Kohler 17RES, 8.5RES, 12RES, 18RES, 12TRES Operation Manual

...
Page 1
Operation
Residential/Commercial Generator Sets
Models:
17RES
Controller:
Advanced Digital Control ADC-RES
TP-6515 10/07
Page 2
California Proposition 65
WARNING
Product Identification Information
Product identification numbers determine service parts. Record the product identification numbers in the spaces below immediately after unpacking the products so that the numbers are readily available for future reference. Record field-installed kit numbers after installing the kits.
Generator Set Identification Numbers
Record the product identification numbers from the generator set nameplate(s).
Model Designation
Specification Number
Serial Number
Accessory Number Accessory Description
Controller Identification
Record the controller description from the generator set operation manual, spec sheet, or sales invoice.
Controller Description
Engine Identification
Record the product identification information from the engine nameplate.
Manufacturer
Model Designation
Serial Number
Page 3
Table of Contents
Product Identification Information 2............................................................
Safety Precautions and Instructions 5........................................................
Introduction 9...............................................................................
Service Assistance 10........................................................................
Section 1 Features 11........................................................................
1.1 Specifications 11.........................................................
1.2 Generator 11............................................................
1.3 Engine 11...............................................................
1.4 Advanced Digital Control 11...............................................
1.5 Generator Set Components 12.............................................
Section 2 Operation 13.......................................................................
2.1 Prestart Checklist 13.....................................................
2.2 Exercising Generator Set 13...............................................
2.3 ADC-RES Controls and Indicators 13.......................................
2.3.1 LED Display 13..................................................
2.3.2 Controller Keypad 14.............................................
2.3.3 Generator Set Master Switch 14...................................
2.4 Controller Power 15......................................................
2.4.1 Standby Mode 15................................................
2.4.2 Sleep Mode 15..................................................
2.5 Generator Set Operation 15...............................................
2.5.1 Starting Generator Set 15.........................................
2.5.2 Stopping Generator Set 15........................................
2.6 Faults 16...............................................................
2.6.1 Shutdowns 16...................................................
2.6.2 Warnings 16.....................................................
2.6.3 Resetting Controller after a Fault Shutdown 16.......................
2.7 Battery Charger 18.......................................................
2.7.1 Battery Charger Operation 18......................................
Section 3 Scheduled Maintenance 19..........................................................
3.1 Routine Maintenance 19..................................................
3.2 Service Schedule 20.....................................................
3.3 Lubrication System 21....................................................
3.3.1 Low Oil Pressure Shutdown 21....................................
3.3.2 Oil Check 21....................................................
3.3.3 Engine Oil Recommendation 21....................................
3.3.4 Oil Change Procedure 21.........................................
3.3.5 Oil Cooler 22....................................................
3.4 Spark Plugs 22..........................................................
3.5 Air Cleaner Service 23....................................................
3.6 Cooling System 23.......................................................
3.7 Exhaust System 24......................................................
3.8 Battery 24...............................................................
3.9 Battery Charger 25.......................................................
3.10 Circuit Protection 25......................................................
3.10.1 Line Circuit Breaker 25...........................................
3.10.2 Fuses 25.......................................................
TP-6515 10/07 Table of Contents
Page 4
Table of Contents, continued
3.11 Storage Procedure 26....................................................
3.11.1 Lubricating System 26............................................
3.11.2 Fuel System 26..................................................
3.11.3 Cylinder Lubrication 26...........................................
3.11.4 Exterior Preparation 26...........................................
3.11.5 Battery 26.......................................................
Section 4 Troubleshooting 27.................................................................
4.1 Introduction 27..........................................................
4.2 Controller Troubleshooting 27.............................................
4.3 Generator Set Troubleshooting 28..........................................
4.4 Battery Charger Troubleshooting 29........................................
Appendix A Abbreviations 31................................................................
TP-6515 10/07Table of Contents
Page 5
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS.
Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS.
This manual has severaltypesofsafety precautions and instructions: Danger, Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a hazard that will cause severe
personal injury,death,orsubstantial property damage.
WARNING
Warning indicates the presence of a hazard that can cause severe
personal injury,death,or substantial property damage.
CAUTION
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage.
NOTICE
Notice communicates installation, operation, or maintenance information that is safety related but not hazard related.
Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals.
Accidental Starting
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before
working on the generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
Battery
WARNING
Sulfuric acid in batteries. Can cause severe injury or death.
Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
WARNING
Explosion. Can cause severe injury or death. Relays in the battery charger cause arcs or sparks.
Locate the battery in a well-ventilated area. Isolate the battery charger from explosive fumes.
Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid
can cause blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid.
Battery acid cleanup. Battery acid can cause severe injury or death.
Battery acid is electrically conductive and corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a containerwith4L(1gal.)ofwaterand mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area.
TP-6515 10/07 5Safety Precautions and Instructions
Page 6
Battery gases. Explosion can cause severe injury or death. Battery gases
can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases.
Battery short circuits. Explosion can cause severe injury or death.
Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Servicing the fuel system. A flash fire can cause severe injury or death.
Do not smoke or permit flames or sparks near the carburetor, fuel line, fuel filter, fuel pump, or other potential sources of spilled fuels or fuel vapors. Catch fuels in an approved container when removing the fuel line or carburetor.
Combustible materials. A fire can cause severe injury or death.
Generator set engine fuels and fuel vapors are flammable and explosive. Handle these materials carefully to minimize the risk of fire or explosion. Equip the compartment or nearby area with a fully charged fire extinguisher. Select a fire extinguisher rated ABC or BC for electrical fires or as recommended by the local fire code or an authorized agency. Train all personnel on fire extinguisher operation and fire prevention procedures.
Exhaust System
WARNING
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in exhaust gases. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Carbon monoxide poisoning symptoms include but are not limited to the following:
D Light-headedness, dizziness D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate or speak clearly, blurred vision
D Stomachache, vomiting, nausea If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.
Engine Backfire/Flash Fire
WARNING
Fire. Can cause severe injury or death.
Do not smoke or permit flames or sparks near fuels or the fuel system.
Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator
set with the air cleaner removed.
Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide
is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust gas could seep inside or be drawn into a potentially occupied building through windows, air intake vents, or other openings.
TP-6515 10/076 Safety Precautions and Instructions
Page 7
Fuel System
WARNING
Explosive fuel vapors. Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
Gas fuel leaks. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an
explosion. Check the LP vapor gas or natural gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to 6--8 ounces per square inch (10--14 inches water column). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble.
Hazardous Noise
CAUTION
Hazardous Voltage/ Moving Parts
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
WARNING
Hazardous voltage. Backfeed to the utility system can cause property damage, severe injury, or death.
If the generator set is used for standby power, install an automatic transfer switch to prevent inadvertent interconnection of standby and normal sources of supply.
CAUTION
Moving parts.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution
is possible whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turnoff the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Welding on the generator set. Can cause severe electrical equipment damage. Before welding on the
generator set perform the following steps: (1) Remove the battery cables, negative (--) lead first. (2) Disconnect all engine electronic control module (ECM) connectors. (3) Disconnect all generator set controller and voltage regulator circuit board connectors. (4) Disconnect the engine battery­charging alternator connections. (5) Attach the weld ground connection close to the weld location.
Connecting the battery and the battery charger. Hazardous voltage can cause severe injury or death.
Reconnect the battery correctly, positive to positive and negative to negative, to avoid electrical shock and damage to the battery charger and battery(ies). Have a qualified electrician install the battery(ies).
Short circuits. Hazardous
Hazardous noise. Can cause hearing loss.
Never operate the generator set without a muffler or with a faulty exhaust system.
Engine noise. Hazardous noise can cause hearing loss. Generator sets
not equipped with sound enclosures can produce noise levels greater than 105 dBA. Prolonged exposure to noise levels greater than 85 dBA can cause permanent hearing loss. Wear hearing protection when near an operating generator set.
TP-6515 10/07 7Safety Precautions and Instructions
Welding the generator set. Can cause severe electrical equipment damage.
