IMPORTANTSAFETY
INSTRUCTIONS. Electromechanical
equipment, including generator sets,
transfer switches, switchgear, and
accessories, can cause bodily harm
and pose life-threatening danger when
improperly installed, operated, or
maintained. To prevent accidents be
aware of potential dangers and act
safely.Read and follow all safety
precautions and instructions. SAVE
THESE INSTRUCTIONS.
This manual hasseveral types ofsafety
precautions and instructions: Danger,
Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a
hazard that will cause severe
personal injury,death,orsubstantial
property damage.
WARNING
Warning indicates the presence of a
hazard that can cause severe
personal injury,death, or substantial
property damage.
Accidental Starting
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disablingthegeneratorset.
Accidental startingcancause
severe injury or death.Before
working on the generator set or
equipment connected to the set,
disable the generator set as follows:
(1) Disconnect the power to the battery
charger, if equipped. (2) Remove the
battery cables, negative (-- ) lead first.
Reconnect the negative (--) lead last
when reconnecting the battery. Follow
these precautions to prevent the
starting of the generator set by the
remote start/stop switch.
Battery electrolyte is a diluted
sulfuric acid. Battery acid can cause
severe injury or death. Battery acid
can cause blindness and burn skin.
Alwayswearsplashproof safety
goggles, rubber gloves, and boots
when servicing the battery. Do not
open a sealed battery or mutilate the
battery case. If battery acid splashes in
the eyes or on the skin, immediately
flush the affected area for 15 minutes
with large quantities of clean water.
Seek immediate medical aid in the case
of eye contact. Never add acid to a
battery after placing the battery in
service, as this may result in hazardous
spattering of battery acid.
Battery acid cleanup. Battery acid
can cause severe injury or death.
Battery acid is electrically conductive
and corrosive. Add 500 g (1 lb.) of
bicarbonate of soda (baking soda) to a
containerwith4L(1gal.)ofwaterand
mix the neutralizing solution. Pour the
neutralizing solution on the spilled
battery acid and continue to add the
neutralizing solution to the spilled
battery acid until all evidence of a
chemical reaction(foaming) has
ceased. Flush the resulting liquid with
water and dry the area.
CAUTION
Caution indicates the presence of a
hazard that will or can cause minorpersonal injury or property damage.
NOTICE
Noticecommunicatesinstallation,
operation, or maintenance information
that is safety related but not hazard
related.
Safety decals affixed to the equipment
in prominent places alert the operator
or service technician to potential
hazards and explain how to act safely.
The decals are shown throughout this
publicationtoimproveoperator
recognition.Replace missing or
damaged decals.
Battery
WARNING
Sulfuric acid in batteries.
Can cause severe injury or death.
Wearprotectivegogglesand
clothing. Battery acid may cause
blindness and burn skin.
Battery gases. Explosion can cause
severe injury or death. Battery gases
can cause an explosion. Do not smoke
or permit flamesor sparks to occur near
a battery at any time, particularly when
it is charging. Do not dispose of a
battery in a fire. To prevent burns and
sparks that could cause an explosion,
avoid touching the battery terminals
with tools or other metal objects.
Remove wristwatch, rings, and other
jewelry before servicing the equipment.
Discharge static electricity from your
body before touching batteries by first
touching a grounded metal surface
away from the battery. To avoid sparks,
do not disturb the battery charger
connections while the battery is
charging.Always turn the battery
charger off before disconnecting the
battery connections.Ventilate the
compartments containing batteries to
prevent accumulation of explosive
gases.
TP-6079 3/00Safety Precautions and Instructions I
Page 4
Battery short circuits. Explosion
can cause severe injury or death.
Short circuits can cause bodily injury
and/orequipmentdamage.
Disconnectthebatterybefore
generatorsetinstallationor
maintenance.Remove wristwatch,
rings, and other jewelry before
servicingthe equipment. Use tools with
insulated handles.Remove the
negative(--)leadfirstwhen
disconnecting the battery. Reconnect
the negative (-- ) lead last when
reconnecting the battery.Never
connect the negative (--) battery cable
to the positive (+) connection terminal
of the starter solenoid. Do not test the
battery condition by shorting the
terminals together.
Engine Backfire/Flash
Fire
WARNING
Fire.
Can cause severe injury or death.
Do not smoke or permit flames or
sparks near fuels or the fuel system.
Servicing the air cleaner. A sudden
backfire can cause severe injury or
death. Do not operate the generator
set with the air cleaner removed.
Servicing the fuel system. A flash
fire can cause severe injury or death.
Do not smoke or permit flames or
sparks near the carburetor, fuel line,
fuel filter, fuel pump, or other potential
sources of spilled fuels or fuel vapors.
Catch fuels in an approved container
when removing the fuel line or
carburetor.
Combustible materials. A fire can
cause severe injury or death.
Generator set engine fuels and fuel
vapors are flammable and explosive.
Handle these materials carefully to
minimize the risk of fire or explosion.
Equip the compartment or nearby area
with a fully charged fire extinguisher.
Select a fire extinguisher rated ABC or
BCforelectricalfiresoras
recommended by the local fire code or
an authorized agency.Train all
personnelonfireextinguisher
operationandfireprevention
procedures.
Exhaust System
WARNING
Carbon monoxide.
Can cause severe nausea, fainting,
or death.
The exhaust system must be
leakproof and routinely inspected.
Generator set operation.Carbon
monoxide can cause severe nausea,
fainting, or death. Carbon monoxide
is an odorless, colorless, tasteless,
nonirritating gas that can cause death if
inhaled for even a short time. Avoid
breathingexhaust fumes when working
on or near the generator set. Never
operate the generator set inside a
building unless the exhaust gas is
piped safely outside. Never operate
the generator set where exhaust gas
could accumulate and seep back inside
a potentially occupied building or
vehicle. Do not obstruct the exhaust
outlet when parking your vehicle. The
exhaust gases must discharge freely to
preventcarbonmonoxidefrom
deflecting into the vehicle.
Carbonmonoxidesymptoms.
Carbon monoxide can cause severe
nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in
exhaust gases.Carbon monoxide
poisoning symptoms include but are
not limited to the following:
D Light-headedness, dizziness
D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms
and carbon monoxide poisoning is
possible, seek fresh air immediately
and remain active. Do not sit, lie down,
or fall asleep.Alert others to the
possibilityofcarbonmonoxide
poisoning. Seek medical attentionifthe
condition of affected persons does not
improve within minutes of breathing
fresh air.
Installing the exhaust tail pipe.
Carbon monoxide can cause severe
nausea, fainting, or death. Install the
exhaust system tail pipe to prevent the
drawing of discharged exhaust gases
into the vehicle interior through
windows, doors, air conditioners, and
other openings. Do not use flexible tail
piping because it could crack and allow
lethal exhaust fumes to enter the
vehicle.
Inspecting the exhaust system.
Carbon monoxide can cause severe
nausea, fainting, or death. For the
safetyof the vehicle’s occupants, install
a carbon monoxide detector. Consult
the coach builder or dealer for
approveddetectorlocationand
installation. Inspectthe detector before
each generator set use. In addition to
routine exhaust system inspection, test
the carbon monoxide detector per the
manufacturer’s instructions and keep
the detector operational at all times.
II Safety Precautions and InstructionsTP-6079 3/00
Page 5
Fuel System
Hazardous Noise
WARNING
WARNING
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.
The fuel system.Explosive fuel
vapors can cause severe injury or
death.Vaporized fuels are highly
explosive. Use extreme care when
handling and storing fuels. Store fuels
in a well-ventilated area away from
spark-producing equipment and out of
the reach of children. Never add fuel to
the tank while the engine is running
because spilled fuel may ignite on
contact with hot parts or from sparks.
Do not smoke or permit flames or
sparks to occur near sources of spilled
fuel or fuel vapors. Keep the fuel lines
and connections tight and in good
condition. Do not replace flexible fuel
lines with rigid lines.Use flexible
sections to avoid fuel line breakage
caused by vibration. Do not operate the
generator set in the presence of fuel
leaks, fuel accumulation, or sparks.
Repair fuel systems before resuming
generator set operation.
Explosive fuel vapors can cause
severe injury or death.Ta k e
additional precautions when using the
following fuels:
Gasoline—Store gasoline only in
approvedredcontainersclearly
marked GASOLINE.
Draining the fuel system. Explosive
fuel vapors can cause severe injury
or death. Spilled fuel can cause an
explosion. Use a container to catch fuel
when draining the fuel system. Wipe up
spilled fuel after draining the system.
CAUTION
Hazardous noise.
Can cause hearing loss.
Never operate the generator set
without a muffler or with a faulty
exhaust system.
Engine noise. Hazardous noise can
cause hearing loss. Generator sets
not equipped with sound enclosures
can produce noise levels greater than
105 dBA. Prolonged exposure to noise
levels greater than 85 dBA can cause
permanent hearing loss. Wear hearing
protection when near an operating
generator set.
Hazardous
V oltage/Electrical
Shock
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
Moving rotor.
Hazardous voltage.
Backfeed to the utility system can
cause severe injury, death, or
property damage.
Connect the generator set to the
building’s electrical system only
throughan approved device and after
the building’s main switch is opened.
Grounding electrical equipment.
Hazardousvoltagecancause
severe injury or death. Electrocution
is possible whenever electricity is
present.Open the main circuit
breakers of all power sources before
servicing the equipment. Configure the
installation to electrically ground the
generator set, transfer switch, and
related equipmentandelectrical
circuits to comply with applicable codes
andstandards.Never contact
electrical leads or appliances when
standing in water or on wet ground
because these conditions increase the
risk of electrocution.
Shortcircuits.Hazardous
voltage/current can cause severe
injury or death. Short circuits can
cause bodily injury and/or equipment
damage.Do not contact electrical
connections with tools or jewelry while
makingadjustmentsorrepairs.
