10.6 Remote Start and 2-Meter Panel56.............
10.7 Remote Start and 4-Meter Panel57.............
Appendix A AbbreviationsA-1................
Appendix B Common Hardware Application
GuidelinesA-3...............................
Appendix C General Torque
SpecificationsA-4............................
Appendix D Common Hardware
IdentificationA-5.............................
Appendix E Common Hardware ListA-6.......
TP-6053 7/04Table of Contents
Page 4
Notes
TP-6053 7/04Table of Contents
Page 5
Safety Precautions and Instructions
IMPORTANTSAFETY
INSTRUCTIONS. Electromechanical
equipment, including generator sets,
transfer switches, switchgear, and
accessories, can cause bodily harm
and pose life-threatening danger when
improperly installed, operated, or
maintained. To prevent accidents be
aware of potential dangers and act
safely.Read and follow all safety
precautions and instructions. SAVE
THESE INSTRUCTIONS.
This manual has severaltypesofsafety
precautions and instructions: Danger,
Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a
hazardthatwillcausesevere
personal injury,death,orsubstantial
property damage.
WARNING
Warning indicates the presence of a
hazard thatcancause severe
personal injury,death,or substantial
property damage.
CAUTION
Caution indicates the presence of a
hazard that will or can cause minorpersonal injury or property damage.
NOTICE
Noticecommunicatesinstallation,
operation, or maintenance information
that is safety related but not hazard
related.
Safety decals affixed to the equipment
in prominent places alert the operator
or service technician to potential
hazards and explain how to act safely.
The decals are shown throughout this
publicationtoimproveoperator
recognition.Replace missing or
damaged decals.
Accidental Starting
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generatorset.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disablingthegeneratorset.
Accidentalstartingcancause
severe injury or death.Before
working on the generator set or
equipment connected to the set,
disable the generator set as follows:
(1) Place the generator set start/stop
switchintheSTOPposition.
(2) Disconnect the power to the battery
charger, if equipped. (3) Remove the
battery cables, negative (--) lead first.
Reconnect the negative (--) lead last
when reconnecting the battery. Follow
these precautions to prevent the
starting of the generator set by the
remote start/stop switch.
Battery
WARNING
Sulfuric acid in batteries.
Can cause severe injury or death.
Wearprotectivegogglesand
clothing. Battery acid may cause
blindness and burn skin.
Battery electrolyte is a diluted
sulfuric acid. Battery acid can cause
severe injury or death. Battery acid
can cause blindness and burn skin.
Alwayswearsplashproofsafety
goggles, rubber gloves, and boots
when servicing the battery. Do not
open a sealed battery or mutilate the
battery case. If battery acid splashes in
the eyes or on the skin, immediately
flush the affected area for 15 minutes
with large quantities of clean water.
Seek immediate medical aid in the case
of eye contact. Never add acid to a
battery after placing the battery in
service, as this may result in hazardous
spattering of battery acid.
Battery acid cleanup. Battery acid
can cause severe injury or death.
Battery acid is electrically conductive
and corrosive. Add 500 g (1 lb.) of
bicarbonate of soda (baking soda) to a
containerwith4L(1gal.)ofwaterand
mix the neutralizing solution. Pour the
neutralizing solution on the spilled
battery acid and continue to add the
neutralizing solution to the spilled
battery acid until all evidence of a
chemicalreaction(foaming)has
ceased. Flush the resulting liquid with
water and dry the area.
Battery gases. Explosion can cause
severe injury or death. Battery gases
can cause an explosion. Do not smoke
or permit flames or sparks to occur near
a battery at any time, particularly when
it is charging. Do not dispose of a
battery in a fire. To prevent burns and
sparks that could cause an explosion,
avoid touching the battery terminals
with tools or other metal objects.
Remove all jewelry before servicing the
equipment. Discharge static electricity
from your body before touching
batteries by first touching a grounded
metal surface away from the battery. To
avoid sparks, do not disturb the battery
charger connections while the battery
is charging. Always turn the battery
charger off before disconnecting the
battery connections.Ventilate the
compartments containing batteries to
prevent accumulation of explosive
gases.
TP-6053 7/04ISafety Precautions and Instructions
Page 6
Battery short circuits.Explosion
can cause severe injury or death.
Short circuits can cause bodily injury
and/orequipmentdamage.
Disconnectthebatterybefore
generatorsetinstallationor
maintenance.Remove all jewelry
before servicing the equipment. Use
tools with insulated handles. Remove
the negative (--) lead first when
disconnecting the battery. Reconnect
the negative (--) lead last when
reconnecting the battery.Never
connect the negative (--) battery cable
to the positive (+) connection terminal
of the starter solenoid. Do not test the
battery condition by shorting the
terminals together.
Engine Backfire/Flash
Fire
WARNING
Fire.
Can cause severe injury or death.
Do not smoke or permit flames or
sparks near fuels or the fuel system.
Servicing the air cleaner. A sudden
backfire can cause severe injury or
death. Do not operate the generator
set with the air cleaner/silencer
removed.
Combustible materials. A sudden
flash fire can cause severe injury or
death. Do not smoke or permit flames
or sparks near the fuel system. Keep
the compartment and the generator set
clean and free of debris to minimize the
risk of fire. Wipe up spilled fuels and
engine oil.
Combustible materials. A fire can
cause severe injury or death.
Generator set engine fuels and fuel
vapors are flammable and explosive.
Handle these materials carefully to
minimize the risk of fire or explosion.
Equip the compartment or nearby area
with a fully charged fire extinguisher.
Select a fire extinguisher rated ABC or
BCforelectricalfiresoras
recommended by the local fire code or
an authorized agency.Train all
personnelonfireextinguisher
operationandfireprevention
procedures.
Exhaust System
WARNING
Carbon monoxide.
Cancauseseverenausea,
fainting, or death.
The exhaustsystemmust be
leakproof and routinely inspected.
Carbonmonoxidesymptoms.
Carbon monoxide can cause severe
nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in
exhaust gases.Carbon monoxide
poisoning symptoms include but are
not limited to the following:
D Light-headedness, dizziness
D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms
and carbon monoxide poisoning is
possible, seek fresh air immediately
and remain active. Do not sit, lie down,
or fall asleep.Alert others to the
possibilityofcarbonmonoxide
poisoning. Seek medical attention if
the condition of affected persons does
not improve within minutes of breathing
fresh air.
Copper tubing exhaust systems.
Carbon monoxide can cause severe
nausea, fainting, or death. Do not
use copper tubing in diesel exhaust
systems.Sulfur in diesel exhaust
causes rapid deterioration of copper
tubing exhaust systems, resulting in
exhaust/water leakage.
Inspecting the exhaust system.
Carbon monoxide can cause severe
nausea, fainting, or death. For the
safety of the craft’s occupants, install a
carbon monoxide detector. Consult the
boat builder or dealer for approved
detector location and installation.
Inspect the detector before each
generator set use. In addition to routine
exhaust system inspection, test the
carbon monoxide detector per the
manufacturer’s instructions and keep
the detector operational at all times.
Operating the generator set. Carbon
monoxide can cause severe nausea,
fainting, or death. Carbon monoxide
is an odorless, colorless, tasteless,
nonirritating gas that can cause death if
inhaled for even a short time. Use the
following precautions when installing
and operating the generator set. Do not
install the exhaust outlet where exhaust
can be drawn in through portholes,
vents, or air conditioners.If the
generator set exhaust discharge outlet
is near the waterline, water could enter
the exhaust discharge outlet and close
or restrict the flow of exhaust. Never
operate the generator set without a
functioning carbon monoxide detector.
Be especially careful if operating the
generatorsetwhenmooredor
anchoredundercalmconditions
because gases may accumulate. If
operating the generator set dockside,
moor the craft so that the exhaust
discharges on the lee side (the side
sheltered from the wind). Always be
aware of others, making sure your
exhaust is directed away from other
boats and buildings. Avoid overloading
the craft.
TP-6053 7/04IISafety Precautions and Instructions
Page 7
Fuel System
WARNING
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.
Draining the fuel system. Explosive
fuel vapors can cause severe injury
or death. Spilled fuel can cause an
explosion. Use a container to catch fuel
when draining the fuel system. Wipe up
spilled fuel after draining the system.
Installing the fuel system. Explosive
fuel vapors can cause severe injury
or death. Fuel leakage can cause an
explosion. Do not modify the tank or
the propulsion engine fuel system.
Equip the craft with a tank that allows
one of the two pickup arrangements
described in the installation section.
The tank and installation must conform
to USCG Regulations.
The fuel system.Explosive fuel
vapors can cause severe injury or
death.Vaporized fuels are highly
explosive. Use extreme care when
handling and storing fuels. Store fuels
inawell-ventilatedareaawayfrom
spark-producing equipment and out of
the reach of children. Never add fuel to
the tank while the engine is running
because spilled fuel may ignite on
contact with hot parts or from sparks.
Do not smoke or permit flames or
sparks to occur near sources of spilled
fuel or fuel vapors. Keep the fuel lines
and connections tight and in good
condition. Do not replace flexible fuel
lines with rigid lines.Use flexible
sections to avoid fuel line breakage
caused by vibration. Donot operate the
generator set in the presence of fuel
leaks, fuel accumulation, or sparks.
Repair fuel systems before resuming
generator set operation.
Pipe sealant. Explosive fuel vapors
can cause severe injury or death.
Fuel leakage can cause an explosion.
Use pipe sealant on all threaded fittings
to prevent fuel leakage.Use pipe
sealant that resists gasoline, grease,
lubrication oil, common bilge solvents,
salt deposits, and water.
Ignition-protectedequipment.
Explosive fuel vapors can cause
severe injury or death.Gasoline
vapors can cause an explosion.
USCG Regulation 33CFR183 requires
that all electrical devices (ship-to-shore
transfer switch, remote start panel,
etc.) must be ignition protected when
used in a gasoline and gaseous-fueled
environment. The electrical devices
listed above are not ignition protected
and are not certified to operate in a
gasolineandgaseous-fueled
environment such as an engine room or
near fuel tanks. Acceptable locations
are the wheelhouse and other living
areas sheltered from rain and water
splash.
Hazardous Noise
CAUTION
Hazardous noise.
Can cause hearing loss.
Never operate the generator set
without a muffler or with a faulty
exhaust system.
Engine noise. Hazardous noise can
cause hearing loss. Generator sets
not equipped with sound enclosures
can produce noise levels greater than
105 dBA. Prolonged exposure to noise
levels greater than 85 dBA can cause
permanent hearing loss. Wear hearing
protection when near an operating
generator set.
Hazardous Voltage
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
CAUTION
Welding the generator set.
Cancausesevereelectrical
equipment damage.
Never weld components of the
generatorsetwithoutfirst
disconnecting the battery, controller
wiring harness, and engine electronic
control module (ECM).
Grounding electrical equipment.
Hazardousvoltagecancause
severe injury or death. Electrocution
is possible whenever electricity is
present.Open the main circuit
breakers of all power sources before
servicing the equipment. Configure the
installation to electrically ground the
generator set, transfer switch, and
relatedequipmentandelectrical
circuits to comply with applicable codes
andstandards.Nevercontact
electrical leads or appliances when
standing in water or on wet ground
because these conditions increase the
risk of electrocution.
Moving rotor.
TP-6053 7/04IIISafety Precautions and Instructions
Page 8
Disconnecting the electrical load.
Hazardousvoltagecancause
severe injury or death. Disconnect
the generator set from the load by
opening the line circuit breaker or by
disconnecting the generator set output
leads from the transfer switch and
heavily taping the ends of the leads.
High voltage transferred to the load
during testing may cause personal
injury and equipment damage. Do not
use the safeguard circuit breaker in
place of the line circuit breaker. The
safeguard circuit breaker does not
disconnect the generator set from the
load.
Welding the generator set.Can
cause severe electrical equipment
damage. Before welding the generator
set perform the following steps:
(1) Removethebatterycables,
negative (--) lead first. (2) Disconnect
all engine electronic control module
(ECM) connectors. (3) Disconnect all
generator set controller and voltage
regulator circuit board connectors.
(4) Disconnect the engine batterychargingalternatorconnections.
(5) Attach the weld ground connection
close to the weld location.
Shortcircuits.Hazardous
voltage/current can cause severe
injury or death. Short circuits can
cause bodily injury and/or equipment
damage.Do not contact electrical
connections with tools or jewelry while
makingadjustmentsorrepairs.
Remove all jewelry before servicing the
equipment.
Testingthevoltageregulator.
Hazardousvoltagecancause
severe injury or death. High voltage
is present at the voltage regulator heat
sink. To prevent electrical shock do not
touch the voltage regulator heat sink
when testing the voltage regulator.
(PowerBoostt, PowerBoostt III, and
PowerBoostt Vvoltageregulator
models only)
Electrical backfeed to the utility.
Hazardous backfeed voltage can
cause severe injury or death.
Connect the generator set to the
building/marina electrical system only
through an approved device and after
the building/marina main switch is
opened. Backfeed connections can
cause severe injury or death to utility
personnel working on power lines
and/or personnel near the work area.
Some states and localities prohibit
unauthorized connection to the utility
electricalsystem.Installa
ship-to-shore transfer switch to prevent
interconnection of the generator set
power and shore power.
Testingliveelectricalcircuits.
Hazardous voltage or current can
cause severe injury or death. Have
trained and qualified personnel take
diagnosticmeasurementsoflive
circuits.Use adequately rated test
equipment with electrically insulated
probes and follow the instructions of the
test equipment manufacturer when
performing voltage tests. Observe the
following precautions when performing
voltage tests: (1) Remove all jewelry.
(2) Stand on a dry, approved electrically
insulated mat. (3) Do not touch the
enclosure or components inside the
enclosure. (4) Be prepared for the
system to operate automatically.
(600 volts and under)
Hot Parts
WARNING
Hot coolant and steam.
Can cause severe injury or death.
Before removing the pressure cap,
stop the generator set and allow it to
cool. Then loosen the pressure cap
to relieve pressure.
WARNING
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
Checking the coolant level.Hot
coolant can cause severe injury or
death.Allow the engine to cool.
Release pressure from the cooling
system before removing the pressure
cap. To release pressure, cover the
pressure cap with a thick cloth and then
slowly turn the cap counterclockwise to
the first stop. Remove the cap after
pressurehasbeencompletely
released and the engine has cooled.
Check the coolant level at the tank if the
generator set has a coolant recovery
tank.
Servicing the exhaust system. Hot
parts can cause severe injury or
death. Do not touch hot engine parts.
The engine and exhaust system
components become extremely hot
during operation.
TP-6053 7/04IVSafety Precautions and Instructions
Page 9
Moving Parts
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
WARNING
Rotating parts.
Can cause severe injury or death.
Operate the generator set only when
all guards, screens, and covers are in
place.
Wear protective goggles and clothing
when using power tools, hand tools,
or compressed air.
Moving rotor.
Tightening the hardware.Flying
projectiles can cause severe injury
or death. Loose hardware can cause
the hardware or pulley to release from
the generator set engine and can cause
personalinjury.Retorqueall
crankshaft and rotor hardware after
servicing. Do not loosen the crankshaft
hardware or rotor thrubolt when making
adjustments or servicing the generator
set. Rotate the crankshaft manually in
a clockwise direction only. Turning the
crankshaft boltor rotorthrubolt
counterclockwise canloosen the
hardware.
Servicing the generator set when it
is operating. Exposed moving parts
can cause severe injury or death.
Keep hands, feet, hair, clothing, and
test leads away from the belts and
pulleys when the generator set is
running. Replace guards, screens, and
covers before operating the generator
set.
Sound shield removal.Exposed
moving parts can cause severe
injury or death. The generator set
must be operating in order to perform
somescheduledmaintenance
procedures. Be especially careful if the
sound shield has been removed,
leaving the belts and pulleys exposed.
