Kohler 18TRES, 12RES, 8.5RES, 12TRES, 18RES Installation Manual

...
Page 1
Installation
Residential/Commercial Generator Sets
Models:
8.5/12/17/18RES 12/18TRES
Controller:
Advanced Digital Control ADC-RES
TP-6514 9/09e
Page 2
California Proposition 65
WARNING
Engine exhaust from this product contains chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.
Product Identification Information
Generator Set Identification Numbers
Record the product identification numbers from the generator set nameplate(s).
Model Designation
Specification Number
Serial Number
Accessory Number Accessory Description
Engine Identification
Record the product identification information from the engine nameplate.
Manufacturer
Model Designation
Serial Number
Controller Identification
Record the controller description from the generator set operation manual, spec sheet, or sales invoice.
Controller Description
Page 3
Table of Contents
Product Identification Information 2............................................................
Safety Precautions and Instructions 5........................................................
Introduction 9...............................................................................
Service Assistance 12........................................................................
Section 1 Installation 13......................................................................
1.1 General 13..............................................................
1.2 Lifting 13...............................................................
1.3 Generator Set Inspection 13...............................................
1.4 Location and Mounting 13.................................................
1.4.1 Exhaust Requirements 21.........................................
1.4.2 Air Requirements 21..............................................
1.5 Power Supply 22.........................................................
1.6 Fuel Requirements 22....................................................
1.6.1 Fuel Supply 22..................................................
1.6.2 Fuel Pipe Size 24................................................
1.7 Fuel Conversion 24......................................................
1.7.1 Fuel Conversion, 8.5/12 kW 25....................................
1.7.2 Fuel Conversion, 17/18 kW 26.....................................
1.8 Electrical Connections 28.................................................
1.8.1 AC Connections 28...............................................
1.8.2 Remote Start Connection 30.......................................
1.8.3 Grounding 30....................................................
1.8.4 Battery Charger 30...............................................
1.9 Battery 31...............................................................
1.10 Accessories 32..........................................................
1.10.1 Common Fault and Auxiliary Run Relay Board 32....................
1.10.2 Carburetor Heater 33.............................................
1.11 Prestart Installation Check 35..............................................
1.12 Startup Notification 35....................................................
1.13 Controller Configuration 35................................................
1.13.1 System Parameters 35............................................
1.13.2 Application Code Version 36.......................................
1.14 Voltage and Frequency Adjustments 38.....................................
1.14.1 Voltage Adjustment 38............................................
1.14.2 Frequency Adjustment 39.........................................
Section 2 Wiring Diagrams 43................................................................
Appendix A Abbreviations 53..................................................................
TP-6514 9/09 Table of Contents 3
Page 4
Notes
TP-6514 9/094
Page 5
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS.
Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS.
This manual has several types of safety precautions and instructions: Danger, Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a hazard that will cause severe
personal injury, death,orsubstantial property damage.
WARNING
Warning indicates the presence of a hazard that can cause severe
personal injury, death, or substantial property damage.
CAUTION
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage.
NOTICE
Notice communicates installation, operation, or maintenance information that is safety related but not hazard related.
Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals.
Accidental Starting
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before
working on the generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
Battery
WARNING
Sulfuric acid in batteries. Can cause severe injury or death.
Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
WARNING
Explosion. Can cause severe injury or death. Relays in the battery charger cause arcs or sparks.
Locate the battery in a well-ventilated area. Isolate the battery charger from explosive fumes.
Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid
can cause blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid.
Battery acid cleanup. Battery acid can cause severe injury or death.
Battery acid is electrically conductive and corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a containerwith4L(1gal.)ofwaterand mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area.
TP-6514 9/09 5Safety Precautions and Instructions
Page 6
Battery gases. Explosion can cause severe injury or death. Battery gases
can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases.
Battery short circuits. Explosion can cause severe injury or death.
Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Engine Backfire/Flash Fire
WARNING
Fire. Can cause severe injury or death.
Do not smoke or permit flames or sparks near fuels or the fuel system.
Servicing the fuel system. A flash fire can cause severe injury or death.
Do not smoke or permit flames or sparks near the carburetor, fuel line, fuel filter, fuel pump, or other potential sources of spilled fuels or fuel vapors. Catch fuels in an approved container when removing the fuel line or carburetor.
Combustible materials. A fire can cause severe injury or death.
Generator set engine fuels and fuel vapors are flammable and explosive. Handle these materials carefully to minimize the risk of fire or explosion. Equip the compartment or nearby area with a fully charged fire extinguisher. Select a fire extinguisher rated ABC or BC for electrical fires or as recommended by the local fire code or an authorized agency. Train all personnel on fire extinguisher operation and fire prevention procedures.
Exhaust System
WARNING
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide
is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust gas could seep inside or be drawn into a potentially occupied building through windows, air intake vents, or other openings.
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in exhaust gases. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Carbon monoxide poisoning symptoms include but are not limited to the following:
D Light-headedness, dizziness D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate or speak clearly, blurred vision
D Stomachache, vomiting, nausea If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.
Fuel System
WARNING
Explosive fuel vapors. Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
Gas fuel leaks. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an
explosion. Check the LP vapor gas or natural gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to 6--8 ounces per square inch (10--14 inches water column). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble.
Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator
set with the air cleaner removed.
TP-6514 9/096 Safety Precautions and Instructions
Page 7
Hazardous Noise
CAUTION
Hazardous noise. Can cause hearing loss.
Never operate the generator set without a muffler or with a faulty exhaust system.
Engine noise. Hazardous noise can cause hearing loss. Generator sets
not equipped with sound enclosures can produce noise levels greater than 105 dBA. Prolonged exposure to noise levels greater than 85 dBA can cause permanent hearing loss. Wear hearing protection when near an operating generator set.
Hazardous Voltage/ Moving Parts
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
WARNING
Hazardous voltage. Backfeed to the utility system can cause property damage, severe injury, or death.
If the generator set is used for standby power, install an automatic transfer switch to prevent inadvertent interconnection of standby and normal sources of supply.
Moving parts.
CAUTION
Welding the generator set. Can cause severe electrical equipment damage.
Never weld components of the generator set without first disconnecting the battery, controller wiring harness, and engine electronic control module (ECM).
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution
is possible whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turnoff the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Welding on the generator set. Can cause severe electrical equipment damage. Before welding on the
generator set perform the following steps: (1) Remove the battery cables, negative (--) lead first. (2) Disconnect all engine electronic control module (ECM) connectors. (3) Disconnect all generator set controller and voltage regulator circuit board connectors. (4) Disconnect the engine battery­charging alternator connections. (5) Attach the weld ground connection close to the weld location.
Connecting the battery and the battery charger. Hazardous voltage can cause severe injury or death.
Reconnect the battery correctly, positive to positive and negative to negative, to avoid electrical shock and damage to the battery charger and battery(ies). Have a qualified electrician install the battery(ies).
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can
cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death. Install
a transfer switch in standby power installations to prevent the connection of standby and other sources of power. Electrical backfeed into a utility electrical system can cause severe injury or death to utility personnel working on power lines.
WARNING
Airborne particles. Can cause severe injury or blindness.
Wear protective goggles and clothing when using power tools, hand tools, or compressed air.
Heavy Equipment
WARNING
Unbalanced weight. Improper lifting can cause severe injury or death and equipment damage.
Do not use lifting eyes. Lift the generator set using lifting bars inserted through the lifting holes on the skid.
TP-6514 9/09 7Safety Precautions and Instructions
Page 8
Hot Parts
Notice
WARNING
Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts.
The engine and exhaust system components become extremely hot during operation.
Servicing the engine heater. Hot parts can cause minor personal injury or property damage. Install the
heater before connecting it to power. Operating the heater before installation can cause burns and component damage. Disconnect power to the heater and allow it to cool before servicing the heater or nearby parts.
NOTICE
Canadian installations only.For standby service connect the output of the generator set to a suitably rated transfer switch in accordance with Canadian Electrical Code, Part 1.
TP-6514 9/098 Safety Precautions and Instructions
Page 9
Introduction
This manual provides installation instructions for Residential/Commercial model generator sets listed on the front cover. Refer to TP-6515, Operation Manual, for generator set operation and maintenance instructions.
The generator set is approved for use in stationary applications in locations served by a reliable utility power source.
Have an authorized distributor/dealer install the generator set outdoors according to the instructions in this manual. The generator set installation must comply with the National Electrical Code (NEC) and local code requirements. Do not install this generator set indoors.
Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this publication and the products represented without notice and without any obligation or liability whatsoever.
Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury. Read and follow the Safety Precautions and Instructions section at the beginning of this manual.
