Section 3 Drawings and Diagrams45..........................................................
Appendix A Abbreviations67................................................................
Appendix B Electrical Lead Entry Template69.................................................
TP-6803 6/15Table of Contents
Page 5
Safety Precautions and Instructions
IMPORTANTSAFETY INSTRUCTIONS.
Electromechanicalequipment,
includinggenerator sets,transfer
switches, switchgear, and accessories,
can cause bodily harm and pose
life-threateningdangerwhen
improperlyinstalled, operated, or
maintained. To prevent accidents be
aware of potential dangers and act
safely.Read and follow all safety
precautions and instructions. SAVE
THESE INSTRUCTIONS.
This manual has several types of safety
precautions and instructions: Danger,
Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a
hazardthatwillcausesevere
personal injury, death,orsubstantial
property damage.
WARNING
Warning indicates the presence of a
hazardthatcancausesevere
personal injury, death, or substantial
property damage.
CAUTION
Caution indicates the presence of a
hazard that will or can cause minorpersonal injury or property damage.
NOTICE
Noticecommunicatesinstallation,
operation, or maintenance information
that is safety related but not hazard
related.
Safety decals affixed to the equipment
in prominent places alert the operator
or service technician to potential
hazards and explain how to act safely.
The decals are shown throughout this
publicationtoimproveoperator
recognition.Replace missing or
damaged decals.
Accidental Starting
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working onthe generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disablingthegeneratorset.
Accidentalstartingcancause
severe injury or death.Before
working on the generator set or
equipment connected to the set,
disable the generator set as follows:
(1) Press the generator set off/reset
button to shut down the generator set.
(2) Disconnect the power to the battery
charger, if equipped. (3) Remove the
battery cables, negative (--) lead first.
Reconnect the negative (--) lead last
when reconnecting the battery. Follow
these precautions to prevent the
starting of the generator set by the
remote start/stop switch.
Battery
WARNING
Sulfuric acid in batteries.
Can cause severe injury or death.
Wearprotectivegogglesand
clothing.Battery acid may cause
blindness and burn skin.
WARNING
Explosion.
Can cause severe injury or death.
Relays in the battery charger
cause arcs or sparks.
Locate the battery in a well-ventilated
area. Isolate the battery charger from
explosive fumes.
Battery electrolyte is a diluted
sulfuric acid. Battery acid can cause
severe injury or death. Battery acid
can cause blindness and burn skin.
Alwayswearsplashproofsafety
goggles, rubber gloves, and boots
when servicing the battery. Do not
open a sealed battery or mutilate the
battery case. If battery acid splashes in
the eyes or on the skin, immediately
flush the affected area for 15 minutes
with large quantities of clean water.
Seek immediate medical aid in the case
of eye contact. Never add acid to a
battery after placing the battery in
service, as this may result in hazardous
spattering of battery acid.
Battery acid cleanup. Battery acid
can cause severe injury or death.
Battery acid is electrically conductive
and corrosive. Add 500 g (1 lb.) of
bicarbonate of soda (baking soda) to a
container with 4 L (1 gal.) of water and
mix the neutralizing solution. Pour the
neutralizing solution on the spilled
battery acid and continue to add the
neutralizing solution to the spilled
battery acid until all evidence of a
chemicalreaction(foaming)has
ceased. Flush the resulting liquid with
water and dry the area.
TP-6803 6/155Safety Precautions and Instructions
Page 6
Battery gases. Explosion can cause
severe injury or death. Battery gases
can cause an explosion. Do not smoke
or permit flames or sparks to occur near
a battery at any time, particularly when
it is charging. Do not dispose of a
battery in a fire. To prevent burns and
sparks that could cause an explosion,
avoid touching the battery terminals
with tools or other metal objects.
Remove all jewelry before servicing the
equipment. Discharge static electricity
from your body before touching
batteries by first touching a grounded
metal surface away from the battery. To
avoid sparks, do not disturb the battery
charger connections while the battery
is charging. Always turn the battery
charger off before disconnecting the
battery connections.Ventilate the
compartments containing batteries to
prevent accumulation of explosive
gases.
Battery short circuits.Explosion
can cause severe injury or death.
Short circuits can cause bodily injury
and/orequipmentdamage.
Disconnectthebatterybefore
generatorsetinstallationor
maintenance.Remove all jewelry
before servicing the equipment. Use
tools with insulated handles. Remove
the negative (--) lead first when
disconnecting the battery. Reconnect
the negative (--) lead last when
reconnecting the battery.Never
connect the negative (--) battery cable
to the positive (+) connection terminal
of the starter solenoid. Do not test the
battery condition by shorting the
terminals together.
Engine Backfire/Flash
Fire
WARNING
Risk of fire.
Can cause severe injury or death.
Servicing the air cleaner. A sudden
backfire can cause severe injury or
death. Do not operate the generator
set with the air cleaner removed.
Servicing the fuel system. A flash
fire can cause severe injury or death.
Do not smoke or permit flames or
sparks near the carburetor, fuel line,
fuel filter, fuel pump, or other potential
sources of spilled fuels or fuel vapors.
Catch fuels in an approved container
when removing the fuel line or
carburetor.
Combustible materials. A fire can
cause severe injury or death.
Generator set engine fuels and fuel
vapors are flammable and explosive.
Handle these materials carefully to
minimize the risk of fire or explosion.
Equip the compartment or nearby area
with a fully charged fire extinguisher.
Select a fire extinguisher rated ABC or
BCforelectricalfiresoras
recommended by the local fire code or
an authorized agency.Train all
personnelonfireextinguisher
operationandfireprevention
procedures.
Exhaust System
WARNING
Carbon monoxide.
Cancauseseverenausea,
fainting, or death.
The exhaustsystemmustbe
leakproof and routinely inspected.
Generator set operation.Carbon
monoxide can cause severe nausea,
fainting, or death. Carbon monoxide
is an odorless, colorless, tasteless,
nonirritating gas that can cause death if
inhaled for even a short time. Avoid
breathing exhaust fumes when working
on or near the generator set. Never
operate the generator set inside a
building. Never operate the generator
set where exhaust gas could seep
inside or be drawn into a potentially
occupied building through windows, air
intake vents, or other openings.
Carbonmonoxidedetectors.
Carbon monoxide can cause severe
nausea, fainting, or death.Install
carbon monoxide detectors on each
level of any building adjacent to the
generator set. Locate the detectors to
adequatelywarnthebuilding’s
occupants of the presence of carbon
monoxide.Keepthe detectors
operational at all times. Periodically
test and replace the carbon monoxide
detectorsaccordingtothe
manufacturer’s instructions.
Carbonmonoxidesymptoms.
Carbon monoxide can cause severe
nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in
exhaust gases. Carbon monoxide is an
odorless,colorless,tasteless,
nonirritating gas that can cause death if
inhaled for even a short time. Carbon
monoxide poisoning symptoms include
but are not limited to the following:
D Light-headedness, dizziness
D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms
and carbon monoxide poisoning is
possible, seek fresh air immediately
and remain active. Do not sit, lie down,
or fall asleep.Alert others to the
possibilityofcarbonmonoxide
poisoning. Seek medical attention if
the condition of affected persons does
not improve within minutes of breathing
fresh air.
Do not smoke or permit flames or
sparks near fuels or the fuel system.
TP-6803 6/156Safety Precautions and Instructions
Page 7
Fuel System
WARNING
Natural Gas—Adequate ventilation is
mandatory. Because natural gas rises,
install natural gas detectors high in a
room. Inspect the detectors per the
manufacturer’s instructions.
WARNING
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.
The fuel system.Explosive fuel
vapors can cause severe injury or
death.Vaporized fuels are highly
explosive.Use extreme care when
handling and storing fuels. Store fuels
in a well-ventilated area away from
spark-producing equipment and out of
the reach of children. Never add fuel to
the tank while the engine is running
because spilled fuel may ignite on
contact with hot parts or from sparks.
Do not smoke or permit flames or
sparks to occur near sources of spilled
fuel or fuel vapors. Keep the fuel lines
and connections tight and in good
condition. Do not replace flexible fuel
lines with rigid lines.Use flexible
sections to avoid fuel line breakage
caused by vibration. Do not operatethe
generator set in the presence of fuel
leaks, fuel accumulation, or sparks.
Repair fuel systems before resuming
generator set operation.
Gas fuel leaks.Explosive fuel
vapors can cause severe injury or
death. Fuel leakage can cause an
explosion. Check the LPG vapor or
natural gas fuel system for leakage by
using a soap and water solution with
the fuel system test pressurized to
6--8 ouncespersquareinch
(10--14 inches water column). Do not
use a soap solution containing either
ammonia or chlorine because both
prevent bubble formation. A successful
test depends on the ability of the
solution to bubble.
Explosive fuel vapors can cause
severe injury or death.Ta ke
additional precautions when using the
following fuels:
Propane (LPG)—Adequate ventilation
is mandatory.Because propane is
heavier than air, install propane gas
detectors low in a room. Inspect the
detectorsperthe manufacturer’s
instructions.
Hazardous Noise
CAUTION
Hazardous noise.
Can cause hearing loss.
Never operate the generator set
without a muffler or with a faulty
exhaust system.
Engine noise. Hazardous noise can
cause hearing loss. Generator sets
not equipped with sound enclosures
can produce noise levels greater than
105 dBA. Prolonged exposure to noise
levels greater than 85 dBA can cause
permanent hearing loss. Wear hearing
protection when near an operating
generator set.
Hazardous Voltage/
Moving Parts
DANGER
Hazardous voltage.
Will cause severe injury or death.
This equipment must be installed and
servicedbyqualifiedelectrical
personnel.
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
Moving parts.
Hazardous voltage.
Backfeed to the utility system can
cause property damage, severe
injury, or death.
If the generator set is used for
standby power, install an automatic
transfer switch to prevent inadvertent
interconnectionofstandbyand
normal sources of supply.
CAUTION
Welding the generator set.
Cancausesevereelectrical
equipment damage.
Never weld components of the
generatorsetwithoutfirst
disconnecting the battery, controller
wiring harness, and engine electronic
control module (ECM).
Grounding electrical equipment.
Hazardousvoltagecancause
severe injury or death. Electrocution
is possible whenever electricity is
present. Ensure you comply with all
applicablecodesandstandards.
Electrically ground the generator set,
transfer switch, and related equipment
and electrical circuits. Turn off the main
circuit breakers of all power sources
before servicing the equipment. Never
contact electrical leads or appliances
when standing in water or on wet
ground because these conditions
increase the risk of electrocution.
Welding on the generator set. Can
cause severe electrical equipment
damage.Before welding on the
generator set perform the following
steps: (1) Remove the battery cables,
negative (--) lead first. (2) Disconnect
all engine electronic control module
(ECM) connectors. (3) Disconnect all
generator set controller and voltage
regulator circuit board connectors.
(4) Disconnect the engine batterychargingalternatorconnections.
(5) Attach the weld ground connection
close to the weld location.
TP-6803 6/157Safety Precautions and Instructions
Page 8
Connecting the battery and the
battery charger. Hazardous voltage
can cause severe injury or death.
Reconnectthebatterycorrectly,
positive to positive and negative to
negative, to avoid electrical shock and
damage to the battery charger and
battery(ies).Haveaqualified
electrician install the battery(ies).
Shortcircuits.Hazardous
voltage/current can cause severe
injury or death. Short circuits can
cause bodily injury and/or equipment
damage.Do not contact electrical
connections with tools or jewelry while
makingadjustmentsorrepairs.
Remove all jewelry before servicing the
equipment.
Electrical backfeed to the utility.
Hazardous backfeed voltage can
cause severe injury or death. Install
a transfer switch in standby power
installations to prevent the connection
of standby and other sources of power.
Electrical backfeed intoautility
electrical system can cause severe
injury or death to utility personnel
working on power lines.
Hot Parts
WARNING
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
Servicing the exhaust system. Hot
parts can cause severe injury or
death. Do not touch hot engine parts.
The engine and exhaust system
components become extremely hot
during operation.
Servicing the engine heater.Hot
parts can cause minor personal
injury or property damage. Install the
heater before connecting it to power.
Operating the heater before installation
can cause burns and component
damage.Disconnect power to the
heater and allow it to cool before
servicing the heater or nearby parts.
