Kohler 14RESA, 20RESA, 14RESAL, 20RESAL Installation Manual

Installation (EN)
Installation (FR)
Instalación (ES)
Installation (DE)
Installatie (NL)
Установка (RU)
安装 (ZH)
14/20RESA
TP-6803-CMP 1/15j
Installation
Residential/Commercial Generator Sets
Models:
14/20RESA
14/20RESAL
Controllers:
RDC2
DC2
TP-6803 1/15j
California Proposition 65
WARNING
Engine exhaust from this product contains chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.
Product Identification Information
Generator Set Identification Numbers
Record the product identification numbers from the generator set nameplate(s).
Model Designation
Specification Number
Serial Number
Accessory Number Accessory Description
Engine Identification
Record the product identification information from the engine nameplate.
Manufacturer
Model Designation
Serial Number
Controller Identification
Record the controller description from the generator set operation manual, spec sheet, or sales invoice.
Controller Description
Table of Contents
Product Identification Information 2.............................................................
Safety Precautions and Instructions 5.........................................................
Introduction 9...............................................................................
Startup and Registration 9.....................................................
Service Assistance 10.........................................................................
Section 1 Installation 11......................................................................
1.1 Introduction 11...........................................................
1.2 Lifting 11................................................................
1.3 Generator Set Inspection 12...............................................
1.4 Location and Mounting 12.................................................
1.4.1 Mounting Area 12................................................
1.4.2 Concrete Mounting Pads 12.......................................
1.4.3 Exhaust Requirements 12.........................................
1.5 Dimension Drawings 13...................................................
1.6 Access the Air Intake Area 13..............................................
1.7 Fuel Requirements 14.....................................................
1.7.1 Fuel Supply 14...................................................
1.7.2 Fuel Pipe Size 15.................................................
1.7.3 Connecting the Fuel Supply 15.....................................
1.8 Fuel Conversion 16.......................................................
1.8.1 Fuel Conversion, 14RESA/RESAL Equipped with Fuel Block 16........
1.8.2 Fuel Conversion, 14RESA/RESAL Equipped with Fuel Orifice Fittings 18
1.8.3 Fuel Conversion, 20RESA/RESAL 20...............................
1.8.4 Regulator Vent Hose 20...........................................
1.9 Electrical Connections 21..................................................
1.9.1 Grounding 22....................................................
1.9.2 Electrical Lead Entry 22...........................................
1.9.3 Field-Connection Terminal Block 22.................................
1.9.4 AC Power Supply 24..............................................
1.10 ATS and Accessory Connections 25........................................
1.10.1 Transfer Switch Connection 25.....................................
1.10.2 Communication Cable Specifications 26.............................
1.10.3 System Connections with Accessory Modules 26.....................
1.11 Battery 30...............................................................
1.12 Generator Set Accessories 32..............................................
1.12.1 Programmable Interface Module (PIM) 32...........................
1.12.2 Load Control Module (LCM) 33.....................................
1.12.3 Load Shed Kit 34.................................................
1.12.4 Regulator Heater 35..............................................
1.12.5 Carburetor Heater 37.............................................
1.12.6 Battery Heater 39.................................................
1.12.7 OnCue Plus Generator Management System 40......................
1.13 Prestart Installation Check 41..............................................
1.14 Set the Exerciser 42......................................................
1.14.1 RDC2 Controller 42...............................................
1.14.2 DC2 Controller 42................................................
1.14.3 Loaded Exercise 42
Section 2 Drawings and Diagrams 43..........................................................
...............................................
Appendix A Abbreviations 55................................................................
Appendix B Electrical Lead Entry Template 57.................................................
TP-6803 1/15 Table of Contents 3
Notes
TP-6803 1/154
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS.
Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS.
This manual has several types of safety precautions and instructions: Danger, Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a hazard that will cause severe
personal i njury, death,orsubstantial property damage.
WARNING
Warning indicates the presence of a hazard that can cause severe
personal injury, death, or substantial property damage.
CAUTION
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage.
NOTICE
Notice communicates installation, operation, or maintenance information that is safety related but not hazard related.
Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals.
Accidental Starting
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before
working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
Battery
WARNING
Sulfuric acid in batteries. Can cause severe injury or death.
Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
WARNING
Explosion. Can cause severe injury or death. Relays in the battery charger cause arcs or sparks.
Locate the battery in a well-ventilated area. Isolate the battery charger from explosive fumes.
Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid
can cause blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid.
Battery acid cleanup. Battery acid can cause severe injury or death.
Battery acid is electrically conductive and corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a container with 4 L (1 gal.) of water and mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area.
TP-6803 1/15 5Safety Precautions and Instructions
Battery gases. Explosion can cause severe injury or death. Battery gases
can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases.
Battery short circuits. Explosion can cause severe injury or death.
Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Engine Backfire/Flash Fire
WARNING
Fire. Can cause severe injury or death.
Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator
set with the air cleaner removed.
Servicing the fuel system. A flash fire can cause severe injury ordeath.
Do not smoke or permit flames or sparks near the carburetor, fuel line, fuel filter, fuel pump, or other potential sources of spilled fuels or fuel vapors. Catch fuels in an approved container when removing the fuel line or carburetor.
Combustible materials. A fire can cause severe injury or death.
Generator set engine fuels and fuel vapors are flammable and explosive. Handle these materials carefully to minimize the risk of fire or explosion. Equip the compartment or nearby area with a fully charged fire extinguisher. Select a fire extinguisher rated ABC or BC for electrical fires or as recommended by the local fire code or an authorized agency. Train all personnel on fire extinguisher operation and fire prevention procedures.
Exhaust System
WARNING
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide
is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust gas could seep inside or be drawn into a potentially occupied building through windows, air intake vents, or other openings.
Carbon monoxide detectors. Carbon monoxide can cause severe nausea, fainting, or death. Install
carbon monoxide detectors on each level of any building adjacent to the generator set. Locate the detectors to adequately warn the building’s occupants of the presence of carbon monoxide. Keep the detectors operational at all times. Periodically test and replace the carbon monoxide detectors according to the manufacturer’s instructions.
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in exhaust gases. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Carbon monoxide poisoning symptoms include but are not limited to the following:
D Light-headedness, dizziness D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.
Do not smoke or permit flames or sparks near fuels or the fuel system.
TP-6803 1/156 Safety Precautions and Instructions
Fuel System
WARNING
Natural Gas—Adequate ventilation is
mandatory. Because natural gas rises, install natural gas detectors high in a room. Inspect the detectors per the manufacturer’s instructions.
