Engine exhaust from this product contains chemicals
known to the State of California to cause cancer, birth
defects, or other reproductive harm.
California Proposition 65
WARNING
!
Product Identification Information
Product identification numbers determine service
parts. Record the product identification numbers in
the spaces below immediately after unpacking the
products so that the numbers are readily available for
future reference. Record field-installed kit numbers
after installing the kits.
Generator Set Identification Numbers
Record the product identification numbers from the
generator set nameplate(s).
Model Designation ___________________________
Specification Number _________________________
Serial Number ______________________________
Accessory NumberAccessory Description
Controller Identification
Record the controller description from the generator
set operation manual, spec sheet, or sales invoice.
Controller Description _________________________
Engine Identification
Record the product identification information from the
engine nameplate.
IMPORTANT SAFETY INSTRUCTIONS
Electro-mechanical equipment, including
generator sets, transfer switches,
switchgear, and accessories, can cause
bodily harm and pose life-threatening
danger when improperly installed,
operated, or maintained. To prevent
accidents be aware of potential dangers
and act safely. Read and follow all safety
precautions and instructions. SAVE
THESE INSTRUCTIONS.
This manual has several types of
safety precautions and instructions:
Danger, Warning, Caution, and Notice.
Danger indicates the presence of a
hazard that will cause severe
personal injury, death, or
substantial property damage.
Warning indicates the presence of a
hazard that can cause severe personal
injury, death, or substantial property
damage.
Caution indicates the presence of a
hazard that will or can cause minorpersonaI injury or property damage.
Notice communicates installation,
operation, or maintenance information
that is safety related but not hazard
related.
Safety decals affixed to the equipment
in prominent places alert the operator
or service technician to potential
hazards and explain how to act safely.
The decals are shown throughout this
publication to improve operator
recognition. Replace missing or
damaged decals.
Accidental Starting
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (–) lead first
when disconnecting the battery.
Reconnect the negative (–) lead last
when reconnecting the battery.
Disabling the generator set.
Accidental starting can cause
severe injury or death. Before
working on the generator set or
equipment connected to the set,
disable the generator set as follows:
(1) Press the generator set
OFF/RESET button to shut down the
generator set. (2) Disconnect the
power to the battery charger, if
equipped. (3) Remove the battery
cables, negative (–) lead first.
Reconnect the negative (–) lead last
when reconnecting the battery. Follow
these precautions to prevent the
starting of the generator set by the
remote start/stop switch.
Battery
!
WARNING
Sulfuric acid in batteries.
Can cause severe injury or death.
Wear protective goggles and
clothing. Battery acid may cause
blindness and burn skin.
Explosion.
Can cause severe injury or death.
Relays in the battery charger
cause arcs or sparks.
Locate the battery in a
well-ventilated area. Isolate the
battery charger from explosive
fumes.
Battery electrolyte is a diluted
sulfuric acid. Battery acid can
cause severe injury or death.
Battery acid can cause blindness and
burn skin. Always wear splashproof
safety goggles, rubber gloves, and
boots when servicing the battery. Do
not open a sealed battery or mutilate
the battery case. If battery acid
splashes in the eyes or on the skin,
immediately flush the affected area for
15 minutes with large quantities of
clean water. Seek immediate medical
aid in the case of eye contact. Never
add acid to a battery after placing the
battery in service, as this may result in
hazardous spattering of battery acid.
Battery acid cleanup. Battery acid
can cause severe injury or death.
Battery acid is electrically conductive
and corrosive. Add 500 g (1 lb.) of
bicarbonate of soda (baking soda) to a
container with 4 L (1 gal.) of water and
mix the neutralizing solution. Pour the
neutralizing solution on the spilled
battery acid and continue to add the
neutralizing solution to the spilled
battery acid until all evidence of a
chemical reaction (foaming) has
ceased. Flush the resulting liquid with
water and dry the area.
TP-6843 1/13Safety Precautions and Instructions5
Battery gases. Explosion can
WARNING
!
WARNING
!
cause severe injury or death.
Battery gases can cause an explosion.
Do not smoke or permit flames or
sparks to occur near a battery at any
time, particularly when it is charging.
Do not dispose of a battery in a fire.
To prevent burns and sparks that
could cause an explosion, avoid
touching the battery terminals with
tools or other metal objects. Remove
all jewelry before servicing the
equipment. Discharge static electricity
from your body before touching
batteries by first touching a grounded
metal surface away from the battery.
To avoid sparks, do not disturb the
battery charger connections while the
battery is charging. Always turn the
battery charger off before
disconnecting the battery connections.
Ventilate the compartments containing
batteries to prevent accumulation of
explosive gases.
Battery short circuits. Explosion
can cause severe injury or death.
Short circuits can cause bodily injury
and/or equipment damage.
Disconnect the battery before
generator set installation or
maintenance. Remove all jewelry
before servicing the equipment. Use
tools with insulated handles. Remove
the negative (–) lead first when
disconnecting the battery. Reconnect
the negative (–) lead last when
reconnecting the battery. Never
connect the negative (–) battery cable
to the positive (+) connection terminal
of the starter solenoid. Do not test the
battery condition by shorting the
terminals together.
Engine Backfire/Flash
Fire
Servicing the air cleaner. A sudden
backfire can cause severe injury or
death. Do not operate the generator
set with the air cleaner removed.
Servicing the fuel system. A flash
fire can cause severe injury or
death. Do not smoke or permit flames
or sparks near the carburetor, fuel line,
fuel filter, fuel pump, or other potential
sources of spilled fuels or fuel vapors.
Catch fuels in an approved container
when removing the fuel line or
carburetor.
Combustible materials. A fire can
cause severe injury or death.
Generator set engine fuels and fuel
vapors are flammable and explosive.
Handle these materials carefully to
minimize the risk of fire or explosion.
Equip the compartment or nearby area
with a fully charged fire extinguisher.
Select a fire extinguisher rated ABC or
BC for electrical fires or as
recommended by the local fire code or
an authorized agency. Train all
personnel on fire extinguisher
operation and fire prevention
procedures.
Exhaust System
Carbon monoxide.
Can cause severe nausea,
fainting, or death.
The exhaust system must be
leakproof and routinely inspected.
Carbon monoxide detectors.
Carbon monoxide can cause severe
nausea, fainting, or death. Install
carbon monoxide detectors on each
level of any building adjacent to the
generator set. Locate the detectors to
adequately warn the building’s
occupants of the presence of carbon
monoxide. Keep the detectors
operational at all times. Periodically
test and replace the carbon monoxide
detectors according to the
manufacturer’s instructions.
Carbon monoxide symptoms.
Carbon monoxide can cause severe
nausea, fainting, or death. Carbon
monoxide is a poisonous gas present
in exhaust gases. Carbon monoxide
is an odorless, colorless, tasteless,
nonirritating gas that can cause death
if inhaled for even a short time.
Carbon monoxide poisoning
symptoms include but are not limited
to the following:
• Light-headedness, dizziness
• Physical fatigue, weakness in
joints and muscles
• Sleepiness, mental fatigue,
inability to concentrate or speak
clearly, blurred vision
• Stomachache, vomiting, nausea
If experiencing any of these symptoms
and carbon monoxide poisoning is
possible, seek fresh air immediately
and remain active. Do not sit, lie
down, or fall asleep. Alert others to
the possibility of carbon monoxide
poisoning. Seek medical attention if
the condition of affected persons does
not improve within minutes of
breathing fresh air.
Generator set operation. Carbon
monoxide can cause severe
nausea, fainting, or death. Carbon
monoxide is an odorless, colorless,
tasteless, nonirritating gas that can
cause death if inhaled for even a short
time. Avoid breathing exhaust fumes
Fire.
Can cause severe injury or death.
Do not smoke or permit flames or
sparks near fuels or the fuel system.
6Safety Precautions and InstructionsTP-6843 1/13
when working on or near the generator
set. Never operate the generator set
inside a building. Never operate the
generator set where exhaust gas
could seep inside or be drawn into a
potentially occupied building through
windows, air intake vents, or other
openings.
Fuel System
WARNING
!
CAUTION
!
DANGER
!
WARNING
!
CAUTION
!
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.
The fuel system. Explosive fuel
vapors can cause severe injury or
death. Vaporized fuels are highly
explosive. Use extreme care when
handling and storing fuels. Store fuels
in a well-ventilated area away from
spark-producing equipment and out of
the reach of children. Never add fuel
to the tank while the engine is running
because spilled fuel may ignite on
contact with hot parts or from sparks.
Do not smoke or permit flames or
sparks to occur near sources of spilled
fuel or fuel vapors. Keep the fuel lines
and connections tight and in good
condition. Do not replace flexible fuel
lines with rigid lines. Use flexible
sections to avoid fuel line breakage
caused by vibration. Do not operate
the generator set in the presence of
fuel leaks, fuel accumulation, or
sparks. Repair fuel systems before
resuming generator set operation.
Gas fuel leaks. Explosive fuel
vapors can cause severe injury or
death. Fuel leakage can cause an
explosion. Check the LP vapor gas or
natural gas fuel system for leakage by
using a soap and water solution with
the fuel system test pressurized to 6-8
ounces per square inch (10-14 inches
water column). Do not use a soap
solution containing either ammonia or
chlorine because both prevent bubble
formation. A successful test depends
on the ability of the solution to bubble.
Hazardous Noise
Hazardous noise.
Can cause hearing loss.
Never operate the generator set
without a muffler or with a faulty
exhaust system.
Engine noise. Hazardous noise can
cause hearing loss. Generator sets
not equipped with sound enclosures
can produce noise levels greater than
105 dBA. Prolonged exposure to
noise levels greater than 85 dBA can
cause permanent hearing loss. Wear
hearing protection when near an
operating generator set.
Hazardous
Voltage/Moving Parts
Hazardous voltage.
Will cause severe injury or death.
This equipment must be installed
and serviced by qualified electrical
personnel.
!
WARNING
Hazardous voltage. Moving parts.
Can cause severe injury or death.
Hazardous voltage.
Backfeed to the utility system can
cause property damage, severe
injury, or death.
If the generator set is used for
standby power, install an automatic
transfer switch to prevent inadvertent
interconnection of standby and
normal sources of supply.
Welding the generator set.
Can cause severe electrical
equipment damage.
Never weld components of the
generator set without first
disconnecting the battery,
controller wiring harness, and
engine electronic control module
(ECM).
Grounding electrical equipment.
Hazardous voltage can cause
severe injury or death. Electrocution
is possible whenever electricity is
present. Ensure you comply with all
applicable codes and standards.
Electrically ground the generator set,
transfer switch, and related equipment
and electrical circuits. Turn off the
main circuit breakers of all power
sources before servicing the
equipment. Never contact electrical
leads or appliances when standing in
water or on wet ground because these
conditions increase the risk of
electrocution.
Operate the generator set only when
all guards and electrical enclosures
are in place.
TP-6843 1/13Safety Precautions and Instructions7
Welding on the generator set. Can
WARNING
!
WARNING
!
cause severe electrical equipment
damage. Before welding on the
generator set perform the following
steps: (1) Remove the battery cables,
negative (–) lead first. (2) Disconnect
all engine electronic control module
(ECM) connectors. (3) Disconnect all
generator set controller and voltage
regulator circuit board connectors. (4)
Disconnect the engine batterycharging alternator connections. (5)
Attach the weld ground connection
close to the weld location.
Connecting the battery and the
battery charger. Hazardous voltage
can cause severe injury or death.
Reconnect the battery correctly,
positive to positive and negative to
negative, to avoid electrical shock and
damage to the battery charger and
battery(ies). Have a qualified
electrician install the battery(ies).
Short circuits. Hazardous
voltage/current can cause severe
injury or death. Short circuits can
cause bodily injury and/or equipment
damage. Do not contact electrical
connections with tools or jewelry while
making adjustments or repairs.
Remove all jewelry before servicing
the equipment.
Hot Parts
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set
until it cools.
Servicing the exhaust system. Hot
parts can cause severe injury or
death. Do not touch hot engine parts.
The engine and exhaust system
components become extremely hot
during operation.
