oil capacity, L (U.S. qts) (w/filter)
Low oil pressure shutdown, kPa (psi)
Oil recommendation (API)
Battery voltage 12 volt (standard)
Battery recommendation, minimum
Battery charging 15 amps
Starter motor Bendix automotive type
1.36 (1.44)
96.5 (14)
SC, SD, SE, SF,
SG, SH, or SJ
260 CCA
1.3 Fuel
Fuel recommendation Unleaded 87 octane
Fuel pump Electric
Fuel pump operating, kPa (psi)
Fuel filter inlet hose, mm (in.) ID
13.8--24.1 (2.0--3.5)
6.35 (0.25)
1.4 Cooling
Recommended coolant
Coolant capacity L (U.S. qts.) (approx.)
Thermostat, _C(_F)
Pressure cap rating, kPa (psi)
High temperature shutdown, _C(_F)
High exhaust temperature shutdown, _C(_F)
Inlet water line hose ID,
seawater pumpinlet),
mm (in.)
Outlet water line hose ID,
ng e
mm (in.)
Max. water pump inlet pressure, kPa (psi)
outlet),
50% ethylene glycol; 50%
clean, softened water
2.84 (3.0)
91 (195)
97 (14)
111 (232)
102 (215)
.75
5
34.5 (5.0)
TP-5986 4/03 1Section 1 Specifications
Page 16
1.5 Generator
1.6 Torque
Component Specification Value
Rotor field voltage/current readings at rated voltage (hot)
No load (63 Hz) (volts/amps) 13/3.82
Full load (60 Hz) (volts/amps) 47/13.82
Cold main field (rotor) resistance (ohms) 3.4
Stator output voltages with separately excited generator, using 12-volt battery (60 Hz only)
1--2, 3--4, 33--44 (VAC) 145
55--66 (VAC) 190
B1-B2 (VAC) 14
Cold stator resistance
1--2, 3--4, 33--44 (ohms) 0.16
55--66 (ohms) 1.70
B1-B2 (ohms) 0.05
Component Torque Nm (in. lbs.)
Rotor bolt 23.1 (204)
Generator overbolts 13.6 (120)
Mounting plate to end bracket bolts
Lift eye bolts 19.0 (168)
Generator adapter to engine bolts
Engine oil drain boss (inside generator adapter)
Generator adapter to exhaust manifold
High exhaust temp. switch 13.6 (120)
Spark plugs 12--17 (106--150)
Bolts that hold the coverplate over the impeller
6.8 (60)
14.9 (132)
47.5 (420)
13.6 (120)
3.4 (30)
TP-5986 4/032 Section 1 Specifications
Page 17
1.7 Service Views
33
32
31
1
3 5 13
2
30 29 2627
6
7
28
84
9
SERVICE VIEW
1110
25
12
14 15
16
17
18 19 20
21
22
23
24
1. Electric choke (on carburetor)
2. Carburetor/choke linkage
3. Spark plug (also one on nonservice side)
4. Oil fill
5. Overflow tube
6. Pressure cap (coolant fill location after draining coolant)
7. High water temp. switch
8. Controller
9. Start/Stop switch
10. Nameplate (top)
11. AC load lead connector (nonservice side)
12. Input fuse
13. Battery charging fuse
14. AC circuit breaker
15. Voltage regulator
16. Remote start connector (nonservice side)
17. Voltage regulator fuse
ENGINE-END VIEW
18. Hourmeter
19. Heat exchanger
20. Anticorrosion zinc anode
21. Seawater drain (remove zinc anode)
22. Seawater pump (water inlet)
23. Cooling air inlet
24. High exhaust temp. switch on mixing elbow (nonservice side)
25. Fuel filter (fuel inlet)
26. Fuel feed pump
27. Oil check
28. Coolant drain (remove hose clamp to drain coolant)
29. Oil drain valve
30. Lube oil filter
31. Low oil pressure switch
32. Antidieseling solenoid (on carburetor)
33. Air intake silencer/backfire flame arrestor
34. Coolant overflow bottle (daily coolant check/fill location)
34
ADV-6395-A
GY-250000-A
Figure 1-1 Service Views
TP-5986 4/03 3Section 1 Specifications
Page 18
Notes
TP-5986 4/034 Section 1 Specifications
Page 19
Section 2 Scheduled Maintenance
2.1 General
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the generator set as follows: (1) Place the generator set start/stop switch in the STOP position. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
WARNING
Sound shield removal. Exposed moving parts can cause severe injury or death. The generator set must be operating
in order to perform some scheduled maintenance procedures. Be especially careful if the sound shield has been removed, leaving the belts and pulleys exposed.
(Sound-shield-equipped models only)
NOTICE
Saltwater damage. Saltwater quickly deteriorates metals. Wipe up saltwater on and around the generator set and remove salt deposits from metal surfaces.
Note: See the generator set operation manual for the
service schedule and other service not included in this manual.
2.2 Lubrication System
Use oil that meets the American Petroleum Institute (API) classification of SC, SD, SE, SF, SG, SH, or SJ. Using unsuitable oil or neglecting an oil change may result in engine damage that is not covered by the engine warranty. Figure 2-1 shows the recommended Society of Automotive Engineers (SAE) viscosity designation for given operating temperature ranges.
Do not mix different oil brands. Incompatibility could cause a breakdown of lubricating ingredients and reduce engine protection.
SAE40
Rotating parts. Can cause severe injury or death.
Operate the generator set only when all guards, screens, and covers are in place.
Servicing the generator set when it is operating. Exposed moving parts can cause severe injury or death. Keep
hands, feet, hair, clothing, and test leads away from the belts and pulleys when the generator set is running. Replace guards, screens, and covers before operating the generator set.
TP-5986 4/03 5Section 2 Scheduled Maintenance
SAE5W-20*
°C-20
* Using multigrade oil causes greater oil consumption.
Figure 2-1 Recommended SAE Viscosity Grades
SAE10W-30/SAE 10W-40*
14°F-4
-10
0102030 40
SAE30
50 68 86 10432
Page 20
Notes
TP-5986 4/036 Section 2 Scheduled Maintenance
Page 21
Section 3 Intake and Exhaust System
3.1 Backfire Flame Arrestor
At the interval specified in the service schedule, inspect, clean or replace the backfire flame arrestor. Check the wire mesh screen for accumulated oil or dirt that could clog the element and cause poor performance. See Figure 3-1.
1
TP603531
1. Wire mesh screen
Figure 3-1 Air Intake
Exhaust System. Check for exhaust leaks and
blockages. Check the silencer and piping condition and check for tight exhaust system connections.
Inspect the exhaust system components (exhaust manifold, mixing elbow, exhaust line, hose clamps, silencer, and outlet flapper) for cracks, leaks, and corrosion.
D Check the hoses for softness, cracks, leaks, or dents.
Replace the hoses as needed.
D Check for corroded or broken metal parts and replace
them as needed.
D Check for loose, corroded, or missing clamps.
Tighten or replace the hose clamps as needed.
D Check that the exhaust outlet is unobstructed.
D Check the exhaust gas color. If the exhaust is blue or
black, contact your local distributor/dealer.
D Visually inspect for exhaust leaks. Check for carbon
or soot residue on exhaust components. Carbon and soot residue indicates an exhaust leak. Seal leaks as needed.
3.2 Exhaust
WARNING
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Inspecting the exhaust system. Carbon monoxide can cause severe nausea, fainting, or death. For the safety of
the craft’s occupants, install a carbon monoxide detector. Consult the boat builder or dealer for approved detector location and installation. Inspect the detector before each generator set use. In addition to routine exhaust system inspection, test the carbon monoxide detector per the manufacturer’s instructions and keep the detector operational at all times.
D Ensure that the carbon monoxide detector(s) is (1) in
the craft, (2) functional, and (3) energized whenever the generator set operates.
Note: Never operate the generator set without a
functioning carbon monoxide detector.
TP-5986 4/03 7Section 3 Intake and Exhaust System
Page 22
Notes
TP-5986 4/038 Section 3 Intake and Exhaust System
Page 23
Section 4 Fuel System
WARNING
Explosive fuel vapors. Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly explosive. Use
extreme care when handling and storing fuels. Store fuels in a well-ventilated area away from spark-producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts or from sparks. Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors. Keep the fuel lines and connections tight and in good condition. Do not replace flexible fuel lines with rigid lines. Use flexible sections to avoid fuel line breakage caused by vibration. Do not operate the generator set in the presence of fuel leaks, fuel accumulation, or sparks. Repair fuel systems before resuming generator set operation.
Explosive fuel vapors can cause severe injury or death.
Take additional precautions when using the following fuels:
4.1 General
In most installations, both the generator set and the vehicle’s engine operate from a common fuel tank with a dual dip tube arrangement. The generator set’s dip tube may be shorter than the vehicle engine’s dip tube. With this arrangement, fuel may not be available to the generator set when the fuel supply is low. See Figure 4-1 for fuel system schematic.
Vehicles engine
1
1. Fuel tank
2. Dual dip tubes
3. Fuel filter
2
Figure 4-1 Fuel System Schematic Typical
3
Generator set fuel pump
598641
Gasoline—Store gasoline only in approved red containers clearly marked GASOLINE.
Draining the fuel system. Explosive fuel vapors can cause severe injury or death. Spilled fuel can cause an
explosion. Use a container to catch fuel when draining the fuel system. Wipe up spilled fuel after draining the system.
4.2 Float Bowl Vent System
The float bowl vent system prevents fuel from overflowing into the bilge. In the event of an overflowing float bowl due to a sticking float valve, the float bowl vent tube redirects the unused fuel back into the intake per USCG regulations. Check for fuel leakage at the backfire flame arrestor for troubleshooting an overflowing float bowl.
4.3 Fuel Pump and Filter
Electric fuel pumps draw gasoline from the fuel tank, through a filter, and supply clean gasoline at the proper pressure and quantity to the generator set engine carburetor.
TP-5986 4/03 9Section 4 Fuel System
Page 24
4.4 Fuel Pump Troubleshooting
4.5 Carburetor Troubleshooting
The fuel pump transfers fuel from a source to the carburetor.
Fuel Pump Test Procedure
1. Connect the inlet side of the pump to a fuel source.
2. Disconnect the outlet hose from the fuel filter and place the end in a container to catch the fuel.
3. Disconnect the P9 connector.
4. Connect the positive (70) terminal of the fuel pump to the positive (+) terminal of a 12-volt battery.
5. Connect the negative (N) terminal of the fuel pump to the negative (--) terminal of the battery. The pump should operate and fuel should discharge from the pump outlet. If the pump does not operate, replace the pump.
This section is for fuel-related problems only. Use for basic carburetor troubleshooting.
Note: When troubleshooting the fuel system, it is
important to have an adequate fuel supply.
A lean or rich fuel condition can reduce power output and cause poor acceleration.
Symptoms of a Lean Condition:
D Hard starting D Stalling D Rough idle D Surging above idle
Symptoms of a Rich Condition:
D Hard starting D Stalling D Rough idle D Percolation D Flooding D Leaking carburetor
Figure 4-2 Fuel System Exploded View
4.5.1 Hard Starting
A flooded engine, improperly adjusted or inoperative choke, dirty carburetor (lean condition), or improper idle fuel mixture can cause hard starting.
4.5.2 Stalling
Improper idle air/fuel mixture or a dirty carburetor can cause stalling. Clogged idle air bleeds, idle air passages, or an idle discharge port can cause stalling because of a lean condition. Clean or adjust the carburetor.
598642
TP-5986 4/0310 Section 4 Fuel System
Page 25
4.5.3 Flooding
Flooding occurs from a float level set too high, improperly adjusted fuel pressure, improperly installed fuel pump, a sticking choke plate or float, or a fuel inlet needle held off its seat either by improper seating or dirt particles. A punctured or leaking float admitting fuel becomes gas-logged causing a heavy float, high fuel level, and flooding.
increase the generator output. Overspeeding can cause equipment parts to exceed design limitations, resulting in component failure.
Governor 60 Hz to 50 Hz Conversion Procedure
1. Change the spring to the 50 Hz position. See Figure 4-3.
If flooding occurs, disassemble the carburetor, observe the operation and condition of components, and repair or replace components as necessary.
4.5.4 Hunting
A low fuel level because of an improperly adjusted float, a clogged main jet, restricted main jet passages, or an improperly sized main jet for the application can cause hunting. Clean, adjust, or replace inoperative components.