Never weld components of the generator set without first disconnecting the battery, controller wiring harness, and engine electronic control module (ECM).
voltage/current can cause severe injury or death. Short circuits can
cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death. Install
a transfer switch in standby power installations to prevent the connection of standby and other sources of power. Electrical backfeed into a utility electrical system can cause severe injury or death to utility personnel working on power lines.
Page 8
WARNING
Airborne particles. Can cause severe injury or blindness.
Hot Parts
WARNING
Hot engine and exhaust system. Can cause severe injury or death.
Wear protective goggles and clothing when using power tools, hand tools, or compressed air.
Heavy Equipment
WARNING
Unbalanced weight. Improper lifting can cause severe injury or death and equipment damage.
Do not use lifting eyes. Lift the generator set using lifting bars inserted through the lifting holes on the skid.
Do not work on the generator set until it cools.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts.
The engine and exhaust system components become extremely hot during operation.
Servicing the engine heater. Hot parts can cause minor personal injury or property damage. Install the
heater before connecting it to power. Operating the heater before installation can cause burns and component damage. Disconnect power to the heater and allow it to cool before servicing the heater or nearby parts.
Notice
NOTICE
Canadian installations only.For standby service connect the output of the generator set to a suitably rated transfer switch in accordance with Canadian Electrical Code, Part 1.
TP-6515 10/078 Safety Precautions and Instructions
Page 9
Introduction
This manual provides operation and maintenance instructions for model 17RES generator sets equipped with the Kohlerr ADC-RES Advanced Digital Control.
This generator set is approved for use in stationary applications in locations served by a reliable utility power source. Have the generator set installed by an authorized distributor/dealer or service technician. Refer to TP-6514, Installation Manual, for installation instructions.
Information in this publication represents data available at the time of print. The manufacturer may provide this manual for models not listed on the front cover. Kohler Co. reserves the right to change this publication and the products represented without notice and without any obligation or liability whatsoever.
Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury. Read and follow the Safety Precautions and Instructions section at the beginning of this manual. Keep this manual with the equipment for future reference.
Emission Compliance
An engine or generator set with the following identification label is certified to meet Small Off-Road Engine emission standards for EPA/CARB.
This engine/generator is certified to operate using natural gas or propane fuel.
The 17RES generator set engine is certified to meet emission regulations for U.S. EPA phase 2 small off-road engines and CA 2006 and later LSI engines (large spark-ignited engines at or below 1 liter).
The equipment service requirements are very important to safe and efficient operation. Inspect the parts often and perform required service at the prescribed intervals. Obtain service from an authorized service distributor/ dealer to keep equipment in top condition.
Nameplate
The following illustration shows a typical generator set nameplate. Copy the model, serial, and specification numbers from the nameplate into the spaces provided in the product information section on the inside front cover of this manual. See Section 1.5, Service Views, for the nameplate location.
Figure 1 Engine Identification Label
The Emission Compliance Period referred to on the Engine Identification label indicates the number of operating hours for which the engine has been shown to meet EPA emission requirements. The engine compliance period (in hours), associated with the Category A descriptor found on the certification label, is 1000 hours.
Refer to the certification label for engine displacement.
The exhaust emission control system for the CH980 engine is EM.
TP-6515 10/07 9Introduction
Page 10
Service Assistance
For professional advice on generator set power requirements and conscientious service, please contact your nearest Kohler distributor or dealer.
D Consult the Yellow Pages under the heading
Generators—Electric.
D Visit the Kohler Power Systems website at
KohlerPower.com.
D Look at the labels and stickers on your Kohler product
or review the appropriate literature or documents included with the product.
D Call toll free in the US and Canada 1-800-544-2444.
D Outside the US and Canada, call the nearest regional
office.
Headquarters Europe, Middle East, Africa (EMEA)
Kohler Power Systems ZI Senia 122 12, rue des Hauts Flouviers 94517 Thiais Cedex France Phone: (33) 1 41 735500 Fax: (33) 1 41 735501
Asia Pacific
Power Systems Asia Pacific Regional Office Singapore, Republic of Singapore Phone: (65) 6264-6422 Fax: (65) 6264-6455
China
North China Regional Office, Beijing Phone: (86) 10 6518 7950
(86) 10 6518 7951 (86) 10 6518 7952
Fax: (86) 10 6518 7955
East China Regional Office, Shanghai Phone: (86) 21 6288 0500 Fax: (86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office Bangalore, India Phone: (91) 80 3366208
(91) 80 3366231
Fax: (91) 80 3315972
Japan, Korea
North Asia Regional Office Tokyo, Japan Phone: (813) 3440-4515 Fax: (813) 3440-2727
Latin America
Latin America Regional Office Lakeland, Florida, USA Phone: (863) 619-7568 Fax: (863) 701-7131
TP-6515 10/0710 Service Assistance
Page 11
Section 1 Features
1.1 Specifications
The generator set specification sheets provide specific generator and engine information. Refer to the spec sheet for data not supplied in this manual. Consult the generator set service manual, engine operation manual, and engine service manual for additional specifications. Obtain copies of the latest spec sheets, manuals, diagrams, and drawings from your local distributor/ dealer.
1.2 Generator
The generator uses Kohler’s unique PowerBoostt voltage regulation system, which provides instant response to load changes.
PowerBoostt ensures reliable motor starting and consistent voltage levels. PowerBoostt utilizes a voltage excitation system that employs a winding independent of the main output windings to provide excitation voltage.
1.3 Engine
The generator set has a four-cycle, twin cylinder, air­cooled Kohlerr engine. The engine operates on clean­burning natural gas or propane (LP) vapor. Engine features include:
D Efficient overhead valve design and full pressure
lubrication for maximum power, torque, and reliability under all operating conditions.
D Dependable, maintenance-free electronic ignition.
D Precision-formulated cast iron construction of parts
subjected to the most wear and tear.
D Field-convertible multi-fuel systems that allow fuel
changeover from natural gas to LP vapor (and vice-versa) while maintaining CARB emission certification.
D Digital spark advance optimizes ignition timing for the
selected fuel.
1.4 Advanced Digital Control
The generator set is equipped with the Kohlerr ADC-RES Advanced Digital Control. Controller features include the following:
D Compact controller
D Integrally mounted to the generator set
D LED display:
D Engine runtime, hours D AC voltage D Frequency (Hz) D Engine temperature D Battery voltage D Crank cycle status D Setup information D Application software version
D LED display communicates faults:
D High battery voltage D High engine temperature D Low battery voltage D Low oil pressure D Overcrank safety D Overfrequency D Overspeed D Overvoltage D Underfrequency D Undervoltage
D Membrane keypad for configuration and adjustment
D Password-protected user access to menus D Voltage, gain, and speed adjustment D System configuration (system voltage, phase, and
frequency settings, battery voltage, and generator set model)
D Remote two-wire start/stop capability
D Digital isochronous governor to maintain
steady-state speed at all loads
D Digital voltage regulation: ±1.5% RMS no-load to
full-load
D Automatic start for programmed cranking cycle
D Master control switch mounted on the junction box:
Run/Off-Reset/Auto
D Upgradeable application software
TP-6515 10/07 11Section 1 Features
Page 12
1.5 Generator Set Components
17
Control detail, top view
12
11
8
9
10
See control
12 5421
3
6
18
19
20
22
detail
7
23
30
29
24
28
27
25
25
25
1. Muffler
2. Oil check
3. Oil fill
4. Air cleaner
5. Spark plug locations (both sides)
6. Oil filter
7. Oil cooler location
8. ADC-RES Advanced Digital Control user interface
9. Generator set master switch (RUN-OFF/RESET-AUTO)
10. Line circuit breaker
11. Fuses
12. RS-232 connector (for application program updates)
13. Engine starting battery location (battery purchased separately)
14. Oil drain hose
15. Nameplate location (on base)
16. Oil drain valve
16
Figure 1-1 Generator Set Components
13
1415
17. Exhaust outlet
18. Relay board location (optional)
19. Carburetor heater access opening
20. LP fuel orifice location (inside hose fitting)
21. Gas regulator assembly
22. DSAI leads
23. Fuel solenoid valve
24. Fuel inlet
25. Air intake
26. Battery cables
27. Battery charger
28. Field-connection terminal block location (optional)
29. 120 VAC receptacles for battery charger and optional carburetor heater (provided with optional terminal block)
30. Field connections inside junction box if optional terminal block is not used
26
ADV-7341A-B
TP-6515 10/0712 Section 1 Features
Page 13
Section 2 Operation
2.1 Prestart Checklist
To ensure continued satisfactory operation, perform the following checks or inspections before or at each startup, as designated, and at the intervals specified in the service schedule. In addition, some checks require verification after the unit starts.