WARNING
Explosive fuel vapors. Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly
explosive. Use extreme care when handling and storing fuels. Store fuels in a well-ventilated area away from spark-producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts or from sparks. Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors. Keep the fuel lines and connections tight and in good condition. Do not replace flexible fuel lines with rigid lines. Use flexible sections to avoid fuel line breakage caused by vibration. Do notoperate the generator set in the presence of fuel leaks, fuel accumulation, or sparks. Repair fuel systems before resuming generator set operation.
Gas fuel leaks. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an
explosion. Check the LPG vapor or natural gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to 6--8 ounces per square inch (10--14 inches water column). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. Asuccessful test depends on the ability of the solution to bubble.
Explosive fuel vapors can cause severe injury or death. Ta ke
additional precautions when using the following fuels:
Propane (LPG)—Adequate ventilation is mandatory. Because propane is heavier than air, install propane gas detectors low in a room. Inspect the detectors per the manufacturer’s instructions.
Hazardous Noise
CAUTION
Hazardous noise. Can cause hearing loss.
Never operate the generator set without a muffler or with a faulty exhaust system.
Engine noise. Hazardous noise can cause hearing loss. Generator sets
not equipped with sound enclosures can produce noise levels greater than 105 dBA. Prolonged exposure to noise levels greater than 85 dBA can cause permanent hearing loss. Wear hearing protection when near an operating generator set.
Hazardous Voltage/ Moving Parts
DANGER
Hazardous voltage. Will cause severe injury or death.
This equipment must be installed and serviced by qualified electrical personnel.
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Moving parts.
Hazardous voltage. Backfeed to the utility system can cause property damage, severe injury, or death.
If the generator set is used for standby power, install an automatic transfer switch to prevent inadvertent interconnection of standby and normal sources of supply.
CAUTION
Welding the generator set. Can cause severe electrical equipment damage.
Never weld components of the generator set without first disconnecting the battery, controller wiring harness, and engine electronic control module (ECM).
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution
is possible whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Welding on the generator set. Can cause severe electrical equipment damage. Before welding on the
generator set perform the following steps: (1) Remove the battery cables, negative (--) lead first. (2) Disconnect all engine electronic control module (ECM) connectors. (3) Disconnect all generator set controller and voltage regulator circuit board connectors. (4) Disconnect the engine battery­charging alternator connections. (5) Attach the weld ground connection close to the weld location.
TP-6803 1/15 7Safety Precautions and Instructions
Connecting the battery and the battery charger. Hazardous voltage can cause severe injury or death.
Reconnect the battery correctly, positive to positive and negative to negative, to avoid electrical shock and damage to the battery charger and battery(ies). Have a qualified electrician install the battery(ies).
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can
cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death. Install
a transfer switch in standby power installations to prevent the connection of standby and other sources of power. Electrical backfeed into a utility electrical system can cause severe injury or death to utility personnel working on power lines.
Hot Parts
WARNING
Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts.
The engine and exhaust system components become extremely hot during operation.
Servicing the engine heater. Hot parts can cause minor personal injury or property damage. Install the
heater before connecting it to power. Operating the heater before installation can cause burns and component damage. Disconnect power to the heater and allow it to cool before servicing the heater or nearby parts.
Notice
NOTICE
Canadian installations only.For
standby service connect the output of the generator set to a suitably rated transfer switch in accordance with Canadian Electrical Code, Part 1.
Heavy Equipment
WARNING
Unbalanced weight. Improper lifting can cause severe injury or death and equipment damage.
Do not use lifting eyes. Lift the generator set using lifting bars inserted through the lifting holes on the skid.
TP-6803 1/158 Safety Precautions and Instructions
Introduction
This manual provides installation instructions for Residential/Commercial Model generator sets. See Figure 1. Refer to TP-6804, Operation Manual, for generator set operation and maintenance instructions.
The generator set is approved for use in stationary applications in locations served by a reliable utility power source.
Have a Kohlerr authorized distributor/dealer install the generator set outdoors according to the instructions in this manual. The generator set installation must comply with the National Electrical Code (NEC) and local code requirements. Do not install this generator set indoors.
Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this publication and the products represented without notice and without any obligation or liability whatsoever.
Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury. Read and followthe Safety Precautions and Instructions section at the beginning of this manual.
List of Related Literature
Figure 2 identifies related literature available for the generator sets covered in this manual. Only trained and qualified personnel should install or service the generator set.
Literature Type Part Number
Operation Manual, 14/20RESA/RESALGenerator Set
Operation/Installation Manual, Model RXT Automatic Transfer Switch
Service Manual, 14/20RESA/RESAL Generator Set
Operation Manual, OnCue Plus TP-6928
Operation/Installation Manual, Model RDT Transfer Switch
Installation Manual, Model RSB Transfer Switch
Operation Manual, Model RSB Transfer Switch
Installation Instructions, Load Control Module (LCM)
Installation Instructions, Programmable Interface Module (PIM)
Installation Instructions, Concrete Mounting Pads
Figure 2 Related Literature
TP-6804
TP-6807
TP-6735
TP-6345
TP-6486
TP-6487
TT-1574
TT-1584
TT--1619
Startup and Registration
When the generator set is installed, complete the startup and installation checklists supplied with the startup notification form. Complete and sign the startup notification form and register the unit using the Kohler
zaa28533
Figure 1 14/20RESA/RESAL Generator Set
TP-6803 1/15 9
online Warranty Processing System.
Service Assistance
For professional advice on generator set power requirements andconscientious service, pleasecontact your nearest Kohler distributor or dealer.
D Consult the Yellow Pages under the heading
Generators—Electric.
D Visit the Kohler Power Systems website at
KOHLERPower.com.
D Look at thelabels and stickers onyour Kohler product
or review the appropriate literature or documents included with the product.
D Call toll free in the US and Canada 1-800-544-2444.
D Outside the US and Canada, call the nearest regional
office.