Servicing the engine heater. Hot
parts can cause minor personal
injury or property damage. Install
the heater before connecting it to
power. Operating the heater before
installation can cause burns and
component damage. Disconnect
power to the heater and allow it to cool
before servicing the heater or nearby
parts.
Heavy Equipment
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Do not use lifting eyes.
Lift the generator set using lifting
bars inserted through the lifting holes
on the skid.
8Safety Precautions and InstructionsTP-6843 1/13
Introduction
This manual provides operation and maintenance
instructions for the DC (direct current) variable speed
model 6VSG generator sets equipped with Kohler VSC
generator set controllers.
This generator set is approved for use in stationary
applications in locations served by a public utility,
photovoltaic cells, wind turbines or any combination of
power sources tied to a battery bank. Have the
generator set installed by an authorized
distributor/dealer or service technician. Refer to
Installation Manual, for installation instructions.
Information in this publication represents data
available at the time of print. Kohler Co. reserves the
right to change this publication and the products
represented without notice and without any obligation
or liability whatsoever.
Read this manual and carefully follow all procedures
and safety precautions to ensure proper equipment
operation and to avoid bodily injury. Read and follow
the Safety Precautions and Instructions section at the
beginning of this manual. Keep this manual with the
equipment for future reference.
List of Related Literature
Figure 2 identifies related literature available for the
generator sets covered in this manual. Only trained
and qualified personnel should install or service the
generator set.
Figure 2
Literature Type Part Number
Installation Manual, Model 6VSG
Generator Set TP-6842
The equipment service requirements are very
important to safe and efficient operation. Inspect the
parts often and perform required service at the
prescribed intervals. Obtain service from an
authorized service distributor/dealer to keep
equipment in top condition.
Figure 1
Figure 1 6VSG Generator Set
TP-6843 1/13Introduction9
Nameplate
GM12070
Emission Information
The following illustration shows a typical generator set
nameplate. Copy the model, serial, and specification
numbers from the nameplate into the spaces provided
in the product information section on the inside front
cover of this manual. See the service views in Section
1.7 for the nameplate location.
Figure 3
Figure 3 Typical Nameplate
The Kohler Model CH740 engine used on the 6VSG
generator set is certified to operate using natural gas
or LPG fuel.
The Emission Compliance Period referred to on the
Emission Control or Air Index label indicates the
number of operating hours for which the engine has
been shown to meet CARB or EPA emission
requirements. Figure 4 provides the engine
compliance period (in hours) associated with the
category descriptor, which may be found on the
certification label.
Figure 4
Emission Compliance Period
EPA Category C
250 hours
CARB Moderate 125
hours
Category B
500 hours
Intermediate
250 hours
Category A
1000 hours
Extended 500
hours
Figure 4 Emission Compliance Period
Refer to the certification label for engine displacement.
The exhaust emission control system for the CH740
engines (6VSG) is EM for U.S. EPA, California, and
Europe. See Figure 1-2 for engine certification label
location.
10IntroductionTP-6843 1/13
Service Assistance
For professional advice on generator set power
requirements and conscientious service, please
contact your nearest Kohler distributor or dealer.
• Consult the Yellow Pages under the heading
Generators—Electric.
• Visit the Kohler Power Systems website at
KOHLERPower.com.
• Look at the labels and stickers on your Kohler
product or review the appropriate literature or
documents included with the product.
• Call toll free in the US and Canada 1-800-544-2444.
• Outside the US and Canada, call the nearest
regional office.
Headquarters Europe, Middle East, Africa
(EMEA)
Kohler Power Systems
3 rue de Brennus
93200 Saint Denis
France
Phone: (33) 1 49 178300
Fax:(33) 1 49 178301
Asia Pacific
Power Systems Asia Pacific Regional Office
Singapore, Republic of Singapore
Phone: (65) 6264-6422
Fax:(65) 6264-6455
China
North China Regional Office, Beijing
Phone: (86) 10 6518 7950
(86) 10 6518 7951
(86) 10 6518 7952
Fax:(86) 10 6518 7955
East China Regional Office, Shanghai
Phone: (86) 21 6288 0500
Fax:(86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office
Bangalore, India
Phone: (91) 80 3366208
(91) 80 3366231
Fax:(91) 80 3315972
Japan, Korea
North Asia Regional Office
Tokyo, Japan
Phone: (813) 3440-4515
Fax:(813) 3440-2727
Latin America
Latin America Regional Office
Lakeland, Florida, USA
Phone: (863) 619-7568
Fax:(863) 701-7131
TP-6843 1/13Service Assistance11
Notes
12Service AssistanceTP-6843 1/13
Section 1 Descriptions and Service Views
KPS_048
GM77569
1.1Introduction
The generator set specification sheets provide specific
generator and engine information. Refer to the spec
sheet for data not supplied in this manual. Consult the
generator set service manual, engine operation
manual, and engine service manual for additional
specifications. Obtain copies of the latest spec sheets,
manuals, diagrams, and drawings from your local
distributor/dealer.
1.2Engine
The generator set has a four-cycle, twin cylinder,
air-cooled Kohler engine. The engine operates on
cleanburning natural gas or LPG fuel. Engine
features include:
• Efficient overhead valve design and full pressure
lubrication for maximum power, torque, and
reliability under all operating conditions.
• Precision-formulated cast iron construction of parts
subjected to the most wear and tear.
1.4Alternator
The 6VSG is a direct current (DC) output machine. It
utilizes a 24-pole permanent magnet construction to
create high frequency three-phase alternating current
which is rectified to produce low-ripple DC output.
1.5Controller
The Model 6VSG generator set comes equipped with
the VSC controller. See Figure 1-1. The controller
provides integrated control for the generator set and
the optional programmable interface module (PIM) or
optional communications kit interface board.
The controller’s two-line LCD screen displays status
messages and system settings that are clear and easy
to read in all lighting conditions, including direct
sunlight and low light.
Figure 1-1
• Field-convertible multi-fuel systems that allow fuel
changeover from natural gas to LPG (and vice
versa) while maintaining CARB emission
certification.
• The variable-speed engine runs at 2300 rpm at no
load and 2900 rpm when supplying full load.
1.3Generator Set Enclosure
The generator set is housed in a steel enclosure with
Power Armor powder coat paint. The enclosure has a
hinged, locking door that allows easy access to the
generator set controller when required, but locks
securely to prevent unauthorized access.
To open the door, insert the tool provided with the
enclosure and turn counterclockwise 1/2 turn.
Be sure to close and lock the enclosure, and keep the
tool in a secure location.
Figure 1-1 VSC Controller
1.5.1VSC Controller Features
• Six-button keypad
◦ OFF, AUTO, and RUN pushbuttons
◦ Select and arrow buttons for access to system
configuration and adjustment menus
• LED indicators for OFF, AUTO, and RUN modes
• LED indicators for percentage of load being output
•LCD display
◦ Two lines x 16 characters per line
TP-6843 1/13Section 1 Descriptions and Service Views13
◦ Backlit display with adjustable contrast for
excellent visibility in all lighting conditions
• Scrolling system status display
◦ Generator set status
◦ Voltage and percent load
◦ Engine temperature
◦ Oil pressure
◦ Battery voltage
◦ Engine runtime hours
• Date and time displays
• Smart engine cooldown senses engine temperature
• Digital voltage regulation: ±1.0% RMS no-load to
full-load
• Automatic start with programmed cranking cycle
• Programmable exerciser can be set to start
automatically on any future day and time, and run
every week or every two weeks
• Three exercise modes
• Front-access mini USB connector for SiteTech
connection
• Integral Ethernet connector for Kohler
• Built-in 2.5 amp battery charger
• Remote two-wire start/stop capability
• Diagnostic messages
®
OnCue
™
®
◦ Displays diagnostic messages for the engine,
generator, and programmable interface
module (PIM)
◦ Over 70 diagnostic messages can be displayed
• Maintenance reminders
• System settings
◦ System voltage and percent load
◦ Voltage adjustment
1.6Accessories
The following optional accessories are offered for the
6VSG generator sets.
1.6.1Carburetor Heater
An optional carburetor heater is recommended for
improved cold starting in locations where the ambient
temperature drops below 0°C (32°F). The carburetor
heater prevents condensation and carburetor icing.
The heater requires a continuous source of AC power.
See the generator set Installation manual for more
information.
1.6.2OnCue® Generator Management
System
The Kohler® OnCue® Generator Management System
allows monitoring and control of your 6VSG generator
set from a personal computer located in your home or
at other remote locations. OnCue
configured to send email or text message notifications
in the event of a generator set fault.
Note: Be sure to obtain the correct version of the
OnCue
OnCue
generator sets.
®
kit for the VSC controller.
®
version 3.1 or higher is required for 6VSG
1.6.3Programmable Interface Module
(PIM)
The optional Programmable Interface Module (PIM)
provides two programmable inputs and six
programmable dry contact outputs for connection to
customer-supplied equipment. The outputs are
controlled by the VSC controller, and can also be
controlled remotely using the OnCue
The PIM is mounted in a NEMA 3R aluminum
enclosure, which can be mounted indoors or outdoors.
See the installation instructions provided with the PIM.
1.6.4Communications Kit
®
can also be
®
program.
◦ Measurement system, English or metric
• Programmable Interface Module (PIM) status
displays
◦ Input status (active/inactive)
◦ Output status (active/inactive)
14Section 1 Descriptions and Service ViewsTP-6843 1/13
The optional communications kit includes the following
factory-installed items:
• Interface board with factory-set inputs and outputs
and customer connection terminal blocks
11. Engine starting battery location (battery not included)
12. Lifting hole
13. Controller
14. Engine certification label
15. Load circuit breaker
16. Oil dipstick
17. Exhaust outlet
18. Fuel inlet
19. Electrical inlet
20. Battery cables (included)
21. Nameplate
1
2
3
4
5
6
7
8
9
10
11
12
16
13
14
15
17
18
19
20
21
Figure 1-2
Figure 1-2 Service View (see Figure 1-3 for optional communications kit components)
TP-6843 1/13Section 1 Descriptions and Service Views15
Figure 1-3
ComKitB
GM85956C
1. Interface board (factory-wired to terminal blocks)
2. Intrusion alarm switch
3. Interface board input and output connection terminal blocks
4. Fuel pressure switch
1
2
3
4
Figure 1-3 Optional Communications Kit Components
16Section 1 Descriptions and Service ViewsTP-6843 1/13
Section 2 Generator Set Operation
KPS_105
KPS_106
2.1Theory of Operation
The generator set utilizes a permanent-magnet
alternator to produce 3-phase AC voltage. This
voltage is rectified using a full-wave 3-phase rectifier
(single block rectifier for 36V and 48V, three individual
rectifier blocks for 24V) to produce low-ripple DC
output. See Figure 2-1 and Figure 2-2.
Figure 2-1
The VSC measures the average DC voltage on the
output and lists this on the auto-scrolling display, in the
Overview menu and in the Generator metering menu.
Figure 2-1 Basic VSG Power Connections
Figure 2-2
Figure 2-2 Output Waveform, with Rectified Signal
The voltage is regulated to maintain a constant output
voltage, which is equal to the System Voltage setting.
When the load on the 6VSG generator increases, the
generator controller increases the engine speed. The
6VSG series is designed to produce rated voltage at
2300 rpm with no load and at 2900 rpm when
supplying full load. The output current and power
increase with the engine speed. The engine speed is
limited to a maximum of 2900 rpm. See
Section 3.14.1 for more information.
2.2Prestart Checklist
To ensure continued satisfactory operation, perform
the following checks or inspections before or at each
startup, as designated, and at the intervals specified in
the service schedule. In addition, some checks
require verification after the unit starts.
Air Cleaner. Check for a clean and installed air
cleaner element to prevent unfiltered air from entering
the engine.
Air Inlets. Check for clean and unobstructed air inlets.
Battery. Check for tight battery connections. Consult
the battery manufacturer’s instructions regarding
battery care and maintenance.
Enclosure. Check that all enclosure panels and
internal baffling are in place.
TP-6843 1/13Section 2 Generator Set Operation17
Exhaust System. Check for exhaust leaks and
blockages. Check the muffler condition.
• Inspect the exhaust system components for cracks,
leaks, and corrosion. Check for tight exhaust
system connections.
• Check for corroded or broken metal parts and
replace them as needed.