An incorrect throttle linkage adjustment, a binding throttle linkage, a sticking throttle shaft, or a loose throttle shaft in the throttle body or bore can cause inconsistent idle speed.
4.5.5 Leaking Carburetor
Loose fuel connections, a cracked carburetor body, a sticking fuel inlet needle, or an inoperative float can cause a leaking carburetor. Adjust, repair, or replace the affected components.
2. Adjust the generator frequency using a frequency meter. Set the no load speed at 52.5 Hz for 50 Hz operation or 63 Hz for 60 Hz operation.
3. Replace the governor speed adjusting bolt. The 50 Hz bolt is X-6284-7 and is 65 mm long. The 60 Hz bolt is M933-5050-60 and is 50 mm long.
4. Adjust the voltage regulator volt/Hz rolloff point. Refer to Section 7.2.2.
2
1
3
4
598643
4.6 Governor 60 Hz to 50 Hz Conversion
Governors are adjusted at the factory and further adjustments should not be necessary.
1. 60 Hz governor spring position
2. 50 Hz governor spring position
3. Governor arm
4. Governor speed adjusting bolt (X-6284-7 for 50 Hz, M933-5050-60 for 60 Hz)
Figure 4-3 Governor 60 Hz to 50 Hz Conversion
TP-5986 4/03 11Section 4 Fuel System
Page 26
Notes
TP-5986 4/0312 Section 4 Fuel System
Page 27
5.1 General
The heat exchanger cooling system consists of a heat exchanger with a coolant recovery tank, a thermostat, a rubber impeller seawater pump, a centrifugal-type
Section 5 Cooling System
engine circulating pump, a water-cooled exhaust manifold, and an exhaust mixer. See Figure 5-1 for cooling system components.
12
1
2
3
4
5
6
7
8
9
Seawater
Coolant/Antifreeze
1. Engine block
2. Exhaust manifold
3. Exhaust mixer elbow
4. Outlet flapper
5. Silencer
6. Thermostat
10
11
7. Heat exchanger
8. Engine seawater pump
9. Seawater strainer
10. Seacock
11. Intake strainer
12. Engine-driven water pump
Figure 5-1 Cooling System Components
TP-5986 4/03 13Section 5 Cooling System
Page 28
5.2 Closed Heat Exchanger
In a closed cooling system, the seawater circulates through separate chambers within the heat exchanger to cool the engine water. The seawater then mixes with the engine exhaust and ejects out of the exhaust outlet. The cooling capacity for the 5/7.3E and 4/6EF is 2.84 L (3.0 qts.). The capacity of the recovery tank is an additional 0.24 L (8.0 oz.).
WARNING
Hot coolant and steam. Can cause severe injury or death.
Before removing the pressure cap, stop the generator set and allow it to cool. Then loosen the pressure cap to relieve pressure.
Checking the coolant level. Hot coolant can cause severe injury or death. Allow the engine to cool. Release pressure
from the cooling system before removing the pressure cap. To release pressure, cover the pressure cap with a thick cloth and then slowly turn the cap counterclockwise to the first stop. Remove the cap after pressure has been completely released and the engine has cooled. Check the coolant level at the tank if the generator set has a coolant recovery tank.
NOTICE
Saltwater damage. Saltwater quickly deteriorates metals. Wipe up saltwater on and around the generator set and remove salt deposits from metal surfaces.
Do not add coolant to a hot engine. Adding coolant to a hot engine can cause the cylinder block or cylinder head to crack. Wait until the engine has cooled.
Note: Coolant solution. A coolant solution of 50%
ethylene glycol provides freezing protection to
-- 3 7 _C(--34_F) and overheating protection to 129°C (265°F). A coolant solution with less than 50% ethylene glycol may not provide adequate freezing and overheating protection. A coolant solution with more than 50% ethylene glycol can cause engine or component damage. Do not use alcohol or methanol antifreeze or mix them with the specified coolant. Consult the engine manufacturer’s operation manual for engine coolant specifications.
5.4 Flush and Clean Cooling System
For optimum protection, drain, flush, and refill the cooling system at the interval listed in the operation manual’s service schedule.
Pay special attention to the coolant level. Check the coolant level as described earlier.
Flush and Clean Procedure
1. Remove the hose clamp at the coolant hose. See Section 1 for location.
2. Remove the pressure cap to simplify draining.
3. Drain, clean, and flush the coolant recovery tank.
5.3 Check and Fill Coolant
Keep the coolant recovery tank approximately 1/4 full. Before filling the cooling system, close all petcocks and tighten all hose clamps. Use a solution of 50% ethylene glycol and 50% clean, softened water to inhibit rust and corrosion and to prevent freezing. Add additional coolant mixture, as necessary, to the coolant recovery tank. Periodically check the coolant level on closed systems by removing the pressure cap. Do not rely solely on the level in the coolant recovery tank. Add fresh coolant until the level is just below the overflow tube opening.
4. Flush the system with clean water.
5. Replace the hose clamp to secure the coolant hose.
6. Fill the cooling system with the recommended coolant.
7. Bleed the air from the cooling system.
8. Replace the pressure cap.
TP-5986 4/0314 Section 5 Cooling System
Page 29
5.5 Impeller
1
This model uses a direct-driven seawater pump located on the generator end. Check and change the seawater pump impeller at the interval specified in the service schedule. Follow the instructions included with the impeller kit. If the instructions are not included with the kit, use the following procedure.
Impeller Inspection/Replacement Procedure
1. Close the seacock.
2. Remove the seawater pump coverplate. See Figure 5-2.
3. Remove the impeller.
4. Inspect the impeller for damaged, cracked, broken, missing or flattened vanes. The impeller vanes should be straight and flexible. See Figure 5-3. Replace the impeller if it is damaged.
1
11
2
3
598653
1. Flat spot
2. Crack
3. Broken vane
Figure 5-3 Worn Impeller
Note: Impeller pieces can cause blockage and
overheating. Locate and remove all missing impeller pieces from the cooling system.
5. Lubricate the impeller with soapy water before installation.
6. While installing the impeller, always rotate the drive shaft and the impeller together in the same direction as the engine rotation.
10
5
9
1. Seawater pump
2. Coverplate
3. Gasket
4. Impeller
5. Bearing
6. Housing
8
6
7
7. Pulley
8. Drive shaft
9. Washer
10. Nut
11. Mechanical seal, if equipped
Figure 5-2 Seawater Pump, Typical
7. Inspect the coverplate and gasket for corrosion and/or damage. Replace components as
2
3
4
necessary.
8. Lubricate the gasket with petroleum jelly and install the gasket and coverplate to the seawater pump
598652
housing.
9. Open the seacock.
10. Start the generator set and check for leaks.
11. Stop the generator set and repair leaks or replace components as necessary.
TP-5986 4/03 15Section 5 Cooling System
Page 30
5.6 Siphon Break
4. Check that the reed valve opening is clear.
A siphon break prevents seawater entry into the engine when the engine exhaust manifold outlet is less than 23 cm (9 in.) above waterline. Check the siphon break at the interval listed in the service schedule. Use the following procedure and Figure 5-4 to ensure correct functioning of the siphon break.
Siphon Break Inspection Procedure
1. Stop the generator set.
2. Remove the retaining cap and the reed valve for inspection. See Figure 5-4.
3. Use a light detergent to clean the reed valve.
2
3
1
21
5. Replace the siphon break if it is cracked or if the reed valve material has hardened or deteriorated.
6. Install the reed valve downward into the mounting base.
7. Install the retaining cap and finger-tighten only. Do not overtighten.
8. Restart the generator set and inspect the reed assembly for leaks. Replace the reed valve if leakage occurs.
Note: Consult the installation manual for a
complete explanation of the dimensions and other installation considerations.
7
6
8
9
10
19
Waterline
20
18
1. Mounting holes
2. Retaining cap
3. Reed valve assembly
4. Silencer vertical lift 1.2 m (4 ft.) max.
5. Exhaust mixer elbow distance above waterline. If less than 23 cm (9 in.), a siphon break is required.
6. Siphon break distance above waterline 30.5 cm (1 ft.) min.
7. Siphon break
8. Exhaust mixer elbow
9. Heat exchanger (locations vary by model)
10. Coolant recovery tank
Figure 5-4 Siphon Break, Plastic “U” Type
5
4
15
16
17
11. Seawater strainer
12. Seacock
13. Intake strainer
14. Engine-driven seawater pump
15. Exhaust hose pitch 1.3 cm per 30.5 cm (0.5 in. per ft.) min.
16. Water lock (optional)
17. Silencer distance from exhaust mixer elbow 3 m (10 ft.) max.
18. Silencer (customer-supplied)
19. Exhaust hose pitch 1.3 cm per 30.5 cm (0.5 in. per ft.) min.
20. Exhaust outlet distance above waterline 10 cm (4 in.) min.
21. Seawater outlet
14
13
11
12
TP-5586-3
TP-5986 4/0316 Section 5 Cooling System
Page 31
5.7 Anticorrosion Zinc Anode
4. Install the zinc anode into the heat exchanger.
The heat exchanger contains an anticorrosion zinc anode (plug) to prevent electrolytic corrosion by seawater.
Check and replace the zinc anode at intervals recommended by the operation manual’s service schedule.
Anticorrosion Zinc Anode Replacement Procedure
1. With the generator set cooled, close the seacock, remove the zinc plug from the heat exchanger, and drain the coolant into a container.
2. Remove the corrosion on the zinc anode. Replace the anode when the percent of the zinc remaining is less than 50% of the length and diameter shown in Figure 5-5.
3. Clean the threaded opening of the heat exchanger and coat the threads of the zinc anode with pipe sealant suitable for marine applications.
5. Open the seacock.
6. Refill the cooling system.
7. Start the generator set and check for leaks at the zinc anode location. The pump is operating if cooling water flows from the exhaust outlet. If water is not discharging at the exhaust outlet, stop the generator set. For seawater pump priming, see the Prestart Checklist in the operation manual.
1
2
TP-5586-3
1. Diameter: 9 mm (0.34 in.)
2. Length: 43 mm (1.7 in.)
Figure 5-5 Anticorrosion Zinc Anode (Plug)
TP-5986 4/03 17Section 5 Cooling System
Page 32
5.8 Generator Storage
Perform the generator storage procedure while the craft is afloat. Follow the procedure below when storing your generator set for 3 months or more.
Generator Storage Procedure
1. Add fuel stabilizer to the fuel tank of gasoline-powered generator sets. Follow the fuel stabilizer manufacturer’s recommendation.
2. Start and run the generator set until it reaches operating temperature; about 30 minutes.
3. Stop the generator set.
4. Change the oil and oil filter. See the operation manual.
5. Drain the seawater from the heat exchanger by removing the seawater zinc anode. See Section 1.7, Service Views, for location.
6. Close the seacock and remove the hose at the seacock. Place the hose in a container having approximately 3.7--7.5 L (1--2 gal.) of marine antifreeze. Kohler Co. recommends using an environmentally friendly potable antifreeze such as PeakR RV/marine propylene glycol/water mix or equivalent.
7. With a container at the exhaust outlet, run the generator set until coolant discharges at the exhaust outlet or until depleting the coolant
mixture. Do not allow the coolant mixture to flow into waterways.
8. Stop the generator set.
9. Connect the hose to the seacock. Leave the seacock closed.
10. Check the coolant level of the heat exchanger and add coolant if necessary.
Note: Use antifreeze with the lowest available
temperature rating.
11. Clean the exterior of the generator set and spread a light film of oil or silicon spray over any exposed surfaces which may be subject to rust or corrosion.
12. Remove the spark plugs.
13. Pour one tablespoon of engine oil into each spark plug hole.
14. Toggle the generator set start/stop switch to crank the engine two or three revolutions to lubricate the cylinders.
15. Reinstall the spark plugs and torque them to specifications.
16. Disconnect and remove the battery. Place the battery in a dry location for the storage period. Recharge the battery once a month to maintain a full charge.
17. Cover the entire unit with a breathable dust cover.
TP-5986 4/0318 Section 5 Cooling System
Page 33
Section 6 Controller Troubleshooting
6.1 Sequence of Operation
This section describes the controller sequence of operation during the generator start, run, stop, and fault shutdown modes and describes the relay testing procedures. Use this section as a starting point for controller fault identification. Use the LEDs on the controller circuit board to assist in the troubleshooting process. An illuminated LED indicates that the respective relay is receiving power; the LED does not indicate whether that relay is energized or working properly.