(Sound-shield-equipped models only)
Notice
NOTICE
This generator set has been
rewired from its nameplate voltage
to
NOTICE
Voltage reconnection. Affix a notice
to the generator set after reconnecting
the set to a voltage different from the
voltage on the nameplate.Order
voltage reconnection decal 246242
fromanauthorizedservice
distributor/dealer.
NOTICE
Hardware damage. The engine and
generator set may use both American
Standard and metric hardware. Use
the correct size tools to prevent
rounding of the bolt heads and nuts.
NOTICE
When replacing hardware, do not
substitutewithinferiorgrade
hardware.Screws and nuts are
available in different hardness ratings.
Toindicatehardness,American
Standard hardware uses a series of
markings, and metric hardware uses a
numeric system. Check the markings
on the bolt heads and nuts for
identification.
NOTICE
Fuse replacement.Replace fuses
with fuses of the same ampere rating
and type (for example: 3AB or 314,
ceramic).Do not substitute clear
glass-type fuses for ceramic fuses.
Refer to the wiring diagram when the
ampereratingisunknownor
questionable.
NOTICE
Saltwater damage. Saltwater quickly
deteriorates metals. Wipe up saltwater
on and around the generator set and
remove salt deposits from metal
surfaces.
TP-6053 7/04VSafety Precautions and Instructions
246242
Page 10
Notes
TP-6053 7/04VISafety Precautions and Instructions
Page 11
Introduction
This manual provides troubleshooting and repair
instructions for 5--10EOZ/EFOZ model generator sets,
controllers, and accessories.
Refer to the engine service manual for generator set
engine service information.
x:in:001:001
This manual may be used for models not listed on the
front cover.
Information in this publication represents data available
at the time of print. Kohler Co. reserves the right to
change this publication and the products represented
without notice and without any obligation or liability
whatsoever.
Forprofessionaladviceongeneratorpower
requirements and conscientious service, please contact
your nearest Kohler distributor or dealer.
D Consult the Yellow Pages under the heading
Generators—Electric
Read this manual and carefully follow all procedures
and safety precautions to ensure proper equipment
operation and to avoid bodily injury. Read and follow the
Safety Precautions and Instructions section at the
beginning of this manual. Keep this manual with the
equipment for future reference.
The equipment service requirements are important for
safe and efficient operation. Inspect the parts often and
perform required service at the prescribed intervals.
Maintenance work must be performed by appropriately
skilled and suitably-trained maintenance personnel
familiar with generator set operation and service.
x:in:001:003
Service Assistance
China
North China Regional Office, Beijing
Phone: (86) 10 6518 7950
(86) 10 6518 7951
(86) 10 6518 7952
Fax:(86) 10 6518 7955
D VisittheKohler PowerSystemswebsite at
KohlerPowerSystems.com
D Look at the labels and stickers on your Kohler product
or review the appropriate literature or documents
included with the product
D Call toll free in the US and Canada 1-800-544-2444
D Outside the US and Canada, call the nearest regional
office
Headquarters Europe, Middle East, Africa
(EMEA)
Kohler Power Systems
ZI Senia 122
12, rue des Hauts Flouviers
94517 Thiais Cedex
France
Phone: (33) 1 41 735500
Fax:(33) 1 41 735501
Asia Pacific
Power Systems Asia Pacific Regional Office
Singapore, Republic of Singapore
Phone: (65) 6264-6422
Fax:(65) 6264-6455
East China Regional Office, Shanghai
Phone: (86) 21 6288 0500
Fax:(86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office
Bangalore, India
Phone: (91) 80 3366208
(91) 80 3366231
Fax:(91) 80 3315972
Japan, Korea
North Asia Regional Office
Tokyo, Japan
Phone: (813) 3440-4515
Fax:(813) 3440-2727
Latin America
Latin America Regional Office
Lakeland, Florida, USA
Phone: (863) 619-7568
Fax:(863) 701-7131
TP-6053 7/04iIntroduction
Page 12
Product Information
Product identification numbers determine service parts.
Record the product identification numbers in the spaces
below immediately after unpacking the products so that
the numbers are readily available for future reference.
Record field-installed kit numbers after installing the
kits.
Generator Set Identification Numbers
Record the product identification numbers from the
generator set nameplate(s).
Model Number
Specification Number
Serial Number
Accessory NumberAccessory Description
Engine Identification
Record the product identification information from the
engine nameplate.
Manufacturer
Model Number
Serial Number
TP-6053 7/04iiIntroduction
Page 13
Section 1 Specifications
1.1General
This manual covers the operation, maintenance,
troubleshooting, and repair of the alternating current
marine generator sets.
Have an authorized service dealer/distributor perform
required servicing to assure your unit continues to meet
USCG requirements.
Please take a few moments to read this manual, then
carefully follow all service recommendations.See
Figure 1-1 through Figure 1-3 for identification and
location of components.
The 5EOZ/4EFOZ models are powered by a Yanmar
three-cylinder, water-cooled, four-cycle diesel engine.
The three-cylinder engine with heat exchanger is model
3TNE68.
The 8EOZ/6.5EFOZ models are powered by a Yanmar
three-cylinder, water-cooled, four-cycle diesel engine.
The three-cylinder engine with heat exchanger is model
3TNE74.
The 9EOZ/8EFOZ models are powered by a Yanmar
three-cylinder, water-cooled, four-cycle diesel engine.
The three-cylinder engine with heat exchanger is model
3TNE78A.
The 10EOZ/9EFOZ models are powered by a Yanmar
three-cylinder, water-cooled, four-cycle diesel engine.
The three-cylinder engine with heat exchanger is model
3TNE82A.
Kohler Co. develops all Kohlerr marine generator set
ratings using accepted reference conditions of 25_C
(77_F) and pressure of 98.9 kPa (29.2 in. Hg) dry
barometer. ISO 3046 and ISO 8528-1 include reference
conditions and output calculations. Obtain technical
information bulletin (TIB-101) on ratings guidelines for
complete ratings definitions.
TP-6053 7/041Section 1 Specifications
Page 14
1.2Service Views
1
25
24
23 5679
4811
26
27
28
10
12
13
14
15
16
181920212223
17
29
34
1. Start/stop switch
2. Hourmeter
3. Controller
4. Nameplate
5. DC circuit breaker
6. AC circuit breaker
7. Air cleaner
8. Fuel solenoid
9. Fuel injectors
10. Fuel return connection
11. High water temperature switch
12. Oil fill
13. V-belts
14. Seawater pump (water inlet)
15. Coolant (fresh water) drain
16. Heat exchanger
17. Coolant drain (fresh water)
33
32
30
31
DK-250000
18. Anticorrosion zinc anode
19. Fuel filter
20. Oil filter
21. Oil drain valve and hose
22. Fuel feed pump
23. Oil check
24. Fuel inlet connection
25. Low oil pressure safety shutdown switch
26. Wet exhaust manifold
27. Thermostat
28. AC load lead connector
29. Remote start connector
30. High exhaust temperature safety shutdown switch
31. Mixing elbow
32. Water temperature sender
33. Engine starter
34. Battery charging alternator
Figure 1-1 Generator Set Service View (5EOZ/4EFOZ)
TP-6053 7/042Section 1 Specifications
Page 15
245678 9
103
11
33
1
24
1617181920212223
2528
26
27
12
13
14
15
1. Start/stop switch
2. Controller
3. Nameplate
4. Hourmeter
5. DC circuit breaker
6. AC circuit breaker
7. Air cleaner
8. Coolant recovery bottle
9. Pressure cap
10. Fuel return connection
11. High water temperature shutdown switch
12. Oil fill
13. Seawater pump (water inlet)
14. V-belts
15. Heat exchanger
16. Coolant drain (fresh water)
17. Anticorrosion zinc anode
32
29
30
31
18. Fuel filter
19. Oil filter
20. Oil drain valve and hose
21. Fuel feed pump
22. Oil check
23. Fuel inlet connection
24. Low oil pressure safety shutdown switch
25. Wet exhaust manifold
26. Thermostat
27. AC load lead connector
28. Remote start connector
29. High exhaust temperature safety shutdown switch
30. Mixing elbow
31. Engine starter
32. Water temperature sender
33. Battery charging alternator
A-358000A-A
Figure 1-2 Generator Set Service View (8EOZ/6.5EFOZ)
TP-6053 7/043Section 1 Specifications
Page 16
22
21
456791011
83
12
2
1
11
13
14
151617181920
34
33
1. Start/stop switch
2. Controller
3. Nameplate
4. Hourmeter
5. DC circuit breaker
6. AC circuit breaker
7. Air cleaner
8. Coolant overflow bottle
9. Low oil pressure safety shutdown switch
10. Pressure cap
11. Oil fill
12. High water temperature safety shutdown switch
13. V-belts
14. Seawater pump (water inlet)
15. Fuel filter
16. Oil drain valve and hose
17. Oil filter
23
24
25
26
27
28
A-358000A-A
303132
29
18. Fuel feed pump
19. Fuel inlet connection
20. Oil check
21. Coolant drain (fresh water)
22. Fuel return
23. Wet exhaust manifold
24. Thermostat
25. AC load lead connector
26. Remote start connector
27. High exhaust temperature safety shutdown switch
28. Mixing elbow
29. Anticorrosion zinc anode
30. Engine starter
31. Heat exchanger
32. Coolant drain (fresh water)
33. Water temperature sender
34. Battery charging alternator
Figure 1-3 Generator Set Service View (9/10EOZ and 8/9EFOZ)
Engine manufacturerYanmar
Engine model3TNE683TNE743TNE78A3TNE82A
Number of cylinders3
Cylinder block materialCast iron
Cylinder head materialCast iron
Piston rings2 compression/1 oil
Crankshaft materialStamped forging
Connecting rod materialForged carbon steel
GovernorCentrifugal, mechanical
Bore x stroke, mm (in.)68 x 72 (2.67 x 2.83) 74 x 78 (2.91 x 3.07) 78 x 84 (3.07 x 3.30) 82 x 84 (3.22 x 3.30)
Displacement, L (CID)0.784 (47.83)1.006 (61.39)1.204 (73.45 )1.330 (81.14)
Compression ratio23.0:118.0:1
Horsepower, 60/50 Hz10.1/8.414/11.617.7/14.8
RPM, 60/50 Hz1800/1500
Direction of rotation
(as viewed from generator end)
Lubrication systemPressure, trochoid pump
Lube oil capacity w/filter, L (qts.)3 (3.2)2.4 (2.3)5.2 (5.5)3.4 (3.6)
Oil recommendation, APICD, CD/CC, or CC
Engine firing order
Flex plate to rotor bolt torque
(3/8-16), Nm (ft. lbs.)
Flex plate to flywheel bolt torque
(M8-1.25), Nm (ft. lbs.)
Overbolt torque (M10-1.5),
Nm (ft. lbs.)
Inlet water line hose ID
(seawater pump inlet), mm (in.)
Outlet water line hose ID
(mixing elbow outlet), mm (in.)
Fuel inlet (fuel pump inlet)1/4 NPT
Fuel return size type1/4 NPT
45 (35)36.6 (27)45 (35)38 (28)
25 (20)38 (28)25 (20)19 (14)
45 (35)34 (25)45 (35)34 (25)
0.15--0.25 (0.006--0.010)
10--15 (0.4--0.6)
16 (5/8)
51 (2)
1.4Generator
Generator Model5/8EOZ and 4/6.5EFOZ9/10EOZ and 8/9EFOZ
Hot exciter field voltage/current readings at rated voltage*
No load (63 Hz) (volts/amps)19/0.912/0.8
Full load (60 Hz) (volts/amps)32/1.533/2.2
Resistor (F1 lead to exciter field) (ohms)15 ±210 ±2
Cold exciter field resistance (ohms)4.8
Cold exciter armature resistance (ohms)1.2
Cold main field (rotor) resistance (ohms)5.05.7
Stator output voltages with separately excited generator, using 12-volt battery (60 Hz only)*
1--2, 3--4, 33--44 (volts)8111 5
33--55 (volts)105155
B1-B2 (volts)1015
Cold stator resistance
1--2, 3--4, 33--44 (ohms)0.30.2
33--55 (ohms)2.11.9
B1-B2 (ohms)0.1
* Includes resistor in exciter field circuit.
TP-6053 7/046Section 1 Specifications
Page 19
Section 2 Scheduled Maintenance
2.1General
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generatorset.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set.Accidental starting can
cause severe injury or death.Before working on the
generator set or equipment connected to the set, disable the
generator set as follows: (1) Place the generator set start/stop
switch in the STOP position. (2) Disconnect the power to the
battery charger, if equipped. (3) Remove the battery cables,
negative (--) lead first. Reconnect the negative (--) lead last
when reconnecting the battery. Follow these precautions to
prevent the starting of the generator set by the remote
start/stop switch.
Sound shield removal. Exposed moving parts can cause
severe injury or death. The generator set must be operating
in order to perform some scheduled maintenance procedures.
Be especially careful if the sound shield has been removed,
leaving the belts and pulleys exposed.
(Sound-shield-equipped models only)
NOTICE
Saltwater damage. Saltwater quickly deteriorates metals.
Wipe up saltwater on and around the generator set and
remove salt deposits from metal surfaces.
Note: See the generator set operation manual for the
service schedule and other service not included
in this manual.
Use oil that meets the American Petroleum Institute
(API) classification of CD, CC/CD, or CC.Using
unsuitable oil or neglecting an oil change may result in
damage and a shorter engine life. Figure 2-1 shows the
recommended Society of Automotive Engineers (SAE)
viscosity designation for given operating temperature
ranges.
WARNING
Rotating parts.
Can cause severe injury or death.
Operate the generator set only when
all guards, screens, and covers are in
place.
Servicing the generator set when it is operating. Exposed
moving parts can cause severe injury or death. Keep
hands, feet, hair, clothing, and test leads away from the belts
and pulleys when the generator set is running. Replace
guards, screens, and covers before operating the generator
set.
Note: Failure to observe these standards may cause
inadequate lubrication/oil pressure and coldstarting difficulties.
SAE
Service
Grade
°C°F--30 --20 --10 010 203040
5W20
20W40
10W30
20W20
20W30
20W40
0204060 80 100°C°F
Operating Temperature
TP-5856-1
Figure 2-1 Engine Oil Selection
TP-6053 7/047Section 2 Scheduled Maintenance
Page 20
Electric Oil-Drain/Oil-Fill Procedure
1. Connect the pump to the end of the oil-drain hose.
2. Place the pump outlet hose into a container.
Remove the oil-fill cap(s). One is located near the
top of the engine on the valve cover and one is
located near the governor.
3. Activate the pump until all of the oil is removed.
Allow ample time for all of the oil to drain.
4. Turn the valve at the base of the oil-drain hose to
the closed position.
5. Replace the engine oil filter.
6. Fill the engine crankcase to the specified level with
oil. The figures in Section 1 show typical oil fill
locations.See Figure 2-1 for oil selection and
Figure 2-2 for oil capacities.
7. Start the generator set and check for oil leaks.
8. Stop the generator set. Check the oil level. Add oil,
as necessary, to bring the level up to the Max mark
on the dipstick.
ModelL (Qts.)
5EOZ and 4EFOZ3.0 (3.2)
8EOZ and 6.5EFOZ2.3 (2.4)
9EOZ and 8EFOZ5.2 (5.5)
10EOZ and 9EFOZ5.2 (5.5)
Figure 2-2 Oil Capacities
2.3Battery
Consultthebatterymanufacturer’sinstructions
regarding battery care and maintenance.
WARNING
Sulfuric acid in batteries.
Can cause severe injury or death.
Wearprotectivegogglesand
clothing. Battery acid may cause
blindness and burn skin.
Battery electrolyte is a diluted sulfuric acid. Battery acid
can cause severe injury or death. Battery acid can cause
blindness and burn skin. Always wear splashproof safety
goggles, rubber gloves, and boots when servicing the battery.
Do not open a sealed battery or mutilate the battery case. If
battery acid splashes in the eyes or on the skin, immediately
flush the affected area for 15 minutes with large quantities of
clean water. Seek immediate medical aid in the case of eye
contact. Never add acid to a battery after placing the battery in
service, as this may result in hazardous spattering of battery
acid.
