Kohler 40EOZ, 65EOZ, 50EOZ, 65COZ, 80EOZ Service Manual

...
Page 1
Service
Marine Generator Sets
Models:
40COZ/33CFOZ, 40EOZ/33EFOZ 50COZ/40CFOZ, 50EOZ/40EFOZ 65COZ/50CFOZ, 65EOZ/55EFOZ
80EOZ/70EFOZ, 99EOZ/80EFOZ
125EOZ/100EFOZ, 150EOZ/125EFOZ
Controllers:
Decision-Makert 3+
Decision-Makert 1 Standard
TP-5737 5/01b
Page 2
Product Identification Information
Product identification numbers determine service parts. Record the product identification numbers in the spaces below immediately after unpacking the products so that the numbers are readily available for future reference. Record field-installed kit numbers after installing the kits.
Generator Set Identification Numbers
Record the product identification numbers from the generator set nameplate(s).
Model Designation
Specification Number
Serial Number
Accessory Number Accessory Description
Engine Identification
Record the product identification information from the engine nameplate.
Manufacturer
Model Designation
Serial Number
Page 3
Table of Contents
Product Identification Information Inside front cover............................................
Safety Precautions and Instructions I........................................................
Introduction i...............................................................................
Service Assistance i........................................................................
Section 1 Specifications 1...................................................................
1.1 Introduction 1..........................................................
1.2 Specifications 1.........................................................
1.3 Accessories 2..........................................................
1.3.1 Remote Annunciator Kit 2........................................
1.3.2 Safeguard Breaker 3............................................
1.3.3 Line Circuit Breaker 3...........................................
1.3.4 Run Relay Kit 3.................................................
1.3.5 FASTCHECK Diagnostic Tester (Microprocessor Controller Only) 4....
Section 2 Operation 5.......................................................................
2.1 Fast-Responset II Concepts 5...........................................
2.2 Short Circuit Performance 5..............................................
2.3 Prestart Checklist 6.....................................................
2.4 Marine Inspection 6.....................................................
2.5 Angular Operation 6.....................................................
2.6 Exercising the Generator Set 6...........................................
2.7 Decision-Makert 3+ 16-Light Microprocessor Controller Operation 7..........
2.7.1 Controls and Indicators 8........................................
2.7.2 Fuses and Terminal Strips 9......................................
2.7.3 Auxiliary Fault Lamp Conditions 10.................................
2.7.4 Starting the Generator Set 10......................................
2.7.5 Stopping the Generator Set 10.....................................
2.7.6 Prime Power Mode Operation 11...................................
2.7.7 Fault Shutdowns 11..............................................
2.7.8 Controller Resetting Procedure (Following Fault Shutdown) 12.........
2.7.9 Resetting the Emergency Stop Switch 12............................
2.8 Expanded Decision-Makert 1 Controller Operation 13........................
2.8.1 Controls and Indicators 13........................................
2.8.2 Starting the Generator Set 14......................................
2.8.3 Stopping the Generator Set 14.....................................
2.8.4 Fault Shutdowns 14..............................................
2.8.5 Controller Resetting Procedure (Following Fault Shutdown) 14.........
2.9 Standard Decision-Makert 1 Controller Operation 15.........................
2.9.1 Controls and Indicators 15........................................
2.9.2 Starting the Generator Set 15......................................
2.9.3 Stopping the Generator Set 15.....................................
2.9.4 Fault Shutdowns 16..............................................
2.9.5 Controller Resetting Procedure (Following Fault Shutdown) 16.........
Section 3 Scheduled Maintenance 17..........................................................
3.1 General Maintenance 17..................................................
3.2 Generator Bearing 18....................................................
3.3 Storage Procedure 18....................................................
3.3.1 Lubrication System 18............................................
3.3.2 Cooling System 18...............................................
3.3.3 Fuel System 18..................................................
3.3.4 Exterior 18......................................................
3.3.5 Battery 18.......................................................
Section 4 General Troubleshooting 19.........................................................
TP-5737 5/01 Table of Contents
Page 4
Table of Contents, continued
Section 5 Decision-Makert 3+ Troubleshooting 23.............................................
5.1 Decision-Makert 3+ Controller 23.........................................
5.1.1 Decision-Maker 3+ Circuit Board Terminal/Connector Identification 25...
5.1.2 Fault Shutdowns, Decision-Maker 3+ Controller 31...................
5.2 Microprocessor Controller Relay Descriptions 32.............................
5.2.1 K1 Relay, Starter Solenoid 32......................................
5.2.2 K2 Relay, Crank Relay on Main Circuit Board 32.....................
5.2.3 K3 Relay, Run Relay on Main Circuit Board 32.......................
5.2.4 K4 Relay, Emergency Stop Relay on Main Circuit Board 32............
5.2.5 K5 Relay, Governor Control Relay 32...............................
5.3 Microprocessor Controller 32..............................................
5.3.1 Troubleshooting 33...............................................
5.3.2 Fuses 34.......................................................
5.4 FASTCHECK Features and Operation 39...................................
5.4.1 Features 39.....................................................
5.4.2 Application 40...................................................
5.4.3 Connect/Operate Procedure 40....................................
5.4.4 Overcrank 41....................................................
5.4.5 Controller Speed Sensor Circuitry 41...............................
5.4.6 Generator Condition Indicator Terminal (TB1 Terminal Strip) 42.........
Section 6 Decision-Makert 1 Controller Troubleshooting 45....................................
6.1 Decision-Makert 1 and Decision-Makert 1 Expanded Relay Controller 45......
6.2 Relay Controller 52.......................................................
Section 7 Component Testing and Adjustment 57..............................................
7.1 Generator Troubleshooting 57.............................................
7.2 Generator Testing 60.....................................................
7.2.1 No Output On Any Phase 60.......................................
7.2.2 Overvoltage 62..................................................
7.2.3 Fluctuating Voltage 62............................................
7.3 LED Circuit Board Test 62.................................................
7.4 SCR Assembly and Photo Transistor Board 64...............................
7.4.1 Concept and Equipment 64........................................
7.4.2 SCR Assembly and Photo Transistor Board Test 64...................
7.5 Automatic Voltage Regulator (AVR) Operation and Adjustment 66..............
7.6 Stator 68................................................................
7.7 Generator Field 69.......................................................
7.8 Exciter Armature 70......................................................
7.9 End Bracket Removal and Replacement 72..................................
7.10 Speed Sensor Test 73....................................................
7.11 Current Transformers 73..................................................
7.11.1 Function and Application 73.......................................
7.11.2 Testing 74.......................................................
7.12 Reactive Droop Compensator 74...........................................
7.12.1 Function and Application 74.......................................
7.12.2 Initial Adjustment 74..............................................
7.12.3 Final Adjustment 75..............................................
7.12.4 Testing 75.......................................................
7.13 Gauge Senders 76.......................................................
7.13.1 Oil Pressure Sender Testing 76....................................
7.13.2 Water Temperature Sender Testing 76..............................
TP-5737 5/01Table of Contents
Page 5
Table of Contents, continued
7.14 Governor Adjustment 77..................................................
7.14.1 Mechanical Governor 77..........................................
7.14.2 Electronic Governor, Barber-Colman Dyna 2500
7.14.3 Electronic Governor, Barber-Colman Dyna 70025
Section 8 Disassembly/Reassembly 83........................................................
8.1 Disassembly 87..........................................................
8.2 Reassembly 89..........................................................
Section 9 Wiring Diagrams 95................................................................
9.1 Voltage Reconnection 116.................................................
9.1.1 Introduction 116...................................................
9.1.2 Voltage Reconnection Procedure 116................................
9.2 Overvoltage Shutdown Adjustment 119......................................
9.3 Generator Set Frequency Change and Adjustment 121.........................
9.3.1 Frequency Change 121............................................
9.3.2 Frequency Adjustment 121.........................................
Appendix A Abbreviations A-1..................................................................
Appendix B Common Hardware Application Guidelines A-3........................................
Appendix C General Torque Specifications A-4...................................................
Appendix D Common Hardware Identification A-5.................................................
125--150 kW John Deere Engine-Powered 6081 77...................
using Stanadyne D Series Injection Pump
35--99 kW John Deere-Engine Powered 4045 and 6068 80............
Appendix E Common Hardware List A-6.........................................................
Appendix F Operating Hour Service Log A-8.....................................................
TP-5737 5/01 Table of Contents
Page 6
Page 7
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS. Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS.
This manual has several types of safety precautions and instructions: Danger, Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a hazard that will cause severe
personal injury, death,orsubstantial property damage.
WARNING
Warning indicates the presence of a hazard that can cause severe
personal injury, death, or substantial property damage.
CAUTION
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage.
NOTICE
Notice communicates installation, operation, or maintenance information that is safety related but not hazard related.
Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals.
Accidental Starting
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before
working on the generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
Battery
WARNING
Sulfuric acid in batteries. Can cause severe injury or death.
Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid
can cause blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid.
Battery acid cleanup. Battery acid can cause severe injury or death.
Battery acid is electrically conductive and corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a containerwith4L(1gal.)ofwaterand mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area.
TP-5737 5/01 ISafety Precautions and Instructions
Page 8
Battery gases. Explosion can cause severe injury or death. Battery gases
can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases.
Battery short circuits. Explosion can cause severe injury or death.
Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Engine Backfire/Flash Fire
Servicing the fuel system. A flash fire can cause severe injury or death.
Do not smoke or permit flames or sparks near the carburetor, fuel line, fuel filter, fuel pump, or other potential sources of spilled fuels or fuel vapors. Catch fuels in an approved container when removing the fuel line or carburetor.
Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator
set with the air cleaner/silencer removed.
Combustible materials. A sudden flash fire can cause severe injury or death. Do not smoke or permit flames
or sparks near the fuel system. Keep the compartment and the generator set clean and free of debris to minimize the risk of fire. Wipe up spilled fuels and engine oil.
Combustible materials. A fire can cause severe injury or death.
Generator set engine fuels and fuel vapors are flammable and explosive. Handle these materials carefully to minimize the risk of fire or explosion. Equip the compartment or nearby area with a fully charged fire extinguisher. Select a fire extinguisher rated ABC or BC for electrical fires or as recommended by the local fire code or an authorized agency. Train all personnel on fire extinguisher operation and fire prevention procedures.
Exhaust System
WARNING
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in exhaust gases. Carbon monoxide poisoning symptoms include but are not limited to the following:
D Light-headedness, dizziness D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.
Copper tubing exhaust systems. Carbon monoxide can cause severe nausea, fainting, or death. Do not
use copper tubing in diesel exhaust systems. Sulfur in diesel exhaust causes rapid deterioration of copper tubing exhaust systems, resulting in exhaust/water leakage.
Inspecting the exhaust system. Carbon monoxide can cause severe nausea, fainting, or death. For the
safety of the craft’s occupants, install a carbon monoxide detector. Consult the boat builder or dealer for approved detector location and installation. Inspect the detector before each generator set use. In addition to routine exhaust system inspection, test the carbon monoxide detector per the manufacturer’s instructions and keep the detector operational at all times.
WARNING
Fire. Can cause severe injury or death.
Do not smoke or permit flames or sparks near fuels or the fuel system.
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
TP-5737 5/01II Safety Precautions and Instructions
Page 9
Operating the generator set. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide
is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Use the following precautions when installing and operating the generator set. Do not install the exhaustoutlet where exhaust can be drawn in through portholes, vents, or air conditioners. If the generator set exhaust discharge outlet is near the waterline, water could enter the exhaust discharge outlet and close or restrict the flow of exhaust. Never operate the generator set without a functioning carbon monoxide detector. Be especially careful if operating the generator set when moored or anchored under calm conditions because gases may accumulate. If operating the generator set dockside, moor the craft so that the exhaust discharges on the lee side (the side sheltered from the wind). Always be aware of others, making sure your exhaust is directed away from other boats and buildings. Avoid overloading the craft.
Fuel System
WARNING
Explosive fuel vapors. Can cause severe injury or death.
The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly
explosive. Use extreme care when handling and storing fuels. Store fuels inawell-ventilatedareaawayfrom spark-producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts or from sparks. Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors. Keep the fuel lines and connections tight and in good condition. Do not replace flexible fuel lines with rigid lines. Use flexible sections to avoid fuel line breakage caused by vibration. Do not operate the generator set in the presence of fuel leaks, fuel accumulation, or sparks. Repair fuel systems before resuming generator set operation.
Draining the fuel system. Explosive fuel vapors can cause severe injury or death. Spilled fuel can cause an
explosion. Use a container to catch fuel when draining the fuel system. Wipe up spilled fuel after draining the system.
Installing the fuel system. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an
explosion. Do not modify the tank or the propulsion engine fuel system. Equip the craft with a tank that allows one of the two pickup arrangements described in the installation section. The tank and installation must conform to USCG Regulations.
Pipe sealant. Explosive fuel vapors can cause severe injury or death.
Fuel leakage can cause an explosion. Use pipe sealant on all threaded fittings to prevent fuel leakage. Use pipe sealant that resists gasoline, grease, lubrication oil, common bilge solvents, salt deposits, and water.
Hazardous Noise
CAUTION
Hazardous noise. Can cause hearing loss.
Never operate the generator set without a muffler or with a faulty exhaust system.
Engine noise. Hazardous noise can cause hearing loss. Generator sets
not equipped with sound enclosures can produce noise levels greater than 105 dBA. Prolonged exposure to noise levels greater than 85 dBA can cause permanent hearing loss. Wear hearing protection when near an operating generator set.
Use extreme care when handling, storing, and using fuels.
TP-5737 5/01 IIISafety Precautions and Instructions
Page 10
Hazardous Voltage/ Electrical Shock
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution
is possible whenever electricity is present. Open the main circuit breakers of all power sources before servicing the equipment. Configure the installation to electrically ground the generator set, transfer switch, and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Disconnecting the electrical load. Hazardous voltage can cause severe injury or death. Disconnect
the generator set from the load by opening the line circuit breaker or by disconnecting the generator set output leads from the transfer switch and heavily taping the ends of the leads. High voltage transferred to the load during testing may cause personal injury and equipment damage. Do not use the safeguard circuit breaker in place of the line circuit breaker. The safeguard circuit breaker does not disconnect the generator set from the load.
Moving rotor.
Testing the voltage regulator. Hazardous voltage can cause severe injury or death. High voltage
is present at the voltage regulator heat sink. To prevent electrical shock do not touch the voltage regulator heat sink when testing the voltage regulator.
(PowerBoostt, PowerBoostt III, and PowerBoostt V voltage regulator models only)
Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death.
Connect the generator set to the building/marina electrical system only through an approved device and after the building/marina main switch is opened. Backfeed connections can cause severe injury or death to utility personnel working on power lines and/or personnel near the work area. Some states and localities prohibit unauthorized connection to the utility electrical system. Install a ship-to-shore transfer switch to prevent interconnection of the generator set power and shore power.
Testing live electrical circuits. Hazardous voltage or current can cause severe injury or death. Have
trained and qualified personnel take diagnostic measurements of live circuits. Use adequately rated test equipment with electrically insulated probes and follow the instructions of the test equipment manufacturer when performing voltage tests. Observe the following precautions when performing voltage tests: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Do not touch the enclosure or components inside the enclosure. (4) Be prepared for the system to operate automatically.
(600 volts and under)
Hot Parts
WARNING
Hot coolant and steam. Can cause severe injury or death.
Before removing the pressure cap, stop the generator set and allow it to cool. Then loosen the pressure cap to relieve pressure.
WARNING
Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
Checking the coolant level. Hot coolant can cause severe injury or death. Allow the engine to cool.
Release pressure from the cooling system before removing the pressure cap. To release pressure, cover the pressure cap with a thick cloth and then slowly turn the cap counterclockwise to the first stop. Remove the cap after pressure has been completely released and the engine has cooled. Check the coolant level at the tank if the generator set has a coolant recovery tank.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts.
The engine and exhaust system components become extremely hot during operation.
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can
cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
TP-5737 5/01IV Safety Precautions and Instructions
Page 11
Moving Parts
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
WARNING
Rotating parts. Can cause severe injury or death.
Operate the generator set only when all guards, screens, and covers are in place.
WARNING
Airborne particles. Can cause severe injury or blindness.
Wear protective goggles and clothing when using power tools, hand tools, or compressed air.
Moving rotor.
Tightening the hardware. Flying projectiles can cause severe injury or death. Loose hardware can cause
the hardware or pulley to release from the generator set engine and can cause personal injury. Retorque all crankshaft and rotor hardware after servicing. Do not loosen the crankshaft hardware or rotor thrubolt when making adjustments or servicing the generator set. Rotate the crankshaft manually in a clockwise direction only. Turning the crankshaft bolt or rotor thrubolt counterclockwise can loosen the hardware.
Servicing the generator set when it is operating. Exposed moving parts can cause severe injury or death.
Keep hands, feet, hair, clothing, and test leads away from the belts and pulleys when the generator set is running. Replace guards, screens, and covers before operating the generator set.
Sound shield removal. Exposed moving parts can cause severe injury or death. The generator set
must be operating in order to perform some scheduled maintenance procedures. Be especially careful if the sound shield has been removed, leaving the belts and pulleys exposed.
(Sound-shield-equipped models only)
Notice
NOTICE
This generator set has been rewired from its nameplate voltage to
246242
NOTICE
Voltage reconnection. Affix a notice to the generator set after reconnecting the set to a voltage different from the voltage on the nameplate. Order voltage reconnection decal 246242 from an authorized service distributor/dealer.
NOTICE
Hardware damage. The engine and generator set may use both American Standard and metric hardware. Use the correct size tools to prevent rounding of the bolt heads and nuts.
NOTICE
When replacing hardware, do not substitute with inferior grade hardware. Screws and nuts are
available in different hardness ratings. To indicate hardness, American Standard hardware uses a series of markings, and metric hardware uses a numeric system. Check the markings on the bolt heads and nuts for identification.
NOTICE
Fuse replacement. Replace fuses with fuses of the same ampere rating and type (for example: 3AB or 314, ceramic). Do not substitute clear glass-type fuses for ceramic fuses. Refer to the wiring diagram when the ampere rating is unknown or questionable.
TP-5737 5/01 VSafety Precautions and Instructions
NOTICE
Saltwater damage. Saltwater quickly deteriorates metals. Wipe up saltwater on and around the generator set and remove salt deposits from m etal surfaces.
Page 12
Notes
TP-5737 5/01VI Safety Precautions and Instructions
Page 13
Introduction
This manual provides troubleshooting and repair instructions for 40COZ/33CFOZ, 40EOZ/33EFOZ, 50COZ/40CFOZ, 50EOZ/40EFOZ, 65COZ/50CFOZ, 65EOZ/55EFOZ, 80EOZ/70EFOZ, 99EOZ/80EFOZ, 125EOZ/100EFOZ, and 150EOZ/125EFOZ model generator sets, controllers, and accessories.
Refer to the engine service manual for generator set engine service information.
x:in:001:001
This manual may be used for models not listed on the front cover.
Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this publication and the products represented
Please contact a local authorized distributor/dealer for sales, service, or other information about Kohler Co. Generator Division products.
D Look on the product or in the information included
with the product
D Consult the Yellow Pages under the heading
Generators—Electric
D Visit the Kohler Co. Generator Division web site at
www.kohlergenerators.com
D Inside the U.S.A. and Canada, call 1-800-544-2444 D Outside the U.S.A. and Canada, call the nearest
regional office
Africa, Europe, Middle East
London Regional Office Langley, Slough, England Phone: (44) 1753-580-771 Fax: (44) 1753-580-036
Australia
Australia Regional Office Queensland, Australia Phone: (617) 3893-0061 Fax: (617) 3893-0072
China
China Regional Office Shanghai, People’s Republic of China Phone: (86) 21-6482 1252 Fax: (86) 21-6482 1255
without notice and without any obligation or liability whatsoever.
Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury. Read and follow the Safety Precautions and Instructions section at the beginning of this manual. Keep this manual with the equipment for future reference.
The equipment service requirements are very important to safe and efficient operation. Inspect the parts often and perform required service at the prescribed intervals. Obtain service from an authorized service distributor/dealer to keep equipment in top condition.
x:in:001:002:a
Service Assistance
India, Bangladesh, Sri Lanka
India Regional Office Bangalore, India Phone: (91) 80-2284270
(91) 80-2284279
Fax: (91) 80-2284286
Japan
Japan Regional Office Tokyo, Japan Phone: (813) 3440-4515 Fax: (813) 3440-2727
Latin America
Latin America Regional Office Lakeland, Florida, U.S.A. Phone: (941) 619-7568 Fax: (941) 701-7131
South East Asia
Singapore Regional Office Singapore, Republic of Singapore Phone: (65) 264-6422 Fax: (65) 264-6455
X:in:008:001
TP-5737 5/01 iIntroduction
Page 14
Notes
TP-5737 5/01ii Service Assistance
Page 15
Section 1 Specifications
1.1 Introduction
The spec sheets for each generator set provide specific generator and engine information. Refer to the respective spec sheet for data not supplied in this manual. Consult the generator set operation manual, generator installation manual, engine operation manual, and engine service manual for additional specifications.