6.1.1 Start
Close the start/stop switch between N and 47 (local or remote).
The K2 relay energizes and LED2 is illuminated. The normally-open K2 contacts close to energize the K3 relay (LED3 lights), fuel pump (FP), choke heater (CHTR), antidiesel solenoid (ADS), ignition (IGN), and hourmeter (HR).
The K6 relay energizes. The normally-open K6 contacts close, latching itself on. The normally-closed K6 contacts open, preventing inadvertent starter engagement by disabling the the K3 relay.
The K3 relay is deenergized (LED3 Off). The K3 contacts open, deenergizing the K20 relay. The K20 contacts open, deenergizing the starter relay and starter motor.
2
1
Flashing of the main field occurs when the K2 contacts close.
The normally-open K3 contacts close to energize the K20 relay. The normally-open K20 contacts close, energizing the starter relay and the starter motor.
Note: The normally-closed LOP contacts open when
the engine builds oil pressure. This may take a few seconds after engine cranking is initiated.
6.1.2 Run
The bridged rectifier (BR1) receives AC voltage (12--15 volts) through the B1 and B2 windings of the stator.
The K1 relay energizes (LED1 lights).
The normally-open K1 contacts close to maintain voltage to the K2 relay, allowing the function of the fuel pump (FP), choke heater (CHTR), antidiesel solenoid (ADS), ignition (IGN), hourmeter (HR), and the remote panel gauges.
The normally-closed K1 contacts open, ending the flashing by preventing battery voltage to the main field (+) and (--).
3
6
5
4
598161
1. Controller circuit board
2. PBIIIE voltage regulator
3. K20 relay
4. Fuses
5. Start/stop switch
6. Hourmeter
Figure 6-1 Controller
TP-5986 4/03 19Section 6 Controller Troubleshooting
Page 34
At the same time the K1 relay is energized, the time delay for the K5 relay starts. After 5--10 seconds, the K5 relay is energized (LED 5 lights).
The normally-open K5 contacts close to permit the function of the engine safety shutdown switches.
6.1.3 Stop
Close the start/stop switch between N and 43 (local or remote).
The K4 relay energizes (LED4 lights).
The normally-closed K4 contacts open, disabling the fuel pump (FP), choke heater (CHTR), antidiesel solenoid (ADS), and ignition (IGN).
The normally-open K4 contacts close, latching the circuit to the K4 relay until the generator set comes to a complete stop.
6.2 Engine Safety Shutdown Switches
The generator shuts down, as described in Section 6.1.3.
Note: During cranking, the low oil pressure shutdown
switch deactivates until the K5 relay energizes. This delay allows the engine to reach normal operating oil pressure.
6.2.2 Loss of Coolant Switch (LCS) Shutdown
When the coolant level is low, the LCS contacts close, energizing the K4 relay (LED4 lights). The generator shuts down, as described in Section 6.1.3.
6.2.3 High Engine Temperature Switch (HET) Shutdown
When the engine temperature exceeds 110_C (230_F), the HET contacts close, energizing the K4 relay (LED4 lights). The generator shuts down, as described in Section 6.1.3.
6.2.4 Controller Circuit Board
6.2.1 Low Oil Pressure (LOP) Shutdown
When low oil pressure occurs, the LOP shutdown switch contacts close energizing the K4 relay (LED4 lights).
11
The controller circuit board has light emitting diodes (LEDs) that indicate the presence of relay coil power. When any of the relays K1--K5 receive power, the corresponding LED lights.
Figure 6-2 GM10516 Controller Circuit Board
GM10516
TP-5986 4/0320 Section 6 Controller Troubleshooting
Page 35
6.2.5 Troubleshooting
Use the following flowchart as an aid in troubleshooting the main circuit board and the entire generator set. If the prescribed remedy does not correct the problem, the
circuit board may have to be replaced. Use this chart for component testing only. Always check the continuity of the wires between components.
Press the start switch (local or remote).
Does the K2 relay LED light while cranking?
No
Is 10-amp controller fuse functional?
YesNo
Does the engine crank?
Check the battery condition and connections.
Is there continuity between N and 47 while pressing the start/stop switch?
Yes
No
TheK2relayis faulty. Replace the circuit board.
No
Yes
Is the K3 relay LED lit?
Is voltage present at the K20 relay coil (P1-4 connector)?
No
TheK2relayis faulty. Replace the circuit board.
No
Go to A (next page).
Yes
Yes
Replace or repair the wiring harness.
Replace the fuse.
Replace the circuit board.
Yes
Yes
Is there 12 volts at P1--14?
No
Replace or repair the wiring harness.
Replace the K20 relay.
Figure 6-3 Troubleshooting Relay Controller Circuit Board (1 of 4)
Is voltage present at the starter relay?
No
Replace the starter relay.
Yes
Is voltage present at the starter?
No
Yes
Replace or repair the starter motor.
TP-5986 4/03 21Section 6 Controller Troubleshooting
Page 36
A
Does the engine start?
Yes
Go to B (next page).
No
No
Is there continuity between P1-9 and P9-1?
No
No
No
Is there continuity between P9-2 and P1-8?
Is there continuity between P1-8 and P1-14?
Is the K4 relay LED lit?
No
Is there12 volts DC present at the fuel pump (P9-2)?
Yes
Yes
Yes
Is there continuity across the P1, P4, and P9 connectors?
Yes
Replace the fuel pump.
Yes
Is the fuel pump working?
No
Yes
Troubleshoot the engine. refer to the engine service manual.
Is there continuity between P4-5 and N?
Go to C
No
(next page).
Is there continuity between P2-8 and N?
Yes
Disconnect the P2 connector. Is there continuity between P2-5 and N?
Yes
Check the wiring for
Yes
open circuits.
Check the connectors for open circuits.
Figure 6-4 Troubleshooting Relay Controller Circuit Board (2 of 4)
No
Replace the remote start/stop switch.
Yes
Replace the start/stop switch.
TP-5986 4/0322 Section 6 Controller Troubleshooting
Page 37
B
to run after the start
Yes
switch is released?
Does the engine continue
Does using the stop switch stop the engine?
Yes
No
The generator set is
No
C
Did the K4 relay LED light?
functioning properly?
No
Does the K5 relay LED light after 5--10 seconds of running time?
No
Replace the circuit board (the K5 relay is inoperative).
Go to D (next page).
Does the K1 relay LED light?
Yes
Is the K3 LED out?
No
Replace the circuit board (the K6 relay is inoperative).
Check the oil level. Repair/replace the oil pump.
Yes
Yes
Yes
No
Replace LOP switch.
Is the LOP switch functional?
Yes
Does the engine have proper oil pressure? Use a mechanical gauge to verify pressure.
No
Yes
Replace the inoperative temperature switch.
Replace the switch.
No
No
Replace the circuit board (inoperative
No
K4 relay).
Fill the cooling system and check for leaks.
Figure 6-5 Troubleshooting Relay Controller Circuit Board (3 of 4)
Is the temperature (HET) safety shutdown switch functional?
Yes
Is the low coolant switch functional?
Yes
Is the coolant level low?
Yes
TP-5986 4/03 23Section 6 Controller Troubleshooting
Page 38
Is there AC output when the start button
D
is held and the unit is running?
No
Is there approximately 12VDC at the exciter field?
Yes
No
Separately excite the generator set to determine if other components are inoperative. (See Section 7.1.2, Separate Excitation).
Is there AC output voltage?
No
Is the stator and rotor functional?
No
Is there 12 volts AC output at the B1/B2 stator winding?
Yes
Yes
Is the voltage regulator fuse functional?
No
Is the stator functional?
No
Replace the stator.
Yes
Yes
Replace the circuit board.
Replace the circuit board.
Replace inoperative components.
No
Replace the fuse.
Figure 6-6 Troubleshooting Relay Controller Circuit Board (4 of 4)
No
Is the voltage regulator functional?
Yes
Replace the voltage regulator.
TP-5986 4/0324 Section 6 Controller Troubleshooting
Page 39
Section 7 Generator Troubleshooting
7.1 General
Before beginning the following troubleshooting procedures, read all the safety precautions at the beginning of this manual. The following tests include additional safety precautions; OBSERVE THESE PRECAUTIONS!
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Testing the voltage regulator. Hazardous voltage can cause severe injury or death. High voltage is present at the
voltage regulator heat sink. To prevent electrical shock do not touch the voltage regulator heat sink when testing the voltage regulator.
(PowerBoostt, PowerBoostt III, and PowerBoostt V voltage regulator models only)
Moving rotor.
7.1.1 Troubleshooting
To determine the cause of no- or low-AC output , refer to the following steps and the troubleshooting flowchart (Figure 7-1). Verify the operation of the alternator components before replacing the controller board or voltage regulator.
General Troubleshooting
1. Check the condition of the voltage regulator’s 10-amp fuse.
2. If the fuse is functional, separately excite the generator. See Section 7.1.2. The separate excitation test duplicates the role of the voltage regulator by providing excitation current to the rotor.
Generator has no
output
Check for flashing
voltage at the brushes
Troubleshoot controller
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible
whenever electricity is present. Open the main circuit breakers of all power sources before servicing the equipment. Configure the installation to electrically ground the generator set, transfer switch, and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury
and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
Separately
excite
generator
Generator has no
output
Test r o tor
Generator has output
regulator and
Figure 7-1 General Troubleshooting
Test voltage
wiring
Test stator
TP-598651
TP-5986 4/03 25Section 7 Generator Troubleshooting
Page 40
7.1.2 Separate Excitation
By separately exciting the generator to determine the presence of a faulty voltage regulator, it is possible to determine if a running fault exists in the rotor and/or stator. A generator component that appears functional while static (stationary) may exhibit a running open or short circuit while dynamic (moving). Centrifugal forces acting on the windings during rotation or insulation breakdown as temperatures increase can cause short circuits.
Note: It is not necessary to separately excite the
generator if there is AC output with flashing voltage.
Separate Excitation Procedure
1. Disconnect all of the leads from the voltage regulator.
2. Disconnect the P10 (F1, F2) connector.
3. Connect a separate excitation circuit as shown in Figure 7-2. Connect an ammeter and a 10-amp fuse in series with F1. Note and record the ammeter reading.
4. The approximate ammeter reading should equal battery voltage divided by the specified rotor resistance (cold). See Section 1, Specifications, for the correct values.
7. Remove the jumper wire and reverse the positive (+) and negative (--) leads on the rotor. Repeat step 5. If the ammeter is stable, ground the negative (--) lead at its new location on the rotor to the engine block. Replace the rotor if the ammeter reading fluctuates.
8. Check for AC output across the stator leads and compare the measured output to the values in Section 1, Specifications. If the output varies considerably from those listed, a faulty stator, rotor, rectifier module, or armature is likely.
If there is no generator output during normal operation but output is available when the generator set is separately excited, the voltage regulator may be inoperative.
Note: See Section 1, Specifications, for the stator
output voltages (with separately excited generator). These specifications are based on a battery voltage of 12 volts. Should the battery voltage vary, the resulting stator output values will also vary.
1
5
A
11
4
2 3
Example:
12 Volts (Battery Voltage)
3.4 Ohms Rotor Resistance
3.5-amp
=
Ammeter reading
5. Start the engine and check that the ammeter remains stable. An increasing meter reading indicates a shorted rotor. A decreasing meter reading to zero, or unstable reading, suggests a running open in the rotor. If the ammeter is stable, continue with step 6.
6. With a jumper wire, ground the negative (--) lead from the rotor to the engine block. An increased current reading or a fluctuating reading indicates a grounded rotor winding. Replace the rotor if the ammeter reading fluctuates. If the ammeter is stable, continue with step 7.
10
1. Voltage regulator
2. (--) Terminal—(P10-2)
3. (+) Terminal—(P10-1)
4. 10-amp fuse
5. DC ammeter
6. 12-volt battery (DC)
+
7
8
9
+—
7. Brushes
8. Collector rings
9. Main field (rotor)
10. Jumper lead
11. Engine ground
Figure 7-2 Separate Excitation Connections
6
TP-598652
TP-5986 4/0326 Section 7 Generator Troubleshooting
Page 41
7.2 PowerBoosttIIIE Voltage Regulators
Regulator Test Procedure
1. Connect the components as shown in Figure 7-4.
The generator set is equipped with a PowerBoostt IIIE voltage regulator. See Figure 7-3.