Air Cleaner. Check for a clean and installed air cleaner element to prevent unfiltered air from entering the engine.
Air Inlets. Check for clean and unobstructed air inlets.
Battery. Check for tight battery connections. Consult
the battery manufacturer’s instructions regarding battery care and maintenance.
Exhaust System. Check for exhaust leaks and blockages. Check the muffler condition and check for tight exhaust system connections.
Inspect the exhaust system components for cracks, leaks, and corrosion.
D Check for corroded or broken metal parts and replace
them as needed.
2.3 ADC-RES Controls and Indicators
Figure 2-1 illustrates the ADC-RES user interface and other items on the generator set junction box. Figure 2-3 describes the ADC-RES controls and indicators.
2
1
6
6
3
4
D Check that the exhaust outlet is unobstructed.
Oil Level. Maintain the oil level at or near, not over, the full mark on the dipstick.
Operating Area. Check for obstructions that could block the flow of cooling air. Keep the air intake area clean. Do not leave rags, tools, or debris on or near the generator set.
2.2 Exercising Generator Set
Operate the generator set without load once each week for 20 minutes. If the generator set is not connected to an automatic transfer switch (ATS) with an exercise option, exercise the unit in the presence of an operator.
The operator should perform all of the prestart checks before starting the exercise procedure. Start the generator set according to the starting procedure in the controller section of this manual. While the generator set is operating, listen for a smooth-running engine and visually inspect the generator set for fluid or exhaust leaks. Check the air inlets and outlets and remove any items restricting the air flow.
5
1. Select button (use for setup and adjustment only)
2. LED display
3. Up and down arrow buttons
4. Generator set master switch
5. Line circuit breaker
6. Fuses
7. RS-232 connector (for application program upgrade)
xxx
Figure 2-1 ADC-RES Controls
2.3.1 LED Display
The LED display is activated by a start or RUN command as follows:
D Move the master switch to RUN.
D With the master switch in AUTO, send a remote start
command (close the remote start contact across leads 3 and 4).
The LED display indicates generator set status as shown in Figure 2-3. When the generator set is running, engine runtime hours are shown unless the arrow
TP-6515 10/07 13Section 2 Operation
Page 14
buttons are used to step through the other displays as described in Section 2.3.2.
When the master switch is in AUTO, the display turns off 48 hours after generator set shutdown. See Section 2.4.
2.3.3 Generator Set Master Switch
The generator set master switch is located on the junction box below the ADC-RES user interface. The master switch positions are RUN, OFF/RESET, and AUTO. See Section 2.5 for operation instructions.
2.3.2 Controller Keypad
The three buttons on the controller keypad are Select, Up, and Down.
When the generator set is running, the up and down arrow buttons can be used to step through system data displays as shown in Figure 2-2. After 10 seconds, the display returns to engine runtime hours.
The buttons on the controller keypad are also used for system configuration and adjustment. The system configuration is factory-set and should not require changes under normal operating conditions. Contact an authorized distributor/dealer or service technician if adjustments are required.
Control or Indicator Item Description
LED display
Keypad Select and arrow
Generator set master switch
Runtime hours Displays total generator set runtime hours while the generator set is running and when no
Metering display Displays AC voltage (output), frequency, and battery voltage. Press the up or down arrow
Crank indication Displays CC_1, CC_2, or CC_3 to indicate the first, second, or third attempt to start the
Software version number
Fault codes Flashes a 2- or 3-letter fault code to indicate various fault conditions. See Section 2.6.
buttons
Three-position switch
other codes are displayed.
when runtime hours are displayed to step through these displays.
engine. The last digit flashes during the crank cycle rest periods.
The software version number (v#.##) is displayed when entering configuration mode. See the Installation Manual.
Use the arrow buttons to step through the data displays. See Figure 2-2.
The keypad is also used for controller setup and adjustment. The setup and adjustment functions are password-protected. Have setup and adjustments performed only by an authorized distributor/dealer.
Switch functions as the generator set operation and controller reset switch.
Engine Runtime
XXX.X hours
Output Voltage
VAC
Output Frequency
Hz
Battery Voltage
VDC
tp6515
1. Generator set master switch in AUTO
2. Step through using up or down arrow buttons
3. After 10 seconds, display returns to runtime hours
Figure 2-2 Data Displays
Figure 2-3 ADC-RES Controls and Indicators
TP-6515 10/0714 Section 2 Operation
Page 15
2.4 Controller Power
The ADC-RES is powered by the generator set engine starting battery.
Note: The generator sets are equipped with factory-
installed battery chargers to prevent battery discharge. The battery charger must be connected to 120 VAC.
2.4.1 Standby Mode
When the generator set master switch is in the AUTO position, the controller is in standby mode. Engine runtime hours are shown on the display. A remote start signal (contact closure) will start and run the generator set.
If there is no start signal for 48 hours, the controller goes into sleep mode.
Crank Cycle
The controller attempts to start the generator set three times (three crank cycles, 15 seconds crank and 15 seconds off). See Figure 2-3 for display information during the crank cycle. If the generator set does not start in three attempts, the system shuts down on an overcrank fault. See Section 2.6.
2.5.2 Stopping Generator Set
Local Stopping
1. Run the generator set with no load for at least 2 minutes to ensure adequate engine cooldown.
2. Move the generator set master switch to the OFF/RESET position. The engine stops.
Automatic Stopping
2.4.2 Sleep Mode
When the generator set master switch is in the AUTO position, the controller powers down automatically if there is no start signal for 48 hours after shutdown. The controller display is dark and battery draw is minimized. A remote start signal (from a transfer switch or a remote start/stop switch connected to controller leads 3 and 4) reactivates the controller. Moving the generator set master switch to the RUN position also activates the controller.
2.5 Generator Set Operation
2.5.1 Starting Generator Set
Local Starting
Move the generator set master switch to the RUN position to immediately start the generator set.
Auto (Automatic) Starting
With the generator set master switch in the AUTO position, open the contact across engine start leads 3 and 4 to signal the generator set to stop.
An automatic transfer switch (ATS) connected to controller leads 3 and 4 operates as follows:
1. The ATS disconnects the load from the generator set.
2. If the ATS is equipped with an engine cooldown time delay, the generator set continues to run for a preset engine cooldown time.
Note: There is no engine cooldown time delay on
the ADC-RES controller.
3. The ATS opens the connection between controller leads 3 and 4. The generator set shuts down. The controller enters standby mode and displays engine runtime hours.
Move the generator set master switch to the AUTO position to allow startup by an automatic transfer switch (ATS) or remote start/stop switch, if equipped. Close a contact across engine start leads 3 and 4 to signal the controller to start the generator set.
TP-6515 10/07 15Section 2 Operation
Page 16
2.6 Faults
Use the following procedure to reset the generator set controller after a fault shutdown.
2.6.1 Shutdowns
Under the fault shutdown conditions listed in Figure 2-4, the generator set shuts down automatically and the controller displays a fault code. The generator set cannot be restarted until the fault condition is corrected and the controller is reset. See Section 2.6.3 to reset the controller after a fault shutdown.
The shutdown switches on the generator set will automatically reset when the problem is corrected. For example, the high engine temperature switch resets automatically when the generator set cools. However, the fault does not clear until the controller is reset.