1.2 Specifications
The generator set consists of a rotating-field generator combined with a smaller rotating-armature generator turned by a common shaft. The main rotating-field generator supplies current to the load circuits while the rotating-armature (exciter) generator supplies rectified AC (DC) to excite the main generator’s field.
Engine
Specification
Engine Prealarm and
Shutdown Switches
Anticipatory high engine temperature switch
Anticipatory low oil pressure switch
High engine temperature shutdown switch
Low oil pressure shutdown switch
High exhaust temperature switch (wet exhaust only)
Controller Gauge
Senders
Oil Pressure Sender
0kPa(0psi) 120 (+9/--8) 240 (+17/--15)
172 kPa (25 psi) 76.5 (+6/--7.5) 153 (+12/--15)
690 kPa (100 psi) 16.8 33.5
Water Temperature Sender
54° C (130° F) 100 ±15 180 ±12
82° C (180° F) 40 ±6 71 ±8
COZ/CFOZ and EOZ/EFOZ
Models
96_ C (205_ F) ±7
138 kPa ±14 kPa
(20 psi ±2)
103_ C (218_ F) ±7
103 kPa ±14 kPa
(15 psi ±2)
88--102_ C
(190--215_ F) ±5
Specification
(in ohms)
COZ/CFOZ
Models
Specification
(in ohms)
EOZ/EFOZ
Models
Generator
Component Specification Value
Controller/battery electrical system 12 or 24 volts DC
Generator field resistance (F+/ F--):
40/50COZ and 33/40CFOZ 2.0--2.9 ohms
65COZ and 50CFOZ 1.8--2.2 ohms
40EOZ and 33EFOZ 2.1--2.5 ohms
50EOZ and 40EFOZ 2.7--3.1 ohms
65/80EOZ and 55/70EFOZ 1.7--2.1 ohms
99EOZ and 80EFOZ 2.0--2.4 ohms
125EOZ and100EFOZ 1.4--1.8 ohms
150EOZ and 125EFOZ 1.6--2.0 ohms
Exciter armature resistance:
40/50COZ and 33/40CFOZ 0.13 ohms
65COZ and 50CFOZ 0.27 ohms
40EOZ and 33EFOZ 0.23 ohms
50EOZ and 40EFOZ 0.14 ohms
65/80EOZ and 55/70EFOZ 0.27 ohms
99EOZ and 80EFOZ 0.27 ohms
125EOZ and100EFOZ 0.27 ohms
150EOZ and 125EFOZ 0.27 ohms
SCR assembly terminal nut torque 1.4 Nm (12 in. lbs.)
Fan to rotor flange torque 29 Nm (260 in. lbs.)
Drive disks to rotor shaft torque 61 Nm (45 ft. lbs.)
Speed sensor air gap 0.36--0.71 mm
(0.014--0.028 in.)
Speed sensor voltage 2 (black) &
16 (white)
3--6 volts DC
2 (black) & 24 (red)
8--10 volts DC
Electronic governor magnetic pickup air gap
Magnetic pickup output voltage during cranking
Flex plate to flywheel bolt torque (3/8-16)
0.36--0.71 mm
(0.014--0.028 in.)
2.5 volts AC min.
52.9 Nm
(39 ft. lbs.)
TP-5737 5/01 1Section 1 Specifications
Page 16
1.3 Accessories
1.3.1 Remote Annunciator Kit
Kohler Co. offers several accessories to finalize the installation and to add convenience to operation and service. Accessories vary with each generator set model and controller. Kohler Co. offers accessories factory-installed and/or shipped loose. Some accessories are available only with microprocessor controllers. Obtain current information by contacting your local authorized service distributor/dealer. Several accessories available at the time of print of this publication are detailed in the following subsections.
Remote Annunciator
A remote annunciator allows convenient monitoring of the generator set’s condition from a remote location. See Figure 1-1. The flush-mounted annunciator panel extends all of the fault and prealarm lights/audio of the Decision-Maker 3+ controller. The remote annunciator includes an alarm horn, an alarm silence switch, a lamp test, and the same lamp indicators (except air damper and auxiliary prealarm) as the microprocessor controller, plus the following:
Line Power. Lamp illuminates to indicate the power source is shore power.
Generator Power. Lamp illuminates to indicate the power source is the generator set.
14-Relay Dry Contact Box
42A 2 K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K13 K14K12
CONTACTRATINGS: 10A@120VAC RES.LOAD
INPUT
NO C CNO CNO CNO CNO CNO CNO CNO CNO CNO CNO CNO CNO CNO
K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 K14
.01A@28VDC MIN.
10A@28VDC MAX.
42B
FBA--1
10 AMP
LOT NO.
P
Figure 1-1 Remote Annunciator with 14-Relay Dry Contact Kit
PCBASSY A--320639
N
P
A-344522­TP-5750-1
TP-5737 5/012 Section 1 Specifications
Page 17
1.3.2 Safeguard Breaker
1.3.4 Run Relay Kit
The safeguard breaker senses output current on each generator phase and shuts off the AC voltage regulator in the event of a sustained overload or short circuit. It is not a line circuit breaker and does NOT disconnect the generator from the load. See Figure 1-2.
X-796
Figure 1-2 Safeguard Breaker
1.3.3 Line Circuit Breaker
The line circuit breaker interrupts generator output in the event of an overload or short circuit. Use the kit to manually disconnect the generator set from the load when servicing the generator set. See Figure 1-3.
The run relay kit energizes only when the generator set is running. Typically, the three sets of contacts control air intake and/or compartment ventilation fans. However, alarms and other signalling devices can also connect to the contacts. See Figure 1-4.
273705
Figure 1-4 Run Relay Kit
TP-5352-1
Figure 1-3 Line Circuit Breaker
TP-5737 5/01 3Section 1 Specifications
Page 18
1.3.5 FASTCHECK Diagnostic Tester (Microprocessor Controller Only)
The FASTCHECKâdiagnostic tester simulates engine operation to identify faults in the controller and engine circuitry. Use the FASTCHECK startup problems or to test and troubleshoot the controller when the controller is removed from the generator. Perform tests without starting the generator set. Functions performed by the FASTCHECKâare listed below; refer to Figure 1-5 to identify LEDs and switches.
â
when troubleshooting
LEDs on the FASTCHECK
â
indicate the energizing of
the following circuits:
D Fuel solenoid (diesel) D Engine crank D AC voltage regulator D Battery connection (correct polarity) D Engine malfunction alarm and/or alarm shutdown
â
Switches on the FASTCHECK
D Engine cranking D Engine running D Engine overspeed D Low fuel D Low engine coolant temperature D Anticipatory low engine oil pressure D Anticipatory high engine coolant temperature D Low engine oil pressure D High engine coolant temperature
simulate the following:
B-291930
Figure 1-5 FASTCHECKâDiagnostic Tester
TP-5737 5/014 Section 1 Specifications
Page 19
2.1 Fast-Responset II Concepts
The generator excitation system uses a permanent magnet exciter with a silicon controlled rectifier (SCR) assembly that controls the amount of DC current fed to the generator field. This type of system uses a voltage regulator that signals the SCR assembly through an optocoupler. The voltage regulator monitors generator output voltage and engine speed and signals the SCR assembly to turn on or off accordingly through the optocoupler. The optical coupler consists of a light emitting diode (LED) mounted on the stationary end bracket and a photo transistor mounted on the rotating shaft. The photo transistor picks up the infrared signal from the LED and signals the SCR assembly to turn on or off, depending upon the need, as dictated by the voltage regulator. See Figure 2-1.
Section 2 Operation
2
3
1
4
7
5
6
8
The voltage recovery period of this type of generator is several times faster than the conventionally wound field brushless generator because the generator set does not have to contend with the inductance of the exciter field. The generator set also has better recovery characteristics than the static-excited machine because it is not dependent upon the generator set output voltage for excitation power. Possibly the greatest advantage of this type of machine is its inherent ability to support short-circuit current and allow system coordination for tripping downstream branch circuit breakers.
The generator set systems deliver exciter current to the main field within 50 milliseconds (0.050 seconds) of a change in load demand.
2.2 Short Circuit Performance
When a short circuit occurs in the load circuit(s) being served, output voltage drops and amperage momentarily rises to 600--1000% of the generator set’s rated current until removal of the short. The SCR assembly sends full exciter power to the main field. The generator then sustains up to 300% of its rated current. Sustained high current causes correspondingly rated load circuit fuses/breakers to trip. The safeguard breaker kit shuts down the excitation system in the event of a sustained heavy overload or short circuit.
12
11
13
16
1. Main armature
2. Main field
3. Main generator
4. Stator
5. SCR assembly
6. Exciter armature
7. Rotor
8. Exciter generator
9. Exciter field magnets
10. Optical coupler
11. LED board (PCB assembly)
12. Photo transistor board (PCB assembly)
13. AC voltage regulator
14. Starting battery
15. Safeguard breaker (optional)
16. Main output leads
15
Figure 2-1 Alternator Schematic
9
10
14
TP-5353-1
TP-5737 5/01 5Section 2 Operation
Page 20
2.3 Prestart Checklist
To ensure continued satisfactory operation perform the following checks or inspections before or at each startup, as designated, and at the intervals specified in the service schedule. In addition, some checks require verification after the unit starts.
Air Cleaner. Check for a clean and installed air cleaner element to prevent unfiltered air from entering the engine.
Air Inlets. Check for clean and unobstructed air inlets.
Air Shrouding. Check for securely installed and
positioned air shrouding.
Battery. Check for tight battery connections. Consult the battery manufacturer’s instructions regarding battery care and maintenance.
Fuel Level. Check the fuel level and keep the tank(s) full to ensure adequate fuel supply.
Oil Level. Maintain the oil level at or near, not over, the full mark on the dipstick.
Operating Area. Check for obstructions that could block the flow of cooling air. Keep the air intake area clean. Do not leave rags, tools, or debris on or near the generator set.
Seawater Pump Priming. Prime the seawater pump before initial startup. To prime the pump: (1) close the seacock, (2) remove the hose from the water-filter outlet, (3) fill the hose and seawater pump with clean water, (4) reconnect the hose to the water filter outlet, and (5) open the seacock. Confirm sea water pump operation on startup as indicated by water discharge from the exhaust outlet.
Coolant Level. Check the coolant level according to the cooling system maintenance information.
Drive Belts. Check the belt condition and tension of the water pump and battery charging alternator belt(s).
Exhaust System. Check for exhaust leaks and blockages. Check the silencer and piping condition and check for tight exhaust system connections.
Inspect the exhaust system components (exhaust manifold, mixing elbow, exhaust line, hose c lamps, silencer, and exhaust outlet) for cracks, leaks, and corrosion.
D Check the hoses for softness, cracks, leaks, or dents.
Replace the hoses as needed.
D Check for corroded or broken metal parts and replace
them as needed.
D Check for loose, corroded, or missing clamps.
Tighten or replace the hose clamps as needed.
D Check that the exhaust outlet is unobstructed.
D Visually inspect for exhaust leaks (blowby). Check
for carbon or soot residue on exhaust components. Carbon and soot residue indicates an exhaust leak. Seal leaks as needed.
D Ensure that the carbon monoxide detector is (1) in the
craft, (2) functional, and (3) energized whenever the generator set operates.
2.4 Marine Inspection
Kohler Co. recommends that all boat owners have their vessels—especially the exhaust system attached to the generator set—inspected at the start of each boating season by the local Coast Guard Auxiliary. If there is no Coast Guard Auxiliary in the area, contact an authorized Kohler distributor/dealer for the inspection.
m:op:001:003
2.5 Angular Operation
See Figure 2-2 for angular operation limits for units covered in this manual.
Intermittent—
Continuous
25_ 30_
Maximum value for all directions
3 minutes or less
Figure 2-2 Angular Operation
m:op:001:004
2.6 Exercising the Generator Set
Operate the generator set under load once each week for one hour with an operator present.
The operator should perform all of the prestart checks before starting the exercise procedure. Start the generator set according to the starting procedure in the controller section of this manual. While the generator set is operating, listen for a smooth-running engine and visually inspect the generator set for fluid or exhaust leaks.
x:op:001:005
TP-5737 5/016 Section 2 Operation
Page 21
2.7 Decision-Makerä 3+ 16-Light Microprocessor Controller Operation
Figure 2-3 identifies the Decision-Makert 3+ 16-light controller’s indicators and controls and their functions.
12 34 5 6
18
1. Fuses (inside controller)
2. Frequency meter
3. AC voltmeter
4. Controller TB1 and TB2 terminal strips (on circuit board)
5. AC ammeter
6. Scale lamps (upper/lower)
7. Selector switch
8. Annunciator panel lamps
9. Alarm silence switch
10. Lamp test
11. Generator set master switch
12. Alarm horn
13. DC voltmeter
14. Emergency stop switch, if equipped
15. Water temperature gauge
16. Voltage adjustment
17. Oil pressure gauge
18. Hourmeter
7
8
9
1011121314151617
ADV-5849 P1
Figure 2-3 Decision-Makert 3+, 16-Light Microprocessor Controller
TP-5737 5/01 7Section 2 Operation
Page 22
2.7.1 Controls and Indicators
The following table describes the controls and indicators located on the controller.
Name Description
AC ammeter The meter displays the AC output
AC voltmeter The meter displays the AC output
DC voltmeter The meter displays the voltage of
Alarm horn The horn sounds if any fault or
Alarm silence switch The switch disconnects the alarm
Auxiliary fault lamp The lamp flashes or lights when
Frequency meter The meter displays the frequency
Generator set master switch
High engine temperature lamp
Hourmeter The hourmeter records the
amperage. Use the selector switch to choose the phase current.
voltage. Use the selector switch to choose the output lead circuits.
the starting battery(ies).
anticipatory condition exists. Place the generator set master switch in the AUTO position before silencing the horn. See the Controller Resetting Procedure later in this section.
during service (place the generator set master switch in the AUTO position before silencing the alarm horn). Restore the alarm horn switches at all locations (controller, remote annunciator, and audio/visual alarm) to normal positions after correcting the fault shutdown to avoid reactivating the alarm horn. See the Controller Resetting Procedure later in this section.
the controller detects a fault. See the lamp conditions section following.
(Hz) of the generator set output voltage.
The switch functions as the controller reset and generator set operation switch.
The lamp illuminates if the generator set shuts down because of high engine temperature. Shutdown occurs 5 seconds after the engine reaches temperature shutdown range.
generator set total operating hours for reference in maintenance scheduling.
Lamp test switch The switch tests the controller
Low oil pressure lamp
Overcrank lamp The lamp illuminates and cranking
Overspeed lamp The lamp illuminates if the
Water temperature gauge
Oil pressure gauge The gauge displays the engine oil
Scale lamps (upper/lower)
Selector switch The switch selects the generator
Voltage adjustment potentiometer
indicator lamps.
The lamp illuminates if the generator set shuts down because of low oil pressure. Shutdown occurs 5 seconds after the engine reaches oil pressure shutdown range.
stops if the engine does not start after 45 seconds of continuous cranking or 75 seconds of cyclic cranking.
The cranking stops and overcrank lamp lights after 15 seconds if the starter or engine does not turn (locked rotor).
The overcrank lamp flashes if the speed sensor signal is absent longer than one second.
NOTE: The generator set controller’s automatic restart function attempts to restart the generator set if the engine speed drops below 13 Hz (390 rpm). Continued decreased engine speed causes an overcrank condition.
generator set shuts down because governed frequency on 50 and 60 Hz models exceeds 70 Hz.
The gauge displays the engine coolant temperature.
pressure.
The lamps indicate which AC voltmeter and/or ammeter scales to read.
set output circuits to measure. When switched to a position with two circuit labels, measure amperage on the lead shown in the upper label and measure voltage between the two leads shown in the lower label. The AC ammeter and voltmeter function only with the switch in the ON position.
The potentiometer fine-tunes (±5%) the generator set output voltage.
TP-5737 5/018 Section 2 Operation
Page 23
Name Description
Auxiliary prealarm lamp
The lamp illuminates when customer-provided sensing devices activate the pump.
Emergency stop lamp
The lamp illuminates and the generator set shuts down when energizing the optional emergency stop switch. The lamp needs the optional emergency stop switch to function.
Generator switch not in auto lamp
The lamp illuminates when the generator set master switch is in the RUN or OFF/RESET position.
Low fuel lamp The lamp illuminates when the fuel
level in the tank approaches empty. The lamp needs a low fuel sensor in the fuel tank to function.
High water temperature lamp
The lamp illuminates when the water temperature approaches shutdown range. The lamp needs an optional prealarm sender kit to function.
Prealarm high engine temperature lamp
The lamp illuminates when the engine coolant temperature approaches shutdown range. The lamp needs an optional prealarm sender kit to function.
Prealarm low oil pressure lamp
The lamp illuminates when the engine oil pressure approaches shutdown range. The lamp needs an optional prealarm sender kit to function.
System ready lamp The lamp illuminates when the
generator set master switch is in AUTO position and the system senses no faults.
Emergency stop switch
The switch, if activated, instantly shuts down the generator set in emergency situations. Use the emergency stop switch for emergency shutdowns only. Use the generator set master switch for normal shutdowns.
2.7.2 Fuses and Terminal Strips
The following table describes the controller circuit board fuses and controller terminal strips.
Name Description
3-amp remote annunciator fuse
3-amp controller fuse The fuse protects the controller
15-amp engine and accessories fuse
Controller TB1 terminal strip
Controller TB2 terminal strip
The fuse protects the remote annunciator circuit, A/V alarm, and isolated alarm kit, if equipped.
circuit board, speed sensor, and lamp circuit board.
Thefuseprotectsthe engine/starting circuitry and accessories.
The terminal strip provides connection points for customer-supplied sensing devices and generator set accessories such as the emergency stop switch, remote start stop/switch, audio/visual alarms, etc., to the controller. Figure 2-4 shows the location of the TB1 terminal strip on the controller circuit board. Refer to the wiring diagrams for information on connecting accessories to the TB1 terminal strip.
The terminal strip provides connection points for crank mode selection (cyclic or continuous) and remote start/stop switch inputs of operation. Figure 2-4 shows the location of the TB2 terminal strip on the controller circuit board. Refer to the wiring diagrams for connection information.
12
TP-5737 5/01 9Section 2 Operation
3
R41
LED4
P2
1. TB1 terminal strip
2. TB2 terminal strip
3. Fuses
P1
Figure 2-4 TB1 and TB2 Terminal Strips on
Decision-Makert 3+ Controller Circuit Board
A-336415-A
Page 24
2.7.3 Auxiliary Fault Lamp Conditions
2.7.4 Starting the Generator Set
The following descriptions define the possible auxiliary fault lamp conditions.
Flashing Lamp Conditions
No AC Output. The auxiliary lamp flashes immediately if the controller senses no AC output while the generator set runs (except during the first 10 seconds after startup). The flashing stops and the light goes out when the controller senses AC output. The controller requires no manual reset.
Low Battery Voltage. The auxiliary lamp flashes if the battery power was reconnected or was low and then restored while the generator set master switch was in the RUN or AUTO position. A possible cause is a temporary low battery condition when the battery is weak or undersized for the application. To clear the low battery voltage condition, place the generator set master switch in the OFF/RESET position.
Continuous-On Lamp Conditions
Emergency Stop Switch Energized. Upon activation of the emergency stop switch, if equipped, the auxiliary lamp lights and the generator set shuts down immediately.
Emergency Stop Switch Reset. Resetting the optional emergency stop switch while the generator set master switch is in the AUTO or RUN position causes the auxiliary lamp to light. Place the generator set master switch in the OFF/RESET position to clear the auxiliary lamp ON condition.
Note: Auxiliary Delay Shutdown. The auxiliary lamp
lights and the engine shuts down 5 seconds after the high oil temperature (P1-13) or auxiliary delay shutdown (P1-15) fault, if equipped, occurs. Auxiliary Delay Shutdown is inhibited during the first 30 seconds after crank disconnect.
The following procedures describe starting the generator set.
Local Starting (Nonautomatic). Move the generator set master switch to the RUN position to start the generator set at the controller.
Note: The alarm horn sounds whenever the generator
set master switch is not in the AUTO position.
Automatic (Auto) Starting. Move the generator set master switch to the AUTO position to allow startup by the automatic transfer switch or remote start/stop switch (connected to controller terminals TB1-3 and TB1-4).