See Figure 1 and Figure 2 for generator set component locations.
19 2017
75 61234
16
8
9
18 21
22
23
10
15
25
12
14 13
1. Muffler
2. Oil check
3. Oil fill
4. Air cleaner
5. Fuses
6. RS-232 connector (for application program updates)
7. Controller user interface
8. Generator set master switch (RUN-OFF/RESET-AUTO)
9. Load circuit breaker
10. Field-connection terminal block location (RES models)
11. Spark plug locations (both sides)
12. Oil drain hose
13. Oil drain valve
11
14. Oil filter
15. Exhaust
16. Equipment ground
17. Relay board location (optional)
18. Battery charger
19. DSAI lead location
20. Fuel block
21. Gas regulator assembly
22. Fuel solenoid valve
23. Fuel inlet
24. Air intake
25. Engine starting battery location (battery purchased separately)
Figure 1 Generator Set Component Locations, 8.5/12 kW Models
24
ADV-7466-
TP-6514 9/09 9
Page 10
Control detail
8
17
12
9
11
10
See control
12 5421
3
6
18
19
20
22
detail
7
23
24
29
28
27
25
ADV-7341A-B
16
1415
13
26
1. Muffler
2. Oil check
3. Oil fill
4. Air cleaner
5. Spark plug locations (both sides)
6. Oil filter
7. Oil cooler location
8. ADC-RES Advanced Digital Control user interface
9. Generator set master switch (RUN-OFF/RESET-AUTO)
10. Line circuit breaker
11. Fuses
12. RS-232 connector (for application program updates)
13. Engine starting battery location (battery purchased separately)
14. Oil drain hose
15. Nameplate location (on base)
16. Oil drain valve
17. Exhaust
18. Relay board location (optional)
19. Carburetor heater access opening
20. LP fuel orifice location (inside hose fitting)
21. Gas regulator assembly
22. DSAI leads
23. Fuel solenoid valve
24. Fuel inlet
25. Air intake
26. Battery cables
27. Battery charger
28. Field-connection terminal block location (RES models)
29. 120 VAC receptacles for battery charger and optional carburetor heater
Figure 2 Generator Set Component Locations, 17/18 kW Models
TP-6514 9/0910
Page 11
2
1
3
GM66010
1. Emergency stop button
2. Field-connection terminal block and circuit breakers
3. Cable inlet area
Figure 3 Additional Components, TRES (3-phase)
Models
TP-6514 9/09 11
Page 12
Service Assistance
For professional advice on generator set power requirements and conscientious service, please contact your nearest Kohler distributor or dealer.
D Consult the Yellow Pages under the heading
Generators—Electric.
D Visit the Kohler Power Systems website at
KohlerPower.com.
D Look at the labels and stickers on your Kohler product
or review the appropriate literature or documents included with the product.
D Call toll free in the US and Canada 1-800-544-2444.
D Outside the US and Canada, call the nearest regional
office.
Headquarters Europe, Middle East, Africa (EMEA)
Kohler Power Systems 3 rue de Brennus 93200 Saint Denis France Phone: (33) 1 49 178300 Fax: (33) 1 49 178301
Asia Pacific
Power Systems Asia Pacific Regional Office Singapore, Republic of Singapore Phone: (65) 6264-6422 Fax: (65) 6264-6455
China
North China Regional Office, Beijing Phone: (86) 10 6518 7950
(86) 10 6518 7951 (86) 10 6518 7952
Fax: (86) 10 6518 7955
East China Regional Office, Shanghai Phone: (86) 21 6288 0500 Fax: (86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office Bangalore, India Phone: (91) 80 3366208
(91) 80 3366231
Fax: (91) 80 3315972
Japan, Korea
North Asia Regional Office Tokyo, Japan Phone: (813) 3440-4515 Fax: (813) 3440-2727
Latin America
Latin America Regional Office Lakeland, Florida, USA Phone: (863) 619-7568 Fax: (863) 701-7131
TP-6514 9/0912
Page 13
Section 1 Installation
1.1 General
Have an authorized distributor/dealer install the generator set outdoors according to the instructions in this manual. Do not install this generator set indoors.
Use the specifications provided here only in the initial planning. Use the generator set and transfer switch dimension drawings and wiring diagrams for installation.
1.2 Lifting
WARNING
Unbalanced weight. Improper lifting can cause severe injury or death and equipment damage.
Do not use lifting eyes. Lift the generator set using lifting bars inserted through the lifting holes on the skid.
Model Weight, kg (lb.)
8.5 kW 180 (400)
12 kW 186 (410)
17/18 kW 227 (500)
Figure 1-1 Approximate Weights
Approximate generator set weights are shown in Figure 1-1. Use lifting bars inserted through the holes in the skid to lift the unit. See the dimension drawings on the following pages for lifting hole locations.
1.3 Generator Set Inspection
Complete a thorough inspection of the generator set. Check for the following:
1. Inspect the generator set for loose or damaged parts or wires. Repair or tighten any loose parts before installation.
2. Check the engine oil. Fill, if necessary, with the recommended viscosity and grade of oil. Use synthetic oil, API (American Petroleum Institute) Service Class SG or higher. See TP-6515, Operation Manual, for additional information.
1.4 Location and Mounting
See the dimension drawings on the following pages for the generator set dimensions and fuel and electric inlet locations. The drawing dimensions are shown in millimeters, with inches in brackets.
Install the generator set outdoors. Provide the minimum clearance around the generator set shown in the clearance drawings on the following pages. Locate the generator set so that the hot exhaust does not blow on plants or other combustible materials. Do not install the generator set where exhaust gas could accumulate and seep inside or be drawn into a potentially occupied building.
The generator set is shipped on a plastic mounting pad. Prepare a flat, level mounting area covered with a weed barrier and gravel as shown in the generator set clearance drawing. Set the plastic mounting pad directly on the gravel. Do not install the mounting pad directly on grass.
See Figure 1-4 for the high wind mounting detail for the
8.5/12 kW model.
TP-6514 9/09 13Section 1 Installation
Page 14
Figure 1-2 Generator Set Mounting Details and Dimensions, 8.5RES, 12RES, and 12TRES (3-phase),
ADV-7466, Sheet 1
TP-6514 9/0914 Section 1 Installation
Page 15
Figure 1-3 Generator Set Clearances, 8.5RES, 12RES, and 12TRES (3-phase), ADV-7466, Sheet 2
TP-6514 9/09 15Section 1 Installation
Page 16
Figure 1-4 High Wind Mounting Detail, 8.5RES, 12RES, and 12TRES (3-phase), ADV-7466, Sheet 3
TP-6514 9/0916 Section 1 Installation
Page 17
Figure 1-5 Generator Set Mounting Details and Dimensions, 17RES and 18RES, ADV-7341-B, Sheet 1
TP-6514 9/09 17Section 1 Installation
Page 18
Figure 1-6 Generator Set Clearances, 17RES and 18RES, ADV-7341-B, Sheet 2
TP-6514 9/0918 Section 1 Installation
Page 19
Figure 1-7 Generator Set Mounting Details and Dimensions, 18TRES (3-phase), ADV-7713, Sheet 1
TP-6514 9/09 19Section 1 Installation
Page 20
Figure 1-8 Generator Set Clearances, 18TRES (3-phase), ADV-7713, Sheet 2
TP-6514 9/0920 Section 1 Installation
Page 21
1.4.1 Exhaust Requirements
1.4.2 Air Requirements
WARNING
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is an
odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust gas could seep inside or be drawn into a potentially occupied building through windows, air intake vents, or other openings.
The exhaust system is complete for generator sets installed outdoors. Do not install this generator set indoors.
Figure 1-9 gives the exhaust flow and temperature at rated load. The engine exhaust mixes with the generator set cooling air at the exhaust end of the enclosure. Mount the generator set so that the hot exhaust does not blow on plants or other combustible materials. Maintain the clearances shown in Figure 1-3 or Figure 1-6.
Exhaust System 60 Hz 50 Hz
Exhaust flow at rated kW,
3
/min. (cfm)
m
8.5 kW 3.3 (115) 2.7 (96)
12 kW 3.8 (135) 3.2 (113)
17/18 kW 5.3 (187) 4.4 (155)
Exhaust gas exiting the enclosure at rated kW, _C(_F)
Figure 1-9 Exhaust Flow and Temperature
216 (420)
The generator set requires correct air flow for cooling and combustion. The inlet and outlet openings in the sound enclosure provide the cooling and combustion air. Figure 1-10 shows the locations of the cooling air intake and exhaust vents. Inspect the air inlet and outlet openings inside and outside the housing to ensure that the air flow is not blocked.