Notice
NOTICE
Canadian installations only.For
standby service connect the output of
the generator set to a suitably rated
transfer switch in accordance with
Canadian Electrical Code, Part 1.
Heavy Equipment
WARNING
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Do not use lifting eyes.
Lift the generator set using lifting bars
inserted through the lifting holes on
the skid.
TP-6803 6/158Safety Precautions and Instructions
Page 9
Introduction
This manual provides installation instructions for
Residential/Commercial Model 14/20RESA/RESAL
and 20RESC/RESCL generator sets. See Figure 1.
Refer to TP-6804, Operation Manual, for generator set
operation and maintenance instructions.
The generator set is approved for use in stationary
applications in locations served by a reliable utility
power source.
Kohler strongly recommends that only factoryauthorized distributors or dealers install and
service the generator.
Have a Kohlerr authorized distributor/dealer install the
generator set outdoors according to the instructions in
this manual. The generator set installation must comply
with the National Electrical Code (NEC) and local code
requirements. Do not install this generator set indoors.
Information in this publication represents data available
at the time of print. Kohler Co. reserves the right to
change this publication and the products represented
without notice and without any obligation or liability
whatsoever.
Read this manual and carefully follow a ll procedures
and safety precautions to ensure proper equipment
operation and to avoid bodily injury. Read and followthe
Safety Precautions and Instructions section at the
beginning of this manual.
List of Related Literature
Figure 2 identifies related literature available for the
generator sets covered in this manual. Only trained and
qualified personnel should install or service the
generator set.
Literature TypePart Number
Specification Sheet, 20RESAG4-209
Specification Sheet, 20RESALG4-210
Specification Sheet, 14RESAG4-245
Specification Sheet, 14RESALG4-249
Specification Sheet, 20RESCG4-246
Specification Sheet, 20RESCLG4-250
Operation Manual, Generator SetTP-6804
Operation/Installation Manual, Model
RXT Automatic Transfer Switch
Operation/Installation Manual,
Model RDT Transfer Switch
When the generator set is installed, complete the
startup and installation checklists supplied with the
startup notification form. Complete and sign the startup
notification form and register the unit using the Kohler
online Warranty Processing System.
Page 10
Service Assistance
For professional advice on generator set power
requirements andconscientious service, pleasecontact
your nearest Kohler distributor or dealer.
D Consult the Yellow Pages under the heading
Generators—Electric.
D Visit theKohler Power Systemswebsite at
KOHLERPower.com.
D Look at the labels and decals on your Kohler product
or review the appropriate literature or documents
included with the product.
D Call toll free in the US and Canada 1-800-544-2444.
D Outside the US and Canada, callthe nearest regional
office.
Headquarters Europe, Middle East, Africa
(EMEA)
Kohler Power Systems Netherlands B.V.
Kristallaan 1
4761 ZC Zevenbergen
The Netherlands
Phone: (31) 168 331630
Fax:(31) 168 331631
Asia Pacific
Power Systems Asia Pacific Regional Office
Singapore, Republic of Singapore
Phone: (65) 6264-6422
Fax:(65) 6264-6455
China
North China Regional Office, Beijing
Phone: (86) 10 6518 7950
(86) 10 6518 7951
(86) 10 6518 7952
Fax:(86) 10 6518 7955
East China Regional Office, Shanghai
Phone: (86) 21 6288 0500
Fax:(86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office
Bangalore, India
Phone: (91) 80 3366208
(91) 80 3366231
Fax:(91) 80 3315972
Japan, Korea
North Asia Regional Office
Tokyo, Japan
Phone: (813) 3440-4515
Fax:(813) 3440-2727
Latin America
Latin America Regional Office
Lakeland, Florida, USA
Phone: (863) 619-7568
Fax:(863) 701-7131
TP-6803 6/1510
Page 11
Section 1 Installation
1.1Introduction
DANGER
Hazardous voltage.
Will cause severe injury or death.
This equipment must be installed and
servicedbyqualifiedelectrical
personnel.
WARNING
Carbon monoxide.
Cancauseseverenausea,
fainting, or death.
The exhaustsystemmustbe
leakproof and routinely inspected.
Note: DO NOT install these generator sets inside a
building.
Note: Install carbon monoxide (CO) detector(s) on
each level of any building adjacent to a generator
set. Locate the detectors to adequately warn the
building’s occupants of the presence of carbon
monoxide.
Obtain a building permit and contact your local utility
companies to mark the locations of underground pipes
and cables.
Read and follow the safety precautions in this manual
and observe the decals on the equipment. Refer to the
diagrams and drawings in this manual for dimensions
and electrical connections during the installation
procedure. Read the entire installation procedure and
obtain the accessories and tools needed before
beginning installation. Perform the steps in the order
shown.
To install optional accessories, follow the instructions
provided with each kit.
1.2Lifting
Generator set operation. Carbon monoxide can cause
severe nausea, fainting, or death. Carbon monoxide is an
odorless, colorless, tasteless, nonirritating gas that can cause
death if inhaled for even a short time. Avoid breathing exhaust
fumes when working on or near the generator set. Never
operate the generator set inside a building. Never operate the
generator set where exhaust gas could seep inside or be
drawn into a potentially occupied buildingthrough windows, air
intake vents, or other openings.
Carbon monoxide detectors.Carbon monoxide can
cause severe nausea, fainting, or death. Install carbon
monoxide detectors on each level of any building adjacent to
the generator set. Locate the detectors to adequately warn the
building’s occupants of the presence of carbon monoxide.
Keep the detectors operational at all times. Periodically test
and replace the carbon monoxide detectors according to the
manufacturer’s instructions.
Have thegenerator set installed by an authorized Kohler
distributor/dealer or authorized representative. For all
locations, ensure that the installation complies with
applicable national and local codes.In the United
States, the installation must comply with the National
Electrical Code (NEC) and local codes. For Canadian
installations, refer to the Canadian Electrical Code
(CEC).
WARNING
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Do not use lifting eyes.
Lift the generator set using lifting bars
inserted through the lifting holes on
the skid.
ModelWeight, kg (lb.)
14RESA/RESAL
20RESA/RESAL
20RESC/RESCL
Figure 1-1 Approximate Weights
191 (420)
243 (535)
243 (535)
The generator set must be installed outdoors. The
exhaust systems on enclosed units are designed for
outdoor installation only.
TP-6803 6/1511Section 1 Installation
Page 12
Approximate generator set weights are shown in
Figure 1-1. Use lifting bars inserted through the holes in
the skid to lift the unit. See the dimension drawings in
Section 3 for lifting hole locations.
1.3Generator Set Inspection
Complete a thorough inspection of the generator set.
Check for the following:
1. Inspect the generator set for loose or damaged
parts or wires. Repair or tighten any loose parts
before installation.
2. Check the engine oil. Fill, if necessary, with the
recommended viscosity and grade of oil.Use
synthetic oil, API (American Petroleum Institute)
Service Class SG or higher.See TP-6804,
Operation Manual, for additional information.
1.4Location and Mounting
Install the generator set outdoors near the incoming gas
service. The generator set location must allow easy
access for maintenance and service. The required
distance froma structure is dependent onstate and local
codes. See the dimension drawing in Section 3 for the
minimumclearancefromstructuresand
non-combustible materials.
Locate the generator set so that the hot exhaust does
not blow on plants or other combustible materials. No
plants, shrubs, or other combustible materials are
allowed within 1.2 m (4 ft.) of the exhaust end of the
generator set.
Do not install the generator set where exhaust gas could
accumulate and seep inside or be drawn into a
potentially occupied building. Furnace and other similar
intakes must be at least 3 m (10 ft.) from the exhaust
end of the generator set.
Notice
DO NOT locate the generator set near patios,
decks, play areas, o r animal shelters. Keep items
such as lawn furniture, toys, sports equipment,
and all combustible materials away from the
generator set exhaust outlet.
Remind family members, children, and visitors to
use caution near the generator set. Generator
sets connected to automatic transfer switches
start automatically during exercise periods and
power outages. Some generator set components
become hot when the generator set is running and
remain hot for a time after the generator set shuts
down.
1.4.1Mounting Area
The generator set is shipped on an engineered
composite mounting pad. Prepare a flat, level mounting
area covered with a weed barrier and gravel or a
concrete mounting pad. Set the composite mounting
pad directly on the gravel or concrete.
Do not install the composite mounting pad directly on
grass, wood, or other combustible materials. Clear all
combustible materials, including plants and shrubs,
building materials, and lawn furniture, from an area at
least 1.2 m (4 ft.) beyond the exhaust end of the
generator set. See the dimension drawing in Section 3.
1.4.2Concrete Mounting Pads
Kohler Co. offers optional concrete mounting pads that
are custom-designed for Model 14RESA/RESAL,
20RESA/RESAL, and 20RESC/RESCL generator sets.
Three-inch and four-inch thick pads are available.
Four-inch pads are recommended for storm-prone
areas.See TT-1619 for instructions to install the
mounting pad, if necessary.
1.4.3Exhaust Requirements
WARNING
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
TP-6803 6/1512 Section 1 Installation
Page 13
Figure 1-2 gives the exhaust temperature at rated load.
The engine exhaust mixes with the generator set
cooling air at the exhaust end of the enclosure. Mount
the generator set so that the hot exhaust does not blow
on plants or other combustible materials. Maintain the
clearances shown in the dimension drawing in
Section 3.
Temperature,
Exhaust
Exhaust gas exiting the enclosure
at rated kW, _C(_F)
_C(_F)
260 (500)
Figure 1-2 Exhaust Flow and Temperature
1.6Access the Air Intake Area
The battery, fuel system, and electrical connections are
located in theair intake area. Raise the roof and remove
the enclosure panel to access the air intake area during
installation as described below.
1. Remove two screws from the top of the air intake
panel.Pull the the panel up and off.See
Figure 1-4.
2. To make the electrical connections, you will also
need to remove the cover panel over the terminal
block as shown in Section 1.9.3.
The generator set requires correct air flow for cooling
and combustion. The inlet and outlet openings in the
sound enclosure provide the cooling and combustion
air. Figure 1-3 shows the locations of the cooling air
intake and exhaust vents. Inspect the air inlet and outlet
openings inside and outside the enclosure to ensure
that the air flow is not blocked.
1
REAR VIEW
1. Air intake
2. Exhaust outlet
1
2
tp6733
Figure 1-3 Cooling Air Intake and Exhaust
The generator set is designed to operate with all
enclosure panels and internal baffling in place. If during
installation, maintenance or repair the unit must be
operated without the complete enclosure and baffling as
shipped from the factory make sure the exhaust panel is
removed as well.
3. Reinstall the panels after all electrical connections
are complete and the battery is installed and
connected.
1. Remove 2 screws.
ADV-8424
Figure 1-4 Removing the Air Intake Panel
1
1.5Dimension Drawings
See the dimension drawings in Section 3 for the
generator set dimensions, fuel and electric inlet
locations, and recommended clearance.
TP-6803 6/1513Section 1 Installation
Page 14
1.7Fuel Requirements
The generator set operates using natural gas or LPG
fuel. The generator set is EPA-certified for both natural
gas and LPG fuels.
The fuel system installation must complywith applicable
national, state, and local codes.
WARNING
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.
Explosive fuel vapors can cause severe injury or death.
Take additional precautions when using the following fuels:
Propane(LPG)—Adequateventilationismandatory.
Because propane is heavier than air, install propane gas
detectors low in a room.Inspect the detectors per the
manufacturer’s instructions.
Natural Gas—Adequate ventilation is mandatory. Because
natural gas rises, install natural gas detectors high in a room.
Inspect the detectors per the manufacturer’s instructions.
1.7.1Fuel Supply
Because of variable climates and geographical
considerations, contact the local fuel supplier for fuel
system planning and installation. Figure 1-5 lists the
recommended fuel ratings and other fuel supply
information for natural gas and LPG fuels.
Verify that the output pressure from the primary gas
utility pressure regulator is within the range shown in
Figure 1-5 and that the utility gas meter flow rate is
sufficient to supply the generator set at rated load plus
all other gas-consuming appliances. For LPG tanks,
verify that the output pressure is as shown in Figure 1-5.
See Figure 1-6 for fuel consumption. Contact the fuel
supplier for flow rate information or a gas meter
upgrade, if necessary.