• Check that the exhaust outlet is unobstructed.
Oil Level. Check the oil level before starting the
generator set and at the intervals given in Section 4,
Scheduled Maintenance. Maintain the oil level at or
near, not over, the full mark on the dipstick.
Operating Area. Check for obstructions that could
block the flow of cooling air. Keep the air intake area
clean. Do not leave rags, tools, or debris on or near
the generator set.
2.3Exercising the Generator Set
2.4.3Engine Start Crank Cycle
The controller attempts to start the generator set three
times (three crank cycles, 15 seconds crank and
15 seconds off). If the generator set does not start in
three attempts, the system shuts down on an
overcrank fault. See Section 2.6.
Cranking 1, 2, and 3 are displayed during the crank
cycle. Pressing the OFF button during the crank cycle
stops the cranking. No other buttons are
acknowledged during the crank cycle.
2.4.4Engine Cooldown
The engine cooldown time delay allows the engine to
run after the loads have been removed.
The engine cooldown time delay is set to 5 minutes.
The engine stops before the cooldown time delay
expires if the temperature drops below the
cooled-down temperature level, or if the temperature
rises above the high limit during the cooldown cycle.
Operate the generator set without load once each
week or every 2 weeks for 20 minutes. See Section
2.5, Exercise. For instructions to set the exerciser, see
Section 3.6.
2.4Generator Set Operation
2.4.1Local Starting and Stopping
Start: Press the RUN button to immediately start the
generator set.
Stop: Press the OFF button. The engine stops.
Run the generator set with no load for at least
2 minutes to ensure adequate engine cooldown.
2.4.2Remote Starting and Stopping
The generator set must be in automatic mode for
remote operation. Press the AUTO button on the VSC
controller.
A remote switch connected to terminals 3 and 4 can be
used to start and stop the generator set. Close the
switch to start and run the generator set. Open the
switch to stop the generator set.
2.4.5Automatic Operation
The 6VSG monitors the voltage of a storage battery
bank connected to (+) and (–) of the output block to
determine charge condition of the storage battery (see
Figure 2-3).
• If the storage battery voltage falls below the
minimum voltage for more than 3 minutes, or if a
remote start command is received, the generator
set starts. A remote start command can be
activated by closing the remote start contacts
across 3 and 4 or by a start exercise command.
• When the generator set load falls below the
minimum % load for more than 3 minutes, or a
remote stop command is received, the generator set
stops. A remote stop command can be caused by
opening the remote start contacts across 3 and 4 or
by the exercise time ending.
The minimum voltage, minimum load, and time delays
are adjustable using a personal computer and Kohler
SiteTech™ software. Contact your Kohler distributor.
®
Run the generator set with no load for at least
2 minutes to ensure adequate engine cooldown.
18Section 2 Generator Set OperationTP-6843 1/13
Figure 2-3
1. Positive (+)
2. Negative (–)
c. The load limit is returned to 5% for 6 minutes
2
1
to allow the generator to cool down before
stopping.
3. Loaded Full Speed Exercise. The generator
operates normally. Voltage is regulated to Voltage
Regulator Average Voltage Adjustment, and load
is regulated to Genset Maximum Percent
Capacity. The generator stops after 20 minutes,
regardless of the load on the generator.
2.6Faults
The VSC controller displays fault messages for
generator set warnings and shutdowns. Selected fault
messages are shown in Figure 2-5.
KPS_043B
Figure 2-3 Output Block
2.5Exercise
The VSC controllers can be set to automatically run
the generator set at the same time and day each
week. Exercising the generator set weekly or every
two weeks is required to keep the engine and
alternator in good operating condition.
When power is applied to the VSC controller (that is,
when the battery is connected), you will be prompted
to set the date and time, and then to set the exerciser.
See Section 3.1, VSC Generator Set Controller, for
more information
An exercise can be started at any time using Kohler
OnCue®, or can start automatically according to the
exercise schedule programmed on the VSC controller.
Three exercise modes are available. During some
exercise modes the engine speed increases and
decreases. This is normal.
2.6.1Warnings
The controller displays a fault message but the
generator set does not shut down on a warning. The
controller resets automatically after a warning
condition is corrected.
2.6.2Shutdowns
Under a fault shutdown condition, the generator set
shuts down automatically and the controller displays a
fault message. The OFF LED flashes. In some cases,
the engine cooldown cycle runs before the engine
shuts down. See Figure 2-5.
Shutdown switches (such as the low oil pressure
switch or high engine temperature switch) on the
generator set will automatically reset when the
problem is corrected. However, the fault condition at
the controller does not clear until the controller is reset.
®
The generator set cannot be restarted until the fault
condition is corrected and the controller is reset. See
Section 2.6.3 for instructions to reset the controller
after a fault shutdown.
1. Unloaded Full Speed Exercise. The generator
2. Unloaded Cycle Exercise. The generator set
TP-6843 1/13Section 2 Generator Set Operation19
regulates the output load below 5% of capacity.
The generator will stop after 20 minutes.
engine speed varies during the 20-minute
exercise according to the following cycle:
a. The generator set regulates the output load
below 5% of capacity for 11 minutes to warm
up.
b. The output regulation is moved to the Genset
Maximum Percent Capacity for 3 minutes to
test ability to output power.
2.6.3Resetting the Controller After a
Overview ---->
1.2 h
Fault Message
tp6809
Confirm Clear
Fault: NO
Confirm Clear
Fault: YES
Fault Message
Press UP
arrow button.
Fault Shutdown
2. Press Select again. The active fault message is
displayed.
Always identify and correct the cause of a fault
shutdown before resetting the controller. Check the
fault message displayed on the controller and refer to
Figure 2-5 to identify and correct the fault condition
before proceeding. Contact an authorized
distributor/dealer for service, if necessary.
Press the OFF button to reset the controller, or follow
the procedure below. See Figure 2-4.
1. While the fault message is displayed, press the
Select button to go to the Overview menu.
Figure 2-4
3. Press Select. Confirm Clear Fault: NO is
displayed.
4. Press the UP arrow button. Confirm Clear Fault:
YES is displayed.
5. Press the Select button to enter YES and clear
the fault.
6. Press the Select button to return to the overview
menu. The controller changes to OFF mode.
7. Press AUTO to put the generator set into
automatic mode.
Figure 2-5
Figure 2-4 Clearing a Fault on the VSC Controller
Warning (W) or
Fault Message
Accy PwrOver
Warning
Aux Input SD * Auxiliary input. An optional customer-connected
Batt Chg Flt W Battery charger fault. Input to PIM from an
Battery Voltage
CrLow
Battery Voltage
High
Battery Voltage
Low
20Section 2 Generator Set OperationTP-6843 1/13
Shutdown (SD) Condition Check
W Accessory Power Overload. Too many devices
WEngine starting battery voltage is critically low,
W Engine starting battery voltage rises above
W Engine starting battery voltage falls below
on the accessory power port or an over current
fault (short circuit) on the accessory controller
power output. (Feeds RBUS devices - PIM)
input is closed. (Digital input from optional PIM.)
external battery charger (not the built-in battery
charger).
less than 10.5 VDC.
16 VDC for more than 10 seconds. Inhibited
during the engine crank cycle.
Clears when the battery voltage returns to an
acceptable level.
12.5 VDC for more than 90 seconds when the
engine is not running.
Not operative during the engine crank cycle.
Clears when the battery voltage returns to an
acceptable level.
Contact an authorized
distributor/dealer for service.
Check customer-supplied equipment.
Check external battery charger.
Check the battery rating and
condition.
Check the battery charger operation.
Charge or replace the battery.
Check the battery rating and
condition.
Check the battery charger operation.
Check the battery rating and
condition.
Check the battery charger operation.
Charge or replace the battery.
Warning (W) or
Fault Message
Enclosure
Intrusion Alarm
Shutdown (SD) Condition Check
WThe enclosure door is open. (Optional
communications kit required.)
Check for evidence of unauthorized
access to the generator set. Close
and lock the enclosure door.
Engine Oil
Pressure Low
SD * The LOP switch indicates low oil pressure for
more than 5 seconds. Function becomes active
30 seconds after crank disconnect (30 second
inhibit). Note: The low oil pressure shutdown
does not protect against low oil level. Check the
Check for leaks in the lubrication
system.
Check the oil level and add oil if the
level is low.
engine oil level regularly as recommended in
Section 4.
Fuel Pressure
Low
WThe fuel pressure switch measures low fuel
pressure (below 4.5 inches water column).
Check fuel supply and fuel lines.
(Optional communications kit required.)
Engine Speed
High
Exer Not Sch W Exercise not scheduled. No exercise is
Generator
VoltageL1-L2
High
Lo Crank Vlt W Low cranking voltage. Battery voltage falls below
SD * Engine speed exceeds 115% of the normal
running speed for more than 0.3 seconds.
scheduled on the controller.
SD * Generator voltage high. Output voltage exceeds
120% of the system nominal voltage for more
than 2 seconds.
Contact an authorized
distributor/dealer for service.
See Section 3.6 for instructions to set
the exerciser.
Contact an authorized
distributor/dealer for service.
Charge or replace the battery.
8 VDC for more than 6 seconds while the starter
is engaged.
Locked Rotor SD No engine rotation is sensed during cranking.
Shuts down 3 seconds after the fault is detected.
Check the battery.
Check for loose connections.
Contact an authorized
distributor/dealer for service.
MainPwrOverL
Shutdown
Not in Auto W The generator set is not in Automatic (standby)
SD Main power overload. An over current fault on the
controller output (short circuit).
mode. Remote start and stop commands from a
transfer switch or remote switch will be ignored.
Contact an authorized
distributor/dealer for service.
Press AUTO to place the generator
set in Automatic mode, when
appropriate.
Over Crank SD Three unsuccessful starting attempts. Check the fuel supply, spark plug, and
battery.
Check for loose connections.
Contact an authorized
distributor/dealer for service.
Reserve Oil
Empty
WThe oil makeup kit reservoir bottle is empty.
(Optional communications kit and oil makeup kit
Add oil to the oil makeup kit reservoir.
required.)
Speed Sensor
Fault
SD Engine speed sensing has failed or engine
stalled.
Contact an authorized
distributor/dealer for service.
* Engine cooldown runs before shutting down.
Figure 2-5 Controller Fault Messages
TP-6843 1/13Section 2 Generator Set Operation21
Notes
22Section 2 Generator Set OperationTP-6843 1/13
Section 3 VSC Controller Operation
1
2
KPS_049
GM77569
1. User interface (see Figure 3-2)
2. Service access (see Section 5.4)
1
10
3
2
5
11
4
6789
KPS_050
GM81498
1. 2-line LCD display
2. Up button
3. Select button
4. Down button
5. RUN button and LED
6. 100% load LED
7. 75% load LED
8. 50% load LED
9. 25% load LED
10. OFF button and LED
11. AUTO button and LED
3.1VSC Generator Set Controller
All 6VSG generator sets are equipped with the VSC
generator set controller.
The VSC controls generator set and the optional
Programmable Interface Module (PIM) or
Communications Kit.
The VSC controller features include:
• Two-line x 16 character backlit digital display with
adjustable contrast
• OFF, AUTO, and RUN generator set master control
buttons
• Generator set status indicating LEDs (OFF, AUTO,
RUN)
• Up, Down, and Select buttons for navigation
through menus and adjustments
• Power system indicator LEDs to show power output
of the generator
3.2Control and Indicators
Figure 3-1 illustrates the VSC controller. See
Figure 3-2 for details of the controller’s user interface.
Figure 3-1
Figure 3-1 VSC Controls and Indicators
Figure 3-2
TP-6843 1/13Section 3 VSC Controller Operation23
Figure 3-2 VSC User Interface
3.2.1Controller Keypad
3.2.2LED Indicators
The RUN, OFF, and AUTO buttons control the
generator set as described in Figure 3-3.
Use the Select, Up arrow, and Down arrow buttons to
navigate through the menus and change settings, if
necessary. See Section 2.4 for operation instructions.
LEDs above the RUN, OFF, and AUTO buttons
indicate the mode of operation as shown in Figure 3-4.