3
1
2
1. Exhaust outlet
2. Alternator air intake (both sides)
3. Engine air intake
3
tp6195
Figure 1-10 Cooling Air Intake and Exhaust, Typical
Air Requirements, m
Model Hz
8.5 kW
12 kW
17/18 kW
60 26.9 (950) 0.94 (33.4) 27.8 (980)
50 22.4 (790) 0.8 (28.0) 23.2 (820)
60 26.9 (950) 1.1 (39.2) 28.0 (990)
50 22.4 (790) 0.9 (32.6) 23.4 (825)
60 28.0 (989) 1.62 (57.3) 29.6 (1045)
50 22.6 (798) 1.42 (50.1) 24.0 (848)
Cooling
Air
3
/min. (cfm)
Combustion
Air
Tot a l
Inlet Air
Figure 1-11 Air Requirements
TP-6514 9/09 21Section 1 Installation
Page 22
1.5 Power Supply
1.6 Fuel Requirements
Power must be supplied from a source that is GFCI protected to the generator set location for the battery charger and the optional accessories shown in Figure 1-12.
Connect power from a circuit on the essential loads panel to the utility power connection points on the terminal block. See Section 1.8 and the wiring diagrams in Section 2 for connection details. See Figure 1-12 or Figure 1-13 for the power requirements for the battery charger and accessories.
Power Requirement, Max.
Equipment
Battery charger (standard) 192 1.6
Carburetor heater (optional)
Battery heater (optional) 110 0.92
Watts Amps Vol t s
37 0.33
120
Figure 1-12 Power Requirements, RES Models
Power Requirement, Max.
Equipment
Battery charger 60 0.26
Carburetor heater
Watts Amps Vol t s
37 0.16
230
Figure 1-13 Power Requirements, TRES (3-phase)
Models
The generator set operates using natural gas or LP vapor fuel. The generator set is EPA-certified for both natural gas and LP vapor fuels.
The fuel system installation must comply with the NEC and local codes.
1.6.1 Fuel Supply
Because of variable climates and geographical considerations, contact the local fuel supplier for fuel system planning and installation. Figure 1-14 lists the recommended fuel ratings and other fuel supply information for natural gas and LP vapor fuels.
Natural
Fuel type
Fuel supply inlet 1/2 NPT
Fuel supply pressure, kPa (in. H2O)
8.5/12 kW
Fuel supply pressure, kPa (in. H2O), 17/18 kW
Fuel flow rate, Btu/hr.
8.5 kW 132000 180000
12 kW 193000 203000
17/18 kW 242000 280000
Nominal Fuel Rating, Btu/ft.
Natural gas 1000
LP vapor 2500
3
GasLPVapor
1.3--2.7 (5--11)
1.7--2.7 (7--11)
1.7--2.7 (7--11)
Figure 1-14 Fuel Supply
Verify that the output pressure from the primary gas utility (or LP tank) pressure regulator is 1.7--2.7 kPa (7--11 in. water column) and that the utility gas meter flow rate is sufficient to supply the generator set at rated load plus all other gas-consuming appliances. See Figure 1-15, Figure 1-16, or Figure 1-17 for fuel consumption. Contact the fuel supplier for flow rate information or a gas meter upgrade.
Figure 1-2 or Figure 1-5 shows the location of the fuel inlet connection. Use flexible sections to prevent fuel line breakage caused by vibration. Hold the fuel solenoid valve with a wrench when tightening the fuel connections. Protect all fuel lines from machinery or equipment contact, adverse weather conditions, and environmental damage.
TP-6514 9/0922 Section 1 Installation
Page 23
Fuel Consumption, at % load, m
3
/hr. (cfh)
60 Hz 50 Hz
Natural Gas, m3/hr. (cfh)
100% 3.7 (132) 3.3 (118)
75% 3.2 (113) 2.9 (101)
50% 2.6 (93) 2.3 (83)
25% 2.2 (77) 1.9 (69)
LP Vapor, m3/hr. (cfh)
100% 2.0 (72) 1.7 (61)
75% 1.3 (45) 1.1 (38)
50% 1.0 (36) 0.9 (31)
25% 0.8 (29) 0.7 (25)
LP vapor conversion factors:
Nominal fuel rating:
3
8.58 ft.
0.535 m
36.39 ft.
Natural gas: 37 MJ/m LP vapor: 93 MJ/m
=1lb.
3
=1kg
3
= 1 gal.
3
(1000 Btu/ft.3)
3
(2500 Btu/ft.3)
Fuel Consumption, at % load, m
3
/hr. (cfh)
60 Hz 50 Hz
Natural Gas, m3/hr. (cfh)
100% 6.9 (242) 5.7 (203)
75% 5.8 (204) 4.7 (167)
50% 4.4 (155) 3.8 (133)
25% 3.4 (120) 2.9 (103)
LP Vapor, m3/hr. (cfh)
100% 3.2 (112) 2.7 (94)
75% 2.7 (96) 2.2 (79)
50% 2.1 (74) 1.7 (62)
25% 1.6 (57) 1.4 (50)
LP vapor conversion factors:
Nominal fuel rating:
3
8.58 ft.
0.535 m
36.39 ft.
Natural gas: 37 MJ/m LP vapor: 93 MJ/m
=1lb.
3
=1kg
3
= 1 gal.
3
(1000 Btu/ft.3)
3
(2500 Btu/ft.3)
Figure 1-15 Fuel Consumption, 8.5 kW
Fuel Consumption, at % load, m
Natural Gas, m3/hr. (cfh)
100% 5.9 (209) 4.9 (175)
75% 4.8 (168) 4.0 (141)
50% 3.6 (127) 3.0 (106)
25% 2.4 (85) 2.0 (71)
LP Vapor, m3/hr. (cfh)
100% 3.1 (108) 2.5 (89)
75% 2.5 (87) 2.0 (72)
50% 1.9 (65) 1.5 (53)
25% 1.2 (44) 1.0 (36)
LP vapor conversion factors:
8.58 ft.
0.535 m
36.39 ft.
Nominal fuel rating:
Natural gas: 37 MJ/m LP vapor: 93 MJ/m
3
=1lb.
3
3
3
/hr. (cfh)
=1kg
= 1 gal.
3
(1000 Btu/ft.3)
3
(2500 Btu/ft.3)
60 Hz 50 Hz
Figure 1-17 Fuel Consumption, 17/18 kW
Figure 1-16 Fuel Consumption, 12 kW
TP-6514 9/09 23Section 1 Installation
Page 24
1.6.2 Fuel Pipe Size
1.7 Fuel Conversion
Ensure that the natural gas pipe size and length meet the specifications in Figure 1-18, Figure 1-19, or Figure 1-20. Measure the pipe length from the primary gas pressure regulator to the pipe connection on the generator set fuel inlet. Add 2.4 m (8 ft.) to the measured length for each 90 degree elbow. Compare the total pipe length with the chart in Figure 1-18, Figure 1-19, or Figure 1-20 to find required pipe size.
Contact local LP provider for LP installation information.
Pipe Size, in. NPT Maximum Pipe Length m (ft.)
3/4 18.3 m (60 ft.)
1 61 m (200 ft.)
11/4 91.5 m (300 ft.)
Figure 1-18 Fuel Pipe Size, Natural Gas, 8.5 kW
Pipe Size, in. NPT Maximum Pipe Length, m (ft.)
3/4 9.2 m (30 ft.)
1 30 m (100 ft.)
11/4 68.6 m (225 ft.)
Figure 1-19 Fuel Pipe Size, Natural Gas, 12 kW
Minimum Gas Pipe Size Recommendation, in. NPT
Natural Gas
Pipe Length, m (ft.)
8 m (25 ft.) 1 3/4
15 m (50 ft.) 1 1
30 m (100 ft.) 11/4 1
46 m (150 ft.) 11/4 11/4
61 m (200 ft.) 11/4 11/4
(242,000 Btu/hr.)
LP Vapor
(280,000 Btu/hr.)
The multi-fuel system allows conversion from natural gas to LP vapor (or vice-versa) in the field while maintaining emissions-standard compliance. A trained technician or an authorized distributor/dealer can convert the fuel system.
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
WARNING
Figure 1-20 Fuel Pipe Size, 17/18 kW
Explosive fuel vapors. Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
TP-6514 9/0924 Section 1 Installation
Page 25
1.7.1 Fuel Conversion, 8.5/12 kW
4. Turn off the fuel supply.
Two fuel connections on the fuel block allow field­conversion between natural gas and LP vapor. The fuel metering valves are factory-set and sealed to comply with applicable emission standards and to provide the best possible hot and cold starting.