Note: The transient start/stop function of the
Decision-Makert3+ controller prevents accidental cranking of the rotating engine. When the generator set master switch is momentarily placed in the OFF/RESET position, then quickly returned to RUN, the generator set slows to 249 rpm and then recranks before returning to rated speed.
Note: The Decision-Makert 3+ controller’s automatic
restart function attempts to restart the generator set if the engine speed drops below 390 rpm (generator output frequency of 13 Hz). Continued decreased engine speed causes an overcrank fault condition.
Crank Mode Selection
The Decision-Makert3+ controller cranks continuously for up to 45 seconds or cyclically for up to 75 seconds (crank 15 seconds, rest 15 seconds, crank 15 seconds, etc.) before overcrank shutdown. Select the crank mode (cyclic or continuous) on the controller circuit board terminal strip. For cyclic cranking, leave circuit board terminal TB2-9 open. For continuous cranking, attach a jumper between circuit board terminal TB2-9A (ground) and terminal TB2-9.
Note: Overvoltage Shutdown. If a generator set is
equipped with this kit, the auxiliary lamp lights and the engine shuts down immediately when an overvoltage condition occurs.
Note: Auxiliary Immediate Shutdown. The auxiliary
lamp lights and the engine shuts down immediately when any customer-supplied sensing devices connected to auxiliary immediate shutdown ports (P1-17 and P1-18) activate them.
x:op:005:004
2.7.5 Stopping the Generator Set
The following procedures describe stopping the generator set.
Normal Stopping
1. Cooldown. Run the generator set at no load for 5 minutes to ensure adequate engine cooldown.
2. Stopping. Move the generator set master switch to the OFF/RESET position. The engine stops.
TP-5737 5/0110 Section 2 Operation
Page 25
Note: The generator set continues running during
a 5-minute cooldown cycle if a remote switch or automatic transfer switch signals the engine to stop.
Emergency Stopping
Move the generator set master switch to the OFF/RESET position or activate the remote emergency stop, if equipped, for immediate shutdown. The controller AUXILIARY lamp lights and the generator set shuts down on activation of the emergency stop switch. The remote annunciator and/or A/V alarms, if equipped, signal an emergency stop.
2.7.6 Prime Power Mode Operation
The Decision-Makert 3+ controller operates in either the normal mode or the prime power mode. In prime power mode, the controller draws less current, minimizing the battery drain. Consider using the prime power mode for installations that do not have a battery charger.
Moving the generator set master switch to the OFF/RESET position disables all controller functions. Moving the generator set master switch to the AUTO position restores controller functions.
Enabling and Disabling the Prime Power Mode.
Enable the prime power mode by connecting jumpers across the following terminals on terminal strip TB2 on the controller circuit board:
D TB2-1P and TB2-2P
D TB2-3P and TB2-4P
D TB2-3 and TB2-4
See Figure 2-4. Remove the jumpers listed above to disable the prime power mode.
Prime Power Starting. The prime power mode provides local starting only at the controller. When the generator set master switch is in the OFF/RESET position, the controller functions are inoperative. Move the generator set master switch to the AUTO position to start the generator set. Do not start the generator set with the master switch in the RUN position because the alarm horn sounds.
Note: Move the generator set master switch to the
AUTO position to return controller functions to normal.
2.7.7 Fault Shutdowns
The generator set shuts down automatically under the following fault conditions and cannot be restarted until the fault condition is corrected. The system automatically resets when the problem is corrected or the generator set cools (if high engine temperature was the fault).
Name Description
High engine temperature
High exhaust temperature
Low coolant level (water-cooled engines only)
Low oil pressure Shutdown occurs 5 seconds after
Overcrank Shutdown occurs after 45 seconds
Overspeed Shutdown occurs immediately
Overvoltage (optional)
Shutdown occurs 5 seconds after the fault. The high engine temperature shutdown does not function during the first 5 seconds after startup.
NOTE: The high temperature shutdown functions only when the coolant level is in the operating range.
Shutdown occurs 5 seconds after the fault. The high exhaust temperature shutdown does not function during the first 5 seconds after startup.
Shutdown occurs 5 seconds after fault. The low coolant level shutdown does not function during the first 5 seconds after startup.
the fault. The low oil pressure shutdown does not function during the first 5 seconds after startup.
NOTE: The low oil pressure shutdown does not protect against low oil level. Check the engine oil level.
of continuous cranking or 75 seconds of cyclic cranking (crank 15 seconds, rest 15 seconds, crank 15 seconds, etc.).
when governed frequency on 50 and 60 Hz models exceeds 70 Hz.
The generator set shuts down and the auxiliary lamp lights when voltage is 15% or more over the nominal voltage for 2 seconds or longer.
NOTE: Overvoltage can damage sensitive equipment in less than one second. Install separate overvoltage protection on on-line equipment requiring faster shutdown.
x:op:005:007
Prime Power Stopping. Move the generator set master switch to the OFF/RESET position to stop the generator set and power down the controller.
TP-5737 5/01 11Section 2 Operation
Page 26
2.7.8 Controller Resetting Procedure (Following Fault Shutdown)
2.7.9 Resetting the Emergency Stop Switch
Use the following procedure to restart the generator set after a fault shutdown. Refer to Resetting the Emergency Stop Switch in this section to reset the generator set after an emergency stop.
1. Place the controller alarm horn silence switch in the SILENCE position. Place the A/V annunciator alarm switch, if equipped, in the SILENCE position to stop the alarm horn. The A/V annunciator lamp stays lit. (The A/V alarm uses one lamp to indicate a fault shutdown; the respective fault lamp on the remote annunciator lights to indicate a fault condition.)
2. Disconnect the generator set from the load using the line circuit breaker or automatic transfer switch.
3. Correct the cause of the fault shutdown. See the Safety Precautions at the beginning of this section before proceeding.
4. Place the generator set master switch in the OFF/RESET position and then in the RUN position to start the generator set. The A/V annunciator alarm horn sounds and the lamp, if equipped, darkens.
Use the following procedure to restart the generator set after an emergency stop switch shutdown. Refer to the Controller Resetting Procedure in this section to restart the generator set following a fault shutdown. The generator set does not crank until the operator completes the resetting procedure.
Note: The controller auxiliary lamp lights when the
generator set master switch is in the RUN or AUTO position during the resetting procedure.
Procedure to Restart the Generator Set After an Emergency Stop Shutdown:
1. Determine the cause of the emergency stop and correct the problem(s).
2. Reset the controller emergency stop switch by rotating the switch clockwise until the switch springs back to the original position. See Figure 2-3.
3. Toggle the generator set master switch to OFF/RESET and then to RUN or AUTO to restart the generator set.
5. Test operate the generator set to verify that the cause of the shutdown has been corrected.
6. Reconnect the generator set to the load via the line circuit breaker or automatic transfer switch.
7. Place the generator set master switch in the AUTO position for startup by a remote transfer switch or remote start/stop switch. Place the A/V annunciator alarm switch, if equipped, in the NORMAL position.
8. Place the generator set master switch in the AUTO position before silencing the alarm horn.
TP-5737 5/0112 Section 2 Operation
Page 27
2.8 Expanded Decision-Makert 1 Controller Operation
For identification of the expanded controller’s indicators and controls and their functions, refer to Figure 2-5.
13
1. Frequency meter
2. AC voltmeter
3. AC ammeter
4. Scale lamps (upper/lower)
5. Selector switch
6. Hourmeter
7. Generator set master switch
1
12
2
11
Figure 2-5 Expanded Decision-Makert 1 Controller
3
10
9
8. Voltage adjustment potentiometer
9. Fault lamp
10. 10-amp controller fuse
11. DC voltmeter
12. Water temperature gauge
13. Oil pressure gauge
4
8
7
5
6
ADV-5849E-B
x:op:002:001
2.8.1 Controls and Indicators
The following table describes the controls and indicators located on the controller.
Name Description
AC voltmeter The meter displays the AC output
AC ammeter The meter displays the AC output
DC voltmeter The meter displays the voltage of the
Fault lamp The lamp illuminates during engine
Frequency meter The meter displays the frequency (Hz)
Generator set master switch
Hourmeter The hourmeter records the generator
voltage. Use the selector switch to choose the output lead circuits.
amperage. Use the selector switch to choose the phase currents.
starting battery(ies).
shutdown if the engine shuts down because of one of the following faults: high engine temperature, low water level, low oil pressure, overcrank, or overspeed. See Section 2.8.4, Fault Shutdowns, for additional shutdown information.
of the generator set output.
The switch functions as the controller reset and generator set operation switch.
set total operating hours for reference in maintenance scheduling.
Oil pressure gauge
Scale lamps (upper/lower)
The gauge displays the engine oil pressure.
The lamps indicate which AC voltmeter and/or ammeter scales to read.
Selector switch The switch selects the generator set
output circuits to measure. When switched to a position with two circuit labels, measure amperage on the lead shown in the upper label and measure voltage between the two leads shown in the lower label. The AC ammeter and voltmeter function only with the switch in the ON position.
Voltage adjustment
The potentiometer fine-tunes (±5%) the generator set output voltage.
potentiometer
Water temperature
The gauge displays the engine coolant temperature.
gauge
10-amp controller fuse
The fuse protects the controller circuitry from short circuits and overloads.
TP-5737 5/01 13Section 2 Operation
Page 28
2.8.2 Starting the Generator Set
The following procedure describes the actions required to start the generator set.
Local Starting. Move the generator set to the RUN position to immediately start the generator set.
Auto (Automatic) Starting. Move the generator set master switch to the AUTO position to allow startup by the automatic transfer switch or the remote start/stop switch (connected to controller terminals TB1-3 and TB1-4).
Note: The controller provides up to 30 seconds of
continuous cranking before overcrank shutdown occurs.
x:op:002:003
2.8.3 Stopping the Generator Set
2.8.5 Controller Resetting Procedure (Following Fault Shutdown)
Use the following procedure to restart the generator set after a fault shutdown.
1. Disconnect the generator set from the load using the line circuit breaker or automatic transfer switch. See the Safety Precautions at the beginning of this section before proceeding.
2. Correct the cause of the fault shutdown. See the Safety Precautions at the beginning of this section before proceeding.
3. Start the generator set by moving the generator set master switch to RESET/OFF and then to RUN.
4. Verify that the cause of the shutdown has been corrected by test operating the generator set.
The following procedure describe how to stop the generator set.
Normal Stopping
1. Cooldown. Run the generator set at no load for 5 minutes to ensure adequate engine cooldown.
2. Stopping. Move the generator set master switch to the OFF/RESET position. The engine stops.
x:op:002:004
2.8.4 Fault Shutdowns
The generator set shuts down automatically under the following fault conditions and cannot be restarted until the fault condition is corrected. The system automatically resets when the problem is corrected or the generator set cools (if high engine temperature was the fault).
The fault lamp does not stay lit after the generator set shuts down on a fault condition.
5. Reconnect the generator set to the load using the line circuit breaker or automatic transfer switch.
6. Move the generator set master switch to the AUTO position for startup by remote transfer switch or remote start/stop switch.
Fault Description
High engine temperature
High exhaust temperature
Low coolant level Shutdown occurs 5 seconds after the
Low oil pressure Shutdown occurs 5 seconds after the
Overcrank Shutdown occurs after 30 seconds of
Overspeed Shutdown occurs immediately when
Shutdown occurs 5 seconds after the fault. The high engine temperature shutdown does not function during the first 5 seconds after startup.
Note: The high temperature shutdown functions only when the coolant level is in the operating range.
Shutdown occurs 5 seconds after the fault. The high exhaust temperature shutdown does not function during the first 5 seconds after startup.
fault. The low coolant level shutdown does not function during the first 5 seconds after startup.
fault. The low oil pressure shutdown does not function during the first 5 seconds after startup.
Note: The low oil pressure shutdown does not protect against low oil level. Check the oil level at the engine.
continuous cranking. Shutdown occurs after 30 seconds if the engine or starter does not turn (locked rotor).
the governed frequency on the 50 and 60 Hz models exceeds 70 Hz.
x:op:002:006
TP-5737 5/0114 Section 2 Operation
Page 29
2.9 Standard Decision-Makert 1 Controller Operation
For identification of the standard basic controller’s indicators and controls and their functions, refer to Figure 2-6.
1
2.9.2 Starting the Generator Set
The following procedures describe the actions required to start the generator set.
Local Starting. Move the generator set master switch to the RUN position to immediately start the generator set.
Automatic (Auto) Starting. Move the generator set master switch to the AUTO position to allow startup by the automatic transfer switch or the remote start/stop switch (connected to controller terminals TB1-3 and TB1-4).
Note: The controller provides up to 30 seconds of
continuous cranking before the overcrank shutdown occurs.
x:op:004:003
345
1. Hourmeter
2. Voltage adjustment
3. 10-amp controller fuse
4. Fault lamp
5. Generator set master switch
2
A-227600
Figure 2-6 Decision-Makert 1 Controller
x:op:004:001
2.9.1 Controls and Indicators
The following table describes the controls and indicators located on the controller.
Name Description
Fault lamp Lamp illuminates during engine
Generator set master switch
Hourmeter Hourmeter records the generator
Voltage adjust potentiometer
10-amp controller fuse
shutdown if the engine shuts down because of one of the following faults: high engine temperature, low water level, low oil pressure, overcrank, or overspeed. See Section 2.9.4, Fault Shutdowns, for additional shutdown information.
Switch functions as the controller reset and generator operation switch.
set total operating hours for reference in maintenance scheduling.
Potentiometer fine-tunes (±5%) generator output voltage.
Fuse protects the controller circuitry from short circuits and overloads.
x:op:004:002
2.9.3 Stopping the Generator Set
The following procedure describe how to stop the generator set.
Normal Stopping
1. Cooldown. Run the generator set at no load for 5 minutes to ensure adequate engine cooldown.
2. Stopping. Move the generator set master switch to the OFF/RESET position. The engine stops.
x:op:004:004
TP-5737 5/01 15Section 2 Operation
Page 30
2.9.4 Fault Shutdowns
The generator set shuts down automatically under the following fault conditions and cannot be restarted until the fault condition is corrected. The system automatically resets when the problem is corrected or the generator set cools (if high engine temperature was the fault).
Fault Description
High engine temperature
High exhaust temperature
Low coolant level Shutdown occurs 5 seconds after
Low oil pressure Shutdown occurs 5 seconds after
Overcrank Shutdown occurs after 30 seconds
Overspeed Shutdown occurs immediately
Shutdown occurs 5 seconds after the fault. The high engine temperature shutdown does not function during the first 5 seconds after startup.
NOTE: The high temperature shutdown functions only when the coolant level is in the operating range.
Shutdown occurs 5 seconds after the fault. The high exhaust temperature shutdown does not function during the first 5 seconds after startup.
the fault. Low coolant level shutdown does not function during the first 5 seconds after startup.
the fault. Low oil pressure shutdown does not function during the first 5 seconds after startup.
NOTE: The low oil pressure shutdown does not protect against low oil level. Check the oil level at the engine.
of continuous cranking. Shutdown occurs after 30 seconds if the engine or starter does not turn (locked rotor).
when the governed frequency on 50 and 60 Hz models exceeds 70 Hz.
x:op:004:005
2.9.5 Controller Resetting Procedure (Following Fault Shutdown)
Use the following procedure to restart the generator set after a fault shutdown.
1. Disconnect the generator set from the load using the line circuit breaker or automatic transfer switch. See the Safety Precautions at the beginning of this section before proceeding.
2. Correct the cause of the fault shutdown. See the Safety Precautions at the beginning of this section before proceeding.
3. Start the generator set by moving the generator set master switch to RESET/OFF and then to RUN.
4. Verify that the cause of the shutdown has been corrected by test operating the generator set.
5. Reconnect the generator set to the load using the line circuit breaker or automatic transfer switch.
6. Move the generator set master switch to the AUTO position for startup by remote transfer switch or remote start/stop switch.
x:op:004:006
TP-5737 5/0116 Section 2 Operation
Page 31
Section 3 Scheduled Maintenance
3.1 General Maintenance
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
WARNING
WARNING
Rotating parts. Can cause severe injury or death.
Operate the generator set only when all guards, screens, and covers are in place.
Servicing the generator set when it is operating. Exposed moving parts can cause severe injury or death. Keep
hands, feet, hair, clothing, and test leads away from the belts and pulleys when the generator set is running. Replace guards, screens, and covers before operating the generator set.
See the Safety Precautions and Instructions at the beginning of this manual before attempting to service, repair, or operate the generator set. Have an authorized distributor/dealer perform generator set service.
Engine Service. Perform generator set engine service at the intervals specified by the engine operation manual.
Generator Set Service. Perform generator set service at the intervals specified by the generator set operation manual.
If the generator set operates under dusty or dirty conditions, use dry compressed air to blow dust out of
Hot engine and exhaust system. Can cause severe injury or death.
the alternator. With the generator set running, direct the stream of air in through the cooling slots at the alternator end.
Do not work on the generator set until it cools.
Service Log. Use the Operating Hour Service Log located in the back of this manual to document
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts. The
engine and exhaust system components become extremely hot during operation.
performed services.
Service Schedule. Perform maintenance on each item in the service schedule at the designated intervals for the life of the generator set. For example, an item requiring service every 100 hours or 3 months also requires service after 200 hours or 6 months, 300 hours or 9 months, and so on.
x:sm:004:001
TP-5737 5/01 17Section 3 Scheduled Maintenance
Page 32
3.2 Generator Bearing
3.3.3 Fuel System
Replace the end bracket bearing every 10,000 hours of operation. Service more frequently if bearing inspection indicates excessive rotor end play or bearing damage from corrosion or heat buildup. Replace the tolerance ring, if equipped, if removing the end bracket. The end bracket bearing is sealed and requires no additional lubrication. Have all generator service performed by an authorized service distributor/dealer.
3.3 Storage Procedure
Perform the following storage procedure before taking a generator set out of service for three months or longer. Follow the engine manufacturer’s recommendations, if available, for fuel system and internal engine component storage.
x:sm:002:001
3.3.1 Lubricating System
Prepare the engine lubricating system for storage as follows:
1. Run the generator set for a minimum of 30 minutes to bring it to normal operating temperature.
2. Stop the generator set.
3. With the engine still warm, drain the oil from the crankcase.
Prepare the fuel system for storage as follows:
Diesel-Fueled Engines
1. Fill the fuel tank with #2 diesel fuel.
2. Condition the fuel system with compatible additives to control microbial growth.
3. Change the fuel filter/separator and bleed the fuel system. See the engine service manual.
3.3.4 Exterior
Prepare the exterior for storage as follows:
1. Clean the exterior surface of the generator set.
2. Seal all engine openings except for the air intake with nonabsorbent adhesive tape.
3. To prevent impurities from entering the air intake and to allow moisture to escape from the engine, secure a cloth over the air intake.
4. Mask electrical connections.
5. Spread a light film of oil over unpainted metallic surfaces to inhibit rust and corrosion.
x:sm:002:006a
3.3.5 Battery
4. Remove and replace the oil filter.
5. Refill the crankcase with oil suited to the climate.
6. Run the generator set for two minutes to distribute the clean oil.
7. Stop the generator set.
8. Check the oil level and adjust, if needed.
x:sm:002:002
3.3.2 Cooling System
Prepare the cooling system for storage as follows:
1. Check the coolant freeze protection using a coolant tester.
2. Add or replace coolant as necessary to ensure adequate freezing protection. Use the guidelines included in the engine operation manual.
3. Run the generator set for 30 minutes to redistribute added coolant.
x:sm:002:003
Perform battery storage after all other storage procedures.
1. Place the generator set master switch in the OFF/RESET position.
2. Disconnect the battery(ies), negative (--) lead first.
3. Clean the battery. Refer to the battery manufacturer’s instructions for the battery cleaning procedure.
4. Place the battery in a cool, dry location.
5. Connect the battery to a float/equalize battery charger or charge it monthly with a trickle battery charger. Refer to the battery charger manufacturer’s recommendations.
6. Maintain a full charge to extend battery life.
TP-5737 5/0118 Section 3 Scheduled Maintenance
Page 33
Section 4 General Troubleshooting
This section contains generator set troubleshooting, diagnostic, and repair information.
Use the following chart as a quick troubleshooting reference. The table groups generator set faults and suggests likely causes and remedies. The table also refers you to more detailed information including sections of this manual, the generator set operation manual (O/M), the generator set installation manual (I/M), and the engine service manual (Engine S/M) to correct the indicated problem.
Corrective action and testing often require knowledge of electrical and electronic circuits. To avoid additional problems caused by incorrect repairs, have an authorized service distributor/dealer perform service.
NOTICE
Fuse replacement. Replace fuses with fuses of the same ampere rating and type (for example: 3AB or 314, ceramic). Do not substitute clear glass-type fuses for ceramic fuses. Refer to the wiring diagram when the ampere rating is unknown or questionable.