1
1. Voltage adjustment potentiometer
2. Stability adjustment potentiometer
3. Volts/Hz adjustment potentiometer
3
2
TP-598653
Figure 7-3 PowerBoostt IIIE Voltage Regulator
The voltage regulator monitors the output voltage of the generator set.
The 10-amp regulator fuse protects the alternator stator windings (power supply) 55-33 from excessive current draw because of an inoperative voltage regulator or a downstream short. If the regulator’s 10-amp fuse blows, the generator set will shut down. Verify that the regulator fuse is functional before proceeding with the test.
7.2.1 Voltage Regulator Test
Perform the following test to check the regulator output.
2. Turn the variable transformer setting to zero. Plug in the variable transformer.
3. Turn the variable transformer on. Slowly increase the variable transformer voltage to 100 volts. The test lamp should light. If the lamp does not light, turn the voltage adjustment potentiometer (pot) clockwise. If the lamp still does not light, the voltage regulator is inoperative. Replace the voltage regulator. An inoperative voltage regulator causes a generator no/low-output condition.
4. Slowly increase the voltage to 120 volts. The lamp should go out and stay out as the voltage increases. If the lamp remains lit, turn the voltage adjustment pot counterclockwise. If the lamp still remains lit, replace the voltage regulator. A voltage regulator which tests bad causes a generator high voltage output condition.
5. Turn the variable transformer to zero and unplug the AC cord.
Note: For applications requiring fine voltage
adjustment, connect a remote rheostat to voltage regulator terminal 66.
4
2
1
3
66 443355--+
RYOW
GY
5
BK
6
7
D Variable transformer, 0--140 volts, 0.5-amp minimum D Plug, 120 volts AC D Lamp, 120 volts, 100 watts D AC voltmeter D Insulated copper wire, #14 AWG, minimum
TP-5986 4/03 27Section 7 Generator Troubleshooting
1. 120 volts AC
2. Variable transformer
3. AC voltmeter
4. Voltage regulator PowerBoosttIIIE
5. Stator/rotor connections (for reference only)
6. Lead color
7. 120 volt, 100 watt lamp
TP-598654
Figure 7-4 PowerBoosttIIIE Voltage Regulator Test
Page 42
7.2.2 Voltage Regulator Adjustment
Voltage Regulator Adjustment Procedure
The factory sets the voltage regulator and under normal circumstances the regulator requires no further adjustment. However, if the voltage regulator has been replaced or tampered with, or if voltage/frequency reconnection has been done, readjust the voltage regulator according to the following procedure. See Figure 7-5. The following paragraphs describe the voltage regulator components.
Voltage Adjustment Pot adjusts the generator output within the range of 100--130 volts.
Stabilizer Pot fine-tunes regulator circuitry to minimize AC voltage fluctuation.
1
3
15
33
2
66
GY R
3
44 33 55
YOWBK
66
33
4
44
14
B1
12
B2
1. Optional remote rheostat
2. Voltage adjustment pot
3. PowerBoostIIIE voltage regulator
4. Stabilizer pot
5. Volts/Hz pot
6. Stator/rotor connections (for reference only)
7. DC output
8. Rotor
9. 10-amp fuse
10. AC power input (aux.)
11. Main (2 and 1)
12. Control
13. Stator
14. Sensing
15. Main (3 and 4)
13
2
11
55
9
1
10
4
5
6
+
--
7
8
+
--
TP-598655
Figure 7-5 PowerBoostt IIIE Voltage Regulator
Volts/Hz Pot feature allows the voltage to drop if the
load imposed on the generator causes the engine speed to fall below a predetermined RPM or frequency. This reduction of voltage results in a decrease of starting kW (load) allowing the governor to recover the engine speed.
1. Stop the generator set.
2. Turn the remote rheostat, if equipped, to the midpoint. Turn the voltage and stabilizer pots fully counterclockwise. Connect the voltmeter to the AC circuit or an electrical outlet.
3. Start the generator set.
4. Adjust the generator frequency using a frequency meter. Set the no load speed at 52.5 Hz for 50 Hz operation or 63 Hz for 60 Hz operation.
5. Rotate the voltage adjustment pot clockwise to increase the voltage or counterclockwise to decrease the voltage to achieve the desired output voltage.
6. Connect a 120-volt light bulb to the AC plug on the generator set.
7. Rotate the stability pot clockwise until the light bulb flickers minimally.
8. Readjust the voltage adjustment pot to achieve the desired output voltage.
9. Disconnect the 120-volt light bulb.
10. Turn the volts/Hz pot completely clockwise to decrease the Hz rolloff point. See Figure 7-6.
125
120
115
110
Volts (AC)
105
100
40 42 44 46 48 50 52 54 56 58 60 62 64
Frequency (Hz)
60Hz Models
50Hz Models
Counterclockwise to increase Hz rolloff
Clockwise to decrease Hz rolloff
Figure 7-6 Volts/Hz Rolloff Chart
TP-5986 4/0328 Section 7 Generator Troubleshooting
Page 43
11. Set engine speed to 47.5 Hz for 50 Hz generator sets and 57.5 Hz for 60 Hz generator sets for the desired cut-in frequency.
12. Slowly turn the volts/Hz pot counterclockwise until the frequency matches that of the engine frequency (47.5 or 57.5 Hz) or until the voltage just begins to drop.
13. Reset the engine speed to the normal frequency (50Hzor60Hz).
Note: Use the values in Section 1 as a reference for
rotor resistance readings. Take readings at room temperature or about 21°C(70°F). Rotor resistance will vary directly with increase in temperature.
To check whether the rotor is shorted to ground, touch one ohmmeter lead to either collector ring and the other lead to the rotor poles or shaft. The meter should register no continuity.
14. Recheck the AC voltage output and stability as described in steps 5--7.
15. Stop the generator set.
7.3 Rotor
The two-pole rotor creates the magnetic field needed to sustain alternating current in the stator windings. Before testing, inspect the rotor for visible damage to pole shoes, insulation, exposed coil windings, and collector ring surfaces. Check the rotor bearing for noisy operation, excessive wear, radial or axial movement, and/or heat discoloration. Replace or repair as necessary.
Collector rings acquire a glossy brown finish in normal operation. Do not attempt to maintain a bright, newly machined appearance. Wipe the collector rings with a dry, lint-free cloth. Use a commutator stone to remove the groves on the collector rings. Do not use emery or carborundum paper or cloth. Remove all carbon dust from the generator. Remove the black or pitted surface of the collector rings using a lathe.
Check the rotor for continuity and resistance. Lift the brushes and measure the rotor resistance between the two collector rings. See Section 1.5.
Note: When checking rotor resistance with the rotor
installed, brushes must not be in contact with rotor collector rings. Use a brush retainer on brushes for accurate resistance readings.
Repair or replace the rotor if the previous tests detect any faults.
7.4 Stator
The stator consists of a series of coils of wire laid in a laminated steel frame. The stator leads supply voltage to the AC load and exciter regulator. See Figure 7-7 for coil lead description.
Stator Leads Description
1--2 Output coil
3--4 Output coil
33--44 Control wires from 3 and 4
55--33 Voltage regulator power source
B1--B2 Controller power source
Figure 7-7 Stator Coil Lead Description
Before testing the stator, inspect it for heat discoloration and visible damage to the exposed coil windings and varnished areas of the frame laminations. Be sure the stator is securely fastened in the stator housing.
The stator produces electrical output (AC) as the magnetized main field rotates within the stator windings. Test the condition of the stator according to the following procedure.
Leads 1, 2, 3, and 4 are the generator output leads. Leads 33, 44, and 55 are the voltage regulator supply and sensing leads. The output of leads B1 and B2 is the control voltage for the controller.
TP-5986 4/03 29Section 7 Generator Troubleshooting
Page 44
Stator Test Procedure
1. Place the generator start/stop switch in the STOP position.
2. Disconnect the generator set engine starting battery, negative (--) lead first.
3. Check the generator output lead connections. See Section 10, Wiring Diagrams and Voltage Reconnection.
4. Disconnect all of the stator leads to isolate the windings. To check the stator continuity, set the ohmmeter on the R x 1 scale. Check the stator continuity by connecting the meter leads to the stator leads as shown in Figure 7-8. Perform the stator tests on all the stator windings.
Note: When taking an ohmmeter reading using
lead 55, make the connection prior to the in-line fuse.
5. Check the cold resistance of the stator windings by connecting the meter leads to the stator leads 1-4, 2-5, 3-6, etc. See Section 1, Specifications, for the stator resistance values.
6. Perform a megohmmeter test on the stator as described in step 7.
Note: Consider the stator functional if the
resistance reading (continuity) is low and there is no evidence of shorted windings (heat discoloration).
Note: The stator resistance varies directly with
increased temperature.
If the stator readings vary considerably during the previous checks, repair or replace the stator.
7. Check the stator for a grounded condition using a megohmmeter. Apply 500 volts DC to any stator lead from each winding and the stator frame. Follow the instructions of the megohmmeter manufacturer when performing this test. Repeat the test on the other leads until all the stator windings have been tested. A reading of approximately 3--5 megohms and higher indicates the stator is functional. A reading of less than approximately 3--5 megohms indicates deterioration of the winding insulation and possible current flow to ground. Replace the stator.
Between Leads Continuity
1 and 2 3 and 4
55 and 66
B1 and B2 1 and 3, 4, 33, 44, 55 1 and 55, B1, and B2
4 and B1 and B2
55 and B1 and B2
Any stator lead and ground
Yes Yes Yes Yes
No No No No No
Figure 7-8 Stator Continuity
TP-5986 4/0330 Section 7 Generator Troubleshooting
Page 45
7.5 Brushes
The brushes provide a current path from the voltage regulator to the collector rings. Because the brushes carry a low current, inspect them every 1000--1500 hours. Abrasive dust on the collector rings could, however, shorten the life of the brushes. Excessive arcing at the brushes could damage the voltage regulator. Weak springs, damaged collector rings, sticking brushes, a loose holder, or poor brush contact can cause arcing at the brushes.
The brushes must be free to move within the holder and be held in contact by the springs. When properly positioned, spring pressure on the brush surface will cause the brush to wear evenly. Brushes must ride 100% on the collector rings or arcing will occur and cause burned rings or failure of the voltage regulator. Figure 7-9 shows the correct positioning of the brushes. Add or remove spacers as necessary to center brushes on collector rings. Replace brushes if they show excessive or uneven wear.
Use a retainer wire (such as a paper clip) to contain the brushes during disassembly and reassembly. Push the brushes into the brush holder until the retainer wire can be inserted into the brush keeping hole. See Figure 7-10. Replace brushes when they are worn to half of their original size.
1
6
2
3
4
5
1
1. Correct position
2. Brush holder
3. Incorrect position
4. Generator collector rings
Figure 7-9 Brush Positioning
2
3
1. Brush holder
2. Retainer (paper clip)
3. Mounting screw
4. Alignment shim(s)
5. Brush
6. Spring
TP-598658
Figure 7-10 Brush Holder
4
TP-598657
TP-5986 4/03 31Section 7 Generator Troubleshooting
Page 46
Notes
TP-5986 4/0332 Section 7 Generator Troubleshooting
Page 47
Section 8 Component Troubleshooting
8.1 Engine/Generator Components
See Figure 8-1 through Figure 8-3 for engine/generator component testing.
With the generator set battery connected, check the wiring harness and the engine/generator components
Component Voltmeter Connections Procedure Results
Hourmeter and wiring Connect the red test lead to
Stator auxiliary winding B1 and B2
the hourmeter positive (+) terminal. Connect the black test lead to the hourmeter negative (--) terminal.
None (see Procedure) Disconnect the hourmeter
Connect the AC voltmeter leads to the B1 and B2 windings at connector P11. Stop the generator set.
listed in the following tables. Check each component using a multimeter to verify that the switches function and that voltage is present at each component.
Set the voltmeter to 12 volts DC or greater. Start the generator set.
leads and apply 12 volts DC to the hourmeter. The hourmeter is polarity sensitive.
Set the voltmeter setting 20 volts AC or greater. Crank the generator set and allow the set to reach rated its speed.
A 12 volt DC reading indicates the wiring harness is functional.
If functional, hourmeter operates.
A reading of 12--15 volts AC indicates a functional B1/B2 winding.