Battery gases. Explosion can cause severe injury or
death. Battery gases can cause an explosion. Do not smoke
or permit flames or sparks to occur near a battery at any time,
particularly when it is charging. Do not dispose of a battery in a
fire. To prevent burns and sparks that could cause an
explosion, avoid touching the battery terminals with tools or
other metal objects. Remove all jewelry before servicing the
equipment. Discharge static electricity from your body before
touching batteries by first touching a grounded metal surface
away from the battery. To avoid sparks, do not disturb the
battery charger connections while the battery is charging.
Always turn the battery charger off before disconnecting the
battery connections. Ventilate the compartments containing
batteries to prevent accumulation of explosive gases.
TP-6053 7/048Section 2 Scheduled Maintenance
Page 21
2.4Generator Storage
7. Stop the generator set.
Perform the generator storage procedure while the craft
is afloat. Follow the procedure below when storing your
generator set for 3 months or more.
Storage Procedure
1. Start and run the generator set until it reaches
operating temperature, about 30 minutes.
2. Stop the generator set.
3. Change the oil and oil filter. See the generator set
operation manual.
4. Drain the seawater from the heat exchanger by
removing the coolant drain plug.
5. Close the seacock and remove the hose at the
seacock. Place the hose in a container having
approximately 3.7--7.5 L (1--2 gal.) of marine
antifreeze. Use an environmentally safe marine
antifreeze with corrosion inhibitors.
6. With a container at the exhaust outlet, run the
generator set until coolant discharges at the
exhaust outlet or until depleting the coolant
mixture. Do not allow the coolant mixture to flow
into waterways.
8. Connect the hose to the seacock.Leave the
seacock closed.
9. Check the coolant level in the heat exchanger and
add coolant if necessary.
Note: Use antifreeze with the lowest available
temperature rating.
10. Clean the exterior of the generator set and spread
a light film of oil or silicon spray over any exposed
surfaces which may be subject to rust or corrosion.
11. Disconnect and remove the battery. Place the
battery in a dry location for the storage period.
Recharge the battery once a month to maintain a
full charge.
12. Cover the entire unit with a breathable dust cover.
TP-6053 7/049Section 2 Scheduled Maintenance
Page 22
Notes
TP-6053 7/0410 Section 2 Scheduled Maintenance
Page 23
Section 3 Intake and Exhaust System
3.1Air Intake Silencer/Filter
A dry-type air cleaner silences and filters the intake air.
The air intake silencer assembly connects to the intake
manifold via a flexible hose.
At the interval specified in the service schedule, clean or
replace the air intake silencer. Clean or replace the air
cleaner more frequently in dirty, dusty conditions.
Follow the procedure described below.
Air Cleaner Service/Replacement Procedure
1. Release the four spring clips to open the housing
and remove the air silencer element.
2. Tap the element lightly against a flat surface to
dislodge loose surface dirt.Do not clean the
element in any liquid or use compressed air as
these will damage the filter element.
3. Examine the element and its housing for damage
and wear. Replace the element or its housing, if
necessary.
4. Wipe the cover and base with a clean rag to remove
any dirt.Make sure the sealing surfaces fit
correctly and reattach the spring clips.
Check for exhaust leaks and blockages. Check the
silencer and piping condition and check for tight exhaust
system connections.
Inspect the exhaust system components (exhaust
manifold, mixing elbow, exhaust line, hose clamps,
silencer, and outlet flapper) for cracks, leaks, and
corrosion.
D Check the hoses for softness, cracks, leaks, or dents.
Replace the hoses as needed.
D Check for corroded or broken metal parts and replace
them as needed.
D Check for loose, corroded, or missing clamps.
Tighten or replace the hose clamps and/or hangers
as needed.
D Check that the exhaust outlet is unobstructed.
D Visually inspect for exhaust leaks. Check for carbon
or soot residue on exhaust components. Carbon and
soot residue indicates an exhaust leak. Seal leaks as
needed.
D Ensure that the carbon monoxide detector is (1) in the
craft, (2) functional, and (3) energized whenever the
generator set operates.
3.2Exhaust System
WARNING
Carbon monoxide.
Cancauseseverenausea,
fainting, or death.
The exhaustsystemmust be
leakproof and routinely inspected.
Inspecting the exhaust system. Carbon monoxide can
cause severe nausea, fainting, or death. For the safety of
the craft’s occupants, install a carbon monoxide detector.
Consult the boat builder or dealer for approved detector
location and installation. Inspect the detector before each
generator set use. In addition to routine exhaust system
inspection, test the carbon monoxide detector per the
manufacturer’s instructions and keep the detector operational
at all times.
3.3Mixing Elbow
Check the mixing elbow for carbon buildup and
corrosion inside the pipe. Clean the residual carbon
buildup with a wire brush. Inspect the exhaust manifold
flange for cracking and corrosion. The mixing elbow
combines high temperature exhaust and cooling
seawater.The mixture, when exposed to engine
vibration,makesconditionsconducivetorapid
deterioration and failure if not correctly maintained. If
any damage is detected with the mixing elbow or other
exhaust components, replace the damaged components
to prevent engine exhaust (carbon monoxide) leakage.
TP-6053 7/0411Section 3 Intake and Exhaust System
Page 24
Notes
TP-6053 7/0412 Section 3 Intake and Exhaust System
Page 25
Section 4 Fuel System
4.1General
In most installations, both the generator set and the
propulsion engine operate from a common fuel tank with
a dual dip tube arrangement. The generator set dip tube
is shorter than the propulsion engine’s dip tube. With
this arrangement, fuel may not be available to the
generator set when the fuel supply is low.See
Figure 4-1 for a fuel system schematic.
To fuel
pump
Propulsion
Engine
1
1. Fuel tank
2. Dual dip tubes
3. Fuel filter
4. Fuel feed pump
2
Figure 4-1 Fuel System Schematic Typical
4
3
Generator
Set
4.3Fuel Filter
The quality and condition of the fuel largely determine
the filter’s useful life. Replace the fuel filter element
according to the service schedule. Section 1.2 shows
the location of the fuel filter. There are two types of fuel
filtering systems, the spin-on fuel filter and the fuel filter
element. Use the applicable procedure below to replace
the fuel filter. See Figure 4-2 or Figure 4-3.
Spin-On Fuel Filter Replacement Procedure
1. Place the generator set start/stop switch in the
STOP position.
2. Disconnect the generator set engine starting
battery, negative (--) lead first.
3. Close the fuel supply valve.
4. Remove the fuel filter. See Figure 4-2.
5. Clean the contact surface of the fuel filter adapter.
6. Lightly lubricate the gasket surface of the new fuel
filter with fresh fuel.Thread the filter onto the
adapteruntilthegasketmakescontact;
hand-tighten the filter an additional one-half turn.
7. Open the fuel supply valve.
4.2Fuel Specifications
Use a clean, good quality diesel fuel oil with a cetane
number of 45 or greater. Clean fuel prevents diesel fuel
injectors and pumps from clogging.
Fuel Recommendation
United States
United KingdomBS 2869-1983, Part 2 Class A2
GermanyDIN 51 601-1978
ISO 8217 DMA, BS 2869 Part 1 Class
A1 or Part 2 Class A2
8. Reconnect the generator set engine starting
battery, negative (--) lead last.
9. Bleed the fuel system. See Section 4.4.
1
2
3
4
1. Fuel filter adapter
2. Fuel filter
3. Removal (counterclockwise)
4. Installation (clockwise)
<
<
<
<
TP-606111
Figure 4-2 Spin-On Fuel Oil Filter
TP-6053 7/0413Section 4 Fuel System
Page 26
Fuel Filter Element Replacement Procedure
1. Place the generator set start/stop switch in the
STOP position.
2. Disconnect the generator set engine starting
battery, negative (--) lead first.
3. Close the fuel supply valve.
4.4Bleed the Fuel System
Bleed the air from the fuel system to prevent starting
failures and/or erratic operation. One or more of the
following causes air to collect in the fuel system:
1. The generator set operates until the fuel supply is
emptied.
4. Remove the retaining ring, filter cup, o-ring, fuel
filter element and spring.
5. Replace the fuel filter element and install as shown
in Figure 4-3.
6. Open the fuel supply valve.
7. Reconnect the generator set engine starting
battery, negative (--) lead last.
8. Bleed the fuel system. See Section 4.4.
2
1
3
4
5
6
2. The air leaks in the suction side of the fuel system.
3. Replacing the fuel filter.
4. Vapor lock.
Note: Connect the battery during the priming procedure
to allow engine cranking.Do not allow the
engine/generator to start. To prevent starting,
toggle the start/stop switch by momentarily
placing the start/stop switch in the START
position for a few seconds and then placing the
switch in the STOP position. Close the seacock
during bleeding.
Fuel System Bleeding Procedure
1. Loosen the fuel filter screw at position 1. See
Figure 4-4.
2. Toggle the start/stop switch until fuel, free of air
bubbles, flows from the vent screw at position 1.
Tighten the screw.
3. Loosen the fuel filter screw at position 2.
4. Toggle the start/stop switch until fuel, free of air
bubbles, flows from the vent screw at position 2.
Tighten the screw.
7
1. Fuel strainer assembly
2. Body
3. Fuel element
4. Spring
5. O-ring
6. Filter cup
7. Retaining ring
Figure 4-3 Fuel Oil Filter Element
5. Loosen the fuel injection pump screw at position 5.
6. Toggle the start/stop switch until fuel, free of air
bubbles, flows from the vent screw at position 5.
Tighten the screw.
TP-561633
TP-6053 7/0414 Section 4 Fuel System
Page 27
1
5/8EOZ and 4/6.5EFOZ Models
2
4.5Fuel Solenoid
The fuel solenoid serves to pull the injector pump lever
to the fuel-on position when energized.The fuel
solenoid is spring loaded to return the injector-pump
lever to the fuel-off position when deenergized.
4
9/10EOZ and 8/9EFOZ Models
6
1. Vent screw, position 1
2. Vent screw, position 2
3. Fuel return
4. Fuel filter
5. Fuel injection pump
6. Vent screw, position 5
6
5
The generators in this manual use a 3-lead fuel
solenoid. This solenoid has a white lead (P) which
energizes the pull-in coil only during cranking. During
operation, the red lead energizes the hold coil and the
black lead is the common ground.
Current (amps) and resistance readings are shown in
Figure 4-5.Resistance readings determine if the
solenoid windings are open or shorted. These readings
must be taken with fuel solenoid disconnected from
engine wiring harness.
2
1
3
4
5
TP-5586-3
Figure 4-5 Fuel Solenoid Readings
Fuel SolenoidReading
Pull-In
Hold
Black-White (P) Leads
Black-Red Leads
0.12--0.26 Ohms
11-13 Ohms
50 Amps
1.0 Amps
Figure 4-4 Fuel System Bleed Points, Typical
TP-6053 7/0415Section 4 Fuel System
Page 28
In addition to the ohmmeter test, check for smooth,
non-binding movement of the plunger. It is important
that the linkage between the fuel solenoid and the fuel
injection pump lever be properly adjusted to allow the
solenoid plungerto fullycompress.Improper
adjustment may cause burnout of the pull-in coil. If the
fuel solenoid setting is suspected to be incorrect, use the
following procedure to correct and see Figure 4-6.
Fuel Solenoid Adjustment Procedure
1. Remove the fuel solenoid linkage.
2. With the fuel solenoid’s plunger fully compressed,
align the linkage and check injection pump lever for
travel. The fuel solenoid should fully compress and
the injection pump lever should be 1.6 mm
(0.05 in.) before the lever reaches the stop
(internal full open) position.
Note: The fuel solenoid must compress (bottom)
fully or burnout of the fuel solenoid pull-in
coil will occur.
3. If the alignment is not correct, check the linkage
and mounting brackets. Loosen locknuts and
adjust the ball joint’s length in or out to attain proper
alignment. Tighten the locknut.
4.6Fuel Pump
The fuel pump transfers fuel from a source to the fuel
injection pump.
Fuel Pump Test Procedure
1. Remove the two leads from the terminals at the
bottom of the fuel pump. The pump terminals are
labeled (--) and (+). See Figure 4-7.
2. Connect the inlet side of the pump to a fuel source.
Disconnect the outlet hose from the fuel filter and
place the hose end in a container to catch the fuel.
3. Connect the positive (+) terminal of the 12-volt
battery to the positive terminal of the fuel pump.
Connect the negative terminal of the fuel pump to
the negative (--) terminal of the battery. You should
hear the pump operate and see the fuel discharge
from the pump outlet. Replace the pump if it does
not operate.
Stop
1. Fuel solenoid
2. Locknuts
3. Ball joints
Run
Adjust 1/16 inch
for max.
Stop Lever
3
Figure 4-6 Fuel Solenoid Linkage
1
1
2
1. Fuel inlet
2
2. Negative terminal
3. Positive terminal
4. Fuel outlet
3
4
I-940
Figure 4-7 Fuel Pump
TP-6053 7/0416 Section 4 Fuel System
Page 29
4.7Governor
The centrifugal, mechanical governor keeps the engine
speed constant by automatically adjusting the amount
of fuel supplied to the engine according to changes in
the load. No regular service is required on the governor.
The factory adjusts the governor during run-in, and
further adjustment should not be needed unless poor
governor control develops after extended generator
usage.
60 Hz generator sets are designed to operate at
57--63 Hz, 1800 rpm under full load and 1890 rpm under
no load.
50 Hz generator sets are designed to operate at
47--53 Hz, 1500 rpm under full load and 1590 rpm under
no load.
Check the engine speed using a frequency meter
connected to the load leads. Loosen the locking nut on
the speed adjusting screw. Turn the screw clockwise to
increase the speed and frequency. Turn the screw
counterclockwise to decrease the speed. Tighten the
locknut at the new setting. See Figure 4-8 or Figure 4-9.
1
1. Locknut
2. Speed adjusting screw
2
ED-250000A-N
Figure 4-9 Governor, 8/9/10EOZ and 6.5/8/9EFOZ
12
1. Locknut
2. Speed adjusting screw
Figure 4-8 Governor, 5EOZ/4EFOZ
DK-250000B-D
TP-6053 7/0417Section 4 Fuel System
Page 30
Notes
TP-6053 7/0418 Section 4 Fuel System
Page 31
5.1General
The heat exchanger cooling system consists of a heat
exchanger with a coolant recovery tank, a thermostat, a
rubber impeller seawater pump, a centrifugal-type
engine circulating pump, a water-cooled exhaust
manifold, and an exhaust mixer. See Figure 5-1 for
cooling system components.
WARNING
Hot coolant and steam.
Can cause severe injury or death.
Before removing the pressure cap,
stop the generator set and allow it to
cool. Then loosen the pressure cap
to relieve pressure.
Section 5 Cooling System
Checking the coolant level. Hot coolant can cause severe
injury or death. Allow the engine to cool. Release pressure
from the cooling system before removing the pressure cap. To
release pressure, cover the pressure cap with a thick cloth and
then slowly turn the cap counterclockwise to the first stop.
Remove the cap after pressure has been completely released
and the engine has cooled. Check the coolant level at the tank
if the generator set has a coolant recovery tank.
NOTICE
Saltwater damage. Saltwater quickly deteriorates metals.
Wipe up saltwater on and around the generator set and
remove salt deposits from metal surfaces.
1. Engine block
2. Exhaust manifold
3. Exhaust mixer elbow
4. Outlet flapper
5. Silencer
6. Thermostat
12
1
2
3
4
5
6
7
8
9
Seawater
10
11
Coolant/Antifreeze
60531099
7. Heat exchanger
8. Engine seawater pump
9. Seawater strainer
10. Seacock
11. Intake strainer
12. Engine-driven water pump
Figure 5-1 Cooling System Components
TP-6053 7/0419Section 5 Cooling System
Page 32
5.2Water-Cooled Exhaust
Manifold
Each generator set is equipped with a water-cooled
exhaust manifold. Engine coolant circulates through the
manifold, reducing the amount of heat radiated from the
exhaust into the surrounding area.The engine
thermostat is located in the manifold. See Section 1 for
the thermostat location. See Figure 5-2 and Figure 5-3
for exhaust manifold bolt tightening sequence and
torques.