2.6.2 Warnings
The controller displays a fault code but the generator set does not shut down on a high battery voltage warning or a low battery voltage warning. The controller resets automatically after a battery voltage fault condition is corrected.
2.6.3 Resetting Controller after a Fault Shutdown
Always identify and correct the cause of a fault shutdown before resetting the controller. Check the fault code displayed on the ADC-RES and refer to Figure 2-4 to identify and correct the fault condition before proceeding.
1. Move the generator set master switch to OFF/RESET.
2. Disconnect the generator set from the load using the line circuit breaker or ATS. See the safety precautions at the beginning of this manual before proceeding.
3. Identify and correct the cause of the fault shutdown. See the safety precautions at the beginning of this manual before proceeding. Refer to Section 4, Troubleshooting.
4. Start the generator set by moving the generator set master switch to RUN. Test operate the generator set to verify that the cause of the shutdown has been corrected.
5. Move the generator set master switch to OFF/RESET.
6. Reconnect the generator set to the load using the line circuit breaker or ATS.
7. Move the generator set master switch to the AUTO position for startup by remote transfer switch or remote start/stop switch.
Note: The controller’s LED display remains off
until an engine start command is received.
TP-6515 10/0716 Section 2 Operation
Page 17
Code Fault Description Check
Checkforlooseconnection
s
AF Auxiliary fault
input shutdown
HE High engine
temperature shutdown
LOP Low oil pressure
shutdown
Overcrank
OC
shutdown
Locked rotor The generator set also shuts down on OC if no engine rotation is
OF Overfrequency
shutdown
OS Overspeed
shutdown
OU Overvoltage
shutdown
UF Underfrequency
shutdown
UU Undervoltage
shutdown
HB High battery
voltage warning
LB Low battery
voltage warning
Not used.
Shutdown occurs if the engine coolant temperature exceeds the maximum temperature for more than 5 seconds. This protective becomes active after the engine reaches the crank disconnect speed.
Shutdown occurs if a low oil pressure condition exists for more than 5 seconds. This protective becomes active 30 seconds after the engine has reached crank disconnect speed (30 second inhibit).
Note: The low oil pressure shutdown does not protect against low oil level. Check the oil level at the engine.
Shutdown occurs after 3 unsuccessful starting attempts. The crank cycle is set for three starting attempts of 15 seconds cranking and 15 seconds rest.
sensed during cranking. Shuts down 3 seconds after the fault is detected.
Shutdown occurs when the governed frequency exceeds 110% of the system’s frequency setpoint for more than 5 seconds. This protective becomes active 10 seconds after engine start (10 second inhibit).
Shutdown occurs if the engine speed exceeds 110% of the normal running speed for more than 0.3 seconds.
Shutdown occurs if the voltage exceeds 120% of the system nominal voltage for more than 2 seconds.
Shutdown occurs if the governed frequency falls below 54 Hz for more than 5 seconds.
Shutdown also occurs if the governed frequency falls below
56.5 Hz for more than 60 seconds.
This protective becomes active 10 seconds after engine start. (10 second inhibit).
Shutdown occurs if the voltage falls below 80% of the nominal system voltage for more than 10 seconds.
Fault code is displayed if the engine starting battery voltage rises above 16 VDC for more than 30 seconds when the engine is running. Not operative during the engine crank cycle, this fault condition does not inhibit engine starting.
The fault condition clears when the battery voltage returns to an acceptable level.
Fault code is displayed if the engine starting battery voltage falls below 11 VDC for more than 30 seconds when the engine is not running. Not operative during the engine crank cycle, this fault condition does not inhibit engine starting.
The fault condition clears when the battery voltage returns to an acceptable level.
Check for blocked air inlets and exhaust outlets.
Check for leaks in the lubrication system.
Check the oil level and add oil if the level is low.
Check the fuel supply, spark plug, and battery.
Contact an authorized distributor/dealer for service if problem continues.
Contact an authorized distributor/dealer for service if problem continues.
Contact an authorized distributor/dealer for service if problem continues.
Contact an authorized distributor/dealer for service if problem continues.
Reduce the load and restart the generator set.
Contact an authorized distributor/dealer for service if problem continues.
Reduce the load and restart the generator set.
Contact an authorized distributor/dealer for service if problem continues.
Check the battery rating and condition.
Check the battery charger operation.
Check the battery rating and condition.
Check the battery charger operation.
Charge or replace the battery.
.
Figure 2-4 ADC-RES Fault Codes
TP-6515 10/07 17Section 2 Operation
Page 18
2.7 Battery Charger
The generator set is equipped with a 6-amp float/equalize battery charger to maintain the engine starting battery. The charger’s power cord must be connected to a 120 VAC power source. Figure 2-5 illustrates the battery charger.
The battery charger uses an AGS 10 inline fuse. The fuse is located in the battery lead. See Figure 2-5.
1
INDICATOR Red:
VOLTS=11.8--14.0 AMPS=5.0--6.0
Red& Green:
VOLTS=14.0--14.5 AMPS=1.5--5.0
Green:
VOLTS=13.0--13.6 AMPS=0.1--1.5
CAUTION:Toreduce the riskof elect rical shock,
connectonly to properly grounded outlet.
INPUT:115 VAC50/60Hz @ 1.6A
OUTPUT:12 VDC @6 Amps
MAX.BAT.: 180Amp Hr. Max.
DATE:
AllowableBattery Types:Lead Acida nd GelCell
4
6AMP AUTOMATIC BATTERYCHARGER
R
C USLISTED
BATTERYCHARGER
53AB
2608KH
2
3
1. LED indicators
2. AC power cord
3. Fuse
4. Battery leads, 12 VDC
Figure 2-5 6-Amp Float/Equalize Battery Charger
2.7.1 Battery Charger Operation
Figure 2-6 Charging Method
Display Operating Condition
Red ON Green OFF
Red ON Green ON
Red OFF Green ON
When the red LED is on, it indicates the battery is discharged and the battery charger is recharging at the BULK rate (stage 1). This charging rate is 6 amps. While the red LED is on, the voltage measured (with the battery charger on) will be
11.8--14 volts.
If the red LED stays on for more than 24 hours, refer to Section 4.4 in this manual.
When both the green and the red LEDs are on, the battery charger is charging at an ABSORPTION rate of between 1.5 and 5 amps (stage 2). This mode of charging gradually tops off your battery, and reduces harmful sulfating. While both LEDs are on, the voltage measured (with the battery charger on) should be approximately
14.0--14.5 VDC.
If both LEDs stay on longer than 24 hours, refer to Section 4.4 in this manual.
When the green LED is on, the battery charger is charging at a FLOAT or MAINTENANCE rate of less than 1.5 amps (stage 3). Your battery is now 90% charged and ready for use. This float charging current will gradually decrease to as low as 0.1 amps as the battery reaches 100% charge. It will now be kept at full charge without overcharging.
If the green LED stays on when your battery is known to be low, refer to Section 4.4 in this manual.
Figure 2-6 illustrates the three-stage charging method. Red and green LEDs indicate charger operation. The chart in Figure 2-7 describes the LED indicator operation during each stage of the charging process.
Figure 2-7 Battery Charger LED Indicator Functions
TP-6515 10/0718 Section 2 Operation
Page 19
Section 3 Scheduled Maintenance
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
WARNING
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Servicing the generator set when it is operating. Exposed moving parts can cause severe injury or death. Keep
hands, feet, hair, clothing, and test leads away from the belts and pulleys when the generator set is running. Replace guards, screens, and covers before operating the generator set.
Moving parts.
3.1 Routine Maintenance
Refer to the following service schedule and the runtime hours displayed on the ADC-RES display to schedule routine maintenance. Intervals are shown in hours of operation and/or time intervals (i.e. weekly, monthly, quarterly, etc.) Have an authorized distributor/ dealer service the generator set at the designated intervals in the service schedule for the life of the generator set. Service units subject to extreme weather, long operating hours, or dusty or dirty conditions more frequently.
Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts. The
engine and exhaust system components become extremely hot during operation.
Contact an authorized distributor/dealer for parts.