Figure 8-1 Engine/Generator Component Testing, Relay Controller
TP-5986 4/03 33Section 8 Component Troubleshooting
Page 48
WARNING
To further check the generator set components, disconnect the battery and remove the wiring harness plugs from the controller circuit board. Use an ohmmeter to check the continuity of the components and to isolate inoperative components. Refer to
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury
and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
Component Ohmmeter Connections Procedure Results
Start/stop switch Connect the ohmmeter to the
K20 relay coil and wiring Connect the ohmmeter to the
Starter solenoid (S relay)
Controller 10-amp circuit breaker and wiring
Moving rotor.
P2-6 and P2-4 leads.
Connect the ohmmeter to the P2-6 and P2-5 leads.
P1-4 and P1-9 leads.
Connect the ohmmeter to the P4-22 lead and the battery positive (+) cable. Note:The J4 and P4 leads must be disconnected to perform this test.
Connect the ohmmeter to the battery positive (+) cable and the P1-14 lead. Note:TheJ4 and P4 leads must be connected to perform this test.
Figure 8-2 and Figure 8-3.
Note: Before performing ohmmeter checks, disconnect
the generator set battery to prevent damage to the ohmmeter.
Place the ohmmeter on the R x 1000 scale. Place the rocker switch in the START position.
Place the ohmmeter on the R x 1000 scale. Place the rocker switch in the STOP position.
Place the ohmmeter on the Rx1scale.
Place the ohmmeter on the Rx1scale.
Place the ohmmeter on the R x 1000 scale.
If the switch is functional, zero ohms continuity. Any resistance other than zero or very low ohms, replace the switch.
If the switch is functional, zero ohms continuity. Any resistance other than zero or very low ohms, replace the switch.
If functional, 85 ohms. Low resistance, shorted C relay coil and/or wiring. High resistance, open C relay and/or wiring.
If functional, approximately
0.5--0.6 ohms at 27_C(80_F)
If functional, zero or very low ohms. No reading (infinity), open circuit or circuit breaker tripped.
Figure 8-2 Engine/Generator Component Testing, Relay Controller
TP-5986 4/0334 Section 8 Component Troubleshooting
Page 49
Component Ohmmeter Connections Procedure Results
Main field (rotor) Disconnect the P10 and P11
B1/B2 stator windings Connect the ohmmeter to the
P1 ground connection Connect the ohmmeter to the
Low oil pressure (LOP) safety shutdown switch
High exhaust temperature (HET), low coolant (LCS) safety shutdown switches
connectors and connect the ohmmeter to P10-1 and P10-2 leads.
P11-1 and P11-2 leads. Note: Disconnect P11 and J11 to perform this test.
P1-9 and ground.
Connect the ohmmeter to the P13-1 and engine block (ground).
Connect the ohmmeter to the P1-15 and engine block (ground). Note: Remove and isolate the LOP switch lead.
Place the ohmmeter on the Rx1scale.
Place the ohmmeter on the Rx1scale.
Place the ohmmeter on the Rx1scale.
Place the ohmmeter on the R x 1000 scale. This test is not conclusive until the temperature shutdown switches are checked.
Place the ohmmeter on the R x 1000 scale.
If functional, see Section 1, Specifications. Low resistance, rotor windings shorted. High resistance, rotor windings open.
If functional, see Section 1, Specifications. Low resistance, B1/B2 windings shorted. High resistance, B1/B2 windings open.
If functional, zero ohms (continuity). Any other reading indicates a poor ground connection.
If functional, zero ohms (continuity). Then, disconnect LOP switch lead and isolate terminal. Meter reading should show an open circuit.
If functional, open circuit. Any continuity suggests an inoperative temperature switch(es). Disconnect individual leads to inoperative switch.
Figure 8-3 Engine/Generator Component Testing, Relay Controller
8.2 Remote Panels (Optional)
Kohler Co. offers three remote panels for connection to the generator set.
Troubleshooting Remote Start Panels
Generally, if the sender changes its resistance values as its respective pressure/temperature changes, it is working correctly. An inoperative sender will either be
D A panel with a start/stop switch
open or shorted. Refer to Figure 8-4 and Figure 8-5 for resistance values.
D A panel with a start/stop switch and two gauges
(engine oil pressure and water temperature)
D A panel with a start/stop switch and four gauges
(DC voltmeter, engine oil pressure, water temperature, and hourmeter)
If difficulty with the remote operation occurs, test the
Figure 8-4 Water Temperature Sender Resistance switch, gauges, and gauge senders using the following procedures. See Sections 10.6, 10.7, or 10.8 to identify the location for the appropriate panel.
Figure 8-5 Oil Pressure Sender Resistance
2-Meter and 4-Meter Panels Temperature
60_C (140_F) 134.0 ±10 ohms
90_C (194_F) 51.5 ± 4 ohms
100_C (212_F) 38.0 ± 3 ohms
2-Meter and 4-Meter Panels Pressure
0 kPa (0 psi) 10 ohms
345 kPa (50 psi) 80 ohms
690 kPa (100 psi) 135 ohms
TP-5986 4/03 35Section 8 Component Troubleshooting
Page 50
Refer to Figure 8-6 for troubleshooting information on the remote start panels.
Component Ohmmeter Connections Procedure Results
Remote start/stop switch
Remote switch: yellow/red wire terminal and black wire terminal.
Remote switch: grey/black wire terminal and black wire
.
Generator set ON light, gauge lights, DC voltmeter, and hourmeter
terminal
Connect the red test lead to P3-4 and black test lead to P3-1.
Water temperature gauge Connect the red test lead to
P3-4 (socket side) and black test lead to P3-2 (socket side).
Oil pressure gauge Connect the red test lead to
P3-4 (socket side) and black test lead to P3-3 (socket side).
Note: Check continuity of gauge wiring and extension harness before replacing components.
Place the ohmmeter on the R x 1 scale. Press the rocker switch to the START position.
Place the ohmmeter on the R x 1 scale. Press the rocker switch to the STOP position.
If 12 volts DC is present and the component does not function after the J3 is connected to the controller P3, replace the component. Place the controller rocker switch to the START position. Stop the generator set when the test is complete.
Start the generator set for the test. If 0.5--12-volts DC is present and the gauge does not function after the J3 is connected to controller, replace the gauge.
Start the generator set for the test. If 0.5--12-volts DC is present and the gauge does not function after the J3 is connected to the controller, replace the gauge.
Continuity, the switch is functional.
Continuity, the switch is functional.
Voltmeter setting 12 volts or greater. Generator set does not need to be running, just cranking for this test. Note: If the hourmeter is not illuminated, test by connecting it to a 12-volt battery. Note: The hourmeter is polarity sensitive.
Voltmeter setting 12 volts or greater.
Voltmeter setting 12 volts or greater.
Figure 8-6 Remote Start Panels Troubleshooting
TP-5986 4/0336 Section 8 Component Troubleshooting
Page 51
Section 9 Generator Disassembly/Reassembly
9.1 Disassembly
Disconnect the external connections—battery cables at the battery (negative (--) lead first), AC-output leads in the controller, remote start panel at the controller P3 connector, water line at the seawater pump, fuel line at the fuel pump filter inlet, and exhaust line at the mixing elbow. Observe all of the safety precautions listed during the disassembly/reassembly procedures.
Disassembly Procedure
1. Place the start/stop switch in the STOP position.
2. Disconnect the generator set engine starting battery, the negative (--) lead first.
3. Remove the controller cover.
4. Disconnect the P4 (22-pin) connector from J4.
5. Disconnect the controller ground strap (generator side).
Note: It is possible to connect the output leads in
various positions for different voltage configurations. Mark the leads for correct reconnection.
6. Disconnect the generator output leads 1, 2, 3, and 4 from the circuit breaker and the neutral stud (L0).
1
2
3
598691
1. Alternator end cover
2. Water pump
3. Vibromount nuts
Figure 9-1 Alternator end cover
14. Push the brushes into the holder. Secure the brushes into position by sliding a retainer into the brush keeping holes. Refer to Section 7.5.
15. Remove the brush holder and carefully pull the leads out of the stator housing. See Figure 9-3.
16. Remove the generator side vibromount nuts. See Figure 9-1.
17. Tilt the generator set up and brace it with a block of wood. Figure 9-2.
7. Disconnect the P11 (FP and FN) and P10 (F1 and F2) connectors.
8. Remove the fuel inlet hose.
9. Close the seacock and remove the water inlet hose from the water pump.
10. Remove the sound shield enclosure, if equipped.
11. If the generator set is not equipped with a sound shield enclosure, lift the controller from the rubber mounts while guiding the leads through the bottom opening of the controller box.
12. Remove the fuel pump and line from the generator.
13. Remove the alternator coverplate. See Figure 9-1.
1
598691
1. Block of wood
Figure 9-2 Raising the Generator
TP-5986 4/03 37Section 9 Generator Disassembly/Reassembly
Page 52
3, 4, 5 6
10 11
2
9
8
1
9
8
1. Generator adapter plate bolt, quantity 4
2. Generator adapter
3. Spring
4. Brush holder
5. Brush, quantity 2
6. Brush holder shim
7. Rotor bolt
8. Hardened washer
9. Generator overbolt, quantity 4
10. Retainer wire
11. Brush assembly mounting screws, quantity 2
7
12
1314
88
1718192021
12. Bracket, brush holder
13. Fan guard bolts, quantity 2
14. Fan guard
15. End bracket
16. Pipe plug
17. End drive fitting
18. End bracket bearing
19. O-ring
20. Stator assembly
21. Rotor assembly
1516
99
201-191-1
Figure 9-3 Alternator Assembly Components
1. Rotor bolt
2. Hammer
Figure 9-4 Removing the Rotor
18. Remove the end bracket overbolts. See Figure 9-3. Use a rubber mallet to separate the
1
end bracket from the stator housing.
19. Carefully remove the stator assembly from the generator adaptor plate.
20. Remove the rotor bolt and end drive fitting.
2
21. Reinstall the rotor bolt (without end fitting), finger tighten, and back off two turns.
598692
22. Strike the bolt with a hammer until the rotor is freed from the engine tapered drive shaft. Do not damage through bolt threads or bolt head. See Figure 9-4.
TP-5986 4/0338 Section 9 Generator Disassembly/Reassembly
Page 53
9.2 Collector Ring and Bearing Replacement
9. Install the sound shield enclosure.
10. Install the fuel line and fuel pump.
1. Unsolder the collector ring leads from the collector ring terminals.
2. Remove the collector rings with a three-jaw puller.
3. Remove the bearing with a three-jaw puller.
4. Press the new bearing onto the rotor shaft.
5. Align the collector ring keyway with the keyway on the rotor shaft. See Figure 9-6.
6. Press the new collector rings onto the rotor shaft.
Note: The new collector rings must be turned
downtoafinishof32microinchesusinga lathe and commutator stones. Turn down the collector rings on the rotor shaft.
7. Solder the leads onto the collector ring terminals. The connection is not to exceed 9.65 mm (0.38 in.) beyond the collector rings. See Figure 9-6.
8. Test to ensure continuity at the collector rings.
11. Reconnect the water inlet hose to the water pump.
12. Guide the leads from the stator through the bottom opening of the controller. Secure the controller.
13. Reconnect the leads from the stator to the controller using the reverse procedure of that listed in Section 9.1. Refer to Section 10, Wiring Diagrams.
14. Connect the generator set starting battery, the positive (+) lead first.
15. Test the generator operation.
Min. diameter mm (in.) 57.15 (2.250)
Max. finish 32 micro inches
Max. eccentricity mm (in.) 0.08 (0.003)
Max. out-of-round mm (in.) 0.01 (0.0002)
Figure 9-5 Collector Ring Dimensions
.38 maximum (as soldered)
9.3 Reassembly
1. Apply antiseize compound to the tapered shaft of the engine.
2. Align the rotor onto the engine shaft and secure with the end drive fitting and rotor bolt. Torque the rotor to 23.1 Nm (204 in. lbs.).
3. Carefully slide the stator assembly over the rotor.
4. Replace the end bracket o-ring.
5. Install the end bracket and torque the overbolts to
13.6 Nm (120 in. lbs).
6. Feed the brush leads inside the stator housing up through the opening. Secure the brush holder using the original screws.
7. Remove the brush retainer and check the brush alignment. See Section 7.5.
8. Install the coverplate and torque the coverplate bolts to 6.8 Nm (60 in. lbs.).
90°
2
View A-A
1. Collector ring leads
2. Keyways
Figure 9-6 Rotor Assembly
A
A
1
598695
TP-5986 4/03 39Section 9 Generator Disassembly/Reassembly
Page 54
Notes
TP-5986 4/0340 Section 9 Generator Disassembly/Reassembly
Page 55
Section 10 Wiring Diagrams and Voltage Reconnection
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the generator set as follows: (1) Place the generator set start/stop switch in the STOP position. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible
whenever electricity is present. Open the main circuit breakers of all power sources before servicing the equipment. Configure the installation to electrically ground the generator set, transfer switch, and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Moving rotor.