1
3
6
5EOZ/4EFOZ8EOZ/6.5EFOZ
5
1
2
4
3
6
3
6
1
5
4
2
5
2
4
glycol and 50% clean, softened water to inhibit rust and
corrosion and to prevent freezing.Add additional
coolant mixture, as necessary to the coolant recovery
tank. Periodically check the coolant level on closed
systems by removing the pressure cap. Do not rely
solely on the level in the coolant recovery tank. Add
fresh coolant mixture until the level is just below the
overflow tube opening.
Do not add coolant to a hot engine. Adding coolant to a
hot engine can cause the cylinder block or cylinder head
to crack. Wait until the engine has cooled.
Note: Coolant solution. A coolant solution of 50%
ethylene glycol provides freezing protection to
-- 3 7 _C(--34_F)and overheating protection to
129°C (265°F). A coolant solution with less than
50% ethylene glycol may not provide adequate
freezing and overheating protection. A coolant
solution with more than 50% ethylene glycol can
cause engine or component damage. Do not use
alcohol or methanol antifreeze or mix them with
the specified coolant.Consult the engine
manufacturer’s operation manual for engine
coolant specifications.
In a closed cooling system, the seawater circulates
through separate chambers within the heat exchanger
to cool the engine water. The seawater then mixes with
engine exhaust and ejects out the exhaust outlet. See
Section 1.3 for the coolant capacities. Add an additional
0.24 L (8.0 oz.) of coolant to the coolant recovery tank.
5.4Fill Check and Coolant
Keep the coolant recovery tank approximately 1/4 full.
Before filling the cooling system, close all petcocks and
tighten all hose clamps. Use a solution of 50% ethylene
5.5Flush and Clean Cooling
System
For optimum protection, drain, flush, and refill the
cooling system at the interval listed in the operation
manual’s service schedule.
Pay special attention to the coolant level. Check the
coolant level as described earlier.
Flush and Clean Procedure
1. Remove the pipe plug located in the heat
exchanger.
2. Open the petcocks on the engine block and cooling
system and let the system drain completely. Some
models may have petcocks located behind the belt
guard.
3. Remove the pressure cap to simplify draining.
4. Drain, clean, and flush the cooling system,
including the coolant recovery tank, with clean
water.
5. Close the petcocks.
6. Fill the cooling system with recommended coolant.
TP-6053 7/0420 Section 5 Cooling System
Page 33
5.6Pressure Cap
9. Open the seacock.
Closed heat exchanger systems utilize a pressure cap
to raise the boiling point of the coolant, enabling higher
operating temperatures. If the cap leaks, replace it with
a cap having the same temperature rating.
5.7Impeller Inspection and
Replacement
The belt-driven seawater pump is located on the service
side of the generator set.Check and change the
seawater pump impeller at the interval specified in the
service schedule. Follow the instructions included with
the impeller kit. If the instructions are not included with
the kit, use the following procedure.
Inspection and Replacement Procedure
1. Close the seacock.
2. Remove the seawater pump coverplate.See
Figure 5-4.
3. Remove the impeller.
4. Inspect the impeller for damage, including visible
cracked, broken, worn or missing fins.The
impeller vanes should be straight and flexible. See
Figure 5-5.
10. Start the generator set and check for leaks.
11. Stop the generator set and repair leaks or replace
components as necessary.
1
2
3
10
8
9
1. Seawater pump
2. Coverplate
3. Gasket
4. Impeller
5. Bearing
6
7
4
5
TP-5936-28
6. Housing
7. Pulley
8. Drive shaft
9. Washer
10. Nut
Figure 5-4 Seawater Pump, Typical
1
2
5. Lubricate the impeller with soapy water before
re-installation.
6. While installing the impeller, always rotate the drive
shaft and the impeller together in the same
direction as the engine rotation.
7. Inspect the coverplate and gasket for corrosion
and/or damage.Replace damaged or worn
components.
8. Lubricate the gasket with silicon grease and attach
the gasket and coverplate to the seawater pump
housing.
3
TP-5936-57
1. Flat spot
2. Crack
3. Broken vane
Figure 5-5 Worn Impeller
TP-6053 7/0421Section 5 Cooling System
Page 34
5.8Belt Tension
7. Tighten the adjusting arm pivot screw and
alternator pivot screw.
WARNING
Rotating parts.
Can cause severe injury or death.
Operate the generator set only when
all guards, screens, and covers are in
place.
Servicing the generator set when it is operating. Exposed
moving parts can cause severe injury or death. Keep
hands, feet, hair, clothing, and test leads away from the belts
and pulleys when the generator set is running. Replace
guards, screens, and covers before operating the generator
set.
Check the belt tensions at the interval specified in the
service schedule. If the tensions are not within
specifications, adjust as necessary using the following
procedure.
Belt Tensioning Procedure
1. Stop the generator set.
8. Recheck and adjust the belt tension as necessary.
9. Replace the belt guard.
10. Reconnect the generator set engine starting
battery, negative (--) lead last.
Belt TypeDeflection mm (in.)Force (kgf) N
New(7--9) 0.3--0.4(10) 98
Used(10--15) 0.4--0.6(10) 98
Figure 5-6 Belt Specifications
3
1
2
4
10
9
5
2. Disconnect the generator set engine starting
battery, negative (--) lead first.
3. Remove the belt guard.
4. Check the belt tension at the midpoint of the
longest span of the belt by pressing the belt with
your finger and measuring the resulting deflection.
See Figure 5-6 and Figure 5-7. If the belt is not
within specifications, go to step 5. If the belt is
within specifications, go to step 9.
5. Loosen the adjusting arm pivot screw, alternator
pivot screw, and alternator adjusting screw.
6. While prying the alternator outward, tighten the
alternator screw.
8
1. Adjusting arm pivot screw
2. Battery charging alternator pulley
3. Adjusting screw
4. Alternator pivot screw
5. Check alternator belt tension here
6. Crankshaft pulley
7. Check seawater pump belt tension here
8. Adjusting screw
9. Seawater pump pulley
10. Pivot screw
7
Figure 5-7 Belt Tension, Typical
6
TP-5586-3
TP-6053 7/0422 Section 5 Cooling System
Page 35
5.9Siphon Break
3. Use a light detergent to clean the reed valve.
A siphon break prevents seawater entry into the engine
when the engine exhaust manifold outlet is less than
23 cm (9 in.) above waterline. Check the siphon break
at the interval listed in the service schedule. Use the
following procedure and Figure 5-8 to ensure correct
functioning of the siphon break.
Siphon Break Inspection Procedure
1. Stop the generator set.
2. Remove the retaining cap and the reed valve for
inspection. See Figure 5-8.
2
3
1
21
4. Check that the reed valve opening is clear.
5. Replace the siphon break if it is cracked or if the
reed valve material has hardened or deteriorated.
6. Install the reed valve downward into the mounting
base.
7. Install the retaining cap and finger-tighten only. Do
not overtighten.
Note: Consult the installation manual for a complete
5. Exhaust mixer elbow distance above waterline. If less than
23 cm (9 in.), a siphon break is required.
6. Siphon break distance above waterline 30.5 cm (1 ft.) min.
7. Siphon break
8. Exhaust mixer elbow
9. Heat exchanger (locations vary by model)
10. Coolant recovery tank (locations vary by model)
5
4
15
16
17
11. Seawater strainer
12. Seacock
13. Intake strainer
14. Engine-driven seawater pump
15. Exhaust hose pitch 1.3 cm per 30.5 cm (0.5 in. per ft.) min.
16. Water lock (optional)
17. Silencer distance from exhaust mixer elbow 3 m (10 ft.) max.
18. Silencer (customer-supplied)
19. Exhaust hose pitch 1.3 cm per 30.5 cm (0.5 in. per ft.) min.
20. Exhaust outlet distance above waterline 10 cm (4 in.) min.
21. Seawater outlet
14
13
11
12
TP-5586-3
Figure 5-8 Siphon Break, Plastic “U” Type
TP-6053 7/0423Section 5 Cooling System
Page 36
5.10 Anticorrosion Zinc Anode
The heat exchanger contains an anticorrosion zinc
anode (plug) to prevent electrolytic corrosion of
generator components by seawater.
Check and replace the zinc anode at intervals
recommended by the operation manual’s service
schedule.
1
5EOZ/4EFOZ
3
2
Anticorrosion Zinc Anode Replacement Procedure
1. With the generator set cooled, close the seacock,
remove the zinc plug from the heat exchanger, and
drain the coolant into a container.
2. Remove the corrosion on the zinc anode. Replace
the anode when the percent of the zinc remaining is
less than 50% of the length and diameter shown in
Figure 5-10.
3. Clean the threaded opening of the heat exchanger
and coat the threads of the zinc anode with pipe
sealant.
4. Install the zinc anode into the heat exchanger.
5. Open the seacock.
6. Refill the cooling system.
7. Start the generator set and check for leaks at the
zinc anode’s location. The pump is operating if
cooling water flows from the exhaust outlet. If water
is not discharging at the exhaust outlet stop the
generator set. For seawater pump priming see the
Prestart Checklist in the operation manual.
1
8EOZ/6.5EFOZ
2
3
9/10EOZ and 8/9EFOZ
1. Anticorrosion zinc anode (seawater drain)
2. Heat exchanger
3. Coolant drain
2
3
GA-250000C-G
1
2
TP-5586-3
1. Diameter: 9 mm (0.34 in.)
2. Length: 43 mm (1.7 in.)
Figure 5-10 Anticorrosion Zinc Anode (Plug)
1
Figure 5-9 Anticorrosion Zinc Anode
TP-6053 7/0424 Section 5 Cooling System
Page 37
Section 6 Controller Troubleshooting
6.1General
Thefollowingsectioncoversthecontroller
troubleshooting procedure for generator sets equipped
with the relay controller and related engine components.
RefertoFigure 6-1toidentifythecontroller
components.
1
7
shutdown modes.Use this as a starting point for
controller fault identification.Use the LEDs on the
controller circuit board to assist in the troubleshooting
process.An illuminated LED indicates that the
respective relay is receiving power; the LED does not
indicate whether that relay is energized.Additional
relay test procedures are covered later in this section.
Refer to the wiring diagrams in Section 10, Voltage
Reconnection and Wiring Diagrams, to assist in the
troubleshooting procedure.
6.2.1Start
Close the start/stop switch between N (ground) and 47
(local or remote starting).
The K2 relay energizes. The normally open K2 contacts
close to energize the K3 relay (LED3 lights), the K25
(fuel solenoid) relay, the controller hourmeter, and the
generator armature exciter field.
The K25 relay normally open contacts close to energize
the fuel solenoid.
5
4
6
1. Voltage regulator
2. DC circuit breaker
3. K25 relay
4. Hourmeter
3
46
2
2
A-229301-N
5. K20 relay
6. START/STOP switch
7. Controller circuit board
Figure 6-1 Controller Internal Components
6.2Controller Sequence of
Operation
The following text covers the controller’s sequence of
operation during generator start, run, stop, and fault
The K3 relay normally open contacts close to energize
the K20 (starter) relay. The K20 relay normally open
contacts close to energize the S relay (starter solenoid).
The S relay normally open contacts close to energize
the starter motor.
6.2.2Run
The B1 and B2 windings of the stator supply AC voltage
to the bridged rectifier (BR1), the K1 relay energizes
(LED1 lights). After a 5--10 second time delay, the K5
relay energizes (LED5 lights).
Note: Voltage to the K1 and K5 relays is rectified and
regulated at 12 volts DC by the bridge rectifier
(BR1) and the voltage regulator (VR1).
Stator winding 33--34 provides a voltage sensing source
to the voltage regulator (PBIIIE).
The normally open K1 contacts close to maintain
voltage to the K2 relay (LED2 remains lit).
The normally open K2 contacts remain closed to
maintain voltage to the fuel solenoid and the controller
hourmeter.
The normally open K1 contacts close to energize the
(optional) oil pressure, coolant temperature, battery
voltmeter, and hourmeter gauges and the generator ON
light.
The normally open K5 contacts close to permit the high
water temperature (HWT), high exhaust temperature
(HET), and low oil pressure (LOP) switches to function.
6.3Engine Safety Shutdown
Switches
6.3.1Low Oil Pressure (LOP) Shutdown
When low oil pressure occurs, the LOP shutdown switch
contacts close and energize the K4 relay (LED4 lights).
Note: The low oil pressure (LOP) switch contacts open
when the engine develops oil pressure.
One set of normally closed K1 contacts opens to
disconnect the circuit to the positive (+) connection of
the exciter fields (field flashing).
A set of normally closed K1 contacts opens to
disconnect the circuit to the negative (--) connection of
the exciter field (field flashing). The normally closed K1
contacts open to deenergize the K3 relay (LED3 goes
out) and prevent accidental reenergizing of the starter
motor. The K3 contacts open to deenergize the K20
relay. The K20 contacts open to deenergize the S relay.
The S contacts open to deenergize the starter motor.
When the generator set is running, the start switch
contacts N and 47 open by releasing the start/stop
rocker switch.
6.2.3Stop
Close the start/stop switch between N and 43 (local or
remote).
Note: During cranking the low oil pressure shutdown
switch is deactivated until the K5 relay energizes.
This delay allows the engine to reach normal
operating oil pressure. The normally closed LOP
contacts open when the generator set develops
adequate oil pressure.
The normally closed K4 contacts open to deenergize the
K25 relay. The K25 normally open contacts open to
deenergize the fuel solenoid.
The normally open K4 contacts close to maintain ground
to the K4 relay.
As the generator set shuts down, the K1 relay
deenergizes (LED1 goes out). The normally open K1
contacts open to deenergize the K2 relay (LED2 goes
out). The normally closed K2 contacts close to ground
the circuit to the K4 relay until the generator set comes to
a complete stop.
6.3.2High Water Temperature (HWT)
and High Exhaust Temperature
(HET) Shutdown Switch
The K4 relay energizes (LED4 lights).
The normally closed K4 contacts open to deenergize the
K25 relay. The K25 normally open contacts open to
deenergize the fuel solenoid.
The normally open K4 contacts close to maintain ground
to the K4 relay.
As the generator set shuts down, the K1 relay
deenergizes (LED 1 goes out). The normally open K1
contacts open to deenergize the K2 relay (LED 2 goes
out). The normally closed K2 contacts close to ground
the circuit to the K4 relay until the generator set comes to
a complete stop.
When a high temperature is encountered at one (or
both) of these sources, the shutdown switch contacts
close and energize the K4 relay (LED4 lights).
The normally closed K4 contacts open to deenergize the
K25 relay. The K25 normally open contacts open to
deenergize the fuel solenoid.
The normally open K4 contacts close to maintain ground
to the K4 relay.
As the generator set shuts down, the K1 relay
deenergizes (LED1 goes out). The normally open K1
contacts open to deenergize the K2 relay (LED2 goes
out). The normally closed K2 contacts close to ground
the circuit to the K4 relay until the generator set comes to
a complete stop.
If functional, approximately 270 ohms.
Low resistance (continuity), shorted coil.
High resistance, open coil.
If functional, approximately 270 ohms.
Low resistance (continuity), shorted coil.
High resistance, open coil.
If functional, approximately 400 ohms.
Low resistance (continuity), shorted coil.
High resistance, open coil.
If functional, approximately 125 ohms.
Low resistance (continuity), shorted coil.
High resistance, open coil.
If functional, approximately 510 ohms.
Low resistance (continuity), shorted coil.
High resistance, open coil.
Figure 6-2 Relay Testing
6.4Controller Circuit Board
Some controller circuit board components can be tested
without removing the component from the circuit board.
Perform these checks prior to installing a new circuit
board and attempting startup.Use a high-quality
multimeter and follow the manufacturer’s instructions.