Remove wristwatch, rings, and jewelry
before servicing the equipment.
Testingthevoltageregulator.
Hazardousvoltagecancause
severe injury or death. High voltage is
present at the voltage regulator heat
sink. To prevent electrical shock do not
touch the voltage regulator heat sink
when testing the voltage regulator.
(PowerBoostt, PowerBoostt III, and
PowerBoostt Vvoltageregulator
models only)
TP-6079 3/00Safety Precautions and Instructions III
Page 6
Electrical backfeed to the utility.
Hazardous backfeed voltage can
cause severe injury or death.
Connect the generator set to the
building/campground electrical system
only through an approved device and
after the building/campground main
switchisopened.Backfeed
connections can cause serious injury
or death to utility personnel working on
power lines and/or personnel near the
work area. Some states and localities
prohibit unauthorized connection to the
utility electrical system.Install a
transferswitchtoprevent
interconnection of the generator set
power and other sources of power.
Testingliveelectrical circuits.
Hazardous voltage or current can
cause severe injury or death. Have
trained and qualified personnel take
diagnostic measurementsof live
circuits.Use adequately rated test
equipment with electrically insulated
probes and follow the instructions of the
test equipment manufacturer when
performing voltage tests. Observe the
following precautions when performing
voltage tests:(1) Remove rings,
wristwatch, and jewelry. (2) Stand on a
dry, approved electrically insulated
mat. (3) Do not touch the enclosure or
components inside the enclosure. (4)
Be prepared for the system to operate
automatically.
(600 volts and under)
Hot Parts
Servicing the exhaust system. Hot
parts can cause severe injury or
death. Do not touch hot engine parts.
The engine and exhaust system
components become extremely hot
during operation.
Combustible materials.Fire can
cause severe injury or death. A hot
exhaust system can ignite adjacent
combustible materials. Do not locate
electricalwiring,fuellines,or
combustible materials above the
exhaust muffler.Exercise caution
when parking your vehicle to prevent
the exhaust system and hot exhaust
gases from starting grass fires.
Combustible materials.Fire can
cause severe injury or death. A hot
generator set can ignite debris in the
compartment. Keep the compartment
and generator set clean and free of
debris and combustible materials to
minimize the possibility of fire. Do not
block the fuel/oil drain opening in the
generator set mounting tray. Cut a
corresponding hole in the subfloor, if
used, for the drain opening.
Moving Parts
WARNING
Hazardous voltage.
Can cause severe injury or death.
Moving rotor.
WARNING
Rotating parts.
Can cause severe injury or death.
Operate the generator set only when
all guards, screens, and covers are in
place.
Tightening the hardware.Flying
projectiles can cause severe injury
or death. Loose hardware can cause
the hardware or pulley to release from
the generator set engine and can
cause personal injury. Retorque all
crankshaft and rotor hardware after
servicing. Do not loosen the crankshaft
hardware or rotor thrubolt when making
adjustments or servicing the generator
set. Rotate the crankshaft manually in
a clockwise direction only. Turning the
crankshaft bolt or rotor thrubolt
counterclockwise can loosen the
hardware.
Servicing the generator set when it is
operating. Exposed moving parts
can cause severe injury or death.
Keep hands, feet, hair, clothing, and
test leads away from the belts and
pulleys when the generator set is
running. Replace guards, screens, and
covers before operating the generator
set.
WARNING
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
IV Safety Precautions and InstructionsTP-6079 3/00
Operate the generator set only when
all guards and electrical enclosures
areinplace.
Page 7
Notice
NOTICE
This generator set has been
rewired from its nameplatevoltage
to
246242
NOTICE
Voltage reconnection. Affix a notice
to the generator set after reconnecting
the set to a voltage different from the
voltage on the nameplate.Order
voltage reconnection decal 246242
fromanauthorizedservice
distributor/dealer.
NOTICE
Hardware damage. The engine and
generator set may use both American
Standard and metric hardware. Use
the correct size tools to prevent
rounding of the bolt heads and nuts.
NOTICE
When replacing hardware, do not
substitutewithinferiorgrade
hardware.Screws and nuts are
available in different hardness ratings.
Toindicatehardness,American
Standard hardware uses a series of
markings, and metric hardware uses a
numeric system. Check the markings
on the bolt heads and nuts for
identification.
NOTICE
Canadian installations only.For
standby service connect the output of
the generator set to a suitably rated
transfer switch in accordance with
Canadian Electrical Code, Part 1.
NOTICE
This generator set does not comply
with United States Coast Guard
(USCG) requirements and must not
be used for marine applications. For
marine installations use only generator
sets specified for marine use. USCG
Regulation 33CFR183 requires that a
generator setmustbeignition
protectedwhenusedina
gasoline-fueled environment.
TP-6079 3/00Safety Precautions and Instructions V
Page 8
Notes
VI Safety Precautions and InstructionsTP-6079 3/00
Page 9
Introduction
This manual provides troubleshooting and repair
instructions for 5ERKM and 4EFRKM model generator
sets, controllers, and accessories.
Refer to the engine service manual for generator set
engine service information.
This manual may be used for models not listed on the
front cover.
Information in this publication represents data available
at the time of print. Kohler Co. reserves the right to
change this publication and the products represented
without notice and without any obligation or liability
whatsoever.
Read this manual and carefully follow all procedures
and safety precautions to ensure proper equipment
operation and to avoid bodily injury. Read and follow the
Safety Precautions and Instructions section at the
beginning of this manual. Keep this manual with the
equipment for future reference.
The equipment service requirements are very important
to safe and efficient operation. Inspect the parts often
and perform required service at the prescribed intervals.
Maintenance work must be performed by appropriately
skilled and suitably-trained maintenance personnel,
familiar with generator set operation and service.
Before installing a mobile generator set, obtain the
most current installation manual from your local
distributor/dealer. Only qualified persons should
install the generator set.
x:in:001:002:a
Introduction iTP-6079 3/00
Page 10
Service Assistance
Service Information
Please contact a local authorized distributor/dealer for
sales, service, or other information about Kohler
Generator Division products.
To locate a local authorized distributor/dealer inside
the U.S.A. and Canada
D Look on the product or in the information included with
the product
D Consult the Yellow Pages under the heading
Generators— Electric
D Visit the Kohler Generator Division web site at
www.kohlergenerators.com
D Call 1-800-544-2444
To locate a local authorized distributor/dealer
outside the U.S.A. and Canada
D Look on the product or in the information included
with the product
D Consult the telephone directory under the heading
Generators—Electric
D Visit the Kohler Generator Division web site at
www.kohlergenerators.com
D Contact the nearest regional office
Africa, Europe, Middle East
London Regional Office
Langley, Slough, England
Phone: (44) 1753-580-771
Fax:(44) 1753-580-036
Australia
Australia Regional Office
Queensland, Australia
Phone: (617) 3893-0061
Fax:(617) 3893-0072
China
China Regional Office
Shanghai, People’s Republic of China
Phone: (86) 21-6482 1252
Fax:(86) 21-6482 1255
India, Bangladesh, Sri Lanka
India Regional Office
Bangalore, India
Phone: (91) 80-2284270
(91) 80-2284279
Fax:(91) 80-2284286
Japan
Japan Regional Office
Tokyo, Japan
Phone: (813) 3440-4515
Fax:(813) 3440-2727
Latin America
Latin America Regional Office
Lakeland, Florida, U.S.A.
Phone: (941) 619-7568
Fax:(941) 701-7131
Product identification numbers determine service parts.
Record the product identification numbers in the spaces
below immediately after unpacking the products so that
the numbers are readily available for future reference.
Record field-installed kit numbers after installing the
kits.
Generator Set Identification Numbers
Record the product identification numbers from the
generator set nameplate(s).
Model Number
Specification Number
Serial Number
Accessory NumberAccessory Description
Engine Identification
Record the product identification information from the
engine nameplate.
Manufacturer
Model Number
Serial Number
TP-6079 3/00ii Introduction
Page 11
Section 1 Specifications
1.1General
The 5ERKM and 4EFRKM units are powered by a
one-cylinder, air-cooled, four-cycle gasoline engine.
Kohler Co. develops all Kohler mobile generator set
ratings using accepted reference conditions of 25_C
(77_F) and pressure of 98.9 kPa (29.2 in. Hg) dry
barometer. ISO 3046 and ISO 8528-1 include reference
conditions and output calculations. Obtain technical
information bulletin (TIB-101) on ratings guidelines for
complete ratings definitions.
1.2Engine
Engine Specifications
Engine manufacturerKohler
Engine modelCS12
Number of cylinders1
Cylinder block materialAluminum
Cylinder head materialAluminum
Piston rings
GovernorMechanical
Bore x stroke, mm (in.)85 x 63 (3.35 x 2.48)
Displacement, L (CID)0.357 (21.79)
Compression ratio8.1:1
Horsepower, 60/50 Hz11.5/8
RPM, 60/50 Hz3600/3000
Lubrication systemSplash
Lube oil capacity L (U.S. qts)2.0 (2.1)
Oil recommendation, APISC or SH
Battery voltage, standard, DC12
Battery CCA recommendation,
min.
Battery charging10 amps
Starter motorBendix automotive type
2 compression
1 oil control
250
1.4Generator
Component Specifications
Hot exciter field voltage/current
readings at rated voltage
No load (63 Hz) (volts/amps)10.1/4.4
Full load (60 Hz) (volts/amps)50.5/8.5
Cold main field (rotor) resistance (ohms)3.7
Stator output voltages with separately
excited generator, using 12-volt battery
(60 Hz only)
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set. Accidental starting can
cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the
generator set as follows: (1) Disconnect the power to the
battery charger, if equipped. (2) Remove the battery cables,
negative (--) lead first. Reconnect the negative (--) lead last
when reconnecting the battery. Follow these precautions to
prevent the starting of the generator set by the remote
start/stop switch.