TP-6515 10/07 19Section 3 Scheduled Maintenance
Page 20
3.2 Service Schedule
Procedure
See
System Component or Procedure
Section
Fuel
Flexible lines and connections Q R
Main tank supply level W
Fuel piping Y
Lubrication
Oil level 3.3.2 8orE
Change oil 3.3.4 Yor150
Replace filter 3.3.4 Yor150
Crankcase breather hose Yor500
Oil cooler 3.3.5 Y Yor100
Cooling
Air ducts, louvers Y Y
Exhaust System
Leakage W W
Insulation, fire hazards Y
Obstructions or combustible materials near exhaust outlet W
DC Electrical System
Battery charger operation, charge rate M
Remove corrosion, clean and dry battery and rack Y Y
Clean and tighten battery terminals and inspect boots Y Y
Battery electrolyte level and specific gravity * Y
3.3
3.6
3.7
3.8
AC Electrical System
Tighten control and power wiring connections Y
Remote control system, if equipped M
Visible wear or damage Q
Wire abrasions where subject to motion 6 months 6 months
Wire-cable insulation condition 3Y or 500
Engine and Mounting
Visible wear or damage W
Air cleaner service [
Spark plugs 3.4 150 300
Replace stepper motor coupling and bushing S/M 500 (D)
3.5 150 300
Generator
Visible wear or damage 2.1 Q
Exercise generator set 2.2 W
Brushes and collector ring S/M Y(D) Y(D)
Measure and record resistance readings of windings with insulation tester (Meggerr, with SCR assembly or rectifier and load leads disconnected)
S/M 3Y (D)
General Condition of Equipment
Evidence of vibration, leakage, deterioration, unusual or excessive noise or temperature
Interior of sound enclosure Q Q
* Not necessary for maintenance-free batteries. [ Service more frequently under extremely dusty/dirty conditions. Meggerr is a registered trademark of Biddle Instruments.
EEachuse W Weekly M Monthly Q Quarterly Y Yearly
Visually
Inspect
W W W
Check Change Clean Test
Number = hours of operation D Authorized distributor/dealer only R Replace as necessary S/M Service Manual
TP-6515 10/0720 Section 3 Scheduled Maintenance
Page 21
3.3 Lubrication System
See Section 3.2, Service Schedule, for oil change and oil filter replacement intervals. See Section 1.5, Service Views, for the oil drain, oil check, oil fill, and oil filter locations.
3.3.1 Low Oil Pressure Shutdown
The low oil pressure (LOP) shutdown feature protects the engine against internal damage if the oil pressure drops below a minimum pressure because of oil pump failure or other malfunction.
Note: The LOP shutdown feature does not protect
against damage caused by operating when the oil level is low; it is not a low oil level shutdown. Check the oil level regularly, and add oil as needed.
3.3.2 Oil Check
The generator set is shipped with oil. Before operating the generator set, check the engine oil in the crankcase. See Figure 3-1 for the dipstick location.
Maintain the oil level at or near, not over, the full mark on the dipstick. Add 5W-30 synthetic oil when the oil level is low. See Section 3.3.3, Engine Oil Recommendation.
Check the oil level before each use. For extended operation, check the oil level every 8 hours. Do not check the oil level when the generator set is running. Shut down the generator set and wait several minutes before checking the oil.
and thickens less than other oils and leaves the engine intake valves and pistons cleaner.
3.3.4 Oil Change Procedure
Note: Dispose of all waste materials (engine oil, fuel,
filter, etc.) in an environmentally safe manner.
Drain the oil while it is still warm.
1. Drain the oil.
a. Place the generator set master switch in the
OFF position.
b. Disconnect the power to the battery charger.
c. Disconnect the generator set engine starting
battery, negative (--) lead first.
d. Remove the housing side panel.
e. Clean the area around the dipstick and oil fill
cap.
f. Remove the oil drain hose from its retaining
clip. Remove the cap from the oil drain hose and lower the hose into an oil collection container.
g. Open the oil drain valve on the engine.
h. Remove the dipstick and oil fill cap. Allow time
for the engine oil to drain completely.
i. Close the oil drain valve. Replace the cap on
the oil drain hose. Replace the oil drain hose in its retaining clip.
j. Replace the dipstick.
2. Replace the oil filter.
a. Clean the area around the oil filter. Remove the
oil filter by rotating it counterclockwise with an oil filter wrench.
b. Clean the gasket sealing surface of the oil filter
adapter.
c. Apply a light coat of clean oil to the rubber seal
of the new oil filter.
6515
Figure 3-1 Oil Check
d. Install the new oil filter following the instructions
provided with the filter.
3.3.3 Engine Oil Recommendation
Use 5W-30 API (American Petroleum Institute) Service Class SG, SH, or SJ synthetic oil. Synthetic oil oxidizes
TP-6515 10/07 21Section 3 Scheduled Maintenance
Page 22
3. Fill with oil.
a. Fill the engine to the F mark on the dipstick.
The engine oil capacity is approximately 2.8 L (3.0 qt.). See Section 3.3.3, Engine Oil Recommendation, for oil selection.
b. Reinstall the dipstick and the oil fill cap.
Clean the outside of the oil cooler fins with a brush or with compressed air.
3.4 Spark Plugs
Reset the spark plug gap or replace the plugs with new plugs as necessary.
c. Check that the generator set master switch is in
the OFF position.
d. Reconnect the generator set engine starting
battery, negative (--) lead last.
e. Reconnect the power to the battery charger.
f. Start and run the generator set for a minute to
allow the oil pressure to reach operating range.
g. Stop the generator set, wait 1 minute, and then
recheck the oil level. Add oil to bring the level up to the F mark on the dipstick.
4. Check for leaks.
a. Check for oil leaks.
b. Fix leaks and recheck the oil level.
c. Reinstall the housing side panel.
3.3.5 Oil Cooler
Inspect and clean the oil cooler at the intervals indicated in the service schedule. The oil cooler must be kept free of debris.
1. Clean the area around the base of the spark plug to keep dirt and debris out of the engine.
2. Remove the spark plug and check its condition. Replace the spark plug if it is worn or if its reuse is questionable.
3. Check the spark plug gap using a wire feeler gauge. Adjust the gap to 0.76 mm (0.030 in.) by carefully bending the ground electrode. See Figure 3-3 and Figure 3-4.
4. Reinstall the spark plug into the cylinder head. Torque the spark plug to 24.4--29.8 Nm (18--22 ft. lb.)
1--514
Figure 3-3 Checking the Spark Plug Gap
See Figure 3-2 for the oil cooler location. The oil cooler is located under the No. 2 cylinder shroud. Remove the top mounting screw and loosen the two side screws, then lift off the cylinder shroud.
1. Oil cooler
1
62 590 01
Figure 3-2 Oil Cooler Location
1--511
Figure 3-4 Adjusting the Spark Plug Gap
TP-6515 10/0722 Section 3 Scheduled Maintenance
Page 23
3.5 Air Cleaner Service
The engine is equipped with a replaceable, high density paper air cleaner element. See Figure 3-5.
1
Kohler element. Handle new elements carefully; do not use if the sealing surfaces are bent or damaged.
4. When servicing the air cleaner, check the air cleaner base and latch. Make sure it is secured and not bent or damaged. Also, check the element cover for damage or improper fit. Replace all damaged air cleaner components.
2
3
4
tp6515
1. Knobs (qty.2)
2. Cover
3. Paper element
4. Air filter latch
Figure 3-5 Air Cleaner Components
Check the air cleaner daily or before starting the engine. Check for a buildup of dirt and debris around the air cleaner system. Keep this area clean. Also check for loose or damaged components. Replace all bent or damaged air cleaner components.
Note: Operating the engine with loose or damaged air
cleaner components could allow unfiltered air into the engine causing premature wear and failure.
Note: If any loose dirt or debris fell on the air cleaner
base when the element was removed, carefully remove it and wipe the base clean. Be careful that none of it drops into the intake throat.
5. Reinstall the paper element onto the air cleaner base. Make sure the element is flat and properly seated. Rotate the latch clockwise, over the molded lip on the element.