To obtain accurate readings when testing, remove all
the circuit board connectors and conformal coating
(transparent insulation) from component terminals. Use
the chart in Figure 6-2 and the controller circuit board
illustration in Figure 6-3.
1
13
23
4
5
The controller circuit board has light-emitting diodes
(LEDs) which indicate relay coil power and aid in the
circuit board and the generator fault detection. When
the K1, K2, K3, K4, or K5 relays receive power the
corresponding LED lights. The LED does not indicate
whether the relay coil is energized. Determine if the
relay coil is energized by analyzing the generator faults
when performing a continuity test on the relay coil.
Beforebeginningthefollowingtroubleshooting
procedures, read all the safety precautions at the
beginning of this manual. The following tests include
additional safety precautions; OBSERVE THESE
PRECAUTIONS!
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
Testing the voltage regulator. Hazardous voltage can
cause severe injury or death. High voltage is present at the
voltage regulator heat sink. To prevent electrical shock do not
touch the voltage regulator heat sink when testing the voltage
regulator.
(PowerBoostt, PowerBoostt III,and PowerBoostt V
voltage regulator models only)
Moving rotor.
7.2General Troubleshooting
To determine the cause of no- or low-AC output , refer to
the following steps and the troubleshooting flow chart
(Figure 7-1).
General Troubleshooting Procedure
1. Check the condition of the voltage regulator’s
8-amp fuse.
2. If the fuse is functional, separately excite the
generator. (See Section 7.3.)The separate
excitation test duplicates the role of the voltage
regulator by providing excitation current to the
rotor.
Generator has no
output
Separately
excite generator
Generator has
output
Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible
whenever electricity is present.Open the main circuit
breakers of all power sources before servicing the equipment.
Configure the installation to electrically ground the generator
set, transfer switch, and related equipment and electrical
circuits to comply with applicable codes and standards. Never
contact electrical leads or appliances when standing in water
or on wet ground because these conditions increase the risk of
electrocution.
High voltage test. Hazardous voltage can cause severe
injury or death. Follow the instructions of the test equipment
manufacturer when performing high-voltage tests on the rotor
or stator. An improper test procedure can damage equipment
or lead to generator set failure.
Short circuits. Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
Generator has
no output
Test the exciter circuit
and rectifier module
Test rotor
Test voltage
regulator and wiring
Test stator
Figure 7-1 General Troubleshooting
TP-598651
TP-6053 7/0433Section 7 Generator Troubleshooting
Page 46
7.3Separate Excitation
By separately exciting the generator to determine the
presence of a faulty voltage regulator, it is possible to
determine if a running fault exists in the rotor and/or
stator. A generator component that appears functional
while static (stationary) may exhibit a running open or
short circuit while dynamic (moving). Centrifugal forces
acting on the windings during rotation or insulation
breakdown as temperatures increase can cause short
circuits.
5. Start the engine and check that the ammeter
remains stable.An increasing meter reading
indicates a shorted rotor.A decreasing meter
reading to zero or unstable reading, suggests a
running open in the rotor. If the ammeter is stable,
continue with step 6.
6. Check for AC output across the stator leads and
compare the measured output to the values in
Section 1, Specifications.If the output varies
considerably from those listed, a faulty stator, rotor,
rectifier module, or armature is the likely cause.
Separate Excitation Procedure
1. Disconnect all the leads from the voltage regulator.
2. Disconnect the P10 (F1, F2) connector.
3. Connect a separate excitation circuit as shown in
Figure 7-2. Connect an ammeter and a 10-amp
fuse in series with F1.Note and record the
ammeter reading.
4. The approximate ammeter reading should equal
battery voltage divided by the specified exciter
resistances (cold). Disconnect the resistor leads
and determine the resistance value using an
ohmmeter. See Section 1, Specifications, for the
correct values.
Example:
12 Volts (Battery Voltage)
3.5 Ohms Exciter Resistance
+—
9
P6
8
F1F2
1. Voltage regulator
2. 10-amp fuse
3. DC ammeter
4. Battery
5. Ground to generator frame
6. Exciter armature
7. Exciter field
8. 10- or 15-ohm resistor
9. P6 connector (disconnect P6 connector before separate
excitation)
1
7
6
3.4-amp
=
Exciter Current
2
5
3
4
Figure 7-2 Separate Excitation Connections
Note: See Section 1, Specifications, for the stator
outputvoltages(withseparatelyexcited
generator). These specifications are based on a
battery of 12 volts. Should the battery voltage
vary, the resulting stator output values will also
vary.
If there is no generator output during normal operation
but output is available when the generator set is
separately excited, the voltage regulator is probably
inoperative.
7.4PowerBoost IIIE Voltage
Regulators
The generator set is equipped with a PowerBoostt IIIE
voltage regulator. See Figure 7-3.
The voltage regulator monitors the output voltage to the
generator exciter field.
If the regulator’s 8-amp fuse blows, the generator set will
shut down. Verify that the regulator fuse is functional
before proceeding with the test.
When the frequency drops below 57.5/47.5 Hz, the AC
voltage should decline. Perform the following test to
check the regulator output.
Use the following components to test the voltage
regulator:
D Variable transformer, 0--140 volts, 0.5-amp minimum
D Plug, 120 volts AC
D Lamp, 120 volt, 100 watt
D AC voltmeter
D Insulated copper wire, #14 AWG, minimum
Regulator Test Procedure
1. Connect the components as shown in Figure 7-4.
123
66 443355--+
RYOW
GY
1. 120 volts AC
2. Variable transformer
3. AC voltmeter
4. Voltage regulator PowerBoosttIIIE
5. Stator/rotor connections (for reference only)
6. Lead color
7. 120 volt, 100 watt lamp
4
5
BK
6
7
TP-598654
2. Turn the variable transformer setting to zero. Plug
in the variable transformer.
3. Turn the variable transformer on. Slowly increase
the variable transformer voltage to 100 volts. The
test lamp should light. If the lamp does not light,
turn the voltage adjustment potentiometer (pot)
clockwise.If the lamp still does not light, the
voltage regulator is inoperative.Replace the
voltage regulator. An inoperative voltage regulator
causes a generator no/low-output condition.
4. Slowly increase the voltage to 120 volts. The lamp
should go out and stay out as the voltage
increases. If the lamp remains lit, turn the voltage
adjustment pot counterclockwise. If the lamp still
remains lit, replace the voltage regulator.An
inoperative voltage regulator causes a generator
high voltage output condition.
5. Turn the variable transformer to zero and unplug
the AC cord.
Note: For applications requiring fine voltage
adjustment, connect a remote rheostat to
voltage regulator terminal 66.
Figure 7-4 PowerBoosttIIIE Voltage Regulator Test
7.4.2Voltage Regulator Adjustment
Kohler Co. sets the voltage regulator and, under normal
circumstances, the regulator requires no further
adjustment. However, if the voltage regulator has been
replaced or tampered with, or if voltage/frequency
reconnection has been done, readjust the voltage
regulator according to the following procedure. The
following paragraphs describe the voltage regulator
components.
Voltage Adjustment Pot adjusts the generator output
within the range of 100--130 volts.
Stabilizer Pot fine-tunes regulator circuitry to reduce
light flicker.
Volts/Hz Pot adjustment determines the engine speed
(Hz) at which the generator output voltage begins to
drop.
Note: The volts/Hz adjustment does not apply to the
followingmodels:4/6.5/8/9EFOZand
5/8/9/10EOZ. On these models, turn the volts/Hz
adjustment pot full counterclockwise to stop and
seal.No further volts/Hz adjustments are
required.
TP-6053 7/0435Section 7 Generator Troubleshooting
Page 48
Voltage Regulator Adjustment Procedure
1. Stop the generator set.
2. Turn the remote rheostat, if equipped, to the
midpoint. Turn the voltage and stability pots fully
counterclockwise. Connect the voltmeter to the AC
circuit or an electrical outlet.
3. Start the generator set.
4. Adjust the engine speed to 1800 rpm on 60 Hz units
and 1500 rpm on 50 Hz units.
5. Rotate the voltage adjustment pot clockwise to
increase the voltage or counterclockwise to
decrease the voltage to achieve the desired output
voltage.
8. Use the remote rheostat, if equipped, to make final
voltage adjustments.
9. Stop the generator set.
7.5Exciter Field
DC current from the battery magnetizes the exciter field.
Whentheexciterarmaturerotateswithinthe
magnetized exciter field windings, an electrical current
develops within the exciter armature. There will be low
or no generator output if the exciter field is inoperative.
Test the exciter field according to the following
procedure.
Exciter Field Test Procedure
6. Rotate the stability pot clockwise until the light
flickers minimally.
7. Readjust the voltage adjustment pot to achieve
the desired output voltage.
17
1
66
33
4
3
16
33
44
66
GY R
44 33 55
YOWBK
15
13
B1
14
B2
55
10
11
21
12
1. Voltage adjustment potentiometer
2. Stabilizer potentiometer
3. Volt/Hz potentiometer
4. Exciter connections (for reference only)
5. Lead color
6. DC output
7. Exciter
8. Rotor
9. Armature
10. 8-amp fuse
11. AC power input (aux.)
12. Main (2 and 1)
13. Control
14. Stator
15. Sensing
16. Main (3 and 4)
17. Remote rheostat (optional)
2
3
4
+
--
5
6
8
7
9
605375
1. Place the start/stop switch in the STOP position.
2. Disconnect the generator set engine starting
battery, negative (--) lead first.
3. Disconnect the P6 and P7 connectors.
4. Check the exciter field resistance by connecting an
ohmmeter across exciter field FP and FN leads.
See Section 1, Specifications, for the resistance
reading of a cold exciter field.A low reading
indicates an internal short and a high reading
indicates an open winding. Repair or replace the
exciter field if the ohmmeter readings indicate a
inoperative exciter field. If the resistance test
proves inconclusive, perform a megohmmeter test
on the exciter field as described in the next step.
5. Check the exciter field for a grounded condition.
Use a megohmmeter to apply 500 volts DC to the
FP or FN lead and the exciter field frame. Follow
the instructions of the megohmmeter manufacturer
when performing this test.A reading of
approximately 500 kOhms (1/2 megohm) and
higher indicates the field winding is functional. A
reading of less than approximately 500 kOhms
indicates deterioration of the winding insulation
and possible current flow to ground. Repair or
replace the exciter field.
AC
AC
AC
1
F+
F--
6
5
3
2
4
1
P7
4
FPFN
2
3
558858
1. Ohmmeter
2. Frame connection
3. Exciter armature
4. Exciter field
Figure 7-7 Megohmmeter Connections on the
Exciter Field
7.6Exciter Armature
The exciter armature supplies excitation current to the
generator main field through the rectifier module. There
will be low or no generator output if the exciter armature
is inoperative. Test the exciter armature as described in
the following steps. Disassemble the generator set prior
to performing this test.
1. Main field (rotor)
2. Stator windings
3. Rectifier module
4. Ohmmeter
5. Armature
6. Exciter field
Figure 7-8 Exciter Armature Ohmmeter Test
5. Check if the exciter armature winding is ground.
Use a megohmmeter to apply 500 volts DC to
either armature lead and the armature frame.
Follow the instructions of the megohmmeter’s
manufacturer when performing this test.See
Figure 7-9. A reading of approximately 500 kOhms
(1/2 megohm) and higher indicates that the exciter
armature is functional.A reading of less than
approximately 500 kOhms indicates deterioration
of the winding insulation and possible current flow
to ground. Repair or replace the exciter armature.
AC
AC
AC
1
F+
F--
3
2
7
6
558878
Exciter Armature Test Procedure
1. Disassemble the alternator.
2. Disconnect the armature leads from the rectifier
module AC terminals.
3. With an ohmmeter on the R x 1 scale, check the
resistance across the exciter armature leads. See
Figure 7-8. The armature resistance should be
0.6--0.8 ohms (continuity). No continuity indicates
an open armature winding. Replace the armature.
4. Perform a megohmmeter test on the exciter
armature as described in the next step. Consider
the exciter armature good if the resistance reading
(continuity) is low and there is no evidence of a
shorted winding (heat discoloration).
TP-6053 7/0437Section 7 Generator Troubleshooting
4
5
558879
1. Main field rotor
2. Stator windings
3. Rectifier module
4. Ohmmeter
5. Shaft connection
6. Armature
7. Exciter field
Figure 7-9 Megohmmeter Connections on Exciter
Armature
Page 50
7.7Rectifier Module
7.8Rotor
The rectifier module, located between the exciter
armature and the main field, converts the AC from the
exciter armature to DC which magnetizes the generator
main field. Test the rectifier module as described in the
following steps.
Rectifier Module Test Procedure
1. Disconnect the exciter armature and the main field
leads from the rectifier module.
2. Use an ohmmeter on the R x 100 scale to check the
resistance between the rectifier diodes as shown in
Figure 7-10.Theohmmetershouldshow
resistance in one direction and, upon reversing the
ohmmeter leads, a high resistance in the other
direction. Replace the rectifier module if any of the
diodes tests differently than described.
A
B
+
--
The generator rotor (magnetized by DC current from the
rectifier module) rotating within the stator windings
induces AC voltage in the stator windings. Test the
generator rotor (main field) as described in the following
steps.
Rotor Test Procedure
1. Disassemble the generator.
2. Disconnect the generator main field windings from
rectifier module terminals F+ and F--.
3. Check the main field resistance by connecting an
ohmmeter across the main field F+ and F-- leads.
See Figure 7-11. The resistance reading for a cold
main field should be approximately 2.5--4.5 ohms.
A low reading indicates an internal short and a high
reading indicates an open winding. Replace the
main field if the ohmmeter readings indicate that
the main field is inoperative.
4. Perform a megohmmeter test on the main field as
described in the next step.
5. Check the main field for a grounded condition by
using a megohmmeter. Apply 500 volts DC to
either field lead and the main field frame. Follow
theinstructionsofthemegohmmeter’s
manufacturer when performing this test.See
Figure 7-12.Areadingofapproximately
500 kOhms (1/2 megohm) and higher indicates the
main field is good.A reading of less than
approximately500kOhmsindicatesthe
deterioration of the winding insulation and possible
current flow to ground. Repair or replace the main
field.
7
6
AC
AC
AC
1
F+
F--
3
2
Stator Test Procedure
1. Check the generator output lead connections. See
Section 10, Voltage Reconnection and Wiring
Diagrams.
2. Disconnect all the stator leads to isolate the
windings. To check the stator continuity, set the
ohmmeter on the R x 1 scale. Contact the red and
black ohmmeter leads; adjust the ohmmeter to
zero ohms.Check the stator continuity by
connecting the meter leads to the stator leads as
shown in Figure 7-13. Perform the stator tests on
all the stator windings. See Figure 7-14.
3. Contact the ohmmeter leads and readjust the
ohmmeter to zero ohms.Check the cold
resistance of the stator windings by connecting the
meter leads to the stator leads 1 and 2, 3 and 4,
B1 and B2, etc. See Section 1, Specifications, for
the stator resistance values. Replace the stator if
readings do not fall within the specified value.
5
4
5588712
1. Main field (rotor)
2. Stator windings
3. Rectifier module
4. Shaft connection
5. Megohmmeter
6. Armature
7. Exciter field
Figure 7-12 Megohmmeter Connections on Main
Field
7.9Stator
The stator consists of a series of coils of wire laid in a
laminated steel frame. The stator leads supply voltage
to the AC load and exciter regulator.
Leads 1, 2, 3, and 4 are the generator output leads.
Leads 33, 44, and 55 are the voltage regulator supply
and sensing leads. The output of leads B1 and B2 are
rectified by BR1 to supply the control voltage. BR1 is
located on the controller circuit board.
Prior to testing, inspect the stator for heat discoloration
and visible damage to the housing lead wires or
exposed and varnished areas of the frame laminations.
Be sure the stator is securely fastened in the stator
housing.
The stator produces electrical output (AC) as the
magnetized main field rotates within the stator windings.