Headquarters Europe, Middle East, Africa (EMEA)
Kohler Power Systems Netherlands B.V. Kristallaan 1 4761 ZC Zevenbergen The Netherlands Phone: (31) 168 331630 Fax: (31) 168 331631
Asia Pacific
Power Systems Asia Pacific Regional Office Singapore, Republic of Singapore Phone: (65) 6264-6422 Fax: (65) 6264-6455
China
North China Regional Office, Beijing Phone: (86) 10 6518 7950
(86) 10 6518 7951 (86) 10 6518 7952
Fax: (86) 10 6518 7955
East China Regional Office, Shanghai Phone: (86) 21 6288 0500 Fax: (86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office Bangalore, India Phone: (91) 80 3366208
(91) 80 3366231
Fax: (91) 80 3315972
Japan, Korea
North Asia Regional Office Tokyo, Japan Phone: (813) 3440-4515 Fax: (813) 3440-2727
Latin America
Latin America Regional Office Lakeland, Florida, USA Phone: (863) 619-7568 Fax: (863) 701-7131
TP-6803 1/1510
Section 1 Installation
1.1 Introduction
DANGER
Hazardous voltage. Will cause severe injury or death.
This equipment must be installed and serviced by qualified electrical personnel.
WARNING
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is an
odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust gas could seep inside or be drawn into a potentially occupied buildingthrough windows, air intake vents, or other openings.
The generator set must be installed outdoors. The exhaust systems on enclosed units are designed for outdoor installation only.
Note: DO NOT install these generator sets inside a
building.
Note: Install carbon monoxide (CO) detector(s) on
each level of any building adjacent to a generator set. Locate the detectors to adequately warn the building’s occupants of the presence of carbon monoxide.
Obtain a building permit and contact your local utility companies to mark the locations of underground pipes and cables.
Read and follow the safety precautions in this manual and observe the decals on the equipment. Refer to the diagrams and drawings in this manual for dimensions and electrical connections during the installation procedure. Read the entire installation procedure and obtain the accessories and tools needed before beginning installation. Perform the steps in the order shown.
To install optional accessories, follow the instructions provided with each kit.
1.2 Lifting
WARNING
Carbon monoxide detectors. Carbon monoxide can cause severe nausea, fainting, or death. Install carbon
monoxide detectors on each level of any building adjacent to the generator set. Locate the detectors to adequately warn the building’s occupants of the presence of carbon monoxide. Keep the detectors operational at all times. Periodically test and replace the carbon monoxide detectors according to the manufacturer’s instructions.
Have thegenerator set installed by an authorized Kohler distributor/dealer or authorized representative. For all locations, ensure that the installation complies with applicable national and local codes. In the United States, the installation must comply with the National Electrical Code (NEC) and local codes. For Canadian installations, refer to the Canadian Electrical Code (CEC).
TP-6803 1/15 11Section 1 Installation
Unbalanced weight. Improper lifting can cause severe injury or death and equipment damage.
Do not use lifting eyes. Lift the generator set using lifting bars inserted through the lifting holes on the skid.
Model Weight, kg (lb.)
14RESA/RESAL
20RESA/RESAL
191 (420)
243 (535)
Figure 1-1 Approximate Weights
Approximate generator set weights are shown in Figure 1-1. Uselifting bars inserted through the holes in the skid to lift the unit. See the dimension drawings in Section 2 for lifting hole locations.
1.3 Generator Set Inspection
Complete a thorough inspection of the generator set. Check for the following:
1. Inspect the generator set for loose or damaged parts or wires. Repair or tighten any loose parts before installation.
2. Check the engine oil. Fill, if necessary, with the recommended viscosity and grade of oil. Use synthetic oil, API (American Petroleum Institute) Service Class SG or higher. See TP-6804, Operation Manual, for additional information.
1.4 Location and Mounting
Install the generator set outdoors near the incoming gas service. The generator set location must allow easy access for maintenance and service. The recommended distance from a structure is dependent on state and local codes. See the dimension drawing in Section 2 for the recommended clearance from structures and non-combustible materials.
Locate the generator set so that the hot exhaust does not blow on plants or other combustible materials. No plants, shrubs, or other combustible materials are allowed within 1.2 m (4 ft.) of the exhaust end of the generator set.
Do not installthe generator set where exhaust gas could accumulate and seep inside or be drawn into a potentially occupied building. Furnace and other similar intakes must be at least 3 m (10 ft.) from the exhaust end of the generator set.
Notice
DO NOT locate the generator set near patios,
decks, play areas, o r animal shelters. Keep items such as lawn furniture, toys, sports equipment, and all combustible materials away from the generator set exhaust outlet.
Remind family members, children, and visitors to use caution near the generator set. Generator sets connected to automatic transfer switches start automatically during exercise periods and power outages. Some generator set components become hot when the generator set is running and remain hot for a time after the generator set shuts down.
1.4.1 Mounting Area
The generator set is shipped on an engineered composite mounting pad. Prepare a flat, level mounting area covered with a weed barrier and gravel or a concrete mounting pad. Set the composite mounting pad directly on the gravel or concrete.
Do not install the composite mounting pad directly on grass, wood, or other combustible materials. Clear all combustible materials, including plants and shrubs, building materials, and lawn furniture, from an area at least 1.2 m (4 ft.) beyond the exhaust end of the generator set. See the dimension drawing in Section 2.
1.4.2 Concrete Mounting Pads
Kohler Co. offers optional concrete mounting pads that are custom-designed for Model 14RESA/RESAL and 20RESA/RESAL generator sets. Three-inch and four-inch thick pads are available. Four-inch pads are recommended for storm-prone areas. See TT-1619 for instructions to install the mounting pad, if necessary.
1.4.3 Exhaust Requirements
WARNING
Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
TP-6803 1/1512 Section 1 Installation
Figure 1-2 gives the exhaust temperature at rated load. The engine exhaust mixes with the generator set cooling air at the exhaust end of the enclosure. Mount the generator set so that the hot exhaust does not blow on plants or other combustible materials. Maintain the clearances shown in the dimension drawing in Section 2.
Temperature,
Exhaust
Exhaust gas exiting the enclosure at rated kW, _C(_F)
_C(_F)
260 (500)
Figure 1-2 Exhaust Flow and Temperature
1.6 Access the Air Intake Area
The battery, fuel system, and electrical connections are located in theair intake area. Raise the roof and remove the enclosure panel to access the air intake area during installation as described below.
1. Remove two screws from the top of the air intake panel. Pull the the panel up and off. See Figure 1-4.
2. To make the electrical connections, you will also need to remove the cover panel over the terminal block as shown in Section 1.9.3.
The generator set requires correct air flow for cooling and combustion. The inlet and outlet openings in the sound enclosure provide the cooling and combustion air. Figure 1-3 shows the locations of the cooling air intake and exhaust vents. Inspect the air inlet and outlet openings inside and outside the enclosure to ensure that the air flow is not blocked.