Natural
Fuel type
Gas
LPG
Fuel supply inlet1/2 NPT
Fuel supply pressure, kPa (in. H2O)
14RESA/RESAL1.3--2.7
(5--11)
20RESA/RESAL1.3--2.7
(5--11)
20RESC/RESCL0.9--2.7
(3.5--11)
1.7--2.7
(7--11)
1.7--2.7
(7--11)
1.7--2.7
(7--11)
Fuel flow rate, maximum, Btu/hr.:
14RESA/RESAL193,000203,000
20RESA/RESAL281,000340,000
20RESC/RESCL281,000340,000
Nominal Fuel Rating, Btu/ft.
3
Natural gas1000
LPG2500
Figure 1-5 Fuel Supply
Fuel Type% Load
100%5.4(193)4.9(175)8.0(281)6.4(225)
Natural Gas
LPG
LPG conversion factors:
8.58 ft.
0.535 m
36.39 ft.
3
=1lb.
3
3
=1kg
= 1 gal.
75%4.7(163)4.2(148)6.9(243)5.4(189)
50%3.5(124)3.1(108)4.6(161)3.9(139)
25%2.6(93)2.4(84)3.6(127)2.9(103)
100%2.3(81)2.1(74)3.9(136)2.9(102)
75%2.1(75)1.9(68)3.1(109)2.4(85)
50%1.8(60)1.5(53)2.3(82)1.8(63)
25%1.2(45)1.1(40)1.7(59)1.3(47)
Figure 1-6 Fuel Consumption
Fuel Consumption, m3/hr. (cfh)
14RESA/RESAL20RESA/RESAL/RESC/RESCL
60 Hz50 Hz60 Hz50 Hz
Nominal fuel rating:
Natural gas:37 MJ/m
LPG:93 MJ/m
3
(1000 Btu/ft.3)
3
(2500 Btu/ft.3)
TP-6803 6/1514 Section 1 Installation
Page 15
1.7.2Fuel Pipe Size
Ensure that the fuel pipe size and length meet the
specifications in Figure 1-7. Measure the pipe length
from the primary gas pressure regulator to the pipe
connection on the generator set fuel inlet. Add 2.4 m
(8 ft.) to the measured length for each 90 degree elbow.
Compare the total pipe length with the chart in
Figure 1-7 to find the required pipe size.
Contact local LPG provider for LPG installation
information.
Minimum Gas Pipe Size Recommendation, in. NPT
20RESA/RESAL
14RESA/RESAL
Pipe
Length,
m (ft.)
8(25)3/43/413/4
15(50)13/411
30 (100)1111/41
46 (150)11/4111/411/4
61 (200)11/4111/411/4
Natural
Gas
(193,000
Btu/hr.)
LPG
(203,000
Btu/hr.)
Figure 1-7 Fuel Pipe Size Recommendations
20RESC/RESCL
Natural
Gas
(281,000
Btu/hr.)
LPG
(340,000
Btu/hr.)
Apply pipe sealant that is approved for fuel connections.
Hold the fuel solenoid valve with a wrench when
tightening the fuel connections.
Note: Do not hold the fuel solenoid valve coil when
tightening the fuel connections. See Figure 1-8
for the recommended wrench locations.
1
Note: Do NOT hold the valve
coil when tightening
connections.
IMG_0351
1. Hold valve with wrench on flats of valve body
2. Alternate wrench location
2
1.7.3Connecting the Fuel Supply
The dimension drawing in Section 3 shows the location
of the fuel inlet connection. Have the fuel supplier install
rigid gas piping and a manual fuel shut-off valve. The
fuel supply line should line up with the generator set fuel
inlet and end about 12 inches away to allow connection
with asection of flexiblefuel line. Use flexible sectionsto
prevent fuel line breakage caused by vibration.
Note: Do not bend the flexible fuel line to make up for
misalignment of the fuel supply line and the
generator set fuel inlet.
Figure 1-8 Holding Fuel Valve to Tighten Fuel
Connections
Open the manual fuel valves and test all fuel
connections using soapy water. If a leak is found, close
the fuel valves, clean the fittings, and apply fresh
sealant. Check for fuel leaks again with the generator
set running.
Protect all fuel lines from machinery or equipment
contact, adverse weather conditions, and environmental
damage.
TP-6803 6/1515Section 1 Installation
Page 16
1.8Fuel Conversion
The multi-fuel system allows conversion from natural
gas to LPG (or vice-versa) in the field while maintaining
emissions-standard compliance. A trained technician
or an authorized distributor/dealer can convert the fuel
system.
After converting the fuel system, change the Fuel Type
setting on the controller. See the Operation Manual for
instructions to change settings at the controller, or use a
personal (laptop) computer and Kohlerr SiteTecht
software to change the setting.
Rating Change
Converting the fuel will change the generator set rating.
See the generator set specification sheetfor ratings with
natural gas and LP. Order a new nameplate with the
updated rating and fuel information from an authorized
distributor/dealer, if necessary. Provide the following
information from the original nameplate:
WARNING
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.
Explosive fuel vapors can cause severe injury or death.
Take additional precautions when using the following fuels:
Propane(LPG)—Adequateventilationismandatory.
Because propane is heavier than air, install propane gas
detectors low in a room.Inspect the detectors per the
manufacturer’s instructions.
Natural Gas—Adequate ventilation is mandatory. Because
natural gas rises, install natural gas detectors high in a room.
Inspect the detectors per the manufacturer’s instructions.
D Model NumberD kVA
D Spec NumberD Amps
D Serial NumberD Volts
D Fuel (original and new)D Hz
D kW
Attach the new nameplate over the old one. Do NOT
cover the UL listing information on the old nameplate.
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working onthe generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
1.8.1Fuel Conversion, 14RESA/RESAL
Equipped with Fuel Block
Note: Model 14RESA/RESAL generator sets built
before June 26, 2014 use a fuel block for the fuel
type selection.See Figure 1-9 and use the
instructions in this section for fuel conversion.
Model 14RESA/RESAL generators built June 26,
2014, or later are not equippedwith the fuel block.
These units use fuel orifice fittings installed in the
hose fitting at the fuel regulator. See Section
1.8.2 for fuel conversion instructions.
Two fuel connections on the fuel block allow fieldconversion between natural gas and LPG. The fuel
metering valves are factory-set and sealed to comply
with applicable e mission standards and to provide the
best possible hot and cold starting.
Note: Do not adjust the factory-sealed fuel-metering
adjustments on the fuel block. Changing the fuelmetering adjustmentsmay violate federalor state
laws.
Disabling the generator set.Accidental starting can
cause severe injury or death.Before working on the
generator set or equipment connected to the set, disable the
generator set as follows: (1) Press the generator set off/reset
button to shut down the generator set. (2) Disconnect the
power to the battery charger, if equipped. (3) Remove the
battery cables, negative (--) lead first. Reconnect the negative
(--) lead last when reconnecting the battery. Follow these
precautions to prevent the starting of the generator set by the
remote start/stop switch.
Use the following procedure to convert from natural gas
(NG) to LPG.See Figure 1-9 for the fuel system
component locations.
TP-6803 6/1516 Section 1 Installation
Page 17
Procedure to convert from NG to LPG,
14RESA/RESAL with fuel block
1. Press the OFF button on the generator set
controller.
2. Disconnect the power to the battery charger.
3. Disconnect the generator set engine starting
battery, negative (--) lead first.
4. Turn off the fuel supply.
Conversion from LPG to Natural Gas
To convert from LPG to natural gas, follow the fuel
conversion procedure above, moving the hose fitting to
the natural gas port and plugging the LP port. Connect
the DSAI leads for natural gas. See Figure 1-9.
1
10
2
LPG setup
shown
5. Remove the hose clamp and fuel hose from the
hose fitting in the fuel block. See Figure 1-9.
6. Remove the hose fitting from the natural gas outlet
port in the fuel block. See Figure 1-9.
7. Remove the plug from the LP port in the fuel block.
SeeFigure1-9.
8. Clean the plug with a dry cloth or brush, apply fresh
pipe sealant, and install the plug into the natural
gas outlet port.
9. Clean the hose fitting with a dry cloth or brush,
apply fresh pipe sealant to the threads, and install
the fitting into the LP port.
Note: Do not adjust the fuel metering valves.
10. Slide the hose onto the hose fitting and secure it
with the clamp.
11. Disconnect digital ignition timing leads 65 and N3
for LPG. The ignition timing leads are located near
the fuel solenoid valve. See Figure 1-9.
9
8
7
6
3
4
photo223
5
12. Connect and turn on the new fuel supply.
13. Reconnect the generator set engine starting
battery leads, negative (--) lead last.
14. Reconnect power to the battery charger.
15. Start the generator set by pressing the RUN button
on the generator set controller.
16. Check for leaks using a gas leak detector.
1. Fuel block
2. Fuel metering valves—factory-sealed, do not adjust
3. Fuel solenoid valve coil
4. Fuel inlet, 1/2 in. NPT
5. Ignition timing leads 65 and N3
6. Recommended holding points for tightening fuel connection
7. Fuel regulator
8. Ports are labeled LP and NG
9. Plug
10. Hose fitting
Ignition Timing Lead Connection
17. Run the generator set and check the operation.
Figure 1-9 Fuel System, 14RESA/RESAL Equipped
18. Press the OFF button toto shut down thegenerator
set.
TP-6803 6/1517Section 1 Installation
with Fuel Block (built before June 26,
2014)
Page 18
1.8.2Fuel Conversion, 14RESA/RESAL
Equipped with Fuel Orifice
Fittings
Note: Model 14RESA/RESAL generator sets built
before June 26, 2014, use a fuel block for the fuel
type selection.See Figure 1-9 and use the
instructions Section 1.8.1 for fuel conversion.
Model 14RESA/RESALgenerators built June 26,
2014, or later are not equippedwith the fuel block.
These units use fuel orifice fittings installed in the
hose fitting at the fuel regulator. See Figure 1-11
and use the instructions in this section for fuel
conversion.
For natural gas and LPG fuel, orifice fittings are used in
the fuel line. See Figure 1-10. The natural gas orifice
fitting is silver in color and stamped NG. The LPG fitting
is gold in color and stamped LPG. The fittings are
threaded. A straight-blade screwdriver is required to
remove and replace the fittings.
1
2
NGLPG
Figure 1-10 NG and LPG Fuel Orifice Fittings
The unit is typically shipped set up for natural gas, with
the LPG fitting tied near the fuel solenoid valve. To
convert to LPG, remove the NG fitting and install the
LPG fitting as described below. See Figure 1-11 for the
fuel system component locations.
Procedure to Convert from NG to LPG,
14RESA/RESAL with fuel orifice fittings
1. Press the OFF button on the generator set
controller.
2. Disconnect the utility power to the generator.
3. Disconnect the generator set engine starting
battery, negative (--) lead first.
4. Turn off and disconnect the fuel supply.
5. Remove the hose clamp and fuel hose from the
hose fitting. See Figure 1-11.
3
Ignition Timing Lead Connection
1. LPG fitting tied to bracket for shipping
2. Fuel hose and clamp
3. Ignition timing leads
Figure 1-11 Fuel System, As Shipped (Model
14RESA/RESAL built after June 26,
2014)
6. Use a straight-blade screwdriver to remove the NG
orifice from the hose fitting. See Figure 1-12.
7. Insert the LPG orifice into the hose fitting. Use a
straight-blade screwdriver to tighten the fitting until
it is snug.
8. Slide the hose onto the hose fitting and secure it
with the clamp.
9. Disconnect ignition timing leads 65 and N3 for
LPG. The ignition timing leads are located near the
fuel solenoid valve. See Figure 1-11.
TP-6803 6/1518 Section 1 Installation
Page 19
10. Connect and turn on the new fuel supply.
15. Run the generator set and check the operation.
11. Reconnect the generator set engine starting
battery leads, negative (--) lead last.
12. Reconnect the utility power to the generator.
13. Start the generator set by pressing the RUN button
on the generator set controller.
14. Check for leaks using a gas leak detector.
1
2
16. Press the OFF button to shut down the generator
set.
Conversion from LPG to Natural Gas
To convert from LPG to natural gas, repeat the steps
above, removing the LPG fuel orifice and installing the
NG fitting. Connect ignition timing leads 65 and N3
together for natural gas.