Maintain a record of repairs and adjustments performed on the equipment. If the procedures in this manual do not explain how to correct the problem, contact an authorized distributor/dealer. Use the record to help describe the problem and repairs or adjustments made to the equipment.
x:gt:001:002a:
TP-5737 5/01 19Section 4 General Troubleshooting
Page 34
Section or
Reference*
Publication
Section 2
Move the controller master switch to the RUN or AUTO
position.
Section 2, W/D
Section5or6
troubleshoot the controller.[
Replace the controller master or start/stop switch.
Troubleshoot the controller.[
Eng. O/M
cooling system.
Restore the coolant to normal operating level. Gen. O/M
Trouble Symptoms
Probable Causes Recommended Actions
abnormal noise Excessive or
consumption High fuel
pressure Low oil
Overheats
Lacks power
suddenly Stops
output voltage No or low
Starts hard
does not start Cranks but
crank Does not
Controller
OFF/RESET position
x Controller master switch in the
x x x Controller fuse blown Replace the blown controller fuse. If the fuse blows again,
x x Controller circuit breaker tripped Reset the controller circuit breaker. Section 2
inoperative
x Controller fault
x Controller master or start/stop switch
x x Controller circuit board(s) inoperative Replace the controller circuit board. Section5or6
x x Air openings clogged Clean the air openings.
Cooling System
x Impeller inoperative Replace the impeller Gen. O/M
x x Seawater strainer clogged or restricted Clean the strainer. Gen. O/M
x High temperature shutdown Allow the engine to cool down. Then troubleshoot the
equipped
x Low coolant level shutdown, if
x Coolant level low Restore the coolant to normal operating level. Gen. O/M
x Thermostat inoperative Replace the thermostat. Eng. S/M
x Cooling water pump inoperative Tighten or replace the belt. Replace the water pump. Eng. O/M or S/M
Manual; S/S—Spec Sheet; W/D—Wiring Diagram Manual
[ Have an authorized service distributor/dealer perform this service.
* Sec./Section—numbered section of this manual; ATS—Automatic Transfer Switch; Eng.—Engine; Gen.—Generator Set; I/M—Installation Manual; O/M—Operation Manual; S/M—Service
20 Section 4 Troubleshooting
TP-5737 5/01
Page 35
Section or
Section or
Reference*
Reference*
Publication
Publication
Recommended ActionsProbable Causes
Recommended ActionsProbable Causes
Eng. O/M
Verify that the battery connections are correct, clean, and
tight.
S/S
recommended battery CCA rating.
W/D
Disconnect the engine harness connector(s) then
Eng. S/M
S/S
I/M
I/M
Section 7
Eng. S/M
reconnect it to the controller.
Replace the inoperative switch. Gen. S/M or W/D
Replace the inoperative switch. Gen. S/M
Check the compression.[
sheet for wattage specifications.
exhaust system components.[
system components.[
Adjust the governor.[
Adjust the valves.[
x x Battery connections loose, corroded,
Electrical System (DC circuits)
or incorrect
x x Battery weak or dead Recharge or replace the battery. The spec sheet provides
abnormal noise Excessive or
consumption High fuel
pressure Low oil
Overheats
Lacks power
suddenly Stops
output voltage
Trouble Symptoms
TP-5737 5/01 21Section 4 Troubleshooting
No or low
Starts hard
does not start Cranks but
crank Does not
x x Engine harness connector(s) not
locked tight
x Fault shutdown Reset the fault switches and troubleshoot the controller. Section 2
inoperative
x High exhaust temperature switch
x x Starter/starter solenoid inoperative Replace the starter or starter solenoid. Eng. S/M
inoperative
x High water temperature switch
Engine
x x x x Air cleaner clogged Clean or replace the filter element. Gen. O/M
x x x x x Compression weak
x x x x x Engine overload Reduce the electrical load. See the generator set spec
x Exhaust system leak Inspect the exhaust system. Replace the inoperative
x Exhaust system not securely installed Inspect the exhaust system. Tighten the loose exhaust
x Vibration excessive Tighten all loose hardware.
x x Valve clearance incorrect
x x x x Governor inoperative
Manual; S/S—Spec Sheet; W/D—Wiring Diagram Manual
[ Have an authorized service distributor/dealer perform this service.
* Sec./Section—numbered section of this manual; ATS—Automatic Transfer Switch; Eng.—Engine; Gen.—Generator Set; I/M—Installation Manual; O/M—Operation Manual; S/M—Service
Page 36
Section or
Section or
Reference*
Reference*
Publication
Publication
Recommended ActionsProbable Causes
Recommended ActionsProbable Causes
Eng. S/M
Troubleshoot the fuel solenoid.[
Eng. S/M
Clean, test, and/or replace the inoperative fuel injector.[
Eng. S/M
Adjust the fuel injection timing.[
Eng. S/M
Rebuild or replace the injection pump.[
bp #
Section 7
Section 7
Section 7
generator side of the circuit breaker.
Move the transfer switch test switch to the AUTO position. AT S O /M
Check for continuity. Section 7, W/D
Test and/or replace the rotor.[
Test and/or replace the stator.[
Tighten loose components.[
troubleshoot the voltage regulator.
Eng. O/M
Change the oil. Use oil with a viscosity suitable for the
operating climate.
abnormal noise Excessive or
consumption High fuel
pressure Low oil
Overheats
Lacks power
suddenly Stops
output voltage
Trouble Symptoms
22 Section 4 Troubleshooting
No or low
Starts hard
does not start Cranks but
x x Fuel tank empty or fuel valve shut off Add fuel and move the fuel valve to the ON position.
crank Does not
Fuel System
x x x x Fuel filter restriction Clean or replace the fuel filter. Eng. O/M
x Fuel solenoid inoperative
x x x Air in fuel system (diesel only) Bleed the diesel fuel system. Eng. O/M
(diesel only)
x x x Fuel or fuel injectors dirty or faulty
(diesel only)
(diesel only)
x x x x Fuel injection timing out of adjustment
x x x Fuel feed or injection pump inoperative
x AC output circuit breaker open Reset the breaker and check for AC voltage at the
Generator
position
x Transfer switch test switch in the OFF
field open
x Wiring, terminals, or pin in the exciter
grounded)
x Main field (rotor) inoperative (open or
x Vibration excessive
x Stator inoperative (open or grounded)
x x Voltage regulator out of adjustment Adjust the voltage regulator. Section 7
x x Voltage regulator inoperative Replace the voltage regulator fuse, If the fuse blows again,
x x x Oil level low Restore the oil level. Inspect the generator set for oil leaks. Eng. O/M
Lube System
ambient temperature
x Low oil pressure shutdown Check the oil level. Eng. O/M
x x x x Crankcase oil type incorrect for
TP-5737 5/01
Manual; S/S—Spec Sheet; W/D—Wiring Diagram Manual
[ Have an authorized service distributor/dealer perform this service.
* Sec./Section—numbered section of this manual; ATS—Automatic Transfer Switch; Eng.—Engine; Gen.—Generator Set; I/M—Installation Manual; O/M—Operation Manual; S/M—Service
Page 37
Section 5 Decision-Makert 3+ Troubleshooting
5.1 Decision-Makert 3+ Controller
For external features, see Section 2, Operation. Figure 5-1 through Figure 5-11 show the locations of controller components and connections. Figure 5-12
1
3
contains the logic schematic showing input/output circuits for reference in troubleshooting. This information deals directly with the 16-light microprocessor.
4
625
12
1. Selector switch
2. Lamp circuit board
3. Panel lamps
4. Controller DC ground terminal
5. AC fuse terminal block (TB3)
6. CT/meter scale terminal block (TB2)
Figure 5-1 Decision-Makerä 3+ Controller
TP-5737 5/01 23Section 5 Decision-Makert 3+ Troubleshooting
11 7
7. Accessory wire guide loops
8. Controller fuses
9. Lamp selection jumper
10. Control panel harness connector (P2)
11. Controller main circuit board
12. P3/P4 harness
10 9
8
A-328917-X
Page 38
15
14
16
321
4
5
6
7
13 11 91012 8
1. K2 relay: control relay (crank)
2. K3 relay: control relay (run)
3. K4 relay: emergency stop
4. LED1
5. Microprocessor chip
6. TB1 terminal strip
7. TB2 terminal strip
8. P3 connector (control panel harness) to P4 (LED indicator panel assembly)
9. LED4 (K4 relay)
10. P1 connector (DC harness)
11. LED3 (K3 relay)
12. P2 connector (AC harness)
13. LED2 (K2 relay)
14. Fuse: 3 amp (F1) remote annunciator
15. Fuse: 3 amp (F2) controller
16. Fuse: 15 amp (F3) engine and accessories
Figure 5-2 Decision-Makerä 3+ Controller Circuit Board Components, Typical
A-336415-L
TP-5737 5/0124 Section 5 Decision-Makert 3+ Troubleshooting
Page 39
5.1.1 Decision-Maker 3+ Circuit Board Terminal/Connector Identification
Terminal Wire Description
1 1A Emergency stop relay (K4) coil
2 1 Ground—emergency stop relay (K4)
3 42A Battery voltage (fuse #1 protected)
4 2 Ground
5 70C Generator in cool-down mode signal
6 70R Generator in running mode signal
7 56 Air damper indicator, if equipped
8 48 Emergency stop indicator
9 32A Common fault/prealarm
10 26 Auxiliary indicator
11 12 Overcrank indicator
12 39 Overspeed indicator
13 38 Low oil pressure indicator
14 36 High engine temperature indicator
15 60 System ready indicator
16 80 Not-in-auto indicator
17 41 Prealarm low oil pressure indicator
18 62 Low battery volts (active low*)
19 32 Common fault/prealarm
20 35 Low water temperature
21 40 Prealarm high engine temperature
indicator
22 63 Low fuel (active low*)
23 61 Battery charger fault (active low*)
* Check the operation of active low circuits by placing ground on
terminals so designated.
Figure 5-3 Terminal Strip TB1
Pin Description
1 Output to K1 relay (crank relay), wire 71
2 Ground for speed sensor, wire 2
3 Output to safeguard breaker terminal, wire 70 (and
K5 relay if equipped with electronic governor)
4 Not used
5 Ground (--), wire N
6 Speed sensor shield ground, wire S2
7 Output to fuel solenoid (FS), wire 70
8 Battery positive to speed sensor, wire 24
9 Input from speed sensor, wire 16
10 Not used
11 Not used
12 Input from battery positive (14P)
13 Not used
14 Input from high exhaust temperature switch,
wire 31
15 Not used
16 Input from pre-high engine temperature switch, wire
40A
17 Input from aux. immediate shutdown
18 Not used
19 Not used
20 Not used
21 Input from high engine temperature switch, wire 34
22 Input from low oil pressure switch, wire 13
23 Input from pre-low oil pressure switch, wire 41A
24 Not used
* Check the operation of active low circuits by placing ground on
terminals so designated.
Figure 5-5 P1 Connector Pins
Terminal Wire Description
1 1P Prime power operation (requires
optional kit)
2 2P Prime power operation (requires
optional kit)
3 3P Prime power operation (requires
optional kit)
4 4P Prime power operation (requires
optional kit)
5 9 Crank mode (open-cyclic ground
continuous)
6 9A Crank mode ground
7 4 Remote start (active low*)
8 3 Remote start (ground)
* Check the operation of active low circuits by placing ground on
terminals so designated.
Pin Description
1 Output to engine gauge, wire 70
2 Not used
3 Input for AC crank disconnect & instrumentation,
wire V7F
4 Not used
5 Input for AC crank disconnect & instrumentation,
wire V0
6 Engine ground, wire 2
Figure 5-6 P2 Connector Pins
Figure 5-4 Terminal Strip TB2
TP-5737 5/01 25Section 5 Decision-Makert 3+ Troubleshooting
Page 40
Pin Description
1 Ground (--), front panel, wire 2
2 Not used
3 Not used
4 Input from generator set master switch, auto
position, wire 46
5 Not used
6 Voltage (+) to front panel, wire 24
7 Output to low oil pressure indicator, wire 38
8 Output to overspeed indicator, wire 39
9 Output to overcrank indicator, wire 12
10 Output to auxiliary indicator, wire 26
11 Output to emergency stop lamp, wire 48
12 Output to pre-high engine temperature indicator,
wire 40
13 Output to high engine temperature indicator, wire 36
14 Output to system ready indicator, wire 60
15 Output to not-in-auto indicator, wire 80
16 Output to low water temperature indicator, wire 35
17 Output to pre-low oil pressure indicator, wire 41
18 Output to air damper indicator, if equipped, wire 56
19 Output to low battery volts indicator, wire 62
20 Output to battery charger fault indicator, wire 61
21 Output to low fuel indicator, wire 63
22 Output to common alarm, wire 32 23 Input from generator master switch, off/reset
position, wire 43
24 Input from generator set master switch, run position,
wire 47
Figure 5-7 P3 Connector Pins
Pin Description
1 Ground (--), front panel, wire 2
2 Not used
3 Not used
4 Output from generator set master switch, auto
position, wire 46
5 Not used
6 Voltage (+) to front panel, wire 24
7
Input to low oil pressure indicator, wire 38[
8
Input to overspeed indicator, wire 39[
9
Input to overcrank indicator, wire 12[
10 Input to auxiliary indicator, wire 26
11 Input to emergency stop lamp, wire 48
12 Input to pre-high engine temperature indicator, wire
40[
13
Input to high engine temperature indicator, wire 36[
14 Input to system ready indicator, wire 60
15 Input to not-in-auto indicator, wire 80
16
Input to low water temperature indicator, wire 35[
17
Input to pre-low oil pressure indicator, wire 41[
18 Input to air damper indicator, if equipped, wire 56
19 Input to low battery volts indicator, wire 62
20 Input to battery charger fault indicator, wire 61
21
Input to low fuel indicator, wire 63[
22
Input to common alarm, wire 32[
23 Output from generator master switch, off/reset
position, wire 43
24 Output from generator set master switch, run
position, wire 47
[ Common alarm triggered by high engine temp., high engine temp.
prealarm, low oil pressure, low oil pressure prealarm, low water temp., overcrank, overspeed, low fuel, and auxiliary faults.
Figure 5-8 P4 Connector Pins
TP-5737 5/0126 Section 5 Decision-Makert 3+ Troubleshooting
Page 41
Common Fault Indicator Activated By:
HWT AWT LOP AOP LWT OC OS LF AUX
Connect AV Alarm or Common Fault Relay Kit
Emergency Stop
E.STOP
Running Mode
Cool-Down Mode
B+
B--
AUX
OC
OS
LOP
HWT
System Ready
NIA
AOP
AWT
Common Fault /Prealarm (Line 2)
Low Battery
Common Fault /Prealarm (Line 1)
LWT
Low Fuel
Battery Charger Fault
Prime Power Operation
(--)
(--)
Crank Mode
Remote Switch
A-336415-L
Figure 5-9 Decision-Makerä 3+ Controller Connections (TB1 and TB2 terminal strips)
TP-5737 5/01 27Section 5 Decision-Makert 3+ Troubleshooting
Page 42
V7
120 VAC for Crank Disconnect
OP
WT
--
BATTERY
VO
BV HR
Voltage Reg.
2
Safeguard Circuit Breaker
+
6
3
5
2
1
4
P2
Panel Lamps
1B
Ign. B+
K5
70
Magnetic
Pickup
14N
K1 71
P1
1
FS
14P
16
2
24
Alternator Flash
70
PHET
4
40A
41A
PLOP
0
+
--
70
31
LOP
HXT
13
21
24
HET
AOP Anticipatory (Low) Oil Pressure AUX. Auxiliary AUX PRE Auxiliary Prealarm AWT Anticipatory (High) Water Temperature BCF Battery Charger Fault EAD Engine Air Damper E. STOP Emergency Stop FS Fuel Solenoid HWT High Water Temperature HXT High Exhaust Temperature LBV Low Battery Volts LF Low Fuel
34
LOP Low Oil Pressure LWT Low Water Temperature NIA Not In Auto OC Overcrank OS Overspeed SG Safeguard Circuit Breaker SYS RDY System Ready WLS Water Level Switch
Auxiliary Immediate Shutdown Switch
Figure 5-10 Decision-Makerä 3+ Controller Connections (P1 and P2)
Input
Output
A-336415-L
TP-5737 5/0128 Section 5 Decision-Makert 3+ Troubleshooting
Page 43
AOP Anticipatory (Low) Oil Pressure AUX. Auxiliary AUX PRE Auxiliary Prealarm AHET Anticipatory High Engine Temperature AWT Anticipatory (High) Water Temperature BC Battery Charger Fault EAD Engine Air Damper ES Emergency Stop FS Fuel Solenoid HET High Engine Temperature HWT High Water Temperature LBV Low Battery Volts LF Low Fuel LOP Low Oil Pressure LWT Low Water Temperature NIA Not-In-Auto OC Overcrank OS Overspeed SG Safeguard Circuit Breaker SYS RDY System Ready WLS Water Level Switch
Input
Output
Controller Circuit Board
T27
AUX PRE
TB1-- 26
TB1-- 12
TB1-- 39
TB1-- 32
P3
On
BC
TB1-- 56
AOP LW TLBVLF NIA
EAD
Controller 16-Light LED Indicators
TB1-- 35
TB1-- 41
TB1-- 62
TB1-- 61
TB1-- 63
TB1-- 36
TB1-- 40
AHET
TB1-- 48
TB1-- 16
ES AUX
TB1-- 60
TB1-- 80
SYS RDY
TB1-- 38
12V REG.
Off/Reset
123456789101112131415161718192021222324
Run
Generator Control Switch
Auto
Grd.
Switch Logic
AUTO
OFF/ RESET
RUN
A-336415-L
Horn
Silence
Lamp Test
OC OS LOPHET
Alarm Horn
Figure 5-11 Decision-Makerä 3+ to 16-Light LED Indicator Panel Connections (P3)
TP-5737 5/01 29Section 5 Decision-Makert 3+ Troubleshooting
Page 44
Figure 5-12 Logic Schematic, Decision-Makerä 3+
ADV-6122-B
TP-5737 5/0130 Section 5 Decision-Makert 3+ Troubleshooting
Page 45
5.1.2 Fault Shutdowns,
p
Highenginetemperaturelamp
p
g
Aux
Decision-Maker 3+ Controller
If the generator set does not start or stops running because of a fault shutdown (fault lamp lit), refer to
Indicator Fault Condition/Causes
Figure 5-13 to identify fault conditions. Consult the Engine Service Manual for detailed information on correcting engine-related faults. To reset the set after a fault shutdown, see Section 2, Operation.
Highengine temperature lam lights
Low oil pressure lamp lights Engine oil pressure is below shutdown range, see Section 1, Specifications
Overspeed lamp lights Governed frequency is in excess of 70 Hz (2100 rpm)
Overcrank lamp lights
Overcrank lamp flashes Speed sensor signal is absent longer than one second
Auxiliary lamp flashes
iliary lamp lights
Emergency stop, ifequipped
Multiple lamps light (where illumination may appear dim)
Engine coolant temperature is above shutdown range; see Section 1, Specifications
Cooling system malfunction
Continuous cranking is more than 45 seconds
Cyclic cranking is more than 75 seconds
Locked rotor
No AC output is present
Battery power was reconnected or was low and then came back up again while generator set master switch was in the RUN or AUTO position
Optional emergency stop switch is reset while the generator set master switch is in the RUN or AUTO position
High exhaust temperature (P1-14) or auxiliary delay shutdown (P1-15) faults occur,if sensor equipped
Overvoltage, if equipped, has occurred, voltage 15% greater than nominal voltage (for period longer than two seconds)
Activated by customer-supplied sensing device connected to auxiliary immediate shutdown ports (P1-17 and P1-18)
Emergency stop switch is activated (local or remote)
Emergency stop switch(es) are disconnected from controller terminals TB1-1 or 1A
Main circuit board F1 (3-amp) fuse blown. F1 fuse supplies battery voltage to a remote annunciator and/or dry contact kit.
Figure 5-13 Fault Shutdown Troubleshooting Chart
TP-5737 5/01 31Section 5 Decision-Makert 3+ Troubleshooting
Page 46
5.2 Microprocessor Controller
Relay Descriptions
A description of the controller and generator relays follows. Use this information to troubleshoot the generator set in conjunction with the troubleshooting microprocessor controller flowcharts on the following pages. Use the troubleshooting section following and the respective wiring diagram for additional information.
5.2.1 K1 Relay, Starter Solenoid
The K1 relay, located on the engine, energizes the starter.
1234
576
A-336415-L
5.2.2 K2 Relay, Crank Relay on Main Circuit Board
The K2 relay energizes the K1 relay. The LED2 lights when energized during crank mode. The K2 relay is located on the controller circuit board. See Figure 5-14.
5.2.3 K3 Relay, Run Relay on Main Circuit Board
The K3 relay energizes the fuel solenoid and instrumentation.