1
REAR VIEW
1. Air intake
2. Exhaust outlet
1
2
tp6733
Figure 1-3 Cooling Air Intake and Exhaust
The generator set is designed to operate with all enclosure panels and internal baffling in place. If during installation, maintenance or repair the unit must be operated without the complete enclosure and baffling as shipped from the factory make sure the exhaust panel is removed as well.
3. Reinstall the panels after all electrical connections are complete and the battery is installed and connected.
1. Remove 2 screws.
ADV-8424
Figure 1-4 Removing the Air Intake Panel
1
1.5 Dimension Drawings
See the dimension drawings in Section 2 for the generator set dimensions, fuel and electric inlet locations, and recommended clearance.
TP-6803 1/15 13Section 1 Installation
1.7 Fuel Requirements
1.7.1 Fuel Supply
The generator set operates using natural gas or LPG fuel. The generator set is EPA-certified for both natural gas and LPG fuels.
The fuel system installation must comply with the NEC and local codes.
WARNING
Explosive fuel vapors. Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
Explosive fuel vapors can cause severe injury or death.
Take additional precautions when using the following fuels:
Propane (LPG)—Adequate ventilation is mandatory. Because propane is heavier than air, install propane gas detectors low in a room. Inspect the detectors per the manufacturer’s instructions.
Natural Gas—Adequate ventilation is mandatory. Because natural gas rises, install natural gas detectors high in a room. Inspect the detectors per the manufacturer’s instructions.
Because of variable climates and geographical considerations, contact the local fuel supplier for fuel system planning and installation. Figure 1-5 lists the recommended fuel ratings and other fuel supply information for natural gas and LPG fuels.
Verify that the output pressure from the primary gas utility pressure regulator is within the range shown in Figure 1-5 and that the utility gas meter flow rate is sufficient to supply the generator set at rated load plus all other gas-consuming appliances. For LPG tanks, verify that the output pressure is as shown in Figure 1-5. See Figure 1-6 for fuel consumption. Contact the fuel supplier for flow rate information or a gas meter upgrade, if necessary.
Natural
3
Gas
1.3--2.7 (5--11)
LPG
1.7--2.7 (7--11)
Fuel type
Fuel supply inlet 1/2 NPT
Fuel supply pressure, kPa (in. H
O)
2
Fuel flow rate, maximum, Btu/hr.:
14RESA/RESAL 193,000 203,000
20RESA/RESAL 281,000 340,000
Nominal Fuel Rating, Btu/ft.
Natural gas 1000
LPG 2500
Fuel Type % Load
100% 5.4 (193) 4.9 (175) 8.0 (281) 6.4 (225)
Natural Gas
LPG
LPG conversion factors:
8.58 ft.
0.535 m
36.39 ft.
3
=1lb.
3 3
=1kg
= 1 gal.
75% 4.7 (163) 4.2 (148) 6.9 (243) 5.4 (189)
50% 3.5 (124) 3.1 (108) 4.6 (161) 3.9 (139)
25% 2.6 (93) 2.4 (84) 3.6 (127) 2.9 (103)
100% 2.3 (81) 2.1 (74) 3.9 (136) 2.9 (102)
75% 2.1 (75) 1.9 (68) 3.1 (109) 2.4 (85)
50% 1.8 (60) 1.5 (53) 2.3 (82) 1.8 (63)
25% 1.2 (45) 1.1 (40) 1.7 (59) 1.3 (47)
Figure 1-6 Fuel Consumption
Figure 1-5 Fuel Supply
Fuel Consumption, m3/hr. (cfh)
14RESA/RESAL 20RESA/RESAL
60 Hz 50 Hz 60 Hz 50 Hz
Nominal fuel rating:
Natural gas: 37 MJ/m LPG: 93 MJ/m
3
(1000 Btu/ft.3)
3
(2500 Btu/ft.3)
TP-6803 1/1514 Section 1 Installation
1.7.2 Fuel Pipe Size
Ensure that the fuel pipe size and length meet the specifications in Figure 1-7. Measure the pipe length from the primary gas pressure regulator to the pipe connection on the generator set fuel inlet. Add 2.4 m (8 ft.) to the measured length for each 90 degree elbow. Compare the total pipe length with the chart in Figure 1-7 to find the required pipe size.
Contact local LPG provider for LPG installation information.
Minimum Gas Pipe Size Recommendation, in. NPT
14RESA/RESAL 20RESA/RESAL
Pipe
Length,
m (ft.)
8 (25) 3/4 3/4 1 3/4
15 (50) 1 3/4 1 1
30 (100) 1 1 11/4 1
46 (150) 11/4 1 11/4 11/4
61 (200) 11/4 1 11/4 11/4
Natural
Gas
(193,000
Btu/hr.)
LPG
(203,000
Btu/hr.)
Figure 1-7 Fuel Pipe Size Recommendations
Natural
Gas
(281,000
Btu/hr.)
LPG
(340,000
Btu/hr.)
Apply pipe sealant thatis approved for fuel connections. Hold the fuel solenoid valve with a wrench when tightening the fuel connections.
Note: Do not hold the fuel solenoid valve coil when
tightening the fuel connections. See Figure 1-8 for the recommended wrench locations.
1
Note: Do NOT hold the valve
coil when tightening connections.
IMG_0351
1. Hold valve with wrench on flats of valve body
2. Alternate wrench location
2
1.7.3 Connecting the Fuel Supply
The dimension drawing in Section 2 shows the location of the fuel inlet connection. Have the fuel supplier install rigid gas piping and a manual fuel shut-off valve. The fuel supply line should line up with the generator set fuel inlet and end about 12 inches away to allow connection with asection of flexible fuel line. Use flexible sections to prevent fuel line breakage caused by vibration.
Note: Do not bend the flexible fuel line to make up for
misalignment of the fuel supply line and the generator set fuel inlet.
Figure 1-8 Holding Fuel Valve to Tighten Fuel
Connections
Open the manual fuel valves and test all fuel connections using soapy water. If a leak is found, close the fuel valves, clean the fittings, and apply fresh sealant. Check for fuel leaks again with the generator set running.
Protect all fuel lines from machinery or equipment contact, adverse weather conditions, and environmental damage.
TP-6803 1/15 15Section 1 Installation
1.8 Fuel Conversion
The multi-fuel system allows conversion from natural gas to LPG (or vice-versa) in the field while maintaining emissions-standard compliance. A trained technician or an authorized distributor/dealer can convert the fuel system.