2.2Lubrication System
Use oil that meets the American Petroleum Institute
(API) classification of SC or SH. Using unsuitable oil or
neglecting an oil change may result in engine damage
that is not covered by the engine warranty. Figure 2-1
shows the recommended Society of Automotive
Engineers (SAE) viscosity designation for given
operating temperature ranges.
Do not mix different oil brands. Incompatibility could
cause a breakdown of lubricating ingredients and
reduce engine protection.
WARNING
Rotating parts.
Can cause severe injury or death.
Operate the generator set only when
all guards, screens, and covers are in
place.
Servicing the generator set when it is operating. Exposed
moving parts can cause severe injury or death. Keep
hands, feet, hair, clothing, and test leads away from the belts
and pulleys when the generator set is running. Replace
guards, screens, and covers before operating the generator
set.
Note: See the generator set operation manual for the
service schedule and other service not included
in this manual.
Figure 2-1 Recommended SAE Viscosity Grades
TP-6079 3/003Section 2 Scheduled Maintenance
Page 14
2.3Air Intake System
At the interval specified in the service schedule, inspect,
clean, or replace the air filter element.
2.4Exhaust System
WARNING
Carbon monoxide.
Cancauseseverenausea,
fainting, or death.
The exhaust system must be
leakproof and routinely inspected.
Inspect the exhaust system components (exhaust
manifold, exhaust line, exhaust clamps, and muffler) for
cracks and corrosion.
D Check for corroded or broken metal parts and replace
them as needed.
D Check for loose, corroded, or missing clamps and
hangers. Tighten or replace the exhaust clamps
and/or hangers as needed.
D Check that the exhaust outlet is unobstructed.
D Check the exhaust gas color. If the exhaust is blue or
black, contact your local distributor/dealer.
D Visually inspect for exhaust leaks. Check for carbon
or soot residue on exhaust components. Carbon and
soot residue indicates an exhaust leak. Seal leaks as
needed.
Exhaust System.Check for exhaust leaks and
blockages. Check the muffler and piping condition and
check for tight exhaust system connections.
D Ensure that the carbon monoxide detector is (1) in the
vehicle, (2) functional, and (3) energized whenever
the generator set operates.
m:op:001:003
TP-6079 3/004Section 2 Scheduled Maintenance
Page 15
Section 3 Fuel System
WARNING
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.
The fuel system. Explosive fuel vapors can cause severe
injury or death. Vaporized fuels are highly explosive. Use
extreme care when handling and storing fuels. Store fuels in a
well-ventilated area away from spark-producing equipment
and out of the reach of children. Never add fuel to the tank
while the engine is running because spilled fuel may ignite on
contact with hot parts or from sparks. Do not smoke or permit
flames or sparks to occur near sources of spilled fuel or fuel
vapors. Keep the fuel lines and connections tight and in good
condition. Do not replace flexible fuel lines with rigid lines. Use
flexible sections to avoid fuel line breakage caused by
vibration. Do not operate the generator set in the presence of
fuel leaks, fuel accumulation, or sparks. Repair fuel systems
before resuming generator set operation.
3.2Fuel Pump
Electric fuel pumps draw fuel from the fuel tank through
a filter and supply clean fuel at the proper pressure and
quantity to the generator set engine carburetor.
Fuel Pump Test Procedure:
1. Connect the inlet side of the pump to a fuel source.
2. Disconnect the outlet hose from the fuel filter and
place the end in a container to catch the fuel.
3. Disconnect the P9 connector.
4. Connect the positive terminal (70) of the fuel pump
to the positive terminal (+) of a 12-volt battery.
5. Connect the negative terminal (N) of the fuel pump
to the negative terminal (--) of the battery. The
pump should operate and fuel should discharge
from the pump outlet. If the pump does not operate,
replace the pump.
Explosive fuel vapors can cause severe injury or death.
Take additional precautions when using the following fuels:
Draining the fuel system. Explosive fuel vapors can
cause severe injury or death. Spilled fuel can cause an
explosion. Use a container to catch fuel when draining the fuel
system. Wipe up spilled fuel after draining the system.
3.1General
In most installations, both the generator set and the
vehicle’s engine operate from a common fuel tank with a
dual dip tube. The generator set’s dip tube may be
shorter than the vehicle engine’s dip tube. With this
arrangement, fuel may not be available to the generator
set when the fuel supply is low. See Figure 3-1 for a fuel
system schematic.
Vehicle’s
engine
3
1. Dual dip tubes
2. Fuel filter
3. Fuel tank
1
2
Generator
set fuel
pump
Figure 3-1 Fuel System Schematic, Typical
598641
TP-6079 3/005Section 3 Fuel System
Page 16
3.3Carburetor Troubleshooting
This section is for fuel-related problems and basic
carburetor troubleshooting.See Figure 3-2 for
carburetor component identification.
Note: When troubleshooting the fuel system, it is
important to have an adequate fuel supply.
A lean or rich fuel condition can reduce power output
and cause poor acceleration.
Symptoms of a lean condition:
D Hard starting
D Stalling
D Hunting
Symptoms of a rich condition:
D Hard starting
D Stalling
D Percolation
D Flooding
D Leaking carburetor
If a rich condition occurs, remove the air cleaner
element and observe the choke plate to ensure that it is
fully open. The choke will not fully open until the engine
is warm. If the choke does not fully open, test the
bi-metallic strip and the choke pull-off. See Figure 3-2.
Replace components as necessary.
Bi-metallic Strip Test Procedure:
1. Start and run the generator set until it reaches
normal operating temperature. (5--10 minutes).
2. If the chokeplate levercan berotated
counterclockwise adjust or replace the bi-metallic
strip.
4
1. Choke pull-off
2. Bi-metallic strip
3. Choke linkage
4. Choke plate lever
3
2
1
Figure 3-2 Fuel System Exploded View
598642
Choke Pull-off Vacuum Solenoid Test Procedure:
1. Remove the vacuum hose that is connected to the
back of the choke pull-off vacuum solenoid.
2. Push and hold the choke linkage into the choke
pull-off vacuum solenoid.
3. Seal the vacuum port on the back of the solenoid
and release the choke linkage. If the choke linkage
moves back to the original location while the
vacuum port is sealed, replace the choke pull-off
vacuum solenoid.
3.3.1Hard Starting
A flooded engine, an improperly adjusted or inoperative
choke, or a dirty carburetor (lean condition) can cause
hard starting.
3.3.2Stalling
A dirty carburetor can cause stalling. Clogged idle air
bleeds, idle air passages, or an idle discharge port can
cause stalling because of a lean condition. To remedy
this condition, clean or adjust the carburetor.
TP-6079 3/006Section 3 Fuel System
Page 17
3.3.3Flooding
3.560 and 50 Hz Conversions
Flooding occurs from a float level set too high, an
inoperative bi-metallic strip, an inoperative choke
pull-off, a sticking choke plate or float, or a fuel inlet
needle held off its seat either by improper seating or dirt
particles. A punctured or leaking float admitting fuel
becomes gas-logged causing a heavy float, high fuel
level, and flooding.
3.3.4Hunting
A low fuel level because of an improperly adjusted float,
a clogged main jet, restricted main jet passages, or an
improperly sized main jet for the application can cause
hunting. To remedy this condition, clean, adjust, or
replace inoperative components.
An incorrect throttle linkage adjustment, a binding
throttle linkage, a sticking throttle shaft, or a loose
throttle shaft in the throttle body or bore can cause
inconsistent idle speed.
3.3.5Leaking Carburetor
Loose fuel connections, a cracked carburetor body, a
sticking fuel inlet needle, or an inoperative float can
cause a leaking carburetor. Adjust, repair, or replace the
affected components.
3.4Governor
The factoryadjuststhegovernorandfurther
adjustments should not be necessary.
To convert the generator set to 50 or 60 Hz follow the
procedure below.
Governor 50 or 60 Hz Conversion Procedure:
1. Adjust the generator frequency by adjusting the
generator speed adjusting screw.Using a
frequency meter set the no load speed at 52.5 Hz
for 50 Hz operation or 63 Hz for 60 Hz operation.
2. Adjust the voltage regulator volt/Hz roll-off point.
Refer to Section 5.2.2.
1
1. Generator speed adjusting screw
Figure 3-3 Governor 60 Hz to 50 Hz Conversion
598643
Note: Never tamper with the governor settings to
increase the generator output. Overspeeding
can cause equipment parts to exceed design
limitations, resulting in component failure.
TP-6079 3/007Section 3 Fuel System
Page 18
Notes
TP-6079 3/008Section 3 Fuel System
Page 19
Section 4 Controller Troubleshooting
4.1Sequence of Operation
This section describes the controller sequence of
operation during the generator start, run, stop, and fault
shutdown modes and describes the relay testing
procedures. Use this section as a starting point for
controller fault identification.Use the LEDs on the
controller circuit board to assist in the troubleshooting
process.An illuminated LED indicates that the
respective relay is receiving power; the LED does not
indicate whether that relay is energized or working
properly.Unfold and use the wiring diagram in
Section 8.5 to follow the sequence of operation in this
section.
2
3
1
4.1.1Start
Press the start/stop switch to the START position to
close the start/stop switch between N and 47 (local or
remote).
The K2 relay energizes and LED2 illuminates. The
normally open K2 contacts close energizing the K3 relay
(LED3 lights), fuel pump (FP), choke heater (CHTR),
antidiesel solenoid (ADS), ignition (IGN), hourmeter
(HR), and the main field (FP and FN).
Flashing of the main field occurs when the K2 contacts
close.