The K3 relay also energizes the generator voltage regulator. LED3 lights when energized during crank and run modes. The K3 relay is located on the controller circuit board.
5.2.4 K4 Relay, Emergency Stop Relay on Main Circuit Board
The K4 relay is continuously energized except during emergency stop. LED4 is lit at all times except during emergency stop. The K4 relay is located on the controller circuit board. If the emergency stop kit is connected (local or remote), remove the jumper from circuit board TB1-1 and 1A. If no emergency stop kit is connected, a jumper must connect terminals TB1-1 and 1A. See Figure 5-14.
1. K2 relay
2. K3 relay
3. K4 relay
4. LED1
5. LED4
6. LED3
7. LED2
Figure 5-14 Main Circuit Board Relays
5.2.5 K5 Relay, Governor Control Relay
The K5 relay energizes the engine governor control circuit. The K5 relay is located in the generator junction box.
5.3 Microprocessor Controller
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible
whenever electricity is present. Open the main circuit breakers of all power sources before servicing the equipment. Configure the installation to electrically ground the generator set, transfer switch, and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Moving rotor.
TP-5737 5/0132 Section 5 Decision-Makert 3+ Troubleshooting
Page 47
WARNING
Accidental starting. Can cause severe injury or death.
To quickly check the condition of the components mentioned in the following flowcharts, use an ohmmeter to read resistance between the designated terminal and ground. See Figure 5-16. With the ohmmeter on the R x 1 scale, a reading of less than one ohm (continuity) indicates that the component may be inoperative. Isolate the inoperative component and repair or replace it.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
5.3.1 Troubleshooting
Use the following charts as a quick reference in troubleshooting individual problems. Consult the first chart for aid in locating the cause of blown fuses. In the successive charts, generator faults are listed by specific groups and correlated with possible causes and corrective action. Before beginning any troubleshooting procedure, read all safety precautions at the beginning of this manual and those included in the text. Do not neglect these precautions.
Note: If starting the unit by remote switch, verify proper
operation of the remote switch before troubleshooting the controller. Test the remote switch operation by placing the generator set master switch in the AUTO position and running a jumper between terminals 3 and 4 on the controller circuit board. If the generator does not start, proceed with the controller troubleshooting procedure outlined in the following pages.
Component
Engine gauges Connector P2, pin 1
Crank (K1 relay) circuit Connector P1, pin 1
(Diesel) fuel solenoid circuit Connector P1, pin 7
Connect between
ground and terminal:
Figure 5-15 Checking P1 and P2 Connections
2
W
1
1. Ground connection
2. P2 connection
Figure 5-16 Checking P1 and P2 Connections
3-187
TP-5737 5/01 33Section 5 Decision-Makert 3+ Troubleshooting
Page 48
5.3.2 Fuses
The following chart lists the possible causes of blown controller fuses F1, F2, and F3. If a fuse blows, replace it
Blown F1 fuse (remote annunciator: 3 amp)
and resume operation. If the fuse blows again, use Figure 5-17 to identify the faulty component(s).
Inoperative dry contact kit Remaining accessories connected to TB1-42A
Battery connections reversed Shorted DC supply to indicator panel Shorted controller circuit board
Inoperative engine electrical components Inoperative overvoltage board Inoperative panel lamps, engine gauges
Inoperative audio/visual alarm
Blown F2 fuse (controller: 3 amp)
Blown F3 fuse (engine and accessories: 15 amp)
Figure 5-17 Checking F1, F2, and F3 Fuses
TP-5737 5/0134 Section 5 Decision-Makert 3+ Troubleshooting
Page 49
Engine does not crank with the generator set master switch in the RUN position.
Is the battery fully charged? Yes
No
Charge the battery and attempt restart. If the engine does not crank, continue the troubleshooting sequence.
Is the controller LED4 lit?
Yes
No
Is the emergency stop switch (controller or remote) activated? See emergency stopping in Section 2, Operation.
YesNo
Reset the emergency stop switch (controller or remote). Is LED4 lit?
No
Press the lamp test button. Do lamps light?
Check the P3/P4 harness and connections. Are the connections okay?
No
Replace the P3/P4 harness.
Do the controller’s LED2 and LED3 light with the generator set master switch in the RUN position?
No
Was there a fault shutdown?
No Yes
Replace the circuit board.
Correct the fault.
Yes
No
Yes
Replace the inoperative indicator panel circuit board.
Yes
Check the engine start circuit (P1 harness, starter, solenoid, battery connections, etc.). Is the start circuit okay?
No Yes
Repair the inoperative component.
Yes
Replace the circuit board.
Place the test jumper between TB1-1 and TB1-1A. Is LED4 lit? Remove the test jumper before proceeding.
No
Check for DC voltage at the F2 fuse (3 amp). See Figure 5-20. Voltage at the fuse indicates the fuse is good. Is voltage present?
No
Check the fuse. Is the fuse okay?
No
Replace the fuse. If the fuse blows again, refer to Section
5.3.2, Fuses.
Figure 5-18 Engine Does Not Crank
Yes
Repair/replace the
Yes
inoperative emergency stop switch (controller or remote.)
Yes
Replace the circuit board.
Check the P1 connector/harness. Check if the battery connections are loose or reversed.
TP-5737 5/01 35Section 5 Decision-Makert 3+ Troubleshooting
Page 50
Engine cranks but does not start.
Is fuel low? Yes
No
Is LED3 lit?
Yes
Are the controller panel lights lit?
No
Check the bulbs. Are the bulbs burned out?
No
Check the circuit board P2 harness and connector pins. Is the harness inoperative?
No
Replace the circuit board.
No
Add fuel.
Replace the circuit board.
Yes
Yes
Yes
Replace the bulbs
Repair or replace the harness.
Check the engine starting circuit. Check for battery voltage at the fuel solenoid/injector pump/electronic governor
Does the engine starting circuit check out okay? Check for battery voltage at the governor controller (on diesel units).
Yes
Check the P1 harness and connector pins. Is the harness inoperative?
No
Replace the circuit board.
Repair or replace the harness.
No
Repair or replace the harness and/or components.
Yes
Figure 5-19 Engine Cranks, But Does Not Start
V
1
1. Fuse terminal
Figure 5-20 Checking Condition of F2 Fuse
3-187
1
1. AC fuse terminal block
Figure 5-21 AC Fuse Terminal Block
A-328917-X
TP-5737 5/0136 Section 5 Decision-Makert 3+ Troubleshooting
Page 51
Controller instrumentation not functioning properly.
Is there a loose input or component lead connection at the AC fuse terminal block or at the component?
No
Yes
Secure the connection.
Is there a blown 1.5-amp fuse at the AC fuse terminal block? See Figure 5-21.
No
Instrumentation is inoperative. Replace or repair the component.
Figure 5-22 Controller Instrumentation
Lamp circuit board not functioning or not functioning properly (i.e., fault lamps and alarm horn only).
Press the lamp test button. Do the lamps light?
No
Is the lamp circuit board receiving power? Check for input voltage at P4-6 and P4-1 soldered connections on the lamp circuit board. See Figure 5-24.
Yes
Yes
Replace the fuse.
Improper input signal. The main circuit board is inoperative.
Yes
The panel circuit board is inoperative. Replace it.
No
Is the P3/P4 ribbon connector undamaged and properly connected?
No
Replace the ribbon connector.
Figure 5-23 Lamp Circuit Board
TP-5737 5/01 37Section 5 Decision-Makert 3+ Troubleshooting
Yes
Replace the main circuit board.
Page 52
1
2
1. P4-6 (+) connection
2. P4-1 (--) connection
Figure 5-24 Checking Input to Lamp Circuit Board
Engine starts and runs, but overcrank lamp flashes.
3-187
Note: The overcrank lamp flashes if the speed sensor signal is absent longer than one second.
Is the speed sensor air gap greater than that specified in Section 1?
No
Is there an open speed sensor circuit? Check the continuity of wire 2 (black), wire 16 (white), and wire 24 (red) between the P1 connector and the speed sensor. Check for 8-10 volts DC across the speed sensor (+) positive terminal and (--) negative terminal. Check wire 16 for 3-6 volts DC, and wire 24 for 8-10 volts DC. Does this test check out okay?
No
Repair the circuit.
Figure 5-25 Overcrank Lamp
Yes
Adjust the speed sensor air gap to
0.014-0.028 in. (0.36-0.71 mm). See Figure 5-26.
Inoperative speed sensor.
Yes
See Section 7.10, Speed Sensor Test.
TP-5737 5/0138 Section 5 Decision-Makert 3+ Troubleshooting
Page 53
3
2
1
1
6
4
0 + ---
5
3-100
R12758-3
1. Speed sensor
2. Wire 16: white/clear
3. Wire 24: red
4. Wire 2: black
5. Air gap: 0.36--0.71 mm (0.014--0.028 in.)
6. Actuator cup
Figure 5-26 Speed Sensor Air Gap
5.4 FASTCHECK Features and
Operation
The FASTCHECKâserves as an engine simulator for testing and troubleshooting the microprocessor controller.
5.4.1 Features
The following paragraphs detail the FASTCHECK features. See Figure 5-27 for an illustration. The following engine switch positions simulate engine conditions:
D OFF—locked engine (starter energized but not
turning)
D CRANK—engine cranking, but not started D RUN—engine running
TP-5353-6
D BATT—(battery) lamp:
D Lights when the test battery(ies) or DC power
supply is live and properly connected
Note: LOP, HWT, and OVERSPEED simulate
malfunctions causing the engine to shut down. LOP and HWT circuits start timing after the engine has run for 30 seconds. The engine shutdown should occur 5 seconds after pushing
â
the fault switch.
1
Indicator Lamps:
D IGN—(ignition) lamp:
D Shows battery voltage supplied to fuel solenoid D Lights during cranking and running
D CRK—(crank) lamp:
D Shows battery voltage switched to starter (engine
not necessarily turning)
D Lights only during on-crank cycles
D REG—(regulator) lamp:
D Shows battery voltage supplied to the generator
set’s AC voltage regulator
D Lights only during cranking and running
TP-5737 5/01 39Section 5 Decision-Makert 3+ Troubleshooting
1. Toggle switches
2. Indicator lamps
3. Overspeed button
4. Engine switch
Figure 5-27 FASTCHECKâSimulator
2
3
4
B-291930
Page 54
Switches:
D LOP—low oil pressure D HWT—high water (engine) temperature D OVERSPEED—simulates a 70 Hz overspeed
condition
D LF—low fuel (not used for testing) D LWT—low engine water temperature D AOP—anticipatory (low) oil pressure D AWT—anticipatory (high) water temperature
5. Clip the red (+) and black ( --) harness leads to a battery(ies) or DC power supply of proper voltage for the generator set (12 or 24 volts). Adjust the output voltage to 1-2 volts above battery voltage when using a DC power supply. See the BATT rating on the generator nameplate. Use the generator set battery(ies) if accessible and fully charged.
Note: Observe the correct polarity when
connecting FASTCHECK
â
, otherwise
circuit board damage occurs.
5.4.2 Application
Use the FASTCHECKâto test the microprocessor controller on the generator set when troubleshooting startup problems or to test and troubleshoot the controller when removed from the generator set.
To operate the FASTCHECKâthe following equipment is required:
D FASTCHECK
â
simulator (B-291930) and harness
(255915).
D Variable low-voltage DC power supply; 0--30 volt,
3 amp minimum current, 0.5% maximum output voltage ripple at 30 volts DC. A 12- or 24-volt battery (depending on system voltage) can also be used to operate the FASTCHECK
â
.
5.4.3 Connect/Operate Procedure
Use the following procedure to connect/operate the FASTCHECK
Procedures to test the overcrank circuitry, speed sensor circuitry, and generator condition indicators are described later in this section.
â
tester.
Note: Because of the absence of AC output, the
auxiliary lamp flashes during controller testing (on 16-light microprocessor controllers). The NOT-IN-AUTO lamp illuminates whenever the generator set master switch is not in the AUTO position on 16-light microprocessor controllers.
6. Move the generator set master switch to the RUN position. Move the FASTCHECKâengine switch to the CRANK position. The FASTCHECK
â
IGN, CRK, and REG lamps should light. The generator controller causes the engine to crank until the FASTCHECK
â
switch is moved to the RUN position (or OVERCRANK shutdown appears on generator controller).
7. Move the FASTCHECK
â
engine switch to the RUN position. CRK lamp should go out and REG and IGN lamps should stay on.
4
3
1. Unplug the DC engine harness from the DC harness connector (P1). See Figure 5-28.
2. Connect the FASTCHECK
â
harness connector (P1) and to the top of the FASTCHECK
â
.
3. Move the generator set master switch to the OFF/RESET position.
4. Move the FASTCHECK
â
engine switch to the OFF
position.
harness to the DC
1
1. FASTCHECKâ
2. Wiring harness
3. DC harness connector
4. DC power supply
2
Figure 5-28 FASTCHECKâConnections
R1111 8-2
3-187
TP-5737 5/0140 Section 5 Decision-Makert 3+ Troubleshooting
Page 55
8. Simulate engine malfunctions by pressing FASTCHECK
â
fault switches. The corresponding fault lamp on the controller should light during each simulated engine malfunction.
5.4.5 Controller Speed Sensor Circuitry
To check the controller’s ability to respond to signals from the speed sensor, perform the following test:
Note: Leave the FASTCHECK
â
engine switch in the RUN position for at least 30 seconds before pushing toggle switches. Toggle the generator set master switch to the OFF/RESET position and the FASTCHECKâengine switch to the OFF position, then back to the RUN position after simulated fault shutdowns.
5.4.4 Overcrank
Use the following procedure to test the controller’s ability to detect a locked engine and to stop a startup attempt if the starter locks or does not engage.
Overcrank Circuitry Test Procedure
1. Move the FASTCHECK position.
2. Move the generator set master switch to the OFF position and then move the switch to the RUN position.
3. IGN, CRK, and REG lamps on FASTCHECK should light for approximately 5 seconds and then go out. Five seconds later, the IGN, CRK, and REG lamps should relight for 5 seconds before going out again (15 seconds total elapsed time). The controller OVERCRANK lamp lights. Check for operating voltage between TB1-42A (+) and TB1-12 (--).
â
engine switch to the OFF
Speed Sensor Circuitry Test Procedure
1. Move the generator set master switch to the OFF/RESET position.
â
2. Move the FASTCHECK
engine switch to the OFF
position.
3. Move the generator set master switch to the RUN position. Observe the IGN, CRK, and REG lamps light.
4. Within 5 seconds, move the FASTCHECK
â
engine
switch to the RUN position.
â
5. If the FASTCHECK
CRK lamp goes out, the controller speed sensor circuitry is functioning correctly.
â
4. This test verifies the proper operation of the engine overcrank circuit. If the OVERCRANK shutdown fails to function, check the speed sensor and related circuitry. See Section 5.4.5, Controller Speed Sensor Circuitry, and Section 7.10, Speed Sensor Test.
TP-5737 5/01 41Section 5 Decision-Makert 3+ Troubleshooting
Page 56
5.4.6 Generator Condition Indicator Terminal (TB1 Terminal Strip)
Remote accessories (audiovisual alarm, remote annunciator, dry contact kits, etc.) may be connected to the controller TB1 terminal strip to signal the condition of the generator set. Some generator sets may not be equipped with the optional sending devices necessary to operate all generator condition indicators. If the remote accessories do not operate, test for output voltage at the TB1 terminal strip. To test the operation of each indicator, move the generator set master switch and FASTCHECK Test point voltage is slightly less than the voltage being supplied to the controller (12 or 24 volts). If correct voltage is not detected at the test point, remote accessories (audiovisual alarm, remote annunciator, dry contact kits, etc.) do not function. Test point connections are shown in Figure 5-29 and Figure 5-30.
Note: When checking controller test point voltage,
place the negative (--) lead of the voltmeter on the terminal designated in Figure 5-30 and the voltmeter positive (+) lead on TB1-42A.
â
toggle in the position prescribed.
Note: Because of the absence of AC output, the
auxiliary lamp flashes during the controller testing on 16-light microprocessor controllers. The NOT-IN-AUTO lamp illuminates whenever the generator set master switch is not in the AUTO position on 16-light microprocessor controllers.
Note: Leave the FASTCHECK
â
engine switch in the RUN position for at least 30 seconds before pushing the toggle switches. Toggle the generator set master switch to the OFF/RESET
â
position. Move the FASTCHECK
engine switch to the OFF position. Move the generator set master switch to the RUN position. Observe IGN, CRK, and REG lamps light. Within 5 seconds, move the FASTCHECK
â
engine switch to the
RUN position.
1
2
1. TB1-42A 2. TB1—(see chart titled generator condition indicator terminals)
Figure 5-29 Indicator Lamp Test Connections
A-336415-L
TP-5737 5/0142 Section 5 Decision-Makert 3+ Troubleshooting
Page 57
Indicator Switch Position/Remarks Check For Voltage Between
System Ready Master switch in AUTO position; engine switch in OFF
TB1-42A (+) and TB1-60 (--)
position.
High (Engine) Water Temperature (HWT)
Low Oil Pressure (LOP) Master switch in RUN position; engine switch in RUN
Master switch in RUN position; engine switch in RUN position; hold toggle switch to HWT for at least 5 seconds
TB1-42A (+) and TB1-36 (--)
TB1-42A (+) and TB1-38 (--)
position; hold toggle switch to LOP for at least 5 seconds
Auxiliary Fault (16-light controller)
Master switch in RUN position; engine switch in RUN position; wait 10 seconds. A flashing AUX lamp indicates
TB1-42A (+) and TB1-26 (--)
proper operation of all auxiliary functions
Emergency Stop (local/remote), if equipped
Master switch in RUN position; engine switch in RUN position; remove switch lead connected to controller
Not Applicable
terminals TB1-1 or 1A.
Generator Switch Not-in-Auto Master switch in RUN or OFF/RESET; engine switch in any
TB1-42A (+) and TB1-80 (--)
position
Anticipatory (High Engine) Water Temperature (AWT)
Anticipatory (Low Engine) Oil Pressure (AOP)
Low Water Temperature (LWT), if equipped
Low Fuel, if equipped Generator set master switch in OFF/RESET; engine switch in
Master switch in RUN position; engine switch in RUN; hold toggle switch to AWT
Master switch in RUN position; engine switch in RUN; hold toggle switch to AOP
Master switch in RUN position; engine switch in RUN; hold toggle switch to LWT
TB1-42A (+) and TB1-40 (--)
TB1-42A (+) and TB1-41 (--)
TB1-42A (+) and TB1-35 (--)
Not Applicable
RUN position
Ground controller terminal TB1-63 to test. If the Low Fuel lamp lights, the circuit is functioning correctly
Battery Charger Fault (if battery charger equipped and connected)
Generator set master switch in OFF/RESET; engine switch in RUN position
Ground controller terminal TB1-61 to test. If the Battery
Not Applicable
Charger lamp lights, the circuit is functioning correctly
Low Battery Volts (if battery charger equipped and connected)
Generator set master switch in OFF/RESET; engine switch in RUN position
Ground controller terminal TB1-62 to test. If the Low Battery
Not Applicable
Volts lamp lights, the circuit is functioning correctly
Overspeed See Section 5.4.5, Controller Speed Sensor Circuitry. Not Applicable
Overcrank See Section 5.4.4, Overcrank. Not Applicable
Auxiliary Prealarm (Common Fault)
Master switch in RUN position; engine switch in RUN position; hold toggle switch to LWT, HWT, or LOP
TB1-42 (+) and TB1-32 (--)
Figure 5-30 Generator Condition Indicator Terminals
TP-5737 5/01 43Section 5 Decision-Makert 3+ Troubleshooting
Page 58
Notes
TP-5737 5/0144 Section 5 Decision-Makert 3+ Troubleshooting
Page 59
Section 6 Decision-Makert 1 Controller Troubleshooting
6.1 Decision-Makert 1 and Decision-Makert 1 Expanded Relay Controller
The following text covers the relay controller sequence of operation during generator start, run, stop, and fault shutdown modes. Use this information as a starting point for controller fault identification. See Section 2 to identify controller external components. See Figure 6-1 and Figure 6-2 to identify internal components of the relay controller. Use the LEDs on the controller circuit board to assist in the troubleshooting process. An illuminated LED indicates the respective relay is receiving power; the LED does not indicate whether that relay is energized. See Figure 6-3 and Figure 6-4.