ORIFICE FITTING DETAIL
1. Orifice fitting (see detail)
2. Hose barb fitting
Figure 1-12 14RESA/RESAL Fuel System Showing Orifice Fittings (generators built after June 26, 2014)
GM84143
TP-6803 6/1519Section 1 Installation
Page 20
1.8.3Fuel Conversion,
20RESA/RESAL/RESC/RESCL
For LPG fuel, an orifice is used in the fuel line. The unit is
typically shipped set up for natural gas, with the loose
orifice tied near the fuel solenoid valve. To convert to
LPG, install the LPG orifice as described below. See
Figure 1-13 for the fuel system component locations.
Note: The generator set harness may contain a pair of
ignition timing leads near the fuel solenoid valve.
Connecting or disconnecting these leads has no
effect on the 20RESA/RESAL/RESC/RESCL
operation.
Procedure to Convert from NG to LPG,
20RESA/RESAL/RESC/RESCL
1. Press the OFF button on the generator set
controller.
LPG setup
shown
1
2
3
1. LPG orifice
2. Hose fitting
3. Regulator
4. Regulator vent tubes (vent to the outside of the controller)
4
GM84143
2. Disconnect the power to the battery charger.
3. Disconnect the generator set engine starting
battery, negative (--) lead first.
4. Turn off the fuel supply.
5. Remove the hose clamp and fuel hose from the
hose fitting. See Figure 1-13.
6. Insert the LPG orifice into the hose fitting. See
Figure 1-13.
7. Slide the hose onto the hose fitting and secure it
with the clamp.
8. Connect and turn on the new fuel supply.
9. Reconnect the generator set engine starting
battery leads, negative (--) lead last.
10. Reconnect power to the battery charger.
11. Start the generator set by pressing the RUN button
on the generator set controller.
12. Check for leaks using a gas leak detector.
Figure 1-13 Fuel Regulator and LPG Orifice,
20RESA/RESAL/RESC/RESCL
1.8.4Regulator Vent Hose
Model 20RESA/RESAL/RESC/RESCL generators are
equipped with fuel regulator vent hoses. Drill or punch
two holes in the enclosure at the locations shown on the
template in Appendix B. It may be convenient to cut
openings for the electrical leads at the same time as
shown on the template and in Section 1.9.2.
Insert the open ends of the hoses through the holes to
the outside of the enclosure as shown in Figure 1-14.
1
13. Run the generator set and check the operation.
14. Press the OFF button to shut down the generator
set.
Conversion from LPG to Natural Gas
To convert from LPG to natural gas, repeat the steps
above to remove the LPG fuel orifice.
2
sb722
1. Fuel regulator vent tubes, qty. 2
2. Drill or punch two holes and route both hoses to the outside
of the enclosure
Figure 1-14 Fuel Regulator Vent Hoses
TP-6803 6/1520 Section 1 Installation
Page 21
1.9Electrical Connections
DANGER
Hazardous voltage.
Will cause severe injury or death.
This equipment must be installed and
servicedbyqualifiedelectrical
personnel.
Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all
applicable codes and standards.Electrically ground the
generator set, transfer switch, and related equipment and
electrical circuits. Turn off the main circuit breakers of all
power sources before servicing the equipment. Never contact
electrical leads or appliances when standing in water or on wet
ground because these conditions increase the risk of
electrocution.
Electrical backfeed to the utility. Hazardous backfeed
voltage can cause severe injury or death. Install a transfer
switch in standby power installations to prevent the connection
of standby and other sources of power. Electrical backfeed
into a utility electrical system can cause severe injury or death
to utility personnel working on power lines.
NOTICE
Canadian installations only. For standby service connect
the output of the generator set to a suitably rated transfer
switch in accordance with Canadian Electrical Code, Part 1.
Have an authorized distributor/dealer or a licensed
electrician make the following electrical connections.
The electrical installation must comply with the National
Electrical Coder (NEC) class 1 wire designation and all
applicable local codes. Canadian installations must
comply with the Canadian Electrical Code (CEC) and
applicable local codes.
AC circuit protection. All AC circuits must include
circuit breaker or fuse protection. The circuit breaker
must be rated for a maximum of 125% of the rated
generator set output current. The circuit breaker must
open all ungrounded connectors. The generator set is
equipped with a factory-installed circuit breaker.
Forcustomer-suppliedwiring,selectthewire
temperature rating in Figure 1-15 based upon the
following criteria:
D Select row 1, 2, 3, or 4 if the circuit rating is
110 amperes or less or requires #1 AWG (42.4 mm
2
or smaller conductors.
D Select row 3 or 4 if the circuit rating is greater than
110 amperes or requires #1 AWG (42.4 mm
2
)or
larger conductors.
)
Row Temp . Ra t i n g Copper (Cu) OnlyCu/Aluminum (Al) CombinationsAl Only
1
60_C (140_F)
or
75_C (167_F)
2
60_C (140_F)Use No. * AWG, 60_CwireUse 60_C wire, either No. * AWG Cu or No. *
3
75_C (167_F)Use No. *[ AWG, 75_CwireUse 75_C wire, either No. *[ AWG Cu or No.
4
90_C (194_F)Use No. *[ AWG, 90_CwireUse 90_C wire, either No. *[ AWG Cu or No.
* The wire size for 60_C (140_F) wire is not required to be included in the marking. If included, the wire size is based on ampacities for the
wire given in Table 310-16 of the National Electrical Coder, in ANSI/NFPA 70, and on 115% of the maximum current that the circuit carries
under rated conditions. The National Electrical Coder is a registered trademark of the National Fire Protection Association, Inc.
[ Use the larger of the following conductors: the same size conductor as that used for the temperature test or one selected using the
guidelines in the preceding footnote.
Use No. * AWG, 60_Cwireor
use No. * AWG, 75_Cwire
Use 60_C wire, either No. * AWG Cu, or No. *
AWG Al or use 75_C wire, either No. * AWG
Cu or No. * AWG Al
AWG Al
*[ AWG Al
*[ AWG Al
Use 60_Cwire,No.*AWGor
use 75_Cwire,No.*AWG
Use 60_Cwire,No.*AWG
Use 75_Cwire,No.*[ AWG
Use 90_Cwire,No.*[ AWG
Figure 1-15 Terminal Markings for Various Temperature Ratings and Conductors
The National Electrical Coder is a registered trademark of the National Fire Protection Association, Inc.
TP-6803 6/1521Section 1 Installation
Page 22
1.9.1Grounding
1.9.3Field-Connection Terminal Block
Ground the generator set. The grounding method
must comply with NEC and local codes. Connect the
grounding cable to the generator set ground terminal
GND on the field-connection terminal block.
Generator sets are shipped with the generator neutral
bonded (connected) to the generator ground in the
junction box. The requirement for having a bonded
(grounded) neutral orungrounded neutral is determined
by the type of installation. At installation, the neutral can
be grounded at the generator set or lifted from the
ground stud and isolated if the installation requires an
ungrounded neutral connection at the generator. The
generator setwill operate properlywith the neutraleither
bonded to ground or isolated from ground at the
generator.
Various regulations andsite configurations including the
National Electrical Code (NEC), local codes, and the
type of transfer switch used in the application determine
the grounding of the neutral at the generator. NEC
Section 250 is one example that has a very good
explanation of the neutral grounding requirements for
generators.
The generator set is equipped with a field-connection
terminal block located in the air intake area near the
junction box. Leads have been factory-installed from
the junction box to the terminal block for easy field
wiring.
See Figure 1-17 for the terminal block location.
Remove the cover panel for access to the field
connections.
1
1.9.2Electrical Lead Entry
Drill or punch holes in the enclosure for the electrical
conduit in the locations shown in Figure 1-16.A
full-scale dimensioned template for the hole locations is
printed in Appendix B. See page 69.
1
2
5
4
Note: See Appendix B for a full-scale template
with dimensions.
1. Optional emergency stop switch location. Do not use to
route wiring.
2. Utility voltage electrical lead entry point (drill or punch)
3. Do not drill holes in this part of the panel
4. ATS signal electrical lead entry point (drill or punch)
5. 1/2 NPT female fuel inlet
3
ADV--8424
adv-8424
1. Cover panel. Remove for access to field-connection terminal
block.
Figure 1-17 Field-Connection Terminal Block
Location
Figure 1-16 Electrical Lead Entry Locations
TP-6803 6/1522 Section 1 Installation
Page 23
See Figure 1-18 for terminal block details. Refer to the
terminal block decal shownin Figure 1-19 for
connections and cable sizes. Also see the wiring
diagram in Section 3.
Route AC leads through flexible conduit. Ensure that
the leads and conduit do not interfere with the operation
of the generator set or obstruct the serviceareas. Route
low-voltage communication leads through separate
conduit.
Procedure
a. Route the network cable with other low-voltage
signalwiring(forexample,theRBUS
communication leads or engine start leads to
the transfer switch), in separate conduit from
the ACload leads. If the networkcable is longer
than 100 meters (328 ft.), use a repeater or
switch.
b. Use an RJ45 inline coupler to connect the
Ethernet cable to the cable in the customer
connection box. See Figure 1-18. The inline
coupler is included with the OnCue Plus kit.
1. Drill holes for the conduit fittings. See Figure 1-16
and Appendix B for the recommended electrical
inlet locations.Feed the cables through the
openings.
2. Connect the leads from the transfer switch
emergency source lugs to the L1, L2, and L3
connections on the generator set terminal block as
applicable for single or three-phase applications.
See Figure 1-18 and Figure 1-19.
3. Connect the neutral (L0) and ground (GRD) leads
from the ATS and the main panel to the
corresponding connection points on the terminal
block. See Section 1.9.1, Grounding.
4. Connect AC power source leads to the terminal
block connections labeled LINE, NEUTRAL and
GROUND. Connect the circuit to the load side of
the transfer switch. See Section 1.9.4 for more
information about the AC power requirement.
Note: AC power must be connected to maintain
the charge on the engine starting battery.
5. For connection of optional transfer switches, the
programmable interface module (PIM), and/or a
load shed kit, see Section 1.10.1.
Note: The ground lug near the terminal block
(item 3 in Figure 1-18) is used to connect
the shield on the communication cable for
the accessories.
6. If the OnCuer Plus Generator Management
System will be used with the generator set, run
category 5E network cable from the generator set
to the customer’s router or modem.
7. When connections to the terminal block are
complete, replace the cover plate.
4
3
2
1
GM84094
Note: The number of terminals varies for 1-phase
and 3-phase models. See Figure 1-19.
1. Low voltage RBUS communication to RXT ATS, PIM, load
shed kit, and/or APM.
2. Engine start connections from transfer switches other than
theRXT,ifused.
3. Ground connection for communication cable shield
4. Ethernet cable for optional OnCue Plus connection
5. AC load connections
6. AC power connections required for battery charging and
accessories
7. Connection decal; see Figure 1-19.
Figure 1-18 Field Connection Terminal Blocks
5
6
7
Note: The OnCue Plus Wireless kit allows
connection of the generator controller to the
customer’s wireless router without running a
network cable from the generator to the
customer’s router or modem. If the OnCue
Plus Wireless is used, follow the instructions
provided with the kit to install and set up the
wireless kit and proceed to step 7.
TP-6803 6/1523Section 1 Installation
Page 24
1-Phase, 1-Pole Circuit Breaker
1-Phase, 2-Pole Circuit Breaker
1.9.4AC Power Supply
The installer must connect AC power for the battery
charger (which is integral to the RDC2 controller) and
the optional accessories shown in Figure 1-20. The
power source must comply with state and local codes.
The power to the battery charger and accessories must
be backed upby the generator so thatpower is available
at all times.
Be sure to disconnect power at the distribution panel
before makingthe connections. Connect power leadsto
the AC power connection points labeled LINE,
NEUTRAL, and GROUND on the field-connection
terminal block. Connect the circuit to the load side of the
transfer switch so that it is backed up by the generator.
See Figure 1-18 and the wiring diagrams in Section 3 for
connection details.
Power Requirement, Max.
Equipment
Battery charger
(standard)
Carburetor heater
(optional)
Battery heater (optional)
Fuel regulator heater
(optional; available for
20RESA/RESAL/RESC/
RESCL only)
WattsVolts at 50/60 Hz
50100--120 VAC
50200--250 VAC
37
37
50
50
60100--120 VAC
100200--250 VAC
100--120 VAC
200--250 VAC
100--120 VAC
200--250 VAC
3-Phase
Figure 1-19 Terminal Block Connection Decals
Figure 1-20 Power Requirements
TP-6803 6/1524 Section 1 Installation
Page 25
1.10 ATS and Accessory
Communication Connections
Thefollowingsectionscovercommunication
connections fromthe generator setto automatic transfer
switches and RBUS accessories,including the
programmable interface module (PIM) and the load
shed kit.