TP-5986 4/03 41Section 10 Wiring Diagrams and Voltage Reconnection
Page 56
10.1 Schematic Wiring Diagram
359343-J
TP-5986 4/0342 Section 10 Wiring Diagrams and Voltage Reconnection
Page 57
10.2 Point-to-Point Wiring Diagram
TP-5986 4/03 43Section 10 Wiring Diagrams and Voltage Reconnection
359343-J
Page 58
10.3 Reconnection Diagram 100--120 V, 60 & 50 Hz
10.5 Reconnection Diagram 220--240 V, 50 Hz
10.4 Reconnection Diagram 100--120/200--240 V, 60 & 50 Hz
ADV-5857
ADV-5857
10.6 Remote Start Panel
+--
P
10-amp Fuse
P
P1-14
P2-3 P2-7 P2-8 P2-9
70
P3-4
J3-4 J3-5 J3-1J3-6
Violet
47
P2-4
K2
K1
47
P3-5 P3-6 P3-1
Yellow/ Red
Local switch
Start
Relay circuit board
Grey/ Black
Stop
Start
Stop
43
P2-5 P2-6
43
Remote switch
ADV-5857
N
P1-9
N
N
Black
Gen. ON light
TP-5588-7
TP-5986 4/0344 Section 10 Wiring Diagrams and Voltage Reconnection
Page 59
10.7 Remote Start and Two-Meter Panel
10.8 Remote Start and Four-Meter Panel
+--
P
10-amp fuse
P
P1-14
K2
K1
P2-3
70
P3-4
J3-4 J3-5
Violet
Yellow/ Red
47
P2-4
P2-7
47
P3-5 P3-6
Local switch
Start
Relay circuit board
Grey/ Black
Stop
Start
Stop
43
P2-5 P2-6
P2-8 P2-9
43
P3-1
J3-6
Remote switch
N
P1-9
N
N
J3-1
Black
W.T. sender
P4-2 P4-3
7C
5
P3-2
P3-3
J3-2
Tan
L. Blue
O.P. sender
J3-3
+--
P
10-amp fuse
P
P1-14
K2
K1
P2-3
70
P3-4
J3-4 J3-5
Violet
Yellow/ Red
Gen. ON light
47
P2-4
P2-7
47
P3-5
Local switch
Start
Relay circuit board
Grey/ Black
Stop
Start
Stop
P2-8 P2-9
P3-6
Remote switch
43
P2-5 P2-6
43
P3-1
J3-6
N
P1-9
N
N
W.T. sender
P4-2 P4-3
7C
5
P3-2
J3-1 J3-2 J3-3
Black
P3-3
Tan
O.P. sender
L. Blue
Gen. ON light
Water temp. gauge
Oil pressure gauge
TP-5588-7
Water temp. gauge
Oil pressure gauge
DC voltmeter
Hourmeter
TP-5588-7
TP-5986 4/03 45Section 10 Wiring Diagrams and Voltage Reconnection
Page 60
Notes
TP-5986 4/0346 Section 10 Wiring Diagrams and Voltage Reconnection
Page 61
Appendix A Abbreviations
The following list contains abbreviations that may appear in this publication.
A, amp ampere ABDC after bottom dead center AC alternating current A/D analog to digital ADC analog to digital converter adj. adjust, adjustment ADV advertising dimensional
AHWT anticipatory high water
AISI American Iron and Steel
ALOP anticipatory low oil pressure alt. alternator Al aluminum ANSI American National Standards
AO anticipatory only API American Petroleum Institute approx. approximate, approximately AR as required, as requested AS as supplied, as stated, as
ASE American Society of Engineers ASME American Society of
assy. assembly ASTM American Society for Testing
ATDC after top dead center ATS automatic transfer switch auto. automatic aux. auxiliary A/V audiovisual avg. average AVR automatic voltage regulator AWG American Wire Gauge AWM appliance wiring material bat. battery BBDC before bottom dead center BC battery charger, battery
BCA battery charging alternator BCI Battery Council International BDC before dead center BHP brake horsepower blk. black (paint color), block
blk. htr. block heater BMEP brake mean effective pressure bps bits per second br. brass BTDC before top dead center Btu British thermal unit Btu/min. British thermal units per minute C Celsius, centigrade cal. calorie CARB California Air Resources Board CB circuit breaker cc cubic centimeter CCA cold cranking amps ccw. counterclockwise CEC Canadian Electrical Code cfh cubic feet per hour cfm cubic feet per minute
drawing
temperature
Institute
Institute (formerly American Standards Association, ASA)
suggested
Mechanical Engineers
Materials
charging
(engine)
CG center of gravity CID cubic inch displacement CL centerline cm centimeter CMOS complementary metal oxide
cogen. cogeneration Com communications (port) conn. connection cont. continued CPVC chlorinated polyvinyl chloride crit. critical CRT cathode ray tube CSA Canadian Standards
CT current transformer Cu copper cu. in. cubic inch cw. clockwise CWC city water-cooled cyl. cylinder D/A digital to analog DAC digital to analog converter dB decibel dBA decibel (A weighted) DC direct current DCR direct current resistance deg., ° degree dept. department dia. diameter DI/EO dual inlet/end outlet DIN Deutsches Institut fur Normung
DIP dual inline package DPDT double-pole, double-throw DPST double-pole, single-throw DS disconnect switch DVR digital voltage regulator E, emer. emergency (power source) EDI electronic data interchange EFR emergency frequency relay e.g. for example (exempli gratia) EG electronic governor EGSA Electrical Generating Systems
EIA Electronic Industries
EI/EO end inlet/end outlet EMI electromagnetic interference emiss. emission eng. engine EPA Environmental Protection
EPS emergency power system ER emergency relay ES engineering special,
ESD electrostatic discharge est. estimated E-Stop emergency stop etc. et cetera (and so forth) exh. exhaust ext. external F Fahrenheit, female
substrate (semiconductor)
Association
e. V. (also Deutsche Industrie Normenausschuss)
Association
Association
Agency
engineered special
fglass. fiberglass FHM flat head machine (screw) fl. oz. fluid ounce flex. flexible freq. frequency FS full scale ft. foot, feet ft. lbs. foot pounds (torque) ft./min. feet per minute ggram ga. gauge (meters, wire size) gal. gallon gen. generator genset generator set GFI ground fault interrupter
GND, gov. governor gph gallons per hour gpm gallons per minute gr. grade, gross GRD equipment ground gr. wt. gross weight H x W x D height by width by depth HC hex cap HCHT high cylinder head temperature HD heavy duty HET high exhaust temperature hex hexagon Hg mercury (element) HH hex head HHC hex head cap HP horsepower hr. hour HS heat shrink hsg. housing HVAC heating, ventilation, and air
HWT high water temperature Hz hertz (cycles per second) IC integrated circuit ID inside diameter, identification IEC International Electrotechnical
IEEE Institute of Electrical and
IMS improved motor starting in. inch in. H in. Hg inches of mercury in. lbs. inch pounds Inc. incorporated ind. industrial int. internal int./ext. internal/external I/O input/output IP iron pipe ISO International Organization for
J joule JIS Japanese Industry Standard k kilo (1000) K kelvin kA kiloampere KB kilobyte (2
ground
conditioning
Commission
Electronics Engineers
O inches of water
2
Standardization
10
bytes)
TP-5986 4/03 Appendix A-1
Page 62
kg kilogram
2
kg/cm
kgm kilogram-meter kg/m
kilograms per square centimeter
3
kilograms per cubic meter kHz kilohertz kJ kilojoule km kilometer kOhm, kkilo-ohm kPa kilopascal kph kilometers per hour kV kilovolt kVA kilovolt ampere kVAR kilovolt ampere reactive kW kilowatt kWh kilowatt-hour kWm kilowatt mechanical L liter LAN local area network L x W x H length by width by height lb. pound, pounds
3
lbm/ft
pounds mass per cubic feet LCB line circuit breaker LCD liquid crystal display ld. shd. load shed LED light emitting diode Lph liters per hour Lpm liters per minute LOP low oil pressure LP liquefied petroleum LPG liquefied petroleum gas LS left side L
wa
sound power level, A weighted LWL low water level LWT low water temperature m meter, milli (1/1000) M mega (10
3
m
3
m
units), male
cubic meter
/min. cubic meters per minute
6
when used with SI
mA milliampere man. manual max. maximum MB megabyte (2
20
bytes) MCM one thousand circular mils MCCB molded-case circuit breaker meggar megohmmeter MHz megahertz mi. mile mil one one-thousandth of an inch min. minimum, minute misc. miscellaneous MJ megajoule mJ millijoule mm millimeter mOhm, m
milliohm
MOhm, M
megohm MOV metal oxide varistor MPa megapascal mpg miles per gallon mph miles per hour MS military standard m/sec. meters per second MTBF mean time between failure MTBO mean time between overhauls mtg. mounting
MW megawatt mW milliwatt μF microfarad N, norm. normal (power source) NA not available, not applicable nat. gas natural gas NBS National Bureau of Standards NC normally closed NEC National Electrical Code NEMA National Electrical
Manufacturers Association
NFPA National Fire Protection
Association Nm newton meter NO normally open no., nos. number, numbers NPS National Pipe, Straight NPSC National Pipe, Straight-coupling NPT National Standard taper pipe
thread per general use NPTF National Pipe, Taper-Fine NR not required, normal relay ns nanosecond OC overcrank OD outside diameter OEM original equipment
manufacturer OF overfrequency opt. option, optional OS oversize, overspeed OSHA Occupational Safety and Health
Administration OV overvoltage oz. ounce p., pp. page, pages PC personal computer PCB printed circuit board pF picofarad PF power factor
ph.,
phase
PHC Phillips head crimptite (screw) PHH Phillips hex head (screw) PHM pan head machine (screw) PLC programmable logic control PMG permanent-magnet generator pot potentiometer, potential ppm parts per million PROM programmable read-only
memory psi pounds per square inch pt. pint PTC positive temperature coefficient PTO power takeoff PVC polyvinyl chloride qt. quart qty. quantity R replacement (emergency)
power source rad. radiator, radius RAM random access memory RDO relay driver output ref. reference rem. remote RFI radio frequency interference RH round head RHM round head machine (screw) rly. relay
rms root mean square rnd. round ROM read only memory rot. rotate, rotating rpm revolutions per minute RS right side RTV room temperature vulcanization SAE Society of Automotive
Engineers scfm standard cubic feet per minute SCR silicon controlled rectifier s, sec. second SI Systeme international d’unites,
International System of Units SI/EO side in/end out sil. silencer SN serial number SPDT single--pole, double--throw SPST single--pole, single--throw spec, specs
specification(s) sq. square sq. cm square centimeter sq. in. square inch SS stainless steel std. standard stl. steel tach. tachometer TD time delay TDC top dead center TDEC time delay engine cooldown TDEN time delay emergency to
normal TDES time delay engine start TDNE time delay normal to
emergency TDOE time delay off to emergency TDON time delay off to normal temp. temperature term. terminal TIF telephone influence factor TIR total indicator reading tol. tolerance turbo. turbocharger typ. typical (same in multiple
locations) UF underfrequency UHF ultrahigh frequency UL Underwriter’s Laboratories, Inc. UNC unified coarse thread (was NC) UNF unified fine thread (was NF) univ. universal US undersize, underspeed UV ultraviolet, undervoltage V volt VAC volts alternating current VAR voltampere reactive VDC volts direct current VFD vacuum fluorescent display VGA video graphics adapter VHF very high frequency W watt WCR withstand and closing rating w/ with w/o without wt. weight xfmr transformer
TP-5986 4/03A-2 Appendix
Page 63
Appendix B Common Hardware Application Guidelines
Use the information below and on the following pages to identify proper fastening techniques when no specific reference for reassembly is made.
Bolt/Screw Length: When bolt/screw length is not given, use Figure 1 as a guide. As a general rule, a minimum length of one thread beyond the nut and a maximum length of 1/2 the bolt/screw diameter beyond the nut is the preferred method.
Washers and Nuts: Use split lock washers as a bolt locking device where specified. Use SAE flat washers with whiz nuts, spiralock nuts, or standard nuts and preloading (torque) of the bolt in all other applications.