2
1
3
4
5
12 3 4 5
6
7
7
1011
1. TB1 AC terminal block
2. Governor
3. Controller main circuit board (E-254717 COZ models or F-254717 EOZ models)
4. 15-amp fuse
5. K5 relay
6. Ground strap
7. Hourmeter (front panel)
8. Fault lamp (front panel)
9. Voltage adjust potentiometer (front panel)
10. 10-amp fuse (front panel)
11. Generator set master switch (front panel)
A-336597A-D
891011
1. TB2 terminal block
6
8
9
2. Governor
3. K5 relay
4. Controller main circuit board (E-254717 COZ models or F-254717 EOZ models)
5. TB1 AC terminal block
6. Ground strap
7. Fault lamp (front panel)
8. Hourmeter (front panel)
9. Generator set master switch (front panel)
10. Voltage adjust potentiometer (front panel)
11. 10-amp fuse (front panel)
A-336598A-K
Figure 6-2 Decision-Makerä 1 Expanded
Relay Controller Internal Components
A change in the circuit board affects the function of some relays. Circuit board E-254717 has four internal relays with an external K5 relay for engine run components. Circuit board F-254717 has five relays with an external K10 relay for engine run components. The fifth relay designated K5 latches the fault lamp during fault shutdown when in the auto/remote start mode. Although the circuit boards are similar, the changes relating to K5/K10 alter the troubleshooting information.
Figure 6-1 Decision-Makerä 1 Relay Controller
Internal Components
TP-5737 5/01 45Section 6 Decision-Makert 1 Controller Troubleshooting
Page 60
Function Relay
g
g
within30secondsorovercrankfault
p
ping
Stopping:Movethestart/stopswitcht
o
x
theexhausttemperaturereache
s
K2 Open Close
Starting: Close the start/stop switch between N and 47. Note: Fault shutdowns are inhibited during startup until K3 energizes.
K10 or K5
K4 Open Close K20 relay K20 Open Close Starter motor
Running: Generator winding 7--10 producesAC output. Note: K3 relay must obtain AC output
occurs.
Sto
: Move the start/stopswitch to
open circuit between N and 47.
K3 Closed Open
K4 Open Open Deenergizes starter motor
K2 Open Open
Fault shutdowns: Low oil pressure (LOP), high engine temperature (HET) after the engine operating temperature reaches 103_C (218_F), and high exhaust temperature (ETS) (wet exhaust only) after
haust temperature reaches
the e 88--102_C (190--215_F). Contacts close 5--8 seconds after reaching shutdown level. Note: The fault shutdown latches to keep
K1 Closed Open
the fault lamp lit. Move the generator set master switch to OFF/RESET.
Fault shutdown: Overspeed (OS). Contacts close when engine speed reaches shutdown level. Factory set at 70 Hz. Note: The fault shutdown latches to keep fault lamp lit. Move the generator set
K1 Closed Open master switch to OFF/RESET. Fault shutdown: Overcrank (OC).
Contacts close on overcrank (locked rotor) if the speed sensor signal is absent longer than 30 seconds. Note: The fault shutdown latches to keep the fault lamp lit. Move the generator set
K1 Closed Open master switch to OFF/RESET.
Relay Contact Normal Position
Relay Contact Action
Open Close
Energizes/Action:
K2 relay and LED2 lights K10 relay (with F-254717) or K5
relay (with E-254717, engine components (fuel system, governor, ignition, etc.), K4 relay, and LED4 lights
Hourmeter on Decision-Makert 1 and Decision-Makert 1 Expanded controllers and engine gauges (battery voltage, water temperature, and oil pressure) on Decision-Makert 1 Expanded controllers
K3 relay and LED3 lights
Deenergizes K4 relay and LED4 deenergizes
Deenergizes K2 relay and LED2 deenergizes
Deenergizes engine components; generator set shuts down
K1 relay, LED1 lights, and fault lamp
Deenergizes engine components; generator set shuts down
K1 relay, LED1 lights, and fault lamp
Deenergizes engine components; generator set shuts down
K1 relay, LED1 lights, and fault lamp
Deenergizes engine components; generator set shuts down
Figure 6-3 Relay Controller Sequence of Operation
TP-5737 5/0146 Section 6 Decision-Makert 1 Controller Troubleshooting
Page 61
10 amp
K2
15 amp
K20
K2
5 Second
Shutdown
Reset
K1
+--
K10
N
D5
70
K4
Run
47
Off/Reset
Auto
4
GS
FS
OP
WT
BV
HR
K20
K10
M
Remote Start
3
Fault
Starter
K5
K3
NOTE
D Overcrank, Overspeed, LWL, HET, and
LOP drive the fault shutdown circuit.
D Fault latch provided by K1 normally open
contacts.
D Overcrank shutdown is only driven by
AC.
D Crank disconnect driven by AC and
speed sensor input.
D Relays K1, K2, K3, K4, and K5 are part of
the controller circuit board and their electrical connections and circuits are simplified in this diagram.
D Fault latch line, fault shutdown, crank
disconnect, overcrank, overspeed, and speed sensor (dotted lines) are part of the controller circuit board and their electrical connections and circuits are simplified in this diagram.
Overspeed
16
Speed Sensor
Speed Pickup
Speed Sensor
Actuator
Photo-Coupling
LED Circuit Board
Voltage Regulator
11
6
FP
AC
F3
G
AC
Photo Transistor
Circuit Board
9
K1
K4
K1
K3
Overcrank
10
4
2
Exciter
Field
Exciter
Armature
V7
V8
FN
F2F1
K5
Fault Latch Line
2
Q
Fault
Shutdown
3
Q
Crank
Disconnect
AC
G
AC
SCR Assembly
ETS
HET
BV Battery Volts ETS High Exhaust Temperature Switch
K3
LOP
FS Fuel System GS Governor System HET High Engine Temperature Switch HR Hourmeter K1 Fault Shutdown Relay K2 Engine Run Relay K3 Crank Disconnect/
Flashing Control Relay K4 Crank Disconnect Relay K5 Fault Latch Relay K10 Auxiliary Run Relay
V7
V0
7
10
8
11
K20 Starter Relay Solenoid LOP Low Oil Pressure Switch LWL Low Water Level Sender M Starter Motor OP Oil Pressure Gauge
2
5
Main Rotor
Field
1
4
12
F+
F ---
Stator
9
3
6
WT Water Temperature Gauge
ADV-5353-6
Figure 6-4 Relay Controller Sequence of Operation with F-254717 and Later Circuit Boards
TP-5737 5/01 47Section 6 Decision-Makert 1 Controller Troubleshooting
Page 62
Figure 6-5 Decision-Makerä 1 Relay Controller with E-254717 Circuit Board
ADV-6120-A
TP-5737 5/0148 Section 6 Decision-Makert 1 Controller Troubleshooting
Page 63
Figure 6-6 Decision-Makerä 1 Relay Controller with F-254717 Circuit Board
TP-5737 5/01 49Section 6 Decision-Makert 1 Controller Troubleshooting
ADV-6120-D
Page 64
Figure 6-7 Decision-Makerä 1 Expanded Relay Controller with E-254717 Circuit Board
ADV-6121-
TP-5737 5/0150 Section 6 Decision-Makert 1 Controller Troubleshooting
Page 65
Figure 6-8 Decision-Makerä 1 Expanded Relay Controller with F-254717 Circuit Board
TP-5737 5/01 51Section 6 Decision-Makert 1 Controller Troubleshooting
ADV-6121-C
Page 66
6.2 Relay Controller
Use the following charts as a reference in troubleshooting individual problems. Before beginning any troubleshooting procedure, read all safety precautions at the beginning of this manual and those included in the text. Do not neglect these precautions.
WARNING
Hazardous voltage. Can cause severe injury or death.
Moving rotor.
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
Operate the generator set only when all guards and electrical enclosures areinplace.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible
whenever electricity is present. Open the main circuit breakers of all power sources before servicing the equipment. Configure the installation to electrically ground the generator set, transfer switch, and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Use the following flowchart and Figure 6-9 and Figure 6-10 as an aid in troubleshooting the main circuit board and the generator set. If the prescribed remedy does not correct the problem, replace the circuit board. The controller circuit board includes light emitting diodes (LEDs) indicating relay coil power and aids in circuit board and generator fault detection. When the K1, K2, K3, K4, or K5 relays receive power, the corresponding LED lights. The LED does not indicate whether the relay coil is energized. Determine if relay coil is energized, by analyzing the generator faults and performing a continuity test on the relay coil.
TP-5737 5/0152 Section 6 Decision-Makert 1 Controller Troubleshooting
Page 67
12 34
12 34
E-254717-A
56789
1. LED1
2. K1 relay (fault)
3. K3 relay (crank/run)
4. LED3
5. LED4
6. K4 relay (crank)
7. P1 connector
8. K2 relay (run)
9. LED2
Figure 6-9 Relay Controller Circuit Board E-254717
(COZ/CFOZ Models)
6.2.1 Relay Controller Flowchart
Move the
generator
set master
switch to
the RUN
position
No Yes
Is the 10-amp
fuse functioning?
Yes
D Check the condition/
connections of the start/stop switch (N, 4, and 47). See Wiring Diagrams
D Check the battery
condition and connections
Do the above items check out okay?
Does the
engine crank?
No
Is the K2 relay
LED2 lit?
No
Replace the fuse
Yes
No
Yes
Is the K4 relay
LED4 lit?
TheK2orK4relayis
inoperative. Replace
the circuit board
Is diode D5
open?
No
TheK2relayis faulty—replace
the board
Repair/replace
the components
No
1011
1. K5 relay (fault latch)
2. K1 relay (fault)
3. K3 relay (crank/run)
4. LED3
5. LED4
6. K4 relay (crank)
Figure 6-10 Relay Controller Circuit Board F-254717
Yes
Yes
Replace
board
D Check the starter and K20
relay. See Wiring Diagrams and the engine service manual
D Check battery(ies). Load
test the battery(ies)
10. LED1
11. LE D 5
(EOZ/EFOZ Models)
Verify that the K4 relay
is energized by
checking for DC
voltage at the K20
relay coil when the
start switch is in the
RUN position. Is
voltage present at the
K20 relay?
No
TheK4relayis faulty—replace
the circuit
board
F-254717-
56789
7. P1 connector
8. K2 relay (run)
9. LED2
Go to
A
Yes
Is voltage present
at the starter
motor?
No
Yes
Replace
the K20
relay
Check battery(ies).
Load test battery(ies).
Repair/replace the starter motor. See the engine service
manual.
TP-5737 5/01 53Section 6 Decision-Makert 1 Controller Troubleshooting
Page 68
A
Does the
engine start?
Yes
Go to
B
No
Does the engine
crank for 30
seconds and
then shut down?
No
Is 12-volts DC
present at the fuel solenoid?
See the Wiring
Diagrams
Yes
Engine mechanical problem. See the engine service manual. Check the following components:
D Fuel supply
D Fuel solenoid
D Compression
Yes
No
Is the
15-amp
fuse okay?
No
Replace
the fuse
If shutdown is
immediate, check
the overspeed circuit
If shutdown occurs after 5--7 seconds,
check the low oil
pressure, high
engine temperature,
or high exhaust
temperature circuits
Unit shuts down on overcrank.
Troubleshoot the engine using the
engine service manual
Yes
Is the K1
relay LED1
No
lit?
Yes
Unit starts but
then shuts down
F-254717) or K5 (with
If shutdown
occurs after 30
seconds, check
the overcrank
circuit
wiring between
TB1 terminal 70
and the fuel
Is the K2
relay
energized?
Yes
Is the K10 (with
E-254717) relay
energized?
Yes
Check the
solenoid
No
Replace
the K10
or K5
relay
Check for 12-volts
No
DC at 70. Check the engine wiring
connections from the control board
to the component.
continuity of the
Does the engine
checkout okay?
Yes
Replace
the
circuit
board
harness
Check the
harness leads.
wiring harness
No
Repair/ replace
the
wiring
harness
TP-5737 5/0154 Section 6 Decision-Makert 1 Controller Troubleshooting
Page 69
The engine starts but
B
shuts down after 30
No
seconds or more?
The engine runs but
cannot be stopped by
the start/stop switch
No
Check for 120-volts AC output
from the stator 10-7 winding at V0
and V7. See Section 7, Stator
Testing. Run the generator set
while performing this test
Test the speed sensor operation
as described in Section 7
If correct voltage is present and
the speed sensor tests okay,
replace the circuit board
Note: Allow a 60-second
cooldown between cranking
attempts if the set does not start
Yes
Is the K3 relay
LED3 lit?
Yes
Is the K1
relay
LED1 lit?
No
Replace the circuit board
Replace the inoperative
start/stop switch
Do the engine
systems including low
Yes
oil pressure, high
engine temperature,
and high exhaust
temperature circuits
checkout okay?
Replace the
circuit board
Check the condition/connections
of the start/stop switch (local or
remote). See the Wiring
Diagrams. Does the start/stop
switch function correctly and the
wiring check out okay?
No
Yes
Replace the circuit board
(inoperative K2 relay).
Repair/replace
No
the inoperative
engine system
Yes
TP-5737 5/01 55Section 6 Decision-Makert 1 Controller Troubleshooting
Page 70
Notes
TP-5737 5/0156 Section 6 Decision-Makert 1 Controller Troubleshooting
Page 71
Section 7 Component Testing and Adjustment
7.1 Generator Troubleshooting
Use the following flowchart to troubleshoot the generator set when detecting no or high voltage. The remaining parts of this section give additional and more detailed information about the individual checks/tests mentioned in the flowchart. Use the flowchart to initially isolate the possible problem.
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible
whenever electricity is present. Open the main circuit breakers of all power sources before servicing the equipment. Configure the installation to electrically ground the generator set, transfer switch, and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Disconnecting the electrical load. Hazardous voltage can cause severe injury or death. Disconnect the generator set
from the load by opening the line circuit breaker or by disconnecting the generator set output leads from the transfer switch and heavily taping the ends of the leads. High voltage transferred to the load during testing may cause personal injury and equipment damage. Do not use the safeguard circuit breaker in place of the line circuit breaker. The safeguard circuit breaker does not disconnect the generator set from the load.
Moving rotor.
TP-5737 5/01 57Section 7 Component Testing and Adjustment
Page 72
No output voltage is detected
Is the safeguard circuit breaker in the ON position?
Yes
Do a flashlight test on the photo transistor board. (See Section 7.3, LED Circuit Board Tes t )
No
Place the safeguard circuit breaker to the ON position
If no voltage is detected, remove the G and F+ (red) leads from the SCR assembly. Jumper G and AC on the SCR assembly.
If high voltage is detected, replace the photo transistor board
Replace the rotor Replace the SCR
If high voltage is detected, check for battery voltage at the voltage regulator. Is battery voltage present?
If no voltage is detected, test the rotor. Do the exciter armature and main field windings check out okay?
YesNo
assembly
No
Yes
Check DC voltage at the LED circuit board
If no DC voltage is present, unplug the connector at the LED circuit board and check voltage
If no DC voltage is present, check the wiring between the voltage regulator and the LED circuit board. Does wiring check out okay?
Check the wiring to the voltage regulator
If DC voltage of 6--12 volts is present, replace the LED circuit board. (LED is open)
If DC voltage of 6--12 volts is present, replace the LED circuit board. (LED or flyback diode is shorted and/or grounded)
Figure 7-1 Troubleshooting Generator, No Output Voltage
Repair/replace the wiring
YesNo
Replace voltage the regulator
TP-5737 5/0158 Section 7 Component Testing and Adjustment
Page 73
High output voltage is detected
Turn safeguard circuit breaker to the OFF position. Does output voltage remain high?
Yes
Remove G and F+ (red) leads from the SCR assembly. Does output voltage remain high?
Turn the safeguard circuit breaker to the ON position. Is
No
Check for open wiring between the stator and the voltage regulator
sensing voltage (190--277 volts) at leads V7 and V8 available at the regulator?
If the sensing voltage is high, replace the voltage regulator
No
Yes
If the sensing voltage is low, check the voltage on all phases. Is voltage balanced on all windings?
No
If no voltage is detected, replace the photo transistor board
Replace
Yes
the voltage regulator
YesNo
Replace the SCR assembly
Test the stator windings
Figure 7-2 Troubleshooting Generator, High Output Voltage
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
TP-5737 5/01 59Section 7 Component Testing and Adjustment
Page 74
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Disconnecting the electrical load. Hazardous voltage can cause severe injury or death. Disconnect the generator set
from the load by opening the line circuit breaker or by disconnecting the generator set output leads from the transfer switch and heavily taping the ends of the leads. High voltage transferred to the load during testing may cause personal injury and equipment damage. Do not use the safeguard circuit breaker in place of the line circuit breaker. The safeguard circuit breaker does not disconnect the generator set from the load.
Follow all safety precautions located in the front of this manual and the additional precautions found within the text. Figure 7-3 lists the various generator output conditions and component tests. Refer to Figure 7-4, AC Voltage Control for assistance in troubleshooting.
Moving rotor.
7.2 Generator Testing
This section covers generator testing for the following generator conditions:
D No output on any phase D Overvoltage D Fluctuating voltage
7.2.1 No Output On Any Phase
No Output On Any Phase Test Procedure
1. Check the safeguard breaker, if equipped. If the safeguard breaker is open, close the breaker and, with the set running, check the AC voltmeter for AC output voltage.
2. If AC output is not present, then:
a. Check wire 1B from the safeguard breaker and
wire 7N (ground) to the voltage regulator.
b. Check for voltage to the safeguard breaker, if
equipped.
3. If all items in step 2 are functioning, proceed to Section 7.3, LED Circuit Board Test, and Section 7.5, Automatic Voltage Regulator (AVR) Operation and Adjustment.
4. If tests indicate LED and AVR are functioning correctly, proceed with the test of the photo transistor board and SCR assembly (see Section 7.4). Otherwise, continue with the AVR test.
5. If the photo transistor board test indicates the board is functioning correctly, proceed to the exciter armature test as described later in Section 7.8.
6. If the exciter armature test indicates the armature is functioning correctly, proceed to the generator field test as described later in Section 7.7.
7. If the generator field test indicates the field is functioning correctly, replace the SCR assembly or the photo transistor board as described later in Section 7.4.
Components and Circuits to Test Under Certain Generator Output Conditions
Generator
Output
Condition
No
Output
Over
Voltage
Fluctuating
Voltage
* No output voltage if voltage adjustment potentiometer circuit is open or shorted to ground. [ Overvoltage may occur if an outside light source is present when the LED board and cover are removed.
LED
Board
D D D D D D D D D*
D D D D D D D
Photo
Transistor
Board
D[ D D
Regulator (AVR)
Figure 7-3 Troubleshooting Guide
Automatic
Voltage
SCR
Assembly
Safeguard
Breaker
Exciter
Armature
Generator
Field
Generator
Stator
Voltage
Adjustment
Pot
TP-5737 5/0160 Section 7 Component Testing and Adjustment
Page 75
V/Hz 60 Hz
STAB.
V/HZ
50 Hz
67 7N 68
3B
5B
60 Hz
1B
T2T1 T3
AC VOLTAGE REGULATOR CIRCUIT BOARD
V8
V9
V7
50 Hz
VOLTAGE ADJUSTMENT RHEOSTAT
SELECTOR SWITCH
7N
AC AMPS
SAFEGUARD
1B
12
11
10
9
8
7
6
5
4
3
2
1
12 LEAD STATOR
BREAKER
T2
T3 T1
CONTROL RELAY CONTACTS
P4
70
SOLENOID
STARTER
15 AMP
---
BATTERY
HC
P
P S
+
5B 3B
C
D2
A
LED BOARD
PHOTO TRANSISTOR BOARD
Figure 7-4 AC Voltage Control, Typical
AC
AC
MAGNETS
EXCITER ARMATURE
F3
G
MAGNETS
AC
G
AC
SCR ASSEMBLY
F+
F ---
GENERATOR FIELD
TP-5353-7
TP-5737 5/01 61Section 7 Component Testing and Adjustment
Page 76
7.2.2 Overvoltage
7.3 LED Circuit Board Test
Overvoltage Test Procedure
Note: If overvoltage occurs, disconnect the harness
plug at the voltage regulator. If overvoltage continues, the problem lies in the photo transistor circuit and/or SCR assembly; proceed through the following troubleshooting steps. If output voltage disappears, the problem is in the AVR, including connections and/or wiring.
1. Remove the LED board and cover.
2. Examine the photo transistor board for visible signs of damage (open foil patterns or heat discoloration). Replace the photo transistor board if it is visibly damaged. If overvoltage continues after replacement of the photo transistor board, proceed to step 3.
3. Remove the green (center) lead from the G terminal and the red lead from the F+ terminal of the SCR assembly. Tape each terminal end of leads to prevent contact with adjacent metal components.
4. With the safeguard breaker open, start the generator set. The lack of AC output indicates the SCR assembly is functioning properly. If overvoltage continues, replace the SCR assembly.
Note: When replacing the SCR assembly do not
exceed a torque value of 0.9 Nm (8 in. lbs.) when tightening the SCR mounting bolts.