After converting the fuel system, change the Fuel Type setting on the controller. See the Operation Manual for instructions to change settings at the controller, or use a personal (laptop) computer and Kohlerr SiteTecht software to change the setting.
Rating Change
Converting the fuel will change the generator set rating. See the generator set specification sheet for ratings with natural gas and LP. Order a new nameplate with the updated rating and fuel information from an authorized distributor/dealer, if necessary. Provide the following information from the original nameplate:
WARNING
Explosive fuel vapors. Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
Explosive fuel vapors can cause severe injury or death.
Take additional precautions when using the following fuels:
Propane (LPG)—Adequate ventilation is mandatory. Because propane is heavier than air, install propane gas detectors low in a room. Inspect the detectors per the manufacturer’s instructions.
Natural Gas—Adequate ventilation is mandatory. Because natural gas rises, install natural gas detectors high in a room. Inspect the detectors per the manufacturer’s instructions.
D Model Number D kVA D Spec Number D Amps D Serial Number D Volts D Fuel (original and new) D Hz D kW
Attach the new nameplate over the old one. Do NOT cover the UL listing information on the old nameplate.
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
1.8.1 Fuel Conversion, 14RESA/RESAL Equipped with Fuel Block
Note: Model 14RESA/RESAL generator sets built
before June 26, 2014 use a fuel block for the fuel type selection. See Figure 1-9 and use the instructions in this section for fuel conversion.
Model 14RESA/RESAL generators built June 26, 2014, or later are not equipped with the fuel block. These units use fuel orifice fittings installed in the hose fitting at the fuel regulator. See Section
1.8.2 for fuel conversion instructions.
Two fuel connections on the fuel block allow field­conversion between natural gas and LPG. The fuel metering valves are factory-set and sealed to comply with applicable e mission standards and to provide the best possible hot and cold starting.
Note: Do not adjust the factory-sealed fuel-metering
adjustments on the fuel block. Changing the fuel­metering adjustmentsmay violate federalor state laws.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
Use the following procedure to convert from natural gas (NG) to LPG. See Figure 1-9 for the fuel system component locations.
TP-6803 1/1516 Section 1 Installation
Procedure to convert from NG to LPG, 14RESA/RESAL with fuel block
1. Press the OFF button on the generator set controller.
2. Disconnect the power to the battery charger.
3. Disconnect the generator set engine starting battery, negative (--) lead first.
4. Turn off the fuel supply.
Conversion from LPG to Natural Gas
To convert from LPG to natural gas, follow the fuel conversion procedure above, moving the hose fitting to the natural gas port and plugging the LP port. Connect the DSAI leads for natural gas. See Figure 1-9.
1
10
2
LPG setup shown
5. Remove the hose clamp and fuel hose from the hose fitting in the fuel block. See F igure 1-9.
6. Remove the hose fitting from the natural gas outlet port in the fuel block. See Figure 1-9.
7. Remove the plug from the LP port in the fuel block. SeeFigure1-9.
8. Clean the plug with a dry cloth or brush, apply fresh pipe sealant, and install the plug into the natural gas outlet port.
9. Clean the hose fitting with a dry cloth or brush, apply fresh pipe sealant to the threads, and install the fitting into the LP port.
Note: Do not adjust the fuel metering valves.
10. Slide the hose onto the hose fitting and secure it with the clamp.
11. Disconnect digital spark-advance ignition (DSAI) leads 65 and N3 for LPG. The DSAI leads are located near the fuel solenoid valve. See Figure 1-9.
9
8
7
6
3
4
photo223
5
12. Connect and turn on the new fuel supply. DSAI Lead Connection
13. Reconnect the generator set engine starting
battery leads, negative (--) lead last.
14. Reconnect power to the battery charger.
15. Start the generator set by pressing the RUN button
on the generator set controller.
16. Check for leaks using a gas leak detector.
17. Run the generator set and check the operation.
1. Fuel block (14RES only)
2. Fuel metering valves—factory -sealed, do not adjust
3. Fuel solenoid valve coil
4. Fuel inlet, 1/2 in. NPT
5. DSAI leads 65 and N3
6. Recommended holding points for tightening fuel connection
7. Fuel regulator
8. Ports are labeled LP and NG
9. Plug
10. Hose fitting
Figure 1-9 Fuel System, 14RESA/RESAL Equipped
with Fuel Block (built before June 26,
18. Press the OFF button to to shut down the generator
2014)
set.
TP-6803 1/15 17Section 1 Installation
1.8.2 Fuel Conversion, 14RESA/RESAL Equipped with Fuel Orifice Fittings
Note: Model 14RESA/RESAL generator sets built
before June 26, 2014, use a fuel block for the fuel type selection. See Figure 1-9 and use the instructions Section 1.8.1 for fuel conversion.
Model 14RESA/RESALgenerators built June 26, 2014, or later are not equipped with the fuel block. These units use fuel orifice fittings installed in the hose fitting at the fuel regulator. See Figure 1-11 and use the instructions in this section for fuel conversion.
For natural gas and LPG fuel, orifice fittings are used in the fuel line. See Figure 1-10. The natural gas orifice fitting is silver in color and stamped NG. The LPG fitting is gold in color and stamped LPG. The fittings are threaded. A straight-blade screwdriver is required to remove and replace the fittings.
1
2
NG LPG
Figure 1-10 NG and LPG Fuel Orifice Fittings
The unit is typically shipped set up for natural gas, with the LPG fitting tied near the fuel solenoid valve. To convert to LPG, remove the NG fitting and install the LPG fitting as described below. See Figure 1-11 for the fuel system component locations.
Procedure to Convert from NG to LPG, 14RESA/RESAL with fuel orifice fittings
1. Press the OFF button on the generator set controller.
2. Disconnect the utility power to the generator.
3. Disconnect the generator set engine starting battery, negative (--) lead first.
4. Turn off and disconnect the fuel supply.
5. Remove the hose clamp and fuel hose from the hose fitting. See Figure 1-11.
3
DSAI Lead Connection
1. LPG fitting tied to bracket for shipping
2. Fuel hose and clamp
3. DSAI Leads
Figure 1-11 Fuel System, As Shipped (Model
14RESA/RESAL built after June 26,
2014)
6. Use a straight-blade screwdriver to remove the NG orifice from the hose fitting. See Figure 1-12.
7. Insert the LPG orifice into the hose fitting. Use a straight-blade screwdriver to tighten the fitting until it is snug.