6. Install the air cleaner cover and secure with the two retaining knobs.
7. When element replacement is necessary, order genuine Kohler parts.
3.6 Cooling System
The engine fan draws cooling air through the openings in the sides and end near the battery. The alternator fan draws cooling air through openings on the side walls of the enclosure. The cooling air mixes with the engine exhaust and is discharged at the exhaust outlet. See Figure 3-6. To prevent generator set damage caused by overheating, keep the housing cooling inlets and outlets clean and unobstructed at all times.
Note: Do not block the generator set cooling air inlets or
mount other equipment above them. Overheating and severe generator damage may occur.
Paper Element Service
Replace the paper element at the intervals indicated in the service schedule. See Section 3.2 for the service schedule. See Figure 3-5 for the air cleaner components.
1. Loosen the two cover retaining knobs and remove the cover.
2. Rotate the air filter latch counterclockwise to unlock, then remove the paper element.
3. Do not wash the paper element or use pressurized air, as this will damage the element. Replace a dirty, bent, or damaged element with a genuine
TP-6515 10/07 23Section 3 Scheduled Maintenance
1
2
1. Exhaust outlet
2. Alternator air intake (both sides)
3. Engine air intake
Figure 3-6 Cooling Air Intake and Exhaust
3
3
tp6195
Page 24
3.7 Exhaust System
Remove all combustible materials from the exhaust location. Combustible materials include building materials as well as natural surroundings. Keep dry field grass, foliage, and combustible landscaping material a minimum of 1.5 m (5 ft.) from the exhaust outlet.
Periodically inspect the exhaust system components for cracks, leaks, and corrosion.
D Check for corroded or broken metal parts and replace
them as needed.
D Check that the exhaust outlet is clear.
3.8 Battery
WARNING
Sulfuric acid in batteries. Can cause severe injury or death.
Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid can cause
blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid.
Battery gases. Explosion can cause severe injury or death. Battery gases can cause an explosion. Do not smoke
or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases.
Battery short circuits. Explosion can cause severe injury or death. Short circuits can cause bodily injury and/or
equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Refer to this section for general battery information and maintenance. Also consult the battery manufacturer’s instructions for battery maintenance.
All generator set models use a negative ground with a 12-volt engine electrical system. Consult the generator set nameplate for the engine electrical system voltage. Consult the generator spec sheet for battery capacity recommendations for replacement purposes. Wiring diagrams provide battery connection information. See Figure 3-7 for typical battery connections.
1
2
Battery acid cleanup. Battery acid can cause severe injury or death. Battery acid is electrically conductive and
corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a container with 4 L (1 gal.) of water and mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area.
EZ-273000-J
1. To positive (+) terminal on starter solenoid.
2. To ground (--) terminal on or near starter motor.
Figure 3-7 12-Volt Engine Electrical System Single
Starter Motor, Typical Battery Connection
TP-6515 10/0724 Section 3 Scheduled Maintenance
Page 25
Clean the battery and cables and tighten battery terminals using the service schedule recommendations. To prevent corrosion, maintain tight, dry electrical connections at the battery terminals. To remove corrosion from battery terminals, disconnect the cables from the battery and scrub the terminals with a wire brush. Clean the battery and cables with a solution of baking soda and water. After cleaning, flush the battery and cables with clean water and wipe them with a dry, lint-free cloth.
After reconnecting the battery cables, coat the battery terminals with petroleum jelly, silicone grease, or other nonconductive grease.
3.9 Battery Charger
3.10 Circuit Protection
If the generator set circuit breaker trips or the fuses blow repeatedly, see Section 4, Troubleshooting, for possible causes.
3.10.1 Line Circuit Breaker
A line circuit breaker interrupts the generator output in the event of a fault in the wiring between the generator and the load. The line circuit breaker location is shown in Figure 1-1. The circuit breaker rating is shown in Figure 3-9. If the circuit breaker trips, reduce the load and switch the breaker back to the ON position. With the breaker in the OFF position the generator set runs but the generator output is disconnected from the load.
The generator set is equipped with a 6-amp float/equalize battery charger to maintain the engine starting battery. Figure 3-8 illustrates the battery charger.
The charger’s DC leads are factory-wired. Periodically tighten all connections.
1
2
INDICATOR Red:
VOLTS=11.8--14.0 AMPS=5.0--6.0
Red& Green:
VOLTS=14.0--14.5 AMPS=1.5--5.0
Green:
VOLTS=13.0--13.6 AMPS=0.1--1.5
CAUTION:Toreduce the riskof elect rical shock,
connectonly to properly gr ounded outlet.
INPUT:115 VAC50/60Hz @ 1.6A
OUTPUT:12 VDC @6 Amps
MAX.BAT.: 180Amp Hr. Max.
DATE:
AllowableBattery Types:Lead Acida ndGel Cell
6AMP AUTOMATIC BATTERYCHARGER
R
C USLISTED
BATTERYCHARGER
53AB
2608KH
5
4
2
3
Model Circuit Breaker Rating, Amp
17RES 70
Figure 3-9 Line Circuit Breaker Rating
3.10.2 Fuses
Three panel-mounted fuses protect the alternator and electrical controls. See Section 1.5 for fuse locations. Another 10-amp fuse protects the battery charger. See Figure 3-8 for the battery charger fuse location.
See Figure 3-10 for fuse part numbers. Always identify and correct the cause of a blown fuse before restarting the generator set. Refer to Section 4, Troubleshooting, for conditions that may indicate a blown fuse. Replace blown fuses with identical replacement parts.
Fuse Rating, Amp Label Part Number
Auxiliary winding 20 F1 292937
Relay interface board 10 F2 223316
Controller 10 F3 223316
Battery charger 10 AGS 10
1. LED indicators
2. Mounting flanges
4. Fuse
5. Battery leads, 12 VDC
3. AC power cord
Figure 3-8 6-Amp Float/Equalize Battery Charger
TP-6515 10/07 25Section 3 Scheduled Maintenance
Figure 3-10 Fuses
Page 26
3.11 Storage Procedure
3.11.3 Cylinder Lubrication
Perform the following storage procedure before removing the generator set from service for three months or longer. Follow the engine manufacturer’s recommendations for storage, if available.
Note: Run the generator set monthly whenever
possible.
3.11.1 Lubricating System
1. Operate the generator set until it reaches operating temperature, or about 15 minutes.
2. Stop the generator set.
3. While the engine is still warm, drain the engine lubrication oil from the engine crankcase.
4. Refill the engine crankcase with oil. See Section
3.3.3 for oil recommendations.
5. Run the generator set for a few minutes to distribute the clean oil.
6. Stop the generator set.
3.11.2 Fuel System
1. Start the generator set.
1. Remove the spark plugs.
2. Pour one tablespoon of engine oil into each spark plug hole. Install the spark plugs and ground the spark plug leads. Do not connect the leads to the
plugs.
3. Toggle the generator set master switch to crank the engine two or three revolutions to lubricate the cylinders.
3.11.4 Exterior Preparation
1. Clean the exterior surface of the generator set.
2. Seal all openings in the engine with nonabsorbent adhesive tape.
3. Mask all areas to be used for electrical contact.
4. Spread a light film of oil over unpainted metallic surfaces to prevent rust and corrosion.
3.11.5 Battery
Perform battery storage last.
1. Place the generator set master switch in the OFF/ RESET position.
2. With the generator set running, shut off the gas supply.
3. Run the generator set until the engine stops.
4. Place the generator set master switch in the OFF/ RESET position.
2. Disconnect the battery, negative (--) lead first.
3. Clean the battery.
4. Place the battery in a warm, dry location.
5. Connect the battery to a float/equalize battery charger, or charge the battery monthly using a trickle charger. Follow the battery charger manufacturer’s recommendations.