The normally open K3 contacts close energizing the
K20 relay. The normally open K20 contacts close,
energizing the starter relay (SR). The SR normally open
contacts close energizing the starter motor (SM).
4.1.2Run
The bridged rectifier (BR1) receives AC voltage
(12--15 volts) through the B1 and B2 windings of the
stator.
7
6
1. PBIIIE voltage regulator
2. K20 relay
3. K25 relay
4. Controller circuit board
5. Fuses
6. Start/stop switch
7. Hourmeter
4
The K1 relay energizes (LED1 lights).
The normally open K1 contacts close maintaining
voltage to the K2 relay, allowing the function of the fuel
pump (FP), choke heater (CHTR), antidiesel solenoid
(ADS), ignition (IGN), and hourmeter (HR).
The normally closed K1 contacts open, ending the
flashing by preventing battery voltage to the main field
(+) and (--).
The K6 relay energizes. The normally open K6 contacts
close, latching the K6 relay on. The normally closed K6
5
contactsopen,preventinginadvertentstarter
engagement by disabling the the K3 relay.
The K3 relay deenergizes (LED3 off). The K3 contacts
open, deenergizing the K20 relay. The K20 contacts
open, deenergizing the starter relay and starter motor.
At the same time the K1 relay energizes, the time delay
GM11919
for the K5 relay starts. After 5--10 seconds, the K5 relay
energizes (LED 5 lights).
The normally open K5 contacts close permitting the
function of the engine safety shutdown switch.
Figure 4-1 Controller
TP-6079 3/009Section 4 Controller Troubleshooting
Page 20
4.1.3Stop
4.1.4Low Oil Level (LOL) Safety Switch
Close the start/stop switch between N and 43 (local or
remote).
The K4 relay energizes (LED4 lights).
The normally closed K4 contacts open, disabling the
fuel pump (FP), choke heater (CHTR), antidiesel
solenoid (ADS), and ignition (IGN).
The normally open K4 contacts close, latching the circuit
to the K4 relay until the generator set comes to a
complete stop.
11
When the oil level is low, the LOL shutdown switch
contacts close energizing the K4 relay (LED4 lights).
The generator set shuts down, as described in
Section 4.1.3.
4.2Controller Circuit Board
The controller circuit board has light emitting diodes
(LEDs) that indicate the presence of relay coil power.
When any of the relays K1--K5 receives power, the
corresponding LED lights.
Use the following flow chart as an aid in troubleshooting
the main circuit board and the entire generator set. If the
prescribed remedy does not correct the problem, the
circuit board may have to be replaced. Use this chart for
component testing only. Always check the continuity of
the wires between components. Always disconnect
external components (remote start/stop switches, the
engine gauge panel, dry relay contact kits, etc.) before
performing troubleshooting procedures.
Press the start switch
(local or remote).
Check the battery
Does the K2 relay LED
light while cranking?
No
Is the 10-amp controller
fuse functional?
YesNo
Does the engine crank?
condition and
connections.
Yes
the circuit board.
Is there continuity between
N and 47 while pressing
the start/stop switch?
No
No
TheK2relayis
faulty. Replace
Yes
Is the K3 relay LED lit?
Is voltage present at the K20 relay coil
(P1-4 connector)?
No
TheK2relayis
faulty. Replace
the circuit board.
No
Go to A
(next page).
Yes
Yes
Replace or repair
the wiring harness.
Is voltage present
at the starter relay?
No
Replace the
K20 relay.
Replace the starter
Is voltage present at
the starter?
No
relay.
Yes
Yes
Replace or
repair the
starter motor.
Replace the fuse.
Replace the
circuit board.
Yes
Yes
Is there 12 volts
at P1--14?
No
Yes
Is the start/stop
switch functional?
No
Replace the
start/stop switch.
Figure 4-3 Troubleshooting the Relay Controller Circuit Board (1 of 4)
Beforebeginningthefollowingtroubleshooting
procedures, read all the safety precautions at the
beginning of this manual. The following tests include
additional safety precautions; OBSERVE THESE
PRECAUTIONS!
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
Testing the voltage regulator. Hazardous voltage can
cause severe injury or death. High voltage is present at the
voltage regulator heat sink. Toprevent electrical shock do not
touch the voltage regulator heat sink when testing the voltage
regulator.
(PowerBoostt, PowerBoostt III, and PowerBoostt V
voltage regulator models only)
Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible
whenever electricity is present.Open the main circuit
breakers of all power sources before servicing the equipment.
Configure the installation to electrically ground the generator
set, transfer switch, and related equipment and electrical
circuits to comply with applicable codes and standards. Never
contact electrical leads or appliances when standing in water
or on wet ground because these conditions increase the risk of
electrocution.
Short circuits. Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs.Remove wristwatch, rings, and jewelry before
servicing the equipment.
Moving rotor.
5.1.1General Troubleshooting
To determine the cause of no- or low-AC output , refer to
the following steps and the troubleshooting flow chart
(Figure 5-1).Verify the operation of the alternator
components before replacing the controller board or
voltage regulator.
General Troubleshooting:
1. Check the condition of the voltage regulator’s
10-amp fuse.
2. If the fuse is functional, separately excite the
generator. (See Section 5.1.2.)The separate
excitation test duplicates the role of the voltage
regulator by providing excitation current to the
rotor.
Generator has no
or low output
Check for flashing
voltage at the brushes
Separately
excite generator
Generator has
no output
Test rotor
Figure 5-1 General Troubleshooting
Troubleshoot
controller
Generator has
output
Test voltage
regulator and
wiring
Test stator
TP-598651
TP-6079 3/0015Section 5 Generator Troubleshooting
Page 26
5.1.2Separate Excitation
a
By separately exciting the generator to determine the
presence of a faulty voltage regulator, it is possible to
determine if a running fault exists in the rotor and/or
stator. A generator component that appears functional
while static (stationary) may exhibit a running open or
short circuit while dynamic (moving). Centrifugal forces
acting on the windings during rotation or insulation
breakdown as temperatures increase can cause short
circuits.
Note: It is not necessary to separately excite the
generator if there is AC output with flashing
voltage.
Separate Excitation Procedure:
1. Disconnect all of the leads from the voltage
regulator.
2. Disconnect the P10 (F1, F2) connector.
3. Connect a separate excitation circuit as shown in
Figure 5-2. Connect an ammeter and a 10-amp
fuse in series with F1.Note and record the
ammeter reading.
7. Remove the jumper wire and reverse the
positive (+) and negative (--) leads on the rotor.
Repeat step 5. If the ammeter is stable, ground the
negative (--) lead at its new location on the rotor to
the engine block. Replace the rotor if the ammeter
reading fluctuates.
8. Check for AC output across the stator leads and
compare the measured output to the values in
Section 1, Specifications.If the output varies
considerably from those listed, a faulty stator, rotor,
rectifier module, or armature is the likely cause.
If there is no generator output during normal operation,
but output is available when the generator set is
separately excited, the voltage regulator may be
inoperative.
Note: See Section 1, Specifications, for the stator
outputvoltages(withseparatelyexcited
generator). These specifications are based on
12 volts at the battery. Should the battery voltage
vary, the resulting stator output values will also
vary.
321
4. Divide the battery voltage by the exciter resistance
(cold) to determine the exciter current. Disconnect
the resistor leads and determine the exciter current
value using an ohmmeter.See Section 1.3,
Specifications, for the normal values.
B
Exciter Current =
Example :
12 VDC
3.7 Ohms
tteryVoltage
Exciter Resistance
= 3.2 Amps
5. Start the engine and check that the ammeter
remains stable.An increasing meter reading
indicates a shorted rotor. A decreasing meter
reading to zero, or unstable reading, suggests a
running open in the rotor. If the ammeter is stable,
continue with step 6.
6. With a jumper wire, ground the negative (--) lead
from the rotor to the engine block. An increased
current reading or a fluctuating reading indicates a
grounded rotor winding. Replace the rotor if the
ammeter reading fluctuates. If the ammeter is
stable, continue with step 7.
The generator set is equipped with a PowerBoostt IIIE
voltage regulator. See Figure 5-3.
The voltage regulator monitors the output voltage of the
generator set.
The 10-amp regulator fuse protects the alternator stator
windings (power supply) 55--33 from excessive current
draw because of an inoperative voltage regulator or a
downstream short. If the regulator’s 10-amp fuse blows,
the generator set will shut down. Verify that the regulator
fuse is functional before proceeding with the test.
132
1. Voltage potentiometer
2. Stability potentiometer
3. Volts/Hz potentiometer
TP-598653
Figure 5-3 PowerBoostt IIIE Voltage Regulator
5.2.1Voltage Regulator Test
Perform the following test to check the regulator output.
Use the following components to test the voltage
regulator:
2. Turn the variable transformer setting to zero. Plug
in the variable transformer.
3. Turn the variable transformer on. Slowly increase
the variable transformer to 100 volts. Thetest lamp
should light. If the lamp does not light, turn the
voltage adjustment potentiometer (pot) clockwise.
If the lamp still does not light, the voltage regulator
is inoperative. Replace the voltage regulator. An
inoperative voltage regulator causes a generator
no/low-output condition.
4. Slowly increase the variable transformer to
120 volts. The lamp should go out and stay out as
the voltage increases. If the lamp remains lit, turn
the voltage adjustment pot counterclockwise. If the
lamp still remains lit, replace the voltage regulator.
A voltage regulator that is inoperative causes a
generator high voltage output condition.
5. Turn the variable transformer to zero and unplug
the AC cord.
Note: For applications requiring fine voltage
adjustment, connect a remote rheostat to
voltage regulator terminal 66.