Load indication LEDs indicate the load on the
generator set. A steadily lighted LED indicates that
the load on the generator set is greater than or equal
to the level label for that LED. The next LED flashes
and stays on for a longer time as the load increases.
Figure 3-3
ButtonButton Function
RUN Starts the generator set. The engine start time delay is ignored.
OFF Stops the generator set. The cooldown time delay is ignored.
During the engine crank cycle, pressing OFF will stop the crank cycle.
Press OFF to clear faults and reset the controller.
AUTO Places the generator set in Automatic (standby) mode.
Down arrow Use to navigate through menus and change settings. This manual contains instructions
Select
Up arrow
to navigate the controller menus and adjust settings on the VSC controller.
Figure 3-3 VSC Controller Pushbutton Operation
Figure 3-4
LEDLED Operation
RUN Lights when the generator set has been started locally by pressing the RUN button.
Remote start and stop commands are ignored.
OFF Lights for 2 seconds, then flashes every 2 seconds when the generator set and controller
AUTO Lights when the generator is in automatic (standby) mode. Generator set will respond to
25% loadLED flashes and stays on longer as load increases from 1% to 25%.
50% loadLED flashes and stays on longer as load increases from 26% to 50%.
75% loadLED flashes and stays on longer as load increases from 51% to 75%.
100% loadLED flashes and stays on longer as load increases from 76% to 100%.
are off. Remote start/stop commands have no effect. The exercise cycle will not run.
In Auto mode, OFF LED flashes quickly to indicate a fault shutdown. Attention required.
Identify and correct the fault condition before resetting the controller.
engine start and stop commands from the controller (for example, exercise start and stop
commands) or an ATS. Time delays operate as described in Section 2.4.
Figure 3-4 VSC Controller LED Operation
24Section 3 VSC Controller OperationTP-6843 1/13
3.2.3LCD Display
Genset Status
Running
Voltage: 54V
Load: 73%
Engine: 125F
Oil Pressure: Okay
Battery
13.3V
Engine Runtime:
100.6 h
Date: 02DEC2011
Time: HR:MNpm
Active Alert
Sample data shown.
tp6804
Battery
13.3V
Engine Runtime:
100.6 h
Date: 02DEC2011
Time: HR:MNpm
Next Maintenance:
150 h or Mar2012
Sample data shown.
Genset Status
Standby
Active Alert
Next Exercise:
09:00p 09Dec2011
The controller is equipped with a two-line x
16-character backlit digital display with adjustable
contrast. When the generator is running, the controller
automatically scrolls through the displays shown in
Figure 3-5. The VSC controller measures and
displays the average DC output voltage on the
auto-scrolling display. When the system is in standby
mode and the controller is in AUTO, the screens
shown in Figure 3-6 are displayed.
When a fault or warning condition exists, the controller
will show the corresponding message. See Section
2.6 for more information about faults.
Controller menus display power system information,
including status information for the engine, generator,
and optional RBUS accessories, exercise settings,
and event history. Some menus allow changes to the
controller settings. See Sections 3.7 through 3.18 for
menu diagrams.
Figure 3-5
The display contrast is adjustable. Navigate to the
Genset System menu and step down to the Contrast
screen. Press the Select button, and then use the up
and down arrow buttons to adjust the contrast. See
Section 3.5, Changing Settings, and Section 3.14,
Genset System Menu.
The display backlight turns off after about a minute of
no activity. The backlight turns on when a button is
pressed or when the generator set starts.
Figure 3-6
Figure 3-5 Autopaging Displays, Generator Running
Figure 3-6 Autopaging Displays, Automatic Mode
TP-6843 1/13Section 3 VSC Controller Operation25
3.3Controller Power
3.5.1Procedure to Change Settings
The VSC controller is powered by the generator set
engine starting battery and the built-in battery charger.
Note: To disconnect controller power, disconnect the
AC power to the generator set starting battery.
If controller power is disconnected and reconnected,
you will be prompted to set the time, date, and
exerciser. The first setting will flash. Press the Up and
Down arrow buttons to change the setting. Press
Select to save the setting and move on to the next.
Repeat until all settings are saved and the controller
returns to the main menu. See Section 3.5 for more
detailed instructions to change settings on the VSC.
See Section 3.6 for more detailed instructions to set
the exerciser or change the exercise settings.
3.4Battery Charging
The controller includes a built-in battery charger to
maintain the engine starting battery. The VSC
controller monitors the battery voltage and provides a
constant 13.8 ±2% VDC voltage and maximum
2.5 amps to charge the battery.
The installer must connect 120 VAC/60Hz power on a
breaker-protected circuit for the built-in battery
charger.
3.5Changing Settings
Some settings can be changed from the controller
keypad. The controller settings and generator set
output are factory-set and should not require field
adjustment under normal circumstances. Check and
adjust the settings and/or output when:
• The controller has been replaced.
1. Press the Select button to enter the main menu.
2. Press the down arrow button until the desired
menu is displayed.
3. Press the Select button to enter the genset
system displays. See Figure 3-10.
4. Press the down arrow button to step through the
generator set system settings.
5. To change any of the genset system settings,
press the Select button. The selected setting
flashes.
6. Press the up or down arrow buttons to increase
or decrease the setting.
7. When the desired setting is shown, press Select.
The value stops flashing. If there are additional
adjustable settings on the screen, the next setting
flashes. For example, in the date menu, the day,
month, and year can be adjusted. The settings
are saved on completion of step 7.
8. Repeat steps 6 and 7 for each setting on the
screen.
9. Press the down arrow to step to the next screen.
10. To exit, press the down arrow button until Return
is displayed. Press the Select button to exit the
menu.
11. Press the AUTO or OFF button to exit the main
menu.
Note: If no buttons are pushed, the controller
exits the menus and returns to the
generator set status display after
5 minutes.
• The voltage requires adjustment for a particular
application.
• Troubleshooting generator set problems.
Have controller setup and adjustment performed only
by an authorized Kohler distributor/dealer or
authorized representative.
The following procedure explains how to change
settings. See Figure 3-7 for an example using the
Date and Time settings.
Note: Use caution when navigating the controller
menus. In some menus, pressing the Select
button can enable editing of the controller
settings. Changing the settings to incorrect
values can adversely affect generator set
operation or render the unit inoperable.
26Section 3 VSC Controller OperationTP-6843 1/13
Figure 3-7
1. Press the Select button to enter the main menu.
2. Press the down arrow button until the desired
menu is displayed. See Figure 3-9. Date and Time
are used for this example.
3. Press the Select button to enter the Date and Time
menu.
4. To change the date and time settings, press the
Select button again. The year will flash.
5. Press the up or down arrow buttons to change the
year.
6. When the correct year is shown, press the Select
button. The year is saved and the next setting
(month) flashes.
7. Repeat steps 5 and 6, using the arrow and select
buttons to set the month and the date.
Press:
Changing Date/Time
Press:Display:
Overview ---->
1.2 h
Display:
Press:Display:
Press:Display:
Date---->
and Time
Date:
05Dec2011
8. When the correct date is shown, press the Select
button. The saved date is shown.
9. Press the down arrow button to step to the next
menu.
10. Repeat steps 5 and 6, using the arrow and select
buttons to set and save the time.
Note: To change from am to pm, press the up arrow
key to increase the hour until the correct hour
and pm is displayed.
11. In the time format menu, press Select and then
press the up or down arrow button to change the
format, 12 hr. or 24 hr. Press Select to save the
displayed format.
12. Press the down arrow button.Return is
displayed.
13. Press Select to return to the Date and Time
menu.
14. Press the Up or Down arrow buttons to step to a
different menu.
15. Press Auto to signal the controller to exit the
menus and return to the generator set status
display.
Note: If no buttons are pressed, the controller returns
to the status display after 5 minutes.
Press:
Display:
OR
Press:Display:
Press:Display:
<---- Return
Press:Display:
Time:
01:49pm
Date---->
and Time
AUTO
Press:
Display:
Genset State
Standby
Date:
05Dec2011
Date:
05Dec2012
Press:Display:
Date:
05Dec2012
Press:Display:
Date:
03Jan2012
Figure 3-7 Changing Settings
TP-6843 1/13Section 3 VSC Controller Operation27
3.6Setting the Exerciser
Set the exerciser to automatically run the generator set
for 20 minutes every week or every two weeks.
3.6.1Setting the Exerciser at Controller
Power-up
When battery power is connected to the controller, you
will be prompted to set the date and time, and then to
set the exerciser.
The first setting will flash. Press the Up and Down
arrow buttons to change the setting. Press Select to
save the setting and move on to the next. See Section
3.5 for more detailed instructions to change settings on
the VSC.
If the battery is disconnected and reconnected during
generator set maintenance or service, the time, date,
and exercise settings will need to be re-entered.
3.6.2Changing the Exercise Settings
This section explains how to change the exercise
settings after the initial setup.
10. Repeat steps 5 through 9 to change the next item
on the line until the desired settings are
displayed.
11. Press Select to save after all settings have been
selected. Settings will stop flashing.
12. Set the exercise frequency (weekly or every two
weeks). Weekly exercises are recommended.
13. Press the down arrow button to step to the Return
menu. Press the Select button to return to the
main menu.
After a scheduled exercise run, the next exercise time
and date will be updated automatically based on the
Exercise Frequency setting.
Exerciser Reset
To reset the exerciser to run at a different day and/or
time or to change the exercise mode, follow the
procedure in Section 3.6.2 to change the exerciser
settings.
Follow the procedure below and see the flowchart in
Figure 3-8 to set the exercise time and date, mode,
and frequency.
Procedure to Set the Exerciser
1. Press the AUTO button on the controller.
2. Press the Select button to go to the main menu.
See Figure 3-9.
3. Press the down arrow button to step to the
Genset System menu.
4. Press the Select button to enter the Genset
system menu. See Figure 3-11.
5. Use the down arrow button to step to the Next
Exercise menu. If the exerciser is not set, No
Exercise Scheduled will be displayed.
6. Press and HOLD the Select button to enable
editing.
7. Press the Select button. The setting flashes to
show that it can be changed. For example, HR
flashes to show that the hour can be changed.
8. Press the Up or Down arrow buttons to change
the setting.
9. Press the Select button to save the setting and
move to the next. For example, save HR setting
and move to MN.
28Section 3 VSC Controller OperationTP-6843 1/13
Figure 3-8
Genset---->
System
System Voltage:
54.0V
Auto Start Volt: (V)
Auto Stop Load: (%)
Load Limit: (%)
Fuel Type:
Natual Gas
Next Exercise *
HR:MN PM MM/DD/YY
HOLD:
Next Exercise
HR:MN PM MM/DD/YY
Exercise Mode:
Loaded
Exercise Freq:
Weekly
Language:
English
Contrast:
50
<---- Return
HOLD:
Exercise Mode:
Loaded Full Sp
Unloaded Cycle
Loaded Full Sp
HOLD:
Exercise Freq:
Weekly/Bi-Weekly
tp6804
* If the exerciser has not been set, No Exercise Sch will be displayed.
Figure 3-8 Procedure to Set the Exerciser on the VSC Controller
TP-6843 1/13Section 3 VSC Controller Operation29
3.7VSC Controller Menus
Overview ---->
1.2 h
Engine---->
Metering
Generator---->
Metering
Genset---->
Information
Genset---->
Run Time
Date---->
and Time
Genset---->
System
Event Log---->
PIM---->
Status
Network -- -->
Information
Status
Displays
Press the Up and Down arrow buttons
to move between menus.
Press OFF or AUTO to exit the menus.
Controller menus display power system information,
including status information for the engine, generator,
and optional RBUS accessories, exercise settings,
and event history. Some menus allow changes to the
controller settings.
Diagrams in the following sections show how to
navigate through the menus.
Note: Use caution when navigating the controller
menus. In some menus, pressing the Select
button can enable editing of the controller
settings. Changing the settings to incorrect
values can adversely affect generator set
operation or render the unit inoperable.
Figure 3-9
If a setting on the controller display is flashing, edit
mode has been enabled. Press the OFF or AUTO
button to exit the edit mode.
3.8Main Menu
Press the Select button once to bring up the main
menu. Overview is displayed. See Figure 3-9. Press
the down arrow button to step to the next menu,
Engine Metering. Use the UP and DOWN arrow
buttons to step up and down through the menus
shown in Figure 3-9.