1.10.1 Transfer Switch Connection
Connect the ATS or remote start/stop switch. Connect
the load leads from the generator set to the Emergency
source lugs onthe ATS.Route low-voltage
communication leads through separate conduit from the
AC power and load leads. All connections must comply
with applicable state and local codes.
Note: Do not use the Kohlerr Model RRT transfer
switch with the RESA/RESAL or RESC/RESCL
generator sets covered in this document.
1
Communication connections for a Model RXT
transfer switch
One Model RXT transfer switch can be connected to the
generator set.See Figure 1-21.Use shielded,
twisted-pair communication cable to connect P10-1
through P10-4 on the transfer switch interface module to
the generatorset terminal block connections A, B, PWR,
and COM. See Section 1.10.2 for the communication
cable recommendations and maximum cable length.
Note: Connections 3 and 4 on the generator set are not
used with the Model RXT transfer switch.
Engine start connection for other transfer
switches or a remote start/stop switch
Connect the engine start leads from the transfer switch
or remote start switch to terminals 3 and 4 on the
terminal block. See Figure 1-22. Route the engine start
leads through separate conduit from the AC power and
load leads.
2
Generator Set
RBUS
12 VDC
GND
PWR
COM
A
B
4
3
A
B
PWR
COM
3
4
A
B
PWR
COM
4
RXT*
Note: Generator set terminal block connections 3 and 4 are NOT USED with the Model RXT ATS.
* RXT transfer switch with standard or combined interface/load management board.
1. Generator set terminal block. See Figure 1-17 for location. Check the decal on the generator set for terminal block connections.
2. Connect one end of each cable shield to GROUND at the generator set.
3. Communication cable Belden #9402 or equivalent 20 AWG shielded, twisted-pair cable. See Section 1.10.2, Cable Specifications.
4. Leave one end of each cable shield disconnected. If accessory modules (PIM or load shed kit) are connected, see Section 1.10.3.
Figure 1-21 Model RXT Transfer Switch Communication Connection to Generator Set Terminal Block
TP-6803 6/1525Section 1 Installation
Page 26
Generator Set
1
A
B
PWR
COM
4
3
1. Generator Set Terminal Block. See the dimension drawings in Section 3 for location. Check the decal on the generator set for terminal
block connections.
2. Engine start leads 3 and 4. See the ATS manual for cable size specifications.
2
ATS
(with engine
start contacts)
Figure 1-22 Engine Start Connections with Transfer Switch Models other than Model RXT
1.10.2 Communication Cable
Specifications
D For the longer cable runs shown inthe last tworows of
Figure 1-23, use 12 or 14 AWG cable for PWR and
COM, and use the 20 AWG communication cable
RBUS Connections A and B
For the RBUS communication connections A and B to
the optional RBUS modules, u se 20 AWG shielded,
specified above for the A and B connections only. In
this case, single-pair communication cable such as
Belden #8762 can be used for the A and B
connections.
twisted-pair communication cable.Belden #9402
(two-pair) or Belden #8762 (single-pair) or equivalent
cable is recommended. Optional RBUS modules can
include the Model RXT transfer switch, RXT combined
interface/loadmanagementboard,automatic
paralleling module (APM), programmable interface
module (PIM), and/or the load shed kit for the RDT or
RXT transfer switch.
For outdoor installations, including those with buried
cables and/or conduit, use outdoor-rated Belden
#1075A or equivalent 20 AWG shielded, twisted-pair
communication cable.
1.10.3 System Connections with
Accessory Modules
See Figure 1-24 through Figure 1-28 for connection
options to RBUS accessory modules. Note the cable
shield connections shown in Figure 1-24.
Note: Refer to the installation instructions provided with
the automatic paralleling module (APM) for
RBUS connections to the APM.
The maximum cable length depends on the number of
RBUS modules connected. See Figure 1-23 for the
PWR and COM Connections
maximum cable lengths with 1, to 4 modules per cable
run.
For the PWR and COM connections, the cable size and
maximum cable length depends on the number of
modules connected. See Figure 1-23.
Note: A model RXT transfer switch with combined
interface/load management board acts as two
RBUS modules: one RXT transfer switch and
D For short cable runs shown in the first two rows of
one load management device.
Figure 1-23,useonepairinthetwo-pair
communication cable for the A and B connections,
and use the second pair for the PWR and COM
Power Relay Modules are not RBUS modules and do
not add to the number of modules in Figure 1-23.
connections.
tp6803
TP-6803 6/1526 Section 1 Installation
Page 27
Maximum length per run, meters (ft.)
Number of Modules (RXT, APM, PIM, and/or load management device) per Run
Cable (TB1-- PWR and COM)
Belden #9402 or equivalent 20AWG
for indoor installations
Belden #1075A or equivalent 20AWG
for outdoor installations or buried
1 Module2 Modules3 Modules4 Modules
46(150)15(50)5(17)Do not use 20AWG
for PWR and COM
46(150)15(50)5(17)Do not use 20AWG
for PWR and COM
cables
14 AWG *
12 AWG *
* Use 12 or 14 AWG cable for PWR and COM connections only. For RBUS connections A and B, use shielded, twisted pair communication
cable specified above.
137(450)137(450)107(350)107(350)
137(450)137(450)137(450)137(450)
Figure 1-23 Total Cable Lengths for PWR and COM Connections
Generator Set
RBUS
12 VDC
1
GND
B
PWR
COM
4
3
2
4
3
RXT*
A
A
B
PWR
COM
A
B
PWR
COM
A
B
PWR
COM
PIM
A
B
PWR
COM
A
B
PWR
COM
Note: Connec t A to A, B to B, PWR to PWR, and COM to COM.
See Section 1.10.2, Cable Specifications.
* RXT transfer switch with standard or combined interface/load management board.
Do not use a load shed kit with a combined interface board.
1. Generator set terminal block. See Figure 1-17 for location. Check the decal on the generator set for terminal block connections.
2. Connect one end of each cable shield to GROUND at the generator set.
3. Communication cable Belden #9402 or equivalent 20 AWG shielded, twisted-pair cable.
4. Connect shields together as shown.
5. Leave one end of each cable shield disconnected at the last device.
Figure 1-24 Accessory Module Communication Connection Details
TP-6803 6/1527Section 1 Installation
5
A
B
PWR
COM
Load
Shed
Kit
5
Page 28
2
4
GND
3
RXT*
Generator Set
RBUS
12 VDC
1
A
B
PWR
COM
4
3
A
B
PWR
COM
A
B
PWR
COM
A
B
PWR
COM
6
PIM
A
B
PWR
COM
5
A
B
PWR
COM
A
B
PWR
COM
Load
Shed
Kit
Note: Connec t A to A, B to B, PWR to PWR, and COM to COM.
See Section 1.10.2, Cable Specifications.
* RXT transfer switch with standard or combined interface/load management board.
Do not use a load shed kit with a combined interface board.
1. Generator set terminal block. See Figure 1-17 for location. Check the decal on the generator set for terminal block connections.
2. Connect one end of each cable shield to GROUND at the generator set.
3. Communication cable Belden #8762 or equivalent 20 AWG shielded, twisted-pair cable (one pair).
4. Connect shields together as shown.
5. Leave one end of each cable shield disconnected at the last device.
6. 12 AWG or 14 AWG leads for PWR and COM.
Figure 1-25 Accessory Module Connections with 12--14 AWG Power Leads
TP-6803 6/1528 Section 1 Installation
Page 29
Generator Set
RXT ATS
Termi n a l
Block
Notes:
D See Figure 1-17 for terminal block location on generator set.
Check the decal on the generator set for terminal block
connections.
D See Section 1.10.2, Cable Specifications (3 runs with 1 module
each shown).
D See Figure 1-24 for communication connection detail (A and B,
PWR and COM).
D Use splices or wire nuts to collect multiple leads for connection to
the generator set terminal block. See Figure 1-27.
Figure 1-26 Accessory Module Connections (three cable runs with one module each)
1
2
Generator Set
RBUS
12 VDC
A
B
PWR
COM
4
3
Load
Shed
Kit
PIM
tp6803
3
A
B
PWR
COM
3
A
B
PWR
COM
SHIELDED
CABLE
SHIELDED
CABLE
1. Generator Set Terminal Block. See the dimension drawings in Section 3 for location. Check the decal on the generator set for terminal
block connections.
2. Splice.
3. Connect all of the shield leads on this end to GROUND at the generator set.
Figure 1-27 Multiple Connections to the Generator Set
TP-6803 6/1529Section 1 Installation
tp6803
Page 30
Generator Set
Termi n a l
Block
RXT ATS
Notes:
D See Figure 1-17 for terminal block location on generator
set. Check the decal on the generator set for terminal
block connections.
D See Section 1.10.2, Cable Specifications.
D See Figure 1-24 for communication connection detail (A
and B, PWR and COM).Connect the cable shield to
ground at the generator set.
PIM
Load
Shed
Kit
D Use splices or wire nuts to collect multiple leads for
connection to the generator set terminal block. See
Figure 1-27.
Figure 1-28 Accessory Module Connections (two cable runs with one and two modules shown)
tp6809
TP-6803 6/1530 Section 1 Installation
Page 31
1.11 Battery
WARNING
Battery acid cleanup. Battery acid can cause severe
injury or death. Battery acid is electrically conductive and
corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking
soda) to a container with4L(1gal.)ofwaterandmixthe
neutralizing solution. Pour the neutralizing solution on the
spilled battery acid and continue to add the neutralizing
solution to the spilled battery acid until all evidence of a
chemical reaction (foaming) has ceased. Flush the resulting
liquid with water and dry the area.
Sulfuric acid in batteries.
Can cause severe injury or death.
Wearprotectivegogglesand
clothing.Battery acid may cause
blindness and burn skin.
WARNING
Explosion.
Can cause severe injury or death.
Relays in the battery charger
cause arcs or sparks.
Locate the battery in a well-ventilated
area. Isolate the battery charger from
explosive fumes.
Battery electrolyte is a diluted sulfuric acid. Battery acid
can cause severe injury or death. Battery acid can cause
blindness and burn skin. Always wear splashproof safety
goggles, rubber gloves, and boots when servicing the battery.
Do not open a sealed battery or mutilate the battery case. If
battery acid splashes in the eyes or on the skin, immediately
flush the affected area for 15 minutes with large quantities of
clean water. Seek immediate medical aid in the case of eye
contact. Never add acid to a battery after placing the battery in
service, as this may result in hazardous spattering of battery
acid.
Battery gases. Explosion can cause severe injury or
death. Battery gases can cause an explosion. Do not smoke
or permit flames or sparks to occur near a battery at any time,
particularly when it is charging. Do not dispose of a battery in a
fire.To prevent burns and sparks that could cause an
explosion, avoid touching the battery terminals with tools or
other metal objects. Remove all jewelry before servicing the
equipment. Discharge static electricity from your body before
touching batteries by first touching a grounded metal surface
away from the battery. To avoid sparks, do not disturb the
battery charger connections while the battery is charging.
Always turn the battery charger off before disconnecting the
battery connections. Ventilate the compartments containing
batteries to prevent accumulation of explosive gases.
Battery short circuits. Explosion can cause severe injury
or death.Short circuits can cause bodily injury and/or
equipment damage. Disconnect the battery before generator
set installation or maintenance. Remove all jewelry before
servicing the equipment. Use tools with insulated handles.
Remove the negative (--) lead first when disconnecting the
battery.Reconnect the negative (--) lead last when
reconnecting the battery. Never connect the negative (--)
battery cable to the positive (+) connection terminal of the
starter solenoid. Do not test the battery condition by shorting
the terminals together.
Connecting the battery and the battery charger.
Hazardous voltage can cause severe injury or death.
Reconnect the battery correctly, positive to positive and
negative to negative, to avoid electrical shock and damage to
the battery charger and battery(ies).Have a qualified
electrician install the battery(ies).