Note: Do not adjust the factory-sealed fuel-metering
adjustments on the fuel block. Changing the fuel­metering adjustments may violate federal or state laws.
Use the following procedure to convert from natural gas (NG) to LP vapor, moving the fuel connection from the natural gas to the LP port, plugging the natural gas port, and disconnecting the leads for the digital spark advance ignition (DSAI). See Figure 1-21 for the fuel system component locations.
1
2
5. Remove the hose clamp and fuel hose from the hose fitting in the fuel block. See Figure 1-22.
1
5
2
Natural gas
4
1. Fuel block
2. Fuel metering valves—factory-sealed, do not adjust
3. Fuel inlet, 1/2 in. NPT
4. Hose fitting
5. Plug
setup shown
Figure 1-22 Fuel Block, 8.5/12 kW
3
tp6195
GM29253
1. DSAI connector location
2. Fuel block
3. Fuel inlet, 1/2 in. NPT female
Figure 1-21 Fuel System Locations, 8.5/12 kW
Procedure to convert from NG to LP, 8.5/12 kW
1. Place the generator set master switch in the OFF position.
2. Disconnect the power to the battery charger.
3. Disconnect the generator set engine starting battery, negative (--) lead first.
3
6. Remove the hose fitting from the natural gas outlet port in the fuel block. See Figure 1-22.
7. Remove the plug from the LP port in the fuel block. See Figure 1-22. Clean the plug with a dry cloth or brush, apply fresh pipe sealant, and install the plug into the natural gas outlet port.
8. Clean the hose fitting with a dry cloth or brush, apply fresh pipe sealant to the threads, and install the fitting into the LP port.
Note: Do not adjust the fuel metering valves.
9. Slide the hose onto the hose fitting and secure it with the clamp.
TP-6514 9/09 25Section 1 Installation
Page 26
10. For the 12 kW: Disconnect the DSAI leads for LP. See Figure 1-23 and Figure 1-24.
Fuel DSAI Leads
Natural Gas Connect
LP Disconnect
Figure 1-23 DSAI Connection,12/17/18 kW Models
tp6195
1.7.2 Fuel Conversion, 17/18 kW
For LP vapor fuel, an orifice is used in the fuel line. The unit is typically shipped set up for natural gas, with the loose orifice tied near the fuel line. To convert to LP vapor, install the orifice and disconnect the spark advance leads as described below. See Figure 1-25 for the fuel system component locations.
1
2
3
4
Fuel System Detail
5
2
6
3
4
1
1. DSAI leads (12 kW model only)
Figure 1-24 Digital Spark Advance Module Leads
(located in generator set air intake area)
11. Connect and turn on the new fuel supply.
12. Check that the generator set master switch is in the OFF position.
13. Reconnect the generator set engine starting battery leads, negative (--) lead last.
14. Reconnect power to the battery charger.
15. Start the generator set by moving the generator set master switch to the RUN position.
16. Check for leaks using a gas leak detector.
17. Run the generator set and check the operation. Use the controller to adjust the output and stability if necessary. See Section 1.14 for instructions.
18. Move the generator set master switch to the OFF/ RESET position to shut down the generator set.
GM51561A-D
1. Hose fitting (LP orifice fits inside; see Figure 1-26)
2. Regulator
3. Fuel valve
4. Fuel inlet, 1/2 in. NPT female
5. Fuel hose with clamp
6. DSAI connector location (see Figure 1-27)
Figure 1-25 Fuel System Components, 17/18 kW
To convert from LP vapor to natural gas, follow the same fuel conversion procedure, moving the hose fitting to the natural gas port and plugging the LP port. For the 12 kW model, connect the DSAI leads for natural gas. See Figure 1-23 and Figure 1-24.
TP-6514 9/0926 Section 1 Installation
Page 27
Procedure to Convert from NG to LP, 17/18 kW
1. Place the generator set master switch in the OFF position.
2. Disconnect the power to the battery charger.
3. Disconnect the generator set engine starting battery, negative (--) lead first.
4. Turn off the fuel supply.
5. Remove the hose clamp and fuel hose from the hose fitting. See Figure 1-25.
6. Insert the orifice into the hose fitting. See Figure 1-26.
7. Slide the hose onto the hose fitting and secure it with the clamp.
8. Disconnect digital spark-advance module (DSAI) leads 65 and N5 for LP. (Connect the leads for natural gas.) See Figure 1-27 and Figure 1-28.
1
1. LP orifice (remove for natural gas)
2. Hose fitting
3. Regulator
Figure 1-26 LP Fuel Orifice, 17/18 kW
2
3
tp6514
9. Connect and turn on the new fuel supply.
10. Check that the generator set master switch is in the OFF position.
11. Reconnect the generator set engine starting battery leads, negative (--) lead last.
12. Reconnect power to the battery charger.
13. Start the generator set by moving the generator set master switch to the RUN position.
14. Check for leaks using a gas leak detector.
15. Run the generator set and check the operation. Use the controller to adjust the output and stability if necessary. See Section 1.14 for instructions.
16. Move the generator set master switch to the OFF/ RESET position to shut down the generator set.
To convert from LP vapor to natural gas, remove the fuel orifice and connect the DSAI leads together.
1
tp6514
1. DSAI leads 65 and N5: connect for natural gas, disconnect for LP.
Figure 1-27 Digital Spark Advance Ignition (DSAI)
Leads 65 and N5, 17/18 kW
Fuel DSAI Leads 65 and N5
Natural Gas Connect
LP Disconnect
Figure 1-28 DSAI Connections
TP-6514 9/09 27Section 1 Installation
Page 28
1.8 Electrical Connections
WARNING
Refer to the transfer switch specifications and the decal below the terminal block for the cable size range for each connection. Route AC leads through flexible conduit. Ensure that the leads and conduit do not interfere with the operation of the generator set or obstruct the service areas.
Hazardous voltage. Backfeed to the utility system can cause property damage, severe injury, or death.
If the generator set is used for standby power, install an automatic transfer switch to prevent inadvertent interconnection of standby and normal sources of supply.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death. Install a transfer
switch in standby power installations to prevent the connection of standby and other sources of power. Electrical backfeed into a utility electrical system can cause severe injury or death to utility personnel working on power lines.
Field Connections to the Terminal Block, RES Models
See Figure 1 or Figure 2 in the Introduction section of this manual for the terminal block location. See Figure 1-29 for terminal block details. Leads have been factory-installed from the junction box to the terminal block for easy field wiring. Make field connections to the terminal block. Refer to the terminal block decal for connections and cable sizes.
1. Drill holes for the conduit fittings. See the dimension drawing for each model for the recommended electrical inlet locations. Feed the cables through the openings.
2. Connect the leads from the transfer switch emergency source lugs to the L1 and L2 connections on the generator set terminal block.
3. Connect the neutral (L0) and ground (GRD) leads from the ATS and the main panel to the corresponding connection points on the terminal block. See Section 1.8.3, Grounding.
NOTICE
Canadian installations only. For standby service connect the output of the generator set to a suitably rated transfer switch in accordance with Canadian Electrical Code, Part 1.
Have an authorized distributor/dealer or a licensed electrician make the following electrical connections. The electrical installation must comply with the National Electrical Code (NEC) and all applicable local codes. Canadian installations must comply with the Canadian Electrical Code (CEC) and applicable local codes.
Ground the generator set from the GRD terminal inside controller compartment according to applicable codes.
1.8.1 AC Connections
The generator set is equipped with a field-connection terminal block located in the air inlet area near the junction box. Refer to the decal near the terminal block for connections. Also see Section 2, Wiring Diagrams.
Note: Sample decal shown. See the decal on the generator
set for wire gauge.
GM58022 GM54820
Figure 1-29 Field-Connection Terminal Block, typical
RES Models
TP-6514 9/0928 Section 1 Installation
Page 29
4. Connect the engine start leads from the automatic transfer switch or remote start switch to terminals 3 and 4 on the terminal block. See Section 1.8.2.
5. The terminal block kit includes 120 VAC receptacles for the battery charger and optional carburetor heater. Connect utility power to the terminal block as shown. Connect to a circuit that is supplied by the generator set if utility power is lost. See Section 1.5 for more information about the 120 VAC power requirement.
1
Field Connections, TRES (3-phase) Models
See Figure 3 in the Introduction section of this manual for the terminal block location. See Figure 1-31 for terminal block details. Leads have been factory­installed from the junction box to the terminal block for easy field wiring. Make field connections to the terminal block. Refer to the decal near the terminal block for connections.