See General Torque Specifications and other torque specifications in the service literature.
Preferred Nut/Bolt Clearance
1
2
Steps for common hardware application
1. Determine entry hole type: round or slotted.
2. Determine exit hole type: fixed female thread (weld nut), round, or slotted.
For round and slotted exit holes, determine if hardware is greater than 1/2 inch in diameter, or 1/2 inch in diameter or less. Hardware that is greater than 1/2 inch in diameter takes a standard nut and SAE washer. Hardware 1/2 inch or less in diameter can take a properly torqued whiz nut or spiralock nut. See the diagram below.
3. Follow these SAE washer rules after determining exit hole type:
a. Always use a washer between hardware and a
slot.
b. Always use a washer under a nut (see 2 above
for exception).
c. Use a washer under a bolt when the female
thread is fixed (weld nut).
Unacceptable Nut/Bolt Clearance
1. 1/2 of bolt diameter
2. Minimum 1 full thread beyond top of nut
3. Below top of nut
Figure 1 Acceptable Bolt Lengths
4. Refer to the diagram below, which depicts the preceding hardware configuration possibilities.
3
G-585
1. Cap screw
2. Entry hole types
3. Standard nut and SAE washer
4. Whiz nut or spiralock: up to 1/2 in. dia. hardware
5. Weld nuts: above 1/2 in. dia. hardware
6. Exit hole types
1
6
2
3
5
4
G-585
TP-5986 4/03 A-3Appendix
Figure 2 Acceptable Hardware Combinations
Page 64
Appendix C General Torque Specifications
A
Assembledinto
A
Use the following torque specifications when service literature instructions give no specific torque values. The charts list values for new plated, zinc phosphate, or
American Standard Fasteners Torque Specifications
Assembled into Cast Iron or Steel
Torque
Size
8-32 in.lbs.(Nm) 16 (1.8) 20 (2.3) 16 (1.8) 10-24 in.lbs.(Nm) 26 (2.9) 32 (3.6) 26 (2.9) 10-32 in.lbs.(Nm) 26 (2.9) 32 (3.6) 26 (2.9) 1/4-20 in.lbs.(Nm) 60 (6.8) 96 (10.8) 132 (14.9) 60 (6.8) 1/4-28 in.lbs.(Nm) 72 (8.1) 108 (12.2) 144 (16.3) 72 (8.1) 5/16-18 in.lbs.(Nm) 120 (13.6) 192 (21.7) 264 (29.8) 120 (13.6) 5/16-24 in.lbs.(Nm) 132 (14.9) 204 (23.1) 288 (32.5) 132 (14.9) 3/8-16 ft. lbs. (Nm) 18 (24) 28 (38) 39 (53) 18 (24) 3/8-24 ft. lbs. (Nm) 20 (27) 31 (42) 44 (60) 20 (27) 7/16-14 ft. lbs. (Nm) 29 (39) 44 (60) 63 (85) — 7/16-20 ft. lbs. (Nm) 32 (43) 50 (68) 70 (95) — 1/2-13 ft. lbs. (Nm) 44 (60) 68 (92) 96 (130) — 1/2-20 ft. lbs. (Nm) 49 (66) 76 (103) 108 (146) — 9/16-12 ft. lbs. (Nm) 60 (81) 98 (133) 138 (187) — 9/16-18 ft. lbs. (Nm) 67 (91) 109 (148) 154 (209) — 5/8-11 ft. lbs. (Nm) 83 (113) 135 (183) 191 (259) — 5/8-18 ft. lbs. (Nm) 94 (128) 153 (208) 216 (293) — 3/4-10 ft. lbs. (Nm) 147 (199) 240 (325) 338 (458) — 3/4-16 ft. lbs. (Nm) 164 (222) 268 (363) 378 (513) — 1-8 ft. lbs. (Nm) 191 (259) 532 (721) 818 (1109) — 1-12 ft. lbs. (Nm) 209 (283) 582 (789) 895 (1214)
Measurement
Grade 2 Grade 5 Grade 8
oiled threads. Increase values by 15% for nonplated threads. All torque values are +0%/--10%.
ssembled into
Aluminum
Grade2or5
Metric Fasteners Torque Specifications, Measured in ft. lbs. (Nm)
Assembled into Cast Iron or Steel
Size (mm) Grade 5.8 Grade 8.8 Grade 10.9
M6 x 1.00 4 (5.6) 7 (9.9) 10 (14) 4 (5.6) M8 x 1.25 10 (13.6) 18 (25) 26 (35) 10 (13.6) M8 x 1.00 16 (21) 18 (25) 26 (35) 16 (21) M10 x 1.50 20 (27) 35 (49) 50 (68) 20 (27) M10 x 1.25 29 (39) 35 (49) 50 (68) 29 (39) M12 x 1.75 35 (47) 61 (83) 86 (117) — M12 x 1.50 48 (65) 65 (88) 92 (125) — M14 x 2.00 55 (74) 97 (132) 136 (185) — M14 x 1.50 74 (100) 103 (140) 142 (192) — M16 x 2.00 85 (115) 148 (200) 210 (285) — M16 x 1.50 104 (141) 155 (210) 218 (295) — M18 x 2.50 114 (155) 203 (275) 288 (390) — M18 x 1.50 145 (196) 225 (305) 315 (425)
Assembled into
luminum
Grade 5.8 or 8.8
TP-5986 4/03A-4 Appendix
Page 65
Appendix D Common Hardware Identification
Screw/Bolts/Studs
Head Styles
Hex Head or Machine Head
Hex Head or Machine Head with Washer
Flat Head (FHM)
Round Head (RHM)
Pan Head
Hex Socket Head Cap or Allent Head Cap
Hex Socket Head or Allent Head Shoulder Bolt
Sheet Metal Screw
Stud
Drive Styles
Hex
Hex and Slotted
Phillipsr
Nuts
Nut Styles
Hex Head
Lock or Elastic
Square
Cap or Acorn
Wing
Washers
Washer Styles
Plain
Split Lock or Spring
Spring or Wave
External Tooth Lock
Internal Tooth Lock
Internal-External Tooth Lock
Hardness Grades
American Standard
Grade 2
Grade 5
Grade 8
Grade 8/9 (Hex Socket Head)
Metric
Number stamped on hardware; 5.8 shown
5.8
Slotted
Hex Socket
Allent head screw is a trademark of Holo-Krome Co.
Phillipsr screw is a registered trademark of Phillips Screw Company.
Sample Dimensions
American Standard (Screws, Bolts, Studs, and Nuts)
1/4-20 x 1
Metric (Screws, Bolts, Studs, and Nuts)
M8-1.25 x 20
Length In Inches (Screws and Bolts)
Threads Per Inch
Major Thread Diameter In Fractional Inches Or Screw Number Size
Length In Millimeters (Screws and Bolts)
Distance Between Threads In Millimeters
Major Thread Diameter In Millimeters
Plain Washers
9/32
x5/8x 1/16
Lock Washers
5/8
Thickness
External Dimension
Internal Dimension
Internal Dimension
TP-5986 4/03 A-5Appendix
Page 66
Appendix E Common Hardware List
The Common Hardware List lists part numbers and dimensions for common hardware items.
American Standard
Part No. Dimensions Hex Head Bolts (Grade 5)
X-465-17 1/4-20 x .38 X-465-6 1/4-20 x .50 X-465-2 1/4-20 x .62 X-465-16 1/4-20 x .75 X-465-18 1/4-20 x .88 X-465-7 1/4-20 x 1.00 X-465-8 1/4-20 x 1.25 X-465-9 1/4-20 x 1.50 X-465-10 1/4-20 x 1.75 X-465-11 1/4-20 x 2.00 X-465-12 1/4-20 x 2.25 X-465-14 1/4-20 x 2.75 X-465-21 1/4-20 x 5.00 X-465-25 1/4-28 x .38 X-465-20 1/4-28 x 1.00
X-125-33 5/16-18 x .50 X-125-23 5/16-18 x .62 X-125-3 5/16-18 x .75 X-125-31 5/16-18 x .88 X-125-5 5/16-18 x 1.00 X-125-24 5/16-18 x 1.25 X-125-34 5/16-18 x 1.50 X-125-25 5/16-18 x 1.75 X-125-26 5/16-18 x 2.00 230578 5/16-18 x 2.25 X-125-29 5/16-18 x 2.50 X-125-27 5/16-18 x 2.75 X-125-28 5/16-18 x 3.00 X-125-22 5/16-18 x 4.50 X-125-32 5/16-18 x 5.00 X-125-35 5/16-18 x 5.50 X-125-36 5/16-18 x 6.00 X-125-40 5/16-18 x 6.50
X-125-43 5/16-24 x 1.75 X-125-44 5/16-24 x 2.50 X-125-30 5/16-24 x .75 X-125-39 5/16-24 x 2.00 X-125-38 5/16-24 x 2.75
X-6238-2 3/8-16 x .62 X-6238-10 3/8-16 x .75 X-6238-3 3/8-16 x .88 X-6238-11 3/8-16 x 1.00 X-6238-4 3/8-16 x 1.25 X-6238-5 3/8-16 x 1.50 X-6238-1 3/8-16 x 1.75 X-6238-6 3/8-16 x 2.00 X-6238-17 3/8-16 x 2.25 X-6238-7 3/8-16 x 2.50 X-6238-8 3/8-16 x 2.75 X-6238-9 3/8-16 x 3.00 X-6238-19 3/8-16 x 3.25 X-6238-12 3/8-16 x 3.50 X-6238-20 3/8-16 x 3.75 X-6238-13 3/8-16 x 4.50 X-6238-18 3/8-16 x 5.50 X-6238-25 3/8-16 x 6.50
Part No. Dimensions Hex Head Bolts, cont.
X-6238-14 3/8-24 x .75 X-6238-16 3/8-24 x 1.25 X-6238-21 3/8-24 x 4.00 X-6238-22 3/8-24 x 4.50
X-6024-5 7/16-14 x .75 X-6024-2 7/16-14 x 1.00 X-6024-8 7/16-14 x 1.25 X-6024-3 7/16-14 x 1.50 X-6024-4 7/16-14 x 2.00 X-6024-11 7/16-14 x 2.75 X-6024-12 7/16-14 x 6.50
X-129-15 1/2-13 x .75 X-129-17 1/2-13 x 1.00 X-129-18 1/2-13 x 1.25 X-129-19 1/2-13 x 1.50 X-129-20 1/2-13 x 1.75 X-129-21 1/2-13 x 2.00 X-129-22 1/2-13 x 2.25 X-129-23 1/2-13 x 2.50 X-129-24 1/2-13 x 2.75 X-129-25 1/2-13 x 3.00 X-129-27 1/2-13 x 3.50 X-129-29 1/2-13 x 4.00 X-129-30 1/2-13 x 4.50 X-463-9 1/2-13 x 5.50 X-129-44 1/2-13 x 6.00
X-129-51 1/2-20 x .75 X-129-45 1/2-20 x 1.25 X-129-52 1/2-20 x 1.50
X-6021-3 5/8-11 x 1.00 X-6021-4 5/8-11 x 1.25 X-6021-2 5/8-11 x 1.50 X-6021-1 5/8-11 x 1.75 273049 5/8-11 x 2.00 X-6021-5 5/8-11 x 2.25 X-6021-6 5/8-11 x 2.50 X-6021-7 5/8-11 x 2.75 X-6021-12 5/8-11 x 3.75 X-6021-11 5/8-11 x 4.50 X-6021-10 5/8-11 x 6.00
X-6021-9 5/8-18 x 2.50
X-6239-1 3/4-10 x 1.00 X-6239-8 3/4-10 x 1.25 X-6239-2 3/4-10 x 1.50 X-6239-3 3/4-10 x 2.00 X-6239-4 3/4-10 x 2.50 X-6239-5 3/4-10 x 3.00 X-6239-6 3/4-10 x 3.50
X-792-1 1-8 x 2.25 X-792-5 1-8 x 3.00 X-792-8 1-8 x 5.00
Part No. Dimensions Type
Hex Nuts
X-6009-1 1-8 Standard
X-6210-3 6-32 Whiz X-6210-4 8-32 Whiz X-6210-5 10-24 Whiz X-6210-1 10-32 Whiz
X-6210-2 1/4-20 Spiralock X-6210-6 1/4-28 Spiralock X-6210-7 5/16-18 Spiralock X-6210-8 5/16-24 Spiralock X-6210-9 3/8-16 Spiralock X-6210-10 3/8-24 Spiralock X-6210-11 7/16-14 Spiralock X-6210-12 1/2-13 Spiralock X-6210-15 7/16-20 Spiralock X-6210-14 1/2-20 Spiralock
X-85-3 5/8-11 Standard X-88-12 3/4-10 Standard X-89-2 1/2-20 Standard
Washers
Bolt/
Part No. ID OD Thick. Screw
X-25-46 .125 .250 .022 #4 X-25-9 .156 .375 .049 #6 X-25-48 .188 .438 .049 #8 X-25-36 .219 .500 .049 #10 X-25-40 .281 .625 .065 1/4 X-25-85 .344 .687 .065 5/16 X-25-37 .406 .812 .065 3/8 X-25-34 .469 .922 .065 7/16 X-25-26 .531 1.062 .095 1/2 X-25-15 .656 1.312 .095 5/8 X-25-29 .812 1.469 .134 3/4 X-25-127 1.062 2.000 .134 1
TP-5986 4/03A-6 Appendix
Page 67
Metric
Hex head bolts are hardness grade 8.8 unless noted.