The controller will exit the main menu after 5 minutes if
no buttons are pressed. To exit the main menu
immediately, press the controller’s OFF or AUTO
button.
Figure 3-9 VSC Main Menu
30Section 3 VSC Controller OperationTP-6843 1/13
3.9Overview Menu
Overview ---->
1.2 h
Active Alert
(if any)
Genset Status
Standby
Generator: 54V
% Load 73%
Engine: 125F
Oil Pressure: OK
Battery:
13.3V
Engine Runtime:
100.6 h
Date: 02DEC2011
Time: HR:MNpm
Next Exercise:
09:00p 09Dec2011
Next Maintenance:
150 h or Mar2012
SW Version:
4.06
<---- Return
tp6810
Eng Speed:
2300 R/min
Battery:
13.3 V
<---- Return
Engine ---->
Metering
Oil Pressure:
Switch: OK
Oil Temperature:
125 F
Figure 3-10
3.10 Engine Metering Menu
The engine metering menu displays engine status
information as shown in Figure 3-11. This menu
displays status information only. No settings can be
changed from this menu.
Figure 3-11
Figure 3-11 Engine Metering Menu
Figure 3-10 Overview Menu
TP-6843 1/13Section 3 VSC Controller Operation31
3.11 Generator Metering Menu
DANGER
!
Generator ---->
Metering
Reset
Calibration
<---- Return
Reset
Calib? No
Volts:
54.0V
Reset
Calib? Yes
Load:
73%
Reset
Calibration
The generator metering menu displays the generator
voltage and % load. See Figure 3-12.
Figure 3-12
3.11.1 Calibration
Hazardous voltage.
Will cause severe injury or death.
This equipment must be installed
and serviced by qualified electrical
personnel.
The calibration mode can be entered from the
Generator Metering menu. Contact a
Kohler-authorized distributor/dealer for service.
The Reset Calibration menu allows you to set the
readings back to the default settings after calibration, if
necessary. See Figure 3-12.
Figure 3-12 Generator Metering Menu
32Section 3 VSC Controller OperationTP-6843 1/13
3.12 Generator Set Information
tp6804
Genset M/N:
6VSG-48V
Genset S/N:
Controller S/N:
<---- Return
Genset ---->
Information
########
########
tp68
Eng Runtime:
100.6 h
Eng Starts:
127
<---- Return
Genset ---->
Run Time
Next Maintenance:
150 h or Mar2012
Menu
The generator set model number and serial numbers
are displayed (see Figure 3-13). No changes are
allowed from this menu.
Model and serial numbers are factory-set and should
not require changes in the field, except in the event
that the controller is being replaced. A personal
computer running Kohler
required to enter the generator set model number and
serial numbers on a replacement controller. Contact
an authorized Kohler distributor/dealer for service.
Figure 3-13
®
SiteTech™ software is
3.13 Genset Run Time Menu
The data shown in Figure 3-14 are displayed. No
changes are allowed from this menu.
The Next Maintenance menu shows the number of
hours of generator set operation until maintenance is
required. The estimated date for the next scheduled
maintenance is also displayed. The maintenance
reminder intervals are based on the engine
manufacturer’s recommendation for changing the oil.
See Section 4, Scheduled Maintenance, for
maintenance instructions.
After changing the oil and performing other
recommended maintenance, go to the Overview menu
to reset the maintenance timer. See Section 4.2.5 for
instructions to reset the maintenance timer.
Figure 3-14
Figure 3-13 Generator Set Information Menu
Figure 3-14 Generator Set Run Time Menu
TP-6843 1/13Section 3 VSC Controller Operation33
3.14 Genset System Menu
The genset system menu displays the system
information shown in Figure 3-19. Generator sets are
factory-set and should not require changes to the
system settings in the field.
A Kohler-authorized distributor or dealer can adjust
these settings, if necessary. If the generator set is
reconnected to a different voltage or the system
settings require adjustment for some other reason, see
Section 3.5 for instructions to enable editing and
change the system settings.
Note: Use caution when navigating the controller
menus. In some menus, pressing the Select
button can enable editing of the controller
settings. Changing the settings to incorrect
values can adversely affect generator set
operation or render the unit inoperable.
3.14.1 System Parameters for Battery
Bank Charging
System Voltage: The system voltage is the output
voltage of the generator set. Default values are shown
in Figure 3-15. The system voltage is set to the
required output voltage to properly support the load
and charge the battery. Do not confuse this value with
the voltage designation of the battery stack. For
example, four 12V batteries in series results in a 48V
battery stack, but the output voltage needed to charge
the battery stack is 54V.
Figure 3-15
Nominal Voltage24V36V48V
Default System Voltage, VDC2740.554
Figure 3-15 System Voltage Default Settings
Refer to the battery manufacturer’s documentation for
the recommended charging voltage. If the system
voltage needs to be changed, contact an authorized
Kohler distributor or dealer.
Note: Setting the system voltage to a higher value
than the factory default setting will decrease the
power output of the generator set.
The following system parameters can be viewed in the
Genset System menu on the user interface on the
generator set’s VSC controller.
•System Voltage
• Auto Start Voltage
• Auto Stop Load (%)
• Load Limit
Note: Changing these settings can damage your
generator set and batteries. Always refer to the
information provided by the battery bank
manufacturer for the correct voltage and charge
current limits for your batteries. Contact an
authorized Kohler distributor or dealer for
assistance if the default settings are not
appropriate for the battery bank.
A 6VSG set at the system voltage shown in
Figure 3-15 will have an output of 6 kW. If the system
voltage is set to a higher value, the output current
decreases. The available power output also
decreases below 6 kW due to the limits on the engine
speed. The graphs in Figure 3-17 illustrate the effect
of changing the system voltage.
Auto Start Volt: The 6VSG will automatically start
when the battery bank voltage has reached or fallen
below this value for 180 seconds (3 minutes). Default
settings are shown in Figure 3-16.
Figure 3-16
Nominal Voltage24V36V48V
Default Auto Start Voltage, VDC2537.550
Figure 3-16 Auto Start Voltage
Note: The 3-minute (180-second) time delay can be
changed using a personal computer (laptop)
and Kohler
®
SiteTech™ software. Contact a
Kohler authorized distributor or dealer to adjust
the delay setting, if necessary.
34Section 3 VSC Controller OperationTP-6843 1/13
Figure 3-17
KPS_104
Figure 3-17 Effect of Changing the System Voltage Setting
Auto Stop Load: The auto stop load is set as a
percentage of full load. As the battery bank
approaches the fully charged state, the charge rate
slows, and the load on the generator set decreases.
The 6VSG will automatically stop when the load has
reached or fallen below the Auto Stop Load setting for
180 seconds (3 minutes). The default setting is 40%
load.
Load Limit =
(Recommended charging voltage (VDC) x Maximum charging current (amps)) x 100
Nominal Voltage24V36V48V
System Voltage, VDC2740.554
Maximum Current at 100% Load Limit, Amps222148111
Figure 3-18 Maximum Charge Current at Default Load Limit Setting of 100%
Load Limit (%): This setting limits the current output
to the maximum charge rate specified by the battery
manufacturer or load in the application. The default
setting is 100%, which gives the maximum current
values shown in Figure 3-18. Refer to the battery
manufacturer's recommended maximum charge rate
and contact an authorized Kohler distributor or dealer
if the setting needs to be changed.
6000 watts
Figure 3-18
TP-6843 1/13Section 3 VSC Controller Operation35
tp6804
System Voltage:
54.0V
50V
40%
100%
Genset---->
System
Auto Stop Load:
Load Limit:
Natural Gas
Fuel Type:
Auto Start Volt:
Language:
<---- Return
Next Exercise *
1:00PM 02/12/1011
Exercise Freq:
Weekly
English
Exercise Mode:
Loaded Ful Sp
Contrast:
50
* If the exerciser has not been set,
No Exercise Sch will be displayed.
3.14.2 Setting the Exerciser
Use the Genset System menus to set the generator
set exerciser. See Section 2.5 for instructions to set
the exerciser and for more information about
exercising the generator set.
After a scheduled exercise run, the Next Exercise time
and date will be updated automatically based on the
Exercise Frequency setting.
3.14.3 Adjusting the Display Contrast
To adjust the display contrast, use the down arrow
button to step to the Contrast menu. Press the Select
button, and then use the up and down arrow buttons to
adjust the contrast. Press the Select button to save
the contrast setting.
Figure 3-19
36Section 3 VSC Controller OperationTP-6843 1/13
Figure 3-19 Genset System Menu
3.15 Date and Time Menu
tp6804
Date:
02Dec2011
Time:
12:34pm
Time Format:
12hr
Date and
Time
To change the date and time, press the Select button
See Figure 3-7 for instructions.
<---- Return
tp6810
Networking---->
Information
Networking---->
Status
NS
RBUS---->
Information
RB
<---- Return
Networking---->
Configuration
NC
See Figure 3-22.
See Figure 3-23.
See Figure 3-24.
The date and time will typically be set at controller
powerup. To change the date, time, or time format
(12 hour or 24 hour), use the Date and Time menu.
See Figure 3-20.
3.16 Networking Information Menus
Use the networking menus to view and adjust
communication settings for systems with remote
RBUS devices such as a PIM, and for systems that
use the Kohler
System.
RBUS is a proprietary RS-485 communications
protocol.
The Networking Information menu leads to submenus
for network and RBUS communication settings. See
Figure 3-21.
Figure 3-21
®
OnCue® Generator Management
Figure 3-20
Figure 3-20 Date and Time Menu
Figure 3-21 Networking Information Menu
TP-6843 1/13Section 3 VSC Controller Operation37
3.16.1 Networking Status Submenu
tp68
IP Address:
123.456.789.123
Gateway:
123.456.789.123
<---- Return
Subnet Mask:
123.456.789.123
DHCP:
Enabled
Ethernet Status:
Disconnected
DNS 1:
123.456.789.123
DNS 2:
123.456.789.123
OnCue Server:
123.456.789.123
OnCue Status:
Connected
Networking---->
Status
Networking---->
Information
The Networking Status submenu contains settings for
OnCue
Operation Manual for information about the
appropriate network settings for OnCue
these settings are not typically required.
Figure 3-22
®
. See Figure 3-22. See the OnCue® Software
®
. Changes to
If DHCP is enabled, IP parameters are not displayed.
If DHCP is disabled (i.e., if a static IP address is used),
the IP parameters are displayed.
To enable or disable DHCP and change the IP
settings, go to the Networking Configuration menu.
See Section 3.16.2.
Figure 3-22 Network Status Submenu
38Section 3 VSC Controller OperationTP-6843 1/13
3.16.2 Networking Configuration
tp6804
<---- Return
DHCP:
Enabled
Reset OnCue
Password
Reset OnCue
Password? No
S/N: 1234567
New PW: 12345
Press Select to enter YES
or NO as displayed. New
password is displayed for
approximately 10 seconds.
Networking
Configuration
HOLD
Reset OnCue
Password? Yes
UP arrow for YES,
Down arrow for NO.
Networking---->
Information
Networking---->
Status
Submenu (OnCue® Password)
The networking Configuration menu includes settings
used for communication with the Kohler
Generator Management System. See Figure 3-23.
For most applications, DHCP is enabled and the IP
settings cannot be changed from the controller
keypad. If DHCP is enabled, IP parameters are not
displayed.
If DHCP is disabled (i.e., if a static IP address is
required), then the IP parameters can be modified.
For applications that require static IP addresses, press
and hold the select button to enable editing, disable
DHCP, and then step to the next parameters and enter
the information.
Figure 3-23
®
OnCue
If an error occurs while setting a parameter, an error
message is displayed and then the controller exits the
edit mode. Previous settings are preserved.
®
Password
For the initial OnCue
reset the OnCue
and then enter it into the OnCue
®
setup, you will be required to
®
password on the VSC controller,
®
software. To reset
the password, follow the instructions in Section 3-22.
Note: The password is displayed for only 10 seconds.
Be sure to write down the password and serial
number.
A new password is generated each time the reset
password procedure is performed. If the password is
reset after the OnCue
®
system has been set up, the
connection will be lost. Enter the new password in
OnCue
®
to reconnect.