Test the condition of the stator according to the following
procedure. Refer to the schematic in Figure 7-13 when
performing the following tests.
Note: The stator resistance will vary directly with
increased temperature.
333
F1F2
6
1
F+
AC
AC
AC
F--
5
3
5544
12B1B2
4
1. Main field (rotor)
2. Stator windings
3. Rectifier module
4. Ohmmeter
5. Armature
6. Exciter field
Figure 7-13 Stator Ohmmeter Connections
Between LeadsContinuity
1 and 2
3 and 4
33 and 44
33 and 55
B1 and B2
1 and 3, 4, 33, 44, 55
1 and 55, B1, and B2
4 and B1 and B2
55 and B1 and B2
Any stator lead and ground
Figure 7-14 Stator Continuity
4
2
5588713
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
TP-6053 7/0439Section 7 Generator Troubleshooting
Page 52
4. Perform a megohmmeter test on the stator as
described in the next step. Consider the stator
good if the resistance reading (continuity) is low
and there is no evidence of shorted windings (heat
discoloration).
Note: When taking an ohmmeter reading using
lead 55, make the connection prior to the
in-line fuse.
5. Check the stator for a short to ground using a
megohmmeter. Apply 500 volts DC to any stator
lead from each winding and the stator frame.
Follow the instructions of the megohmmeter
manufacturer when performing this test. Repeat
the test on the other leads until all the stator
windings have been tested.A reading of
approximately 500 kOhms (1/2 megohm) and
higher indicates the stator is good. A reading of
less than approximately 500 kOhms indicates
deterioration of the winding insulation and possible
current flow to ground. Repair or replace the stator.
See Figure 8-1 through Figure 8-3 for component
testing.With the generator set battery connected,
checkthegeneratorwiringharnessandthe
components listed in the following tables. Check each
component using a multimeter to verify that the switches
function and that voltage is present at each component.
WARNING
Short circuits. Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
Component
Hourmeter and wiringConnect the red test lead to
Stator auxiliary winding B1
and B2
Moving rotor.
Voltmeter ConnectionsProcedureResults
the hourmeter positive (+)
terminal. Connect the black
test lead to the hourmeter
negative (--) terminal.
None (see Procedure).Disconnect the hourmeter
Connect the AC voltmeter
leads to the B1 and B2
windings at connector P11.
Set the voltmeter to 12 volts
DC or greater. Start the
generator set.
leads and apply 12 volts DC
to the hourmeter. The
hourmeter is polarity
sensitive.
Stop the generator set.
Connect a voltmeter to the
B1 and B2 windings. Crank
the generator set and allow
the set to reach rated its
speed.
High exhaust
temperature (HET), low
coolant (LCS) safety
shutdown switches
Low oil pressure (LOP)
safety shutdown switch
connectors and connect the
ohmmeter to P10-1 and P10-2
leads.
P11-1 and P11-2 leads.
Note: Disconnect P11 and J11
to perform this test.
P1-9 and ground.
Connect the ohmmeter to the
P1-15 and engine block
(ground). Note: Remove and
isolate the LOP switch lead.
Connect the ohmmeter to the
P13-1 and engine block
(ground).
Place the ohmmeter on the
Rx1scale.
Place the ohmmeter on the
Rx1scale.
Place the ohmmeter on the
Rx1scale.
Place the ohmmeter on the
R x 1000 scale.
Place the ohmmeter on the
R x 1000 scale. This test is
not conclusive until the
temperature shutdown
switches are checked.
If the resistance readings
match those specified in
Section 1, Specifications, the
rotor is functional. Low
resistance, rotor windings
shorted. High resistance,
rotor windings open.
If the resistance readings
match those specified in
Section 1, Specifications, the
B1/B2 windings are
functional. Low resistance,
B1/B2 windings shorted. High
resistance, B1/B2 windings
open.
If functional, zero ohms
(continuity). Any other
reading indicates a poor
ground connection.
If functional, open circuit. Any
continuity suggests an
inoperative temperature
switch(es). Replace the
switch(es).
If functional, zero ohms
(continuity). Then, disconnect
the LOP switch lead and
isolate the terminal. Meter
reading should show an open
circuit.
Kohler Co. offers three remote panels for connection to
the generator set:
Troubleshooting Remote Start Panels
Generally, if the sender changes its resistance values as
its respective pressure/temperature changes, it is
working correctly. An inoperative sender will either be
D A panel with a start/stop switch
open or shorted. Refer to Figure 8-4 and Figure 8-5 for
resistance values.
D A panel with a start/stop switch and two gauges
(engine oil pressure and water temperature)
D A panel with a start/stop switch and four gauges (DC
voltmeter, engine oil pressure, water temperature,
and hourmeter)
If difficulty with the remote operation occurs, test the
switch, gauges, and gauge senders using the following
Figure 8-4 Water Temperature Sender Resistance
procedures. See Sections 10.5 through 10.7 for wiring
diagrams.
345 kPa (50 psi)
690 kPa (100 psi)
2-Meter and 4-Meter Panels
TemperatureResistance
60_C (140_F)
90_C (194_F)
100_C (212_F)
2-Meter and 4-Meter Panels
PressureResistance
0 kPa(0 psi)
134.0 ±10 ohms
51.5 ±4 ohms
38.0 ±3 ohms
10 ohms
80 ohms
135 ohms
TP-6053 7/0443Section 8 Component Troubleshooting
Figure 8-5 Oil Pressure Sender Resistance
Page 56
Refer to Figure 8-6 for troubleshooting information on the remote start panels.
ComponentOhmmeter ConnectionsProcedureResults
Remote start/stop switch
Remote switch: yellow/red
wire terminal and black wire
terminal.
Remote switch: grey/black
wire terminal and black wire
terminal.
Generator set ON light,
gauge lights, DC voltmeter,
and hourmeter
Connect the red test lead to
P3-4 and black test lead to
P3-1.
Water temperature gaugeConnect the red test lead to
P3-4 (socket side) and black
test lead to P3-2 (socket
side).
Oil pressure gaugeConnect the red test lead to
P3-4 (socket side) and black
test lead to P3-3 (socket
side).
Note: Check continuity of gauge wiring and extension harness before replacing components.
Place the ohmmeter on the
Rx1scale.
Press the rocker switch to the
START position.
Place the ohmmeter on the
Rx1scale.
Press the rocker switch to the
STOP position.
Place the controller rocker
switch to the START position.
Stop the generator set when
the test is complete.
Generator set does not need
to be running, just cranking
forthistest.
Note: If the hourmeter is not
illuminated, test it by
connecting it to a 12-volt
battery.
Note: The hourmeter is
polarity sensitive.
Start the generator set for the
test.
Start the generator set for the
test.
Continuity, the switch is
functional. Open, replace
switch.
Continuity, the switch is
functional.
If 12-volts DC is present and
the component does not
function after the J3 is
connected to the controller
P3, replace the
component(s).
If0.5--12-voltsDCispresent
and the gauge does not
function after the J3 is
connected to controller,
replace the gauge.
If0.5--12-voltsDCispresent
and the gauge does not
function after the J3 is
connected to the controller,
replace the gauge.
Disconnect all the external connections—battery cables
at the battery (negative (--) lead first), AC-output leads in
the controller, remote start panel at the controller P3
connector, water line at the seawater pump, fuel line at
the fuel pump filter inlet, and exhaust line at the mixing
elbow. Observe all the safety precautions listed at the
beginning of this manual during the disassembly/
reassembly procedures.
Note: Because this manual covers several models, the
procedure for disassembly may vary because of
product updates and the assembly variations.
Note: The voltage regulator is located in the controller
box. Remove the controller cover to service the
voltage regulator.Adjustments are possible
without removing the voltage regulator from the
controller.
1. Remove the end panel from the alternator end of
the generator set. See Figure 9-1.
2. Loosen the four screws and lift off the controller
cover.
8. Remove the tie wraps from the wire harness as
necessary. Disconnect the F1 connectors from the
resistor leads.
1
2
3
4
CD-250000-AJ
1. Controller cover
2. P4 (22-pin) connector
3. Ground strap
4. Generator end panel
Figure 9-1 Covers
2
3. Disconnect the P4 (22-pin) connector from J4.
4. Remove the bolt and disconnect the ground strap.
Note: It is possible to connect the output leads in
variouspositionsfordifferentvolt
configurations. Mark leads 1, 2, 3, and 4 for
correct reconnection.
5. Disconnect the generator output leads 1, 2, 3, and
4 from the circuit breaker and neutral stud (L0).
6. Remove the four controller mount locknuts. See
Figure 9-2.
7. Lift the controller from the rubber mounts while
guiding the leads through the bottom hole of the
controller box.
9. Disconnect the P7 (FP and FN) and P6 (F1 and F2)
connectors. See Figure 9-3.
10. Remove the four bolts to remove the exciter field.
SeeFigure9-3.
11. Remove the three bolts and spacers from the
rectifier board.
12. Disconnect the main field rotor leads from the
rectifierboardpositive/negativeterminals.
Remove the bolt and washer.
13. Remove the armature from the shaft, guiding rotor
leads through the armature bores. See Figure 9-4.
14. Remove the tie wraps and disconnect the P5 (33,
44, 55, B1, and B2) wire connector.
1
4
1. P7 connector
2. P6 connector
3. F1 connector
4. Exciter field
Figure 9-3 Exciter Field Removal
15. Attach the hoist hook to the generator hoisting eye.
Note: The hoist capacity rating should be one-half
2
ton or greater.
16. Remove the two vibromount bolts. See Figure 9-5.
3
17. Raise the alternator end and place a wood block
under the locator plate. Lower the alternator until
the wood block supports the locator plate. See
Figure 9-5.
18. Remove the four overbolts from the end bracket.
See Figure 9-5.
19. Install a sling on the stator housing.See
Figure 9-6.
20. Use a two-jaw puller to pull the end bracket/stator
assembly from the bearing on the rotor shaft. See
Figure 9-6.
1
4
21. Remove the stator assembly from the rotor.
Remove or rotate the fan guard, if necessary, to
clear the vibromounts.
22. Remove the four locknuts and remove the fan and
fan spacer. See Figure 9-7.
23. Remove the six metric bolts to remove the drive
disc/rotor assembly from the engine flywheel. See
Figure 9-7.
24. Clamp the rotor in a soft-jaw vise. Remove the eight
bolts and remove the drive disc assembly from the
rotor. SeeFigure9-8.
9.2Reassembly
1. Clamp the rotor in a soft-jaw vise. Install the drive
disc on the rotor with disc studs facing the rotor.
Tighten the eight bolts to 40 Nm (30 ft. lbs.). See
Figure 9-8.
2. Install the rotor/drive disc assembly on the engine
flywheel using six washers and bolts. Tighten the
bolts to 27 Nm (20 ft. lbs.).
3
1. Sling
2. Fan guard
3. Two-jaw puller
4. End bracket
Figure 9-6 Stator Assembly Removal
1
2
558867
2
3
4
3. Install the fan to the drive disc using four spacers,
washers, and locknuts.
Note: Install the fan with the flange side facing
away from the flywheel. Space the studs so
that they allow the fan installation in one
position only.
4. Inspect the O-ring in the end bracket bearing bore
and replace the O-ring if damaged. Use a sling to
support the stator assembly while installing the
stator over the rotor. Be careful not to damage the
rotor. SeeFigure9-9.
5. Install the four overbolts (the two long bolts in the
lower holes). Check that the alignment marks on
the stator housing and locator plate match. See
Figure 9-10.Tighten the overbolts to 40 Nm
(30 ft. lbs.).
6. Use the hoist to raise the alternator end. Remove
the wood block from under the locator plate. Lower
the generator set and install a bolt, a large washer,
two small washers, and a locknut in each
vibromount. Tighten the mounting bolts to 28 Nm
(20 ft. lbs.).
7. Apply antiseize compound to the keyed end of the
rotor shaft. Bring the rotor leads through the bores
in the armature while installing the armature on the
shaft. Check the keyway of the shaft and key of the
armature for damage.Install the armature
retaining bolt and washer.
8. Use screws and lock washers to install the rotor
leads to the rectifier board at the positive (+) and
negative (--) terminals.
1
1. O-ring
Figure 9-9 Stator Installation
1
5588612
Note: Position the lock washers against the
rectifier board.
9. Install three spacers and bolts to mount the rectifier
board to the armature.
10. Install the exciter field using four bolts and
washers. The field leads are at the top. Connect
the P6, P7, and F1 connectors. See Figure 9-11.
11. Install tie wraps to secure the wires as necessary.
12. Route output leads 1, 2, 3, and 4 through the
bottom of the controller box.Check that the
grommet is intact and there are no sharp edges
exposed that could damage the wiring. Install the
box on the rubber mounts and install the four
locknuts. Connect the leads to the circuit breaker
andneutralstud(LO)asmarkedduring
disassembly.
Note: Check the generator set’s nameplate to
verify the original voltage configuration. See
Section 10,Voltage Reconnectionand
Wiring Diagrams, for more information
regarding voltage reconnection.
13. Connect the P4 (22-pin) connector. Connect the
ground strap using a bolt, washer, and lock washer
(install the lock washer against the ground strap).
14. Install the controller cover.
15. Install the end panel with the louvered openings
down.
16. Reconnect all the external connections—the
exhaust line to the mixing elbow, the fuel line to the
fuel pump filter inlet, the water line to the seawater
pump, the remote start panel to the controller P3
connector, the AC output leads in controller, and
the battery cables to the battery (negative (--) lead
last).
Section 10 Voltage Reconnection and Wiring Diagrams
10.1 Voltage Reconnection
Thefollowinginformationillustratestheproper
reconnection of 4-lead generator sets. In all cases,
follow the National Electrical Code (NEC).
NOTICE
Voltage reconnection. Affix a notice to the generator set after
reconnecting the set to a voltage different from the voltage on
the nameplate. Order voltage reconnection decal 246242
from an authorized service distributor/dealer.
10.1.1 100--120-Volt Configurations
Load
Side
LO (Neutral)
Ground
Factory
2-Pole
or (2) 1-Pole
Circuit Breakers
LO
GRD
L1
L2
Do not connect the load-side terminals of the circuit
breaker together when using a factory 2-pole circuit
breaker. See Figure 10-1. If the installation requires a
100--120-volt, 2-wire system, use a 1-pole circuit
breaker. See Figure 10-2. When connecting stator
phase leads together, size the output lead (L1)
accordingly. Use a jumper lead on the line side of the
circuit breaker to balance the generator set load.
LO (Neutral)
Ground
Load
Side
1-Pole
Circuit
Breaker
Line
Side
LO
GRD
L1
Line
Side
Jumper
Lead
4321
Stator Leads
L0--L1100--120 Volt100--120 Volt
L0--L2100--120 Volt100--120 Volt
100--120 Volt, 3 Wire
60 Hz50 Hz
Figure 10-1 100--120 Volt, 3 Wire
100--120 Volt, 2 Wire
4321
Stator Leads
60 Hz50 Hz
L0--L1100--120 Volt100--120 Volt
L0--L2100--120 Volt100--120 Volt
Figure 10-2 100--120 Volt, 2 Wire
TP-6053 7/0451Section 10 Voltage Reconnection and Wiring Diagrams
Page 64
10.1.2 100--120/200--240-Volt
Configurations
This configuration does not use a jumper lead. If the unit
was originally wired for straight 100--120 volt, 3 wire,
remove the jumperlead (see Figure 10-1 and
Figure 10-2 for location).Select a circuit breaker
manufactured with a 2-pole circuit breaker. Two 1-pole
circuit breakers do not conform to NEC requirements
when supplying a 200--240-volt load. This is true even if
they are mechanically attached together. Since leads
L1 and L2 are different phases, never connect them
together.
LO (Neutral)
LO
Ground
Load
Side
Line
Side
GRD
L2
L1
Factory
2-Pole
Circuit
Breaker
10.1.3 200--240-Volt Configurations
This configuration does not use a jumper lead. If the unit
was originally wired for straight 100--200 volt, 3 wire,
remove the jumperlead (see Figure 10-1 and
Figure 10-2 for location).