TP-6803 6/1531Section 1 Installation
Page 32
Battery Description
Battery Installation Procedure
Starting batteries are usually the lead-acid type. Use a
12-volt group 51 battery with a minimum rating of 500
cold cranking amps at 0_F. The generator set uses a
negative ground with a 12-volt engine electrical system.
See Figure 1-29 for battery connections. Make sure
that the battery is correctly connected and the terminals
are tight.
Note: The generator set will not start and circuit board
damage may occur if the battery is connected in
reverse.
See the dimension drawing in Section 3 for the engine
starting battery location on the air intake side of the
generator set. Standard battery cables provide easy
connection to the battery.
1
1. To positive (+) terminal on starter solenoid.
2. To ground (--) terminal on or near starter motor.
2
EZ-273000-J
Figure 1-29 Typical Battery Connection
1. Ensure that the starting battery is fully charged
before placing the battery in service.
2. Clean the battery posts and/or adapters if
necessary.
3. Install the battery post adapters, if needed.
4. Place the battery in the housing.
5. Connect the positive (+) lead to the engine starting
battery.
6. Connect the negative (--) lead to the engine starting
battery.
Refer to the generator set operation manual and the
batterymanufacturer’sinstructionsforbattery
maintenance instructions.
When power isapplied to the RDC2/DC2 controller (that
is, when the battery is connected), you will be prompted
to set the date and time, and then to set the exerciser.
See Section 1.13 and the generator set operation
manual for instructions.
If the battery is disconnected for service orreplacement,
the exercise settings on the RDC2/DC2 controller are
lost. Set the exerciserafter installing and connectingthe
battery. See Section 1.13, Set Exerciser.
Use the following procedure to install and connect the
battery.
TP-6803 6/1532 Section 1 Installation
Page 33
1.12 Prestart Installation Check
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
WARNING
Moving parts.
Review the entire installation section. Inspect all wiring
and connections to verify that the generator set is ready
for operation. Check all items in the following Prestart
Checklist.
Prestart Checklist
Air Cleaner. Check that a clean air cleaner element is
installed to prevent unfiltered air from entering the
engine. See the generator set operation manual for
instructions.
Air Inlets. Check for clean and unobstructed air inlets.
Battery. Check for tight battery connections. Consult
the battery manufacturer’s instructions regarding
battery care and maintenance.
Enclosure.Check that all enclosure panels and
internal baffling are in place.
Carbon monoxide.
Cancauseseverenausea,
fainting, or death.
The exhaustsystemmustbe
leakproof and routinely inspected.
Generator set operation. Carbon monoxide can cause
severe nausea, fainting, or death. Carbon monoxide is an
odorless, colorless, tasteless, nonirritating gas that can cause
death if inhaled for even a short time. Avoid breathing exhaust
fumes when working on or near the generator set. Never
operate the generator set inside a building. Never operate the
generator set where exhaust gas could seep inside or be
drawn into a potentially occupied buildingthrough windows, air
intake vents, or other openings.
Carbon monoxide symptoms. Carbon monoxide can
cause severe nausea, fainting, or death. Carbon monoxide
is a poisonous gas present in exhaust gases.Carbon
monoxide is an odorless, colorless, tasteless, nonirritating gas
that can cause death if inhaled for even a short time. Carbon
monoxide poisoning symptoms include but are not limited to
the following:
D Light-headedness, dizziness
D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms and carbon monoxide
poisoning is possible, seek fresh air immediately and remain
active. Do not sit, lie down, or fall asleep. Alert others to the
possibility of carbon monoxide poisoning.Seek medical
attention if the condition of affected persons does not improve
within minutes of breathing fresh air.
Exhaust System.Check for exhaust leaks and
blockages. Check the muffler condition.
D Inspect the exhaust system components for cracks,
leaks, and corrosion. Check for tight exhaust system
connections.
D Check for corroded orbroken metal parts andreplace
them as needed.
D Check that the exhaust outlet is unobstructed.
Oil Level. Maintain the oil level at or near, not over, the
full mark on the dipstick.
Operating Area. Check for obstructions that could
block the flow of cooling air. Keep the air intake area
clean. Do not leave rags, tools, or debris on or near the
generator set.
TP-6803 6/1533Section 1 Installation
Page 34
1.13 Set the Exerciser
1.13.2 DC2 Controller
Set the exerciser to automatically run the generator set
on the desired day and time every week or every two
weeks. See the generator set Operation Manual for
detailed descriptions of the exercise operation.
1.13.1 RDC2 Controller
When power isapplied to the RDC2 controller (when the
battery or the utility power for the battery charger is
connected), you will be prompted to set the date and
time, and then to set the exerciser.
The first setting will flash. Press the Up and Down arrow
buttons to change the setting. Press Select to save the
setting and move on to the next. Repeat until the date,
time, and exercise are set and the controller display
shows the main menu. See the generator set Operation
Manual for more detailed instructions to set the date and
time and set the exerciser.
Press AUTO to place the generator set controller into
automatic mode.
To set the exerciser on the DC2 controller, first press
AUTO to place the controller into automatic (standby)
mode. Then press and hold the Exercise button. The
generator set will start and run a 20-minute unloaded
cycle exercise. The generator set will run automatically
for 20 minutes at the same time every 7 days. See the
generator set Operation Manual for more information.
1.13.3 Loaded Exercise
In order to set a loaded exercise using the RDC2 or DC2
controller, a Kohlerr Model RXT transfer switch must be
connected. See the generator set operation manual for
instructions to set a loaded exercise.
To set a loaded exerciseon a generator set connected to
a transfer switch other than a Model RXT, use the
transfer switch controller to set the exercise. Refer to
the transfer switch operation manual for instructions.
Date:
05Dec2011
Time:
08:31am
Next Exercise:
08:31a 12Dec2011
Setting will flash.
Press the up and down arrow
buttons to change the setting.
Press Select to save the
setting.
Figure 1-30 Set Time, Date, and Exercise (RDC2)
tp6803
TP-6803 6/1534 Section 1 Installation
Page 35
2.1Introduction
This section describes some of the accessories that are
available for the generator sets. Have accessories
installed by an authorized distributor/dealer or a
licensed electrician. This document does not contain
installation instructions for accessories.Follow the
installation instructions provided with each kit.
Section 2 Accessories
1
1
Use separate conduit for AC and DC leads to reduce the
possibility of electricalinterference. Verifythat the leads
and conduit do not interfere with the operation of the
generator set or obstruct the service areas. Verify that
the electrical installation complies with the National
Electrical Code (NEC) and all applicable local codes.
See the wiring diagrams in Section 3 for more
informationregardinggeneratorsetelectrical
connections.
2.2Programmable Interface
Module (PIM)
The optional programmable interface module (PIM)
provides two programmable inputs and six dry contact
outputs, four of which are programmable. See TT-1584
for PIM installation and connection instructions. Also
see Section 1.10 of this manual for connection to the
generator set.
The default settings for the inputs and outputs are
shown in Figure 2-2. To change the input and output
settings, use a personal computer running Kohlerr
SiteTecht software. See TP-6701, SiteTech Software
Operation Manual, for instructions.
KohlerOnCuer PluscanbeusedtoactivelycontrolPIM
outputs. See the OnCue Plus Operation Manual for
instructions.
3. RBUS communication connection to generator set terminal
block TB2
Figure 2-1 Optional PIM
PIM ConnectionFactory Default Setting
Input 1None
Input 2None
Output 1 (Relay 1)Run
Output 2 (Relay 2)Common Fault
Output 3 (Relay 3)Low Battery Voltage
(Programmable)
Output 4 (Relay 4)Not in Auto (Programmable)
Output 5 (Relay 5)Cooldown (Programmable)
Output 6 (Relay 6)Normal Source Failure
(Programmable)
TP-6803 6/1535Section 2 Accessories
Figure 2-2 PIM Inputs and Outputs
Page 36
2.3Load Management Devices
Two optional load management devices are available
for use with single-phase generator sets and a model
RXT or RDT transfer switch:
D The optional Load Shed Kit mounts inside a Model
RDT or RXT transfer switch. Figure 2-3 shows the
load shed assembly.
D The combined interface/load management board is
available for the Model RXT transfer switch.
The devices provide an automatic load management
system to comply with Section 702.5 of NEC 2008. The
installer is responsible for ensuring that the power
system installation complies with all applicable state
and local codes.
Verify that customer-provided equipment complies with
applicable local and national electrical codes.
For detailed installation and connection instructions,
see the installation instructions provided with the load
shed kit or the Operation/Installation Manual for the
Model RXT transfer switch.
1
2
3
Note: Theloadmanagement devicesareonly
compatible with single-phase generator sets.
With a load management system, less critical
appliances can be powered by the generator set when
the more important appliances are not running, allowing
the use of a smaller generator set than would be needed
to run all of the building’s electrical equipment at the
same time.
The load shed kit automatically manages up to six
residential loads:
D Up to four normally closed power relays can be
connected through normally open relay contacts on
the circuit board. See the load shed kit installation
instructions for relay specifications. Kohlerr Power
Relay Modules are recomended.
D Two relays are included on the load management
devicetocontroltwoindependentheating,
ventilation, and air conditioning (HVAC) loads.
Note: Connect only non-essential loads to the load
shed kit.
1. Terminal block TB10
2. Load control circuit board
3. Mounting bracket
Note: Kit includes current transformer (CT), not shown.
GM88281
Figure 2-3 Load Shed Assembly GM88281-1
(mounts inside the transfer switch
enclosure)
2.3.1Power Relay Module
The power relay module kit contains one 50 amp
normally closed relay with connecting lugs in a NEMA
type 3R enclosure. Connect up to four (4) power relay
modules to the load management devices listed above.
The power relay modules can be mounted indoors or
outdoors. Two (2) 120 VAC loads(shed simultaneously)
or a single 240 VAC load can be wired to each relay.
For detailed installation and connection instructions,
see the installation instructions provided with the power
relay module kit.
The load managementdevice receives commands from
the RDC2 or DC2 generator controller and energizes or
de-energizes the appropriate load relays to add or shed
non-critical loads according to their priority.
An adequate electrical supply is required for operation
of the customer-supplied power relays connected to the
load shed kit. Check the electrical requirements of the
customer-provided equipment prior to installation to
determine the wire size and circuit protection required.
Figure 2-4 Power Relay Module
TP-6803 6/1536 Section 2 Accessories
Page 37
2.4Regulator Heater
WARNING
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
Servicing the engine heater. Hot parts can cause minor
personal injury or property damage. Install the heater
before connecting it to power. Operating the heater before
installation can cause burns and component damage.
Disconnect power to the heater and allow it to cool before
servicing the heater or nearby parts.
The optional regulator heater kit is designed for Model
20RESA/RESC and 20RESAL/RESCL generator sets.
The regulator heater kit is recommended in addition to
the carburetor heater for reliable engine starting in
temperatures below --18_C(0_F). See Figure 2-5 for
heater specifications. Order the 120 V or 240 V kit as
appropriate for your application.See specification
sheet G6-126 for kit details.
The fuel regulator heater requires a source of AC power.
Verify that AC power is connected to the generator set
as described in Section 1.9. The circuit must be backed
up by the generator set to provide power at all times.
120 VAC generator sets are equipped with one or two
120 VAC receptacles. Use an adapter or splitter to
connect more than one accessory to the receptacle.
240 volt heater kits use a 3-pin power connector.
Generator sets built after 10/9/2013 with serial numbers
SGM327VFJ or later have a knockout under the
controller for the 240 VAC power connector. 240 volt
fuel regulator heater kits include an adapter harness to
allow connection of two AC accessories.
1
2
120 V Kit240 V Kit
Heater rating120 VAC, 60 W
50/60 Hz
Thermostat
Pad diameter127 mm (5 in.)
Cord length610 mm (24 in.)
4_C/13_C (40_F/55_F) Snap action
240 V, 100W
50/60 Hz
Figure 2-5 Regulator Heater Specifications
The fuel regulator heater is a 127 mm (5 in.) diameter
round heating pad with a snap action thermostat and a
power cord. Figure 2-6 and Figure 2-7 show the heater
installed on the fuel regulator, which is located on the air
intake side of the generator set. To install the regulator
heater kit, follow the instructions in TT-1569, provided
with the kit.
Knockout Detail
Note: Adapter harness for multiple accessories not shown.