Figure 3-23 Network Configuration Submenu
TP-6843 1/13Section 3 VSC Controller Operation39
3.16.3 RBUS Information
tp6804
Modules
Connected: 3
Module Timeouts:
1234
Net Cycle Time:
123ms
Module Errors:
1234
< ---- Return
RD
Remote ---->
Devices
See Figure 3-25.
Networking---->
Information
Networking---->
Status
RBUS---->
Information
<---- Return
Networking---->
Configuration
The RBUS Information menu contains settings for
remote modules that communicate with the VSC
controller using RBUS protocol (see Figure 3-24).
This includes the following optional modules:
Programmable Interface Module (PIM)
Figure 3-24
Figure 3-24 VSC Information Submenu
40Section 3 VSC Controller OperationTP-6843 1/13
3.16.4 Remote Devices Submenu
tp6804
Module Status:
Connected
Firmware Ver.:
122
Module ID:
12
S/N: XXXXXXXXX
<<*DeviceType*>>
Return ---->
S/N: XXXXXXXXX
<<*DeviceType*>>
Comm. Errors:
12345
Comm. Timeouts:
12345
(Dis)Connected:
MM/DD/YY 12:12 PM
<---- Return
Connected: Displays the date and time that the
device was connected.
Disconnected: Displays the last date and time of
successful communication.
Remote ---->
Devices
From Figure 3-24:
Check the status of remote devices communicating
through RBUS (see Figure 3-25). Device types can
include:
Programmable Interface Module (PIM)
The serial numbers for the PIM are printed on the
circuit boards inside the enclosures.
Figure 3-25
Figure 3-25 Remote Devices Submenu
TP-6843 1/13Section 3 VSC Controller Operation41
3.17 Programmable Interface
*
* PIM Status displays the interface board status if the optional communications
kit with factory-installed interface board is installed.
PIM
Status:
P I M 1-- -- >
<---- Return
Input 1
In/Active
Output 1:
In/Active
Input 2
In/Active
Output 2:
In/Active
Output 3:
In/Active
Output 4:
In/Active
Output 5:
In/Active
Output 6:
In/Active
<---- Return
Module (PIM) Status Menu
Note: The PIM status menu appears if a
programmable interface module (PIM) or a
communications kit interface board (IB) is
connected.
The PIM status menu displays the status of inputs and
outputs connected to the programmable interface
module (PIM) or communications kit interface board
(IB). See Figure 3-26. This is a status display menu
only. Input and output settings cannot be changed
from the VSC controller’s user interface.
Figure 3-26
A personal computer running Kohler
®
SiteTech
™
software is required to change the input and output
settings for the PIM. Contact an authorized distributor
or dealer for service.
The Kohler
®
OnCue® Management System can be
used to turn the PIM outputs on and off. See the
OnCue
®
Software Operation Manual for instructions.
The input and output settings for the communications
kit interface board are factory set and locked.
Figure 3-26 Programmable Interface Module (PIM) Status Menu
42Section 3 VSC Controller OperationTP-6843 1/13
3.18 Event Log
The event log displays up to 1000 controller faults and
notices, starting with the most recent event. Events
are numbered 1-1000, with 1 being the most recent.
Each event is displayed with the date and time of the
event, the number of the event, a code to indicate
whether the event was a warning (W), shutdown (S),
or informational notice (I), the engine hours at the time
of the event, and the event description. See
Figure 3-27.
3.18.1 Procedure to View Event History
1. Press Select to enter the main menu.
2. Press the down arrow to step down to the event
log.
3. Press Select to display the most recent event.
4. Press the down arrow to step to the next event.
5. Use the up and down arrow buttons to view
events.
6. Press the Select button to exit the event log.
To stop viewing the event history before the last event,
press the select button to return to the main menu.
Figure 3-27
Date MO/DA/YEAR
Event Log ---->
Press UP and Down arrow
buttons to scroll through events
Press Select button at any time to
return to the main menu.
time HR:MN
event number, W/S/I, engine hours
event name
Date MO/DA/YEAR
time HR:MN
event number, W/S/I, engine hours
event name
tp6810
Figure 3-27 Event Log
TP-6843 1/13Section 3 VSC Controller Operation43
Notes
44Section 3 VSC Controller OperationTP-6843 1/13
Section 4 Scheduled Maintenance
WARNING
!
WARNING
!
!
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (–) lead first
when disconnecting the battery.
Reconnect the negative (–) lead last
when reconnecting the battery.
Disabling the generator set. Accidental starting can
cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the
generator set as follows: (1) Press the generator set
OFF/RESET button to shut down the generator set. (2)
Disconnect the power to the battery charger, if equipped. (3)
Remove the battery cables, negative (–) lead first.
Reconnect the negative (–) lead last when reconnecting the
battery. Follow these precautions to prevent the starting of
the generator set by the remote start/stop switch.
Hazardous voltage. Moving parts.
Can cause severe injury or death.
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set
until it cools.
Servicing the exhaust system. Hot parts can cause
severe injury or death. Do not touch hot engine parts. The
engine and exhaust system components become extremely
hot during operation.
4.1Scheduled Maintenance
Refer to the following service schedules and the
runtime hours displayed on the controller display to
schedule routine maintenance. Intervals are shown in
hours of operation and/or time intervals (i.e. weekly,
monthly, quarterly, etc.) Have an authorized
distributor/dealer service the generator set at the
designated intervals in the service schedule for the life
of the generator set. Service units subject to extreme
weather, long operating hours, or dusty or dirty
conditions more frequently.
Contact an authorized distributor/dealer for parts.
Operate the generator set only when
all guards and electrical enclosures
are in place.
TP-6843 1/13Section 4 Scheduled Maintenance45
4.1.1Service Schedule, 6VSG Models
Procedure
System Component or Procedure
Fuel
Flexible lines and connections X R Quarterly
Main tank supply level (if LPG fueled)X Weekly
Fuel piping X Yearly
Lubrication 4.2
Oil level X X 8 hours or before use
Crankcase breather hose X Yearly or 500 hours
Change oil X Yearly or 100 hours ‡
Replace filter X Yearly or 200 hours
Cooling 4.5
Air ducts, louvers X X Yearly
Exhaust Line 4.6
Leakage X X Weekly
Insulation, fire hazards X Yearly
Obstructions or combustible materials near exhaust
outlet
DC Electrical System 4.7
Battery charger operation, charge rate (if equipped) X Monthly
Remove corrosion, clean and dry battery and rack X X Yearly
Clean and tighten battery terminals and inspect boots X X Yearly
Battery electrolyte level and specific gravity * X Yearly
AC Electrical System
Tighten control and power wiring connections X Yearly
Remote control system (if equipped) X Monthly
Visible wear or damage X Quarterly
Wire abrasions where subject to motion X X 6 months
Wire-cable insulation condition X 3 years or 500 hours
Engine and Mounting
Visible wear or damage X Weekly
Air cleaner and precleaner service † 4.4R Yearly or 100 hours
Spark plugs 4.3X Yearly or 300 hours
Replace stepper motor coupling and bushing D 500 hours
Generator
Visible wear or damage X Quarterly
Exercise generator set X Weekly
Brushes and collector ring D D Yearly
Measure and record resistance readings of windings
with insulation tester (Megger
rectifier and load leads disconnected) *
General Condition of Equipment
Evidence of vibration, leakage, excessive noise,
temperature, or deterioration
Interior of sound enclosure X X Quarterly
* Not necessary for maintenance-free batteries.X Action
† Service more frequently under extremely dusty/dirty conditions.D Authorized distributor/dealer only
‡ Yearly or 250 hours if equipped with optional Oil Makeup Kit.R Replace as necessary
Megger® is a registered trademark of Biddle Instruments.
®
, with SCR assembly or
See
Section
Visually
InspectCheck Change Clean Test
X Weekly
D 3 years
X X X Weekly
Frequency
46Section 4 Scheduled MaintenanceTP-6843 1/13
4.2Lubrication System
KPS_026
4.2.3Engine Oil Recommendation
See the service schedules in Section 4.1 for oil change
and oil filter replacement intervals. See the service
views in Section 1.7 for the oil drain, oil dipstick, oil fill,
and oil filter locations.
4.2.1Low Oil Pressure Shutdown
The low oil pressure (LOP) shutdown feature protects
the engine against internal damage if the oil pressure
drops below a minimum pressure because of oil pump
failure or other malfunction.
Note: The LOP shutdown feature does not protect
against damage caused by operating when the
oil level is low; it is not a low oil level shutdown.
Check the oil level regularly, and add oil as
needed.
4.2.2Oil Check
The generator set is shipped with oil. Before operating
the generator set, check the engine oil in the
crankcase. See Figure 4-1.
Maintain the oil level at or near, not over, the full mark
on the dipstick. Add 5W-30 synthetic oil when the oil
level is low.
Use 5W-30 API (American Petroleum Institute)
Service Class SG, SH, or SJ synthetic oil. Synthetic oil
oxidizes and thickens less than other oils and leaves
the engine intake valves and pistons cleaner.
4.2.4Oil Change Procedure
Note: Dispose of all waste materials (engine oil, fuel,
filter, etc.) in an environmentally safe manner.
Drain the oil while it is still warm.
1. Drain the oil.
a. Press the OFF button on the generator set
controller.
b. Disconnect the AC power to the generator set.
c. Disconnect the generator set engine starting
battery, negative (–) lead first.
d. Open the housing service door and remove
roof panel.
e. Clean the area around the dipstick and oil fill
cap.
f.Remove the screw in plug on drain fitting in
skid rail.
Check the oil level before each use. For extended
operation, check the oil level every 8 hours. Do not
check the oil level when the generator set is running.
Shut down the generator set and wait several minutes
before checking the oil.
Figure 4-1
Figure 4-1 Oil Check (typical)
g. Open the oil drain valve on the engine.
h. Remove the dipstick and oil fill cap. Allow time
for the engine oil to drain completely.
i.Close the oil drain valve. Replace the cap in
skid rail.
j.Replace the dipstick.
2. Replace the oil filter.
a. Clean the area around the oil filter. Remove
the oil filter by rotating it counterclockwise with
an oil filter wrench.
b. Clean the gasket sealing surface of the oil filter
adapter.
c. Apply a light coat of clean oil to the rubber seal
of the new oil filter.
d. Install the new oil filter following the
instructions provided with the filter.
TP-6843 1/13Section 4 Scheduled Maintenance47
3. Fill with oil.
KPS_027
KPS_028
4.3Spark Plugs
a. Fill the engine to the F mark on the dipstick.
The engine oil capacity is shown in Figure 4-2.
See Section 4.2.3 Engine Oil
Recommendation, for oil selection.
Figure 4-2
Generator Set Model Oil Capacity, L (qt.)
6VSG1.9 (2.0)
Figure 4-2 Engine Oil Capacity
b. Reinstall the dipstick and the oil fill cap.
c. Reconnect the generator set engine starting
battery, negative (–) lead last.
d. Reconnect the AC power to the generator set.
e. Press the RUN button on the generator set
controller. The generator set will start.
f.Run the generator set for a minute to allow the
oil pressure to reach operating range.
g. Stop the generator set, wait 1 minute, and then
recheck the oil level. Add oil to bring the level
up to the F mark on the dipstick.
4. Check for leaks.
Reset the spark plug gap or replace the plugs with new
plugs as necessary.
1. Clean the area around the base of the spark plug
to keep dirt and debris out of the engine.
2. Remove the spark plug and check its condition.
Replace the spark plug if it is worn or if its reuse
is questionable.
3. Check the spark plug gap using a wire feeler
gauge. See Figure 4-3 for the recommended
spark plug gap. Adjust the gap by carefully
bending the ground electrode. See Figure 4-4
and Figure 4-5.
4. Reinstall the spark plug into the cylinder head.
Torque the spark plug to 24.4-29.8 Nm
(18-22 ft. lb.)
Figure 4-3
Generator Set Model Spark Plug Gap
6VSG0.76 mm (0.030 in.)
Figure 4-3 Spark Plug Gap
Figure 4-4
a. Check for oil leaks.
b. Fix leaks and recheck the oil level.
c. Reinstall the roof panel and close service
door.