5. If overvoltage is evident with the safeguard breaker closed, check for an open circuit in leads V7 and V8 to the AVR. If these circuits are open or shorted, repair or replace. Check the voltage rheostat circuit (leads 67 and 68). Repair or replace as necessary.
The following procedure provides testing information for the LED circuit board. Certain steps require that the generator set be running. While the generator set is not running, disable the generator set. See the following safety precautions. Disconnect all load from the generator set during this test.
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
WARNING
6. If all the circuits described in step 5 are functioning, check the AVR as described in Section 7.5.
7.2.3 Fluctuating Voltage
Fluctuating Voltage Test Procedure
1. Check the generator output leads for proper connections. See Section 9, Wiring Diagrams.
2. Check for loose connections to the AVR, LED board, photo transistor board, or SCR assembly.
3. Check the stator for shorted or open windings; See Section 7.6, Stator.
4. Verify the AVR adjustment. See Section 7.5, Automatic Voltage Regulator Operation and Adjustment.
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Disconnecting the electrical load. Hazardous voltage can cause severe injury or death. Disconnect the generator set
from the load by opening the line circuit breaker or by disconnecting the generator set output leads from the transfer switch and heavily taping the ends of the leads. High voltage transferred to the load during testing may cause personal injury and equipment damage. Do not use the safeguard circuit breaker in place of the line circuit breaker. The safeguard circuit breaker does not disconnect the generator set from the load.
Moving rotor.
TP-5737 5/0162 Section 7 Component Testing and Adjustment
Page 77
Testing the photo transistor circuit board. Hazardous voltage can cause severe injury or death. When the end
cover is removed, do not expose the photo transistor circuit board mounted on the generator set end bracket to any external light source, as exposure to light causes high voltage. Keep foreign sources of light away from the photo transistor circuit board during testing. Place black electrical tape over the LED on the circuit board before starting the generator set.
LED Circuit Board Test
1. Remove the junction box panels from the generator end of the unit and remove the photo transistor board/LED board cover. See Figure 7-5.
2. With the generator set running at no load, shine a flashlight on the exposed photo transistor board. SeeFigure7-6.
3. Observe the AC output voltmeter. The AC output voltage should be high. Switch the flashlight off or turn it away from the rotating photo transistor board. The AC output voltage should be low. If these conditions exist (high voltage while the photo transistor board is illuminated and low voltage while the photo transistor board is dark), then the photo transistor board and SCR assembly are functioning properly. The fault is likely in the wiring, AVR, or LED circuit board. If the generator does not respond this way to the flashlight test, the fault is probably in the photo transistor board (PCB assembly) or the SCR assembly. Proceed to the tests for these items.
4. With the generator set running, observe approximately 1--2 volts DC at 3B (+) and 5B (--) at the LED board. See Figure 7-7. Shine the flashlight on the photo transistor. DC voltage reading should drop, showing the AVR is functioning properly. If voltages are not observed, refer to the AVR test.
5. Stop the generator set.
R12758-5
Figure 7-6 LED Flashlight Test
3-100
1
1. Photo transistor/LED board cover
Figure 7-5 Panels Removed
TP-5737 5/01 63Section 7 Component Testing and Adjustment
3-100
R8371-5
Figure 7-7 Checking LED Board
3-094
R8936-10
Page 78
7.4 SCR Assembly and Photo Transistor Board
7.4.1 Concept and Equipment
The SCR assembly mounts behind the exciter armature and controls current flow to the generator field. The command and sensing circuitry mounts on the shaft-mounted photo transistor board. See Figure 7-8. The generator set only functions if both components are functional. The following test determines which component is faulty. Because the end bracket must be removed from the set to correctly test these components, do not begin this procedure unless there is reasonable certainty that these components are inoperative. See Section 7.1, Generator Troubleshooting. Examine the photo transistor board for visible signs of damage (open foil patterns and heat discoloration) before removing the entire SCR assembly for testing. See Section 7.9, End Bracket Removal and Replacement, and Section 8, Disassembly/ Reassembly, for end bracket removal.
Testing the SCR assembly and photo transistor board requires the following components:
D Light bulb with socket, one 120-volt/110-watt. D Switch, double-pole/single-throw (DPST), 120-volt
10-amp minimum.
D Fuse, 1 amp, in holder. D Plug with cord, 120-volt AC. D SCR assembly and photo transistor board (one must
be functioning)
7.4.2 SCR Assembly and Photo Transistor Board Test
This test simulates the normal operation of the components when the generator is running. In the test, a known working component (example: photo transistor board) is matched with a component of unknown quality (example: SCR assembly). If the components do not function normally during the test, the component of unknown quality may be inoperative. Test either component in this manner.
1
3-100
R12758-8
1. SCR assembly 2. Photo transistor board
2
B-258545-A
B-292902
Figure 7-8 Component Locations
TP-5737 5/0164 Section 7 Component Testing and Adjustment
Page 79
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Moving rotor.
4. Shield the photo transistor board from all other light sources during this test. Direct the test light to the photo transistor board. If both components are working, the test fixture light bulb lights when the external light source is applied to the photo transistor board. Remove the light source; the fixture light bulb should go out. If the test fixture light bulb does not light or is lit prior to receiving the external light source, the tested component is inoperative (in this example the SCR). Replace the SCR assembly.
Hazardous voltage can cause severe injury or death.
Carefully follow instructions in the equipment manual when testing or servicing generator set in the presence of voltage.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible
whenever electricity is present. Open the main circuit breakers of all power sources before servicing the equipment. Configure the installation to electrically ground the generator set, transfer switch, and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
SCR Assembly and Photo Transistor Board Test
1. Connect the components as illustrated in Figure 7-9. If testing the photo transistor board, the SCR assembly must be working. If testing the SCR assembly, the photo transistor board must be working.
Note: When testing the SCR assembly, secure all
connections with nuts to ensure good contact between the wire terminals and the foil pattern. The threaded studs are insulated from the foil pattern and are not in contact except when secured by a nut. Do not exceed 1.4 Nm (12 in. lbs.) when tightening SCR assembly nuts.
2. With the cord switch in the OFF position, plug in the electrical cord.
3. Turn the cord switch to the ON position.
Note: When replacing the SCR assembly, do not
exceed a torque value of 0.9 Nm (8 in. lbs.) when tightening the SCR mounting bolts.
1
1. SCR assembly
2. White wire
3. Red wire
4. Green wire
5. Black wire
6. Photo transistor board
7. Light source (flashlight)
8. 120-volt/100-watt lamp
9. Fuse (1 amp)
10. Switch (DPST) S1
11. 120 volts AC
2
AC
3
4
F+ AC
G
5
F ---
9
10
11
6
7
8
TP-5353-7
TP-5737 5/01 65Section 7 Component Testing and Adjustment
Figure 7-9 SCR Assembly and Photo Transistor
Board
Page 80
7.5 Automatic Voltage Regulator (AVR) Operation and Adjustment
The AVR monitors output voltage amplitude and frequency to supply current to the stationary LED board. The AVR circuit board includes volts/Hz and stability adjustment potentiometers. The factory sets the volts/Hz adjustment and normally requires no further adjustment. If replacement of the controller circuit board or operation of the generator under extreme loads results in voltage instability, adjust the potentiometers according to the procedure following. See Figure 7-10.
4. Start the generator set. With the generator running at no load, observe light bulb flicker. Excessive light bulb flicker indicates poor stability.
5. Adjust the stability potentiometer until minimum flicker is obtained.
6. Use the controller voltage adjustment potentiometer (or remote voltage adjustment potentiometer) to make adjustments to the generator while running under normal load, if required.
7. Adjust the engine speed to the desired cut-in frequency. Factory setting is 57.5--58.0 Hz for 60 Hz models or 47.5--48.0 Hz for 50 Hz models as measured on the frequency meter. See Section
7.14, Governor Adjustment, for more information on engine adjustment.
1
2
3
C-255670-D
1. 60 Hz voltage adjustment
2. 50 Hz voltage adjustment
3. Stability adjustment
Figure 7-10 AVR Adjustment
Stability Potentiometer. Fine tunes the voltage
regulator to reduce light flicker.
Volt/Hz Potentiometer. This adjustment determines engine speed (Hz) at which the generator output voltage begins to drop.
8. Rotate the Volts/Hz adjustment potentiometer counterclockwise until the voltage level begins to drop (as measured on the voltmeter). When set to these specifications, the generator attempts to maintain normal output until the engine speed drops below the frequency set in the previous step (as load is applied).
9. Adjust the engine speed to the appropriate operating point. See Section 7.14.
10. Use the controller voltage adjustment potentiometer (or remote voltage adjustment potentiometer) to make final adjustments to the generator while running under normal load.
11. Readjust the stability potentiometer, if necessary.
12. Check the AVR’s function by reducing the engine speed (Hz) and watching for a corresponding drop in AC voltage.
At 60 Hz operation, AC voltage remains constant until the engine speed drops below 58 Hz (approximately). If AC frequency drops below 58 Hz, AC voltage declines.
Voltage Regulator Adjustment
1. Place the generator set master switch in the OFF/RESET position.
2. Set the stability potentiometer to the far counterclockwise position.
3. Connect a 100-watt light bulb across terminals V0 and V7 on the controller terminal strip or across the terminals on the controller frequency meter.
At 50 Hz operation, AC voltage remains constant until the engine speed drops to 48 Hz (approximately). If AC frequency drops below 48 Hz, AC voltage declines.
If the AVR does not function as described above, refer to the following test for the cause of the malfunction.
TP-5737 5/0166 Section 7 Component Testing and Adjustment
Page 81
Voltage Regulator Test
1. Close the safeguard breaker, if equipped.
2. Disconnect the wiring harness connector from the voltage regulator and check for continuity between the voltage sensing leads V7 and V8 (pins 4 and
10). See Figure 7-11. If the circuit between V7 and V8 is open, repair or replace it. An open circuit normally results in a high voltage or overvoltage condition.
3. Check the 15-amp fuse, if equipped.
4. If continuity exists between V7 and V8, check for continuity in the voltage adjustment circuit (leads 67 and 68). Disconnect the voltage regulator harness plug and check for resistance between pins 1 and 3. Measured resistance should change as the voltage adjust rheostat is turned. Repair or replace inoperative components as necessary.
Note: An inoperative voltage adjust rheostat
usually results in a nonadjustable voltage.
5. Check the 15-amp fuse, if equipped, inside the controller. If this circuit is open, repair or replace the inoperative components and/or wiring.
1
3-101
R8371-3
6. Check for battery voltage at the voltage regulator harness plug (pins 2 and 11) with the generator set running. If there is no battery voltage between pins 2 and 11, check the safeguard circuit breaker.
Note: Lack of battery voltage to the voltage
regulator usually results in very low voltage at the main output leads.
7. While the generator set is running, check for approximately 1--2 volts DC output between terminals 3B (+) and 5B (--) on the LED board or disconnect the 3B/5B connector at the LED board and check for 8 volts DC (approximately) at the connector. If there is no DC voltage output present between 3B and 5B, check for an open or short circuit in the wiring back to the voltage regulator. If a fault exists in the voltage regulator wiring, repair or replace as necessary. If the voltage regulator wiring appears functional, replace the voltage regulator.
Note: Low or no voltage at the LED circuit board
may cause a low output voltage fault.
2
1. AVR board in junction box
2. Controller terminal strip
Figure 7-11 AVR and Connections
A-328917-X
TP-5737 5/01 67Section 7 Component Testing and Adjustment
Page 82
7.6 Stator
Note: When replacing the rotor or stator, use a
skewed (slanted) rotor with a straight stator per original manufacturer.
Stator Test Procedure
1. Check the generator output leads for proper connections. See Section 9, Wiring Diagrams.
2. Check the stator windings for:
a. Shorted windings: Replace the stator if burnt or
hot windings exist. See Figure 7-12.
Note: Disconnect V7, V8, V9, and V0 leads at
the controller AC fuse terminal blocks before performing the open winding test.
b. Open windings: With an ohmmeter, check each
pair of leads for low resistance readings (continuity). High resistance across A or low resistance (continuity) across B and ground indicates a faulty stator; if so, replace the stator. See Figure 7-13.
142536710811912
A
B
C
A. Continuity/resistance B. No continuity C. No continuity
2
1. Leads
2. Windings
Figure 7-12 Stator
1
R12758-8
TP-5353-7
3-100
Figure 7-13 Stator Winding Test
TP-5737 5/0168 Section 7 Component Testing and Adjustment
Page 83
7.7 Generator Field
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
High voltage test. Hazardous voltage can cause severe injury or death. Follow the instructions of the test equipment
manufacturer when performing high-voltage tests on the rotor or stator. An improper test procedure can damage equipment or lead to generator set failure.
WARNING
Moving rotor.
6. Using a megohmmeter, apply 500 volts DC to the F+ or F-- lead and the rotor shaft. See Figure 7-15. Follow the instructions of the megohmmeter manufacturer when performing this test. A reading of approximately 5--7 kOhms and higher indicates the field winding is functional. A reading of less than 5--7 kOhms (approximately) indicates deterioration of the winding insulation and possible current flow to ground.
7. Repair or replace the rotor assembly.
Repair the F+ and F-- leads if this test shows the leads are shorted to ground. If using splices, solder and insulate the splices. Use new sleeving when tying the leads to the shaft or the heat sink.
Replace the generator rotor assembly if this test shows a shorted or grounded winding.
Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
Servicing the generator. Hot parts can cause severe injury or death. Avoid touching the generator set field or
exciter armature. When shorted, the generator set field and exciter armature become hot enough to cause severe burns.
Generator Field Test
1. Disconnect the generator set engine starting battery, negative (--) lead first.
2. Remove the end bracket. See Section 7.9, End Bracket Removal and Replacement, and Section 8, Disassembly/Reassembly.
3. Disconnect F+ and F-- from the SCR assembly.
4. With an ohmmeter, check for continuity across the F+ and F-- leads (see Figure 7-14). Resistance readings are shown in Section 1, Specifications, Generator.
1
9
1. Ohmmeter connections across F+ and F-- leads
Figure 7-14 Field Continuity Check
3-100
R12758-8
TP-5353-7
5. Check for a grounded generator field. No continuity should exist between the field leads and the rotor assembly.
TP-5737 5/01 69Section 7 Component Testing and Adjustment
Page 84
WARNING
Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
Servicing the generator. Hot parts can cause severe injury or death. Avoid touching the generator set field or
exciter armature. When shorted, the generator set field and exciter armature become hot enough to cause severe burns.
1
M
1. Megohmmeter connections across F+ and F-- leads and rotor shaft
Figure 7-15 High Voltage Test
7.8 Exciter Armature
WARNING
Hazardous voltage. Can cause severe injury or death.
Moving rotor.
3-100
R12758-8
TP-5353-7
Exciter Armature Test
1. Disconnect the generator set engine starting battery, negative (--) lead first.
2. Remove the end bracket. See Section 7.9, End Bracket Removal and Replacement and Section 8, Disassembly/Reassembly for end bracket removal.
3. Disconnect the AC leads from the SCR assembly.
4. With an ohmmeter, check for continuity across the AC leads. See Figure 7-16.
5. Repair the AC leads if they are damaged or open. Solder and insulate any splices used. Use new sleeving when tying the leads to the shaft or the heat sink.
6. Visually check the exciter armature for shorted winding(s); with an ohmmeter check for low resistance readings. See Section 1, Specifications, Generator, for designed resistance readings. See Figure 7-16. Low resistance readings indicate a faulty exciter armature requiring replacement of the rotor assembly.
Operate the generator set only when all guards and electrical enclosures areinplace.
High voltage test. Hazardous voltage can cause severe injury or death. Follow the instructions of the test equipment
manufacturer when performing high-voltage tests on the rotor or stator. An improper test procedure can damage equipment or lead to generator set failure.
TP-5737 5/0170 Section 7 Component Testing and Adjustment
Page 85
8. Repair or replace the rotor.
Repair the AC leads if this test indicates the leads are shorted to ground. Solder and insulate any splices used. Use new sleeving when tying the leads to the shaft or the heat sink.
Replace the rotor assembly if this test shows the armature is shorted to ground.
1
9
3-100
R12758-8
TP-5353-7
1. Ohmmeter connections across AC leads
Figure 7-16 Exciter Armature Continuity Check
7. Using a megohmmeter, apply 500 volts DC to the rotor shaft and either AC lead. See Figure 7-17. Follow the instructions of the megohmmeter manufacturer when performing this test. A reading of approximately 5--7 kOhms and higher indicates the field winding is functional. A reading of less than 5--7 kOhms (approximately) indicates deterioration of the winding insulation and possible current flow to ground.
1
M
1. Megohmmeter connections across either AC lead and rotor shaft
Figure 7-17 Exciter Armature High Voltage Test
3-100
R12758-8
TP-5353-7
TP-5737 5/01 71Section 7 Component Testing and Adjustment
Page 86
7.9 End Bracket Removal and Replacement
See Section 8, Disassembly/Reassembly for more information.
Note: Loosen the generator junction box before
removing the end bracket. Remove the six junction box mounting screws and pull the junction box away from the engine to remove the end bracket.
End Bracket Replacement
Reverse the order of the disassembly to reinstall the end bracket/exciter field assembly.
End Bracket Removal
1. Remove the LED board and cover.
2. Disconnect the leads from the speed sensor.
3. Remove the screws holding the actuator cup and the photo transistor board.
4. Reach inside the stator shell and disconnect the photo transistor board leads from the SCR assembly to allow for slack when removing the end bracket.
5. Remove the four bolts holding the end bracket to the stator.
6. Use a puller tool to remove the end bracket. See Figure 7-18.
Note: To avoid loosening the exciter field magnets,
do not attempt to remove the end bracket by pounding it with a hammer.
7. Pull the end bracket and exciter field assembly over the exciter armature. Do not damage the exciter field magnets or photo transistor board.
2
1. End bracket
2. Puller tool
Figure 7-18 Removing End Bracket
1
3-096
R8936-2
TP-5737 5/0172 Section 7 Component Testing and Adjustment
Page 87
7.10 Speed Sensor Test
The following procedure determines if the speed sensor (overspeed fault) is emitting a signal.
2. Touchthe sensing surface with a flat piece of iron or steel at least 4.1 cm (1/4 cubic inch) in size. The voltmeter test reading should equal the source voltage.
Speed Sensor Signal Test
1. With the generator set master switch in the OFF/RESET position, connect a DC voltmeter between the positive (+) lead (wire 24) at the speed sensor and the ground (wire 2). The voltmeter should indicate approximately 8--10 volts DC.
2. With the generator set running, connect the DC voltmeter negative probe to the 0 terminal (wire 16—white) on the speed sensor. Place the voltmeter positive probe on the positive (+) terminal (wire 24—red). The voltmeter should indicate approximately 12 volts DC.
Note: During the test the controller leads must
remain connected to the speed sensor terminals. Slide the leads from the speed sensor terminals only enough to expose the connection for the test leads. Do not disconnect the leads.
If the speed sensor emits a signal, check the continuity of the speed sensor leads (wires 2, 16, and 24) between the controller P1 connector and the lead terminals at the speed sensor.
If the speed sensor does not emit a signal, test the speed sensor through the following procedure.
Speed Sensor Test
1. Connect the speed sensor, voltmeter, and DC voltage source as shown in Figure 7-19.
3. Remove the iron or steel from the sensing surface. Observe no test voltmeter reading.
7.11 Current Transformers
7.11.1 Function and Application
Current transformers provide several generator set functions including signal/drive for:
D Controller AC voltmeter/ammeter
D Safeguard circuit breaker
D Reactive droop compensator.
Generator set models do not have current transformers when they do not include the above items. The meters and safeguard circuit breaker share the same current transformer while the reactive droop compensator uses a separate current transformer. See Figure 7-20. The generator set junction box contains the stator leads and the current transformers.
When replacing the current transformer or stator assembly, install the current transformer according to the generator reconnection decal on the generator set, or see Section 9, Wiring Diagrams. Observe the correct current transformer position when installing the stator leads. The current transformer dot or HI mark position and the stator lead direction are essential for correct component function.
1
+
o + ---
3
1. DC voltmeter
2. 12-volt battery or DC power supply
3. Speed sensor
Figure 7-19 Speed Sensor Test
TP-5737 5/01 73Section 7 Component Testing and Adjustment
+
---
2
TP-5353-7
Page 88
WARNING
TT-1123/347058 -D
Figure 7-20 Current Transformers
A current transformer contains a coil of wire that induces a secondary voltage/current from the primary or stator lead passing through the center. The number of coil turns inside the current transformer determines the ratio. Replacement current transformers must have the same ratio as the original.
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury
and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
Moving rotor.
7.12.2 Reactive Droop Compensator Adjustment Procedure
Parallel the two generator sets using the following procedure. Read and understand the entire procedure before beginning.
1. Remove any load connected to the generator set. Start each generator set by placing the generator set master switch in the RUN position.