TP-6515 10/0726 Section 3 Scheduled Maintenance
Page 27
Section 4 Troubleshooting
4.1 Introduction
Use the following charts to diagnose and correct common problems. First check for simple causes such
4.2 Controller Troubleshooting
Figure 4-1 contains troubleshooting, diagnostic, and
repair information for the ADC-RES controller. as a dead engine starting battery, loose connections, or an open circuit breaker. The charts include a list of common problems, possible causes of the problem, and recommended corrective actions.
If the procedures in this manual do not explain how to correct the problem, contact an authorized distributor/ dealer. Maintain a record of repairs and adjustments performed on the equipment. Use the record to help describe the problem and repairs or adjustments made to the equipment.
Problem Possible Cause Corrective Action
Controller LED displayisoff
No power to the controller:
The generator set has not run for 48 hours or longer and the controller has powered down.
Controller fuse (F3) is blown. Replace the fuse. If the fuse blows again, contact the
Low or no battery voltage. Check connections.
Generator set master switch is in the OFF/RESET position.
Generator set master switch in AUTO but no start command has been received since last controller reset.
Controller display will automatically activate when a remote start command is received or the generator set master switch is moved to the RUN position. See Section 2.4.
distributor/dealer.
Check generator set battery and battery charger. See Figure 4-2.
Move generator set master switch to the AUTO or RUN position. In AUTO, the display will not turn on until the first start command is received.
Controller display will activate when a remote start command is received or the generator set master switch is moved to the RUN position. Use the remote switch to start generator set and activate the controller display, if desired. See Section 2.3.1.
Figure 4-1 ADC-RES Troubleshooting Chart
TP-6515 10/07 27Section 4 Troubleshooting
Page 28
4.3 Generator Set Troubleshooting
g
a
t
erratically
.
p
p
If a fault code is displayed, identify and correct the cause
of the fault condition. Then reset the controller. See Figure 4-2 contains generator set troubleshooting,
Section 2.6.3. diagnostic, and repair information. Check for loose connections before replacing parts.
Fault Codes
The Advanced Digital Control displays fault codes to aid in troubleshooting. Fault codes, descriptions, and recommended actions are listed in Section 2.6.
Problem Possible Cause Corrective Action
The generator set does not crank.
The generator set cranks but does not start, starts hard, lacks power, or oper erratically.
No AC output.
Low output or excessive drop in voltage.
Generator set stops suddenly.
es
Fault shutdown Check for a fault code on the controller display. See
Battery weak or dead Check power to the battery charger.
Battery charger fuse blown Replace the fuse. Contact an authorized distributor/dealer
Battery connections reversed or poor Check the connections.
Fuse F2 blown Replace the fuse. Contact an authorized distributor/dealer
Fuse F3 blown Replace the fuse. Contact an authorized distributor/dealer
Generator set master switch in the OFF position Move the master switch to AUTO for remote start or to
Air cleaner clogged Clean and/or replace the air cleaner.
Battery weak or dead Check power to the battery charger.
Battery connection poor Clean and tighten the battery connections.
Spark plug wire connection loose Check the spark plug wires.
Low oil pressure shutdown Check the oil level.
Fuel pressure insufficient Check the fuel supply and valves.
Engine malfunction Contact the distributor/dealer.
AC circuit breaker in the OFF position Place the circuit breaker in the ON position.
AC circuit breaker tripping because of overload Reduce the load on the generator set.
AC circuit breaker tripping because of short circuit Contact an authorized distributor/dealer for service.
Auxiliary winding fuse (F1) blown Replace the fuse. Contact an authorized distributor/dealer
Generator set overloaded Reduce the load.
Low oil pressure shutdown Check the oil level.
Outoffuel Check fuel supply.
Overcrank shutdown Reset the controller. If the overcrank fault occurs again,
Controller fuse (F3) blown Replace the fuse. If the fuse blows again, contact the
Overspeed shutdown Reset the controller. If the overspeed fault occurs again,
Generator set master switch in the OFF/RESET position
Remote stop command received from a remote switch or ATS
Engine malfunction Contact the distributor/dealer.
Auxiliary winding fuse (F1) blown Replace the fuse. Contact an authorized distributor/dealer
Section 2.6.
Recharge or replace the battery.
for service if fuse blows repeatedly.
for service if fuse blows repeatedly.
for service if fuse blows repeatedly.
RUN for local start.
Recharge or replace the battery.
for service if fuse blows repeatedly.
contact the distributor/dealer.
distributor/dealer.
contact the distributor/dealer.
Move the switch to the correct position (RUN or AUTO).
Check the remote switch position.
for service if fuse blows repeatedly.
Figure 4-2 General Troubleshooting Chart
TP-6515 10/0728 Section 4 Troubleshooting
Page 29
4.4 Battery Charger
y
y
24h
y
a
batteryisknow
n
LEDsturno
n
Troubleshooting
Use the battery charger’s LED indicators and the table in Figure 4-3 to troubleshoot battery charger operation problems.
Problem Cause Solution
Red LED stays on for more than 24 hours
Red and green LEDs stay on for more than
ours
Green LED stays on when the
tteryis known
b to be low
Neither of the LEDs turn on when the AC power is applied
One or more inoperative or damaged cells. Load test the battery and replace, if necessary
Battery charger has reduced its output voltage below the normal level due to a DC overload or a DC short.
Onboard DC systems are drawing more current than the battery charger can replace.
Onboard DC systems are drawing between 1.5 and 5amps.
One or more inoperative or damaged cells. Load test the battery and replace, if necessary
Extremely low AC voltage at the battery charger. Apply a higher AC voltage source or reduce the length of the
Open DC output fuse. Replace AGS-10 fuse.
Faulty or contaminated terminal connections. Clean and tighten or repair all terminal connections.
One or more inoperative or damaged cells. Load test the battery and replace, if necessary.
No AC power available at the battery charger. Connect AC power or reset the AC breaker on the main panel.
Component failure. Replace battery charger.
Remove the source of the overload or short. Disconnect the battery charger’s black (NEGATIVE) ring terminal from the battery. Reapply AC power and the green LED only should now light.
Turn off all DC equipment while charging.
Turn off all DC equipment while charging.
extension cord.
Figure 4-3 Battery Charger Troubleshooting
TP-6515 10/07 29Section 4 Troubleshooting
Page 30
Notes
TP-6515 10/0730 Section 4 Troubleshooting
Page 31
Appendix A Abbreviations
The following list contains abbreviations that may appear in this publication.