1. Remove the cable inlet cover. See Figure 1-30.
2. Drill holes for the cable fittings into the cable inlet cover and reinstall the cover.
3. Remove the circuit breaker cover.
4. Feed the cables through the openings in the cover and connect the cables. Refer to Figure 1-31 and the decal near the terminal block. See Section
1.8.3, Grounding, and Section 2, Wiring Diagrams.
5. Connect the engine start leads from the automatic transfer switch or remote start switch to terminals 3 and 4 on the terminal block. See Section 1.8.2.
2
1. Terminal block and circuit breaker cover
2. Cable inlet cover
Figure 1-30 TRES (3-phase) Models
Note: See the label near the terminal block for
connections. N5 = Mains Neutral M5 = Mains Live
4
3
2
1
5
6
GM66010
6. Connect utility power (for the battery charger and carburetor heater) to the terminal block as shown on the label. Connect to a circuit that is supplied by the generator set if utility power is lost. See Section
1.5 for more information about the utility power requirement.
GM66066
7. Verify that the cables are secure and there is no stress on the connections.
8. Replace the circuit breaker cover.
1. Engine start connection
2. Utility ground
3. Utility 230V power connection (see label)
4. Auxiliary contact (factory connection)
5. Load connections
6. Ground (earth)
Figure 1-31 Field Connection, TRES (3-phase)
Models
TP-6514 9/09 29Section 1 Installation
Page 30
1.8.2 Remote Start Connection
Connect terminals 3 and 4 to the automatic transfer switch’s engine start terminals or to an optional remote start/stop switch. Route the engine start leads through separate conduit from the AC power and load leads.
type of transfer switch used in the application determine the grounding of the neutral at the generator. NEC 2002 Section 250.20 is one example that has a very good explanation of the neutral grounding requirements for generators.
1.8.3 Grounding
Ground the generator set. The grounding method must comply with NEC and local codes. Connect the grounding strap to the generator set ground lug, terminal GND inside the controller compartment.
Generator sets are shipped with the generator neutral attached to the generator in the junction box. At installation, the neutral can be grounded at the generator set or lifted from the ground stud and isolated if the installation requires an ungrounded neutral connection at the generator. The generator set will operate properly with the neutral either bonded to ground or isolated from ground at the generator.
Various regulations and site configurations including the National Electrical Code (NEC), local codes, and the
1.8.4 Battery Charger
A battery charger is factory-installed in the battery compartment to keep the starting battery fully charged. The battery charger’s DC leads are factory-connected to the battery. Supply power to the generator set for the battery charger and carburetor heater as described in Sections 1.5 and 1.8.1.
RES models: Plug the battery charger’s power cord into the receptacle on the bottom of the controller junction box.
TRES (3-phase) models: The battery charger’s power cord is factory-connected.
Refer to the generator set operation manual for battery charger operation information.
TP-6514 9/0930 Section 1 Installation
Page 31
1.9 Battery
WARNING
Sulfuric acid in batteries. Can cause severe injury or death.
Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
WARNING
Explosion. Can cause severe injury or death. Relays in the battery charger cause arcs or sparks.
Locate the battery in a well-ventilated area. Isolate the battery charger from explosive fumes.
Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid can cause
blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid.
Battery gases. Explosion can cause severe injury or death. Battery gases can cause an explosion. Do not smoke
or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases.
Battery short circuits. Explosion can cause severe injury or death. Short circuits can cause bodily injury and/or
equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Connecting the battery and the battery charger. Hazardous voltage can cause severe injury or death.
Reconnect the battery correctly, positive to positive and negative to negative, to avoid electrical shock and damage to the battery charger and battery(ies). Have a qualified electrician install the battery(ies).
Use a 12-volt battery with a minimum rating of 525 cold cranking amps at 0_F. The generator set uses a negative ground with a 12-volt engine electrical system. See Figure 1-32 for battery connections. Make sure that the battery is correctly connected and the terminals are tight.
1
2
Battery acid cleanup. Battery acid can cause severe injury or death. Battery acid is electrically conductive and
corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a container with 4 L (1 gal.) of water and mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area.
TP-6514 9/09 31Section 1 Installation
EZ-273000-J
1. To positive (+) terminal on starter solenoid.
2. To ground (--) terminal on or near starter motor.
Figure 1-32 12-Volt Engine Electrical System Single
Starter Motor Typical Battery Connection
Note: The generator set will not start and circuit board
damage may occur if the battery is connected in reverse.
Page 32
Figure 1-33 shows the location of the engine starting battery. Standard battery cables provide easy connection to the battery. Use the following procedure to install and connect the battery.
1
If there are no accessories, proceed to Section 1.11, Prestart Installation Check.
1.10.1 Common Fault and Auxiliary Run Relay Board
The optional relay board provides two additional relays to control customer-provided equipment:
D Common fault relay, energized on a fault.
D Auxiliary run relay, energized when the generator set
is running.
ADV-7341A-B
1. Engine starting battery location
Figure 1-33 Battery Location, Air Intake End
Battery Installation Procedure
1. Ensure that the starting battery is fully charged before placing the battery in service.
2. Clean the battery posts and/or adapters if necessary.
3. Install the battery post adapters, if needed.
4. Place the battery in the housing.
5. Verify that the controller master switch is in the OFF position.
6. Connect the positive (+) lead to the engine starting battery.
7. Connect the negative (--) lead to the engine starting battery.
See Figure 1-34 for the relay board location.
1
17/18 kW
2
8.5/12 kW
1
GM53102
Refer to the generator set operation manual and the battery manufacturer’s instructions for battery maintenance instructions.
1.10 Accessories
Have accessories installed by an authorized distributor/ dealer or a licensed electrician. Follow the installation instructions provided with each kit. Use separate conduit for AC and DC leads to reduce the possibility of electrical interference. Verify that the leads and conduit do not interfere with the operation of the generator set or obstruct the service areas. Verify that the electrical installation complies with the National Electrical Code (NEC) and all applicable local codes. See Section 2, Wiring Diagrams, for more information regarding generator set electrical connections.
2
1. Relay board 2. Controller junction box
Figure 1-34 Optional Relay Board Location
TP-6514 9/0932 Section 1 Installation
Page 33
Connect customer equipment to terminal strip TB1 on the relay board, following the markings on the board. Connect to each relay’s normally open or normally closed contacts depending on the application. Use size 14 AWG maximum wire for connections to TB1. See Figure 1-35 and Figure 1-36.
1.10.2 Carburetor Heater
An optional carburetor heater is recommended for improved cold starting in locations where the ambient temperature drops below 0_C(32_F). The carburetor heater prevents condensation and carburetor icing. The heater turns on when the temperature at the thermostat falls below approximately 4_C(40_F) and turns off when the temperature rises above approximately 16_C (60_F). See Figure 1-37 through Figure 1-39.
The heater thermostat is installed in the cord. Figure 1-40 shows the location of the thermostat on the power cord. The heater power cord and thermostat are located in the generator set housing air intake area/ battery compartment. See Figure 1-33.
Note: Do not place the heater thermostat inside the
generator set engine compartment. The thermostat must be exposed to the ambient air.
The heater requires a continuous source of power.
1
1. Connect customer equipment to TB1, 14 AWG max.
GM51403
Figure 1-35 Relay Board Connections
Terminal Label Description
COMMON FAULT NC Common fault relay normally
closed contact. Opens on a fault.
COMMON FAULT COM Common fault relay common
COMMON FAULT NO Common fault relay normally
open contact. Closes on a fault.
AUX RUN NC Auxiliary run relay normally
closed contact. Open when generator set is running.
AUX RUN COM Auxiliary run relay common
AUX RUN NO Auxiliary run relay normally
open contact. Closed when generator set is running.
Note: Use maximum 14 AWG wire for TB1 connections.
Single-phase (RES) models: Plug the carburetor heater into an outlet that supplies continuous 120 VAC power.
Three-phase (TRES) models: The carburetor heater power is factory-connected to the battery charger.
1
2
Figure 1-36 Common Fault and Run Relay Board
Harness Connections
TP-6514 9/09 33Section 1 Installation
tp6195
1. Carburetor heater (air cleaner removed to show heater)
2. Carburetor heater power cord
Figure 1-37 8.5/12 kW Carburetor Heater Location
Page 34
1
2
4
1
GM57969
1. Thermostat
2. Bulkhead opening for carburetor heater access
3. Carburetor heater cord with thermostat
4. 120 VAC receptacles for carburetor heater and battery charger RES models)
Figure 1-38 17/18 kW Carburetor Heater Location
(air intake side of generator set)
1
2
8.5/12 kW Carburetor Heater
1
2
3
tp6514
1. Carburetor heater location
Figure 1-39 17/18 kW Carburetor Heater Location on
Engine (bulkhead removed to show heater location)
3
GM19463
3
1. Power plug (single-phase type shown)
Figure 1-40 Carburetor Heaters
17/18 kW Carburetor Heater
2. Thermostat 3. Heater
GM57968
TP-6514 9/0934 Section 1 Installation
Page 35
1.11 Prestart Installation Check
1.13 Controller Configuration
Review the entire installation section. Inspect all wiring and connections to verify that the generator set is ready for operation. Check all items in the following Prestart Checklist.