8. Slide the hose onto the hose fitting and secure it with the clamp.
9. Disconnect digital spark-advance ignition (DSAI) leads 65 and N3 for LPG. The DSAI leads are
TP-6803 1/1518 Section 1 Installation
located near the fuel solenoid valve. See Figure 1-11.
10. Connect and turn on the new fuel supply.
15. Run the generator set and check the operation.
16. Press the OFF button to shut down the generator set.
11. Reconnect the generator set engine starting battery leads, negative (--) lead last.
12. Reconnect the utility power to the generator.
13. Start the generator set by pressing the RUN button on the generator set controller.
14. Check for leaks using a gas leak detector.
1
2
Conversion from LPG to Natural Gas
To convert from LPG to natural gas, repeat the steps above, removing the LPG fuel orifice and installing the NG fitting. Connect DSAI leads 65 and N3 together for natural gas.
ORIFICE FITTING DETAIL
1. Orifice fitting (see detail)
2. Hose barb fitting
Figure 1-12 14RESA/RESAL Fuel System Showing Orifice Fittings (generators built after June 26, 2014)
GM84143
TP-6803 1/15 19Section 1 Installation
1.8.3 Fuel Conversion, 20RESA/RESAL
For LPG fuel, an orifice is used in the fuel line. The unit is typically shipped set up for natural gas, with the loose orifice tied near the fuel solenoid valve. To convert to LPG, install the LPG orifice as described below. See Figure 1-13 for the fuel system component locations.
Note: The generator set harness may contain a pair of
DSAI leads near the fuel solenoid valve. Connecting or disconnecting these leads has no effect on the 20RESA/RESAL operation.
Procedure to Convert from NG to LPG, 20RESA/RESAL
LPG setup shown
1
2
3
1. Press the OFF button on the generator set controller.
2. Disconnect the power to the battery charger.
3. Disconnect the generator set engine starting battery, negative (--) lead first.
4. Turn off the fuel supply.
5. Remove the hose clamp and fuel hose from the hose fitting. See Figure 1-13.
6. Insert the LPG orifice into the hose fitting. See Figure 1-13.
7. Slide the hose onto the hose fitting and secure it with the clamp.
8. Connect and turn on the new fuel supply.
9. Reconnect the generator set engine starting battery leads, negative (--) lead last.
10. Reconnect power to the battery charger.
1. LPG orifice
2. Hose fitting
3. Regulator
4. Regulator vent tubes (vent to the outside of the controller)
4
GM84143
Figure 1-13 Fuel Regulator and LPG Orifice,
20RESA/RESAL
1.8.4 Regulator Vent Hose
Model 20RESA/RESAL generators are equipped with fuel regulator vent hoses. Drill or punch two holes in the enclosure at the locations shown on the template in Appendix B. It may be convenient to cut openings forthe electrical leads at the same time as shown on the template and in Section 1.9.2.
Insert the open ends of the hoses through the holes to the outside of the enclosure as shown in Figure 1-14.
11. Start the generator set by pressing the RUN button on the generator set controller.
12. Check for leaks using a gas leak detector.
13. Run the generator set and check the operation.
14. Press the OFF button to shut down the generator set.
Conversion from LPG to Natural Gas
To convert from LPG to natural gas, repeat the steps above to remove the LPG fuel orifice.
1
2
sb722
1. Fuel regulator vent tubes, qty. 2
2. Drill or punch two holes and route both hoses to the outside of the enclosure
Figure 1-14 Fuel Regulator Vent Hoses
TP-6803 1/1520 Section 1 Installation
1.9 Electrical Connections
DANGER
Hazardous voltage. Will cause severe injury or death.
This equipment must be installed and serviced by qualified electrical personnel.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death. Install a transfer
switch in standby power installations to prevent the connection of standby and other sources of power. Electrical backfeed into a utility electrical system can cause severe injury or death to utility personnel working on power lines.
NOTICE
Canadian installations only. For standby service connect
the output of the generator set to a suitably rated transfer switch in accordance with Canadian Electrical Code, Part 1.
Have an authorized distributor/dealer or a licensed electrician make the following electrical connections. The electrical installation must comply with the National Electrical Coder (NEC) class 1 wire designation and all applicable local codes. Canadian installations must comply with the Canadian Electrical Code (CEC) and applicable local codes.
AC circuit protection. All AC circuits must include circuit breaker or fuse protection. The circuit breaker must be rated for a maximum of 125% of the rated generator set output current. The circuit breaker must open all ungrounded connectors. The generator set is equipped with a factory-installed circuit breaker.
For customer-supplied wiring, select the wire temperature rating in Figure 1-15 based upon the following criteria:
D Select row 1, 2, 3, or 4 if the circuit rating is
110 amperes or less or requires #1 AWG (42.4 mm
2
or smaller conductors.
D Select row 3 or 4 if the circuit rating is greater than
110 amperes or requires #1 AWG (42.4 mm
2
)or
larger conductors.
)
Row Temp. Ra t i n g Copper (Cu) Only Cu/Aluminum (Al) Combinations Al Only
1
60_C (140_F)
or
75_C (167_F)
2
60_C (140_F) Use No. * AWG, 60_Cwire Use 60_C wire, either No. * AWG Cu or No. *
3
75_C (167_F) Use No. *[ AWG, 75_Cwire Use 75_C wire, either No. *[ AWG Cu or No.
4
90_C (194_F) Use No. *[ AWG, 90_Cwire Use 90_C wire, either No. *[ AWG Cu or No.
* The wire size for 60_C (140_F) wire is not required to be included in the marking. If included, the wire size is based on ampacities for the
wire given in Table 310-16 of the National Electrical Coder, in ANSI/NFPA 70, and on 115% of the maximum current that the circuit carries under rated conditions. The National Electrical Coder is a registered trademark of the National Fire Protection Association, Inc.
[ Use the larger of the following conductors: the same size conductor as that used for the temperature test or one selected using the
guidelines in the preceding footnote.
Use No. * AWG, 60_Cwireor use No. * AWG, 75_Cwire
Use 60_C wire, either No. * AWG Cu, or No. * AWG Al or use 75_C wire, either No. * AWG Cu or No. * AWG Al
AWG Al
*[ AWG Al
*[ AWG Al
Use 60_Cwire,No.*AWGor use 75_Cwire,No.*AWG
Use 60_Cwire,No.*AWG
Use 75_Cwire,No.*[ AWG
Use 90_Cwire,No.*[ AWG
Figure 1-15 Terminal Markings for Various Temperature Ratings and Conductors
The National Electrical Coder is a registered trademark of the National Fire Protection Association, Inc.