4
123
66 443355--+
RYOW
GY
5
BK
6
7
D Variable transformer, 0--140 volts, 0.5-amp minimum
D Plug, 120 volts AC
D Lamp, 120 volts, 100 watts
D AC voltmeter
D Insulated copper wire, #14 AWG, minimum
TP-6079 3/0017Section 5 Generator Troubleshooting
1. 120 volts AC
TP-598654
2. Variable transformer
3. AC voltmeter
4. Voltage regulator PowerBoosttIIIE
5. Stator/rotor connections (for reference only)
6. Lead color
7. 120-volt, 100-watt lamp
Figure 5-4 PowerBoosttIIIE Voltage
Regulator Test
Page 28
5.2.2Voltage Regulator Adjustment
Voltage Regulator Adjustment Procedure:
The factory sets the voltage regulator and, under normal
circumstances, the regulator requires no further
adjustment. However, if the voltage regulator has been
replaced or tampered with or if voltage/frequency
reconnection has been done, readjust the voltage
regulator according to the following procedure. See
Figure 5-5.The following paragraphs describe the
voltage regulator components.
145
66
33
3
4
15
33
44
14
B1
12
B2
1. Optional remote rheostat
2. Voltage adjustment pot
3. PowerBoostä IIIE voltage regulator
4. Stabilizer pot
5. Volts/Hz pot
6. Stator/rotor connections (for reference only)
7. DC output
8. Rotor
9. 10-amp fuse
10. AC power input (aux.)
11. Main (2 and 1)
12. Control
13. Stator
14. Sensing
15. Main (3 and 4)
13
2
55
1
2
3
6
+
--
44 33 55
66
GY R
YOWBK
78
+
--
9
1011
TP-598655
Figure 5-5 PowerBoostt IIIE Voltage Regulator
Voltage Adjustment Pot adjusts the generator output
within the range of 100--130 volts.
Stabilizer Pot fine tunes regulator circuitry to minimize
AC voltage fluctuation.
1. Stop the generator set.
2. Turn the remote rheostat, if equipped, to the
midpoint. Turn the voltage and stabilizer pots fully
counterclockwise. Connect the voltmeter to the AC
circuit or an electrical outlet.
3. Start the generator set.
4. Adjust the generator frequency using a frequency
meter. Set the no load speed at 52.5 Hz for 50 Hz
operation or 63 Hz for 60 Hz operation. Rotate the
voltage adjustment pot clockwise to increase the
voltage or counterclockwise to decrease the
voltage to achieve the desired output voltage.
5. Connect a 120-volt light bulb to the AC plug on the
generator set.
6. Rotate the stability pot clockwise until the light bulb
flickers minimally.
7. Readjust the voltage to achieve the desired output
voltage.
8. Disconnect the 120-volt light bulb.
9. Turn the volts/Hz pot completely clockwise to
decrease the Hz roll-off point. See Figure 5-6.
125
120
115
110
Volts (AC)
105
100
40 42 44 46 48 50 52 54 56 58 60 62 64
Frequency (Hz)
60 Hz Models
50 Hz Models
Counterclockwise to increase Hz roll-off
Volts/Hz Pot allows the voltage to drop if the load
imposed on the generator causes the engine speed to
fall below a predetermined frequency (roll-off point).
This reduction of voltage results in a decrease of starting
kW (load) allowing the governor to recover the engine
speed.
10. Set the engine speed to 47.5 Hz for 50 Hz
generator sets and 57.5 Hz for 60 Hz generator
sets for the desired cut-in frequency.
11. Slowly turn the volts/Hz pot counterclockwise until
the frequency matches that of the engine
frequency (47.5 or 57.5 Hz) or until the voltage just
begins to drop.
12. Reset the engine speed to the normal frequency
(50Hzor60Hz).
13. Recheck the AC voltage output and stability as
described in steps 4--7.
14. Stop the generator set.
5.3Rotor
The two-pole rotor creates the magnetic field needed to
sustain alternating current in the stator windings. Before
testing, inspect the rotor for visible damage to pole
shoes, insulation, exposed coil windings, and collector
ring surfaces. Check the rotor bearing for noisy
operation, excessive wear, radial or axial movement,
and/or heat discoloration.Replace the rotor as
necessary.
Collector rings acquire a glossy brown finish in normal
operation. Do not attempt to maintain a bright, newly
machined appearance. Wipe the collector rings with a
dry, lint-free cloth. Use a commutator stone to remove
the groves on the collector rings. Do not use emery or
carborundum paper or cloth. Remove all carbon dust
from the generator. Remove the black or pitted surface
of the collector rings using a lathe.
Check the rotor for continuity and resistance. Lift the
brushes and measure the rotor resistance between the
two collector rings. See Section 5.5.
Note: When checking rotor resistance with the rotor
installed, brushes must not be in contact with
rotor collector rings. Use a brush retainer on
brushes for accurate resistance readings.
Note: Use the values in Section 1 as a reference for
rotor resistance readings. Take readings at room
temperature or about 21°C(70°F). Rotor
resistance will vary directly with increase in
temperature.
To check whether the rotor is shorted to ground, touch
one ohmmeter lead to either collector ring and the other
lead to the rotor poles or shaft. The meter should
register no continuity.
Repair or replace the rotor if the previous tests detect
any faults.
TP-6079 3/0019Section 5 Generator Troubleshooting
Page 30
5.4Stator
The stator consists of a series of coils of wire laid in a
laminated steel frame. The stator leads supply voltage
to the AC load and exciter regulator. See Figure 5-7 for
coil lead description.
Stator LeadsDescription
1--2Output coil
3--4Output coil
33--44Control wires from 3 and 4
55--33Voltage regulator power source
B1--B2Controller power source
Figure 5-7 Stator Coil Lead Description
Before testing the stator, inspect it for heat discoloration
and visible damage to the exposed coil windings and
varnished areas of the frame laminations. Be sure the
stator is securely fastened in the stator housing.
Note: When taking an ohmmeter reading using
lead 55, make the connection prior to the
in-line fuse.
5. Check the cold resistance of the stator windings by
connecting the meter leads to the stator leads 1-4,
2-5, 3-6, etc. See Section 1, Specifications, for the
stator resistance values.
6. Perform a megohmmeter test on the stator as
described in step 7.
Note: Consider the stator functional if the
resistance reading (continuity) is low and
there is no evidence of shorted windings
(heat discoloration).
Note: The stator resistance varies directly with
increased temperature.
If the stator readings vary considerably during the
previous checks, repair or replace the stator.
The stator produces electrical output (AC) as the
magnetized main field rotates within the stator windings.
Test the condition of the stator according to the following
procedure.
Leads 1, 2, 3, and 4 are the generator output leads.
Leads 33, 44, and 55 are the voltage regulator supply
and sensing leads. The output of leads B1 and B2 is the
control voltage for the controller.
Stator Test Procedure:
1. Place the generator start/stop switch in the STOP
position.
2. Disconnect the generator set engine starting
battery, negative (--) lead first.
3. Check the generator output lead connections. See
Section 8, Reconnection and Wiring Diagrams.
4. Disconnect all of the stator leads to isolate the
windings. To check the stator continuity, set the
ohmmeter on the R x 1 scale. Check the stator
continuity by connecting the meter leads to the
stator leads as shown in Figure 5-8. Perform the
stator tests on all of the stator windings.
7. Check the stator for a grounded condition using a
megohmmeter. Apply 500 volts DC to any stator
lead from each winding and the stator frame.
Follow the instructions of the megohmmeter
manufacturer when performing this test. Repeat
the test on the other leads until all of the stator
windings have been tested.A reading of
approximately 1.5 megohms and higher indicates
the stator is functional. A reading of less than
approximately1.5megohmsindicates
deterioration of the winding insulation and possible
current flow to ground; if so, replace the stator.
The brushes provide a current path from the voltage
regulator to the collector rings. Because the brushes
carry a low current, inspect them every 3000 hours.
Abrasive dust on the collector rings could shorten the life
of the brushes. Excessive arcing at the brushes could
damage the voltage regulator. Weak springs, damaged
collector rings, sticking brushes, a loose holder, or poor
brush contact can cause arcing at the brushes. See
Figure 5-10 for brush component identification.
The brushes must be free to move within the holder and
be held in contact by the springs. When properly
positioned, spring pressure on the brush surface will
cause the brush to wear evenly. The brushes must ride
100% on the collector rings or arcing will occur and
cause burned rings or failure of the voltage regulator.
Figure 5-9 shows the correct positioning of the brushes.
Add or remove alignment shims as necessary to center
the brushes on the collector rings.
Replace brushes if they show excessive or uneven
wear.
Use a retainer wire (such as a paper clip) to contain the
brushes during disassembly and reassembly. Push the
brushes into the brush holder until the retainer wire can
be inserted into the brush keeping hole.
Replace brushes when they are worn to half of their
original size.
See Figure 6-1 through Figure 6-3 for engine/generator
component testing.With the generator set battery
connected, check the wiring harness and the
engine/generator components listed in the following
ComponentVoltmeter ConnectionsProcedureResults
Hourmeter and wiring.Connect the red test lead to
Stator auxiliary winding
B1 and B2.
the hourmeter positive (+)
terminal. Connect the black
test lead to the hourmeter
negative (--) terminal.
None (see procedure).Disconnect the hourmeter
Connect the AC voltmeter
leads to the B1 and B2
windings at connector P11.
tables. Check each component using a multimeter to
verify that the switches function and that voltage is
present at each component.
Set the voltmeter to 12 volts
DC or greater. Start the
generator set.
leads and apply 12 volts DC
to the hourmeter. The
hourmeter is polarity
sensitive.
Stop the generator set. Set
the voltmeter to 20 volts AC
or greater. Crank the
generator set and allow the
set to reach its rated speed.
A 12 volt DC reading
indicates the wiring harness
is functional.
If functional, hourmeter
operates.
A reading of 12--15 volts AC
indicates a functional B1/B2
winding.