Prestart Checklist
Air Cleaner. Check that a clean air cleaner element is
installed to prevent unfiltered air from entering the engine. See the generator set operation manual for instructions.
Air Inlets. Check for clean and unobstructed air inlets.
Battery. Check for tight battery connections. Consult
the battery manufacturer’s instructions regarding battery care and maintenance.
Exhaust System. Check for exhaust leaks and blockages. Check the muffler condition.
D Inspect the exhaust system components for cracks,
leaks, and corrosion. Check for tight exhaust system connections.
D Check for corroded or broken metal parts and replace
them as needed.
D Check that the exhaust outlet is unobstructed.
Oil Level. Maintain the oil level at or near, not over, the full mark on the dipstick.
Operating Area. Check for obstructions that could block the flow of cooling air. Keep the air intake area clean. Do not leave rags, tools, or debris on or near the generator set.
1.13.1 System Parameters
The controller configuration for each generator model is set at the factory and should not normally require changes. The controller’s configuration mode allows adjustment of the system parameters listed in this section. Use the instructions in this section to check the configuration after installation and change them to match the settings shown in Figure 1-41, if necessary.
Parameter Setting Definition
Unit’s system voltage and frequency
Engine type Ec00 8.5/12 kW
Communication setting *
* Controller application code version 1.13 or higher. [ Default setting for application code version 1.13 or higher.
Figure 1-41 Controller Configuration Parameters
Uu01 Single phase, 60 Hz,
120/240 VAC
Uu03 Three-phase, 50 Hz,
230/400 VAC (TRES)
Uu06 Single phase, 50 Hz,
115/230 VAC
Ec12 17/18 kW
Cn00 No J1939 communication.
Sleep mode enabled (48-hour power down in AUTO).
Cn01 [ J1939 communication
enabled. Sleep mode disabled (no power down in AUTO).
1.12 Startup Notification
Complete the startup and installation checklists supplied with the startup notification form. Complete and sign the startup notification form and submit copies to Kohler Co. and the distributor/dealer as instructed on the form.
Standby systems not registered within 60 days of startup are automatically registered using the manufacturer’s ship date as the startup date.
TP-6514 9/09 35Section 1 Installation
Page 36
Follow the instructions in Figure 1-42 to enter the configuration mode while the engine is not running and then step through the following parameters. Use the up (
) and down () arrow buttons to select the appropriate
setting for the application.
The controller will automatically exit the configuration mode without saving any changes after about 1 minute if no buttons are pressed. Start the configuration procedure over again from the beginning if the controller exits the configuration mode before the settings have been saved.
Communication/Sleep Mode Setting (Cn). (Available on controllers with application code version 1.13 or higher.) The communication setting enables or disables J1939 communication, and also disables or enables the sleep mode. When J1939 communication is enabled, the sleep mode is turned off to allow uninterrupted communication with a personal computer running remote monitoring software. If remote monitoring is not used, the communication can be turned off, enabling the sleep mode which causes the controller to power down after 48 hours of inactivity. The generator set master switch must be in AUTO for the sleep mode to function.
Note: Be sure to save your settings before exiting the
configuration mode. The controller reverts to the last saved settings when the master switch is moved to the OFF/RESET position.
Voltage/frequency setting (Uu). Select the system voltage and frequency from the table in Figure 1-41.
Note: The Uu parameter sets the system’s rated
voltage and frequency. To adjust the output (measured) voltage and frequency, see Section
1.14, Voltage and Frequency Adjustments.
Engine configuration (Ec). The engine configuration must match the generator set engine type.
The default setting for controllers with application code version 1.13 or higher is Cn01, communication on/sleep mode off. Controllers with earlier application code versions have communication disabled and the sleep mode enabled. The Cn setting is not adjustable on these earlier versions.
1.13.2 Application Code Version
To check the application code version number, HOLD the select button while moving the generator set master switch to RUN. (The engine will not start when the select button is held.) Wait about 5 seconds for the application code version number to appear on the display. See Figure 1-42.
TP-6514 9/0936 Section 1 Installation
Page 37
Controller Configuration Mode:
Hold the Select button:
Move the generator set master switch to the RUN position. (The generator set engine will not start.)
Wait about 5 seconds until the display shows the program version number. (The number may be different than the one shown here.)
Press the down arrow key and then the up arrow key 3 times to enter the configuration mode. (This is the controller “password.”)
Now release the Select button.
Press:
or
To enter setting and step to the next parameter, engine type Ec.
To change the voltage/frequency setting, if necessary. See Figure 1-41.
Display:
. 0
v 1 1 3
U u 0 1
U u 0 x
Press:
OR
or
To enter setting and step to the next parameter, communication setting Cn.
or
To enter setting and step to SAVE.
To SAVE CHANGES.
To DISCARD CHANGES without saving.
“Yes” or “no” flashes when the up or down arrow is pressed and then the controller exits the configuration mode. The display returns to the runtime hours.
To change the engine type, if necessary.
To change the communication setting, if necessary. See Figure 1-41.
8.5/12 kW 17/18 kW
E c 0 0 E c 1 2
C n 0 x
S A V E
Y E S
n o
x x xx
Now move the master switch to OFF/RESET.
Note: Shaded boxes show which number in the controller display changes when the up or down arrow
keyispressed. X in the runtime hours display above denotes any number from 0 to 9.
Figure 1-42 Configuration Mode (system voltage/frequency, engine type, and communication parameters)
TP-6514 9/09 37Section 1 Installation
Page 38
1.14 Voltage and Frequency Adjustments
WARNING
Hazardous voltage. Can cause severe injury or death.
Moving parts.
Changes in voltage and speed adjustments are lost if not saved before the generator set shuts down. The generator set continues to run with the new settings until it shuts down but then reverts to the previous settings at the next startup if the changes have not been saved.
1.14.1 Voltage Adjustment
Note: Refer to the flowcharts in Figure 1-46 through
Figure 1-48 during the following procedure.
Operate the generator set only when all guards and electrical enclosures areinplace.
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury
and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
The controller’s adjustment mode allows adjustment of the output voltage and frequency, if necessary. Have adjustments performed by an authorized distributor/ dealer or service technician.
Note: A digital multimeter that measures voltage and
frequency is required for these adjustments.
Use a digital multimeter to check the output voltage and frequency. If output voltage or frequency is not within specifications, use the ADC controller to adjust the output voltage and engine speed (frequency) while the generator set is running. See Figure 1-43. The flowcharts in Figure 1-46 through Figure 1-48 outline the adjustment procedures.
Voltage Adjustment Procedure
1. With the generator set off, connect a digital multimeter to the output leads or an electrical outlet on the load side of the generator set. Set the meter to measure AC voltage.
2. Start the generator set by moving the generator set master switch to the RUN position.
3. Use the ADC controller to adjust the voltage (parameter 1P) until the output voltage reaches the desired value. Refer to the flowcharts in Figure 1-46 through Figure 1-48 for instructions to adjust the output voltage. See Figure 1-44 for the approximate change in voltage per step.
Voltage Change per
Measured
Voltage, VAC
85--132 1P00--99 5 0.5
180--251 1P00--99 7 0.7
ADC
Display
Step, VAC
Coarse Fine
Figure 1-44 Voltage Adjustment (approximate)
Note: Be sure to save your changes as instructed in
Figure 1-48 before exiting configuration mode.
1
1. Select button 2. Arrow buttons
2
tp6514
Figure 1-43 Advanced Digital Control
4. Adjust the voltage stability (gain, parameter 2P) to minimize light flicker.
5. Readjust the voltage, if necessary.
6. Set the multimeter to measure frequency.
7. Adjust the engine speed to the cut-in frequency shown in Figure 1-45 by adjusting the engine governor speed (parameter 4P).
Frequency Cut-In Frequency
60 Hz 57.5 Hz
50 Hz 47.5 Hz
Figure 1-45 Cut-In Frequencies
TP-6514 9/0938 Section 1 Installation
Page 39
8. Adjust the volts/Hz (parameter 3P) until the voltage level measured by the multimeter begins to drop. When the volts/Hz is set correctly, the generator (as load is applied) attempts to maintain normal output until the engine speed drops below the cut-in frequency set in step 7.