TP-6803 1/15 21Section 1 Installation
1.9.1 Grounding
1.9.3 Field-Connection Terminal Block
Ground the generator set. The grounding method must comply with NEC a nd local codes. Connect the
grounding cable to the generator set ground terminal GND on the field-connection terminal block.
Generator sets are shipped with the generator neutral bonded (connected) to the generator ground in the junction box. The requirement for having a bonded (grounded) neutral orungrounded neutral is determined by the type of installation. At installation, the neutral can be grounded at the generator set or lifted from the ground stud and isolated if the installation requires an ungrounded neutral connection at the generator. The generator setwill operate properlywith the neutral either bonded to ground or isolated from ground at the generator.
Various regulations andsite configurations including the National Electrical Code (NEC), local codes, and the type of transfer switch used in the application determine the grounding of the neutral at the generator. NEC Section 250 is one example that has a very good explanation of the neutral grounding requirements for generators.
The generator set is equipped with a field-connection terminal block located in the air intake area near the junction box. Leads have been factory-installed from the junction box to the terminal block for easy field wiring.
See Figure 1-17 for the terminal block location. Remove the cover panel for access to the field connections.
1
1.9.2 Electrical Lead Entry
Drill or punch holes in the enclosure for the electrical conduit in the locations shown in Figure 1-16. A full-scale dimensioned template for the hole locations is printed in Appendix B. See page 57.
1
2
4
ADV--8424
3
Note: See Appendix B for a full-scale template
with dimensions.
1. Optional emergency stop switch location. Do not use to
route wiring.
2. Utility voltage electrical lead entry point
3. ATS signal electrical lead entry point
4. 1/2 NPT female fuel inlet
adv-8424
1. Cover panel. Remove for access to field-connection terminal block.
Figure 1-17 Field-Connection Terminal Block
Location
Figure 1-16 Electrical Lead Entry Locations
TP-6803 1/1522 Section 1 Installation
See Figure 1-18 for terminal block details. Refer to the terminal block decal shown in Figure 1-19 for connections and cable sizes. Also see the wiring diagram in Section 2.
Route AC leads through flexible conduit. Ensure that the leads and conduit do not interfere with the operation of the generatorset or obstruct the serviceareas. Route low-voltage communication leads through separate conduit.
Procedure
a. Route the network cable with other low-voltage
signal wiring (for example, the RBUS communication leads or engine start leads to the transfer switch), in separate conduit from the ACload leads. If the networkcable is longer than 100 meters (328 ft.), use a repeater or switch.
b. Use an RJ45 inline coupler to connect the
Ethernet cable to the cable in the customer connection box. See Figure 1-18. The inline coupler is included with the OnCue Plus kit.
1. Drill holes for the conduit fittings. See Figure 1-16 and Appendix B for the recommended electrical inlet locations. Feed the cables through the openings.
2. Connect the leads from the transfer switch emergency source lugs to the L1, L2, and L3 connections on the generator set terminal block as applicable for single or three-phase applications. See Figure 1-18 and Figure 1-19.
3. Connect the neutral ( L0) and ground (GRD) leads from the ATS and the main panel to the corresponding connection points on the terminal block. See Section 1.9.1, Grounding.
4. Connect AC power source leads to the terminal block connections labeled LINE, NEUTRAL and GROUND. Connect the circuit to the load side of the transfer switch. See Section 1.9.4 for more information about the AC power requirement.
Note: AC power must be connected to maintain
the charge on the engine starting battery.
5. For connection of optional transfer switches, the programmable interface module (PIM), and/or a load control module ( LCM) or load shed kit, see Section 1.10.1.
6. If the OnCuer Plus Generator Management System will be used with the generator set, run category 5E network cable from the generator set to the customer’s router or modem.
7. When connections to the terminal block are complete, replace the cover plate.
4
3
2
1
GM84094
Note: The number of terminals varies for 1-phase
and 3-phase models. See Figure 1-19.
1. Low voltage RBUS communication to RXT ATS, PIM, LCM or load shed kit, and/or APM.
2. Engine start connections from transfer switches other than theRXT,ifused.
3. Ground connection for communication cable shield
4. Ethernet cable for optional OnCue Plus connection
5. AC load connections
6. AC power connections required for battery charging and accessories
7. Connection decal; see Figure 1-19.
Figure 1-18 Field Connection Terminal Blocks
5
6
7
Note: The OnCue Plus Wireless kit allows
connection of the generator controller to the customer’s wireless router without running a network cable from the generator to the customer’s router or modem. If the OnCue Plus Wireless is used, follow the instructions provided with the kit to install and set up the wireless kit and proceed to step 7.
TP-6803 1/15 23Section 1 Installation
1-Phase, 1-Pole Circuit Breaker
1-Phase, 2-Pole Circuit Breaker
1.9.4 AC Power Supply
The installer must connect AC power for the battery charger (which is integral to the RDC2 controller) and the optional accessories shown in Figure 1-20. The power source must comply with state and local codes. The power to the battery charger and accessories must be backed upby the generator so thatpower is available at all times.
Be sure to disconnect power at the distribution panel before makingthe connections. Connect power leadsto the AC power connection points labeled LINE, NEUTRAL, and GROUND on the field-connection terminal block. Connect the circuit to the load side of the transfer switch so that it is backed up by the generator. See Figure 1-18 and the wiring diagrams in Section 2 for connection details.
Power Requirement, Max.
Equipment
Battery charger (standard)
Carburetor heater (optional)
Battery heater (optional)
Fuel regulator heater (optional; available for 20RESA/RESAL only)
Figure 1-20 Power Requirements
Watts Volts at 50/60 Hz
50 100--120 VAC
50 200--250 VAC
37
37
50
50
60 100--120 VAC
100 200--250 VAC
100--120 VAC
200--250 VAC
100--120 VAC
200--250 VAC
3-Phase
Figure 1-19 Terminal Block Connection Decals
TP-6803 1/1524 Section 1 Installation
1.10 ATS and Accessory Connections
The following sections cover electrical connections of the automatic transferswitches and RBUS accessories, including the programmable interface module (PIM) and the load control module (LCM) or load shed kit.