1. 240 VAC power connection (see knockout detail)
2. Fuel regulator heater pad
GM79141-E
Figure 2-6 Model 20RESA/RESAL/RESC/RESCL
240 Volt Kit Power Connection
TP-6803 6/1537Section 2 Accessories
Page 38
1
1. Fuel regulator heater pad
2. Receptacle with adapter (120 VAC kits)
Note: See Figure 2-6 for 240 volt power connection.
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
Servicing the engine heater. Hot parts can cause minor
personal injury or property damage. Install the heater
before connecting it to power. Operating the heater before
installation can cause burns and component damage.
Disconnect power to the heater and allow it to cool before
servicing the heater or nearby parts.
A carburetor heater is recommended for improved cold
starting in locations where the ambient temperature
drops below 0_C(32_F).The carburetor heater
prevents condensationand carburetor icing. Theheater
turns on when the temperature at the thermostat falls
below approximately 4_C(40_F) and turns off when the
temperature rises above approximately 16_C(60_F).
The carburetor heaters are shown in Figure 2-9.
To install the carburetor heater, follow the instructions
provided with the kit. Figure 2-10 shows the installed
carburetor heater kit installed for a 14 kW generator set.
Figure 2-11 shows the location for the carburetor heater
kit on a 20 kW generator set.
Carburetor Heater for 14 kW Models
1
2
Carburetor Heater for 20 kW Models
1. Power plug
2. Thermostat
3. Heater
240 Volt Plug
Figure 2-9 Carburetor Heaters
1
2
GM19463
3
GM57968
Verify that AC power is connected to the generator set
as described in Section 1.9. The circuit must be backed
up by the generator set to provide power at all times.
The heater thermostat is installed in the cord.
Figure 2-9 shows the location of the thermostat on the
power cord. The heater power cord and thermostat are
located in the generator set housing air intake area/
battery compartment.
For 120 volt models, plug the carburetor heater into one
of the 120 VAC receptacles provided.
240 volt kits use a 3-pin power connector. Generator
sets built after 10/9/2013 have a knockout in the
bulkhead for the 240 VAC power connector.See
Figure 2-12.
Kit Number120 Volt Kits240 Volt Kits
Voltage120 VAC
Thermostat ON
Thermostat OFF
50/60 Hz
4 ± 4_C(40± 7_F)
16 ± 3_C(60± 5_F)
240 VAC/60 Hz
230 VAC/50 Hz
Figure 2-8 Carburetor Heater Specifications
tp6195
1. Carburetor heater (air cleaner removed to show heater)
2. Carburetor heater power cord
Figure 2-10 Carburetor Heater for 14 kW Models
TP-6803 6/1539Section 2 Accessories
Page 40
1
Detail view:
adv-8424
1
2
3
GM57969-C
1. 240 VAC carburetor heater power cord
2. 240 VAC connector installed in bulkhead knockout
3. 120VAC receptacle location (for reference)
Figure 2-12 240 Volt Power Connection for
Carburetor Heaters
tt1482b
2
1. Carburetor heater location under air cleaner. Insert from the
back of the generator set.
2. Carburetor heater
Figure 2-11 Carburetor Heater Location on 20 kW
Models
TP-6803 6/1540 Section 2 Accessories
Page 41
2.6Battery Heater
2
WARNING
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
Servicing the engine heater. Hot parts can cause minor
personal injury or property damage. Install the heater
before connecting it to power. Operating the heater before
installation can cause burns and component damage.
Disconnect power to the heater and allow it to cool before
servicing the heater or nearby parts.
Optional 120 VAC and 240 VAC battery heater kits are
available. The heater is thermostatically controlled.
See Figure 2-13.
Wrap the heater around the battery and secure the cord
using cable ties. See Figure 2-14. Plug the power cord
into an AC receptacle.
For 120 volt models, plug the carburetor heater into one
of the 120 VAC receptacles on the generator set.
240 volt kits use a 3-pin power connector. Generator
sets built after 10/9/2013 have a knockout in the
bulkhead for the 240 VAC power connector. The 240
volt battery heater kit includes an adapter harness that
allows connection of up to three accessories.
1
3
GM92406
Note: Adapter harness for multiple accessories not shown.
1. Battery heater
2. Battery (not included in battery heater kit)
3. Power cord for 240 volt kits
Figure 2-14 Battery Heater
2.7Emergency Stop Button
An emergency stop button is available as a loose kit.
See the instructions provided with the kit for installation
and connection procedures.
Battery Heater Specifications
Heater wrap voltage100--120 VAC or
200--240 VAC
50/60 Hz
Heater wrap rating, Watts50
Thermostat temperatures:
On
Off
Battery wrap length, mm (in.)711 (28)
Power cord length, mm (in.)1829 (72)
18_C(65_F)
27_C(80_F)
Figure 2-15 Optional Emergency Stop Pushbutton
Figure 2-13 Battery Heater Specifications
TP-6803 6/1541Section 2 Accessories
Page 42
2.8OnCue Plus Generator
Management System
The OnCuer Plus Generator Management System
allows monitoring and control of your generator set from
a personal computer, smart phone, or tablet. OnCue
Plus can also be configured to send email or text
message notifications in the event of a generator set
fault. Both a network cable connection version (OnCue
Plus) and a wireless version (OnCue Plus Wireless) are
available. See TP-6928, OnCue Plus Operation
Manual, for instructions.
OnCue Plus
OnCue Plus is available separately as a loose kit. Use
category 5E network cable to connect the RDC2
controller to the customer-supplied Ethernet router or
modem. Route the cable with other low-voltage signal
wiring (for example, the RBUS communication leads or
engine start leads to the transfer switch), in separate
conduit from the AC load leads. If the network cable is
longer than 100 meters (328 ft.), use a repeater or
switch.
Recommended: Use a laptop computer to verify the
network connection before connecting to the generator
set.
Checking the network connection
1. Check for and turn OFF any wireless connections
to the laptop.
2. Connect the network cable to the laptop. Connect
the other end of the network cable to the
customer’s router or modem.
Connect to the Ethernet cable in the customer
connection area of the generator set. See Figure 2-16.
Use an RJ45 inline coupler, provided with the OnCue
Plus kit, to connect the customer’s Ethernet cable to the
cable in the customer connection box.
1
GM84094
1. Ethernet cable for optional OnCue Plus connection
Figure 2-16 Network Connection for OnCue Plus
OnCue Plus Wireless
The OnCue Plus Wireless kit allows connection of the
generator set to the Internet through the customer’s
wireless router without running a network cable from the
generator to the customer’s Ethernet router. Follow the
instructions provided with the kit to install and set up the
wireless kit.
3. Verify the Internet connection by opening your web
browser and going to www.kohlerpower.com or
any known website.
4. After verifying the connection through the network
cable, disconnect the network cable from the
laptop and turn the laptop wireless connections
back on.
TP-6803 6/1542 Section 2 Accessories
Page 43
2.9PowerSync Automatic
Paralleling Module (APM)
The PowerSyncr Automatic Paralleling Module (APM)
allows the use of two Model 14RESA or two
20RESA/B/C/D generator sets in a single-phase
paralleling system to supply power to one building or
site. See Figure 2-17.
The APM provides a common connection point for
paralleling generators and permits individual control of
thegeneratorconnections,allowingfor
synchronization,redundancy,andgenerator
management.
Generator management provides these features and
benefits:
D Generator management runs one generator set
when power requirements are low, and automatically
starts, synchronizes, and connects the second
generator set when the load increases.
D Longer generator life: Smart generator management
automatically operates the generator with the lowest
operating hours first, splitting the run time evenly
between the two generator sets and extending the life
of both units.
D Redundancy: If one generator set r equires service or
even fails, the other generator set is still available to
provide power to your critical electronics.
Automatic paralleling requires:
D Two single-phase generator sets as shown above
D RDC2 paralleling firmware version 105.4 or higher on
each generator set.Download the paralleling
firmware from TechTools.
D One Model RXT automatic transfer switch (ATS)
D One Automatic Paralleling Module (APM) kit
D Apersonalcomputer(laptop)withKohlerr
SiteTecht software version 3.5 or higher is required
for system setup.
D A load management device is required if one
generator set cannot support the maximum totalload.
The load management device (load shed kit or RXT
combinedinterface/loadmanagementboard)is
necessary in order to shed non-criticalloads in the event
that one generator set shuts down and the other
generator set cannot support all of the loads.
See TT-1596, provided with the APM, for complete
installation instructions.The APM and associated
equipment must be installed b y a Kohlerr trained and
authorized distributor or dealer.
If the APM is not installed within sight of the generator
sets, local codes may require the installation of circuit
breakers near the APM.Circuit breaker kits are
available for installation inside the APM enclosure. See
TT-1596 for the circuit breaker kit numbers for the
14RESA and 20RESA/B/C/D generator sets.
D Dual fuels: Allows operation of one generator set on
natural gas and the other on LPG, if desired.
D Simultaneous exercise: Setting the exercise time
and date on one generator set schedules both
generator sets to exercise at the same time.
D Power during generator service: Customer override
allows maintenance or service to one generator set
while the other continues to run.
The following combinations of single-phase
generator sets can be paralleled:
D Two single-phase model 14RESA generator sets
with the same 110/220, 115/230, 120/240, 220, 230,
or 240 volt configuration
D Two single-phase model 20RESA/B/C/D generator
sets with the same 110/220, 115/230, 120/240, 220,
230 or 240 volt configuration
zab26291
Figure 2-17 PowerSyncr Automatic Paralleling
Module
TP-6803 6/1543Section 2 Accessories
Page 44
Notes
TP-6803 6/1544 Section 2 Accessories
Page 45
Section 3 Drawings and Diagrams
Figure 3-1 lists the drawing numbers and page numbers.
Dimension DrawingsDrawing NumberPage
14/20RESA/RESAL Dimension D rawing:ADV-8424-H
DimensionsSheet 146
Maintenance item locationsSheet 247
Maintenance item locationsSheet 348
Location and clearance requirements, single unitSheet 449
Location and clearance requirements, parallel unitsSheet 550
20RESC/20RESCL Dimension Drawing:ADV-8754
DimensionsSheet 151
Maintenance item locationsSheet 252
Location and clearance requirements, single unitSheet 353
Location and clearance requirements, parallel unitsSheet 454
Wiring Diagrams
14/20RESA/RESAL Schematic DiagramADV-8706-C
1 phase, 2 pole circuit breakerSheet 155
1 phase, 1 pole circuit breakerSheet 256
3 phase, 3 pole circuit breakerSheet 357
14/20RESA/RESAL Wiring DiagramGM93298-C
1 phase, 2 pole circuit breakerSheet 158
1 phase, 1 pole circuit breakerSheet 259
3 phase, 3 pole circuit breakerSheet 360
20RESC/20RESCL Schematic DiagramADV-8771
1 phase, 2 pole circuit breakerSheet 161
1 phase, 1 pole circuit breakerSheet 262
3 phase, 3 pole circuit breakerSheet 363
20RESC/20RESCL Wiring DiagramGM96293
1 phase, 2 pole circuit breakerSheet 164
1 phase, 1 pole circuit breakerSheet 265
3 phase, 3 pole circuit breakerSheet 366
Figure 3-1 Drawings and Diagrams
TP-6803 6/1545Section 3 Drawings and Diagrams
Page 46
Figure 3-2 Dimension Drawing, 14/20RESA/RESAL, ADV-8424, Sheet 1 of 5
TP-6803 6/1546 Section 3 Diagrams and Drawings
Page 47
Figure 3-3 Dimension Drawing, 14/20RESA/RESAL, ADV-8424, Sheet 2 of 5
TP-6803 6/1547Section 3 Diagrams and Drawings
Page 48
Figure 3-4 Dimension Drawing, 14/20RESA/RESAL, ADV-8424, Sheet 3 of 5
TP-6803 6/1548 Section 3 Diagrams and Drawings
Page 49
Figure 3-5 Dimension Drawing, 14/20RESA/RESAL, ADV-8424, Sheet 4 of 5
TP-6803 6/1549Section 3 Diagrams and Drawings
Page 50
Figure 3-6 Dimension Drawing, 14/20RESA/RESAL, ADV-8424, Sheet 5 of 5
TP-6803 6/1550 Section 3 Diagrams and Drawings
Page 51
Figure 3-7 Dimension Drawing, Model 20RESC/20RESCL, ADV-8754, Sheet 1 of 4
TP-6803 6/1551Section 3 Diagrams and Drawings
Page 52
Figure 3-8 Dimension Drawing, Model 20RESC/20RESCL, ADV-8754, Sheet 2 of 4
TP-6803 6/1552 Section 3 Diagrams and Drawings
Page 53
Figure 3-9 Dimension Drawing, Model 20RESC/20RESCL, ADV-8754, Sheet 3 of 4
TP-6803 6/1553Section 3 Diagrams and Drawings
Page 54
Figure 3-10 Dimension Drawing, Model 20RESC/20RESCL, ADV-8754, Sheet 4 of 4
TP-6803 6/1554 Section 3 Diagrams and Drawings
Page 55
Figure 3-11 Schematic Diagram, 14/20RESA/RESAL, ADV-8706, Sheet 1 of 3
TP-6803 6/1555Section 3 Diagrams and Drawings
-
Page 56
Figure 3-12 Schematic Diagram, 14/20RESA/RESAL, ADV-8706, Sheet 2 of 3
-
TP-6803 6/1556 Section 3 Diagrams and Drawings
Page 57
Figure 3-13 Schematic Diagram, 14/20RESA/RESAL, ADV-8706, Sheet 3 of 3
Figure 3-17 Schematic Diagram, Model 20RESC/20RESCL, ADV-8771, Sheet 1 of 3
TP-6803 6/1561Section 3 Diagrams and Drawings
Page 62
Figure 3-18 Schematic Diagram, Model 20RESC/20RESCL, ADV-8771, Sheet 2 of 3
TP-6803 6/1562 Section 3 Diagrams and Drawings
Page 63
Figure 3-19 Schematic Diagram, Model 20RESC/20RESCL, ADV-8771, Sheet 3 of 3
TP-6803 6/1563Section 3 Diagrams and Drawings
Page 64
Figure 3-20 Wiring Diagram, Model 20RESC/20RESCL, GM96293, Sheet 1 of 3
TP-6803 6/1564 Section 3 Diagrams and Drawings
Page 65
Figure 3-21 Wiring Diagram, Model 20RESC/20RESCL, GM96293, Sheet 2 of 3
TP-6803 6/1565Section 3 Diagrams and Drawings
Page 66
Figure 3-22 Wiring Diagram, Model 20RESC/20RESCL, GM96293, Sheet 3 of 3
TP-6803 6/1566 Section 3 Diagrams and Drawings
Page 67
Appendix A Abbreviations
The following list contains abbreviations that may appear in this publication.