2. Set the reactive droop compensator rheostat on generator set no. 1 to the minimum counterclockwise (CCW) setting. Record the RPM or frequency and voltage at 1/4 load steps to full load on unit no. 1
3. Repeat step 2 for generator set no. 2.
7.11.2 Testing
Use an ohmmeter to check the current transformer. Perform this test with the current transformer disconnected from the generator set. A resistance reading of infinity or 0 ohms suggests an open or shorted current transformer that needs replacement. Consider any other resistance reading acceptable.
7.12 Reactive Droop Compensator
7.12.1 Function and Application
The reactive droop compensator kit distributes the generator set load evenly between two generator sets in parallel. If the kit is not factory installed, use the installation instructions supplied with the kit for field installation. Use the following procedure for reactive droop compensator adjustment.
4. Compare the readings and make final adjustments so that the voltage is within 1 volt at each load step and the speed is within three RPM or the frequency is within 0.1 Hz for each unit. Adjust the voltage using the controller or remote voltage adjustment potentiometer. Adjust the speed at the electronic governor or at the remote adjusting potentiometer.
5. Check the droop compensation on each unit as follows:
a. With unit no. 1 operating at the desired speed
and voltage, apply an inductive load one half to full load. Do not use a resistive load for this test.
b. Observe the voltmeter on unit no. 1 with the
reactive droop compensator rheostat set at minimum. As the rheostat is turned clockwise (CW), the voltmeter should show a decrease in voltage. If observing a larger voltage, stop the
TP-5737 5/0174 Section 7 Component Testing and Adjustment
Page 89
generator sets and reverse the direction of the generator load line through the current transformer or reverse the transformer leads on unit no. 1.
c. Restart the generator sets and recheck the
droop on unit no. 1.
6. Apply resistive load (1.0 power factor) until reaching rated current.
7. Adjust the reactive droop compensator rheostat to achieve a 4% droop (decrease) in voltage.
8. Remove the resistive load.
d. Set the reactive droop compensator rheostat to
a value at approximately 4% below rated voltage at full load. As an example, the voltage droops (decreases) 19.2 volts on a 480-volt system at full load or 9.6 volts at one half load. Use the following formula for loads other than full load:
Rated Voltage x 0.04 x Actual Load (expressed as a % of full load) = Voltage Droop
Note: With full load 0.8 power factor, a droop of
3--5% should be adequate for paralleling.
6. Repeat step 5 for generator set no. 2. Adjust unit no. 2 where the voltage droop is equal and at the same point as on unit no. 1. The two units share reactive currents proportionately after correctly performing this procedure.
7. If reactive load is not available, go to Section 7.12.3, Reactive Droop Compensator Alternate Adjustment Procedure. If reactive load is available, go to Section 7.12.4, Testing.
7.12.3 Reactive Droop Compensator Alternate Adjustment Procedure
Initially calibrate each generator set using the following procedure.
1. Turn the reactive droop compensator rheostat on generator set no. 1 to the minimum setting.
2. Remove the controller cover. Move the voltage sensing lead from V7 to V9 at the AC fuse terminal block.
3. Remove any load connected to the generator set.
4. Start the generator set by placing the generator master switch in the RUN position.
9. Stop the generator set by placing the generator master switch in the OFF position.
10. Return the voltage sensing lead from V9 to V7 at the AC fuse terminal block.
11. Replace the controller cover.
12. Repeat steps 1--11 for generator set no. 2.
7.12.4 Testing
Use the following procedure to check that the generator sets share the reactive load proportionately.
1. Parallel the units at one half to full load. Verify that each unit carries equal kW load or a load proportional to its capacity using the wattmeter readings. If load unbalance exists, adjust and recheck the electronic governor throttle control to correctly balance loading. Engine speed determines load sharing ability.
2. With the load balanced, check the ammeters for equal current or proportional according to capacity. If the currents are incorrect, adjust the reactive droop compensator rheostat reducing the current of the unit with the highest reading. Reduce the current to an equal division or proportionately.
3. Stop each generator set by placing the generator master switch in the OFF position.
Note: Step 1 balances the load using the electronic
governor and step 2 balances the current using the reactive droop compensator. Consider these settings optimum for parallel operation.
Note: Voltage must droop (decrease) on lagging power
factor loads (inductive loads). A small change in voltage is acceptable on unity power factor loads (resistive loads).
5. Use the controller or remote voltage adjusting potentiometer on each generator set to fine adjust voltage as necessary.
TP-5737 5/01 75Section 7 Component Testing and Adjustment
Page 90
7.13 Gauge Senders
The resistance of the oil pressure and water temperature sender output signals varies as the respective pressure and temperature change. Use the resistance change for verification of sender function. Disconnect all leads from the sender before checking resistance. If the sender functions and the gauge does not function, check the engine wiring harness, leads, and connectors before replacing the gauge.
Note: Some generator sets may have senders/
switches incorporated with the engine ECM (electronic control module). Identify engine ECM senders/switches by lead designations listed in the following testing information. Refer to Section 9, Wiring Diagrams for additional lead identification information. Use the engine service manual for troubleshooting ECM senders/switches.
7.13.1 Oil Pressure Sender Testing
Disconnect the oil pressure sender lead 7C. See Figure 7-21. Check the sender resistance with an ohmmeter. Compare the resistance values when the generator set is shut down and when it is running at operating temperature to the values shown in Section 1.2, Specifications.
7.13.2 Water Temperature Sender Testing
The water temperature sender is a single function, single-terminal type. See Figure 7-22.
Lead 5
TP-5353-7
Figure 7-22 Water Temperature Sender, Typical
Disconnect the water temperature sender lead 5. Check the sender resistances with an ohmmeter. Compare the resistance values when the generator set is shut down and when it is running at operating temperature to the values in Section 1.2, Specifications.
Use a mechanical oil pressure gauge to further verify correct readings.
Lead 7C
TP-5353-7
Figure 7-21 Oil Pressure Sender, Typical
TP-5737 5/0176 Section 7 Component Testing and Adjustment
Page 91
7.14 Governor Adjustment
7.14.1 Mechanical Governor
7.14.2 Electronic Governor—Barber­Colman Dyna 2500 125--150 kW John Deere Engine-Powered 6081
Note: Before checking and adjusting engine
speed, make sure the engine reaches its normal operating temperature.
Note: All speed specs apply to an engine at
operating temperature under load conditions. The maximum permissible speed variation is 2--3 Hz or 50--90 rpm for fast idle speed.
Mechanical Governor Adjustment Procedure
1. Disconnect the speed control from the fuel injection pump lever and start the engine.
2. Verify that the injector pump lever holds in the fast idle position against the fast idle adjusting screw. See Figure 7-23.
3. Using a frequency meter, check the engine speed. Adjust the engine speed at full load to 1800 rpm (60 Hz) or 1500 rpm (50 Hz). To increase the engine speed, turn the fast idle adjusting screw counterclockwise; turn the fast idle adjusting screw clockwise to decrease engine speed.
Some sets are equipped with Barber-Colman Dyna 2500 electronic governors. Because this is an electronic device, no mechanical drive or hydraulic connection is required. The system consists of a magnetic pickup, an electronic control unit, and an actuator. The magnetic pickup monitors engine speed and transmits this information to the electronic control unit (see Figure 7-24 or Figure 7-25). The electronic control unit interprets the signal from the magnetic pickup to control current input to the throttle actuator. The throttle actuator adjusts the throttle position on the engine. See Figure 7-26.
1
4. Reconnect the speed control to the fuel injection pump lever.
5. Stop the generator set.
12
1. Injection pump lever
2. Fast idle adjusting screw
TP-5353-7
Figure 7-23 Governor Adjustments, Typical
7
2
3
456
KC250000B-A
1. Control unit
2. Magnetic pickup
3. Actuator
4. Connect to safeguard breaker terminal strip
5. Connect to cranking solenoid, battery (+)
6. Connect to 70 on safeguard breaker terminal block
7. Relay
Figure 7-24 Governor Control Unit,
Nonparalleling Generator Set
TP-5737 5/01 77Section 7 Component Testing and Adjustment
Page 92
1
8
2
2
3
4
7
5
6
1. Control unit: terminal #1—positive, terminal #2—negative
2. Magnetic pickup
3. Optional remote speed potentiometer
4. Actuator
5. Connect to safeguard breaker terminal strip
6. Connect to cranking solenoid, battery (+)
7. Relay
8. Connect to 70 on safeguard breaker terminal block
KC250000B-A
Figure 7-25 Governor Control Unit,
Paralleling Generator Set
Adjust the actuator shaft linkage to hold the fuel injection pump lever in the stop position when the power is off. The magnetic pickup air gap is 0.36--0.71 mm (0.014--0.028 in.).
1
1. Actuator
2. Linkage
TP-5353-7
Figure 7-26 Throttle Actuator (Barber-Colman
Dyna 2500, John Deere 6076 Shown)
The Barber-Colman control unit is equipped with switches S1 and S2. Before making governor adjustments, verify that S1 and S2 are in the correct positions for your application. See Figure 7-27. Switch S1 selects the controller response range based upon engine type. Place switch S2 to match the control unit of the governor actuator. These generator sets use the Dyna 2500 actuator.
Fuel Type S1 Switch Position
Diesel Off
Control Unit Type S2 Switch Position
Dyna 2500 On (in all cases)
Figure 7-27 Electronic Governor Switch Settings
TP-5737 5/0178 Section 7 Component Testing and Adjustment
Page 93
Preliminary Adjustment Procedure
1. Place the generator set master switch in the OFF position. Do not run the generator set.
2. Set the control unit “I” adjustment one division from zero, the “D” adjustment four divisions from zero, and the gain adjustment at the third division from zero.
3. For isochronous operation, turn the droop adjustment potentiometer counterclockwise (CCW) to the minimum position. For droop operation, turn the droop potentiometer to the desired droop. Droop adjustment may be necessary with parallel generator operation.
Note: If the governor uses the full stroke of the
actuator shaft and the linkage adjustment uses only the active fuel range, the maximum obtainable droop would be approximately 12% at full load.
4. Position the actuator lever to hold the fuel pump lever in the STOP position when the power is off. Adjust the actuator linkage for smooth, non-binding operation.
Final Adjustment Procedure
1. Place the generator set master switch in the RUN or TEST position to start the generator set.
2. Adjust the control unit speed potentiometer until the engine operates at the desired rpm (50 or 60 Hz on the frequency meter).
4. With the engine running at no load, finalize the “I”, “D”, and gain adjustments.
5. Slowly turn the gain adjustment potentiometer clockwise (CW) until the output shaft and linkage oscillates. Slowly turn the gain adjustment potentiometer CCW until the actuator lever stabilizes.
6. Jog the actuator lever by hand. If the actuator lever oscillates three to five times and then stabilizes, the gain setting is correct.
7. Turn the gain potentiometer one division CCW.
8. Turn the “D” adjustment fully CW while observing the actuator shaft. If the lever does not become unstable, jog it by hand. When the lever oscillates, turn the “D” adjustment CCW slowly until the actuator shaft stabilizes. Jog the lever again, it should oscillate 3--5 times and then become stable. If the system response to load changes is satisfactory at this point, omit step 9 and proceed to step 10.
9. Turn the “I” potentiometer fully CW and watch the actuator shaft. If the actuator lever does not become unstable, jog it by hand. When the actuator lever slowly oscillates, slowly turn the “I” potentiometer CCW until the lever stabilizes.
10. Jog the actuator lever by hand. It should oscillate 3--5 times before stabilizing. The governor is now calibrated.
11. Stop the generator set.
3. If governing is unstable, turn the “I” and gain potentiometers slightly CCW.
Note: Except for the speed potentiometer, control
unit potentiometers have internal stops at 0 and 100%.
TP-5737 5/01 79Section 7 Component Testing and Adjustment
Page 94
7.14.3 Electronic Governor, Barber-Colman Dyna 70025 using Stanadyne D Series Injection Pump 35--99 kW John Deere Engine-Powered 4045 and 6068
Some sets are equipped with Barber-Colman Dyna 70025 electronic governor used in conjunction with a Stanadyne D Series injection pump. This particular setup uses different governor controllers for a nonparalleling generator set or a paralleling generator set. The system consists of a magnetic pickup, an electronic control unit, and an actuator. The magnetic pickup monitors engine speed and transmits this information to the electronic control unit.
See Figure 7-28 for nonparalleling generator sets or Figure 7-29 for paralleling generator sets. The electronic control unit interprets the signal from the magnetic pickup to control the current input to the throttle actuator. The integrated throttle actuator adjusts the throttle position internally in the fuel injection pump. See Figure 7-30. The magnetic pickup air gap is
0.36--0.71 mm (0.014--0.028 in.).
1
2
3 4
6
1
8
2
3
6
7
5
1. Twist magnetic pickup leads before connecting to control. 1 turn per 25 mm (1inch)
2. Power cable
3. Relay
4. Connect to safeguard breaker terminal strip
5. Connect to cranking solenoid, battery (+)
6. Connect to 70 on safeguard breaker terminal strip
7. Actuator
8. Magnetic pickup
4
FT273B-X
5
7
10
11
1. Droop potentiometer
2. Gain potentiometer
3. Idle speed potentiometer
4. Run speed potentiometer
5. Magnetic pickup
6. Power cable
7. Relay
8. Connect to safeguard breaker terminal strip
9. Connect to cranking solenoid, battery (+)
10. Connect to 70 on safeguard breaker terminal strip
11. Actuator
9
Figure 7-29 Governor Control Unit, Paralleling
Generator Set
8
FT273B-X
Figure 7-28 Governor Control Unit, Nonparalleling
Generator Set
TP-5737 5/0180 Section 7 Component Testing and Adjustment
Page 95
12 34 5
1. Low idle adjustment screw
2. High idle adjustment screw
3. Injector pump/actuator
4. Shutoff shaft assembly
5. Droop adjusting screw
TP-5353-7
Note: Follow this procedure carefully to prevent
engine overspeed and damage to the generator or other load.
3. Turn the droop adjusting screw counterclockwise until it stops. Only paralleling generator sets use the droop adjustment.
Note: Turn the droop adjusting screw clockwise
(CW) two full turns. The mechanical governor is now set in a position that permits starting the engine to calibrate the electronic integrated actuator governor. Do not operate the engine without the electronic governor connected and the system calibrated correctly as described in the following procedure. After making this droop adjustment, do not readjust.
Governor Calibration for Nonparalleling Generator Sets
Figure 7-30 Governor Adjustments, Typical
Actuator Calibration Procedure
Use the following procedure to set up the mechanical governor for operation with the electronic integrated actuator. Perform calibration of both the mechanical and electronic governor in order for the system to operate correctly. Lack of maximum power or poor steady state speed control results from incorrect calibration. See Figure 7-30.
Note: The factory actuator calibration procedure
requires no additional adjustment. Perform the actuator calibration procedure only if removal of the fuel injection pump occurs or the adjustment is questionable. Do not perform this procedure unless it is deemed necessary.
1. Turn the shutoff shaft assembly in the fuel injection pump clockwise to the on position. The shutoff shaft assembly is the lever located on the backside of the fuel injection pump. Secure using existing mechanical linkage.
2. Place the throttle shaft assembly in the high idle position. Back out the low idle adjustment screw a maximum of three turns. Excessive backing out of the low idle screw results in the disengagement of the pump’s internal components.
Preliminary Adjustments
1. Place the generator set master switch in the OFF position. Do not run the generator set.
2. Set the gain adjustment three divisions from zero.
Final Adjustments
1. Place the generator set master switch in the RUN position to start the generator set.
2. Adjust the control unit speed potentiometer until the engine operates at the desired rpm (50 or 60 Hz on the frequency meter).
3. If governing is unstable, turn the gain potentiometer slightly counterclockwise.
Note: Gain potentiometer has internal stops at 0
and 100%.
4. With the engine running at no load, finalize the gain adjustment. Turn the gain adjustment clockwise until the output shaft and linkage stabilizes. Upset the linkage by hand. If the linkage oscillates 3--5 times and then stops, the setting is correct.
5. Stop the generator set.
TP-5737 5/01 81Section 7 Component Testing and Adjustment
Page 96
Governor Calibration for Paralleling Generator Sets
Calibration Procedure
1. Place the generator set master switch in the OFF position. Do not run the generator set.
2. Set the gain potentiometer at 30% and turn the droop potentiometer completely counterclockwise.
3. Turning the 20-turn potentiometer clockwise increases idle speed and turning it counterclockwise decreases idle speed.
4. Turning the 20-turn potentiometer clockwise increases run speed and turning it counterclockwise decreases run speed.
5. Place the generator set master switch in the RUN or TEST position to start the generator set.
6. Slowly turn the gain potentiometer clockwise until the engine becomes unstable. After the engine becomes unstable, slowly turn the gain potentiometer counterclockwise until stable. Interrupt the governor by momentarily removing power from the governor. The engine should recover in 3--5 seconds with diminishing oscillation.
Droop Adjustment Procedure
1. Place the generator set master switch in the RUN or TEST position to start the generator set.
2. Use the run speed potentiometer to set the engine rpm to the desired no load speed (frequency) on the frequency meter.
3. Apply full load to the generator set.
4. While observing the frequency meter, slowly turn the droop potentiometer clockwise to the desired droop percentage.
5. Remove full load from the generator set.
6. Using the run speed potentiometer, readjust the engine rpm to the desired no load speed (frequency) on the frequency meter.
7. Stop the generator set.
7. Stop the generator set.
TP-5737 5/0182 Section 7 Component Testing and Adjustment
Page 97
Section 8 Disassembly/Reassembly
Before beginning the generator set disassembly procedure, carefully read all safety precautions at the beginning of this manual. Please observe these precautions and those included in the text during the disassembly/ reassembly procedure.
The following procedures cover many models and some steps may not apply to a particular engine. Use Figure 8-1 and Figure 8-2 to help understand component descriptions and general configuration of the generator set.
Use the disassembly procedure as a step-by-step means to help take apart the generator set. The disassembly procedure provides important information to minimize disassembly time and indicates where special configurations exist which may require taking notes. The reassembly procedure includes important alignment steps and provides critical torque specs.
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
TP-5737 5/01 83Section 8 Disassembly/Reassembly
Page 98
WARNING
Perform the following steps before disassembling the generator set.
Remove the Generator Set from Service
Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts. The
engine and exhaust system components become extremely hot during operation.
WARNING
Explosive fuel vapors. Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly explosive. Use
extreme care when handling and storing fuels. Store fuels in a well-ventilated area away from spark-producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts or from sparks. Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors. Keep the fuel lines and connections tight and in good condition. Do not replace flexible fuel lines with rigid lines. Use flexible sections to avoid fuel line breakage caused by vibration. Do not operate the generator set in the presence of fuel leaks, fuel accumulation, or sparks. Repair fuel systems before resuming generator set operation.
1. Disconnect the generator set engine starting battery, negative (--) lead first and remove the starting batteries from the work area to prevent fire hazard.
2. Disconnect the AC-powered accessories, such as the battery charger, block heater, and fuel transfer pump.
3. Shut off the fuel supply. Drain the fuel system as necessary by emptying fuel into proper containers. Remove any fuel containers from the work area to prevent fire hazard. Ventilate the work area to clear fumes.
4. Disconnect the fuel, cooling, and exhaust systems as necessary to tilt the generator set. Disconnect the output leads or load circuit cables at the generator set.
5. Any cranes, hoists, or other lifting devices used in the disassembly or reassembly procedure must be rated for the weight of the generator set. Check the generator set nameplate or spec sheet for weight.
84 Section 8 Disassembly/Reassembly
TP-5737 5/01
Page 99
16
2
3
4
1
5
6
14
15
13
7
12
11
6
10
1. Voltage regulator terminal strip
2. Voltage regulator panel
3. Voltage regulator
4. Voltage regulator wiring harness
5. Junction box cover
6. Junction box panel
7. Junction box
8. Alternator assembly
8
9
EM-273000-
9. End bracket cover
10. Skid
11. Generator fan guard
12. Drive discs
13. Stud
14. Spacer
15. Flywheel
16. Engine side of flywheel
Figure 8-1 Generator Set Components, Typical
TP-5737 5/01
Section 8 Disassembly/Reassembly
85
Page 100
1
2
3
4
5
6
9
8
7
11
AC
AC
F+
G
F ---
12
10
13
1. LED circuit board cover
2. LED circuit board
3. Photo transistor board
4. Insulating washer
5. Insulator
6. Magnetic actuator
7. End bracket
Figure 8-2 Generator Set Components, Typical
86
Section 8 Disassembly/Reassembly
14
B-257657-Y
8. Exciter field assembly
9. Rotor assembly
10. SCR assembly
11. Generator set fan
12. Drive discs
13. Stator assembly
14. Generator adapter
TP-5737 5/01
Loading...