1.10.1 Transfer Switch Connection
Communication connections for a Kohlerr Model RXT transfer switch
One Model RXT transfer switch can be connected to the generator set. See Figure 1-21. Use shielded, twisted-pair communication cable to connect P10-1 through P10-4 on the transfer switch interface module to the generatorset terminal block connections A, B, PWR, and COM. See Section 1.10.2 for the communication cable recommendations and maximum cable length.
Connect the ATS or remote start/stop switch. Connect the load leads from the generator set to the Emergency source lugs on the ATS. Route low-voltage communication leads through separate conduit fromthe AC power and load leads. All connections must comply with applicable state and local codes.
Note: Do not use the Kohlerr Model RRT transfer
switch with the 14/20RESA or 14/20RESAL generator set.
1
Generator Set
GND
A
B
PWR
COM
3
RBUS
12 VDC
A
B
PWR
COM
4
3
Note: Connections 3 and 4 on the generator set are not
used with the Model RXT transfer switch.
Engine start connection for other transfer switches or a remote start/stop switch
Connect the engine start leads from the transfer switch or remote start switch to terminals 3 and 4 on the terminal block. See Figure 1-22. Route the engine start leads through separate conduit from the AC power and load leads.
2
Interface Board on the Model RXT Transfer Switch
4
A
B
PWR
COM
4
RXT
Note: Generator set terminal block connections 3 and 4 are NOT USED with the Model RXT ATS.
1. Generator set terminal block. See Figure 2-4 for location. Check the decal on the generator set for terminal block connections.
2. Connect one end of each cable shield to GROUND at the generator set.
3. Communication cable Belden #9402 or equivalent 20 AWG shielded, twisted-pair cable. See Section 1.10.2, Cable Specifications.
4. Leave one end of each cable shield disconnected. If accessory modules (PIM, LCM or load shed kit) are connected, see Section
1.10.3.
Figure 1-21 Model RXT Transfer Switch Communication Connection to Generator Set Terminal Block
TP-6803 1/15 25Section 1 Installation
Generator Set
1
A
B
PWR
COM
4
3
1. Generator Set Terminal Block. See the dimension drawings in Section 2 for location. Check the decal on the generator set for terminal block connections.
2. Engine start leads 3 and 4. See the ATS manual for cable size specifications.
2
ATS
(with engine
start contacts)
Figure 1-22 Engine Start Connections with Transfer Switch Models other than Model RXT
1.10.2 Communication Cable Specifications
RBUS Connections A and B
For the RBUS communication connections A and B to the Model RXT transfer switch, optional PIM and/or optional LCM or load shed kit, use 20 AWG shielded, twisted-pair communication cable. Belden #9402 (two-pair) or Belden #8762 (single-pair) or equivalent
and use the second pair for the PWR and COM connections.
D For the longercable runs shownin the lasttwo rows of
Figure 1-23, use 12 or 14 AWG cable for PWR and COM, and use the 20 AWG communication cable specified above for the A and B connections only. In this case, single-pair communication cable such as Belden #8762 can be used for the A and B connections.
cable is recommended.
For outdoor installations, including those with buried cables and/or conduit, use outdoor-rated Belden #1075A or equivalent 20 AWG shielded, twisted-pair communication cable.
1.10.3 System Connections with Accessory Modules
See Figure 1-24 through Figure 1-28 for connection options with accessory modules. Accessory modules can include one Model RXT transfer switch, one
PWR and COM Connections
For the PWR and COM connections, the cable size and maximum cable length depends on the number of modules connected. See Figure 1-23.
D For short cable runs shown in the first two rows of
Figure 1-23, use one pair in the two-pair communication cable for the A and B connections,
programmable interface module (PIM) and/or one load control module (LCM) or load shed kit. Note the cable shield connections shown in Figure 1-24.
The maximum cable length depends on the number of optional modules connected. See Figure 1-23 for the maximum cablelengths with 1,2, or 3modules per cable run.
tp6803
TP-6803 1/1526 Section 1 Installation
Maximum length per run, meters (ft.)
Indoor or
Outdoor
Cable Size for PWR and COM Connections
Installation
20 AWG Belden #9402 or equivalent, two-pair Indoor
20 AWG Belden #1075A or equivalent, two-pair Outdoor
14 AWG *
12 AWG *
* Use 12 or 14 AWG cable for PWR and COM connections only. For RBUS connections A and B, use shielded, twisted pair communication
cable specified in Section 1.10.2.
1 Module 2 Modules 3 Modules
61 (200) 31 (100) 21 (67)
61 (200) 31 (100) 21 (67)
152 (500) 152 (500) 122 (400)
152 (500) 152 (500) 152 (500)
Number of Modules per Run
Figure 1-23 Total Cable Lengths for PWR and COM Connections
Generator Set
RBUS
12 VDC
1
GND
A
B
PWR
COM
4
3
A
B
PWR
COM
2
4
3
RXT
A
B
PWR
COM
A
B
PWR
COM
PIM
A
B
PWR
COM
A
B
PWR
COM
Note: See Section 1.10.2, Cable Specifications.
1. Generator set terminal block. See Figure 2-4 for location. Check the decal on the generator set for terminal block connections.
2. Connect one end of each cable shield to GROUND at the generator set.
3. Communication cable Belden #9402 or equivalent 20 AWG shielded, twisted-pair cable.
4. Connect shields together as shown.
5. Leave one end of each cable shield disconnected at the last device.
Figure 1-24 Accessory Module Communication Connection Details
TP-6803 1/15 27Section 1 Installation
5
A
B
PWR
COM
LCM or load shed kit
5
2
4
Generator Set
RBUS
12 VDC
1
GND
A
B
PWR
COM
4
3
A
B
PWR
COM
3
RXT
A
B
PWR
COM
6
A
B
PWR
COM
PIM
A
B
PWR
COM
5
A
B
PWR
COM
A
B
PWR
COM
LCM or load shed kit
Note: See Section 1.10.2, Cable Specifications.
1. Generator set terminal block. See Figure 2-4 for location. Check the decal on the generator set for terminal block connections.
2. Connect one end of each cable shield to GROUND at the generator set.
3. Communication cable Belden #8762 or equivalent 20 AWG shielded, twisted-pair cable (one pair).
4. Connect shields together as shown.
5. Leave one end of each cable shield disconnected at the last device.
6. 12 AWG or 14 AWG leads for PWR and COM.
Figure 1-25 Accessory Module Connections with 12--14 AWG Power Leads
TP-6803 1/1528 Section 1 Installation
Loading...
+ 410 hidden pages