To further check the generator set components,
disconnect the battery and remove the wiring harness
plugs from the controller circuit board.Use an
ohmmeter to check the continuity of the components
and to isolate inoperative components.Refer to
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
Short circuits. Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs.Remove wristwatch, rings, and jewelry before
servicing the equipment.
ComponentOhmmeter ConnectionsProcedureResults
Start/stop switch.Connect the ohmmeter to the
K20 relay coil and
wiring.
Controller 10-amp fuse
and wiring.
Moving rotor.
P2-6 and P2-4 leads.
Connect the ohmmeter to the
P2-6 and P2-5 leads.
Connect the ohmmeter to the
P1-4 and P1-9 leads.
Connect the ohmmeter to the
battery positive (+) cable and
the P1-14 lead. Note: Connect
the J4 and P4 leads to perform
this test.
Figure 6-2 and Figure 6-3.
Note: Before performing ohmmeter checks, disconnect
the generator set battery to prevent damage to
the ohmmeter.
Place the ohmmeter on the
R x 1000 scale. Place the
rocker switch in the START
position.
Place the ohmmeter on the
R x 1000 scale. Place the
rocker switch in the STOP
position.
Place the ohmmeter on the
Rx1scale.
Place the ohmmeter on the
R x 1000 scale.
If the switch is functional, zero
ohms continuity. Any
resistance other than zero or
very low ohms, replace the
switch.
If the switch is functional, zero
ohms continuity. Any
resistance other than zero or
very low ohms, replace the
switch.
If functional, 85 ohms. Low
resistance, shorted K20 relay
coil and/or wiring. High
resistance, open K20 relay
and/or wiring.
If functional, zero or very low
ohms. No reading (infinity),
open circuit or blown fuse.
Disconnect the external connections—battery cables at
the battery (negative (--) lead first), AC-output leads in
the controller, remote start panel at the controller P3
connector, and the fuel line at the fuel pump filter inlet.
Observe all of the safety precautions listed during the
disassembly/reassembly procedures.
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set. Accidental starting can
cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the
generator set as follows: (1) Disconnect the power to the
battery charger, if equipped. (2) Remove the battery cables,
negative (--) lead first. Reconnect the negative (--) lead last
when reconnecting the battery. Follow these precautions to
prevent the starting of the generator set by the remote
start/stop switch.
WARNING
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.
The fuel system. Explosive fuel vapors can cause severe
injury or death. Vaporized fuels are highly explosive. Use
extreme care when handling and storing fuels. Store fuels in a
well-ventilated area away from spark-producing equipment
and out of the reach of children. Never add fuel to the tank
while the engine is running because spilled fuel may ignite on
contact with hot parts or from sparks. Do not smoke or permit
flames or sparks to occur near sources of spilled fuel or fuel
vapors. Keep the fuel lines and connections tight and in good
condition. Do not replace flexible fuel lines with rigid lines. Use
flexible sections to avoid fuel line breakage caused by
vibration. Do not operate the generator set in the presence of
fuel leaks, fuel accumulation, or sparks. Repair fuel systems
before resuming generator set operation.
1. Place the start/stop switch in the STOP position.
2. Disconnect the generator set engine starting
battery, the negative (--) lead first.
14. Tilt the generator set up and brace it with a block of
wood. See Figure 7-3.
15. Remove the end bracket overbolts. Use a rubber
mallet to separate the end bracket from the stator
housing. See Figure 7-3.
3. Remove the controller cover.
4. Disconnect the P4 (22-pin) connector from J4.
5. Disconnect the controller ground strap (engine
side).
Note: It is possible to connect the output leads in
various positions for different voltage
configurations. Mark the leads for correct
reconnection.
6. Disconnect the generator output leads 1, 2, 3, and
4 from the circuit breaker and the neutral stud (L0).
7. Disconnect the P11 (FP and FN) and P10 (F1 and
F2) connectors.
8. Lift the controller from the rubber mounts while
guiding the leads through the bottom hole of the
controller box.
9. Remove the fuel pump and fuel inlet line from the
generator. See Figure 7-1.
10. Remove the coverplate.
11. Push the brushes into the holder. Secure the
brushes into position by sliding a retainer into the
brush keeping holes. Refer to Section 5.5.
12. Remove the brush holder and carefully slide the
leads out of the stator housing. See Figure 7-2.
16. Carefully remove the stator assembly from the
generator adaptor plate.
17. Loosen the rotor bolt, finger tighten, and back off
two turns.
18. Strike the bolt with a hammer until the rotor is freed
from the engine tapered drive shaft.Do not
damage the bolt threads or the bolt head. See
Figure 7-4.
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set. Accidental starting can
cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the
generator set as follows: (1) Disconnect the power to the
battery charger, if equipped. (2) Remove the battery cables,
negative (--) lead first. Reconnect the negative (--) lead last
when reconnecting the battery. Follow these precautions to
prevent the starting of the generator set by the remote
start/stop switch.
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible
whenever electricity is present.Open the main circuit
breakers of all power sources before servicing the equipment.
Configure the installation to electrically ground the generator
set, transfer switch, and related equipment and electrical
circuits to comply with applicable codes and standards. Never
contact electrical leads or appliances when standing in water
or on wet ground because these conditions increase the risk of
electrocution.
Moving rotor.
TP-6079 3/0031Section 8 Reconnection and Wiring Diagrams
TP-6079 3/0032 Section 8 Reconnection and Wiring Diagrams
Page 43
TP-6079 3/0033Section 8 Reconnection and Wiring Diagrams
8.5 Wiring Diagram 5ERKM/4EFRKM
-
GM11960-
Page 44
TP-6079 3/0034 Section 8 Reconnection and Wiring Diagrams
Notes
Page 45
Appendix A Abbreviations
The following list contains abbreviations that may appear in this publication.
A, ampampere
ABDCafter bottom dead center
ACalternating current
A/Danalog to digital
ADCanalog to digital converter
adj.adjust, adjustment
ADVadvertising dimensional
AHWTanticipatory high water
AISIAmerican Iron and Steel
ALOPanticipatory low oil pressure
alt.alternator
Alaluminum
ANSIAmerican National Standards
AOanticipatory only
APIAmerican Petroleum Institute
approx.approximate, approximately
ARas required, as requested
ASas supplied, as stated, as
ASEAmerican Society of Engineers
ASMEAmerican Society of
assy.assembly
ASTMAmerican Society for Testing
ATDCafter top dead center
ATSautomatic transfer switch
auto.automatic
aux.auxiliary
A/Vaudio/visual
avg.average
AVRautomatic voltage regulator
AWGAmerican Wire Gauge
AWMappliance wiring material
bat.battery
BBDCbefore bottom dead center
BCbattery charger, battery
BCAbattery charging alternator
BCIBattery Council International
BDCbefore dead center
BHPbrake horsepower
blk.black (paint color), block
blk. htr.block heater
BMEPbrake mean effective pressure
bpsbits per second
br.brass
BTDCbefore top dead center
BtuBritish thermal unit
Btu/min. British thermal units per minute
CCelsius, centigrade
cal.calorie
CARBCalifornia Air Resources Board
CBcircuit breaker
cccubic centimeter
CCAcold cranking amps
ccw.counterclockwise
CECCanadian Electrical Code
cfhcubic feet per hour
cfmcubic feet per minute
drawing
temperature
Institute
Institute
(formerly American Standards
Association, ASA)
suggested
Mechanical Engineers
Materials
charging
(engine)
CGcenter of gravity
CIDcubic inch displacement
CLcenterline
cmcentimeter
cmmcubic meters per minute
CMOScomplementary metal oxide
CTcurrent transformer
Cucopper
cu. in.cubic inch
cw.clockwise
CWCcity water-cooled
cyl.cylinder
D/Adigital to analog
DACdigital to analog converter
dBdecibel
dBAdecibel (A weighted)
DCdirect current
DCRdirect current resistance
deg., °degree
dept.department
dia.diameter
DI/EOdual inlet/end outlet
DINDeutsches Institut fur Normung
DIPdual inline package
DPDTdouble-pole, double-throw
DPSTdouble-pole, single-throw
DSdisconnect switch
DVRdigital voltage regulator
E, emer. emergency (power source)
EDIelectronic data interchange
EFRemergency frequency relay
e.g.for example (exempli gratia)
EGelectronic governor
EGSAElectrical Generating Systems
FFahrenheit, female
fglass.fiberglass
FHMflat head machine (screw)
fl. oz.fluid ounce
flex.flexible
freq.frequency
FSfull scale
ft.foot, feet
ft. lbs.foot pounds (torque)
ft./min.feet per minute
ggram