LO (Neutral)
Ground
Load
Side
Line
Side
4321
200--220--240 Volt, 2 Wire
1-Pole
Circuit
Breaker
Tape to insulate
from ground
Stator Leads
60 Hz50 Hz
L0--L1not used200--240 Volt
LO
GRD
L1
100--120/200--240 Volt, 3 Wire
4321
Stator Leads
60 Hz50 Hz
L0--L1100--120 Volt100--120 Volt
L0--L2100--120 Volt100--120 Volt
L1--L2200--240 Volt200--240 Volt
Figure 10-3 100--120/200--240 Volt, 3 Wire
Figure 10-4 200--240 Volt, 2 Wire
TP-6053 7/0452 Section 10 Voltage Reconnection and Wiring Diagrams
Page 65
10.2 Marine Manual (Ship-to-Shore) Transfer Switch
Electro Switch
L1
To Generator
Set
L2
L1
To Generator
Set
L2
2-Wire Generator Sets
2134
6578
To Load
To Shore
Power
Kraus Naimler/American Solenoid
(Early Rectangular Design)
2-Wire Generator Sets
1265
348 7
To Shore
Power
L1
L2
To Generator
Set
L0
L1
L2
To Generator
Set
L0
3-Wire Generator Sets
2134
657 8
1091112
To Load
3-Wire Generator Sets
1265
348 7
91014 13
To Shore
Power
To Shore
Power
L1
To Generator
Set
L2
To Load
Kraus Naimler/American Solenoid
(Newer Round Design)
2-Wire Generator Sets
3241
768 5
To Load
To Shore
Power
L1
L2
To Generator
Set
L0
To Load
3-Wire Generator Sets
3241
768 5
1110129
To Load
To Shore
Power
TP-5399-5
TP-6053 7/0453Section 10 Voltage Reconnection and Wiring Diagrams
Page 66
10.3 Wiring Diagram, Schematic
229294-N
TP-6053 7/0454 Section 10 Voltage Reconnection and Wiring Diagrams
Page 67
10.4 Wiring Diagram, Point-to-Point
TP-6053 7/0455Section 10 Voltage Reconnection and Wiring Diagrams
229294-N
Page 68
10.5 Remote Start Panel
+--
P
10-amp
fuse
P
P1-14
P2-3P2-7P2-8P2-9
70
P3-4
J3-4J3-5J3-1J3-6
Violet
47
P2-4
K2
K1
47
P3-5P3-6P3-1
Yellow/
Red
Local
switch
Start
Relay
circuit
board
Grey/
Black
Stop
Start
Stop
43
P2-5P2-6
43
Remote
switch
N
N
N
P1-9
Black
10.6 Remote Start and 2-Meter
Panel
+--
P
10-amp
fuse
P
P1-1447P2-4
K2
K1
P2-3
70
P3-4
Violet
P2-7
47
P3-5P3-6
J3-4J3-5
Yellow/
Red
Local
switch
Start
Relay
circuit
board
Grey/
Black
Stop
Start
Stop
43
P2-5 P2-6
P2-8 P2-9
43
J3-6
Remote
switch
N
N
P3-1
N
P1-9
P4-2P4-3
P3-2
J3-1
Black
W.T.
sender
5
J3-2
Tan
O.P.
sender
7C
P3-3
J3-3
L. Blue
Gen. ON light
TP-5588-7
Gen. ON light
Water temp.
gauge
Oil pressure
gauge
TP-5588-7
TP-6053 7/0456 Section 10 Voltage Reconnection and Wiring Diagrams
Page 69
10.7 Remote Start and 4-Meter
Panel
+--
P
10-amp
fuse
P
P1-14
K2
K1
P2-3
70
P3-4
J3-4J3-5
Violet
Yellow/
Red
Gen. ON light
Water temp.
gauge
47
P2-4
P2-7
47
P3-5
Local
switch
Start
Relay
circuit
board
Grey/
Black
Stop
Start
Stop
P2-8 P2-9
P3-6
43
N
P2-5 P2-6
N
43
P3-1
J3-6
Remote
switch
N
P1-9
W.T.
sender
P4-2P4-3
5
P3-2
J3-1J3-2J3-3
Tan
Black
O.P.
sender
7C
P3-3
L. Blue
Oil pressure
gauge
DC voltmeter
Hourmeter
TP-5588-7
TP-6053 7/0457Section 10 Voltage Reconnection and Wiring Diagrams
Page 70
Notes
TP-6053 7/0458 Section 10 Voltage Reconnection and Wiring Diagrams
Page 71
Appendix A Abbreviations
The following list contains abbreviations that may appear in this publication.
A, ampampere
ABDCafter bottom dead center
ACalternating current
A/Danalog to digital
ADCanalog to digital converter
adj.adjust, adjustment
ADVadvertising dimensional
AHWTanticipatory high water
AISIAmerican Iron and Steel
ALOPanticipatory low oil pressure
alt.alternator
Alaluminum
ANSIAmerican National Standards
AOanticipatory only
APIAmerican Petroleum Institute
approx.approximate, approximately
ARas required, as requested
ASas supplied, as stated, as
ASEAmerican Society of Engineers
ASMEAmerican Society of
assy.assembly
ASTMAmerican Society for Testing
ATDCafter top dead center
ATSautomatic transfer switch
auto.automatic
aux.auxiliary
A/Vaudiovisual
avg.average
AVRautomatic voltage regulator
AWGAmerican Wire Gauge
AWMappliance wiring material
bat.battery
BBDCbefore bottom dead center
BCbattery charger, battery
BCAbattery charging alternator
BCIBattery Council International
BDCbefore dead center
BHPbrake horsepower
blk.black (paint color), block
blk. htr.block heater
BMEPbrake mean effective pressure
bpsbits per second
br.brass
BTDCbefore top dead center
BtuBritish thermal unit
Btu/min.British thermal units per minute
CCelsius, centigrade
cal.calorie
CARBCalifornia Air Resources Board
CBcircuit breaker
cccubic centimeter
CCAcold cranking amps
ccw.counterclockwise
CECCanadian Electrical Code
cert.certificate, certification, certified
cfhcubic feet per hour
drawing
temperature
Institute
Institute
(formerly American Standards
Association, ASA)
suggested
Mechanical Engineers
Materials
charging
(engine)
cfmcubic feet per minute
CGcenter of gravity
CIDcubic inch displacement
CLcenterline
cmcentimeter
CMOScomplementary metal oxide
CTcurrent transformer
Cucopper
cu. in.cubic inch
cw.clockwise
CWCcity water-cooled
cyl.cylinder
D/Adigital to analog
DACdigital to analog converter
dBdecibel
dBAdecibel (A weighted)
DCdirect current
DCRdirect current resistance
deg., °degree
dept.department
dia.diameter
DI/EOdual inlet/end outlet
DINDeutsches Institut fur Normung
DIPdual inline package
DPDTdouble-pole, double-throw
DPSTdouble-pole, single-throw
DSdisconnect switch
DVRdigital voltage regulator
E, emer. emergency (power source)
EDIelectronic data interchange
EFRemergency frequency relay
e.g.for example (exempli gratia)
EGelectronic governor
EGSAElectrical Generating Systems
EPSemergency power system
ERemergency relay
ESengineering special,
ESDelectrostatic discharge
est.estimated
E-Stopemergency stop
etc.et cetera (and so forth)
substrate (semiconductor)
Association
e. V.
(also Deutsche Industrie
Normenausschuss)
Association
Association
Agency
engineered special
exh.exhaust
ext.external
FFahrenheit, female
fglass.fiberglass
FHMflat head machine (screw)
fl. oz.fluid ounce
flex.flexible
freq.frequency
FSfull scale
ft.foot, feet
ft. lb.foot pounds (torque)
ft./min.feet per minute
ggram
ga.gauge (meters, wire size)
gal.gallon
gen.generator
gensetgenerator set
GFIground fault interrupter
GND,
gov.governor
gphgallons per hour
gpmgallons per minute
gr.grade, gross
GRDequipment ground
gr. wt.gross weight
H x W x D height by width by depth
HChex cap
HCHThigh cylinder head temperature
HDheavy duty
HEThigh exhaust temperature,
hexhexagon
Hgmercury (element)
HHhex head
HHChex head cap
HPhorsepower
hr.hour
HSheat shrink
hsg.housing
HVACheating, ventilation, and air
HWThigh water temperature
Hzhertz (cycles per second)
ICintegrated circuit
IDinside diameter, identification
IECInternational Electrotechnical
IEEEInstitute of Electrical and
IMSimproved motor starting
in.inch
in. H
in. Hginches of mercury
in. lb.inch pounds
Inc.incorporated
ind.industrial
int.internal
int./ext.internal/external
I/Oinput/output
IPiron pipe
ISOInternational Organization for
kHzkilohertz
kJkilojoule
kmkilometer
kOhm, kΩ kilo-ohm
kPakilopascal
kphkilometers per hour
kVkilovolt
kVAkilovolt ampere
kVARkilovolt ampere reactive
kWkilowatt
kWhkilowatt-hour
kWmkilowatt mechanical
Lliter
LANlocal area network
L x W x H length by width by height
lb.pound, pounds
3
lbm/ft
pounds mass per cubic feet
LCBline circuit breaker
LCDliquid crystal display
ld. shd.load shed
LEDlight emitting diode
Lphliters per hour
Lpmliters per minute
LOPlow oil pressure
LPliquefied petroleum
LPGliquefied petroleum gas
LSleft side
L
wa
sound power level, A weighted
LWLlow water level
LWTlow water temperature
mmeter, milli (1/1000)
Mmega (10
bytes)
MCMone thousand circular mils
MCCBmolded-case circuit breaker
meggarmegohmmeter
MHzmegahertz
mi.mile
milone one-thousandth of an inch
min.minimum, minute
misc.miscellaneous
MJmegajoule
mJmillijoule
mmmillimeter
mOhm, mΩ
milliohm
MOhm, MΩ
megohm
MOVmetal oxide varistor
MPamegapascal
mpgmiles per gallon
mphmiles per hour
MSmilitary standard
m/sec.meters per second
MTBFmean time between failure
MTBOmean time between overhauls
mtg.mounting
MWmegawatt
mWmilliwatt
µFmicrofarad
N, norm. normal (power source)
NAnot available, not applicable
nat. gasnatural gas
NBSNational Bureau of Standards
NCnormally closed
NECNational Electrical Code
NEMANational Electrical
Manufacturers Association
NFPANational Fire Protection
Association
Nmnewton meter
NOnormally open
no., nos. number, numbers
NPSNational Pipe, Straight
NPSCNational Pipe, Straight-coupling
NPTNational Standard taper pipe
thread per general use
NPTFNational Pipe, Taper-Fine
NRnot required, normal relay
nsnanosecond
OCovercrank
ODoutside diameter
OEMoriginal equipment
manufacturer
OFoverfrequency
opt.option, optional
OSoversize, overspeed
OSHAOccupational Safety and Health
Administration
OVovervoltage
oz.ounce
p., pp.page, pages
PCpersonal computer
PCBprinted circuit board
pFpicofarad
PFpower factor
ph., ∅phase
PHCPhillips head crimptite (screw)
PHHPhillips hex head (screw)
PHMpan head machine (screw)
PLCprogrammable logic control
PMGpermanent-magnet generator
potpotentiometer, potential
ppmparts per million
PROMprogrammable read-only
memory
psipounds per square inch
pt.pint
PTCpositive temperature coefficient
PTOpower takeoff
PVCpolyvinyl chloride
qt.quart, quarts
qty.quantity
Rreplacement (emergency)
power source
rad.radiator, radius
RAMrandom access memory
RDOrelay driver output
ref.reference
rem.remote
Res/Coml Residential/Commercial
RFIradio frequency interference
RHround head
RHMround head machine (screw)
rly.relay
rmsroot mean square
rnd.round
ROMread only memory
rot.rotate, rotating
rpmrevolutions per minute
RSright side
RTVroom temperature vulcanization
SAESociety of Automotive
Engineers
scfmstandard cubic feet per minute
SCRsilicon controlled rectifier
s, sec.second
SISysteme international d’unites,
International System of Units
SI/EOside in/end out
sil.silencer
SNserial number
SPDTsingle--pole, double--throw
SPSTsingle--pole, single--throw
spec, specs
specification(s)
sq.square
sq. cmsquare centimeter
sq. in.square inch
SSstainless steel
std.standard
stl.steel
tach.tachometer
TDtime delay
TDCtop dead center
TDECtime delay engine cooldown
TDENtime delay emergency to
normal
TDEStime delay engine start
TDNEtime delay normal to
emergency
TDOEtime delay off to emergency
TDONtime delay off to normal
temp.temperature
term.terminal
TIFtelephone influence factor
TIRtotal indicator reading
tol.tolerance
turbo.turbocharger
typ.typical (same in multiple
locations)
UFunderfrequency
UHFultrahigh frequency
ULUnderwriter’s Laboratories, Inc.
UNCunified coarse thread (was NC)
UNFunified fine thread (was NF)
univ.universal
USundersize, underspeed
UVultraviolet, undervoltage
Vvolt
VACvolts alternating current
VARvoltampere reactive
VDCvolts direct current
VFDvacuum fluorescent display
VGAvideo graphics adapter
VHFvery high frequency
Wwatt
WCRwithstand and closing rating
w/with
w/owithout
wt.weight
xfmrtransformer
TP-6053 7/04A-2 Appendix
Page 73
Appendix B Common Hardware Application Guidelines
Use the information below and on the following pages to
identify proper fastening techniques when no specific
reference for reassembly is made.
Bolt/Screw Length: When bolt/screw length is not given,
use Figure 1 as a guide. As a general rule, a minimum
length of one thread beyond the nut and a maximum
length of 1/2 the bolt/screw diameter beyond the nut is
the preferred method.
Washers and Nuts: Use split lock washers as a bolt
locking device where specified. Use SAE flat washers
with whiz nuts, spiralock nuts, or standard nuts and
preloading (torque) of the bolt in all other applications.
See Appendix C, General Torque Specifications, and
other torque specifications in the service literature.
For round and slotted exit holes, determine if
hardware is greater than 1/2 inch in diameter, or
1/2 inch in diameter or less.Hardware that is
greater than 1/2 inch in diameter takes a standard
nut and SAE washer. Hardware 1/2 inch or less in
diameter can take a properly torqued whiz nut or
spiralock nut. See Figure 2.
3. Follow these SAE washer rules after determining
exit hole type:
a. Always use a washer between hardware and a
slot.
b. Always use a washer under a nut (see 2 above
for exception).
c. Use a washer under a bolt when the female
thread is fixed (weld nut).
Unacceptable Nut/Bolt Clearance
3
1. 1/2 of bolt diameter
2. Min. 1 full thread beyond top of nut
3. Below top of nut
Figure 1Acceptable Bolt Lengths
G-585
4. Refer to Figure 2, which depicts the preceding
hardware configuration possibilities.
1
6
1. Cap screw
2. Entry hole types
3. Standard nut and SAE washer
4. Whiz nut or spiralock: up to 1/2 in. dia. hardware
5. Weld nuts: above 1/2 in. dia. hardware
6. Exit hole types
2
3
5
4
G-585
TP-6053 7/04Appendix A-3
Figure 2Acceptable Hardware Combinations
Page 74
Appendix C General Torque Specifications
T
A
lumi
A
Use the following torque specifications when service
literature instructions give no specific torque values.
The charts list values for new plated, zinc phosphate, or
oiled threads. Increase values by 15% for nonplated
threads. All torque values are +0%/--10%.
Assembled into
num
Grade2or5
Metric Fasteners Torque Specifications, Measured in Nm (ft. lb.)