9. Reset the engine speed to the operating frequency (50 or 60 Hz) by adjusting the engine governor speed (parameter 4P).
10. Readjust the voltage stability (gain, parameter 2P), if necessary.
11. Readjust the voltage (parameter 1P), if necessary.
12. Save settings. See Figure 1-48.
Frequency Adjustment Procedure
Note: Refer to the flowcharts in Figure 1-46 through
Figure 1-48 during the following procedure.
1. Attach a frequency meter to the AC output leads or an electrical outlet on the load side of the generator set.
2. Start and run the generator set until it reaches normal operating temperature (at least 10 minutes).
3. Adjust electronic governor speed (parameter 4P) to obtain a frequency reading of 60 Hz (or 50 Hz if appropriate). Each step changes the engine speed about 3.6 rpm, which changes the output frequency about 0.06 Hz.
13. Stop the generator set.
1.14.2 Frequency Adjustment
The engine speed determines the generator output frequency; 60 Hz units operate at 3600 rpm and 50 Hz units run at 3000 rpm. Adjust the engine governor speed and gain to set the output frequency and stability using the following procedure.
Note: Refer to the flowcharts in Figure 1-46 through
Figure 1-48 during the following procedure.
4. Check stability with the generator set running and with no load applied. If the generator set speed is unstable, hunts, or surges, adjust the governor stability (gain, parameter 5P) until the generator set becomes stable with no hunting or surging. (Increasing the gain slows the governor response.)
5. Check the frequency reading. Repeat steps 3 and 4 if necessary to obtain the rated frequency and stable operation.
6. Save settings. See Figure 1-48.
TP-6514 9/09 39Section 1 Installation
Page 40
Output Voltage and Frequency Adjustment M ode:
Move the generator set master switch to the RUN position. The generator set engine starts and the controller display shows the engine runtime hours.
Display :*
x x x x
Hold:
The controller is now in the voltage coarse adjustment mode.
Press:
Wait about 5 seconds until the display changes from runtime hours to the program version number.
Press the down arrow key and then the up arrow key 3 times to enter the adjustment mode. (This is the controller “password.”)
or
or
To raise or lower the voltage in large increments (approximately 5--7 volts per step). (Parameter 1P)
To enter fine voltage adjustment mode.
To raise or lower the voltage in smaller increments (approximately 0.5--0.7 volts per step). (Parameter 1P)
x x
x
.
1 P
1 P
x x
x x
1 P x x
To enter coarse voltage stability (gain) adjustment mode.
2 P
or
To raise or lower the voltage stability (gain) in large increments. (Parameter 2P)
To enter fine voltage stability (gain) adjustment mode.
2 P
or
or
Continued on Figure 1-47.
* Shaded boxes show which character in the controller display changes for each adjustment. X in the
examples above denotes any number from 0 to 9. The actual values may vary from model-to-model.
To raise or lower the voltage stability (gain) in smaller increments. (Parameter 2P)
To enter volts/Hz adjustment mode. (Parameter 3P)
To raise or lower the volts/Hz: 00=low; 09= high
3 P x
x x
xx
x
TP6196
Figure 1-46 Output Voltage and Frequency Adjustments
TP-6514 9/0940 Section 1 Installation
Page 41
Continued from Figure 1-46:
Press:
Display:*
or
or
or
To enter engine governor speed coarse adjustment mode. (Parameter 4P)
To raise or lower the engine speed in large increments.
To enter engine governor speed fine adjustment mode. (Parameter 4P)
To raise or lower the engine speed in smaller increments.
To enter engine governor stability (gain) coarse adjustment mode. (Parameter 5P)
To raise or lower the engine governor stability (gain) in large increments.
To enter engine governor stability (gain) fine adjustment mode. (Parameter 5P)
4 P
4 P
5 P
5 P
x x
xx
x x
xx
or
Note: Be sure to save your settings before exiting the configuration mode. The controller reverts to
the last saved settings when the master switch is moved to the OFF/RESET position.
* Shaded boxes show which character in the controller display changes for each adjustment. X in the
examples above denotes any number from 0 to 9. The actual values may vary from model-to-model.
Figure 1-47 Output Voltage and Frequency Adjustments, Continued
To raise or lower the engine governor stability (gain) in smaller increments.
To enter SAVE mode. Go to Figure 1-48.
S A V E
TP-6514 9/09 41Section 1 Installation
Page 42
There are 3 options when the display says SAVE: Press:
S A V E
To return to the first parameter, coarse voltage adjustment, to check or change settings before saving. See Figure 1-46.
or
To save changes.
or
To discard changes without saving.
“Yes”or “no” flashes when the up or down arrow is pressed and then the controller exits the configuration mode. The display returns to the runtime hours.
Now move the master switch to OFF/RESET.
Figure 1-48 Save Mode
1 P
x x
Y E S
n o
x x x x
TP-6514 9/0942 Section 1 Installation
Page 43
Section 2 Wiring Diagrams
Figure 2-1 lists the wiring diagram numbers and locations.
Wiring Diagram Description Drawing Number Page
8.5/12RES Schematic Diagram ADV-7325 44
8.5/12RES Point-to-Point Wiring Diagram GM51414 45
17/18RES Schematic Diagram ADV-7353 46
17/18RES Point-to-Point Wiring Diagram GM52541 47
12TRES (3-phase) Schematic Diagram ADV-7623 48
12TRES (3-phase) Point-to-Point Wiring Diagram GM63546 49
18TRES (3-phase) Schematic Diagram ADV-7637 50
18TRES (3-phase) Point-to-Point Wiring Diagram GM65661 51
Figure 2-1 Wiring Diagrams and Schematics
TP-6514 9/09 43Section 2 Wiring Diagrams
Page 44
Figure 2-2 Schematic Diagram, Single Phase, 8.5/12RES, ADV-7325-D
-
TP-6514 9/0944 Section 2 Wiring Diagrams
Page 45
Figure 2-3 Point-to-Point Wiring Diagram, Single Phase, 8.5/12RES, GM51414-C
TP-6514 9/09 45Section 2 Wiring Diagrams
-
Page 46
Figure 2-4 Schematic Diagram, Single Phase, 17/18RES, ADV-7353-F
-
TP-6514 9/0946 Section 2 Wiring Diagrams
Page 47
Figure 2-5 Point-to-Point Wiring Diagram, Single Phase, 17/18RES, GM52541-E
TP-6514 9/09 47Section 2 Wiring Diagrams
Page 48
Figure 2-6 Schematic Diagram, Three-Phase, 12TRES, ADV-7623 Sheet 4
TP-6514 9/0948 Section 2 Wiring Diagrams
Page 49
Figure 2-7 Point-to-Point Wiring Diagram, Three-Phase, 12TRES, GM63546, Sheet 3
TP-6514 9/09 49Section 2 Wiring Diagrams
Page 50
Figure 2-8 Schematic Diagram, Three-Phase, 18TRES, ADV-7637, Sheet 3
TP-6514 9/0950 Section 2 Wiring Diagrams
Page 51
Figure 2-9 Point-toPoint Wiring Diagram, Three-Phase, 18TRES, GM65661, Sheet 3
TP-6514 9/09 51Section 2 Wiring Diagrams
Page 52
Notes
TP-6514 9/0952 Section 2 Wiring Diagrams
Page 53
Appendix A Abbreviations
The following list contains abbreviations that may appear in this publication.