5. Reset the maintenance timer on the controller.
4.2.5Resetting the Maintenance Timer
1. In the Overview menu, step down to the Next
Maintenance screen.
2. Press the Select button.
3. Press the Up arrow button so that Reset Maint
Timer? Yes is displayed.
4. Press the Select button. After about two minutes,
the new maintenance interval and date are
displayed.
Figure 4-4 Checking the Spark Plug Gap
Figure 4-5
Figure 4-5 Adjusting the Spark Plug Gap
48Section 4 Scheduled MaintenanceTP-6843 1/13
4.4Air Cleaner Service
1
2
3
4
5
6
7
KPS_029
1. Cover knob
2. Air cleaner cover
3. Element cover nut
4. Element cover
5. Foam precleaner
6. Air cleaner element
7. Air cleaner base
Precleaner Service
The engine has a replaceable high-density paper air
cleaner element with an oiled foam precleaner. See
Figure 4-6.
Figure 4-6
Use the following procedure to wash and oil the
precleaner as indicated in the service schedule. Wash
and oil the precleaner more often under extremely
dusty or dirty conditions.
1. Press the OFF button on the generator set
controller.
2. Disconnect the AC power to the generator set.
3. Disconnect the engine starting battery, negative
(–) lead first.
4. Loosen the cover knob and remove the air
cleaner cover. Remove the precleaner from the
paper element. Wash the precleaner in warm
water with detergent. Rinse the precleaner
thoroughly until all traces of detergent are
eliminated. Squeeze out excess water (do not
wring). Allow the precleaner to air dry.
5. Saturate the precleaner with new engine oil.
Squeeze out all of the excess oil.
6. Reinstall the precleaner over the paper element.
7. Reinstall the air cleaner cover. Secure the cover
with the cover knob.
8. Reconnect the power to the battery charger.
9. Reconnect the generator set engine starting
battery, negative (–) lead last.
Paper Element Service
Use the following procedure to replace the paper
Figure 4-6 Air Cleaner Components
Check for a buildup of dirt and debris around the air
cleaner system. Keep this area clean. Also check for
loose or damaged components. Replace all bent or
damaged air cleaner components.
Note: Operating the engine with loose or damaged air
element at the intervals specified in the service
schedule. Replace the paper element more often
under extremely dusty or dirty conditions.
1. Press the OFF button on the generator set
controller.
2. Disconnect the AC power to the generator set.
cleaner components could allow unfiltered air
into the engine causing premature wear and
failure.
3. Disconnect the generator set engine starting
battery, negative (–) lead first.
4. Loosen the cover knob and remove the cover.
5. Remove the element cover nut, element cover,
and the paper element with precleaner.
6. Remove the precleaner from the paper element.
TP-6843 1/13Section 4 Scheduled Maintenance49
Note: Do not wash the paper element or clean it
with pressurized air, as this will damage
the element.
7. Replace the element if it is dirty, bent, or
damaged.
8. Check the air cleaner base. Make sure it is
secure and not bent or damaged. Also check the
element cover for damage and fit. Replace all
damaged air cleaner components. Remove any
loose dirt or debris from the air cleaner base.
Wipe the base carefully so that no dirt drops into
the intake throat. Check the condition of the
rubber seal on the air cleaner stud and replace
the seal if necessary.
4.7Engine Starting Battery
!
WARNING
9. Reinstall the paper element, precleaner, element
cover, element cover nut, and the air cleaner
cover. Secure the cover with the cover knob.
10. Reconnect the AC power to the generator set.
11. Reconnect the generator set engine starting
battery, negative (–) lead last.
4.5Cooling System
The engine fan draws cooling air through the openings
in the sides. The alternator fan draws cooling air
through an opening on the side wall of the enclosure.
The cooling air mixes with the engine exhaust and is
discharged at the exhaust outlet. See the service view
in Section 1.7 for air intake and exhaust locations. To
prevent generator set damage caused by overheating,
keep the housing cooling inlets and outlets clean and
unobstructed at all times.
Note: Do not block the generator set cooling air inlets
or mount other equipment above them.
Overheating and severe generator damage may
occur.
4.6Exhaust System
Remove all combustible materials from the exhaust
location. Combustible materials include building
materials as well as natural surroundings. Keep dry
field grass, foliage, and combustible landscaping
material a minimum of 1.5 m (5 ft.) from the exhaust
outlet.
Periodically inspect the exhaust system components
for cracks, leaks, and corrosion.
• Check for corroded or broken metal parts and
replace them as needed.
• Check that the exhaust outlet is clear.
Sulfuric acid in batteries.
Can cause severe injury or death.
Wear protective goggles and
clothing. Battery acid may cause
blindness and burn skin.
Battery electrolyte is a diluted sulfuric acid. Battery acid
can cause severe injury or death. Battery acid can cause
blindness and burn skin. Always wear splashproof safety
goggles, rubber gloves, and boots when servicing the
battery. Do not open a sealed battery or mutilate the battery
case. If battery acid splashes in the eyes or on the skin,
immediately flush the affected area for 15 minutes with large
quantities of clean water. Seek immediate medical aid in the
case of eye contact. Never add acid to a battery after
placing the battery in service, as this may result in hazardous
spattering of battery acid.
Battery acid cleanup. Battery acid can cause severe
injury or death. Battery acid is electrically conductive and
corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking
soda) to a container with 4 L (1 gal.) of water and mix the
neutralizing solution. Pour the neutralizing solution on the
spilled battery acid and continue to add the neutralizing
solution to the spilled battery acid until all evidence of a
chemical reaction (foaming) has ceased. Flush the resulting
liquid with water and dry the area.
Battery gases. Explosion can cause severe injury or
death. Battery gases can cause an explosion. Do not
smoke or permit flames or sparks to occur near a battery at
any time, particularly when it is charging. Do not dispose of
a battery in a fire. To prevent burns and sparks that could
cause an explosion, avoid touching the battery terminals with
tools or other metal objects. Remove all jewelry before
servicing the equipment. Discharge static electricity from
your body before touching batteries by first touching a
grounded metal surface away from the battery. To avoid
sparks, do not disturb the battery charger connections while
the battery is charging. Always turn the battery charger off
before disconnecting the battery connections. Ventilate the
compartments containing batteries to prevent accumulation
of explosive gases.
Battery short circuits. Explosion can cause severe
injury or death. Short circuits can cause bodily injury and/or
equipment damage. Disconnect the battery before
generator set installation or maintenance. Remove all
jewelry before servicing the equipment. Use tools with
insulated handles. Remove the negative (–) lead first when
disconnecting the battery. Reconnect the negative (–) lead
last when reconnecting the battery. Never connect the
negative (–) battery cable to the positive (+) connection
terminal of the starter solenoid. Do not test the battery
condition by shorting the terminals together.
50Section 4 Scheduled MaintenanceTP-6843 1/13
Refer to this section for general battery information
KPS_030
1
2
1. To positive (+) terminal on starter solenoid
2. To ground (–) terminal on or near starter motor
and maintenance. Also consult the battery
manufacturer’s instructions for battery maintenance.
All generator set models use a negative ground with a
12-volt engine electrical system. Consult the
generator set nameplate for the engine electrical
system voltage. Consult the generator spec sheet for
battery capacity recommendations for replacement
purposes. Wiring diagrams provide battery connection
information. See Figure 4-7 for typical battery
connections.
Figure 4-7
4.8Storage Procedure
Perform the following storage procedure before
removing the generator set from service for three
months or longer. Follow the engine manufacturer’s
recommendations for storage, if available.
Note: Run the generator set monthly whenever
possible.
4.8.1Lubricating System
1. Operate the generator set until it reaches
operating temperature, or about 15 minutes.
2. Stop the generator set.
3. While the engine is still warm, drain the engine
lubrication oil from the engine crankcase.
4. Refill engine crankcase with oil. See Section
4.2.3 for oil recommendations.
5. Run the generator set for a few minutes to
distribute the clean oil.
6. Stop the generator set.
Figure 4-7 12-Volt Engine Electrical System Single
Starter Motor, Typical Battery Connection
Clean the battery and cables and tighten battery
terminals using the service schedule
recommendations. To prevent corrosion, maintain
tight, dry electrical connections at the battery
terminals. To remove corrosion from battery terminals,
disconnect the cables from the battery and scrub the
terminals with a wire brush. Clean the battery and
cables with a solution of baking soda and water. After
cleaning, flush the battery and cables with clean water
and wipe them with a dry, lint-free cloth.
After reconnecting the battery cables, coat the battery
terminals with petroleum jelly, silicone grease, or other
nonconductive grease.
4.8.2Fuel System
1. Start the generator set.
2. With the generator set running, shut off the gas
supply.
3. Run the generator set until the engine stops.
4. Press the OFF button on the generator set
controller.
4.8.3Cylinder Lubrication
1. Remove the spark plugs.
2. Pour one tablespoon of engine oil into each spark
plug hole. Install the spark plugs and ground the
spark plug leads. Do not connect the leads to the
plugs.
3. Crank the engine two or three revolutions to
lubricate the cylinders.
4.8.4Exterior Preparation
1. Clean the exterior surface of the generator set.
TP-6843 1/13Section 4 Scheduled Maintenance51
2. Seal all openings in the engine with
nonabsorbent adhesive tape.
3. Mask all areas to be used for electrical contact.
4. Spread a light film of oil over unpainted metallic
surfaces to prevent rust and corrosion.
4.8.5Battery
Perform battery storage last.
1. Press the OFF button on the generator set
controller.
2. Disconnect the battery, negative (–) lead first.
3. Clean the battery.
4. Place the battery in a warm, dry location.
5. Connect the battery to a float/equalize battery
charger, or charge the battery monthly using a
trickle charger. Follow the battery charger
manufacturer’s recommendations.
52Section 4 Scheduled MaintenanceTP-6843 1/13
Section 5 Troubleshooting
KPS_031A
GM77569
12
1. USB port (mini-B)
2. Not used
5.1Introduction
Use the troubleshooting charts in this section to
diagnose and correct common problems. First check
for simple causes such as a dead engine starting
battery, loose connections, or an open circuit breaker.
The charts include a list of common problems,
possible causes of the problem, and recommended
corrective actions.
If the procedures in this manual do not explain how to
correct the problem, contact an authorized Kohler
distributor/dealer. Maintain a record of repairs and
adjustments performed on the equipment. Use the
record to help describe the problem and repairs or
adjustments made to equipment.
5.2Fault Messages
The VSC controller displays fault messages to aid in
troubleshooting. Selected fault messages and
recommended checks are listed in Figure 2-5.
Identify and correct the cause of the fault condition.
Then reset the controller after a fault shutdown. See
Section 2.6.3.
5.3.2Line Circuit Breaker
The line circuit breaker interrupts the generator output
in the event of a fault in the wiring between the
generator and the load. If the circuit breaker trips,
reduce the load and switch the breaker back to the ON
position.
5.4Controller Service Access
A USB port is located in the service access area. See
Figure 5-1. Some controller settings can be adjusted
using a laptop computer with Kohler SiteTech
software. Use a USB cable with a mini-B connector to
connect the controller to your PC. See TP-6701,
SiteTech Software Operation Manual, for more
information.
Figure 5-1
5.3Circuit Protection
If the generator set circuit breaker trips repeatedly,
contact an authorized Kohler distributor/dealer for
service.
5.3.1Controller Internal Circuit
Protection
The controller is equipped with internal circuit
protection. A fault message, Accy PwrOver Warning
or MainPwrOverL Shutdown, is displayed if this
internal protection is activated. Press OFF to reset.
Contact an authorized Kohler distributor/dealer for
service.
Figure 5-1 Controller Service Access (cover
removed)
TP-6843 1/13Section 5 Troubleshooting53
5.5Troubleshooting
Figure 5-2 contains generator set troubleshooting, diagnostic, and repair information. Check for loose connections
before replacing parts.
Figure5-2
ProblemPossible CauseRecommended Action
Controller
display back light
is off.
Controller
display is off.
The generator
set does not
crank.
The generator
set cranks but
does not start,
starts hard,
lacks power, or
operates
erratically.
No DC output. Line circuit breaker in the OFF position. Place the circuit breaker in the ON position.
Low output or
excessive drop
in voltage.