Part No. Dimensions Hex Head Bolts (Partial Thread)
M931-05055-60 M5-0.80 x 55 M931-06040-60 M6-1.00 x 40 M931-06055-60 M6-1.00 x 55 M931-06060-60 M6-1.00 x 60 M931-06060-SS M6-1.00 x 60 M931-06070-60 M6-1.00 x 70 M931-06070-SS M6-1.00 x 70 M931-06075-60 M6-1.00 x 75 M931-06090-60 M6-1.00 x 90 M931-06145-60 M6-1.00 x 145 M931-06150-60 M6-1.00 x 150
M931-08035-60 M8-1.25 x 35 M931-08040-60 M8-1.25 x 40 M931-08040-82 M8-1.25 x 40* M931-08045-60 M8-1.25 x 45 M931-08050-60 M8-1.25 x 50 M931-08055-60 M8-1.25 x 55 M931-08055-82 M8-1.25 x 55* M931-08060-60 M8-1.25 x 60 M931-08070-60 M8-1.25 x 70 M931-08070-82 M8-1.25 x 70* M931-08075-60 M8-1.25 x 75 M931-08080-60 M8-1.25 x 80 M931-08090-60 M8-1.25 x 90 M931-08095-60 M8-1.25 x 95 M931-08100-60 M8-1.25 x 100 M931-08110-60 M8-1.25 x 110 M931-08120-60 M8-1.25 x 120 M931-08130-60 M8-1.25 x 130 M931-08140-60 M8-1.25 x 140 M931-08150-60 M8-1.25 x 150
M931-10040-82 M10-1.25 x 40* M931-10040-60 M10-1.50 x 40 M931-10045-60 M10-1.50 x 45 M931-10050-60 M10-1.50 x 50 M931-10050-82 M10-1.25 x 50 M931-10055-60 M10-1.50 x 55 M931-10060-60 M10-1.50 x 60 M931-10065-60 M10-1.50 x 65 M931-10070-60 M10-1.50 x 70 M931-10080-60 M10-1.50 x 80 M931-10080-82 M10-1.25 x 80 M931-10090-60 M10-1.50 x 90 M931-10090-82 M10-1.50 x 90* M931-10100-60 M10-1.50 x 100 M931-10110-60 M10-1.50 x 110 M931-10120-60 M10-1.50 x 120 M931-10130-60 M10-1.50 x 130 M931-10140-60 M10-1.50 x 140 M931-10180-60 M10-1.50 x 180 M960-10330-60 M10-1.25 x 330
M931-12045-60 M12-1.75 x 45 M960-12050-60 M12-1.25 x 50 M960-12050-82 M12-1.25 x 50* M931-12050-60 M12-1.75 x 50 M931-12050-82 M12-1.75 x 50 M931-12055-60 M12-1.75 x 55 M931-12060-60 M12-1.75 x 60 M931-12060-82 M12-1.75 x 60 M931-12065-60 M12-1.75 x 65 M931-12075-60 M12-1.75 x 75 M931-12080-60 M12-1.75 x 80 M931-12090-60 M12-1.75 x 90 M931-12100-60 M12-1.75 x 100 M931-12110-60 M12-1.75 x 110
Part No. Dimensions Hex Head Bolts (Partial Thread),
continued
M960-16090-60 M16-1.50 x 90 M931-16090-60 M16-2.00 x 90 M931-16100-60 M16-2.00 x 100 M931-16120-60 M16-2.00 x 120 M931-16150-60 M16-2.00 x 150
M931-20065-60 M20-2.50 x 65 M931-20100-60 M20-2.50 x 100 M931-20120-60 M20-2.50 x 120 M931-20140-60 M20-2.50 x 140 M931-20160-60 M20-2.50 x 160
M931-22090-60 M22-2.50 x 90 M931-22120-60 M22-2.50 x 120 M931-22160-60 M22-2.50 x 160
M931-24090-60 M24-3.00 x 90 M931-24120-60 M24-3.00 x 120 M931-24160-60 M24-3.00 x 160
Hex Head Bolts (Full Thread)
M933-04006-60 M4-0.70 x 6
M933-05030-60 M5-0.80 x 30 M933-05035-60 M5-0.80 x 35 M933-05050-60 M5-0.80 x 50
M933-06010-60 M6-1.00 x 10 M933-06012-60 M6-1.00 x 12 M933-06014-60 M6-1.00 x 14 M933-06016-60 M6-1.00 x 16 M933-06020-60 M6-1.00 x 20 M933-06025-60 M6-1.00 x 25 M933-06040-60 M6-1.00 x 40 M933-06050-60 M6-1.00 x 50
M933-07025-60 M7-1.00 x 25
M933-08010-60 M8-1.25 x 10 M933-08012-60 M8-1.25 x 12 M933-08016-60 M8-1.25 x 16 M933-08020-60 M8-1.25 x 20 M933-08025-60 M8-1.25 x 25 M933-08030-60 M8-1.25 x 30 M933-08030-82 M8-1.25 x 30*
M933-10012-60 M10-1.50 x 12 M961-10020-60 M10-1.25 x 20 M933-10020-60 M10-1.50 x 20 M933-10025-60 M10-1.50 x 25 M961-10025-60 M10-1.25 x 25 M933-10025-82 M10-1.50 x 25 M961-10030-60 M10-1.25 x 30 M933-10030-60 M10-1.50 x 30 M933-10030-82 M10-1.50 x 30* M961-10035-60 M10-1.25 x 35 M933-10035-60 M10-1.50 x 35 M933-10035-82 M10-1.50 x 35 M961-10040-60 M10-1.25 x 40
M933-12016-60 M12-1.75 x 16 M933-12020-60 M12-1.75 x 20 M961-12020-60F M12-1.50 x 20 M933-12025-60 M12-1.75 x 25 M933-12025-82 M12-1.75 x 25* M961-12030-60 M12-1.25 x 30 M961-12030-82F M12-1.50 x 30 M933-12030-60 M12-1.75 x 30 M933-12035-60 M12-1.75 x 35 M961-12040-82 M12-1.25 x 40* M933-12040-60 M12-1.75 x 40 M933-12040-82 M12-1.75 x 40*
Part No. Dimensions Hex Head Bolts (Full Thread),
continued
M961-14025-60 M14-1.50 x 25 M933-14025-60 M14-2.00 x 25 M961-14050-82 M14-1.50 x 50
M961-16025-60 M16-1.50 x 25 M933-16025-60 M16-2.00 x 25 M961-16030-82 M16-1.50 x 30* M933-16030-82 M16-2.00 x 30* M933-16035-60 M16-2.00 x 35 M961-16040-60 M16-1.50 x 40 M933-16040-60 M16-2.00 x 40 M961-16045-82 M16-1.50 x 45 M933-16045-82 M16-2.00 x 45 M933-16050-60 M16-2.00 x 50 M933-16050-82 M16-2.00 x 50* M933-16060-60 M16-2.00 x 60 M933-16070-60 M16-2.00 x 70
M933-18035-60 M18-2.50 x 35 M933-18050-60 M18-2.50 x 50 M933-18060-60 M18-2.50 x 60
M933-20050-60 M20-2.50 x 50 M933-20055-60 M20-2.50 x 55
M933-24060-60 M24-3.00 x 60 M933-24065-60 M24-3.00 x 65 M933-24070-60 M24-3.00 x 70
Pan Head Machine Screws
M7985A-03010-20 M3-0.50 x 10 M7985A-03012-20 M3-0.50 x 12
M7985A-04010-20 M4-0.70 x 10 M7985A-04016-20 M4-0.70 x 16 M7985A-04020-20 M4-0.70 x 20 M7985A-04050-20 M4-0.70 x 50 M7985A-04100-20 M4-0.70 x 100
M7985A-05010-20 M5-0.80 x 10 M7985A-05012-20 M5-0.80 x 12 M7985A-05016-20 M5-0.80 x 16 M7985A-05020-20 M5-0.80 x 20 M7985A-05025-20 M5-0.80 x 25 M7985A-05030-20 M5-0.80 x 30 M7985A-05080-20 M5-0.80 x 80 M7985A-05100-20 M5-0.80 x 100
M7985A-06100-20 M6-1.00 x 100
Flat Head Machine Screws
M965A-04012-SS M4-0.70 x 12
M965A-05012-SS M5-0.80 x 12 M965A-05016-20 M5-0.80 x 16 M965A-06012-20 M6-1.00 x 12
* This metric hex bolt’s hardness is grade 10.9.
TP-5986 4/03 A-7Appendix
Page 68
Metric, continued
Part No. Dimensions Type Hex Nuts
M934-03-50 M3-0.50 Standard
M934-04-50 M4-0.70 Standard
M934-05-50 M5-0.80 Standard M982-05-60 M5-0.80 Elastic Stop
M934-06-60 M6-1.00 Standard M934-06-64 M6-1.00 Std. (green) M6923-06-80 M6-1.00 Spiralock M982-06-80 M6-1.00 Elastic Stop
M934-08-60 M8-1.25 Standard M6923-08-80 M8-1.25 Spiralock M982-08-80 M8-1.25 Elastic Stop
M934-10-60 M10-1.50 Standard M934-10-60F M10-1.25 Standard M6923-10-80 M10-1.50 Spiralock M6923-10-62 M10-1.50 Spiralock[ M982-10-80 M10-1.50 Elastic Stop
M934-12-60 M12-1.75 Standard M934-12-60F M12-1.25 Standard M6923-12-80 M12-1.75 Spiralock M982-12-80 M12-1.75 Elastic Stop
M982-14-60 M14-2.00 Elastic Stop
M6923-16-80 M16-2.00 Spiralock M982-16-80 M16-2.00 Elastic Stop
M934-18-80 M18-2.5 Standard M982-18-60 M18-2.50 Elastic Stop
M934-20-80 M20-2.50 Standard M982-20-80 M20-2.50 Elastic Stop
M934-22-60 M22-2.50 Standard
M934-24-80 M24-3.00 Standard M982-24-60 M24-3.00 Elastic Stop
M934-30-80 M30-3.50 Standard
Washers
Bolt/
Part No. ID OD Thick. Screw
M125A-03-80 3.2 7.0 0.5 M3 M125A-04-80 4.3 9.0 0.8 M4 M125A-05-80 5.3 10.0 1.0 M5 M125A-06-80 6.4 12.0 1.6 M6 M125A-08-80 8.4 16.0 1.6 M8 M125A-10-80 10.5 20.0 2.0 M10 M125A-12-80 13.0 24.0 2.5 M12 M125A-14-80 15.0 28.0 2.5 M14 M125A-16-80 17.0 30.0 3.0 M16 M125A-18-80 19.0 34.0 3.0 M18 M125A-20-80 21.0 37.0 3.0 M20 M125A-24-80 25.0 44.0 4.0 M24
[ This metric hex nut’s hardness is grade 8.
TP-5986 4/03A-8 Appendix
Page 69
Page 70
Page 71
Page 72
TP-5986 4/03b
E2000, 2003 by Kohler Co. All rights reserved.
KOHLER CO. Kohler, Wisconsin 53044 Phone 920-565-3381, Fax 920-459-1646 For the nearest sales/service outlet in the US and Canada, phone 1-800-544-2444 KohlerPowerSystems.com
Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65)264-6422, Fax (65)264-6455
Loading...