A, amp ampere ABDC after bottom dead center AC alternating current A/D analog to digital ADC advanced digital control;
adj. adjust, adjustment ADV advertising dimensional
Ah amp-hour AHWT anticipatory high water
AISI American Iron and Steel
ALOP anticipatory low oil pressure alt. alternator Al aluminum ANSI American National Standards
AO anticipatory only APDC Air Pollution Control District API American Petroleum Institute approx. approximate, approximately APU Auxiliary Power Unit AQMD Air Quality Management District AR as required, as requested AS as supplied, as stated, as
ASE American Society of Engineers ASME American Society of
assy. assembly ASTM American Society for T esting
ATDC after top dead center ATS automatic transfer switch auto. automatic aux. auxiliary avg. average AVR automatic voltage regulator AWG American Wire Gauge AWM appliance wiring material bat. battery BBDC before bottom dead center BC battery charger, battery
BCA battery charging alternator BCI Battery Council International BDC before dead center BHP brake horsepower blk. black (paint color), block
blk. htr. block heater BMEP brake mean effective pressure bps bits per second br. brass BTDC before top dead center Btu British thermal unit Btu/min. British thermal units per minute C Celsius, centigrade cal. calorie CAN controller area network CARB California Air Resources Board CAT5 Category 5 (network cable) CB circuit breaker CC crank cycle cc cubic centimeter CCA cold cranking amps ccw. counterclockwise CEC Canadian Electrical Code cert. certificate, certification, certified cfh cubic feet per hour
analog to digital converter
drawing
temperature
Institute
Institute (formerly American Standards Association, ASA)
suggested
Mechanical Engineers
Materials
charging
(engine)
cfm cubic feet per minute CG center of gravity CID cubic inch displacement CL centerline cm centimeter CMOS complementary metal oxide
com communications (port) coml commercial Coml/Rec Commercial/Recreational conn. connection cont. continued CPVC chlorinated polyvinyl chloride crit. critical CSA Canadian Standards
CT current transformer Cu copper cUL Canadian Underwriter’s
CUL Canadian Underwriter’s
cu. in. cubic inch cw. clockwise CWC city water-cooled cyl. cylinder D/A digital to analog DAC digital to analog converter dB decibel dB(A) decibel (A weighted) DC direct current DCR direct current resistance deg., ° degree dept. department dia. diameter DI/EO dual inlet/end outlet DIN Deutsches Institut fur Normung
DIP dual inline package DPDT double-pole, double-throw DPST double-pole, single-throw DS disconnect switch DVR digital voltage regulator
2
E
PROM, EEPROM
E, emer. emergency (power source) ECM electronic control module,
EDI electronic data interchange EFR emergency frequency relay e.g. for example (exempli gratia) EG electronic governor EGSA Electrical Generating Systems
EIA Electronic Industries
EI/EO end inlet/end outlet EMI electromagnetic interference emiss. emission eng. engine EPA Environmental Protection
EPS emergency power system ER emergency relay ES engineering special,
ESD electrostatic discharge est. estimated E-Stop emergency stop etc. et cetera (and so forth)
substrate (semiconductor)
Association
Laboratories
Laboratories
e. V. (also Deutsche Industrie Normenausschuss)
electrically-erasable programmable read-only memory
engine control module
Association
Association
Agency
engineered special
exh. exhaust ext. external F Fahrenheit, female FHM flat head machine (screw) fl. oz. fluid ounce flex. flexible freq. frequency FS full scale ft. foot, feet ft. lb. foot pounds (torque) ft./min. feet per minute ftp file transfer protocol ggram ga. gauge (meters, wire size) gal. gallon gen. generator genset generator set GFI ground fault interrupter
GND, gov. governor gph gallons per hour gpm gallons per minute gr. grade, gross GRD equipment ground gr. wt. gross weight H x W x D height by width by depth HC hex cap HCHT high cylinder head temperature HD heavy duty HET high exhaust temp., high
hex hexagon Hg mercury (element) HH hex head HHC hex head cap HP horsepower hr. hour HS heat shrink hsg. housing HVAC heating, ventilation, and air
HWT high water temperature Hz hertz (cycles per second) IBC International Building Code IC integrated circuit ID inside diameter, identification IEC International Electrotechnical
IEEE Institute of Electrical and
IMS improved motor starting in. inch in. H in. Hg inches of mercury in. lb. inch pounds Inc. incorporated ind. industrial int. internal int./ext. internal/external I/O input/output IP internet protocol ISO International Organization for
J joule JIS Japanese Industry Standard k kilo (1000) K kelvin kA kiloampere KB kilobyte (2 KBus Kohler communication protocol kg kilogram
ground
engine temp.
conditioning
Commission
Electronics Engineers
O inches of water
2
Standardization
10
bytes)
TP-6514 9/09 Appendix 53
Page 54
2
kg/cm
kgm kilogram-meter kg/m
kilograms per square centimeter
3
kilograms per cubic meter kHz kilohertz kJ kilojoule km kilometer kOhm, kkilo-ohm kPa kilopascal kph kilometers per hour kV kilovolt kVA kilovolt ampere kVAR kilovolt ampere reactive kW kilowatt kWh kilowatt-hour kWm kilowatt mechanical kWth kilowatt-thermal L liter LAN local area network L x W x H length by width by height lb. pound, pounds
3
lbm/ft
pounds mass per cubic feet LCB line circuit breaker LCD liquid crystal display LED light emitting diode Lph liters per hour Lpm liters per minute LOP low oil pressure LP liquefied petroleum LPG liquefied petroleum gas LS left side L
wa
LWL low water level
sound power level, A weighted
LWT low water temperature m meter, milli (1/1000) M mega (10
3
m
3
m
3
m
units), male
cubic meter
/hr. cubic meters per hour /min. cubic meters per minute
6
when used with SI
mA milliampere man. manual max. maximum MB megabyte (2
20
bytes) MCCB molded-case circuit breaker MCM one thousand circular mils meggar megohmmeter MHz megahertz mi. mile mil one one-thousandth of an inch min. minimum, minute misc. miscellaneous MJ megajoule mJ millijoule mm millimeter mOhm, mmilliohm MOhm, MΩmegohm MOV metal oxide varistor MPa megapascal mpg miles per gallon mph miles per hour MS military standard ms millisecond m/sec. meters per second mtg. mounting MTU Motoren-und Turbinen-Union MW megawatt mW milliwatt μF microfarad N, norm. normal (power source) NA not available, not applicable nat. gas natural gas
NBS National Bureau of Standards NC normally closed NEC National Electrical Code NEMA National Electrical
Manufacturers Association
NFPA National Fire Protection
Association Nm newton meter NO normally open no., nos. number, numbers NPS National Pipe, Straight NPSC National Pipe, Straight-coupling NPT National Standard taper pipe
thread per general use NPTF National Pipe, Taper-Fine NR not required, normal relay ns nanosecond OC overcrank OD outside diameter OEM original equipment
manufacturer OF overfrequency opt. option, optional OS oversize, overspeed OSHA Occupational Safety and Health
Administration OV overvoltage oz. ounce p., pp. page, pages PC personal computer PCB printed circuit board pF picofarad PF power factor ph., phase PHC Phillipsr head Crimptiter
(screw) PHH Phillipsr hex head (screw) PHM pan head machine (screw) PLC programmable logic control PMG permanent magnet generator pot potentiometer, potential ppm parts per million PROM programmable read-only
memory psi pounds per square inch psig pounds per square inch gauge pt. pint PTC positive temperature coefficient PTO power takeoff PVC polyvinyl chloride qt. quart, quarts qty. quantity R replacement (emergency)
power source rad. radiator, radius RAM random access memory RDO relay driver output ref. reference rem. remote Res/Coml Residential/Commercial RFI radio frequency interference RH round head RHM round head machine (screw) rly. relay rms root mean square rnd. round RO read only ROM read only memory rot. rotate, rotating rpm revolutions per minute RS right side RTDs Resistance Temperature
Detectors
RTU remote terminal unit RTV room temperature vulcanization RW read/write SAE Society of Automotive
Engineers scfm standard cubic feet per minute SCR silicon controlled rectifier s, sec. second SI Systeme international d’unites,
International System of Units SI/EO side in/end out sil. silencer SMTP simple mail transfer protocol SN serial number SNMP simple network management
protocol SPDT single-pole, double-throw SPST single-pole, single-throw spec specification specs specification(s) sq. square sq. cm square centimeter sq. in. square inch SMS short message service SS stainless steel std. standard stl. steel tach. tachometer TB terminal block TCP transmission control protocol TD time delay TDC top dead center TDEC time delay engine cooldown TDEN time delay emergency to
normal TDES time delay engine start TDNE time delay normal to
emergency TDOE time delay off to emergency TDON time delay off to normal temp. temperature term. terminal THD total harmonic distortion TIF telephone influence factor tol. tolerance turbo. turbocharger typ. typical (same in multiple
locations) UF underfrequency UHF ultrahigh frequency UIF user interface UL Underwriter’s Laboratories, Inc. UNC unified coarse thread (was NC) UNF unified fine thread (was NF) univ. universal URL uniform resource locator
(web address) US undersize, underspeed UV ultraviolet, undervoltage V volt VAC volts alternating current VAR voltampere reactive VDC volts direct current VFD vacuum fluorescent display VGA video graphics adapter VHF very high frequency W watt WCR withstand and closing rating w/ with WO write only w/o without wt. weight xfmr transformer
TP-6514 9/0954 Appendix
Page 55
Page 56
TP-6514 9/09e
E 2007, 2008, 2009 by Kohler Co. All rights reserved.
KOHLER CO. Kohler, Wisconsin 53044 Phone 920-565-3381, Fax 920-459-1646 For the nearest sales/service outlet in the US and Canada, phone 1-800-544-2444 KohlerPower.com
Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65) 6264-6422, Fax (65) 6264-6455
Loading...