Generator set
stops suddenly.
Figure 5-2 General Troubleshooting Chart
Backlight turns off after about 1 minute with no
activity.
Backlight will turn on when a button is pressed or the
generator set starts.
Low or no battery voltage. Check connections.
Check generator set battery. See Figure 1-2.
Battery weak or dead. Recharge or replace the battery.
Battery connections reversed or poor. Check the connections.
Fault shutdown. Check the controller display for fault messages. See
Section 2.6. Correct the fault condition and reset the
controller.
Generator set in the OFF mode. Press the RUN button to start the engine or press AUTO
to allow remote starting.
Air cleaner clogged. Clean and/or replace the air cleaner.
Battery weak or dead. Recharge or replace the battery.
Battery connection poor. Clean and tighten the battery connections.
Spark plug wire connection loose. Check the spark plug wires.
Low oil pressure shutdown. Check for oil leaks. Check the oil level and add oil if
necessary.
Fuel pressure insufficient. Check the fuel supply and valves.
Engine malfunction. Contact an authorized Kohler distributor/dealer.
Line circuit breaker tripping because of overload. Reduce the load on the generator set.
Line circuit breaker tripping because of short
circuit.
Contact an authorized Kohler distributor/dealer for
service.
Rectifier has failed. Verify that the generator is providing AC voltage.
Generator set overloaded. Reduce the load.
Low oil pressure shutdown. Check for oil leaks. Check the oil level and add oil if
necessary.
Out of fuel. Check fuel supply.
Overcrank shutdown. Reset the controller. If the overcrank fault occurs again,
contact an authorized Kohler distributor/dealer.
Auxiliary winding circuit breaker tripped. Reset the circuit breaker (located in controller’s service
access area). Contact an authorized Kohler
distributor/dealer for service if breaker trips repeatedly.
Fault shutdown. Check the controller display for fault messages. See
Section 2.6. Correct the fault condition and reset the
controller.
Generator set in the OFF mode. Press the RUN button to start the engine or press AUTO
to allow remote starting.
Remote stop command received from a remote
®
switch, or OnCue
.
Check the remote switch position. Check OnCue
®
.
Engine malfunction. Contact an authorized Kohler distributor/dealer.
54Section 5 TroubleshootingTP-6843 1/13
Appendix A Abbreviations
The following list contains abbreviations that may appear in this publication.
A, ampampere
ABDC after bottom dead center
AC alternating current
A/D analog to digital
ADC advanced digital control;
analog to digital converter
adj. adjust, adjustment
ADV advertising dimensional drawing
Ah amp-hour
AHWT anticipatory high water
temperature
AISI American Iron and Steel Institute
ALOP anticipatory low oil pressure
alt. alternator
Al aluminum
ANSI American National Standards
Institute (formerly American
Standards Association, ASA)
AO anticipatory only
APDC Air Pollution Control District
API American Petroleum Institute
approx. approximate, approximately
APU Auxiliary Power Unit
AQMD Air Quality Management District
AR as required, as requested
AS as supplied, as stated, as
suggested
ASE American Society of Engineers
ASME American Society of Mechanical
Engineers
assy. assembly
ASTM American Society for Testing
Materials
ATDC after top dead center
ATS automatic transfer switch
auto. automatic
aux. auxiliary
avg. average
AVR automatic voltage regulator
AWG American Wire Gauge
AWM appliance wiring material
bat. battery
BBDC before bottom dead center
BC battery charger, battery charging
BCA battery charging alternator
BCI Battery Council International
BDC before dead center
BHP brake horsepower
blk. black (paint color), block
(engine)
blk. htr. block heater
BMEP brake mean effective pressure
bps bits per second
br. brass
BTDC before top dead center
Btu British thermal unit
Btu/min. British thermal units per minute
C Celsius, centigrade
cal. calorie
CAN controller area network
CARB California Air Resources Board
CAT5 Category 5 (network cable)
CB circuit breaker
CC crank cycle
cc cubic centimeter
CCA cold cranking amps
ccw. counterclockwise
CEC Canadian Electrical Code
cert. certificate, certification, certified
cfh cubic feet per hour
cfm cubic feet per minute
CG center of gravity
CID cubic inch displacement
CL centerline
cm centimeter
CMOS complementary metal oxide
com communications (port)
coml commercial
Coml/Rec Commercial/Recreational
conn. connection
cont. continued
CPVC chlorinated polyvinyl chloride
crit. critical
CSA Canadian Standards Association
CT current transformer
Cu copper
cUL Canadian Underwriter’s
CUL Canadian Underwriter’s
cu. in. cubic inch
cw. clockwise
CWC city water-cooled
cyl. cylinder
D/A digital to analog
DAC digital to analog converter
dB decibel
dB(A) decibel (A weighted)
DC direct current
DCR direct current resistance
deg., ° degree
dept. department
dia. diameter
DI/EO dual inlet/end outlet
DIN Deutsches Institut fur Normung
DIP dual inline package
DPDT double-pole, double-throw
DPST double-pole, single-throw
DS disconnect switch
DVR digital voltage regulator
PROM, EEPROM
E
2
E, emer. emergency (power source)
ECM electronic control module,
EDI electronic data interchange
EFR emergency frequency relay
e.g. for example (exempli gratia)
EG electronic governor
EGSA Electrical Generating Systems
EIA Electronic Industries Association
EI/EO end inlet/end outlet
EMI electromagnetic interference
emiss. emission
eng. engine
EPA Environmental Protection
EPS emergency power system
ER emergency relay
ES engineering special, engineered
ESD electrostatic discharge
est. estimated
E-Stop emergency stop
etc. et cetera (and so forth)
exh. exhaust
ext. external
F Fahrenheit, female
FHM flat head machine (screw)
fl. oz. fluid ounce
flex. flexible
freq. frequency
FS full scale
ft. foot, feet
ft. lb. foot pounds (torque)
ft./min. feet per minute
ftp file transfer protocol
g gram
ga. gauge (meters, wire size)
gal. gallon
gen. generator
genset generator set
GFI ground fault interrupter
GND, ground
gov. governor
gph gallons per hour
gpm gallons per minute
gr. grade, gross
GRD equipment ground
gr. wt. gross weight
H x W x D height by width by depth
HC hex cap
HCHT high cylinder head temperature
HD heavy duty
HET high exhaust temp., high engine
hex hexagon
Hg mercury (element)
HH hex head
HHC hex head cap
HP horsepower
hr. hour
HS heat shrink
hsg. housing
HVAC heating, ventilation, and air
HWT high water temperature
Hz hertz (cycles per second)
IBC International Building Code
IC integrated circuit
ID inside diameter, identification
IEC International Electrotechnical
IEEE Institute of Electrical and
IMS mproved motor starting
in. inch
in. H
in. Hg inches of mercury
in. lb. inch pounds
Inc. incorporated
ind. industrial
int. internal
int./ext.internal/external
I/O input/output
IP internet protocol
ISO International Organization for
J joule
JIS Japanese Industry Standard
k kilo (1000)
K kelvin
kA kiloampere
KB kilobyte (2
KBus Kohler communication protocol
kg kilogram
kg/cm
kgm kilogram-meter
kg/m
kHz kilohertz
temp.
conditioning
Commission
Electronics Engineers
O inches of water
2
Standardization
10
bytes)
2
kilograms per square centimeter
3
kilograms per cubic meter
TP-6843 1/13Appendix55
kJ kilojoule
km kilometer
kOhm, kΩ kilo-ohm
kPa kilopascal
kph kilometers per hour
kV kilovolt
kVA kilovolt ampere
kVAR kilovolt ampere reactive
kW kilowatt
kWh kilowatt-hour
kWm kilowatt mechanical
kWth kilowatt-thermal
L liter
LAN local area network
L x W x H length by width by height
lb. pound, pounds
3
pounds mass per cubic feet
lbm/ft
LCB line circuit breaker
LCD liquid crystal display
LED light emitting diode
Lph liters per hour
Lpm liters per minute
LOP low oil pressure
LP liquefied petroleum
LPG liquefied petroleum gas
LS left side
sound power level, A weighted
L
wa
LWL low water level
LWT low water temperature
m meter, milli (1/1000)
M mega (10
3
cubic meter
m
3
/hr. cubic meters per hour
m
3
/min. cubic meters per minute
m
units), male
6
when used with SI
mA milliampere
man. manual
max. maximum
MB megabyte (2
20
bytes)
MCCB molded-case circuit breaker
MCM one thousand circular mils
meggar megohmmeter
MHz megahertz
mi. mile
mil one one-thousandth of an inch
min. minimum, minute
misc. miscellaneous
MJ megajoule
mJ millijoule
mm millimeter
mOhm, mΩ milliohm
MOhm, MΩ megohm
MOV metal oxide varistor
MPa megapascal
mpg miles per gallon
mph miles per hour
MS military standard
ms millisecond
m/sec. meters per second
mtg. mounting
MTU Motoren-und Turbinen-Union
MW megawatt
mW milliwatt
μF microfarad
N, norm. normal (power source)
NA not available, not applicable
nat. gas natural gas
NBS National Bureau of Standards
NC normally closed
NEC National Electrical Code
NEMA National Electrical
Manufacturers Association
NFPA National Fire Protection
Association
Nm newton meter
NO normally open
no., nos. number, numbers
NPS National Pipe, Straight
NPSC National Pipe, Straight-coupling
NPT National Standard taper pipe
thread per general use
NPTF National Pipe, Taper-Fine
NR not required, normal relay
ns nanosecond
OC overcrank
OD outside diameter
OEM original equipment manufacturer
OF overfrequency
opt. option, optional
OS oversize, overspeed
OSHA Occupational Safety and Health
Administration
OV overvoltage
oz. ounce
p., pp. page, pages
PC personal computer
PCB printed circuit board
pF picofarad
PF power factor
ph., Ø phase
PHC Phillips head Crimptite (screw)
PHH Phillips hex head (screw)
PHM pan head machine (screw)
PLC programmable logic control
PMG permanent magnet generator
pot potentiometer, potential
SPST single-pole, single-throw
spec specification
specs specification(s)
sq. square
sq. cm square centimeter
sq. in. square inch
SMS short message service
SS stainless steel
std. standard
stl. steel
tach. tachometer
TB terminal block
TCP transmission control protocol
TD time delay
TDC top dead center
TDEC time delay engine cooldown
TDEN time delay emergency to normal
TDES time delay engine start
TDNE time delay normal to emergency
TDOE time delay off to emergency
TDON time delay off to normal
temp. temperature
term. terminal
THD total harmonic distortion
TIF telephone influence factor
tol. tolerance
turbo. turbocharger
typ. typical (same in multiple
ppm parts per million
PROM programmable read-only
memory
psi pounds per square inch
psig pounds per square inch gauge
pt. pint
PTC positive temperature coefficient
PTO power takeoff
PVC polyvinyl chloride
UF underfrequency
UHF ultrahigh frequency
UIF user interface
UL Underwriter’s Laboratories, Inc.
UNC unified coarse thread (was NC)
UNF unified fine thread (was NF)
univ. universal
URL uniform resource locator (web
qt. quart, quarts
qty. quantity
R replacement (emergency) power
communications
RDO relay driver output
ref. reference
rem. remote
Res/Coml Residential/Commercial
RFI radio frequency interference
RH round head
RHM round head machine (screw)
rly. relay
rms root mean square
US undersize, underspeed
UV ultraviolet, undervoltage
V volt
VAC volts alternating current
VAR voltampere reactive
VDC volts direct current
VFD vacuum fluorescent display
VGA video graphics adapter
VHF very high frequency
W watt
WCR withstand and closing rating
w/ with
WO write only
w/o without
wt. weight
xfmr transformer
rnd. round
RO read only
ROM read only memory
rot. rotate, rotating
rpm revolutions per minute
RS right side
RTDs Resistance Temperature
Detectors
RTU remote terminal unit
RTV room temperature vulcanization
RW read/write
SAE Society of Automotive Engineers
scfm standard cubic feet per minute
SCR silicon controlled rectifier
s, sec. second
SI Systeme international d’unites,
International System of Units
SI/EO side in/end out
sil. silencer
SMTP simple mail transfer protocol
SN serial number
SNMP simple network management