A, ampampere
ABDCafter bottom dead center
ACalternating current
A/Danalog to digital
ADCadvanced digital control;
adj.adjust, adjustment
ADVadvertising dimensional
Ahamp-hour
AHWTanticipatory high water
AISIAmerican Iron and Steel
ALOPanticipatory low oil pressure
alt.alternator
Alaluminum
ANSIAmerican National Standards
AOanticipatory only
APDCAir Pollution Control District
APIAmerican Petroleum Institute
approx.approximate, approximately
APUAuxiliary Power Unit
AQMDAir Quality Management District
ARas required, as requested
ASas supplied, as stated, as
ASEAmerican Society of Engineers
ASMEAmerican Society of
assy.assembly
ASTMAmerican Society for Testing
ATDCafter top dead center
ATSautomatic transfer switch
auto.automatic
aux.auxiliary
avg.average
AVRautomatic voltage regulator
AWGAmerican Wire Gauge
AWMappliance wiring material
bat.battery
BBDCbefore bottom dead center
BCbattery charger, battery
BCAbattery charging alternator
BCIBattery Council International
BDCbefore dead center
BHPbrake horsepower
blk.black (paint color), block
blk. htr.block heater
BMEPbrake mean effective pressure
bpsbits per second
br.brass
BTDCbefore top dead center
BtuBritish thermal unit
Btu/min.British thermal units per minute
CCelsius, centigrade
cal.calorie
CANcontroller area network
CARBCalifornia Air Resources Board
CAT5Category 5 (network cable)
CBcircuit breaker
CCcrank cycle
cccubic centimeter
CCAcold cranking amps
ccw.counterclockwise
CECCanadian Electrical Code
cert.certificate, certification, certified
cfhcubic feet per hour
analog to digital converter
drawing
temperature
Institute
Institute (formerly American
Standards Association, ASA)
suggested
Mechanical Engineers
Materials
charging
(engine)
cfmcubic feet per minute
CGcenter of gravity
CIDcubic inch displacement
CLcenterline
cmcentimeter
CMOScomplementary metal oxide
cu. in.cubic inch
cw.clockwise
CWCcity water-cooled
cyl.cylinder
D/Adigital to analog
DACdigital to analog converter
dBdecibel
dB(A)decibel (A weighted)
DCdirect current
DCRdirect current resistance
deg., degree
dept.department
dia.diameter
DI/EOdual inlet/end outlet
DINDeutsches Institut fur Normung
exh.exhaust
ext.external
FFahrenheit, female
FHMflat head machine (screw)
fl. oz.fluid ounce
flex.flexible
freq.frequency
FSfull scale
ft.foot, feet
ft. lb.foot pounds (torque)
ft./min.feet per minute
ftpfile transfer protocol
ggram
ga.gauge (meters, wire size)
gal.gallon
gen.generator
gensetgenerator set
GFIground fault interrupter
GND,
gov.governor
gphgallons per hour
gpmgallons per minute
gr.grade, gross
GRDequipment ground
gr. wt.gross weight
H x W x D height by width by depth
HChex cap
HCHThigh cylinder head temperature
HDheavy duty
HEThigh exhaust temp., high
hexhexagon
Hgmercury (element)
HHhex head
HHChex head cap
HPhorsepower
hr.hour
HSheat shrink
hsg.housing
HVACheating, ventilation, and air
HWThigh water temperature
Hzhertz (cycles per second)
IBCInternational Building Code
ICintegrated circuit
IDinside diameter, identification
IECInternational Electrotechnical
IEEEInstitute of Electrical and
IMSimproved motor starting
in.inch
in. H
in. Hginches of mercury
in. lb.inch pounds
Inc.incorporated
ind.industrial
int.internal
int./ext.internal/external
I/Oinput/output
IPinternet protocol
ISOInternational Organization for
Jjoule
JISJapanese Industry Standard
kkilo (1000)
Kkelvin
kAkiloampere
KBkilobyte (2
kgkilogram
ground
engine temp.
conditioning
Commission
Electronics Engineers
Oinches of water
2
Standardization
10
bytes)
TP-6803 6/15Appendix 67
Page 68
2
kg/cm
kgmkilogram-meter
kg/m
kilograms per square
centimeter
3
kilograms per cubic meter
kHzkilohertz
kJkilojoule
kmkilometer
kOhm, k kilo-ohm
kPakilopascal
kphkilometers per hour
kVkilovolt
kVAkilovolt ampere
kVARkilovolt ampere reactive
kWkilowatt
kWhkilowatt-hour
kWmkilowatt mechanical
kWthkilowatt-thermal
Lliter
LANlocal area network
L x W x H length by width by height
lb.pound, pounds
3
lbm/ft
pounds mass per cubic feet
LCBline circuit breaker
LCDliquid crystal display
LEDlight emitting diode
Lphliters per hour
Lpmliters per minute
LOPlow oil pressure
LPliquefied petroleum
LPGliquefied petroleum gas
LSleft side
L
wa
LWLlow water level
sound power level, A weighted
LWTlow water temperature
mmeter, milli (1/1000)
Mmega (10
3
m
3
m
3
m
units), male
cubic meter
/hr.cubic meters per hour
/min.cubic meters per minute
bytes)
MCCBmolded-case circuit breaker
MCMone thousand circular mils
meggarmegohmmeter
MHzmegahertz
mi.mile
milone one-thousandth of an inch
min.minimum, minute
misc.miscellaneous
MJmegajoule
mJmillijoule
mmmillimeter
mOhm, mmilliohm
MOhm, Mmegohm
MOVmetal oxide varistor
MPamegapascal
mpgmiles per gallon
mphmiles per hour
MSmilitary standard
msmillisecond
m/sec.meters per second
mtg.mounting
MTUMotoren-und Turbinen-Union
MWmegawatt
mWmilliwatt
Fmicrofarad
N, norm. normal (power source)
NAnot available, not applicable
nat. gasnatural gas
NBSNational Bureau of Standards
Association
Nmnewton meter
NOnormally open
no., nos. number, numbers
NPSNational Pipe, Straight
NPSCNational Pipe, Straight-coupling
NPTNational Standard taper pipe
thread per general use
NPTFNational Pipe, Taper-Fine
NRnot required, normal relay
nsnanosecond
OCovercrank
ODoutside diameter
OEMoriginal equipment
manufacturer
OFoverfrequency
opt.option, optional
OSoversize, overspeed
OSHAOccupational Safety and Health
(screw)
PHHPhillipsr hex head (screw)
PHMpan head machine (screw)
PLCprogrammable logic control
PMGpermanent magnet generator
potpotentiometer, potential
ppmparts per million
PROMprogrammable read-only
memory
psipounds per square inch
psigpounds per square inch gauge
pt.pint
PTCpositive temperature coefficient
PTOpower takeoff
PVCpolyvinyl chloride
qt.quart, quarts
qty.quantity
Rreplacement (emergency)
power source
rad.radiator, radius
RAMrandom access memory
RBUSRS-485 proprietary
communications
RDOrelay driver output
ref.reference
rem.remote
Res/Coml Residential/Commercial
RFIradio frequency interference
RHround head
RHMround head machine (screw)
rly.relay
rmsroot mean square
rnd.round
ROread only
ROMread only memory
rot.rotate, rotating
rpmrevolutions per minute
RSright side
RTDsResistance Temperature
Detectors
RTUremote terminal unit
RTVroom temperature vulcanization
RWread/write
SAESociety of Automotive
Engineers
scfmstandard cubic feet per minute
SCRsilicon controlled rectifier
s, sec.second
SISysteme international d’unites,
International System of Units
SI/EOside in/end out
sil.silencer
SMTPsimple mail transfer protocol
SNserial number
SNMPsimple network management
protocol
SPDTsingle-pole, double-throw
SPSTsingle-pole, single-throw
specspecification
specsspecification(s)
sq.square
sq. cmsquare centimeter
sq. in.square inch
SMSshort message service
SSstainless steel
std.standard
stl.steel
tach.tachometer
TBterminal block
TCPtransmission control protocol
TDtime delay
TDCtop dead center
TDECtime delay engine cooldown
TDENtime delay emergency to
normal
TDEStime delay engine start
TDNEtime delay normal to
emergency
TDOEtime delay off to emergency
TDONtime delay off to normal
temp.temperature
term.terminal
THDtotal harmonic distortion
TIFtelephone influence factor
tol.tolerance
turbo.turbocharger
typ.typical (same in multiple
locations)
UFunderfrequency
UHFultrahigh frequency
UIFuser interface
ULUnderwriter’s Laboratories, Inc.
UNCunified coarse thread (was NC)
UNFunified fine thread (was NF)
univ.universal
URLuniform resource locator
(web address)
USundersize, underspeed
UVultraviolet, undervoltage
Vvolt
VACvolts alternating current
VARvoltampere reactive
VDCvolts direct current
VFDvacuum fluorescent display
VGAvideo graphics adapter
VHFvery high frequency
Wwatt
WCRwithstand and closing rating
w/with
WOwrite only
w/owithout
wt.weight
xfmrtransformer
TP-6803 6/1568 Appendix
Page 69
Appendix B Electrical Lead Entry Template
Use the full-scale drawing in Figure 1 to mark the openings for the electrical conduit, if desired. Two 13 mm (0.5 inch)
holes are also shown for the fuel regulator vent tubes, used only on 20 kW models. See Section 1.9.2 for more
information.
SCALE: 1:1
Note: Dimensions are in mm.
Two 13 mm holes are needed for 20 kW models only.
Figure 1Template, Drilled or Punched Openings for Regulator Vent Tubes (20 kW only) and Electrical Conduit
TP-6803 6/15Appendix 69
GM78090-B
Page 70
Notes
TP-6803 6/1570 Appendix
Page 71
Page 72
TP-68036/15l
E 2011, 2012, 2013, 2014, 2015 by Kohler Co. All rights reserved.