Size (mm)
M6 x 1.005.6(4)9.9(7)14.0(10)5.6(4)
M8 x 1.2513.6(10)25.0(18)35.0(26)13.6 (10)
M8 x 1.0021.0(16)25.0(18)35.0(26)21.0 (16)
M10 x 1.5027.0(20)49.0(35)68.0(50)27.0 (20)
M10 x 1.2539.0(29)49.0(35)68.0(50)39.0 (29)
M12 x 1.7547.0(35)83.0(61)117.0(86)—
M12 x 1.5065.0(48)88.0(65)125.0(92)—
M14 x 2.0074.0(55)132.0(97)185.0 (136)—
M14 x 1.50100.0(74)140.0 (103)192.0 (142)—
M16 x 2.00115.0(85)200.0 (148)285.0 (210)—
M16 x 1.50141.0 (104)210.0 (155)295.0 (218)—
M18 x 2.50155.0 (114)275.0 (203)390.0 (288)—
M18 x 1.50196.0 (145)305.0 (225)425.0 (315)—
Assembled into Cast Iron or Steel
Grade 5.8Grade 8.8Grade 10.9
Assembled into
luminum
Grade 5.8 or 8.8
TP-6053 7/04A-4 Appendix
Page 75
Appendix D Common Hardware Identification
Screw/Bolts/Studs
Head Styles
Hex Head or Machine Head
Hex Head or Machine Head
with Washer
Flat Head (FHM)
Round Head (RHM)
Pan Head
Hex Socket Head Cap or
Allent Head Cap
Hex Socket Head or Allent
Head Shoulder Bolt
Sheet Metal Screw
Stud
Drive Styles
Hex
Hex and Slotted
Phillipsr
Nuts
Nut Styles
Hex Head
Lock or Elastic
Square
Cap or Acorn
Wing
Washers
Washer Styles
Plain
Split Lock or Spring
Spring or Wave
External Tooth Lock
Internal Tooth Lock
Internal-External Tooth Lock
Hardness Grades
American Standard
Grade 2
Grade 5
Grade 8
Grade 8/9 (Hex Socket
Head)
Metric
Number stamped on
hardware; 5.8 shown
5.8
Slotted
Hex Socket
Allent head screw is a trademark of Holo-Krome Co.
Phillipsr screw is a registered trademark of Phillips Screw Company.
Sample Dimensions
American Standard (Screws, Bolts, Studs, and Nuts)
1/4-20 x 1
Metric (Screws, Bolts, Studs, and Nuts)
M8-1.25 x 20
Length In Inches (Screws and Bolts)
Threads Per Inch
Major Thread Diameter In Fractional Inches Or Screw Number Size
Length In Millimeters (Screws and Bolts)
Distance Between Threads In Millimeters
Major Thread Diameter In Millimeters
Plain Washers
9/32
x5/8x 1/16
Lock Washers
5/8
Thickness
External Dimension
Internal Dimension
Internal Dimension
TP-6053 7/04Appendix A-5
Page 76
Appendix E Common Hardware List
The Common Hardware List lists part numbers and dimensions for common hardware items.
American Standard
Part No.Dimensions
Hex Head Bolts (Grade 5)
X-465-171/4-20 x .38
X-465-61/4-20 x .50
X-465-21/4-20 x .62
X-465-161/4-20 x .75
X-465-181/4-20 x .88
X-465-71/4-20 x 1.00
X-465-81/4-20 x 1.25
X-465-91/4-20 x 1.50
X-465-101/4-20 x 1.75
X-465-111/4-20 x 2.00
X-465-121/4-20 x 2.25
X-465-141/4-20 x 2.75
X-465-211/4-20 x 5.00
X-465-251/4-28 x .38
X-465-201/4-28 x 1.00
X-125-335/16-18 x .50
X-125-235/16-18 x .62
X-125-35/16-18 x .75
X-125-315/16-18 x .88
X-125-55/16-18 x 1.00
X-125-245/16-18 x 1.25
X-125-345/16-18 x 1.50
X-125-255/16-18 x 1.75
X-125-265/16-18 x 2.00
2305785/16-18 x 2.25
X-125-295/16-18 x 2.50
X-125-275/16-18 x 2.75
X-125-285/16-18 x 3.00
X-125-225/16-18 x 4.50
X-125-325/16-18 x 5.00
X-125-355/16-18 x 5.50
X-125-365/16-18 x 6.00
X-125-405/16-18 x 6.50
X-125-435/16-24 x 1.75
X-125-445/16-24 x 2.50
X-125-305/16-24 x .75
X-125-395/16-24 x 2.00
X-125-385/16-24 x 2.75
X-6238-23/8-16 x .62
X-6238-103/8-16 x .75
X-6238-33/8-16 x .88
X-6238-113/8-16 x 1.00
X-6238-43/8-16 x 1.25
X-6238-53/8-16 x 1.50
X-6238-13/8-16 x 1.75
X-6238-63/8-16 x 2.00
X-6238-173/8-16 x 2.25
X-6238-73/8-16 x 2.50
X-6238-83/8-16 x 2.75
X-6238-93/8-16 x 3.00
X-6238-193/8-16 x 3.25
X-6238-123/8-16 x 3.50
X-6238-203/8-16 x 3.75
X-6238-133/8-16 x 4.50
X-6238-183/8-16 x 5.50
X-6238-253/8-16 x 6.50
Part No.Dimensions
Hex Head Bolts, cont.
X-6238-143/8-24 x .75
X-6238-163/8-24 x 1.25
X-6238-213/8-24 x 4.00
X-6238-223/8-24 x 4.50
X-6024-57/16-14 x .75
X-6024-27/16-14 x 1.00
X-6024-87/16-14 x 1.25
X-6024-37/16-14 x 1.50
X-6024-47/16-14 x 2.00
X-6024-117/16-14 x 2.75
X-6024-127/16-14 x 6.50
X-129-151/2-13 x .75
X-129-171/2-13 x 1.00
X-129-181/2-13 x 1.25
X-129-191/2-13 x 1.50
X-129-201/2-13 x 1.75
X-129-211/2-13 x 2.00
X-129-221/2-13 x 2.25
X-129-231/2-13 x 2.50
X-129-241/2-13 x 2.75
X-129-251/2-13 x 3.00
X-129-271/2-13 x 3.50
X-129-291/2-13 x 4.00
X-129-301/2-13 x 4.50
X-463-91/2-13 x 5.50
X-129-441/2-13 x 6.00
X-129-511/2-20 x .75
X-129-451/2-20 x 1.25
X-129-521/2-20 x 1.50
X-6021-35/8-11 x 1.00
X-6021-45/8-11 x 1.25
X-6021-25/8-11 x 1.50
X-6021-15/8-11 x 1.75
2730495/8-11 x 2.00
X-6021-55/8-11 x 2.25
X-6021-65/8-11 x 2.50
X-6021-75/8-11 x 2.75
X-6021-125/8-11 x 3.75
X-6021-115/8-11 x 4.50
X-6021-105/8-11 x 6.00
X-6021-95/8-18 x 2.50
X-6239-13/4-10 x 1.00
X-6239-83/4-10 x 1.25
X-6239-23/4-10 x 1.50
X-6239-33/4-10 x 2.00
X-6239-43/4-10 x 2.50
X-6239-53/4-10 x 3.00
X-6239-63/4-10 x 3.50
X-792-11-8 x 2.25
X-792-51-8 x 3.00
X-792-81-8 x 5.00
Hex head bolts are hardness grade 8.8 unless noted.
Part No.Dimensions
Hex Head Bolts (Partial Thread)
M931-05055-60M5-0.80 x 55
M931-06040-60M6-1.00 x 40
M931-06055-60M6-1.00 x 55
M931-06060-60M6-1.00 x 60
M931-06060-SSM6-1.00 x 60
M931-06070-60M6-1.00 x 70
M931-06070-SSM6-1.00 x 70
M931-06075-60M6-1.00 x 75
M931-06090-60M6-1.00 x 90
M931-06145-60M6-1.00 x 145
M931-06150-60M6-1.00 x 150
M931-08035-60M8-1.25 x 35
M931-08040-60M8-1.25 x 40
M931-08045-60M8-1.25 x 45
M931-08050-60M8-1.25 x 50
M931-08055-60M8-1.25 x 55
M931-08055-82M8-1.25 x 55*
M931-08060-60M8-1.25 x 60
M931-08070-60M8-1.25 x 70
M931-08070-82M8-1.25 x 70*
M931-08075-60M8-1.25 x 75
M931-08080-60M8-1.25 x 80
M931-08090-60M8-1.25 x 90
M931-08095-60M8-1.25 x 95
M931-08100-60M8-1.25 x 100
M931-08110-60M8-1.25 x 110
M931-08120-60M8-1.25 x 120
M931-08130-60M8-1.25 x 130
M931-08140-60M8-1.25 x 140
M931-08150-60M8-1.25 x 150
M931-08200-60M8-1.25 x 200
M931-10040-82M10-1.25 x 40*
M931-10040-60M10-1.50 x 40
M931-10045-60M10-1.50 x 45
M931-10050-60M10-1.50 x 50
M931-10050-82M10-1.25 x 50*
M931-10055-60M10-1.50 x 55
M931-10060-60M10-1.50 x 60
M931-10065-60M10-1.50 x 65
M931-10070-60M10-1.50 x 70
M931-10080-60M10-1.50 x 80
M931-10080-82M10-1.25 x 80*
M931-10090-60M10-1.50 x 90
M931-10090-82M10-1.50 x 90*
M931-10100-60M10-1.50 x 100
M931-10110-60M10-1.50 x 110
M931-10120-60M10-1.50 x 120
M931-10130-60M10-1.50 x 130
M931-10140-60M10-1.50 x 140
M931-10180-60M10-1.50 x 180
M931-10235-60M10-1.50 x 235
M931-10260-60M10-1.50 x 260
M960-10330-60M10-1.25 x 330
M931-12045-60M12-1.75 x 45
M960-12050-60M12-1.25 x 50
M960-12050-82M12-1.25 x 50*
M931-12050-60M12-1.75 x 50
M931-12050-82M12-1.75 x 50*
M931-12055-60M12-1.75 x 55
M931-12060-60M12-1.75 x 60
M931-12060-82M12-1.75 x 60*
M931-12065-60M12-1.75 x 65
M931-12075-60M12-1.75 x 75
M931-12080-60M12-1.75 x 80
M931-12090-60M12-1.75 x 90
M931-12100-60M12-1.75 x 100
M931-12110-60M12-1.75 x 110
Part No.Dimensions
Hex Head Bolts (Partial Thread),
continued
M960-16090-60M16-1.50 x 90
M931-16090-60M16-2.00 x 90
M931-16100-60M16-2.00 x 100
M931-16100-82M16-2.00 x 100*
M931-16120-60M16-2.00 x 120
M931-16150-60M16-2.00 x 150
M931-20065-60M20-2.50 x 65
M931-20090-60M20-2.50 x 90
M931-20100-60M20-2.50 x 100
M931-20120-60M20-2.50 x 120
M931-20140-60M20-2.50 x 140
M931-20160-60M20-2.50 x 160
M931-22090-60M22-2.50 x 90
M931-22120-60M22-2.50 x 120
M931-22160-60M22-2.50 x 160
M931-24090-60M24-3.00 x 90
M931-24120-60M24-3.00 x 120
M931-24160-60M24-3.00 x 160
M931-24200-60M24-3.00 x 200
Hex Head Bolts (Full Thread)
M933-04006-60M4-0.70 x 6
M933-05030-60M5-0.80 x 30
M933-05035-60M5-0.80 x 35
M933-05050-60M5-0.80 x 50
M933-06010-60M6-1.00 x 10
M933-06012-60M6-1.00 x 12
M933-06014-60M6-1.00 x 14
M933-06016-60M6-1.00 x 16
M933-06020-60M6-1.00 x 20
M933-06025-60M6-1.00 x 25
M933-06030-60M6-1.00 x 30
M933-06040-60M6-1.00 x 40
M933-06050-60M6-1.00 x 50
M933-07025-60M7-1.00 x 25
M933-08010-60M8-1.25 x 10
M933-08012-60M8-1.25 x 12
M933-08016-60M8-1.25 x 16
M933-08020-60M8-1.25 x 20
M933-08025-60M8-1.25 x 25
M933-08030-60M8-1.25 x 30
M933-08030-82M8-1.25 x 30*
M933-10012-60M10-1.50 x 12
M961-10020-60M10-1.25 x 20
M933-10020-60M10-1.50 x 20
M933-10025-60M10-1.50 x 25
M961-10025-60M10-1.25 x 25
M933-10025-82M10-1.50 x 25*
M961-10030-60M10-1.25 x 30
M933-10030-60M10-1.50 x 30
M933-10030-82M10-1.50 x 30*
M961-10035-60M10-1.25 x 35
M933-10035-60M10-1.50 x 35
M933-10035-82M10-1.50 x 35*
M961-10040-60M10-1.25 x 40
Part No.Dimensions
Hex Head Bolts (Full Thread),
continued
M933-12016-60M12-1.75 x 16
M933-12020-60M12-1.75 x 20
M961-12020-60FM12-1.50 x 20
M933-12025-60M12-1.75 x 25
M933-12025-82M12-1.75 x 25*
M961-12030-60M12-1.25 x 30
M933-12030-82M12-1.75 x 30*
M961-12030-82FM12-1.50 x 30*
M933-12030-60M12-1.75 x 30
M933-12035-60M12-1.75 x 35
M961-12040-82M12-1.25 x 40*
M933-12040-60M12-1.75 x 40
M933-12040-82M12-1.75 x 40*
M961-14025-60M14-1.50 x 25
M933-14025-60M14-2.00 x 25
M961-14050-82M14-1.50 x 50*
M961-16025-60M16-1.50 x 25
M933-16025-60M16-2.00 x 25
M961-16030-82M16-1.50 x 30*
M933-16030-82M16-2.00 x 30*
M933-16035-60M16-2.00 x 35
M961-16040-60M16-1.50 x 40
M933-16040-60M16-2.00 x 40
M961-16045-82M16-1.50 x 45*
M933-16045-82M16-2.00 x 45*
M933-16050-60M16-2.00 x 50
M933-16050-82M16-2.00 x 50*
M933-16060-60M16-2.00 x 60
M933-16070-60M16-2.00 x 70
M933-18035-60M18-2.50 x 35
M933-18050-60M18-2.50 x 50
M933-18060-60M18-2.50 x 60
M933-20050-60M20-2.50 x 50
M933-20055-60M20-2.50 x 55
M933-24060-60M24-3.00 x 60
M933-24065-60M24-3.00 x 65
M933-24070-60M24-3.00 x 70
Pan Head Machine Screws
M7985A-03010-20 M3-0.50 x 10
M7985A-03012-20 M3-0.50 x 12
M7985A-04010-20 M4-0.70 x 10
M7985A-04016-20 M4-0.70 x 16
M7985A-04020-20 M4-0.70 x 20
M7985A-04050-20 M4-0.70 x 50
M7985A-04100-20 M4-0.70 x 100
M7985A-05010-20 M5-0.80 x 10
M7985A-05012-20 M5-0.80 x 12
M7985A-05016-20 M5-0.80 x 16
M7985A-05020-20 M5-0.80 x 20
M7985A-05025-20 M5-0.80 x 25
M7985A-05030-20 M5-0.80 x 30
M7985A-05080-20 M5-0.80 x 80
M7985A-05100-20 M5-0.80 x 100
M7985A-06100-20 M6-1.00 x 100
Flat Head Machine Screws
M965A-04012-SS M4-0.70 x 12
M965A-05012-SS M5-0.80 x 12
M965A-05016-20M5-0.80 x 16
M965A-06012-20M6-1.00 x 12
E 2000 and 2004 by Kohler Co. All rights reserved.
KOHLER CO. Kohler, Wisconsin 53044
Phone 920-565-3381, Fax 920-459-1646
For the nearest sales/service outlet in the
US and Canada, phone 1-800-544-2444
KohlerPowerSystems.com
Kohler Power Systems
Asia Pacific Headquarters
7 Jurong Pier Road
Singapore 619159
Phone (65)6264-6422, Fax (65)6264-6455
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.