ga.gauge (meters, wire size)
gal.gallon
gen.generator
gensetgenerator set
GFIground fault interrupter
gnd.ground
gov.governor
gphgallons per hour
gpmgallons per minute
gr.grade, gross
gr. wt.gross weight
H x W x D height by width by depth
HChex cap
HCHThigh cylinder head temperature
HDheavy duty
HEThigh exhaust temperature
hexhexagon
Hgmercury (element)
HHhex head
HHChex head cap
HPhorsepower
hr.hour
HSheat shrink
hsg.housing
HVACheating, ventilation, and air
HWThigh water temperature
Hzhertz (cycles per second)
ICintegrated circuit
IDinside diameter, identification
IECInternational Electrotechnical
IEEEInstitute of Electrical and
IMSimproved motor starting
in.inch
in. H
in. Hginches of mercury
in. lbs.inch pounds
Inc.incorporated
ind.industrial
int.internal
int./ext.internal/external
I/Oinput/output
IPiron pipe
ISOInternational Organization for
Jjoule
JISJapanese Industry Standard
kkilo (1000)
Kkelvin
kAkiloampere
KBkilobyte (2
kgkilogram
conditioning
Commission
Electronics Engineers
Oinches of water
2
Standardization
10
bytes)
TP-6079 3/00Appendix A-1
Page 46
2
kg/cm
kgmkilogram-meter
kg/m
kilograms per square
centimeter
3
kilograms per cubic meter
kHzkilohertz
kJkilojoule
kmkilometer
kOhm, kW kilo-ohm
kPakilopascal
kphkilometers per hour
kVkilovolt
kVAkilovolt ampere
kVARkilovolt ampere reactive
kWkilowatt
kWhkilowatt-hour
kWmkilowatt mechanical
Lliter
LANlocal area network
L x W x H length by width by height
lb.pound
3
lbm/ft
pounds mass per cubic feet
LCBline circuit breaker
LCDliquid crystal display
ld. shd.load shed
LEDlight emitting diode
Lphliters per hour
Lpmliters per minute
LOPlow oil pressure
LPliquefied petroleum
LPGliquefied petroleum gas
LSleft side
L
wa
sound power level, A weighted
LWLlow water level
LWTlow water temperature
mmeter, milli (1/1000)
Mmega (10
bytes)
MCMone thousand circular mils
meggarmegohmmeter
MHzmegahertz
mi.mile
milone one-thousandth of an inch
min.minimum, minute
misc.miscellaneous
MJmegajoule
mJmillijoule
mmmillimeter
mOhm, mW
MOhm, MW
milliohm
megohm
MOVmetal oxide varistor
MPamegapascal
mpgmiles per gallon
mphmiles per hour
MSmilitary standard
m/sec.meters per second
MTBFmean time between failure
MTBOmean time between overhauls
mtg.mounting
MWmegawatt
mWmilliwatt
mFmicrofarad
N, norm. normal (power source)
NAnot available, not applicable
nat. gasnatural gas
NBSNational Bureau of Standards
NCnormally closed
NECNational Electrical Code
NEMANational Electrical
Manufacturers Association
NFPANational Fire Protection
Association
Nmnewton meter
NOnormally open
no., nos. number, numbers
NPSNational Pipe, Straight
NPSCNational Pipe, Straight-coupling
NPTNational Standard taper pipe
thread per general use
NPTFNational Pipe, Taper-Fine
NRnot required, normal relay
nsnanosecond
O/Covercrank
ODoutside diameter
OEMoriginal equipment
manufacturer
O/Foverfrequency
opt.option, optional
O/Soversize, overspeed
OSHAOccupational Safety and Health
Administration
O/Vovervoltage
oz.ounce
p., pp.page, pages
PApacked accessory
PCpersonal computer
PCBprinted circuit board
pFpicofarad
PFpower factor
ph.phase
PHCPhillips head crimptite (screw)
PHHPhillips hex head (screw)
PHMpan head machine (screw)
PLCprogrammable logic control
PMGpermanent magnet generator
potpotentiometer, potential
ppmparts per million
PROMprogrammable read only
memory
psipounds per square inch
pt.pint
PTCpositive temperature coefficient
PTOpower takeoff
PVCpolyvinyl chloride
qt.quart
qty.quantity
Rreplacement (emergency)
power source
rad.radiator, radius
RAMrandom access memory
RDOrelay driver output
ref.reference
rem.remote
RFIradio frequency interference
RHround head
RHMround head machine (screw)
rly.relay
rmsroot mean square
rnd.round
ROMread only memory
rot.rotate, rotating
rpmrevolutions per minute
RSright side
RTVroom temperature vulcanization
SAESociety of Automotive
Engineers
scfmstandard cubic feet per minute
SCRsilicon controlled rectifier
s, sec.second
SISysteme international d’unites,
International System of Units
SI/EOside in/end out
sil.silencer
SNserial number
SPDTsingle-- pole, double-- throw
SPSTsingle--pole, single--throw
spec, specs
specification(s)
sq.square
sq. cmsquare centimeter
sq. in.square inch
SSstainless steel
std.standard
stl.steel
tach.tachometer
TDtime delay
TDCtop dead center
TDECtime delay engine cooldown
TDENtime delay emergency to
normal
TDEStime delay engine start
TDNEtime delay normal to
emergency
TDOEtime delay off to emergency
TDONtime delay off to normal
temp.temperature
term.terminal
TIFtelephone influence factor
TIRtotal indicator reading
tol.tolerance
turbo.turbocharger
typ.typical (same in multiple
locations)
U/Funderfrequency
UHFultrahigh frequency
ULUnderwriter’s Laboratories, Inc.
UNCunified coarse thread (was NC)
UNFunified fine thread (was NF)
univ.universal
U/Sundersize, underspeed
UVultraviolet
U/Vundervoltage
Vvolt
VACvolts alternating current
VARvoltampere reactive
VDCvolts direct current
VFDvacuum fluorescent display
VGAvideo graphics adapter
VHFvery high frequency
Wwatt
WCRwithstand and closing rating
w/with
w/owithout
wt.weight
xfmrtransformer
TP-6079 3/00A-2 Appendix
Page 47
Appendix B Common Hardware Application Guidelines
Use the information below and on the following pages to
identify proper fastening techniques when no specific
reference for reassembly is made.
Bolt/Screw Length: When bolt/screw length is not given,
use Figure 1 as a guide. As a general rule, a minimum
length of one thread beyond the nut and a maximum
length of 1/2 the bolt/screw diameter beyond the nut is
the preferred method.
Washers and Nuts: Use split lock washers as a bolt
locking device where specified. Use SAE flat washers
with whiz nuts, spiralock nuts, or standard nuts and
preloading (torque) of the bolt in all other applications.
See Appendix C, General Torque Specifications, and
other torque specifications in the service literature.
For round and slotted exit holes, determine if
hardware is greater than 1/2 inch in diameter, or
1/2 inch in diameter or less. Hardware that is
greater than 1/2 inch in diameter takes a standard
nut and SAE washer. Hardware 1/2 inch or less in
diameter can take a properly torqued whiz nut or
spiralock nut. See Figure 2.
3. Follow these SAE washer rules after determining
exit hole type:
a. Always use a washer between hardware and a
slot.
b. Always use a washer under a nut (see 2 above
for exception).
c. Use a washer under a bolt when the female
thread is fixed (weld nut).
Unacceptable Nut/Bolt Clearance
3
1. 1/2 of bolt diameter
2. Min. 1 full thread beyond top of nut
3. Below top of nut
Figure 1Acceptable Bolt Lengths
G-585
4. Refer to Figure 2, which depicts the preceding
hardware configuration possibilities.
1
6
1. Cap screw
2. Entry hole types
3. Standard nut and SAE washer
4. Whiz nut or spiralock: up to 1/2 in. dia. hardware
5. Weld nuts: above 1/2 in. dia. hardware
6. Exit hole types
2
3
5
4
G-585
TP-6079 3/00Appendix A-3
Figure 2Acceptable Hardware Combinations
Page 48
Appendix C General Torque Specifications
T
A
lumi
A
Use the following torque specifications when service
literature instructions give no specific torque values.
The charts list values for new plated, zinc phosphate, or
oiled threads. Increase values by 15% for nonplated
threads. All torque values are +0%/--10%.
Assembled into
num
Grade2or5
Metric Fasteners Torque Specifications, Measured in Nm (ft. lb.)
Size (mm)
M6 x 1.005.6(4)9.9(7)14.0(10)5.6(4)
M8 x 1.2513.6(10)25.0(18)35.0(26)13.6 (10)
M8 x 1.0021.0(16)25.0(18)35.0(26)21.0 (16)
M10 x 1.5027.0(20)49.0(35)68.0(50)27.0 (20)
M10 x 1.2539.0(29)49.0(35)68.0(50)39.0 (29)
M12 x 1.7547.0(35)83.0(61)117.0(86)—
M12 x 1.5065.0(48)88.0(65)125.0(92)—
M14 x 2.0074.0(55)132.0(97)185.0 (136)—
M14 x 1.50100.0(74)140.0 (103)192.0 (142)—
M16 x 2.00115.0(85)200.0 (148)285.0 (210)—
M16 x 1.50141.0 (104)210.0 (155)295.0 (218)—
M18 x 2.50155.0 (114)275.0 (203)390.0 (288)—
M18 x 1.50196.0 (145)305.0 (225)425.0 (315)—
Assembled into Cast Iron or Steel
Grade 5.8Grade 8.8Grade 10.9
Assembled into
luminum
Grade 5.8 or 8.8
TP-6079 3/00A-4 Appendix
Page 49
Appendix D Common Hardware Identification
Screw/Bolts/Studs
Head Styles
Hex Head or Machine Head
Hex Head or Machine Head
with Washer
Flat Head (FHM)
Round Head (RHM)
Pan Head
Hex Socket Head Cap or
Allent Head Cap
Hex Socket Head or Allent
Head Shoulder Bolt
Sheet Metal Screw
Stud
Drive Styles
Hex
Hex and Slotted
Phillipsr
Nuts
Nut Styles
Hex Head
Lock or Elastic
Square
Cap or Acorn
Wing
Washers
Washer Styles
Plain
Split Lock or Spring
Spring or Wave
External Tooth Lock
Internal Tooth Lock
Internal-External Tooth Lock
Hardness Grades
American Standard
Grade 2
Grade 5
Grade 8
Grade 8/9 (Hex Socket
Head)
Metric
Number stamped on
hardware; 5.8 shown
5.8
Slotted
Hex Socket
Allent head screw is a trademark of Holo-Krome Co.
Phillipsr screw is a registered trademark of Phillips Screw Company.