A, amp ampere ABDC after bottom dead center AC alternating current A/D analog to digital ADC advanced digital control;
adj. adjust, adjustment ADV advertising dimensional
Ah amp-hour AHWT anticipatory high water
AISI American Iron and Steel
ALOP anticipatory low oil pressure alt. alternator Al aluminum ANSI American National Standards
AO anticipatory only APDC Air Pollution Control District API American Petroleum Institute approx. approximate, approximately AQMD Air Quality Management District AR as required, as requested AS as supplied, as stated, as
ASE American Society of Engineers ASME American Society of
assy. assembly ASTM American Society for Testing
ATDC after top dead center ATS automatic transfer switch auto. automatic aux. auxiliary avg. average AVR automatic voltage regulator AWG American Wire Gauge AWM appliance wiring material bat. battery BBDC before bottom dead center BC battery charger, battery
BCA battery charging alternator BCI Battery Council International BDC before dead center BHP brake horsepower blk. black (paint color), block
blk. htr. block heater BMEP brake mean effective pressure bps bits per second br. brass BTDC before top dead center Btu British thermal unit Btu/min. British thermal units per minute C Celsius, centigrade cal. calorie CAN controller area network CARB California Air Resources Board CB circuit breaker cc cubic centimeter CCA cold cranking amps ccw. counterclockwise CEC Canadian Electrical Code cert. certificate, certification, certified cfh cubic feet per hour
analog to digital converter
drawing
temperature
Institute
Institute (formerly American Standards Association, ASA)
suggested
Mechanical Engineers
Materials
charging
(engine)
cfm cubic feet per minute CG center of gravity CID cubic inch displacement CL centerline cm centimeter CMOS complementary metal oxide
cogen. cogeneration com communications (port) coml commercial Coml/Rec Commercial/Recreational conn. connection cont. continued CPVC chlorinated polyvinyl chloride crit. critical CRT cathode ray tube CSA Canadian Standards
CT current transformer Cu copper cUL Canadian Underwriter’s
CUL Canadian Underwriter’s
cu. in. cubic inch cw. clockwise CWC city water-cooled cyl. cylinder D/A digital to analog DAC digital to analog converter dB decibel dB(A) decibel (A weighted) DC direct current DCR direct current resistance deg., ° degree dept. department DFMEA Design Failure Mode and
dia. diameter DI/EO dual inlet/end outlet DIN Deutsches Institut fur Normung
DIP dual inline package DPDT double-pole, double-throw DPST double-pole, single-throw DS disconnect switch DVR digital voltage regulator E, emer. emergency (power source) ECM electronic control module,
EDI electronic data interchange EFR emergency frequency relay e.g. for example (exempli gratia) EG electronic governor EGSA Electrical Generating Systems
EIA Electronic Industries
EI/EO end inlet/end outlet EMI electromagnetic interference emiss. emission eng. engine EPA Environmental Protection
EPS emergency power system ER emergency relay ES engineering special,
ESD electrostatic discharge
substrate (semiconductor)
Association
Laboratories
Laboratories
Effects Analysis
e. V. (also Deutsche Industrie Normenausschuss)
engine control module
Association
Association
Agency
engineered special
est. estimated E-Stop emergency stop etc. et cetera (and so forth) exh. exhaust ext. external F Fahrenheit, female fglass. fiberglass FHM flat head machine (screw) fl. oz. fluid ounce flex. flexible freq. frequency FS full scale ft. foot, feet ft. lb. foot pounds (torque) ft./min. feet per minute ftp file transfer protocol ggram ga. gauge (meters, wire size) gal. gallon gen. generator genset generator set GFI ground fault interrupter
GND, gov. governor gph gallons per hour gpm gallons per minute gr. grade, gross GRD equipment ground gr. wt. gross weight H x W x D height by width by depth HC hex cap HCHT high cylinder head temperature HD heavy duty HET high exhaust temp., high
hex hexagon Hg mercury (element) HH hex head HHC hex head cap HP horsepower hr. hour HS heat shrink hsg. housing HVAC heating, ventilation, and air
HWT high water temperature Hz hertz (cycles per second) IC integrated circuit ID inside diameter, identification IEC International Electrotechnical
IEEE Institute of Electrical and
IMS improved motor starting in. inch in. H in. Hg inches of mercury in. lb. inch pounds Inc. incorporated ind. industrial int. internal int./ext. internal/external I/O input/output IP iron pipe ISO International Organization for
J joule JIS Japanese Industry Standard
ground
engine temp.
conditioning
Commission
Electronics Engineers
O inches of water
2
Standardization
TP-6515 10/07 Appendix 31
Page 32
k kilo (1000) K kelvin kA kiloampere KB kilobyte (2
10
bytes) KBus Kohler communication protocol kg kilogram
2
kg/cm
kgm kilogram-meter kg/m
kilograms per square centimeter
3
kilograms per cubic meter kHz kilohertz kJ kilojoule km kilometer kOhm, kkilo-ohm kPa kilopascal kph kilometers per hour kV kilovolt kVA kilovolt ampere kVAR kilovolt ampere reactive kW kilowatt kWh kilowatt-hour kWm kilowatt mechanical kWth kilowatt-thermal L liter LAN local area network L x W x H length by width by height lb. pound, pounds
3
lbm/ft
pounds mass per cubic feet LCB line circuit breaker LCD liquid crystal display ld. shd. load shed LED light emitting diode Lph liters per hour Lpm liters per minute LOP low oil pressure LP liquefied petroleum LPG liquefied petroleum gas LS left side L
wa
LWL low water level
sound power level, A weighted
LWT low water temperature m meter, milli (1/1000) M mega (10
3
m
3
m
3
m
units), male
cubic meter
/hr. cubic meters per hour /min. cubic meters per minute
6
when used with SI
mA milliampere man. manual max. maximum MB megabyte (2
20
bytes) MCCB molded-case circuit breaker MCM one thousand circular mils meggar megohmmeter MHz megahertz mi. mile mil one one-thousandth of an inch min. minimum, minute misc. miscellaneous MJ megajoule mJ millijoule mm millimeter mOhm, mmilliohm MOhm, MΩmegohm MOV metal oxide varistor MPa megapascal mpg miles per gallon mph miles per hour MS military standard ms millisecond m/sec. meters per second MTBF mean time between failure
MTBO mean time between overhauls mtg. mounting MTU Motoren-und Turbinen-Union MW megawatt mW milliwatt μF microfarad N, norm. normal (power source) NA not available, not applicable nat. gas natural gas NBS National Bureau of Standards NC normally closed NEC National Electrical Code NEMA National Electrical
Manufacturers Association
NFPA National Fire Protection
Association Nm newton meter NO normally open no., nos. number, numbers NPS National Pipe, Straight NPSC National Pipe, Straight-coupling NPT National Standard taper pipe
thread per general use NPTF National Pipe, Taper-Fine NR not required, normal relay ns nanosecond OC overcrank OD outside diameter OEM original equipment
manufacturer OF overfrequency opt. option, optional OS oversize, overspeed OSHA Occupational Safety and Health
Administration OV overvoltage oz. ounce p., pp. page, pages PC personal computer PCB printed circuit board pF picofarad PF power factor ph., phase PHC Phillipsr head Crimptiter
(screw) PHH Phillipsr hex head (screw) PHM pan head machine (screw) PLC programmable logic control PMG permanent magnet generator pot potentiometer, potential ppm parts per million PROM programmable read-only
memory psi pounds per square inch psig pounds per square inch gauge pt. pint PTC positive temperature coefficient PTO power takeoff PVC polyvinyl chloride qt. quart, quarts qty. quantity R replacement (emergency)
power source rad. radiator, radius RAM random access memory RDO relay driver output ref. reference rem. remote Res/Coml Residential/Commercial RFI radio frequency interference RH round head RHM round head machine (screw) rly. relay
rms root mean square rnd. round ROM read only memory rot. rotate, rotating rpm revolutions per minute RS right side RTU remote terminal unit RTV room temperature vulcanization RW read/write SAE Society of Automotive
Engineers scfm standard cubic feet per minute SCR silicon controlled rectifier s, sec. second SI Systeme international d’unites,
International System of Units SI/EO side in/end out sil. silencer SN serial number SNMP simple network management
protocol SPDT single-pole, double-throw SPST single-pole, single-throw spec specification specs specification(s) sq. square sq. cm square centimeter sq. in. square inch SS stainless steel std. standard stl. steel tach. tachometer TD time delay TDC top dead center TDEC time delay engine cooldown TDEN time delay emergency to
normal TDES time delay engine start TDNE time delay normal to
emergency TDOE time delay off to emergency TDON time delay off to normal temp. temperature term. terminal THD total harmonic distortion TIF telephone influence factor TIR total indicator reading tol. tolerance turbo. turbocharger typ. typical (same in multiple
locations) UF underfrequency UHF ultrahigh frequency UL Underwriter’s Laboratories, Inc. UNC unified coarse thread (was NC) UNF unified fine thread (was NF) univ. universal US undersize, underspeed UV ultraviolet, undervoltage V volt VAC volts alternating current VAR voltampere reactive VDC volts direct current VFD vacuum fluorescent display VGA video graphics adapter VHF very high frequency W watt WCR withstand and closing rating w/ with w/o without wt. weight xfmr transformer
TP-6515 10/0732 Appendix
Page 33
Page 34
Page 35
Page 36
TP-6515 10/07
E 2007 by Kohler Co. All rights reserved.
KOHLER CO. Kohler, Wisconsin 53044 Phone 920-565-3381, Fax 920-459-1646 For the nearest sales/service outlet in the US and Canada, phone 1-800-544-2444 KohlerPower.com
Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65) 6264-6422, Fax (65) 6264-6455
Loading...