Sample Dimensions
American Standard (Screws, Bolts, Studs, and Nuts)
1/4-20 x 1
Metric (Screws, Bolts, Studs, and Nuts)
M8-1.25 x 20
Length In Inches (Screws and Bolts)
Threads Per Inch
Major Thread Diameter In Fractional Inches Or Screw Number Size
Length In Millimeters (Screws and Bolts)
Distance Between Threads In Millimeters
Major Thread Diameter In Millimeters
Plain Washers
9/32
x5/8x 1/16
Lock Washers
5/8
Thickness
External Dimension
Internal Dimension
Internal Dimension
TP-6079 3/00Appendix A-5
Page 50
Appendix E Common Hardware List
The Common Hardware List lists part numbers and dimensions for common hardware items.
American Standard
Part No.Dimensions
Hex Head Bolts (Grade 5)
X-465-171/4-20 x .38
X-465-61/4-20 x .50
X-465-21/4-20 x .62
X-465-161/4-20 x .75
X-465-181/4-20 x .88
X-465-71/4-20 x 1.00
X-465-81/4-20 x 1.25
X-465-91/4-20 x 1.50
X-465-101/4-20 x 1.75
X-465-111/4-20 x 2.00
X-465-121/4-20 x 2.25
X-465-141/4-20 x 2.75
X-465-211/4-20 x 5.00
X-465-251/4-28 x .38
X-465-201/4-28 x 1.00
X-125-335/16-18 x .50
X-125-235/16-18 x .62
X-125-35/16-18 x .75
X-125-315/16-18 x .88
X-125-55/16-18 x 1.00
X-125-245/16-18 x 1.25
X-125-345/16-18 x 1.50
X-125-255/16-18 x 1.75
X-125-265/16-18 x 2.00
2305785/16-18 x 2.25
X-125-295/16-18 x 2.50
X-125-275/16-18 x 2.75
X-125-285/16-18 x 3.00
X-125-225/16-18 x 4.50
X-125-325/16-18 x 5.00
X-125-355/16-18 x 5.50
X-125-365/16-18 x 6.00
X-125-405/16-18 x 6.50
X-125-435/16-24 x 1.75
X-125-445/16-24 x 2.50
X-125-305/16-24 x .75
X-125-395/16-24 x 2.00
X-125-385/16-24 x 2.75
X-6238-23/8-16 x .62
X-6238-103/8-16 x .75
X-6238-33/8-16 x .88
X-6238-113/8-16 x 1.00
X-6238-43/8-16 x 1.25
X-6238-53/8-16 x 1.50
X-6238-13/8-16 x 1.75
X-6238-63/8-16 x 2.00
X-6238-173/8-16 x 2.25
X-6238-73/8-16 x 2.50
X-6238-83/8-16 x 2.75
X-6238-93/8-16 x 3.00
X-6238-193/8-16 x 3.25
X-6238-123/8-16 x 3.50
X-6238-203/8-16 x 3.75
X-6238-133/8-16 x 4.50
X-6238-183/8-16 x 5.50
X-6238-253/8-16 x 6.50
Part No.Dimensions
Hex Head Bolts, cont.
X-6238-143/8-24 x .75
X-6238-163/8-24 x 1.25
X-6238-213/8-24 x 4.00
X-6238-223/8-24 x 4.50
X-6024-57/16-14 x .75
X-6024-27/16-14 x 1.00
X-6024-87/16-14 x 1.25
X-6024-37/16-14 x 1.50
X-6024-47/16-14 x 2.00
X-6024-117/16-14 x 2.75
X-6024-127/16-14 x 6.50
X-129-151/2-13 x .75
X-129-171/2-13 x 1.00
X-129-181/2-13 x 1.25
X-129-191/2-13 x 1.50
X-129-201/2-13 x 1.75
X-129-211/2-13 x 2.00
X-129-221/2-13 x 2.25
X-129-231/2-13 x 2.50
X-129-241/2-13 x 2.75
X-129-251/2-13 x 3.00
X-129-271/2-13 x 3.50
X-129-291/2-13 x 4.00
X-129-301/2-13 x 4.50
X-463-91/2-13 x 5.50
X-129-441/2-13 x 6.00
X-129-511/2-20 x .75
X-129-451/2-20 x 1.25
X-129-521/2-20 x 1.50
X-6021-35/8-11 x 1.00
X-6021-45/8-11 x 1.25
X-6021-25/8-11 x 1.50
X-6021-15/8-11 x 1.75
2730495/8-11 x 2.00
X-6021-55/8-11 x 2.25
X-6021-65/8-11 x 2.50
X-6021-75/8-11 x 2.75
X-6021-125/8-11 x 3.75
X-6021-115/8-11 x 4.50
X-6021-105/8-11 x 6.00
X-6021-95/8-18 x 2.50
X-6239-13/4-10 x 1.00
X-6239-83/4-10 x 1.25
X-6239-23/4-10 x 1.50
X-6239-33/4-10 x 2.00
X-6239-43/4-10 x 2.50
X-6239-53/4-10 x 3.00
X-6239-63/4-10 x 3.50
X-792-11-8 x 2.25
X-792-51-8 x 3.00
X-792-81-8 x 5.00
Hex head bolts are hardness grade 8.8 unless noted.
Part No.Dimensions
Hex Head Bolts (partial thread)
M931-06040-60M6-1.00 x 40
M931-06055-60M6-1.00 x 55
M931-06060-60M6-1.00 x 60
M931-06070-60M6-1.00 x 70
M931-06075-60M6-1.00 x 75
M931-06090-60M6-1.00 x 90
M931-08035-60M8-1.25 x 35
M931-08040-60M8-1.25 x 40
M931-08040-82M8-1.25 x 40*
M931-08045-60M8-1.25 x 45
M931-08050-60M8-1.25 x 50
M931-08055-82M8-1.25 x 55*
M931-08060-60M8-1.25 x 60
M931-08070-60M8-1.25 x 70
M931-08070-82M8-1.25 x 70*
M931-08075-60M8-1.25 x 75
M931-08080-60M8-1.25 x 80
M931-08090-60M8-1.25 x 90
M931-08095-60M8-1.25 x 95
M931-08100-60M8-1.25 x 100
M931-10040-60M10-1.50 x 40
M931-10045-60M10-1.50 x 45
M931-10050-60M10-1.50 x 50
M931-10055-60M10-1.50 x 55
M931-10060-60M10-1.50 x 60
M931-10065-60M10-1.50 x 65
M931-10070-60M10-1.50 x 70
M931-10080-60M10-1.50 x 80
M931-10090-60M10-1.50 x 90
M931-10100-60M10-1.50 x 100
M931-12045-60M12-1.75 x 45
M931-12050-60M12-1.75 x 50
M931-12055-60M12-1.75 x 55
M931-12060-60M12-1.75 x 60
M931-12065-60M12-1.75 x 65
M931-12080-60M12-1.75 x 80
M931-12090-60M12-1.75 x 90
M931-12100-60M12-1.75 x 100
M931-12110-60M12-1.75 x 110
M931-16090-60M16-2.00 x 90
M931-20065-60M20-2.50 x 65
M931-20120-60M20-2.50 x 120
M931-20160-60M20-2.50 x 160
M931-22090-60M22-2.50 x 90
M931-22120-60M22-2.50 x 120
M931-22160-60M22-2.50 x 160
M931-24090-60M24-3.00 x 90
M931-24120-60M24-3.00 x 120
M931-24160-60M24-3.00 x 160
Part No.Dimensions
Hex Head Bolts (full thread)
M933-04006-60M4-0.70 x 6
M933-05050-60M5-0.80 x 50
M933-06010-60M6-1.00 x 10
M933-06014-60M6-1.00 x 14
M933-06016-60M6-1.00 x 16
M933-06020-60M6-1.00 x 20
M933-06025-60M6-1.00 x 25
M933-06040-60M6-1.00 x 40
M933-06050-60M6-1.00 x 50
M933-08016-60M8-1.25 x 16
M933-08020-60M8-1.25 x 20
M933-08025-60M8-1.25 x 25
M933-08030-60M8-1.25 x 30
M933-10012-60M10-1.50 x 12
M961-10020-60M10-1.25 x 20
M933-10020-60M10-1.50 x 20
M933-10025-60M10-1.50 x 25
M933-10030-60M10-1.50 x 30
M933-10030-82M10-1.50 x 30*
M961-10035-60M10-1.25 x 35
M933-10035-60M10-1.50 x 35
M933-12016-60M12-1.75 x 16
M933-12020-60M12-1.75 x 20
M933-12025-60M12-1.75 x 25
M933-12025-82M12-1.75 x 25*
M933-12030-60M12-1.75 x 30
M933-12040-60M12-1.75 x 40
M933-12040-82M12-1.75 x 40*
M961-14025-60M14-1.50 x 25
M933-14025-60M14-2.00 x 25
M961-16025-60M16-1.50 x 25
M933-16025-60M16-2.00 x 25
M933-16030-82M16-2.00 x 30*
M933-16035-60M16-2.00 x 35
M933-16040-60M16-2.00 x 40
M933-16050-60M16-2.00 x 50
M933-16050-82M16-2.00 x 50*
M933-16060-60M16-2.00 x 60
M933-18050-60M18-2.50 x 50
M933-18060-60M18-2.50 x 60
Pan Head Machine Screws
M7985A-03010-20 M3-0.50 x 10
M7985A-03012-20 M3-0.50 x 12
M7985A-04020-20 M4-0.70 x 20
M7985A-05010-20 M5-0.80 x 10
M7985A-05012-20 M5-0.80 x 12
KOHLER CO. Kohler, Wisconsin 53044
Phone 920-565-3381, Web site www.kohlergenerators.com
Fax 920-459-1646 (U.S.A. Sales), Fax 920-459-1614 (International)
For the nearest sales and service outlet in U.S.A. and Canada
Phone 1-800-544-2444
Kohlerr Power Systems
Asia Pacific Headquarters
7 Jurong Pier Road
Singapore 619159
Phone (65)264-6422, Fax (65)264-6455
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.